15 British American Boulevard Latham, New York 12110 tel: 518-782-4500 fax: 518-786-3810 August 11, 2009 Ms. Ilene Tepper Assistant Business Administrator Freehold Township Board of Education Freehold, NJ 07728 Subject: Energy Audit for Freehold Township Board of Education Dear Ms. Tepper: Please find enclosed six sets of our final report detailing the findings and recommendations of CDM’s energy audit for the Freehold Township Board of Education. An electronic copy of this report has also been provided to TRC for their comment and review. Very truly yours, Matthew T. Goss, P.E., C.E.M., C.E.A., LEED ® AP Project Manager CDM c: Theodore C. Schlette (CDM) Colleen Kling (TRC) Enclosure

Transcript of Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold...

Page 1: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

15 British American Boulevard Latham, New York 12110 tel: 518-782-4500 fax: 518-786-3810

August 11, 2009 Ms. Ilene Tepper Assistant Business Administrator Freehold Township Board of Education Freehold, NJ 07728 Subject: Energy Audit for Freehold Township Board of Education Dear Ms. Tepper: Please find enclosed six sets of our final report detailing the findings and recommendations of CDM’s energy audit for the Freehold Township Board of Education. An electronic copy of this report has also been provided to TRC for their comment and review. Very truly yours,

Matthew T. Goss, P.E., C.E.M., C.E.A., LEED®AP Project Manager CDM c: Theodore C. Schlette (CDM) Colleen Kling (TRC)

Enclosure

Page 2: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Freehold Township School District

AUGUST 2009

A

Final Energy Audit Report

Page 3: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

A i C:\cdmxm\fisherbl\d0123757\Table of Contents.doc

Contents

Executive Summary

Section 1 Introduction 1.1 General ....................................................................................................................... 1-1 1.2 Background ............................................................................................................... 1-1 1.3 Purpose and Scope ................................................................................................... 1-3

Section 2 Facility Description 2.1 D.D. Eisenhower Middle School ............................................................................ 2-1 2.1.1 Description of Building Envelope ........................................................... 2-1 2.1.2 Description of Building HVAC ............................................................... 2-1 2.1.3 Description of Building Lighting ............................................................ 2-1 2.1.4 Miscellaneous Equipment ........................................................................ 2-2 2.2 J.J Catena Elementary School .................................................................................. 2-3 2.2.1 Description of Building Envelope ........................................................... 2-3 2.2.2 Description of Building HVAC ............................................................... 2-3 2.2.3 Description of Building Lighting ............................................................ 2-3 2.2.4 Miscellaneous Equipment ........................................................................ 2-4 2.3 C.T. Barkalow Middle School ................................................................................. 2-4 2.3.1 Description of Building Envelope ........................................................... 2-4 2.3.2 Description of Building HVAC ............................................................... 2-5 2.3.3 Description of Building Lighting ............................................................ 2-5 2.3.4 Miscellaneous Equipment ........................................................................ 2-6 2.4 Early Childhood Learning Center .......................................................................... 2-6 2.4.1 Description of Building Envelope ........................................................... 2-7 2.4.2 Description of Building HVAC ............................................................... 2-7 2.4.3 Description of Building Lighting ............................................................ 2-7 2.4.4 Miscellaneous Equipment ........................................................................ 2-8 2.5 M.W. Errickson Elementary School ....................................................................... 2-8 2.5.1 Description of Building Envelope ........................................................... 2-8 2.5.2 Description of Building HVAC ............................................................... 2-8 2.5.3 Description of Building Lighting ............................................................ 2-9 2.5.4 Miscellaneous Equipment ........................................................................ 2-9 2.6 Laura Donovan Elementary School ....................................................................... 2-9 2.6.1 Description of Building Envelope ........................................................... 2-9 2.6.2 Description of Building HVAC ............................................................. 2-10 2.6.3 Description of Building Lighting .......................................................... 2-10 2.6.4 Miscellaneous Equipment ...................................................................... 2-11 2.7 West Freehold Elementary School ....................................................................... 2-11 2.7.1 Description of Building Envelope ......................................................... 2-11 2.7.2 Description of Building HVAC ............................................................. 2-11

Page 4: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Table of Contents Freehold Township School District

Final Energy Audit Report

A ii C:\cdmxm\fisherbl\d0123757\Table of Contents.doc

2.7.3 Description of Building Lighting .......................................................... 2-12 2.7.4 Miscellaneous Equipment ...................................................................... 2-12 2.8 Applegate Elementary School ............................................................................... 2-13 2.8.1 Description of Building Envelope ......................................................... 2-13 2.8.2 Description of Building HVAC ............................................................. 2-13 2.8.3 Description of Building Lighting .......................................................... 2-13 2.8.4 Miscellaneous Equipment ...................................................................... 2-14

Section 3 Baseline Energy Use 3.1 Utility Data Analysis ................................................................................................ 3-1

3.1.1 Electrical Charges ...................................................................................... 3-1 3.1.2 Natural Gas Charges ................................................................................. 3-2 3.1.3 Water Charges ........................................................................................... 3-2

3.2 Facility Results .......................................................................................................... 3-2 3.2.1 D.D. Eisenhower Middle School ............................................................. 3-2 3.2.2 J.J. Catena Elementary School .................................................................. 3-4 3.2.3 C.T. Barkalow Middle School .................................................................. 3-6 3.2.4 Early Childhood Learning Center ........................................................... 3-9 3.2.5 M. Erickson Elementary School ............................................................. 3-11 3.2.6 Laura Donovan Elementary School ...................................................... 3-14 3.2.7 West Freehold Elementary School ........................................................ 3-16 3.2.8 Applegate Elementary School ............................................................... 3-18 3.3 Aggregate Costs ...................................................................................................... 3-20 3.4 Portfolio Manager ................................................................................................... 3-21 3.4.1 Portfolio Manager Overview ................................................................. 3-22 3.4.2 Energy Performance Rating ................................................................... 3-22 3.4.3 Portfolio Manager Account Information.............................................. 3-22

Section 4 Energy Conservation and Retrofit Measures (ECRM) 4.1 Building Lighting Systems ...................................................................................... 4-1

4.1.1 D.D. Eisenhower Middle School ............................................................. 4-1 4.1.2 J.J Catena Elementary School ................................................................... 4-3 4.1.3 C.T. Barkalow Middle School .................................................................. 4-4 4.1.4 Early Childhood Learning Center ........................................................... 4-5 4.1.5 M.W. Errickson Elementary School ........................................................ 4-6 4.1.6 Laura Donovan Elementary School ........................................................ 4-7 4.1.7 West Freehold Elementary School .......................................................... 4-9 4.1.8 Applegate Elementary School ............................................................... 4-10 4.2 Building HVAC Systems ....................................................................................... 4-11

4.2.1 D.D. Eisenhower Middle School ........................................................... 4-12 4.2.2 J.J Catena Elementary School ................................................................. 4-15 4.2.3 C.T. Barkalow Middle School ................................................................ 4-20 4.2.4 Early Childhood Learning Center ......................................................... 4-26

Page 5: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Table of Contents Freehold Township School District

Final Energy Audit Report

A iii C:\cdmxm\fisherbl\d0123757\Table of Contents.doc

4.2.5 M.W. Errickson Elementary School ...................................................... 4-29 4.2.6 Laura Donovan Elementary School ...................................................... 4-33 4.2.7 West Freehold Elementary School ........................................................ 4-36

4.2.8 Applegate Elementary School ............................................................... 4-36 4.3 Photovoltaic Solar Energy System ...................................................................... 4-41 4.3.1 D.D. Eisenhower Middle School ........................................................... 4-42 4.3.2 J.J. Catena Elementary School ................................................................ 4-43

4.3.3 C.T. Barklow Middle School .................................................................. 4-44 4.3.4 Early Childhood Learning Center ......................................................... 4-45

4.3.5 M.W. Erickson Elementary School ........................................................ 4-45 4.3.6 Laura Donovan Elementary School ...................................................... 4-46 4.3.7 West Freehold Elementary School ........................................................ 4-47 4.3.8 C.R. Applegate Elementary School ....................................................... 4-48 4.3.9 Basis for Conceptual Design .................................................................. 4-49

Section 5 Evaluation of Energy Purchasing and Procurement Strategies 5.1 Energy Deregulation ................................................................................................ 5-1 5.1.1 Alternate Third Party Energy Supplier .................................................. 5-2

Section 6 Ranking of Energy Conservation and Retrofit Measures (ECRMs) 6.1. ECRMs ...................................................................................................................... 6-1 6.1.1 Lighting Systems ....................................................................................... 6-1 6.1.2 HVAC Systems .......................................................................................... 6-3 6.1.3 Solar Energy ............................................................................................... 6-4

Section 7 Available Grants, Incentives and Funding Sources 7.1 Solar Energy Incentives and Financial Options .................................................... 7-1 7.1.1 Solar Renewable Energy Certificates ...................................................... 7-1 7.1.2 Financing Options for Solar Projects ...................................................... 7-1 7.2 New Jersey Clean Energy Program ......................................................................... 7-2 7.2.1 Introduction ............................................................................................... 7-2 7.2.2 New Jersey Smart Start Program ............................................................ 7-3 Appendix A Historical Data Analysis Appendix B Statement of Energy Performance Summary Sheets Appendix C eQuest Model Results Appendix D Lighting Spreadsheet – Option 1 Appendix E Lighting Spreadsheet – Option 2 Appendix F Solar Energy Financing Worksheet Appendix G Glacial Energy – Alternative Electrical Supplier Quote Appendix H New Jersey Smart Start Incentive Worksheets Appendix I Engineers Opinion of Probable Construction Costs Appendix J Facility Data Forms

Page 6: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

A ES-1

Executive Summary As part of an initiative to reduce energy cost and consumption, the Freehold Township School District has secured the services of Camp Dresser and McKee (CDM) to perform an energy audit for buildings owned and operated by the District in an effort to develop comprehensive Energy Conservation and Retrofit Measures (ECRMs).

CDM’s energy audit team visited the facilities on May 26th and 27th, 2009. As a result of the site visits and evaluation of the historical energy usage of the facilities, CDM was successful in identifying opportunities for energy savings measures.

CDM has also evaluated the potential for renewable energy technologies to be implemented at the District’s facilities to offset the District’s electrical energy usage. Specifically, the use of solar electric photovoltaic panels was investigated.

In addition, CDM solicited a proposal from a third party electric energy supplier to investigate any additional energy cost savings that may be available for the District.

Not all ECRMs identified as a result of the energy audit are recommended. ECRMs must be economically feasible to be recommended to the District for implementation. The feasibility of each ECRM was measured through a simple payback analysis. The simple payback period was determined after establishing Engineer’s Opinion of Probable Construction Cost estimates, O&M estimates, projected annual energy savings estimates, and the potential value of New Jersey Clean Energy rebates, or Renewable Energy Credits, if applicable. ECRMs with a payback period of 20 years or less can be recommended.

Historical Energy Usage The following table, Table ES-1, summarizes the current annual energy usage at each of the District’s buildings. These values can serve as a benchmarking tool, along with the building profiles that have been established through the EPA’s Portfolio Manager Program, to quantify the reduction in electrical energy and natural gas usage following the implementation of the recommended ECRMs.

Page 7: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Executive Summary

A ES-2

Table ES-1: Annual Energy Usage & Cost (2008)

Electrical Energy

Use (kWH)

Peak Summer Demand

(kW)

Peak Winter

Demand (kW)

Natural Gas Use (therms)

Cost for Electric Service

Cost for Natural

Gas

D.D.Eisenhower 1,953,535 459 770 12,804 $315,452 $18,506

J.J. Catena 1,044,170 365 256 54,565 $171,455 $81,359

C.T. Barkalow 1,243,807 411 409 74,447 $230,866 $107,674

ECLC 510,560 183 114 43,332 $83,881 $63,716

M.W. Errickson 1,328,261 339 339 53,987 $140,455 $78,086

Laura Donovan 1,331,840 403 611 19,821 $224,277 $29,740

West Freehold 2,319,615 524 624 37,180 $367,467 $54,060

Applegate 964,800 524 416 35,542 $159,146 $53,754

Recommended ECRMs The following table, Table ES-2, presents the ranking of recommended ECRMs identified for the building lighting and HVAC systems. Additional ECRMs were identified and evaluated, as discussed in Section 4; however, were not recommended due to longer payback periods. This table includes the Engineer’s Opinion of Probable Construction Cost, projected annual energy cost savings, projected annual energy usage savings, and total simple payback period for each recommended ECRM. The ECRMs are ranked based on payback period.

Table ES-3 summarizes the Total Engineer’s Opinion of Construction Cost, annual energy savings, projected annual energy and O&M cost savings and the payback period based on the implementation of all recommended ECRMs.

Page 8: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Executive Summary

A ES-3

Table ES-2: Ranking of Recommended ECRM’s Overall

Ranking (Based

on Simple

Payback)

ECRM

Engineer’s Opinion of Probable

Construction Cost1

Projected Annual Energy Savings (kWH or therms)

Projected Annual

Energy & O&M Cost Savings

Simple Payback Period (years)

1 JJ Catena – Air Handler Controls $2,245 4,917 therms $11,279 0.2

2 D.D. Eisenhower (Lighting Upgrade - Option 2) $60,319 113,789 kWH $18,394 3.2

3 Early Childhood Learning

Center (Lighting Upgrade - Option 2)

$21,930 39,497 kWH $6,430 3.4

4 West Freehold (Lighting Upgrade - Option 2) $41,622 76,535 kWH $12,184 3.4

5 J.J. Catena (Lighting Upgrade - Option 2) $41,100 70,800 kWH $11,611 3.5

6 Applegate (Lighting Upgrade - Option 2) $43,335 72,321 kWH $11,904 3.6

7 Laura Donovan (Lighting Upgrade - Option 2) $40,387 69,964 kWH $11,858 3.7

8 C.T. Barkalow (Lighting Upgrade - Option 2) $70,490 81,804 kWH $13,252 5.3

9 M.W. Errickson (Lighting Upgrade - Option 2) $88,647 45,917 kWH $7,640 11.6

10 ECLC – Insulation at Attic Floor $39,525 2,454 therms $3,043 13.0

11 C.T. Barkalow – Boiler Upgrade $114,281 6,900 therms $8,556 13.4

12 MW Errickson - ERVs $61,410 1,200 therms 15,800 kWH $4,237 14.5

13 JJ Catena – Boiler Upgrade $114,281 6,100 therms $7,625 15.0

1. Engineers Probable Construction takes into account any applicable rebates.

Page 9: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Executive Summary

A ES-4

Table ES-3: Recommended ECRM’s1

Total Engineer’s Opinion of Probable Construction Cost

Projected Annual Energy Savings

Projected Annual Energy & O&M Cost Savings

Simple Payback Period (years)

$739,572 586,427 kWH & 67,488 therms $128,013 5.8

1. Does not include energy savings associated with Solar Energy System.

Renewable Energy Technologies • Solar Energy

Section 4.3 of the report provides for an economic evaluation of a solar energy system recommended to be installed at each of the District’s schools. The evaluation covered the economic feasibility of the District furnishing and installing a solar energy system under a typical construction contract and to assume full responsibility of the operation of such a system.

Based on the simple payback model, summarized in Table ES-4, it would benefit the District to further investigate the installation of a solar energy system at all eight (8) school buildings. This is primarily based on the initial upfront capital investment required for a solar energy system installation and the 10 year payback period. This payback period justifies installing the solar energy system. Other options such as Power Purchase Agreements are potentially available as well to help finance the project. Solar technology is constantly changing and will most likely continue to lower in price.

Two major factors influencing the project financial evaluation is the variance of the prevailing energy market conditions and Solar Renewable Energy Credit (SREC) rates, with the largest impact to the payback model being the SREC credit pricing. For the payback model, conservative estimates of the SREC’s market value over a 15 year period were assumed, as discussed in Section 4.3.

Table ES-4 includes a simple payback analysis for the installation of a solar energy system at all of the District’s school buildings. Refer to Appendix F for a more detailed solar financing spreadsheet.

Table ES-4: Simple Payback Analysis for Solar Energy System

Parameter Solar

Estimated Budgetary Project Cost $6,331,000

1st Year Production 1,103,332 kWh

Annual Electric Savings $176,533

Annual Estimated SREC Revenue $441,333

Project Simple Payback 10.2 Years

Page 10: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

A 1-1

C:\cdmxm\fisherbl\d0123757\Section 1.doc

Section 1 Introduction 1.1 General As part of an initiative to reduce energy cost and consumption, the Freehold Township School District has secured the services of Camp Dresser and McKee (CDM) to perform an energy audit on the District’s eight (8) school buildings in an effort to develop comprehensive energy conservation initiatives.

The performance of an Energy Audit requires a coordinated phased approach to identify, evaluate and recommend energy conservation and retrofit measures (ECRM). The various phases conducted under this Energy Audit included the following:

Gather preliminary data on all facilities;

Facility inspection;

Identify and evaluate potential ECRMs;

Develop the energy audit report.

Figure 1-1 is a schematic representation of the phases utilized by CDM to prepare the Energy Audit Report.

Figure 1-1: Energy Audit Phases

1.2 Background The Freehold Township School District consists of eight (8) buildings; the D.D. Eisenhower Middle School, the J.J. Catena Elementary School, the C.T. Barkalow Middle School, the Early Childhood Learning Center, the M.W. Errickson Elementary School, the Laura Donovan Elementary School, the West Freehold Elementary School and the Applegate Elementary School.

Page 11: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 1 Introduction

A 1-2

C:\cdmxm\fisherbl\d0123757\Section 1.doc

The D.D. Eisenhower Middle School is a 114,979 ft2 building originally built in 1971, with extensions to provide additional classroom space in 1999 and 2004. The school is utilized for grades 6 through 8, with over 800 students, and 90 faculty and staff members. Classes are in session from 8:25 am to 3 pm, with the building being occupied between 7:30 am - 7:00 pm on a regular basis.

The J.J Catena Elementary School is a 76,045 ft2 building originally built in 1961, with thirteen (13) classrooms and an all-purpose room for lunch, physical education and assemblies. In 1964, twelve (12) more classrooms and a lunch room were constructed and in the late 1970’s a library was built in the rear of the building. In 1999, six additional classrooms, including a music room, a new gym and cafeteria were built in conjunction with a renovation to the original (1961) construction. In 2004, a new kindergarten wing and another all-purpose room were opened. The elementary school is utilized for grades K through 5, for a total of approximately 700 students, in addition to approximately 80 teachers, administration, maintenance and cafeteria staff. Classes are in session from 8:40 am to 3 pm, with the elementary school occupied from 7:00 am and 6:00 pm.

The C.T. Barkalow Middle School is a 110,533 ft2 building that was originally built in 1964, with subsequent additions in 1970, 1999 and 2003. The middle school is utilized for grades 6 through 8, for a total of 830 students and 85 faculty members. The middle school classes run from 8:25 am to 3 pm, and the building is occupied between 7:00 am and 6:00 pm.

The Early Childhood Learning Center is the Township’s pre-school and administration building. The school is housed in the original West Freehold School built in 1956 and later renovated. The older section of the building was converted from classrooms to office space for the Central Office personnel. The building is occupied between 8:00 am and 4:00 pm, with morning and afternoon pre-school sessions and a full-day schedule.

The M.W. Errickson Elementary School is a 78,130 ft2 building originally built in 1972, with extensions built to increase classroom and cafeteria space in 1999 and 2003. The elementary school is utilized for grades K through 5, for a total of 700 students and 80 faculty and staff members. Classes are in session from 8 am to 2:20 pm, with the elementary school occupied from 7:00 am to 6:00 pm.

The Laura Donovan Elementary School is a 76,491 ft2 building that was originally built in 1968, with extensions and renovations in 1999 and 2003. The elementary school is utilized for grades K through 5, for a total of 650 students and 80 faculty and staff members. Classes are in session from 8 am to 2:20 pm, with the elementary school occupied from 7:00 am to 6:00 pm.

The West Freehold Elementary School is a 90,000 ft2 building built in 2004. The elementary school is utilized for grades K through 5, for a total of 575 students and 78

Page 12: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 1 Introduction

A 1-3

C:\cdmxm\fisherbl\d0123757\Section 1.doc

faculty and staff members. Classes run from 8 am to 2:20 pm, with the building occupied between 7:00 am and 6:00 pm.

The Applegate Elementary School is a 81,963 ft2 building that was built in 1975, with a new kindergarten wing in 2004. The elementary school is utilized for grades K through 5, for a total of approximately 600 students and 101 faculty and staff members. Classes run from 8 am to 2:20 pm, with the building occupied between 7:00 am and 6:00 pm.

1.3 Purpose and Scope The objective of the energy audit is to identify energy conservation and retrofit measures to reduce energy usage and to develop an economic basis to financially validate the planning and implementation of identified energy conservation and retrofit measures.

The buildings that comprise the Freehold Township School District were originally designed to comfortably house school children and staff with limited consideration for energy consumption. Currently, due to the rising costs of power and the desire to minimize dependence on foreign oil supplies, energy consumption is taking a higher priority across the nation. Significant energy savings may be available with retrofits to the buildings’ envelopes, heating, cooling and lighting systems. It should be noted that the magnitude of energy savings available is not only dependent on the type of heating, lighting or insulation systems that are in use, but also on the age and condition of the equipment and the capital available to implement major changes.

The purpose of this energy audit is to identify the various critical building comfort systems within the eight (8) buildings that are major consumers of electrical energy and are clear candidates for energy savings measures. The potential for solar electric systems to be installed at each building was also evaluated and presented herein.

In addition to identifying ECRMs and the potential for on-site energy generation, an alternate third party electric supplier was contacted in an effort to identify further cost savings available for the District, by switching service providers. This is discussed further in Section 5.

Page 13: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

A 2-1

Section 2 Facility Description

2.1 D.D. Eisenhower Middle School 2.1.1 Description of Building Envelope The energy audit included an evaluation of the building’s envelope (exterior shell) to determine the components’ effective R-values to be utilized in the building model and to locate and fix any thermal weaknesses that may be present. The components of a building envelope include the exterior walls, foundation and roof. The construction and material, age and general condition of these components, including exterior windows and doors, impact the buildings energy use.

The D.D. Eisenhower Middle School’s walls are composite cavity walls consisting of face brick, cavity and concrete masonry CMU back-up blocks. The original portion of the building has high wood ceilings. The existing roofing system consists of insulation and EPDM over flat roof decks. The windows throughout the D.D. Eisenhower Middle School are insulating double pane windows.

It was determined that the building envelope is in good condition and is currently providing a high level of insulation. As such, any modifications to the insulation system would not prove to be cost effective, from an energy savings stand-point.

2.1.2 Description of Building HVAC The majority of the space within the D.D. Eisenhower Middle School is heated using electric resistance coils. Many of the classrooms in the original building sections employ unit ventilators with electric coils for heat, and outdoor DX condensers for cooling. Spaces such as the library, gym, office areas, and some of the larger classrooms employ packaged air handling units with either rooftop or packaged condensers, and electric resistance heating coils.

The 2003 wing employs a slightly different method of heating and cooling. Within this wing, there are two Aerco 30 HP gas-fired boilers which provide the wing with hot water for heating. This wing utilizes a packaged rooftop air handling system with several condensers for cooling. Each room then uses a VAV system with hot water reheat.

2.1.3 Description of Building Lighting The existing lighting system consists of 2X2 (2 lamp), 1X4 (1 and 2 lamp), 2X4 (2, 3, and 4 lamp), 4X4 (4, 6, and 8-lamp), 4-foot (2 and 3 lamp), and 2-foot (2-lamp) linear fluorescent fixtures, along with compact fluorescent, metal halide, and incandescent fixtures. All of the fluorescent fixtures at this facility already have energy efficient T-8 lamps with electronic ballasts. However there are a small number of existing inefficient incandescent fixtures, which should be replaced. The current indoor HID

Page 14: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-2

fixtures throughout the facility are somewhat efficient by today’s standards, but produce a poor quality of light, and in seeking the highest of efficiency standards, it is recommended that the Metal Halide HID fixtures be replaced with T5 linear fluorescent fixtures for an increase in quality of light, light output, a decrease in energy consumption, and the ability to have instant on/instant off capabilities instead of waiting 5-10 minutes for the HID fixtures to light up. In addition, locations were identified during the audit where the installation of occupancy sensors would increase overall energy savings. Lighting system improvements are discussed further in Section 4.1.

2.1.4 Miscellaneous Equipment On average, each classroom contains at least one (1) computer, printer, smart board or overhead projector and TV. The school also has four (4) media classrooms which contain 45 computers with LCD monitors and 59 computers with CRT monitors. The library has 40 computers with CRT monitors and a number of printers. There is a home economics classroom with a clothing washer and dryer, two (2) refrigerators, two (2) stovetops, two (2) ovens and two (2) microwaves. There is a shop classroom that contains seven (7) electronic tool stations and a dust collection system.

It is recommended that the District consider implementing the standardized use throughout the eight (8) school buildings of Smart Strips, as the need arises. Computer peripherals, such as monitors, printers or scanners, continue to use energy even after they are shut off, which adds up over time. The Smart Strip power strips offer surge protection and the ability to monitor the current on a single ‘control’ outlet. When the computer that is plugged into that single outlet is shut down and Smart Strip shuts off all of the other peripherals on the power strip.

The school also has office areas, faculty rooms and a nurse’s office that contain copiers, microwaves, refrigerators, vending machines, soda machines and coffee makers.

The D.D. Eisenhower Middle School’s kitchen has a number of appliances including refrigerators, warming cabinets and electric warming tables and convection ovens. It is also recommended that the District consider implementing the standardized use of Energy Star appliances throughout each of the schools, as the need arises. Energy Star refrigerators and freezers, for example, use up to 40% less energy than models built in 2001. Energy Star appliances will not only reduce the District’s utility bills, but will also outperform standard appliances, due to the improved design and advanced technologies.

Page 15: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-3

2.2 J.J Catena Elementary School 2.2.1 Description of Building Envelope The J.J. Catena Elementary School’s walls are composite cavity walls consisting of face brick, cavity and concrete masonry CMU back-up blocks. The original portion of the building has high wood ceilings. The existing roofing system consists of insulation and EPDM over flat roof decks. The windows throughout the J.J. Catena Elementary School are insulating double pane windows.

It was determined that the building envelope is in good condition and is currently providing a high level of insulation. As such, any modifications to the insulation system would not prove to be cost effective, from an energy savings stand-point.

2.2.2 Description of Building HVAC The J.J. Catena Elementary School employs a hot water system as its primary heating source. Many classrooms within the 1963 area of the building either utilize unit ventilators or rooftop units with hot water coils for heat, and DX condensers for cooling. A 75 HP H.B. Smith Boiler provides much of the hot water for the heating system within this area of the school.

The 1999 section uses packaged gas-fired rooftop units for heating and cooling in the majority of the rooms.

The 2004 wing uses a two-30 HP Aerco boiler set up, similar to that found in the D.D. Eisenhower School. Cooling is provided by air handling units with rooftop condensers, and VAV boxes with hot water reheat coils for each of the rooms.

2.2.3 Description of Building Lighting The existing lighting system consists of 2X2 (2 lamp), 1X4 (2 lamp), 2X4 (2, 3, and 4 lamp), 4X4 (4 lamp), 8-foot (2 and 4 lamp), 4-foot (1, 2, and 3 lamp), 2-foot (2 lamp) linear fluorescent fixtures, along with compact fluorescent, metal halide, high pressure sodium, and incandescent fixtures. Almost all of the fluorescent fixtures at this facility already have energy efficient T-8 lamps with electronic ballasts. However there are a small number of existing inefficient incandescent and fluorescent fixtures, which should be replaced. The current indoor HID fixtures throughout the facility are somewhat efficient by today’s standards, but produce a poor quality of light, and in seeking the highest of efficiency standards, it is recommended that the Metal Halide HID fixtures be replaced with T5 linear fluorescent fixtures for an increase in quality of light, light output, a decrease in energy consumption, and the ability to have instant on/instant off capabilities instead of waiting 5-10 minutes for the HID fixtures to light up.

2.2.4 Miscellaneous Equipment On average, each classroom contains at least two (2) or three (3) computers, a printer, smart board or overhead projector and TV. The school also has a media center, a

Page 16: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-4

computer room with 25 computers, printer / scanner, plotter and smart board and a library with 11 computers with LCD monitors and printers.

The school also has a server room, office areas, faculty rooms and a nurse’s office that contain copiers, microwaves, refrigerators, vending machines, soda machines and coffee makers.

The J.J. Catena Elementary School’s kitchen has a number of appliances including refrigerators, freezers, electric warming tables and convection ovens. It is recommended that the District consider implementing the standardized use of Smart Strips and Energy Star appliances.

2.3 C.T. Barkalow Middle School 2.3.1 Description of Building Envelope The C.T. Barkalow Middle School’s walls are composite cavity walls consisting of face brick, cavity and concrete masonry CMU back-up blocks. The original portion of the building has high wood ceilings. The existing roofing system consists of insulation and EPDM over flat roof decks. At the time of the audit, there was evidence of leakage on the drop ceilings in the hallways of the original portion of the building and upon further evaluation, it was observed that rain water pools around the sky lights of that section of the roof (as shown in the above picture). As such, it is recommended that the roof drainage system be evaluated and the potential to repair and re-insulate this roof be considered. If the roof is leaking around the sky lights, the insulation and thermal barrier of the roofing system is compromised, which will result in an increase of infiltration of outside air.

If the District pursues roof repair and / or replacement work, it is recommended that a white thermal barrier coating be applied to the roof surface. This coating works to reduce the surface temperature of the roof by reflecting the UV rays, and provides insulation for the interior of the building reducing the heating and cooling loads.

The windows throughout the C.T. Barkalow Middle School are insulating double pane windows, installed in 2003.

Page 17: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-5

2.3.2 Description of Building HVAC The original, 1965, section of the Barkalow School is heated primarily with a hot water system, fed by two-45 HP H.B. Smith boilers, serving unit ventilators in many of the classrooms. Some of the larger rooms employ in room air handling units, with either electric or hot water coils, depending on the room. Large areas, such as the gym and cafeteria, have dedicated packaged rooftop units.

Classrooms within the 1999 wings of the building utilize either unit ventilators or packaged gas-fired rooftop units for air conditioning.

The 2003 wing employs two-30 HP Aerco boilers, which serve VAV boxes with hot water reheat coils. Cooling is provided by a 40-ton rooftop McQuay unit.

At the time of the audit, it was observed that a few of the classroom unit ventilators were blocked by tall grass. It should be noted, that any blockage of the unit ventilators of this type will decrease the heating and cooling capacity of the unit and consequently increase the energy bill. It was brought to our attention that maintenance staff was limited; however, CDM would like to stress the importance of maintenance of the mechanical equipment, in both ensuring that the ventilators aren’t blocked and/or that the filters are cleaned regularly, for example. This will work to ensure that the units are operating as efficiently as possible and that their expected lifetime isn’t compromised.

2.3.3 Description of Building Lighting The existing lighting system consists of 2X2 (2 and 4 lamp), 1X4 (2 lamp), 2X4 (2, 3, and 4 lamp), 4X4 (6 and 8 lamp), 4-foot (1, 2, 3, and 4 lamp), 2-foot (2 lamp) linear fluorescent fixtures, along with compact fluorescent, metal halide, high pressure sodium, and incandescent fixtures. All of the linear fluorescent fixtures at this facility already have energy efficient T-8 lamps with electronic ballasts. However there are a small number of existing inefficient incandescent fixtures, which should be replaced. The current indoor HID fixtures throughout the facility are somewhat efficient by today’s standards, but produce a poor quality of light, and in seeking the highest of efficiency standards, it is recommended that the Metal Halide HID fixtures be replaced with T5 linear fluorescent fixtures for an increase in quality of light, light output, a decrease in energy consumption, and the ability to have instant on/instant off capabilities instead of waiting 5-10 minutes for the HID fixtures to light up. In addition, locations were identified during the audit where the installation of occupancy sensors would increase overall energy savings.

Page 18: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-6

2.3.4 Miscellaneous Equipment On average, each classroom contains at least one (1) computer, printer, smart board or overhead projector and TV. The school also has a library and three (3) computer classrooms with 93 computers and numerous printers. There is a home economics classroom with two (2) refrigerators, four (4) dishwashers, (4) ovens, stovetops, microwaves and mixers. There is a shop classroom that contains five (5) electronic tool stations, ten (10) computers, printer, projector, eyewash/ shower, sick and a dust collection system.

The school also has a server room, office areas, faculty rooms and a nurse’s office that contain copiers, microwaves, refrigerators, vending machines, soda machines and coffee makers.

The C.T. Barkalow Middle School’s kitchen has a number of appliances including two (2) walk-in refrigerators, freezers and refrigerators, electric warming tables, an ice maker, steam kettle and convection ovens. Food for all of the school buildings is stored and prepared at C.T. Barkalow. It is recommended that the District consider implementing the standardized use of Smart Strips and Energy Star appliances.

At the time of the audit, it was noted that the toilets in the boy’s bathroom located in the east hallway of the original building are set to flush automatically every three (3) minutes. If this is in fact the case, it is recommended that the District consider replacement or repair of the bathroom exhaust fan, as it was explained that the automatic flushing was set up to minimize odors. Although not specifically evaluated at the time of the audit, the exhaust fan may not be working properly or may be undersized. Ensuring that the exhaust system is adequate may result in a savings of 14 to 21 gallons every three (3) minutes (3 toilets utilizing 4 to 7 gallons with every flush).

2.4 Early Childhood Learning Center 2.4.1 Description of Building Envelope The Early Childhood Learning Center is the Township’s pre-school and administration building. The walls are composite cavity walls consisting of face brick, cavity and concrete masonry CMU back-up blocks. The original portion of the building, now used as the administration area, is three levels including the attic space. The roof is a sloped singled roof. The attic floor is insulated with a layer of loose foam insulation, with poor sealing around penetrations for HVAC equipment and apparent infiltration between the roof and top of

Page 19: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-7

wall. The remainder of the building is one level and the roofing system over the classroom areas appears to be in good condition, consisting of insulation and EPDM over flat roof decks.

The windows throughout the Early Childhood Learning Center (ECLC) are single pane windows.

2.4.2 Description of Building HVAC The original, 1956, section of the building uses a steam system for heat. Typical rooms have unit ventilators with steam coils for heat, and outdoor DX condensers for cooling. The gymnasium uses an attic unit with a steam coil for heat, there is no cooling. Two-65 HP H.B. Smith boilers feed the steam system.

The newer, 1970, classroom wing uses a hot water system for heating. Typical rooms in this area use unit ventilators with hot water coils, and outdoor DX condensers for cooling. The hot water for this system is created using a steam to hot water heat exchanger, which pulls steam from the fore-mentioned steam system in the main area of the building.

2.4.3 Description of Building Lighting The existing lighting system consists of 2X2 (2 lamp), 1X4 (2 lamp), 2X4 (2, 3, and 4 lamp), 4-foot (1, 2, 3, and 4 lamp), 2-foot (2 lamp) linear fluorescent fixtures, along with compact fluorescent, metal halide, high pressure sodium, and incandescent fixtures. Almost all of the linear fluorescent fixtures at this facility already have energy efficient T-8 lamps with electronic ballasts. However there are a small number of existing inefficient incandescent and fluorescent fixtures, which should be replaced. The current indoor HID fixtures throughout the facility are somewhat efficient by today’s standards, but produce a poor quality of light, and in seeking the highest of efficiency standards, it is recommended that the Metal Halide HID fixtures be replaced with T5 linear fluorescent fixtures for an increase in quality of light, light output, a decrease in energy consumption, and the ability to have instant on/instant off capabilities instead of waiting 5-10 minutes for the HID fixtures to light up. In addition, locations were identified during the audit where the installation of occupancy sensors would increase overall energy savings.

2.4.4 Miscellaneous Equipment The ECLC offices and teachers room contain computers, printers, phones, copiers and scanners, refrigerators and a soda machine. In addition, there are a number of window air conditioning units throughout the ECLC.

Page 20: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-8

This building also has a server room above the boiler room, which consequently, is very hot and air conditioning is run year round. There is a small kitchen in the ECLC that contains a refrigerator and freezer. It is recommended that the District consider implementing the standardized use of Smart Strips and Energy Star appliances.

2.5 M.W. Errickson Elementary School 2.5.1 Description of Building Envelope The M.W. Errickson Elementary School’s walls are composite cavity walls consisting of face brick, cavity and concrete masonry CMU back-up blocks. The roofing system through the building, except for the Kindergarten Wing, consists of insulation and EPDM over flat roof decks. The roof system over the Kindergarten Wing consists of sloped shingled roofs.

It was observed that the windows in the older portions of the Errickson School are single paned, while the windows in the newer Kindergarten Wing are insulating double paned windows.

It was determined that the building envelope is in good condition and is currently providing a high level of insulation. As such, any modifications to the insulation system would not proof to be cost effective, from an energy savings stand-point.

2.5.2 Description of Building HVAC The Errickson Elementary School is comprised of several “pods”, each of which contains approximately 8 classrooms and corresponding corridor and restroom space. Each of these “pods” utilizes a multi-zone packaged, gas-fired rooftop unit with DX condensers for cooling. The media center also uses one of these units. There are also several heating and ventilating units, located near the gymnasium, that serve the gym, stage, and surrounding areas. Each of these units has a corresponding 20-ton rooftop condenser to provide cooling.

The cafeteria uses a packaged, gas-fired rooftop unit for heating and cooling. This unit employs a heat recovery wheel, capable of capturing heat from air being exhausted

Page 21: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-9

from the space and applying it to air coming into the space. This helps to save energy, as exhausted heat is captured and reused.

The 2003 wing of the building uses two-30 HP Aerco boilers, to provide hot water to VAV boxes above each room. Cooling is provided by attic air handling units, with rooftop condensers.

2.5.3 Description of Building Lighting The existing lighting system consists of 2X2 (2 lamp), 1X4 (1 and 2 lamp), 2X4 (2, 3, 4, and 8 lamp), 4X4 (4, 6, and 8-lamp), 4-foot (1, 2, and 3 lamp), 2-foot (2-lamp) linear fluorescent fixtures, along with compact fluorescent, metal halide, and incandescent fixtures. All of the fluorescent fixtures at this facility already have energy efficient T-8 lamps with electronic ballasts. However there are a small number of existing inefficient incandescent fixtures, which should be replaced. In addition, areas were identified during the audit where the installation of occupancy sensors would increase overall energy savings.

2.5.4 Miscellaneous Equipment On average, each classroom contains at least one (1) computer, printer, smart board or overhead projector and TV. The school also has a media center with numerous computers and printers.

The school also has office areas, faculty rooms and a nurse’s office that contain copiers, microwaves, refrigerators, vending machines, soda machines and coffee makers.

The M.W. Errickson Elementary School’s kitchen has a number of appliances including freezers and refrigerators, electric warming tables and convection ovens. It is recommended that the District consider implementing the standardized use of Smart Strips and Energy Star appliances.

2.6 Laura Donovan Elementary School 2.6.1 Description of Building Envelope The Laura Donovan Elementary School’s walls are composite cavity walls consisting of face brick, cavity and concrete masonry CMU back-up blocks. The roofing system through the building, except for the Kindergarten Wing, consists of insulation and EPDM over flat roof decks. The roof system over the Kindergarten Wing consists of sloped shingled roofs. One of the wings in the elementary school, built in the ‘90’s, is modular construction.

Page 22: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-10

The original portion of the building has high wood ceilings. The windows throughout the Laura Donovan School are insulating double paned windows. There are ledges over the windows in the older areas of the building that serve to block the sun.

It was determined that the building envelope is in good condition and is currently providing a high level of insulation. As such, any modifications to the insulation system would not proof to be cost effective, from an energy savings stand-point.

2.6.2 Description of Building HVAC The Laura Donovan Elementary School primarily employs electric heating within its classrooms. Most of the classrooms within the original, 1968, area of the building utilize unit ventilators with electric resistance coils for heat, and outdoor DX condensers for cooling. The condensers couple as air source heat pumps to supplement heating within the classrooms during the heating season. Space conditioning within the gymnasium and stage is provided by five gas-fired rooftop units.

The cafeteria and media center are part of the 1999 addition to the school. These rooms are also conditioned by packaged gas-fired rooftop units.

Classrooms within the 1995 wing of the building also utilize gas-fired rooftop units for space conditioning.

The 2003 wing of the building uses two-30 HP Aerco boilers, to provide hot water to VAV boxes above each room. Cooling is provided by attic air handling units, with rooftop condensers.

2.6.3 Description of Building Lighting The existing lighting system consists of 2X2 (2 lamp), 1X4 (2 lamp), 2X4 (2, 3, and 4 lamp), 8-foot (4 lamp), 4-foot (1, 2, and 3 lamp), 2-foot (2 lamp) linear fluorescent fixtures, along with compact fluorescent, metal halide, high pressure sodium, and incandescent fixtures. All of the linear fluorescent fixtures at this facility already have energy efficient T-8 lamps with electronic ballasts. However there are a small number of existing inefficient incandescent fixtures, which should be replaced. The current indoor HID fixtures throughout the facility are somewhat efficient by today’s

Page 23: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-11

standards, but produce a poor quality of light, and in seeking the highest of efficiency standards, it is recommended that the Metal Halide HID fixtures be replaced with T5 linear fluorescent fixtures for an increase in quality of light, light output, a decrease in energy consumption, and the ability to have instant on/instant off capabilities instead of waiting 5-10 minutes for the HID fixtures to light up. In addition, areas were identified during the audit where the installation of occupancy sensors would increase overall energy savings.

2.6.4 Miscellaneous Equipment On average, each classroom contains at least one (1) computer, printer, smart board or overhead projector and TV. The school also has a media center with seven (7) computers and a computer classroom with thirty-one (31) computers and numerous printers.

The school also has office areas, faculty rooms and a nurse’s office that contain copiers, microwaves, refrigerators, vending machines, soda machines and coffee makers. It is recommended that the District consider implementing the standardized use of Smart Strips and Energy Star appliances.

The Laura Donovan Elementary School’s kitchen has a number of appliances including freezers and refrigerators, electric warming tables, convection ovens, ice cream freezers and milk refrigerators. At the time of the audit, the kitchen door was open and the staff indicated that the kitchen gets very hot. It is recommended that the kitchen ventilation capacity be evaluated further. The kitchen ventilation may not have been sized to account for any addition of appliances.

2.7 West Freehold Elementary School 2.7.1 Description of Building Envelope The West Freehold Elementary School’s walls are composite cavity walls consisting of face brick, cavity and concrete masonry CMU back-up blocks and vapor barrier at foundation. The roofing system through the building consists of insulation and EPDM over flat roof decks or sloped shingled roofs.

The windows throughout the school are insulating double paned windows.

It was determined that the building envelope is in good condition and is currently providing a high level of insulation. As such, any modifications to the insulation system would not proof to be cost effective, from an energy savings stand-point.

2.7.2 Description of Building HVAC The West Freehold Elementary School employs a water source heat pump system. Rooms are conditioned using heat pumps which either heat or cool incoming air based on the entering water temperature. During the heating season, two-60 HP Aerco boilers provide hot water to the heat pumps, which then extract the heat and

Page 24: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-12

transfer it to the incoming air. During the cooling season, two Evapco cooling towers provide chilled water to the heat pumps, which reject heat from the incoming air, into the chilled water.

In addition to this relatively efficient heating and cooling system, the building utilizes several heat recovery ventilators (HRVs) with electric reheat coils. These HRVs save energy by recapturing heat that would otherwise be exhausted from the space, and applying it to outside air being supplied to the space, supplementing the heating provided by the heat pump systems.

As this system is a relatively new, energy efficient design, upgrade measures will likely not prove cost-effective.

2.7.3 Description of Building Lighting The existing lighting system consists of 2X2 (2 and 3 lamp), 1X4 (2 lamp), 2X4 (2 and 3 lamp), 4-foot (2, 3, and 4 lamp) linear fluorescent fixtures, along with compact fluorescent, metal halide, and incandescent fixtures. All of the fluorescent fixtures at this facility already have energy efficient T-8 lamps with electronic ballasts.

2.7.4 Miscellaneous Equipment On average, each classroom contains at least one (1) computer, printer, smart board or overhead projector and TV. The school also has a media center with ten (10) computers and a computer classroom with twenty-eight (28) computers and numerous printers.

The school also has office areas, faculty rooms and a nurse’s office that contain copiers, microwaves, refrigerators, vending machines, soda machines and coffee makers.

The West Freehold Elementary School’s kitchen has a number of appliances including freezers and refrigerators, electric warming tables, warming cabinets, convection ovens, microwaves, ice cream freezers and milk refrigerators. It is recommended that the District consider implementing the standardized use of Smart Strips and Energy Star appliances.

2.8 Applegate Elementary School 2.8.1 Description of Building Envelope The Applegate Elementary School’s walls are composite cavity walls consisting of face brick, cavity and concrete masonry CMU back-up blocks. The existing roofing system consists of insulation and EPDM over flat roof decks. The windows throughout the Applegate Elementary School are single pane windows.

Operations and maintenance staff indicated that roof leakage repairs in the 1999 wing have left portions un-insulated. If this is in fact the case, insulation of these areas will

Page 25: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-13

improve the thermal barrier and reduce the load on the building’s heating and cooling equipment. If further roof repair is required, it is recommended that the application of a white thermal barrier be considered, as discussed previously.

2.8.2 Description of Building HVAC The design of the Applegate Elementary School is very similar to that of the Errickson Elementary School. Most of the classrooms are grouped into “pods”, and each pod is served by a packaged, multi-zone gas-fired rooftop unit with DX condensers for cooling. There are also several heating and ventilating units, located near the gymnasium, that serve the gym, stage, and surrounding areas. Each of these units has a corresponding 20-ton rooftop condenser to provide cooling.

The cafeteria and 5th Grade wings were added to the building in 1999. Each of these areas employs a gas-fired rooftop unit for heating and cooling.

The 2003 wing of the building uses two-30 HP Aerco boilers, to provide hot water to VAV boxes above each room. Cooling is provided by attic air handling units, with rooftop condensers.

2.8.3 Description of Building Lighting The existing lighting system consists of 2X2 (2 lamp), 1X4 (1 and 2 lamp), 2X4 (2, 3, and 4 lamp), 4X4 (4, 6, and 8-lamp), 4-foot (2 and 3 lamp), and 2-foot (2-lamp) linear fluorescent fixtures, along with compact fluorescent, metal halide, and incandescent fixtures. All of the fluorescent fixtures at this facility already have energy efficient T-8 lamps with electronic ballasts. However there are a small number of existing inefficient incandescent fixtures, which should be replaced. The current indoor HID fixtures throughout the facility are somewhat efficient by today’s standards, but produce a poor quality of light, and in seeking the highest of efficiency standards, it is recommended that the Metal Halide HID fixtures be replaced with T5 linear fluorescent fixtures for an increase in quality of light, light output, a decrease in energy consumption, and the ability to have instant on/instant off capabilities instead of waiting 5-10 minutes for the HID fixtures to light up. In addition, areas were identified during the audit where the installation of occupancy sensors would increase overall energy savings.

2.8.4 Miscellaneous Equipment On average, each classroom contains at least one (1) computer, printer, smart board or overhead projector and TV. The school also has a media center with ten (10) computers and a computer classroom with thirty (30) computers and numerous printers.

Page 26: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 2 Facility Description

A 2-14

The school also has office areas, faculty rooms and a nurse’s office that contain copiers, microwaves, refrigerators, vending machines, soda machines and coffee makers.

The Applegate Elementary School’s kitchen has a number of appliances including freezers and refrigerators, electric warming tables, convection ovens, ice cream freezers and milk refrigerators. There was a space heater and a fan in the kitchen. It is recommended that the District consider implementing the standardized use of Smart Strips and Energy Star appliances.

Page 27: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

A 3-1

Section 3 Baseline Energy Use

3.1 Utility Data Analysis The first step in the energy audit process is the compilation and quantification of the facilities current and historical energy usage and associated utility costs. It is important to establish the existing patterns of electric, gas and fuel oil usage in order to be able to identify areas in which energy consumption can be reduced.

For this study, monthly utility bills were analyzed and unit costs of energy obtained. The unit cost of energy, as determined from the monthly utility bills, was utilized in determining the feasibility of switching from one energy source to another or reducing the demand on that particular source of energy to create annual cost savings for the Freehold School District.

3.1.1 Electric Charges It was also important to understand how the utilities charge for the service. The majority of the energy consumed is electric, as a result of both indoor and outdoor lighting and appliances, such as kitchen appliances, computers, printers and projectors. Electricity is charged by three basic components: electrical consumption (kWH), electrical demand (kW) and power factor (kVAR) (reactive power). The cost for electrical consumption is similar to the cost for fuel oil, the monthly consumption appears on the utility bill as kWH consumed per month with a cost figure associated with it. The School District’s service connections are billed with a flat rate for consumption, as explained in Section 3.2.1.

Electrical demand can be as much as 50 percent or more of the electric bill. The maximum demand (kW value) during the billing period is multiplied by the demand cost factor and the result is added to the electric bill. It is often possible to decrease the electric bill by 15 – 25 percent by reducing the demand, while still using the same amount of energy.

The power factor (reactive power) is the power required to energize electric and magnetic fields that result in the production of real power. Power factor is important because transmission and distribution systems must be designed and built to manage the need for real power as well as the reactive power component (the total power). If the power factor is low, then the total power required can be greater than 50 percent or more than the real power alone. The power factor charge is a penalty for having a low power factor. This penalty charge does not impact the School District.

The other parts of the electric bill are the supply charges, delivery charges, system benefits, transmission revenue adjustments, state and municipality tariff surcharges and sales taxes, which cannot be avoided.

Page 28: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-2

3.1.2 Natural Gas Charges New Jersey Natural Gas (NJNG) is the current distributor and supplier of natural gas for the District. As a commercial customer that utilizes more the 5,000 therms annually, the District is billed through NJNG under the monthly Basic Gas Supply Service (BGSS) pricing. The monthly BGSS price is based on the New York Mercantile Exchange (NYMEX) monthly market settlement price. The price for the natural gas commodity is passed on directly to customers with no profit included for NJNG.

The customer charge covers NJNG costs to provide service, including mailings, taxes, system maintenance and record keeping. The delivery charge is the fee applied for delivering gas and maintaining the distribution system. It also includes approved price adjustments related to balancing gas deliveries, variances from normal weather and societal benefits programs such as environmental improvements and NJ’s Clean Energy Program. The current demand charge of $1.50 is applied to the Highest Month Average Daily Usage (HMAD).

3.1.3 Water Charges The Township of Freehold Water and Sewer Department currently supplies treated water to the Freehold School District buildings. Water usage is metered similarly to electric and natural gas usage and the District is billed bimonthly per service location.

3.2 Facility Results 3.2.1 D.D. Eisenhower Middle School Electric power for the D.D. Eisenhower Middle School building is fed from a General Service Secondary Space Heating line from the Jersey Central Power and Light Company (JCP&L). Figure 3.2-1 illustrates the monthly total energy consumption from February 2008 through February 2009. From this graph, it can be determined that the electrical baseline consumption for the D.D. Eisenhower Middle School averages around 110,000 kWH / month. The electrical usage is high as a result of the electric heating and cooling systems that are utilized year round.

This building is billed using a flat rate kWH charge based on JCP&L’s current tariff rates. Demand charges are calculated used the highest measured load for the month. Figure 3.2-2 illustrates the average monthly demand load for 2008.

Page 29: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-3

Figure 3.2-1: D.D. Eisenhower Middle School Building Electrical Usage

The most recent tariff rates available at the time of this audit for General Secondary Service from JCP&L are as follows:

Non-Utility Generation Charges: $0.016960/KWH Societal Benefits Charges: $0.006444/KWH Transitional Assessment Charges: $0.002928/KWH System Control Charge: $0.000079/KWH Delivery Charges: $0.057366/first 1,000 kWH and $0.004958/remaining kWH Demand Charges: $6.47/kW

Figure 3.2-2: D.D. Eisenhower Middle School Maximum Monthly Demand

Page 30: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-4

Refer to Table 3.3-1, in Section 3.3, for average electrical aggregate cost. These tariffs are subject to change quite frequently. For the most up to date tariffs, refer to JCP&L’s website. Refer to Appendix A for complete Historical Data Analysis.

The 2003 wing of D.D. Eisenhower Middle School utilizes natural gas for heat and hot water. Figure 3.2-3 illustrates the building’s monthly natural gas consumption for 2008.

Figure 3.2-3: D.D. Eisenhower Middle School Gas Usage

NJNG bills the District under the BGSS rates, as follows:

General Service Large (GSL) Sales Demand Charge: $147.66/month GSL Customer Charge: $40.00/month BGS charge applied to 40% of total therms: $0.4903/therm BGS charge applied to 60% of total therms: $0.5250/therm Delivery charge applied to total therms: $0.4143/therm

For more on the building gas usage, refer to Section 4.2.

3.2.2 J.J. Catena Elementary School Electric power for the J.J. Catena Elementary School is fed from one General Secondary Service line from JCP&L. Figure 3.2-4 illustrates the Elementary School’s monthly consumption for 2008. For this school, the baseline energy consumption is approximately 62,000 kWH per month.

Page 31: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-5

This building is billed using a flat rate KWH charge based on JCP&L’s current tariff rates. Figure 3.2-5 illustrates the average monthly demand load for 2008.

Figure 3.2-4: J.J. Catena Elementary School Electrical Usage

The current tariff rates for General Secondary Service from JCP&L are as follows:

Non-Utility Generation Charges: $0.016960/KWH Societal Benefits Charges: $0.006444/KWH Transitional Assessment Charges: $0.002928/KWH System Control Charge: $0.000079/KWH Delivery Charges: $0.057366/first 1,000 kWH and $0.004958/remaining kWH Demand Charges: $6.47/kW

Figure 3.2-5: J.J. Catena Elementary School Maximum Monthly Demand

Page 32: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-6

Refer to Table 3-1, in Section 3.3, for average electrical aggregate cost. These tariffs are subject to change quite frequently. For the most up to date tariffs, refer to JCP&L’s website. Refer to Appendix A for complete Historical Data Analysis.

The building’s heating and hot water systems are run on natural gas. Figure 3.2-6 illustrates the building average monthly natural gas consumption for 2008.

Figure 3.2-6: J.J. Catena Elementary School Gas Usage

NJNG bills the District under the BGSS rates, as follows:

General Service Large (GSL) Sales Demand Charge: $677.06/month GSL Customer Charge: $40.00/month BGS charge applied to 40% of total therms: $0.4903/therm BGS charge applied to 60% of total therms: $0.5250/therm Delivery charge applied to total therms: $0.4143/therm

For more on the building gas usage, refer to Section 4.2.

3.2.3 C.T. Barkalow Middle School Electric power for the C.T. Barkalow Middle School is fed from one General Secondary Service line from JCP&L. Figure 3.2-7 illustrates the Middle School’s monthly consumption for 2008. The Middle School’s baseline energy consumption 100,000 kWH per month.

This building is billed using a flat rate KWH charge based on JCP&L’s current tariff rates. Figure 3.2-8 illustrates the monthly demand load for 2008.

Page 33: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-7

Figure 3.2-7: C.T. Barkalow Middle School Electrical Usage

The current tariff rates for General Secondary Service from JCP&L are as follows:

Non-Utility Generation Charges: $0.016960/KWH Societal Benefits Charges: $0.006444/KWH Transitional Assessment Charges: $0.002928/KWH System Control Charge: $0.000079/KWH Delivery Charges: $0.057366/first 1,000 kWH and $0.004958/remaining kWH Demand Charges: $6.47/kW

Refer to Table 3.3-1, in Section 3.3, for average electrical aggregate cost. These tariffs are subject to change quite frequently. For the most up to date tariffs, refer to JCP&L’s website. Refer to Appendix A for complete Historical Data Analysis.

Figure 3.2-8: C.T. Barkalow Middle School Maximum Monthly Demand

Page 34: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-8

The C.T. Barkalow Middle School also has an outdoor lighting service from JCP&L, which amounts to 74 kWH each month. This service is subject to the following rates from JCP&L:

Non-Utility Generation Charges: $0.016960/KWH Societal Benefits Charges: $0.006444/KWH Transitional Assessment Charges: $0.006677/KWH System Control Charge: $0.000079/KWH BGS Energy Charge: $0.094866/kWH BGS Transmission Charges: $0.003812/kWH Delivery Charges: $0.050257/kWH Monthly Lighting Fixture Charges: $4.08

The building’s heating and hot water systems are run on natural gas. Figure 3.2-9 illustrates the building’s monthly natural gas consumption for 2008.

Figure 3.2-9: C.T. Barkalow Middle School Gas Usage

NJNG bills the District under the BGSS rates, as follows:

General Service Large (GSL) Sales Demand Charge: $801.54/month GSL Customer Charge: $40.00/month BGS charge applied to 80% of total therms: $0.5250/therm BGS charge applied to 20% of total therms: $0.5763/therm Delivery charge applied to total therms: $0.4143/therm

For more on the building gas usage, refer to Section 4.2.

Page 35: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-9

3.2.4 Early Childhood Learning Center Electric power for the Early Childhood Learning Center is fed from one General Secondary Service line from JCP&L. Figure 3.2-10 illustrates the building’s monthly consumption for 2008. The baseline electric energy consumption 33,000 kWH per month.

This building is billed using a flat rate KWH charge based on JCP&L’s current tariff rates. Figure 3.2-11 illustrates the monthly demand for 2008.

Figure 3.2-10: ECLC’s Electrical Usage

The current tariff rates for General Secondary Service from JCP&L are as follows:

Non-Utility Generation Charges: $0.016960/KWH Societal Benefits Charges: $0.006444/KWH Transitional Assessment Charges: $0.002928/KWH System Control Charge: $0.000079/KWH Delivery Charges: $0.057366/first 1,000 kWH and $0.004958/remaining kWH Demand Charges: $6.47/kW

Page 36: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-10

Figure 3.2-11: ECLC’s Maximum Monthly Demand

Refer to Table 3-1, in Section 3.3, for average electrical aggregate cost. These tariffs are subject to change quite frequently. For the most up to date tariffs, refer to JCP&L’s website. Refer to Appendix A for complete Historical Data Analysis.

The ECLC’s heating system is fueled by natural gas. Figure 3.2-12 illustrates the building’s monthly natural gas consumption for 2008.

Figure 3.2-12: ECLC’s Gas Usage

Page 37: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-11

NJNG bills the District under the BGSS rates, as follows:

General Service Large (GSL) Sales Demand Charge: $513/month GSL Customer Charge: $40.00/month BGS charge applied to 80% of total therms: $0.6238/therm BGS charge applied to 20% of total therms: $0.8112/therm Delivery charge applied to total therms: $0.4143/therm

For more on the building gas usage, refer to Section 4.2.

3.2.5 M. Errickson Elementary School Electric power for the Errickson Elementary School is fed from three General Secondary Service lines from JCP&L. Figures 3.2-13, 3.2-14 and 3.2-15 illustrate the Elementary School’s monthly consumption for 2008, from meter G28658723, meter G15112467 and meter G98739834 respectively. In this case, the combined baseline energy consumption 75,010 kWH per month.

This building is billed using a flat rate KWH charge based on JCP&L’s current tariff rates. Figures 3.2-16 and 3.2-17 illustrate the monthly demands for 2008.

Figure 3.2-13: Errickson Elementary School Electrical Usage (Meter G28658723)

Page 38: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-12

Figure 3.2-14: Errickson Elementary School Electrical Usage

(Meter G15112467)

Figure 3.2-15: Errickson Elementary School Electrical Usage

(Meter G98739834)

The current tariff rates for General Secondary Service from JCP&L are as follows:

Non-Utility Generation Charges: $0.016960/KWH Societal Benefits Charges: $0.006444/KWH Transitional Assessment Charges: $0.002928/KWH System Control Charge: $0.000079/KWH Delivery Charges: $0.057366/first 1,000 kWH and $0.004958/remaining kWH Demand Charges: $6.47/kW

Page 39: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-13

Figure 3.2-16: Errickson Elementary School Maximum Monthly Demand

(Meter G28658723)

Figure 3.2-17: Errickson Elementary School Maximum Monthly Demand

(Meter G15112467)

Refer to Table 3-1, in Section 3.3, for average electrical aggregate cost. These tariffs are subject to change quite frequently. For the most up to date tariffs, refer to JCP&L’s website. Refer to Appendix A for complete Historical Data Analysis.

The Errickson building’s heating system is fueled by natural gas. Figure 3.2-18 illustrates the building’s monthly natural gas consumption for 2008.

Page 40: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-14

Figure 3.2-18: Errickson Elementary School’s Gas Usage

NJNG bills the District under the BGSS rates, as follows:

General Service Large (GSL) Sales Demand Charge: $621.14/month GSL Customer Charge: $40.00/month BGS charge applied to total therms: $0.5250/therm Delivery charge applied to total therms: $0.4143/therm

For more on the building gas usage, refer to Section 4.2.

3.2.6 Laura Donovan Elementary School Electric power for the Laura Donovan Elementary School is fed from one General Secondary Service line from JCP&L. Figure 3.2-19 illustrates the building’s monthly consumption for 2008. The baseline electric energy consumption 75,000 kWH per month.

This building is billed using a flat rate KWH charge based on JCP&L’s current tariff rates. Figure 3.2-20 illustrates the monthly demand for 2008.

Page 41: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-15

Figure 3.2-19: Laura Donovan Elementary School Electrical Usage

The current tariff rates for General Secondary Service from JCP&L are as follows:

Non-Utility Generation Charges: $0.016960/KWH Societal Benefits Charges: $0.006444/KWH Transitional Assessment Charges: $0.002928/KWH System Control Charge: $0.000079/KWH Delivery Charges: $0.057366/first 1,000 kWH and $0.004958/remaining kWH Demand Charges: $6.47/kW

Figure 3.2-20: Laura Donovan Elementary School’s Maximum Monthly Demand

Page 42: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-16

Refer to Table 3-1, in Section 3.3, for average electrical aggregate cost. These tariffs are subject to change quite frequently. For the most up to date tariffs, refer to JCP&L’s website. Refer to Appendix A for complete Historical Data Analysis.

The Laura Donovan School’s heating system is fueled by natural gas. Figure 3.2-21 illustrates the building’s monthly natural gas consumption for 2008.

Figure 3.2-21 Laura Donovan Elementary School’s Gas Usage

NJNG bills the District under the BGSS rates, as follows:

General Service Large (GSL) Sales Demand Charge: $261.39/month GSL Customer Charge: $40.00/month BGS charge applied to total therms: $0.5250/therm Delivery charge applied to total therms: $0.4143/therm

For more on the building gas usage, refer to Section 4.2.

3.2.7 West Freehold Elementary School Electric power for the West Freehold Elementary School is fed from one General Secondary Service line from JCP&L. Figure 3.2-22 illustrates the building’s monthly consumption for 2008. The baseline electric energy consumption 130,000 kWH per month.

This building is billed using a flat rate KWH charge based on JCP&L’s current tariff rates. Figure 3.2-23 illustrates the monthly demand for 2008.

Page 43: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-17

Figure 3.2-22: West Freehold Elementary School’s Electrical Usage

The current tariff rates for General Secondary Service from JCP&L are as follows:

Non-Utility Generation Charges: $0.016960/KWH Societal Benefits Charges: $0.006444/KWH Transitional Assessment Charges: $0.002928/KWH System Control Charge: $0.000079/KWH Delivery Charges: $0.057366/first 1,000 kWH and $0.004958/remaining kWH Demand Charges: $6.47/kW RGGI Recovery Charge applied to 25% of total kWH: $0.000064

Figure 3.2-23: West Freehold Elementary School’s Maximum Monthly

Demand

Page 44: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-18

Refer to Table 3-1, in Section 3.3, for average electrical aggregate cost. These tariffs are subject to change quite frequently. For the most up to date tariffs, refer to JCP&L’s website. Refer to Appendix A for complete Historical Data Analysis.

The West Freehold School’s heating system is fueled by natural gas. Figure 3.2-24 illustrates the building’s monthly natural gas consumption for 2008.

Figure 3.2-24: West Freehold Elementary School’s Gas Usage

NJNG bills the District under the BGSS rates, as follows:

GSL Sales Demand Charge: $556.38/month GSL Customer Charge: $48.00/month BGS charge applied to 40% of total therms: $0.4903/therm BGS charge applied to 60% of total therms: $0.5250/therm Delivery charge applied to total therms: $0.4143/therm

For more on the building gas usage, refer to Section 4.2.

3.2.8 Applegate Elementary School Electric power for the Applegate Elementary School is fed from one General Secondary Service line from JCP&L. Figure 3.2-25 illustrates the building’s monthly consumption for 2008. The baseline electric energy consumption 61,000 kWH per month.

This building is billed using a flat rate KWH charge based on JCP&L’s current tariff rates. Figure 3.2-26 illustrates the monthly demand for 2008.

Page 45: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-19

Figure 3.2-25: Applegate Elementary School’s Electrical Usage

The current tariff rates for General Secondary Service from JCP&L are as follows:

Non-Utility Generation Charges: $0.016960/KWH Societal Benefits Charges: $0.006444/KWH Transitional Assessment Charges: $0.002928/KWH System Control Charge: $0.000079/KWH Delivery Charges: $0.057366/first 1,000 kWH and $0.004958/remaining kWH Demand Charges: $6.47/kW

Figure 3.2-26: Applegate Elementary School’s Maximum Monthly Demand

Page 46: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-20

Refer to Table 3-1, in Section 3.3, for average electrical aggregate cost. These tariffs are subject to change quite frequently. For the most up to date tariffs, refer to JCP&L’s website. Refer to Appendix A for complete Historical Data Analysis.

The Applegate Elementary School’s heating system is fueled by natural gas. Figure 3.2-27 illustrates the building’s monthly natural gas consumption for 2008.

Figure 3.2-27: Applegate Elementary School’s Gas Usage

NJNG bills the District under the BGSS rates, as follows:

GSL Sales Demand Charge: $528.21/month GSL Customer Charge: $40.00/month BGS charge applied to 70% of total therms: $0.5763/therm BGS charge applied to 30% of total therms: $0.6238/therm Delivery charge applied to total therms: $0.4143/therm

For more on the building gas usage, refer to Section 4.2.

3.3 Aggregate Costs For the purposes of computing energy savings for all identified energy conservation and retrofit measures, aggregate unit costs for electrical energy and natural gas, in terms of cost/kWH and cost/therm, were determined for each building and utilized in the simple payback analyses discussed in subsequent sections. The aggregate unit cost accounts for all distribution and supply charges for each location. Table 3.3-1 and Table 3.3-2 summarize the aggregate costs for electrical energy consumption and therms utilized, respectively.

Page 47: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-21

Table 3.3-1: Electrical Aggregate Unit Costs Service Location Aggregate $ / kW-hr

D.D. Eisenhower Middle School $0.1626

J.J. Catena Elementary School $0.1640

C.T. Barkalow Middle School $0.1620

Early Childhood Learning Center $0.1628

M.W. Errickson Elementary School $0.1664

Laura Donovan Elementary School $0.1695

West Freehold Elementary School $0.1592

Applegate Elementary School $0.1646

Table 3.3-2: Natural Gas Aggregate Unit Costs

Service Location Aggregate $ / therm

D.D. Eisenhower Middle School $1.28

J.J. Catena Elementary School $1.25

C.T. Barkalow Middle School $1.24

Early Childhood Learning Center $1.24

M.W. Errickson Elementary School $1.34

Laura Donovan Elementary School $1.26

West Freehold Elementary School $1.29

Applegate Elementary School $1.30

Page 48: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 3 Baseline Energy Use

A 3-22

3.4 Portfolio Manager 3.4.1 Portfolio Manager Overview Portfolio Manager is an interactive energy management tool that allows the Board of Education to track and assess energy consumption across the School District’s buildings in a secure online environment. Portfolio Manager can help the Board of Education set investment priorities, verify efficiency improvements, and receive EPA recognition for superior energy performance.

3.4.2 Energy Performance Rating For many facilities, you can rate their energy performance on a scale of 1–100 relative to similar facilities nationwide. Your facility is not compared to the other facilities entered into Portfolio Manager to determine your ENERGY STAR rating. Instead, statistically representative models are used to compare your facility against similar facilities from a national survey conducted by the Department of Energy’s Energy Information Administration. This national survey, known as the Commercial Building Energy Consumption Survey (CBECS), is conducted every four years, and gathers data on building characteristics and energy use from thousands of facilities across the United States. Your facility’s peer group of comparison is those facilities in the CBECS survey that have similar facility and operating characteristics. A rating of 50 indicates that the facility, from an energy consumption standpoint, performs better than 50% of all similar facilities nationwide, while a rating of 75 indicates that the facility performs better than 75% of all similar facilities nationwide.

K through 12 grade school buildings are eligible to receive a rating.

3.4.3 Portfolio Manager Account Information A Portfolio Manager account has been established for the District, which includes profiles for the eight (8) school buildings. Information entered into these Portfolio Manager building profiles, including electrical energy consumption and natural gas consumption may be used to apply for an Energy Star rating with the USEPA.

At the time of this report, the school buildings received the following ratings:

D.D. Eisenhower Middle School – 32 J.J. Catena Elementary School – 19 C.T. Barkalow Middle School – 29 Early Childhood Learning Center – 40 M.W. Errickson Elementary School – 6 Laura Donovan Elementary School – 34 West Freehold Elementary School – 3 C. Richard Applegate Elementary School - 57

A Statement of Energy Performance report for each building was generated through Portfolio Manager and included in Appendix B, along with a Portfolio Manager reference sheet.

Page 49: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 50: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

A 4-1

Section 4 Energy Conservation and Retrofit Measures (ECRM) 4.1 Building Lighting Systems The goal of this section is to present any lighting energy conservation measures that may also be cost beneficial. It should be noted that replacing current bulbs with more energy-efficient equivalents will have a small effect on the building heating and cooling loads. The building cooling load will see a small decrease from an upgrade to more efficient bulbs and the heating load will see a small increase, as the more energy efficient bulbs give off less heat.

During the audit it was observed that a significant portion of the lighting fixtures in all eight buildings had been previously retrofit using T8 lamps and electronic ballasts. Additionally, CDM tested light levels throughout all eight buildings and found that light levels were generally above New Jersey State Code (50 footcandles at the desk level in classrooms). As a result of these findings, two retrofit strategies for the District have been developed. The first strategy (Option 1) involves leaving the existing T8 fixtures as-is and retrofitting or replacing other fixtures throughout the district that need to be upgraded to more energy efficient standards, as well as the installation of occupancy sensors. The second strategy (Option 2) involves a more comprehensive project that replaces all of the existing 32-watt T8 lamps with new 28-watt T8 lamps, plus the other retrofit strategies outlined in Option 1.

The Lighting Annual Savings assume the annual hours per year of operation as outlined under the column within the lighting spreadsheet entitled “Hours Code” located in Appendices D & E.

Please note that the probable construction costs presented herein are estimates based on historic data compiled from similar installations and engineering opinions. Additional engineering will be required for each measure identified in this report and final scope of work and budget cost estimates will need to be confirmed prior to the coordination of project financing or the issuance of a Request for Proposal.

4.1.1 D.D. Eisenhower Middle School The existing lighting system at the D.D. Eisenhower Middle School consists of linear fluorescent, compact fluorescent, metal halide, high pressure sodium and incandescent fixtures. All of the linear fluorescent fixtures have energy efficient T-8 lamps with electronic ballasts, as discussed in Section 2.1.3. It is recommended that the small number of existing inefficient incandescent fixtures be replaced. In addition, it is recommended that the current indoor Metal Halide HID fixtures be replaced with T5 linear fluorescent fixtures for an increase in quality of light, light output, a decrease in energy consumption, and the ability to have instant on/instant off capabilities and that occupancy sensors be installed in select locations.

Page 51: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-2

In general, the first strategy (Option 1) for a lighting upgrade project, involves relamping and the installation of occupancy sensors in select locations. Please refer to Appendix D, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 1.

With the implementation of Option 1, the annual energy savings are estimated to be 10.87 kW, 48,006 kWh and $7,805. In addition, the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

In general, the second strategy (Option 2) for a lighting upgrade project is a more comprehensive project that involves replacing the existing 32-watt T8 lamps with new 28-watt T8 lamps, in addition to the recommendations of Option 1. Please refer to Appendix E, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 2.

With the implementation of Option 2, the annual energy savings are estimated to be 45.77 kW, 113,789 kWH and $18,394. In addition the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

The following table, Table 4.1-1, summarizes a simple payback analysis for both lighting system improvement strategies at the D.D. Eisenhower Middle School. Included in this simplified payback analysis summary table is a ‘Return on Investment’ (ROI) values. This value is a performance measure used to evaluate the efficiency of an investment and is calculated by dividing the ‘return’ or savings associated with an investment by the total investment cost. ROI ratings can be utilized to prioritize the implementation of energy savings measures.

Table 4.1-1 D.D. Eisenhower Middle School Lighting System Improvements

Option 1 Option 2

Retrofit Cost (Material and Labor) $27,150 $65,024

New Jersey SmartStart Rebate -$4,705 -$4,705

Total Cost $22,445 $60,319

Annual Energy Savings $7,805 $18,394

Simple Payback 2.8 years 3.2 years

Return on Investment (ROI) 35% 30%

Page 52: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-3

4.1.2 J.J. Catena Elementary School The existing lighting system at the J.J. Catena Elementary School consists of linear fluorescent, compact fluorescent, metal halide and incandescent fixtures. All of the linear fluorescent fixtures have energy efficient T-8 lamps with electronic ballasts, as discussed in Section 2.2.3. It is recommended that the small number of existing inefficient incandescent fixtures be replaced. In addition, it is recommended that the current indoor Metal Halide HID fixtures be replaced with T5 linear fluorescent fixtures for an increase in quality of light, light output, a decrease in energy consumption, and the ability to have instant on/instant off capabilities and that occupancy sensors be installed in select locations.

In general, the first strategy (Option 1) for a lighting upgrade project, involves replacing exit signs that utilize incandescent lamps with new LED exit signs, relamping and the installation of occupancy sensors. Please refer to Appendix D, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 1.

With the implementation of Option 1, the annual energy savings are estimated to be 5.45 kW, 36,826 kWh and $6,039. In addition, the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

In general, the second strategy (Option 2) for a lighting upgrade project is a more comprehensive project that involves replacing the existing 32-watt T8 lamps with new 28-watt T8 lamps, in addition to the recommendations of Option 1. Please refer to Appendix E, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 2.

With the implementation of Option 2, the annual energy savings are estimated to be 26.97 kW, 70,800 kWH and $11,611. In addition the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts. The following table, Table 4.1-2, summarizes a simple payback analysis for both lighting system improvement strategies at the J.J. Catena Elementary School.

Table 4.1-2

J.J. Catena Elementary School Lighting System Improvements Option 1 Option 2

Retrofit Cost (Material and Labor) $19,687 $44,215 New Jersey SmartStart Rebate -$3,115 -$3,115 Total Cost $16,572 $41,100 Annual Energy Savings $6,039 $11,611 Simple Payback 2.7 years 3.5 years Return on Investment (ROI) 36% 28%

Page 53: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-4

4.1.3 C.T. Barkalow Middle School The existing lighting system at the C.T. Barkalow Middle School consists of linear fluorescent, compact fluorescent, metal halide, high pressure sodium and incandescent fixtures. All of the linear fluorescent fixtures have energy efficient T-8 lamps with electronic ballasts, as discussed in Section 2.3.3. It is recommended that the small number of existing inefficient incandescent fixtures be replaced. In addition, it is recommended that the current indoor Metal Halide HID fixtures be replaced with T5 linear fluorescent fixtures for an increase in quality of light, light output, a decrease in energy consumption, and the ability to have instant on/instant off capabilities.

In general, the first strategy (Option 1) for a lighting upgrade project involves relamping, installing energy-efficient lighting retrofit kits and electronic ballasts. Please refer to Appendix D, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 1.

With the implementation of Option 1, the annual energy savings are estimated to be 14.64 kW, 35,575 kWh and $5,763. In addition, the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

In general, the second strategy (Option 2) for a lighting upgrade project is a more comprehensive project that involves replacing the existing 32-watt T8 lamps with new 28-watt T8 lamps, in addition to the recommendations of Option 1. Please refer to Appendix E, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 2.

With the implementation of Option 2, the annual energy savings are estimated to be 38.72 kW, 81,804 kWH and $13,252. In addition the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

The following table, Table 4.1-3, summarizes a simple payback analysis for both lighting system improvement strategies at the C.T. Barkalow Middle School.

Table 4.1-3 C.T. Barkalow Middle School Lighting System Improvements

Option 1 Option 2

Retrofit Cost (Material and Labor) $44,291 $74,570 New Jersey SmartStart Rebate -$4,080 -$4,080 Total Cost $40,211 $70,490 Annual Energy Savings $5,763 $13,252 Simple Payback 7.0 years 5.3 years Return on Investment (ROI) 14% 19%

Page 54: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-5

4.1.4 Early Childhood Learning Center The existing lighting system at the Early Childhood Learning Center consists of linear fluorescent, compact fluorescent, metal halide, high pressure sodium and incandescent fixtures. All of the linear fluorescent fixtures have energy efficient T-8 lamps with electronic ballasts, as discussed in Section 2.4.3. It is recommended that the small number of existing inefficient incandescent fixtures be replaced. In addition, it is recommended that the current indoor Metal Halide HID fixtures be replaced with T5 linear fluorescent fixtures for an increase in quality of light, light output, a decrease in energy consumption, and the ability to have instant on/instant off capabilities and the installation of occupancy sensors.

In general, the first strategy (Option 1) for a lighting upgrade project involves relamping, installing energy-efficient lighting retrofit kits and the installation of occupancy sensors in select locations. Please refer to Appendix D, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 1.

With the implementation of Option 1, the annual energy savings are estimated to be 5.84 kW, 14,933 kWh and $2,431. In addition, the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

In general, the second strategy (Option 2) for a lighting upgrade project is a more comprehensive project that involves replacing the existing 32-watt T8 lamps with new 28-watt T8 lamps, in addition to the recommendations of Option 1. Please refer to Appendix E, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 2.

With the implementation of Option 2, the annual energy savings are estimated to be 18.48 kW, 39,497 kWH and $6,430. In addition the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

The following table, Table 4.1-4, summarizes a simple payback analysis for both lighting system improvement strategies at the Early Childhood Learning Center.

Page 55: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-6

Table 4.1-4 Early Childhood Learning Center Lighting System Improvements Option 1 Option 2

Retrofit Cost (Material and Labor) $10,893 $23,410

New Jersey SmartStart Rebate -$1,480 -$1,480

Total Cost $9,413 $21,930

Annual Energy Savings $2,431 $6,430

Simple Payback 3.9 years 3.4 years

Return on Investment (ROI) 26% 29%

4.1.5 M.W. Errickson Elementary School The existing lighting system at the M.W. Errickson Elementary School consists of linear fluorescent, compact fluorescent, metal halide and incandescent fixtures. All of the linear fluorescent fixtures have energy efficient T-8 lamps with electronic ballasts, as discussed in Section 2.5.3. It is recommended that the small number of existing inefficient incandescent fixtures be replaced and that occupancy sensors be installed in select locations.

In general, the first strategy (Option 1) for a lighting upgrade project involves relamping, installing energy-efficient lighting retrofit kits, electronic ballasts and the installation of occupancy sensors in select locations. Please refer to Appendix D, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 1.

With the implementation of Option 1, the annual energy savings are estimated to be 13.91 kW, 26,451 kWh and $4,401. In addition, the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

In general, the second strategy (Option 2) for a lighting upgrade project is a more comprehensive project that involves replacing the existing 32-watt T8 lamps with new 28-watt T8 lamps, in addition to the recommendations of Option 1. Please refer to Appendix E, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 2.

With the implementation of Option 2, the annual energy savings are estimated to be 20.99 kW, 45,917 kWH and $7,640. In addition the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

Page 56: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-7

The following table, Table 4.1-5, summarizes a simple payback analysis for both lighting system improvement strategies at the M.W. Errickson Elementary School.

Table 4.1-5 M.W. Errickson Elementary School Lighting System

Improvements Option 1 Option 2

Retrofit Cost (Material and Labor) $55,102 $89,157

New Jersey SmartStart Rebate -$510 -$510

Total Cost $54,592 $88,647

Annual Energy Savings $4,401 $7,640

Simple Payback 12.4 years 11.6 years

Return on Investment (ROI) 8% 8.6%

4.1.6 Laura Donovan Elementary School The existing lighting system at the Laura Donovan Elementary School consists of linear fluorescent, compact fluorescent, metal halide, high pressure sodium and incandescent fixtures. All of the linear fluorescent fixtures have energy efficient T-8 lamps with electronic ballasts, as discussed in Section 2.6.3. It is recommended that the small number of existing inefficient incandescent fixtures be replaced. In addition, it is recommended that the current indoor Metal Halide HID fixtures be replaced with T5 linear fluorescent fixtures for an increase in quality of light, light output, a decrease in energy consumption, and the ability to have instant on/instant off capabilities and that occupancy sensors be installed in select locations.

In general, the first strategy (Option 1) for a lighting upgrade project involves relamping, installing electronic ballasts, replacing exit signs that utilize incandescent lamps with new LED exit signs and the installation of occupancy sensors. Please refer to Appendix D, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 1.

With the implementation of Option 1, the annual energy savings are estimated to be 7.15 kW, 30,789 kWh and $5,218. In addition, the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

In general, the second strategy (Option 2) for a lighting upgrade project is a more comprehensive project that involves replacing the existing 32-watt T8 lamps with new 28-watt T8 lamps, in addition to the recommendations of Option 1. Please refer to

Page 57: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-8

Appendix E, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 2.

With the implementation of Option 2, the annual energy savings are estimated to be 29.07 kW, 69,964 kWH and $11,858. In addition the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

The following table, Table 4.1-6, summarizes a simple payback analysis for both lighting system improvement strategies at the Laura Donovan Elementary School.

Table 4.1-6 Laura Donovan Elementary School Lighting System

Improvements Option 1 Option 2

Retrofit Cost (Material and Labor) $19,966 $43,542

New Jersey SmartStart Rebate -$3,155 -$3,155

Total Cost $16,811 $40,387

Annual Energy Savings $5,218 $11,858

Simple Payback 3.2 years 3.7 years

Return on Investment (ROI) 31% 27%

4.1.7 West Freehold Elementary School The existing lighting system at the West Freehold Elementary School consists of linear fluorescent, compact fluorescent, metal halide and incandescent fixtures. All of the linear fluorescent fixtures have energy efficient T-8 lamps with electronic ballasts, as discussed in Section 2.7.3. It is recommended that occupancy sensors be installed in select locations.

In general, the first strategy (Option 1) for a lighting upgrade project involves the installation of occupancy sensors in select locations. Please refer to Appendix D, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 1.

With the implementation of Option 1, the annual energy savings are estimated to be 10,714 kWh and $1,705.

In general, the second strategy (Option 2) for a lighting upgrade project is a more comprehensive project that involves replacing the existing 32-watt T8 lamps with new 28-watt T8 lamps, in addition to the recommendations for occupancy sensors

Page 58: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-9

presented in Option 1. Please refer to Appendix E, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 2.

With the implementation of Option 2, the annual energy savings are estimated to be 31.97 kW, 76,535 kWH and $12,184.

The following table, Table 4.1-7, summarizes a simple payback analysis for both lighting system improvement strategies at the West Freehold Elementary School.

Table 4.1-7 West Freehold Elementary School Lighting System Improvements Option 1 Option 2

Retrofit Cost (Material and Labor) $7,912 $42,447

New Jersey SmartStart Rebate -$825 -$825

Total Cost $7,087 $41,622

Annual Energy Savings $1,705 $12,184

Simple Payback 4.2 years 3.4 years

Return on Investment (ROI) 24% 29%

4.1.8 C.R. Applegate Elementary School The existing lighting system at the C.R. Applegate Elementary School consists of linear fluorescent, compact fluorescent, metal halide and incandescent fixtures. All of the linear fluorescent fixtures have energy efficient T-8 lamps with electronic ballasts, as discussed in Section 2.8.3. It is recommended that the small number of inefficient incandescent fixtures be replaced, that the Metal Halide fixtures be replaced with T5 linear fluorescent fixtures and that occupancy sensors be installed in select locations.

In general, the first strategy (Option 1) for a lighting upgrade project involves relamping, installing energy-efficient lighting retrofit kits, electronic ballasts, replacing exit signs that utilize incandescent lamps with new LED exit signs and the installation of occupancy sensors. Please refer to Appendix D, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 1.

With the implementation of Option 1, the annual energy savings are estimated to be 8.38 kW, 33,873 kWh and $5,575. In addition, the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

In general, the second strategy (Option 2) for a lighting upgrade project is a more comprehensive project that involves replacing the existing 32-watt T8 lamps with new

Page 59: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-10

28-watt T8 lamps, in addition to the recommendations for occupancy sensors presented in Option 1. Please refer to Appendix E, for Lighting Retrofit Spreadsheet with the line-by-line proposed detailed lighting upgrades under Option 2.

With the implementation of Option 2, the annual energy savings are estimated to be 29.76 kW, 72,321 kWH and $11.904. In addition, the project will generate annual maintenance savings from avoided costs related to changing lamps and ballasts.

The following table, Table 4.1-8, summarizes a simple payback analysis for both lighting system improvement strategies at the C.R. Applegate Elementary School.

Table 4.1-8 C.R. Applegate Elementary School Lighting System

Improvements Option 1 Option 2

Retrofit Cost (Material and Labor) $20,276 $45,380

New Jersey SmartStart Rebate -$2,045 -$2,045

Total Cost $18,231 $43,335

Annual Energy Savings $5,575 $11,904

Simple Payback 3.3 years 3.6 years

Return on Investment (ROI) 31% 27%

4.2 HVAC The goal of this section is to present any heating and cooling energy reduction and cost saving measures that may also be cost beneficial. Where possible, measures will be presented with a life-cycle cost analysis. This analysis displays a payback period based on weighing the capital cost of the measure against predicted annual fiscal savings. To do this, the buildings have been modeled as accurately as possible to predict energy usage for space heating and cooling, as well as domestic hot water use.

Each building is modeled using software called eQuest, a Department of Energy-sponsored energy modeling program, to establish a baseline space heating and cooling energy usage. Climate data from Freehold, NJ was used for analysis. Models are created to reflect the existing building and HVAC systems as accurately as possible based on data gathered during the audit. They are then calibrated to match, as closely as possible, the total annual energy usage for one year based on utility bills. Once the baseline model is established, particular components of the HVAC system or envelope may be changed in order to predict energy savings from potential energy reduction measures. Refer to Appendix C for model run summaries.

Page 60: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-11

Once annual energy savings from a particular measure have been predicted and the initial capital cost has been estimated, a payback period may be approximated. Equipment cost estimate calculations are provided in Appendix H.

4.2.1 D.D. Eisenhower Middle School A model of the D.D. Eisenhower Middle School was created in eQuest to predict heating and cooling loads for the building. For the D.D. Eisenhower School, CDM received utility bills dated from February, 2008 through February, 2009.

Figure 4.2-1 compares the model-predicted natural gas usage with actual natural gas usage from February, 2008 through January, 2009.

Figure 4.2-1: D.D. Eisenhower Middle School Natural Gas Usage

The total annual predicted gas usage presented in Figure 4.2-1 was fairly close to the actual 2008-2009 gas usage. It becomes evident, however, that monthly usages during the first half of the year were quite a bit lower than predicted and monthly energy usages during the fall were higher than predicted. This trend was apparent in several models, indicating that perhaps the first half of 2008 was a bit warmer than normal, while the second half may have been cooler.

As the majority of the school is heated via electricity, the primary use of natural gas in the D.D. Eisenhower School is to heat the newer 2003 wing. Because this wing incorporates a newer HVAC system with high-efficiency boilers, CDM finds no energy savings measures related to gas-fired HVAC equipment in this school.

Page 61: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-12

Figure 4.2-2 compares the model-predicted electricity usage with actual electricity usage, from February 2008 through January 2009.

Figure 4.2-2: D.D. Eisenhower Middle School Electricity Usage

It should be noted that the electricity usage predicted in Figure 4.2-2 represents all building electricity use, not just heating and cooling. To understand the impact energy savings measures will have on electricity usage, this chart must first be broken into categories. Based on information gathered about the building and HVAC system, eQuest can predict how much electricity is being used for what task (lighting, plug loads, heating, etc.). In Figure 4.2-3, an expected breakdown of electricity usage into such categories has been displayed. This categorical breakdown is based only on information available to CDM at the time of this audit, and should therefore be interpreted as an approximate, not exact, breakdown of electricity usage.

Page 62: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-13

Figure 4.2-3: D.D. Eisenhower Middle School Predicted Electricity Usage Breakdown

CDM did not find any significant HVAC-related energy savings measures at the D.D. Eisenhower School.

Over several decades, ASHRAE has compiled data pertaining to service lives of most HVAC related equipment. From this, ASHRAE indicates a median service life (life until replacement) for HVAC related equipment that may be used as an estimate for the useful life of HVAC equipment currently in service. For example, ASHRAE indicates a window air conditioning unit has a median service life of 10 years. Therefore, if a window unit has been in service for more than 10 years, the owner may want to consider replacement. Not only will a replacement ensure minimal downtime between units (the unit is replaced before it ceases to function), but it will also maintain rated system efficiency, as efficiency tends to decrease with age.

All major equipment noted during CDM’s on site audit is listed in Table 4.2-1 below, along with estimated current ages and ASHRAE-expected service lives. It should be noted that only equipment that was observed at the time of the audit is included. Where equipment ages were not found on the equipment tags, they have been estimated based on the unit appearance.

Page 63: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-14

Table 4.2-1 Eisenhower Middle School HVAC Equipment Service Lives

Description Service Location

Manufacturer Model Estimated Age

(Years)

ASHRAE Expected

Life (Years)

Rooftop Unit 

524  Trane  TCD048C40C  11  15 

Rooftop Unit 

Cafeteria  Trane  TEH480A4DDOB2HH1AH  11  15 

Rooftop Unit 

Guidance   Trane  TCD036C40CBC  11  15 

Rooftop Unit 

Work Room  Trane  TCD036C40CBC  11  15 

Rooftop Unit 

Gym  Aaon  RK‐16‐3‐EO‐000:H00JCA000SOB  >20  15 

Boiler  03 Wing  Aerco  KC  6  25 

Boiler  03 Wing  Aerco  KC  6  25 

4.2.2 J.J. Catena Elementary School A model of the J.J. Catena Elementary School was created in eQuest.

Figure 4.2-4 compares the model-predicted natural gas usage with actual natural gas usage between February, 2008 and January, 2009.

Page 64: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-15

Figure 4.2-4: J.J. Catena Elementary School Natural Gas Usage

CDM finds that the boiler serving the hot water system in the original building can be upgraded to a high-efficiency condensing boiler. With a high-efficiency condensing boiler, the hot water loop temperature may be decreased from approximately 180F to 100F, resulting in even lower energy usage.

Figure 4.2-5 compares current gas usage with predicted gas usage after upgrading to a high-efficiency condensing boiler. Fiscal savings from such an upgrade are then identified in Table 4.2-2 below.

Page 65: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-16

Figure 4.2-5: J.J. Catena Elementary School Natural Gas Usage – Boiler Upgrade

Table 4.2-2: JJ Catena - Boiler Upgrade Payback

Predicted Annual Savings (Therms) 6,100

Total Annual Savings $7,625

Initial Capital Cost of Upgrade $114,281

Incentives $0

Cost of Upgrade $114,281

Simple Payback 15.0

Figure 4.2-6 displays model-predicted electricity usage compared with actual electricity usage from February 2008 through January 2009.

Page 66: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-17

Figure 4.2-6: J.J. Catena Elementary School Electricity Usage

This predicted electrical usage may now be broken into major usage categories in Figure 4.2-7.

Figure 4.2-7: J.J. Catena Elementary School Predicted Electricity Usage Breakdown

Page 67: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-18

During the site visit, CDM was informed that several of the rooftop units in the JJ Catena School operate 24 hours a day, 7 days a week. Installation of programmable thermostats with night setbacks for each unit would ensure that these units are not operating at full capacity when the building is unoccupied at night. This will also lessen the burden on the fans within the units, resulting in less electricity use and longer unit life. Energy and fiscal savings from such a measure are presented in Table 4.2-3.

Table 4.2-3: JJ Catena – Air Handler Control Change Payback

Predicted Annual Savings (Therms) 4,917

Corresponding Fiscal Savings $6,146

Predicted Annual Savings (kWh) 31,300

Corresponding Fiscal Savings $5,133

Total Annual Savings $11,279

Initial Capital Cost of Upgrade $2,245

Incentives $0

Cost of Upgrade $2,245

Simple Payback 0.2

Table 4.2-3 above predicts savings from incorporating night setbacks into the gas-fired rooftop units servings rooms 231, 232, 234, 236, 238, 240, 242, 244, the faculty room, the gymnasium, and the cafeteria.

All major equipment noted during CDM’s on site audit is listed in Table 4.2-4 below, along with estimated current ages and ASHRAE-expected service lives. Again, it should be noted that only equipment that was observed at the time of the audit is included.

Page 68: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-19

Table 4.2-4 JJ Catena Elementary HVAC Equipment Service Lives

Description Service Location

Manufacturer Model Estimated Age

(Years)

ASHRAE Expected

Life (Years)

Rooftop Unit 

214A, 216A  Lennox  CHA16‐048‐1Y 

<15  15 

Rooftop Unit 216  Lennox  CHA16‐024‐1P 

<15  15 

Rooftop Unit 214  Lennox  CHA16‐030‐1P 

<15  15 

Rooftop Unit Offices  Trane  TCD075C40CBC 

10  15 

Rooftop Unit Library  Trane  TCH180B40BEA 

10  15 

Rooftop Unit 209  Trane  TCD075C40GBC 

10  15 

Rooftop Unit Gym Trane GRBA70GFBB0L1GU305MONPW

10 15

Rooftop Unit Cafeteria Trane YCH480A4HD2B2JH1AFH

10 15

Rooftop Unit CST Trane TCC024F100BD

10 15

Rooftop Unit

Comp Room Trane TCH120C40FAB

10 15

Rooftop Unit 227 Trane TCC024F100BD

10 15

Rooftop Unit Art Rm Trane TCD075C40GBC

10 15

Rooftop Unit Art Rm Trane TCD075C40GBC

10 15

Rooftop Unit 204 Trane TCD075C40GBC

10 15

Rooftop Unit 244 Trane YCC060F4MOBF

10 15

Rooftop Unit 242 Trane YCC060F4MOBF

10 15

Rooftop Unit 238 Trane YCC060F4MOBF

10 15

Rooftop Unit 234 Trane YCC060F4MOBF

10 15

Rooftop Unit 231 Trane YCC060F4MOBF

10 15

Rooftop Unit 240 Trane YCC060F4MOBF

10 15

Rooftop Unit 236 Trane YCC060F4MOBF

10 15

Page 69: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-20

Table 4.2-4 JJ Catena Elementary HVAC Equipment Service Lives

Rooftop Unit 232 Trane YCC060F4MOBF

10 15

Rooftop Unit

Faculty Room Trane YCC060F4MOBF

10 15

Boiler Main Building HB Smith 3743-H

30 35

Boiler 04 Wing Aerco KC 5 25

4.2.3 C.T. Barkalow Middle School A model of the C.T. Barkalow Middle School was created in eQuest.

Figure 4.2-8 compares the model-predicted natural gas usage with actual natural gas usage during 2008.

Figure 4.2-8: C.T. Barkalow Middle School Natural Gas Usage

CDM finds that the boiler serving the hot water system in the original building can be upgraded to a high-efficiency condensing boiler. Again, with such an upgrade, the hot water loop temperature may be decreased to 100F, resulting in even lower energy usage.

Page 70: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-21

Figure 4.2-9 compares current gas usage with predicted gas usage after upgrading to a high-efficiency condensing boiler. Fiscal savings from such an upgrade are then identified in Table 4.2-3 below.

Figure 4.2-9: C.T. Barkalow Middle School Predicted Natural Gas Usage

Table 4.2-5: C.T. Barkalow Boiler Upgrade Payback

Predicted Annual Savings (Therms) 6,900

Total Annual Savings $8,556

Initial Capital Cost of Upgrade $114,281

Incentives $0

Cost of Upgrade $114,281

Simple Payback 13.4

Figure 4.2-10 displays model-predicted electricity usage compared with actual electricity usage during 2008.

Page 71: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-22

Figure 4.2-10: C.T. Barkalow Middle School Electricity Usage

This predicted electrical usage may now be broken into major usage categories in Figure 4.2-11.

Page 72: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-23

Figure 4.2-11: C.T. Barkalow Middle School Predicted Electricity Usage Breakdown

Again, information presented in Figure 4.2-11 is for information purposes, as CDM finds no cost-effective HVAC-related recommendations to decrease electricity usage at this school.

All major equipment noted during CDM’s on site audit is listed in Table 4.2-6 below, along with estimated current ages and ASHRAE-expected service lives. Again, it should be noted that only equipment that was observed at the time of the audit is included.

Page 73: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-24

Table 4.2-6 C.T. Barkalow Middle School HVAC Equipment Service Lives

Description Area Served

Manufacturer Model Estimated Age

(Years)

ASHRAE Expected

Life (Years)

Rooftop Unit

Gym Aaon RK‐16‐EO‐000:H00JCA00000MOX  <15 15

Rooftop Unit

2003 Wing McQuay RPS040CCY  6 15

Rooftop Unit

360 Trane YCD048C3LABF 11 15

Rooftop Unit

361 Trane YCD048C3LABF  11 15

Rooftop Unit

362 Trane YCD048C3LABF  11 15

Rooftop Unit

363 Trane YCD075C3LABE 11 15

Rooftop Unit

364 Trane YCD048C3LABF 11 15

Rooftop Unit

366 Trane YCD048C3LABF 11 15

Rooftop Unit

367 Trane YCD075C3LABE  11 15

Rooftop Unit

368 Trane YCD048C4HABF 11 15

Rooftop Unit

Cafeteria Trane Intellipak SFHFC504PR79C36D1011DKRTUY <15 15

Rooftop Unit

Music Room

Trane TCD048C40ABD <15 15

Rooftop Unit

Nurse’s Office

Trane TCD060C40ABD <15 15

Boiler Main Building

HB Smith 4087 H 40 35

Boiler Main Building

HB Smith 4087 H 40 35

Boiler 2003 Wing Aerco KC 6 25 Boiler 2003 Wing Aerco KC 6 25

Page 74: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-25

4.2.4 Early Childhood Learning Center A model of the Early Childhood Learning Center was created in eQuest.

Figure 4.2-12 compares the model-predicted natural gas usage with actual natural gas usage from February, 2008 through January, 2009.

Figure 4.2-12: Early Childhood Learning Center Natural Gas Usage

CDM noted very little insulation on the attic floor of this building. The addition of R-21 batting insulation at the attic floor could provide significant energy savings, as less heat will be lost through the ceilings. Table 4.2-7 provides a payback estimate for adding insulation at the attic floor of the entire building.

Table 4.2-7: ECLC – Insulation at Attic Floor Payback

Predicted Annual Savings (Therms-Heating) 2,454

Corresponding Fiscal Savings $3,043

Initial Capital Cost of Upgrade $39,525

Incentives $0

Cost of Upgrade $39,525

Simple Payback 13.0

Page 75: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-26

Figure 4.2-13 compares the model-predicted electricity usage with actual electricity usage, from February, 2008 through January, 2009.

Figure 4.2-13: Early Childhood Learning Center Electricity Usage

This predicted electrical usage may now be broken into major usage categories in Figure 4.2-14.

Page 76: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-27

Figure 4.2-14: Early Childhood Learning Center Predicted Electricity Usage Breakdown

Again, Figure 4.2-14 is presented for information purposes. CDM finds no cost-effective HVAC-related recommendations to decrease electricity usage at this school.

All major equipment noted during CDM’s on site audit is listed in Table 4.2-8 below, along with estimated current ages and ASHRAE-expected service lives. Again, it should be noted that only equipment that was observed at the time of the audit is included.

Page 77: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-28

Table 4.2-8 Early Childhood Learning Center HVAC Equipment Service Lives

Description Service Location

Manufacturer Model Estimated Age

(Years)

ASHRAE Expected

Life (Years)

Attic  Gym  Trane  L‐17 Climate Changer  <15  15 

Rooftop Unit  12A,13,13A,12  Trane  TCD075C30CBC  11  15 

Boiler  Whole Building 

HB Smith  28A‐S‐12  ~30  35 

Boiler  Whole Building 

HB Smith  28A‐S‐12  ~30  35 

4.2.5 M.W. Errickson Elementary School A model of the M.W. Errickson Elementary School was created in eQuest.

Figure 4.2-15 compares the model-predicted natural gas usage with actual natural gas usage between February, 2008 and January, 2009.

Figure 4.2-15: M.W. Errickson Elementary School Natural Gas Usage

It may be seen in Figure 4.2-15 that the gas usage in March was exceedingly high. This is likely the result of calculated, not measured, usages in previous months which are then compensated for during the actual usage measurement in March. Therefore, CDM has calibrated the model based on usage during the rest of the year.

Page 78: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-29

Figure 4.2-16 compares the model-predicted electricity usage with actual electricity usage, from February 2008 through January 2009. It can be seen that the electricity use in February was abnormally high. Again, CDM has calibrated the model based on usage during the rest of the year.

Figure 4.2-16: M.W. Errickson Elementary School Electricity Usage

This predicted electrical usage may now be broken into major usage categories in Figure 4.2-17.

Page 79: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-30

Figure 4.2-17: M.W. Errickson Elementary School Predicted Electricity Usage Breakdown

CDM finds that adding energy recovery ventilators with enthalpy wheels to the Mammoth packaged units serving the Library, 2nd&3rd grade wing, 3rd&4th grade wing, and 1st grade wing would provide significant savings in both electricity and natural gas. Table 4.2-9 indicates approximate savings from the addition of energy recovery ventilators.

Table 4.2-9: MW Errickson – Energy Recovery Ventilators Payback

Predicted Annual Savings (Therms-Heating) 1,200

Corresponding Fiscal Savings $1,608

Predicted Annual Savings (kWh-Cooling) 15,800

Corresponding Fiscal Savings $2,629

Total Annual Savings $4,237

Initial Capital Cost of Upgrade $61,410

Incentives $0

Cost of Upgrade $61,410

Simple Payback 14.5

Page 80: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-31

CDM was told at the time of the audit that the Seasons 4 units serving the cafeteria and 5th grade wing already include heat recovery wheels.

CDM also noted that much of the building still utilizes single pane windows. Replacing these single pane windows with energy efficient double pane windows could be an option worth considering. CDM estimates that approximately 15% of the wall area is glazed, most of which is single pane. Based on this estimate, CDM predicts an annual savings from an upgrade to energy-efficient double pane windows of approximately 5,000 kWh and 300 therms, resulting in a total fiscal savings of $1,234. While this is likely not a 20 year payback, savings are presented for information purposes should the District choose to undertake such an upgrade in the future.

All major equipment noted during CDM’s on site audit is listed in Table 4.2-10 below, along with estimated current ages and ASHRAE-expected service lives. Again, it should be noted that only equipment that was observed at the time of the audit is included.

Table 4.2-10 Errickson Elementary HVAC Equipment Service Lives

Description Service Location

Manufacturer Model Estimated Age

(Years)

ASHRAE Expected

Life (Years)

AHU Library Mammoth DHEBFPC-322-G510-C415-MZ9 11 5

AHU 2nd & 3rd Gr Wing

Mammoth DHEBFPC-322-G510-C415-MZ10 11 15

AHU Café Seasons4 3SJK43-0452-MN6.4-10SE <15 15

AHU 3rd 4th Gr Wing

Mammoth DHEBFPC-322-G510-C415-MZ9 11 15

AHU 1st Gr Wing

Mammoth DHEBFPC-322-G510-C415-MZ9

11 15

AHU 5th Gr Wing

Seasons4 3MJG28-0352-MN6.0-12SE <15 15

Boiler 03 Wing Aerco KC 6 25

Boiler 03 Wing Aerco KC 6 25

Page 81: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-32

4.2.6 Laura Donovan Elementary School A model of the Laura Donovan Elementary School was created in eQuest.

Figure 4.2-18 compares the model-predicted natural gas usage with actual natural gas usage from February, 2008 through January, 2009.

Figure 4.2-18: Laura Donovan Elementary School Natural Gas Usage

Figure 4.2-19 compares the model-predicted electricity usage with actual electricity usage, from February 2008 through January 2009.

Page 82: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-33

Figure 4.2-19: Laura Donovan Elementary School Electricity Usage

This predicted electrical usage may now be broken into major usage categories in Figure 4.2-20.

Page 83: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-34

Figure 4.2-20: Laura Donovan Elementary School Predicted Electricity Usage Breakdown

All major equipment noted during CDM’s on site audit is listed in Table 4.2-11 below, along with estimated current ages and ASHRAE-expected service lives. Again, it should be noted that only equipment that was observed at the time of the audit is included.

Page 84: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-35

Table 4.2-11 Laura Donovan School HVAC Equipment Service Lives

Description Service Location

Manufacturer Model Estimated Age

(Years)

ASHRAE Expected

Life (Years)

Rooftop Unit 403C Trane TCD060C40CBC ~15 15

Rooftop Unit 427, 428 Trane YCD060C4HOBA 16 15 Rooftop Unit 427A &

B/RS Trane YCD060C4HOBA 16 15

Rooftop Unit 430SGC Trane TCD060C40CBC 15 15 Rooftop Unit 429, 428 Trane TCD060C40CBC 15 15 Rooftop Unit GYM Lennox LGC120SH1G <15 15 Rooftop Unit GYM Lennox LGC120SH1G <15 15 Rooftop Unit GYM Lennox LGC120SH1G <15 15 Rooftop Unit GYM Lennox LGC120SH1G <15 15 Rooftop Unit 452 Trane TCC024F100BD 11 15 Rooftop Unit STAGE Lennox LGC210SH1G 10 15 Condenser 403A -- RAC-33A >20 20 Rooftop Unit 404C Trane TCC018F100BD <15 15 Rooftop Unit Media

Center Trane YCD210C4LCBA 11 15

Rooftop Unit 437 Lennox LGA036SS2G <15 15 Rooftop Unit Cafeteria Trane SFHFC504PP45C37D1A01ABDEGRT6 <15 15

4.2.7 West Freehold Elementary School Due to the relatively unique nature of the West Freehold Elementary School HVAC system, CDM was not able to accurately model the school in eQuest. However, it is CDM’s assertion that this system is relatively efficient. CDM has therefore found no energy savings measures that will prove cost-effective.

As this school was constructed in 2004, all equipment is 5 years old or less. Therefore, no equipment should warrant replacement due to age in the near future.

4.2.8 Applegate Elementary School A model of the Applegate Elementary School was created in eQuest.

Figure 4.2-21 compares the model-predicted natural gas usage with actual natural gas usage during 2008.

Page 85: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-36

Figure 4.2-21: Applegate Elementary School Natural Gas Usage

Figure 4.2-22 compares the model-predicted electricity usage with actual electricity usage from 2008.

Figure 4.2-22: Applegate Elementary School Electricity Usage

Page 86: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-37

This predicted electrical usage may now be broken into major usage categories in Figure 4.2-23.

Figure 4.2-23: Applegate Elementary School Predicted Electricity Usage Breakdown

Similarly to the Errickson School, the Applegate Elementary School would likely benefit from the addition of heat recovery wheels to the major air handling systems. Table 4.2-12 indicates a potential enrgy savings from the addition of heat recovery wheels to the units serving the cafeteria, library, the 5th grade wing, and the three “pods”.

Page 87: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-38

Table 4.2-12: Applegate – Energy Recovery Ventilators Payback

Predicted Annual Savings (Therms) 3,055

Corresponding Fiscal Savings $3,972

Predicted Annual Savings (kWh) -5,510

Corresponding Fiscal Savings -$906

Total Annual Savings $3,066

Initial Capital Cost of Upgrade $92,115

Incentives $0

Cost of Upgrade $92,115

Simple Payback 30.0

It can be seen that the addition of energy recovery ventilators may actually increase electrical demand of the system. The addition of a heat recovery wheel to an air system increases the static pressure drop (resistance to airflow) across the system. This must be compensated for by an increased ventilation demand (fans require more power to overcome the increased system pressure). So, while the ERVs will provide electrical energy savings by lowering the space cooling demand, this is offset by the increased ventilation electrical demand. In the Errickson School, the savings realized from space cooling exceeded the additional cost from increased ventilation. As seen in Table 4.2-6, this may not be the case in the Applegate School. Despite this, the ERV will ultimately provide savings by also lessening the burden on the school heating system, lowering the natural gas demand.

Again, CDM noted single pane windows in much of the building. Replacing these single pane windows with energy efficient double pane windows could be an option worth considering. CDM estimates that approximately 15% of the wall area is glazed, most of which is single pane. Based on this estimate, CDM predicts an annual savings of approximately 4,430 kWh and 289 therms, resulting in a total fiscal savings of $1,105. While this is likely not a 20 year payback, savings are presented for information purposes should the District choose to undertake such an upgrade in the future.

All major equipment noted during CDM’s on site audit is listed in Table 4.2-13 below, along with estimated current ages and ASHRAE-expected service lives. Again, it should be noted that only equipment that was observed at the time of the audit is included.

Page 88: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-39

Table 4.2-13 Applegate Elementary HVAC Equipment Service Lives

Description Service Location Manufacturer Model Estimated Age

(Years)

ASHRAE Expected

Life (Years)

Rooftop Unit

10, 11, 18, 31, art 15, media center 13 Petra PPH40

6 15

Rooftop Unit

22 through 29, 1st & 2nd grade pod rooms Petra PPH40

6 15

Rooftop Unit

Special Needs Wing, 44 through 50 Petra PPH40

6 15

AHU Gym Lennox DMS2-G275-560 20 15

AHU Lobby, Main hall, Office, Nurse, 36a, 36, 36d, 37, 44c Lennox DMS2-6275-60

20 15

AHU  Stage, 40  Lennox  DMS2‐G275‐560  20  15 

Rooftop Unit  Cafeteria  Mammoth  20195‐02‐01 

<15  15 

Rooftop Unit

5th Grade Wing, Rooms 64 through 75 Mammoth 20195-01-01

<15 15

Rooftop Unit

4th and 5th grade pod, rooms 1 through 8 Petra PPH40

6 15

Boiler 2003 Wing Aerco KC Series 6 25 Boiler 2003 Wing Aerco KC Series 6 25

4.3 Photovoltaic Solar Energy System Photovoltaic (PV) cells convert energy in sunlight directly into electrical energy through the use of silicon semi conductors, diodes and collection grids. Several PV cells are then linked together in a single frame of module to become a solar panel. PV cells are able to convert the energy from the sun into electricity. The angle of inclination of the PV cells, the amount of sunlight available, the orientation of the panels, the amount of physical space available and the efficiency of the individual panels are all factors that affect the amount of electricity that is generated.

Based on the estimated cumulative total available roof area, calculations determine that the installation of a system at the eight (8) schools will be rated at approximately 974.85 kW (dc) and would generate an annual production of approximately 1,103,332 kWh (ac).

Page 89: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-40

As part of this energy audit, a preliminary engineering feasibility study of the sites outlined above to support solar generation facilities was completed consisting of the following tasks:

a. Site Visit by CDM engineers.

b. Satellite Image Analysis and Conceptual design and layout of the photovoltaic system

c. Design and construction cost estimates

d. Determine a preliminary design for the size and energy production of the solar system.

The total unobstructed available area of each section of the roof with southern exposure was evaluated. It is important to note the following:

1. The ages of the roofs vary greatly, even at specific schools because of additions. Ages are provided in the report where possible. The structural integrity of the roofs was not confirmed during the site visit. The schools may require some degree of roofing work prior to the implementation of a solar system. Both need to be addressed prior to the implementation of a PV system.

2. CDM site visits did identify schools with potential issues related to the existing electric service and the need for certain modifications to accommodate a PV system while being compliant with the National Electrical Code. These sites are noted below with language addressing schools requiring potential electric service modifications as part of the project.

3. In the case of the flat areas, the PV system sizing and kWh production was calculated assuming the installation of a crystalline module facing south direction and tilted approximately 10 degrees. Please note that the kWh production as well as system size may differ based on final panel tilt selected during the RFP and design phase.

4. The aggregate costs per kWh, as summarized in Section 3, was utilized in the economic analysis.

The following is a preliminary study on the feasibility of installing a PV solar system at the eight (8) schools in the Freehold Township School District to generate a portion of the facility’s electricity requirements. The system is designed to offset the electricity purchased from the local utility and not as a backup or emergency source of power.

In order to determine the best location for the installation of the PV solar system, a satellite image analysis and site walkthrough of the school district buildings was performed on May 26th. As per the Scope of Work, only the building roofs were considered for PV installation.

Page 90: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-41

Also, as part of the assessment CDM investigated possible locations for electrical equipment that need to be installed such as combiner boxes, disconnect switches and DC to AC inverters. Consideration was also given to locations of interconnection between the solar system and building’s electrical grid.

4.3.1 D.D. Eisenhower Middle School The school is comprised of three sections that have been added over time as student enrollment has increased. The roofs of the buildings are flat, with the exception of a cupola-type roof over the media center. This area was not considered for solar panels. In identifying suitable areas for solar panel installation, the number of rooftop units and the amount of gas and electrical piping in the area was taken into consideration. There appeared to be little to no shading from adjacent foliage in those areas deemed suitable for a solar installation.

The age of the various roofs is between 5 and 10 years old, depending on the section. Overall, the roofs of all buildings appear to be in good condition. The roofs appear to be of the membrane type (Carlisle EPDM). The structural integrity of each roof section was not confirmed. The overall situation with warranties and structural issues will need to be addressed prior to the implementation of a PV system. Because solar panels have the same useful life as a standard roof, the solar panels should be installed following a roof replacement if deemed necessary based on the ages of the existing roofs and any warranties that may still apply.

Based on the facility walkthrough and satellite image analysis, the estimated total available roof area would allow for the installation of a system rated at approximately 251.33 kW (dc).

Electrical Service The building has a dual-switch enclosure located outside, adjacent to the utility company transformer. The service is rated at 3000 amperes, 480/277 volt three-phase four-wire. This outdoor enclosure consists of the CT (metering section) and two disconnect switches, one rated at 1200 amperes that feeds the newer addition, and one rated at 1600 amperes that feeds the existing building. There is ground-fault protection installed for both switches. Because NEC requirements mandate ground-fault protection on this service, the PV system cannot be connected to the load side of either of the switches. A line-side connection would have to made between the CT section and one of the disconnects. While the back of the switchgear could not be opened during the inspection, it is likely that a line-side connection could be made at the rear of the cubicle and would have to be connected to the line side of the main. This would involve modification of the service to some extent in order to accommodate the interconnection point.

Space limitations in the electrical equipment rooms dictate that the inverters for these arrays would have to be located outside on concrete pads enclosed by a chain-link fence. It is possible that the inverters and primary disconnect switches could be installed adjacent to the existing service entrance switchgear. The inverters would be

Page 91: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-42

housed in NEMA 3R enclosures, and the AC wiring would run from the inverters into the connection point(s) at the switchboards. Any connection points would have to meet NEC and local utility requirements.

4.3.2 J.J. Catena Elementary School The roof of this building has a flat roof with a number of obstructions such as exhaust fans, rooftop HVAC units, and electrical and gas piping. There is a minimal amount of shading on the roof from adjacent foliage that would need to be addressed during the design phase of the project and which should be vetted out upon completion of a shading analysis. The older sections of the roof appear to be built-up while newer sections are of the membrane type. School personnel were unable to state if there are any existing warranties. The structural integrity of the roof was not confirmed although a visual inspection revealed no leaks or major defects. As stated earlier, the issues regarding structure and warranty need to be addressed prior to the implementation of a PV system.

Based on the facility walkthrough and satellite image analysis, the estimated total available roof area would allow for the installation of a system rated at approximately 91.84 kW (dc).

Electrical Service This school is served by a 2,000 ampere, three-phase four-wire 480/277 volt service. There are two sub-main breakers: a 1200 ampere feeding the new MDP in the electrical equipment room, and an 800 ampere circuit breaker that feeds panel DPA. There are no available spaces for a load-side interconnection of the arrays. The interconnection point for the solar arrays will require a modification of the service entrance equipment wherein connections will have to be made between the two circuit breakers and the CT section of the switch board. There is no available space for the inverter to be installed within the electrical equipment room. The inverter would probably need to be installed outside on a concrete pad. The inverter would be housed in a NEMA 3R enclosure. The AC wiring would run from the inverters into the connection point(s) at the switchboard. Any connection points would have to meet NEC and local utility requirements.

4.3.3 C.T. Barkalow Middle School The school is composed of three sections. The center core roof has a great deal of HVAC equipment installed on it. The other areas have less roof-mounted equipment and are good areas for the installation of PV panels. There are various levels reflecting the additions to the building. The roofs are primarily of the membrane type and they all appear to be in good condition. School personnel could not confirm the age of the roof or if there are any existing warranties in place. The structural integrity of the roof areas was not confirmed although a visual inspection revealed no major defects.

Based on the facility walkthrough and satellite image analysis, the estimated total available roof area would allow for the installation of a system rated at approximately 118.72 kW (dc).

Page 92: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-43

Electrical Service The building’s service is rated at 2000 amperes 480/277 volts three-phase, four-wire. There are two sub-main breakers, one rated at 1,200 amperes and one rated at 800 amperes. Both circuit breakers have ground-fault protection. NEC rules will not permit a load-side connection on services with ground-fault protection. Therefore, a line-side connection will have to be made for any proposed PV system. This would involve modification of the service entrance equipment between the CT enclosure and the first circuit breaker (800 ampere) in the enclosure sequence. There is no available space in the electrical equipment room for the inverter(s). The inverter(s) will probably have to be installed outside on a concrete pad. They will be housed in a NEMA 3R enclosure. One possible area for the inverter(s) could be near the outside door leading from the electrical equipment room. There appears to be sufficient space for a concrete pad enclosed by a chain-link fence. The AC output from the inverter(s) would then be run into the electrical equipment room and connected at the building’s service entrance equipment. Any connection points would have to meet NEC and local utility requirements.

4.3.4 Early Childhood Learning Center This building has roofs of different levels. They are a combination of asphalt shingles and built-up. The roof areas appear to be in good condition. There are some HVAC units and exhaust fans installed at various points on the roof. The roof is partially of the wooden truss design and is accessible through the attic hatch. The structural integrity of the roof was not confirmed and a visual inspection revealed no leaks or major defects. It is unknown how old the roof is or if there are any existing warranties in place. These issues, if any, will need to be addressed prior to the implementation of a PV system.

Based on the facility walkthrough and satellite image analysis, the estimated total available roof area would allow for the installation of a system rated at approximately 69.98 kW (dc).

Electrical Service This building’s service is rated at 2000 amperes 120/208 volts three-phase, four-wire. There is no main circuit breaker as permitted under NEC rule 230.71. It would appear that a load-side connection would be permitted as there is no ground-fault protection on this service. There is one space in the main distribution panel that will take up to a 200-ampere circuit breaker. This is adequate for the load that would be generated by the solar equipment. The interconnection point would be made at that spare space. There is no room in the electrical equipment room to place the inverter(s). The inverter(s) would probably have to be installed outside on a concrete pad and housed in a NEMA 3R enclosure. The AC output wiring from the inverter would then be run into the electrical equipment room and connected at the main distribution panel for the building. Any connection points would have to meet NEC and local utility requirements.

Page 93: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-44

4.3.5 M.W. Errickson Elementary School The school has multi-level roofs of various ages. It is uncertain how old the original is, but it is known that one wing was installed in 1999, and the other addition was made in 2004. The roof areas are relatively unobstructed and are of the membrane type except for the 2004 addition, which is composed of asphalt shingles. All of the roof areas appeared to be in good condition. While no verification of the structural integrity of the roofs was made, a visual inspection revealed no leaks or major defects. It is unknown if warranties exist on the 1999 and older additions. These items will need to be addressed prior to the implementation of a PV system.

Based on the facility walkthrough and satellite image analysis, the estimated total available roof area would allow for the installation of a system rated at approximately 105.73 kW (dc).

Electrical Service The building has a 2,500 ampere service at 480/277 volts, three-phase, four-wire. The switchgear has two sub-main switches, one rated at 1,600 amperes, and the other rated at 1,200 amperes. Both are Pringle bolted pressure switches with fuses. There does not appear to be ground-fault protection for either one of these devices. The distribution boards are composed of fusible switch-type disconnects. There are no available spares or spaces to make a PV interconnection. It will be necessary to modify the service switchgear between the CT section and the first 1600-ampere Pringle switch. It is possible that a line-side connection could be made at the rear of the switchgear on the busswork between the CT section and the Pringle switch. This should be determined during the final design phase of the project.

There is no space in the electrical equipment room for the inverter. The inverter would probably have to be installed outside on a concrete pad. The inverter will be housed in a NEMA 3R enclosure. There appears to be adequate spaces around the building to accommodate a concrete pad and chain-link fence for the inverter. The AC output from the inverter would run into the electrical equipment room for connection to the building’s switchgear. Any connection points would have to meet NEC code.

4.3.6 Laura Donovan Elementary School The school is composed of three wings of different ages. The roofs are membrane in some areas and asphalt shingles in the newest addition. The roof on the original section was installed in 1995; another two wings were added in 1999, and a third addition was built in 2004. It is unknown if any warranties are still in place on the ’95 and ’99 roofs. A visual inspection revealed no leaks or major defects on any of the roof areas. The structural integrity of the roof areas was not confirmed. Warranty issues and structural integrity will have to be addressed prior to the implementation of a PV system.

Based on the facility walkthrough and satellite image analysis, the estimated total available roof area would allow for the installation of a system rated at 158.14 kW (dc).

Page 94: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-45

Electrical Service The school has a 2000-ampere service rated at 480/277 volts, three-phase, four-wire. There are three sub-main breakers, one rated at 1200 amperes, one rated at 800 amperes, and one rated at 300 amperes. The 1200-amp-rated breaker has ground-fault protection. The service also has transient voltage surge suppression. The service will require modification in order to accommodate the proposed new PV system. A line-side connection will have to be made. There is the possibility that this could be done in the buss-splice section of the main switchgear, between the CT section and breaker section. This is dependent on available space in that compartment. This should be determined during the final design phase of the project.

There is no space in the electrical equipment room for the inverter(s). The inverter(s) would probably have to be installed outside on a concrete pad. The inverter(s) would be housed in NEMA 3R enclosures and placed on a concrete pad. A possible location could be on the same wall where the utility meter is located. There appears to be sufficient space to accommodate a concrete pad and chain-link fence. The AC output from the inverter(s) would run into the electrical equipment room and connect at some point into the building’s main distribution equipment. Any connection points would have to meet NEC and local utility requirements.

4.3.7 West Freehold Elementary School This school was completed in 2004. There are a number of wings around a “core” section. The pitched wing roofs are primarily asphalt shingles. The center (core) section has a flat membrane type roof that houses the bulk of the HVAC units. There is one roof area that is a slight dome; this is a standing seam metal design. Because the roofs are only 5 years old, it is believed that warranties are still in place. This has to be confirmed. While no study of the structural integrity of any of the roofs was made, there appeared to be no leaks or major defects.

Based on the facility walkthrough and satellite image analysis, the estimated total available roof area would allow for the installation of a system rated at approximately 55.10 kW (dc). This may seem small for such a large building, but it was observed during the site walkthrough that most of the pitched roofs face either north or east, thus making them poor candidates for PV panels.

Electrical Service The service for the school is rated at 2000 amperes, 480/277 volts, three-phase, four-wire. The service has ground-fault protection. As a result, a load-side connection will not be permitted under NEC rules. The service will have to be modified to accept a line-side connection. This work would involve having to relocate the CT section of the switchgear, because the CT section is located between the main circuit breaker and the main distribution panel. Any line-side connection made without this modification

Page 95: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-46

would result in the CTs actually metering the PV system output and applying it to kWh consumption and thus is it would actually be billed by the utility company. There is no space in the electrical equipment room for the inverter. The inverter would probably be installed outside on a concrete pad. The AC output wiring from the inverter would then be run into the electrical equipment room and connected at some point to the main distribution panel for the building. Any connection points would have to meet NEC and local utility requirements.

4.3.8 C.R. Applegate Elementary School The building has a number of levels for the roofs. Actual age of the main section is unknown. However it is known that one wing was added in 1999, and another was added in 2004. The roofs are all of the membrane type and a visual inspection revealed them to be in good condition. The structural integrity of the roof areas was not determined, and no leaks or major defects were found. The issue of warranties and structural integrity will need to be addressed prior to the implementation of a PV system.

Based on the facility walkthrough and satellite image analysis, the estimated total available roof area would allow for the installation of a system rated at approximately 124.10 kW (dc).

Electrical Service The building’s service is rated at 2000 amperes, 480/277 volt, three-phase, four-wire. There is no main circuit breaker, rather there are four fused switches (2-800 ampere, one 600-ampere, and one 200-ampere). There is no ground-fault protection on this service. Under NEC rules, a load side connection would be permitted, however, there is no spare or space to install a switch. It would be necessary to modify the switchgear to accommodate a line-side connection. This would be done between the CT section and the first 800-ampere switch. There is no space in the electrical equipment room to install the inverter(s). The inverter(s) would probably have to be installed outside on concrete pads. The inverter(s) would be housed in NEMA 3R enclosures. The AC output wiring from the inverter(s) would then be run into the electrical equipment room and be connected at the main distribution panel for the building. Any connection points would have to meet NEC and local utility requirements.

Page 96: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-47

4.3.9 Basis for Conceptual Design The proposed Photovoltaic (PV) Power systems outlined above for each school are comprised of the PV arrays, inverter(s), combiner boxes, disconnect switches, and all of the necessary wiring and interconnection equipment. The solar panels will be mounted onto the roof. The array outputs will feed power into the DC to AC inverters. AC outputs will then be connected at each building’s electrical service as outlined above. Pending further engineering analysis of the roofs, it is yet to be determined if the solar arrays will be installed using a self-ballasting system, or roof penetration system, or a combination of both.

The most common roof mounted system is referred to as a (“fixed tilt”) system typically mounted to a metal rack that can be fixed at a specific angle. There are also (“tracking systems”) or movable along one or two axes to follow the position of the sun during the day. For a roof-mounted PV system, tracking systems are very rarely installed and are usually used for ground-mounted systems only, as they require more complex racks and higher maintenance costs. For the “fixed” system, the tilt is determined based on the following factors: geographical location, total targeted kWh production, seasonal electricity requirements and weather conditions such as wind. Ideally, the module tilt for Northern New Jersey should be 25-35 degrees with an azimuth as close as possible to 180 (south).

However, experience has shown that PV systems are typically installed at a tilt of 20 degrees or lower in order to avoid any issues with wind and to maximize total system size.

The type of PV panels and equipment used to mount the system shall be determined based on the wind conditions and structural integrity of the roof determined during the design phase of the project. In general, penetration/tie-down systems, non-penetrating ballasted type systems, or a combination of the two should be considered.

PV System Sizing The installation of a south facing, non-tracking, fixed tilt system for each building was investigated as part of this audit. The total size is estimated at approximately 974.85 kW dc. The calculations were based on a poly-crystalline panel such as Sharp ND-224U (rated at 224 watts dc) utilizing a 10-degree panel tilt. The azimuth ranges from 140 to 220 degrees.

Fixed Tilt System

Page 97: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-48

Calculation of PV System Yield An industry accepted software package, PV Watts, was used to calculate projected annual electrical production of the crystalline silicon PV system in its first year, as summarized in Table 4.3-1. The assumptions CDM used in the calculations were as follows: solar array tilt angle of 10°, array azimuth of 140° to 220° and a de-rate factor of 0.8. The energy savings generated by the installation of approximately 239.24 kW dc of photovoltaic power is estimated to be 277,491 kWh ac.

Table 4.3-1: Electrical Production from the 1st Year of the PV System

Site Number of Solar

Panels

Estimated Installed

Cost

1st

Year kWh

Production

Size (in kW dc)

Annual Energy Savings

Est. Annual SREC

D.D. Eisenhower 1,122 $1,631,500 286,690 251.33 $45,870 $114,676

J.J. Catena 410 $598,000 102,982 91.84 $16,477 $41,193

C.T. Barkalow 530 $773,500 135,138 118.72 $21,622 $54,055

Early Childhood Ctr 312 $455,000 80,936 69.89 $12,950 $32,374

M.W. Errickson 472 $682,500 120,959 105.73 $19,353 $48,384

Laura Donovan 706 $1,027,000 180,108 158.14 $28,817 $72,043

West Freehold 246 $357,500 65,997 55.10 $10,560 $26,399

C.R. Applegate 554 $806,000 130,522 124.10 $20,884 $52,209

Totals 4,352 $6,331,000 1,103,332 974.85 $176,533 $441,333

Please note: construction costs are only estimates based on historic data compiled from similar installations, and engineering opinion. Additional engineering and analysis is required to confirm the condition of the roofs, structural integrity of the roofs, the system type, sizing, costs and savings. Budget costs assume existing roofs are structurally sound, do not need to be replaced, and can accommodate a solar system.

As stated above the estimated installation costs are based on significant experience with the pricing of solar installations in New Jersey, and are intended to provide the District with a realistic budget cost. A typical solar installation can vary in cost from $5.00 - $10.00 per watt depending on size, complexity of the system, labor rates, etc. Approximately 60-70% of that number is material costs while the balance is labor, engineering, etc. Like any installation, certain conditions can affect a price upward or downward. For purposes of this analysis the estimated installation cost does not include any roofing or structural work which may be required to maintain warranties or for additional structural support. CDM has included a budget cost for the solar system installation, which includes soft costs and should cover some electrical modification work.

Page 98: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-49

Electric Generation The most obvious direct benefit of solar systems is that they generate electricity on site and result in reduced utility purchases. The following aggregate electrical rates were utilized in this analysis:

Service Location Aggregate $ / kW-hr D.D. Eisenhower Middle School $0.1626 J.J. Catena Elementary School $0.1640 C.T. Barkalow Middle School $0.1620 Early Childhood Learning Center $0.1628 M.W. Errickson Elementary School $0.1664 Laura Donovan Elementary School $0.1695 West Freehold Elementary School $0.1592 Applegate Elementary School $0.1646

In addition, the current design of solar panels can result in gradual decline of output efficiency. Although many systems show negligible decline after years of operation, this financial analysis assumes a 0.5% annual degradation in electric output.

Solar Renewable Energy Certificates As part of New Jersey’s Renewable Portfolio Standards (RPS), electric suppliers are required to have an annually-increasing percentage of their retail sales generated by solar energy. Electric suppliers fulfill this obligation by purchasing SRECs from the owners of solar generating systems. One SREC is created for every 1,000 kWh (1 MWh) of solar electricity generated. Although solar systems generate electricity and SRECs in tandem, the two are independent commodities and sold separately. The RPS, and creation of SRECs, is intended to provide additional revenue flow and financial support for solar projects in New Jersey.

CDM has assumed what is believed to be a conservative estimate of the market value of SRECs over a 15 year period. Over the first 5 years, CDM has assumed that the SREC value would be at 80% of the NJBPU market forecast. For years 6 through 9, CDM has assumed that the SREC value would be at 75% of the NJBPU market forecast. Finally, for the balance of the term, CDM has assumed that the SREC value would be at a floor of $350 per SREC. CDM believes these values to be conservative compared to recent market transactions. CDM knows of recent transactions in excess of $650 for 1 year, $550 for 4 years and $375 for 12 years. Should the winning developer have contracts in place, or a view of the market that SRECs will exceed CDM’s assumptions; the economics of the project will improve.

In addition, State law now requires that the utility must interconnect and net meter the photovoltaic system provided the system passes the local electrical inspection (National Electric Code) and meets the utility safety requirements as outlined in the law. Net metering is the term given which allows the utility meter to literally “spin backward” when the solar panels are producing more electricity than the building is

Page 99: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 4 Energy Savings Measures

A 4-50

using. However, given the high electrical demand of the facility at most times, this scenario is unlikely to happen.

Financing options and potential financial incentives for Solar Projects are discussed in Section 7.

Page 100: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

A 5-1

Section 5 Evaluation of Energy Purchasing and Procurement Strategies 5.1 Energy Deregulation In 1999, New Jersey State Legislature passed the Electric Discount & Energy Competition Act (EDECA) to restructure the electric power industry in New Jersey. This law, the deregulation of the market, allowed all consumers to shop for their electric supplier. The intent was to create a competitive market for electrical energy supply. As a result, utilities were allowed to charge Cost of Service and customers were given the ability to choose a third party supplier. Energy deregulation in New Jersey increased the energy buyers’ options by separating the function of electricity distribution from that of electricity supply.

Jersey Central Power and Lighting (JCP&L) is currently the generator and supplier of energy for the Freehold School District. JCP&L is one of seven subsidiaries of First Energy Corp., an energy company headquartered in Akron, Ohio. Energy deregulation creates the opportunity to choose your electric generation supplier. The benefit of this is the ability to choose a supplier based on what is important to you, for example, lowest rate or how the electric generation supply is produced.

To sell electric generation service in New Jersey, electric power suppliers must be licensed by the New Jersey Board of Public Utilities (NJ BPU). They must also be registered with the local public utility (JCP&L) to sell electric service in that utility’s service areas. The following suppliers are licensed with the NJ BPU and are registered to sell electric service in the JCP&L service territory:

Amerada Hess Corp

BOC Energy Services

Con Edison Solutions, Inc.

Constellation New Energy, Inc.

Direct Energy, LLC.

First Energy Solutions Corp.

Glacial Energy

Integrys Energy Service

Liberty Power

Pepco Energy Services, Inc.

Page 101: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 5 Evaluation of Energy Purchasing and Procurement Practices

A 5-2

PP&L Energy Plus, LLC.

Reliant Energy Solutions East, LLC.

Sempra Energy Solutions

South Jersey Energy

Strategic Energy LLC

Suez Energy Resources NA, Inc

UGI Energy Services

5.1.1 Alternate Third Party Electrical Energy Supplier In evaluating the potential for an alternative third party supplier, CDM contacted and requested quotes for electric service from Glacial Energy. The objective of which was to get an overall idea of whether or not switching electric energy suppliers is an avenue that the School District should pursue further to obtain electrical energy cost savings.

CDM received a proposal from Glacial Energy for electrical service to the eight (8) school buildings. This proposal is included in Appendix G.

Glacial Energy has proposed a flat rate retail cost per kWH over the next 12 month period for each service location. The following table, Table 5.1-1, summarizes the annual cost savings available based on historical energy consumption rates per location. The retail rates used in this analysis represent the baseline generation rates from the two suppliers and do not include any applicable demand charges, societal benefits charges, transmission charges, energy charges, reconciliation charges, transitional assessment charges or system control charges that were included in the aggregate rates presented in Section 3. These baseline generation rates, are used for comparison purposes to identify any potential cost savings, as all other applicable charges cannot be avoided by switching suppliers.

Page 102: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 5 Evaluation of Energy Purchasing and Procurement Practices

A 5-3

Table 5.1-1: Potential Energy Cost Savings with an Alternate Third Party Supplier – Glacial Energy

Service Location

Historical Annual

Consumption (kWH)

Annual Cost with JCP&L

Proposed Annual Cost with Glacial

Energy

Potential Annual Savings

D.D. Eisenhower MS

1,926,165

$228,712 ($0.11874/ kWH)

$185,451 ($0.09628/kWH)

$43,261

J.J Catena ES 1,034,978

$126,308 ($0.12204/kWH)

$100,186 ($0.09680/kWH)

$26,122

C.T. Barkalow MS

1,454,940 $177,808

($0.12221/kWH) $144,199

($0.09911/kWH) $33,609

ECLC 500,736

$61,250 ($0.12232/kWH)

$49,803 ($0.09946/kWH)

$11,447

M.W. Errickson ES

759,925 $94,116

($0.12385/kWH) $77,497

($0.10198/kWH) $16,619

Laura Donovan ES

1,344,566 $162,087

($0.12055/kWH) $132,829

($0.09879/kWH) $29,258

West Freehold ES

2,398,673 $297,195

($0.12390/kWH) $236,245

($0.09849/kWH) $60,950

Applegate ES 940,879

$119,359 ($0.12686/kWH)

$91,801 ($0.09757/kWH)

$27,558

Total Potential Annual Savings: $248,824

As energy cost savings are available by switching to a third party supplier, such as Glacial Energy, this is a recommended energy cost savings measure. The estimated annual cost savings available by switching all eight (8) services over to Glacial Energy is $248,823. CDM recommends that the Freehold School District investigate this opportunity further and compare proposals from alternate third party suppliers to obtain the lowest electrical energy rates available.

Page 103: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

A 6-1

Section 6 Ranking of Energy Conservation and Retrofit Measures (ECRM) 6.1 ECRMs The main objective of this energy audit is to identify potential Energy Conservation and Retrofit Measures and to determine whether or not the identified ECRM’s are economically feasible to warrant the cost for planning and implementation of each measure. Economic feasibility of each identified measure was evaluated through a simple payback analysis. The simple payback analysis consists of establishing the Engineer’s Opinion of Probable Construction Cost estimates, O&M cost savings estimates, projected annual energy savings estimates and the potential value of New Jersey Clean Energy rebates or Renewable Energy Credits, if applicable. The simple payback period is then determined as the amount of time (years) until the energy savings associated with each measure amounts to the capital investment cost.

As discussed is Section 3, aggregate unit costs for electrical energy delivery and usage and natural gas delivery and usage, which accounts for all demand and tariff charges at each facility, was determined and utilized in the simple payback analyses.

In general, ECRMs having a payback period of 20 years or less have been recommended and only those recommended ECRMs within Section 4 of the report have been ranked for possible implementation. The most attractive rankings are those with the lowest simple payback period.

Ranking of ECRMs has been broken down into the following categories:

Lighting Systems

HVAC Systems

Solar Energy

6.1.1 Lighting Systems Table 6.1-1 includes a ranking of the recommended lighting system retrofits for each of the schools. It is recommended that Option 2 be implemented, which includes the replacement of the existing 32-watt T8 lamps with 28-watt T8 lamps, along with the measures of Option 1: the installation of energy-efficient lighting retrofit kits, electronic ballasts, energy-efficient luminaires and occupancy sensors in select areas. A detailed discussion on building lighting systems is presented in Section 4.1.

Page 104: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 6 Ranking of Energy Conservation and Retrofit Measures (ECRM)

A 6-2

Table 6.1-1 Ranking of Energy Savings Measures Summary – Lighting System Retrofits

Site Retrofit

Cost Incentives Total Cost

Annual Fiscal

Savings

Simple Payback (Years)

D.D. Eisenhower (Option 2) $65,024 -$4,705 $60,319 $18,394 3.2 Early Childhood Learning Center (Option 2) $23,410 -$1,480 $21,930 $6,430 3.4 West Freehold (Option 2) $42,447 -$825 $41,622 $12,184 3.4 J.J. Catena (Option 2) $44,215 -$3115 $41,100 $11,611 3.5 Applegate (Option 2) $45,380 -$2,045 $43,335 $11,904 3.6 Laura Donovan (Option 2) $43,542 -$3,155 $40,387 $11,858 3.7 C.T. Barkalow (Option 2) $74,570 -$4,080 $70,490 $13,252 5.3 M.W. Errickson (Option 2) $89,157 -$510 $88.647 $7,640 11.6

Project Totals $427,745 -$19,915 $93,273 PROJECT

TOTAL $407,830

Although Option 2 is recommended, as the lighting system retrofits included under Option 2 will provide for a more comprehensive project and greater energy savings, it is a more costly capital investment. For comparison purposes, Table 6.1-2 has been provided to rank the lighting system retrofits included under Option 1 for each of the schools.

Table 6.1-2 Ranking of Energy Savings Measures Summary – Lighting System Retrofits

Site Retrofit

Cost Incentives Total Cost

Annual Fiscal

Savings

Simple Payback (Years)

J.J. Catena (Option 1) $19,687 -$3,115 $16,572 $6,039 2.7 D.D. Eisenhower (Option 1) $27,150 -$4,705 $22,445 $7,805 2.8 Laura Donovan (Option 1) $19,966 -$3,115 $16,811 $5,218 3.2 Applegate (Option 1) $20,276 -$2,045 $18,231 $5,575 3.3 Early Childhood Learning Center (Option 2) $10,893 -$1,480 $9,413 $2,431 3.9 West Freehold (Option 1) $7,912 -$825 $7,087 $1,705 4.2 C.T. Barkalow (Option 1) $44,291 -$4,080 $40,211 $5,763 7.0 M.W. Errickson (Option 1) $55,592 -$510 $54,592 $4,401 12.4

Project Totals $205,767 -$19,875 $38,937 PROJECT

TOTAL $185,892

Page 105: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 6 Ranking of Energy Conservation and Retrofit Measures (ECRM)

A 6-3

6.1.2 HVAC Systems Table 6.1-2 includes rankings of all recommended ECRMs to provide energy savings for building HVAC systems, which provide a simple payback of less than 20 years. A detailed discussion on building HVAC systems is presented in Section 4.2.

Table 6.1-3

Ranking of Energy Savings Measures Summary – HVAC System Upgrades

Building & Measure Retrofit

Cost IncentivesTotal Cost

Annual Fiscal

Savings

Simple Payback (Years)

JJ Catena – Air Handler Controls $2,245 $0 $2,245 $11,279 0.2 ECLC – Insulation at Attic Floor $39,525 $0 $39,525 $3,043 13.0 C.T. Barkalow – Boiler Upgrade $114,281 $0 $114,281 $8,556 13.4 MW Errickson - ERVs $61,410 $0 $61,410 $4,237 14.5 JJ Catena – Boiler Upgrade $114,281 $0 $114,281 $7,625 15.0

$331,742 $0 $34,740 PROJECT TOTAL $331,742

6.1.3 Solar Energy Implementation of a new solar energy system has been evaluated to determine the economic feasibility for furnishing and installing such systems for the Freehold Township School District buildings. Based on the simple payback modeling performed, it would benefit the District to further investigate installing the solar energy systems at each of the eight (8) schools. This is primarily based on the initial upfront capital investment required for a solar energy system installation and an acceptable payback period.

Two major factors influencing the project financial evaluation is the variance of the prevailing energy market conditions and Solar Renewable Energy Credit (SREC) rates, with the largest impact to the simple payback model being the SREC credit pricing.

Table 6.1-4, includes a ranking of the solar energy ECRMs for the District’s schools.

Page 106: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 6 Ranking of Energy Conservation and Retrofit Measures (ECRM)

A 6-4

Table 6.1-4

Ranking of Energy Savings Measures – Solar Energy

Building Installation Cost

Annual SREC Credit

Annual Fiscal

Savings

Payback Period (Years)

West Freehold $357,500 $26,399 $10,560 9.7

Early Childhood Learning Center $455,000 $32,374 $12,950 10.0

M.W. Errickson $682,500 $48,384 $19,353 10.1

D.D. Eisenhower $1,631,500 $114,676 $45,870 10.2

Laura Donovan $1,027,000 $72,043 $28,817 10.2

C.T. Barkalow $773,500 $54,055 $21,622 10.2

J.J. Catena $598,000 $41,193 $16,477 10.4

C.R. Applegate $806,000 $52,209 $20,884 11.0

Totals $6,331,000 $441,333 $176,533

It should be noted that Federal and other tax incentives were not included in this simple payback model. Refer to Appendix F for a more detailed solar energy financing model.

Page 107: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

A 7-1

Section 7 Available Grants, Incentives and Funding Sources 7.1 Solar Energy Incentives and Financial Options 7.1.1 Solar Renewable Energy Certificates As part of New Jersey’s Renewable Portfolio Standards (RPS), electric suppliers are required to have an annually-increasing percentage of their retail sales generated by solar energy. Electric suppliers fulfill this obligation by purchasing SRECs from the owners of solar generating systems. One SREC is created for every 1,000 kWh (1 MWh) of solar electricity generated. Although solar systems generate electricity and SRECs in tandem, the two are independent commodities and sold separately. The RPS, and creation of SRECs, is intended to provide additional revenue flow and financial support for solar projects in New Jersey.

We have assumed what we believe to be a conservative estimate of the market value of SRECs over a 15 year period. Over the first 5 years, we have assumed that the SREC value would be at 80% of the NJBPU market forecast. For years 6 through 9, we have assumed that the SREC value would be at 75% of the NJBPU market forecast. Finally, for the balance of the term, we have assumed that the SREC value would be at a floor of $350 per SREC. We believe these values to be conservative compared to recent market transactions. We know of recent transactions in excess of $650 for 1 year, $550 for 4 years and $375 for 12 years. Should the winning developer have contracts in place, or a view of the market that SRECs will exceed our assumptions; the economics of the project will improve.

In addition, State law now requires that the utility must interconnect and net meter your photovoltaic system provided your system passes the local electrical inspection (National Electric Code) and meets the utility safety requirements as outlined in the law. Net metering is the term given which allows your utility meter to literally “spin backward” when the solar panels are producing more electricity than the building is using. However, given the high electrical demand of the facility at most times, this scenario is unlikely to happen.

7.1.2 Financing Options for Solar Projects 1. Direct Purchase by SHSD – under this model, SHSD would fund the project

directly, and receive all of the financial benefits of a PV system directly.

2. Power Purchase Agreement (PPA) – under this model, a private, third party would invest all of the capital necessary to build, own, operate, and maintain the PV system. The third party would claim all of the financial benefits of the project, including federal tax incentives and accelerated depreciation benefits that public sector entities are not entitled to. SHSD would enter into a 15 or 20 year agreement to purchase power from the PV system at a rate guaranteed to be less

Page 108: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 7 Available Grants, Incentives and Funding Sources

A 7-2

than the cost of power from the utility. It should be noted that most PPAs require a minimum system size of approximately 300 kW on one building, so SHSD may not qualify for a PPA unless the system size can be increased.

Additional Potential Financial Incentives: Debt Service Aid - Based on the Education Facilities Construction and Financing Act signed into law in 2000, New Jersey Boards of Education are eligible for 40% debt service aid for eligible improvements to school facilities. It is anticipated that the installation of solar photovoltaic panels will be considered eligible improvements. Under this scenario the SHSD would be required to go to referendum for voter approval to gain access to debt service aid.

Clean Renewable Energy Bonds – The federal government made available $750 Million in federal income tax credit allotments in 2007-08 for local governments to support the installation of green energy generation systems including solar photovoltaic. Such allotments may provide for an interest- free loan for the issuer. The recent energy bill for 2008-09 did not include any provisions for this energy bond. However, industry experts expect some allotments will be included prior to execution of the final plan. Although there is no guarantee that SHSD will be awarded such allotments, we have included the calculation for illustration purposes. If the program is approved for 2008-09 an application will be submitted on behalf of the Somerset Hills Board of Education

7.2 New Jersey Clean Energy Program 7.2.1 Introduction New Jersey's Clean Energy Program (N JCEP) promotes increased energy efficiency and the use of clean, renewable sources of energy including solar, wind, geothermal, and sustainable biomass. The results for New Jersey are a stronger economy, less pollution, lower costs, and reduced demand for electricity. NJCEP offers financial incentives, programs, and services for residential, commercial, and municipal customers.

NJCEP reduces the need to generate electricity and burn natural gas which eliminates the pollution that would have been caused by such electric generation or natural gas usage. The benefits of these programs continue for the life of the measures installed, which on average is about 15 years. Thus, the public receives substantial environmental and public health benefits from programs that also lower energy bills and benefit the economy.

7.2.2 New Jersey Smart Start Program The New Jersey Smart Start Program offers rebate incentives for several qualifying equipment such as high efficient premium motors and lighting, and lighting controls.

Page 109: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Section 7 Available Grants, Incentives and Funding Sources

A 7-3

Incentive information and incentive calculation worksheets are provided for the various new equipment installation identified in this report and are included in Appendix G.

Page 110: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

APPENDIX A

UTILITY BILL INFORMATION

Page 111: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 112: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Acct No. 220008871855 (SJE) Meter ‐ 00726662 (NJNG) Total BTUMonth Year kWh Measured Load (kW)

Feb‐08 2008 244800 701.8 1426.00 142600000 1240Mar‐08 2008 157440 770.2 899.00 89900000 782Apr‐08 2008 151680 459.2 422.00 42200000 367May‐08 2008 126720 388.8 623.00 62300000 542Jun‐08 2008 152960 452.2 355.00 35500000 309Jul‐08 2008 126400 280.3 281.00 28100000 244Aug‐08 2008 114560 295.7 548.00 54800000 477Sep‐08 2008 140480 422.1 971.00 97100000 845Oct‐08 2008 112000 363.8 1161.61 116161000 1010Nov‐08 2008 149440 473.9 1785.14 178514000 1553Dec‐08 2008 226880 636.5 2110.14 211014000 1835Jan‐09 2009 246720 677.8 2222.76 222276000 1933Feb‐09 2009 282560 735.4 1553.47 155347000 1351

Dwight D. Eisenhower School Square Footage: 114,979

Therms

Utility Bill ‐ Dwight D. Eisenhower Middle School

DateElectric Gas

BTU/SqftCustomer No. 0801870439 0000435756 (JCP&L)

Page 113: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Acct No. 143465222172Y (SJE) Meter ‐ 726426 (NJNG) Total BTUMonth Year kWh Measured Load (kW)

Feb‐08 2008 96320 232.6 8235.00 823500000 10829.11434Mar‐08 2008 65600 229.1 6361.00 636100000 8364.784009Apr‐08 2008 88000 246.1 2500.00 250000000 3287.527122May‐08 2008 106240 349.8 1904.00 190400000 2503.780656Jun‐08 2008 89600 351.4 158.00 15800000 207.7717141Jul‐08 2008 85120 365.8 143.00 14300000 188.0465514Aug‐08 2008 75200 233.6 470.00 47000000 618.055099Sep‐08 2008 97280 356.5 971.00 97100000 1276.875534Oct‐08 2008 87690 323.2 4197.29 419729000 5519.481886Nov‐08 2008 78720 223.4 8153.51 815351000 10721.95411Dec‐08 2008 104960 230.1 11074.46 1107446000 14563.03505Jan‐09 2009 69440 256 10398.21 1039821000 13673.75896Feb‐09 2009 102400 238.4 8319.92 831992000 10940.78506

J.J Catena Elementary School Square Footage: 76,045

Therms

Utility Bill ‐ J.J Catena Elementary School

DateElectric Gas

BTU/SqftCustomer No. 0801870439 0000435755 (JCP&L)

Page 114: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Acct No. 093418033524 (SJE) Meter ‐ G20066785 (NJNG) Total BTUMonth Year kWh Measured Load (kW)

Jan‐08 2008 14043.00 1404300000 12705Feb‐08 2008 126240 333.3 10346.00 1034600000 9360Mar‐08 2008 116960 333.4 6410.00 641000000 5799Apr‐08 2008 117920 343.4 4743.00 474300000 4291May‐08 2008 119680 397 1328.00 132800000 1201Jun‐08 2008 190.00 19000000 172Jul‐08 2008 125920 392 358.00 35800000 324Aug‐08 2008 160160 411.4 733.00 73300000 663Sep‐08 2008 145600 572.3 2103.00 210300000 1903Oct‐08 2008 104320 408.8 5153.72 515372000 4663Nov‐08 2008 98080 408.8 13061.99 1306199000 11817Dec‐08 2009 127520 331.5 15977.69 1597769000 14455Jan‐09 2009 108000 334.2 11054.86 1105486000 10001

C.T. Barkalow Middle School Square Footage: 110,533

Therms

Utility Bill ‐ C.T. Barkalow Middle School

DateElectric Gas

BTU/SqftCustomer No. 0801870439 0000658762 (JCP&L)

Page 115: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Acct No. 093420523320 (SJE) Meter ‐ 00850870 (NJNG) Total BTUMonth Year kWh Measured Load (kW)

Feb‐08 2008 43200 109.9 7276.00 727600000 19582Mar‐08 2008 39680 105.6 5859.00 585900000 15769Apr‐08 2008 39520 112.6 3458.00 345800000 9307May‐08 2008 39200 121.4 2670.00 267000000 7186Jun‐08 2008 48160 182.6 457.00 45700000 1230Jul‐08 2008 52000 178.1 47.00 4700000 126Aug‐08 2008 48800 171.7 60.00 6000000 161Sep‐08 2008 48320 174.6 90.00 9000000 242Oct‐08 2008 33280 116.5 2267.00 226700000 6101Nov‐08 2008 35520 101.4 4113.85 411385000 11072Dec‐08 2008 45120 105.1 7988.80 798880000 21501Jan‐09 2009 37760 113.8 9044.93 904493000 24343Feb‐09 2009 55360 113.8 6738.59 673859000 18136

Early Childhood Learning Center Square Footage: 37,156

Therms

Utility Bill ‐ Early Childhood Learning Center

DateElectric Gas

BTU/SqftCustomer No. 0801870439 0000388850 (JCP&L)

Page 116: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Acct No. 033417221021 (SJE) Meter ‐ G28658723 (NJNG) Total BTUMonth Year kWh Measured Load (kW) kWh Measured Load (kW) kWh Measured Load 

Feb‐08 2008 61400 243.2 137680 141.1 25 ‐ 5820.00 582000000 7449Mar‐08 2008 60000 184.4 28960 141.1 20 ‐ 16112.00 1611200000 20622Apr‐08 2008 67600 266.4 29040 112.2 19 ‐ 2826.00 282600000 3617May‐08 2008 74600 266.4 39840 117.7 19 ‐ 2321.00 232100000 2971Jun‐08 2008 97200 312.6 35920 139.3 12 ‐ 335.00 33500000 429Jul‐08 2008 103800 338.8 28320 103.8 10 ‐ 275.00 27500000 352Aug‐08 2008 74000 257.6 29440 109 11 ‐ 135.00 13500000 173Sep‐08 2008 84800 320.2 37200 140.6 12 ‐ 323.00 32300000 413Oct‐08 2008 57600 252.8 31360 133.3 13 ‐ 1648.20 164820000 2110Nov‐08 2008 48200 219.8 30800 106.6 13 ‐ 5781.62 578162000 7400Dec‐08 2008 57200 180.4 33440 85 135 ‐ 8045.77 804577000 10298Jan‐09 2009 48400 338.8 31040 86.9 132 ‐ 10364.47 1036447000 13266Feb‐09 2009 74200 184.4 150 ‐ 6826.49 682649000 8737

M.W. Errickson Elementary School Square Footage: 78,130

Therms

Meter G15112467Customer No. 0801870439 0003180480 (JCP&L)

Utility Bill ‐ M.W. Errickson Elementary School

DateMeter G28658723 Gas

BTU/SqftCustomer No. 0801870439 0000658424 (JCP&L)Meter G98739834

Customer No. 08018704390005355004

Page 117: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Acct No. 023440504222 (SJE) Meter ‐ 00720776 (NJNG) Total BTUMonth Year kWh Measured Load (kW)

Feb‐08 2008 165440 611.2 2783.00 278300000 3638.336536Mar‐08 2008 106560 579.2 4162.00 416200000 5441.163013Apr‐08 2008 102080 422.4 1227.00 122700000 1604.110287May‐08 2008 85760 291.2 652.00 65200000 852.3878626Jun‐08 2008 96640 377.6 164.00 16400000 214.404309Jul‐08 2008 94400 403.2 597.00 59700000 780.4839785Aug‐08 2008 83520 297.6 138.00 13800000 180.413382Sep‐08 2008 87680 364.8 584.00 58400000 763.488515Oct‐08 2008 75840 297.6 612.00 61200000 800.0941287Nov‐08 2008 105600 470.4 1584.82 158482000 2071.903884Dec‐08 2008 159360 553.6 3517.48 351748000 4598.554078Jan‐09 2009 168960 585.6 3799.35 379935000 4967.054948Feb‐09 2009 211840 598.4 3919.98 391998000 5124.759776

Laura Donovan Elementary School Square Footage: 76,491

Therms

Utility Bill ‐ Laura Donovan Elementary School

DateElectric Gas

BTU/SqftCustomer No. 08018704390000474310 (JCP&L)

Page 118: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Acct No. 220009244503 (SJE) Meter ‐ 00720782 (NJNG) Total BTUMonth Year kWh Measured Load (kW)

Feb‐08 2008 240000 594.7 4929.00 492900000 5477Mar‐08 2008 220640 480 3135.00 313500000 3483Apr‐08 2008 235520 571.8 734.00 73400000 816May‐08 2008 136640 412.5 464.00 46400000 516Jun‐08 2008 205280 523.5 26.00 2600000 29Jul‐08 2008 161120 343.4 21.00 2100000 23Aug‐08 2008 150880 343.4 25.00 2500000 28Sep‐08 2008 190240 491.8 148.00 14800000 164Oct‐08 2008 133600 400.3 1711.52 171152000 1902Nov‐08 2008 151520 573.1 9826.96 982696000 10919Dec‐08 2008 207680 538.4 7190.68 719068000 7990Jan‐09 2009 286080 623.8 8968.35 896835000 9965Feb‐09 2009 283360 623.4 5053.26 505326000 5615

West Freehold Elementary School Square Footage: 90,000

Therms

Utility Bill ‐West Freehold Elementary School

DateElectric Gas

BTU/SqftCustomer No. 0801870439 0000658424 (JCP&L)

Page 119: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Acct No. 153428098225 (SJE) Meter ‐ 00500524 (NJNG) Total BTUMonth Year kWh Measured Load (kW)

Jan‐08 2008 87200 275.6 6668.00 666800000 8135Feb‐08 2008 83200 305.2 4816.00 481600000 5876Mar‐08 2008 74000 288 3358.00 335800000 4097Apr‐08 2008 78400 356 1154.00 115400000 1408May‐08 2008 100800 523.6 784.00 78400000 957Jun‐08 2008 63200 478 72.00 7200000 88Jul‐08 2008 80800 496.8 94.00 9400000 115Aug‐08 2008 82000 484 212.00 21200000 259Sep‐08 2008 84000 466 885.00 88500000 1080Oct‐08 2008 75600 358 2703.45 270345000 3298Nov‐08 2008 73600 416 6095.65 609565000 7437Dec‐08 2009 82000 416 8699.50 869950000 10614Jan‐09 2009 81200 275.6 7201.56 720156000 8786

Applegate Elementary School Square Footage: 81,963

ThermsCustomer No. 0801870439 0000389177 (JCP&L)

ElectricUtility Bill ‐ Applegate Elementary School

DateGas

BTU/Sqft

Page 120: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

APPENDIX B

STATEMENT OF ENERGY PERFORMANCE SUMMARY SHEETS

PORTFOLIO MANAGER REFERENCE GUIDE

Page 121: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 122: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

OMB No. 2060-0347

STATEMENT OF ENERGY PERFORMANCEDwight D Eisenhower Middle School

Building ID: 1765904 For 12-month Period Ending: December 31, 20081

Date SEP becomes ineligible: N/A Date SEP Generated: June 25, 2009

FacilityDwight D Eisenhower Middle School279 Burlington RoadFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

Year Built: 1971Gross Floor Area (ft2): 114,979

Energy Performance Rating2 (1-100) 32

Site Energy Use Summary3

Electricity (kBtu) 5,877,222 Natural Gas (kBtu)4 1,101,699 Total Energy (kBtu) 6,978,921

Energy Intensity5 Site (kBtu/ft2/yr) 65 Source (kBtu/ft2/yr) 195 Emissions (based on site energy use) Greenhouse Gas Emissions (MtCO2e/year) 954 Electric Distribution Utility Jersey Central Power & Lt Co National Average Comparison National Average Site EUI 56 National Average Source EUI 167 % Difference from National Average Source EUI 17% Building Type K-12

School

Stamp of Certifying Professional

Based on the conditions observed at thetime of my visit to this building, I certify that

the information contained within thisstatement is accurate.

Meets Industry Standards6 for Indoor EnvironmentalConditions:Ventilation for Acceptable Indoor Air Quality N/A Acceptable Thermal Environmental Conditions N/A Adequate Illumination N/A

Certifying ProfessionalMatthew Goss15 British American Blvd Latham, NY 12110

Notes: 1. Application for the ENERGY STAR must be submitted to EPA within 4 months of the Period Ending date. Award of the ENERGY STAR is not final until approval is received from EPA.2. The EPA Energy Performance Rating is based on total source energy. A rating of 75 is the minimum to be eligible for the ENERGY STAR.3. Values represent energy consumption, annualized to a 12-month period.4. Natural Gas values in units of volume (e.g. cubic feet) are converted to kBtu with adjustments made for elevation based on Facility zip code.5. Values represent energy intensity, annualized to a 12-month period.6. Based on Meeting ASHRAE Standard 62 for ventilation for acceptable indoor air quality, ASHRAE Standard 55 for thermal comfort, and IESNA Lighting Handbook for lighting quality.

The government estimates the average time needed to fill out this form is 6 hours (includes the time for entering energy data, PE facility inspection, and notarizing the SEP) and welcomessuggestions for reducing this level of effort. Send comments (referencing OMB control number) to the Director, Collection Strategies Division, U.S., EPA (2822T), 1200 Pennsylvania Ave., NW,Washington, D.C. 20460.

EPA Form 5900-16

Page 123: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

In order for a building to qualify for the ENERGY STAR, a Professional Engineer (PE) must validate the accuracy of the data underlying the building's energyperformance rating. This checklist is designed to provide an at-a-glance summary of a property's physical and operating characteristics, as well as its total energyconsumption, to assist the PE in double-checking the information that the building owner or operator has entered into Portfolio Manager.

Please complete and sign this checklist and include it with the stamped, signed Statement of Energy Performance.NOTE: You must check each box to indicate that each value is correct, OR include a note.

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Building Name Dwight D Eisenhower

Middle School Is this the official building name to be displayed inthe ENERGY STAR Registry of LabeledBuildings?

Type K-12 School Is this an accurate description of the space inquestion?

Location 279 Burlington Road,Freehold, NJ 07728

Is this address accurate and complete? Correctweather normalization requires an accurate zipcode.

Single Structure Single Facility

Does this SEP represent a single structure? SEPscannot be submitted for multiple-buildingcampuses (with the exception of acute care orchildren's hospitals) nor can they be submitted asrepresenting only a portion of a building

Dwight D Eisenhower Middle School (K-12 School)

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Gross Floor Area 114,979 Sq. Ft.

Does this square footage include all supportingfunctions such as kitchens and break rooms usedby staff, storage areas, administrative areas,elevators, stairwells, atria, vent shafts, etc. Alsonote that existing atriums should only include thebase floor area that it occupies. Interstitial(plenum) space between floors should not beincluded in the total. Finally gross floor area is notthe same as leasable space. Leasable space is asubset of gross floor area.

Open Weekends? Yes

Is this building normally open at all on theweekends? This includes activities beyond thework conducted by maintenance, cleaning, andsecurity personnel. Weekend activity couldinclude any time when the space is used forclasses, performances or other school orcommunity activities. If the building is open on theweekend as part of the standard schedule duringone or more seasons, the building should select?yes? for open weekends. The ?yes? responseshould apply whether the building is open for oneor both of the weekend days.

Number of PCs 337 Is this the number of personal computers in theK12 School?

Number of walk-inrefrigeration/freezer

units 0

Is this the total number of commercial walk-in typefreezers and coolers? These units are typicallyfound in storage and receiving areas.

Presence ofcooking facilities Yes

Does this school have a dedicated space in whichfood is prepared and served to students? If theschool has space in which food for students isonly kept warm and/or served to students, or hasonly a galley that is used by teachers and staffthen the answer is "no".

Percent Cooled 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalcooling equipment?

Percent Heated 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalheating equipment?

Page 1 of 4

Page 124: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Months N/A(Optional) Is this school in operation for at least 8 months ofthe year?

High School? No

Is this building a high school (teaching grades 10,11, and/or 12)? If the building teaches to highschool students at all, the user should check 'yes'to 'high school'. For example, if the school teachesto grades K-12 (elementary/middle and highschool), the user should check 'yes' to 'highschool'.

Page 2 of 4

Page 125: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

Energy ConsumptionPower Generation Plant or Distribution Utility: Jersey Central Power & Lt Co

Fuel Type: Electricity

Meter: G15111588 (kWh)Space(s): Entire Facility

Start Date End Date Energy Use (kWh)

11/30/2008 12/29/2008 226,880.00

10/30/2008 11/29/2008 149,440.00

09/30/2008 10/29/2008 112,000.00

08/30/2008 09/29/2008 140,480.00

07/30/2008 08/29/2008 114,560.00

06/30/2008 07/29/2008 126,400.00

05/30/2008 06/29/2008 152,960.00

04/30/2008 05/29/2008 126,720.00

03/30/2008 04/29/2008 151,680.00

03/01/2008 03/29/2008 157,440.00

01/30/2008 02/29/2008 244,800.00

G15111588 Consumption (kWh) 1,703,360.00

G15111588 Consumption (kBtu) 5,811,864.32

Meter: G98739831 (kWh)Space(s): Entire Facility

Start Date End Date Energy Use (kWh)

11/30/2008 12/29/2008 377.00

10/30/2008 11/29/2008 560.00

09/30/2008 10/29/2008 4.00

08/30/2008 09/29/2008 186.00

07/30/2008 08/29/2008 277.00

06/30/2008 07/29/2008 252.00

05/30/2008 06/29/2008 290.00

04/30/2008 05/29/2008 302.00

03/30/2008 04/29/2008 283.00

03/01/2008 03/29/2008 540.00

01/30/2008 02/29/2008 145.00

G98739831 Consumption (kWh) 3,216.00

G98739831 Consumption (kBtu) 10,972.99

Total Electricity Consumption (kBtu) 5,822,837.31

Page 3 of 4

Page 126: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Is this the total Electricity consumption at this building including all Electricity meters?

Fuel Type: Natural Gas

Meter: 00726662 (therms)Space(s): Entire Facility

Start Date End Date Energy Use (therms)

11/14/2008 12/13/2008 1,785.14

10/14/2008 11/13/2008 1,161.61

09/14/2008 10/13/2008 655.00

08/14/2008 09/13/2008 548.00

07/14/2008 08/13/2008 281.00

06/14/2008 07/13/2008 355.00

05/14/2008 06/13/2008 623.00

04/14/2008 05/13/2008 422.00

03/14/2008 04/13/2008 899.00

02/14/2008 03/13/2008 1,426.00

01/14/2008 02/13/2008 1,636.00

00726662 Consumption (therms) 9,791.75

00726662 Consumption (kBtu) 979,175.00

Total Natural Gas Consumption (kBtu) 979,175.00

Is this the total Natural Gas consumption at this building including all Natural Gas meters?

Additional FuelsDo the fuel consumption totals shown above represent the total energy use of this building?Please confirm there are no additional fuels (district energy, generator fuel oil) used in this facility.

Certifying Professional (When applying for the ENERGY STAR, this must be the same PE that signed and stamped the SEP.)

Name: _____________________________________________ Date: _____________

Signature: ______________________________________ Signature is required when applying for the ENERGY STAR.

Page 4 of 4

Page 127: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

FOR YOUR RECORDS ONLY. DO NOT SUBMIT TO EPA.

Please keep this Facility Summary for your own records; do not submit it to EPA. Only the Statement of Energy Performance(SEP), Data Checklist and Letter of Agreement need to be submitted to EPA when applying for the ENERGY STAR.

FacilityDwight D Eisenhower Middle School279 Burlington RoadFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

General InformationDwight D Eisenhower Middle School

Gross Floor Area Excluding Parking: (ft2) 114,979 Year Built 1971 For 12-month Evaluation Period Ending Date: December 31, 2008

Facility Space Use SummaryDwight D Eisenhower Middle School

Space Type K-12 School

Gross Floor Area(ft2) 114,979

Open Weekends? Yes

Number of PCs 337

Number of walk-in refrigeration/freezerunits 0

Presence of cooking facilities Yes

Percent Cooled 100

Percent Heated 100

Monthso N/A

High School? No

School Districto N/A

Energy Performance ComparisonEvaluation Periods Comparisons

Performance Metrics Current(Ending Date 12/31/2008)

Baseline(Ending Date 12/31/2008) Rating of 75 Target National Average

Energy Performance Rating 32 32 75 N/A 50

Energy Intensity

Site (kBtu/ft2) 65 65 44 N/A 56

Source (kBtu/ft2) 195 195 130 N/A 167

Energy Cost

$/year $ 295,367.39 $ 295,367.39 $ 196,987.02 N/A $ 251,924.35

$/ft2/year $ 2.57 $ 2.57 $ 1.71 N/A $ 2.19

Greenhouse Gas Emissions

MtCO2e/year 954 954 636 N/A 814

kgCO2e/ft2/year 8 8 5 N/A 7

More than 50% of your building is defined as K-12 School. Please note that your rating accounts for all of the spaces listed. The National Average column presentsenergy performance data your building would have if your building had an average rating of 50. Notes:o - This attribute is optional.d - A default value has been supplied by Portfolio Manager.

Page 128: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

OMB No. 2060-0347

STATEMENT OF ENERGY PERFORMANCEJJ Catena Elementary School

Building ID: 1766366 For 12-month Period Ending: December 31, 20081

Date SEP becomes ineligible: N/A Date SEP Generated: June 25, 2009

FacilityJJ Catena Elementary School275 Burlington RoadFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

Year Built: 1961Gross Floor Area (ft2): 76,045

Energy Performance Rating2 (1-100) 19

Site Energy Use Summary3

Electricity (kBtu) 3,341,030 Natural Gas (kBtu)4 6,298,485 Total Energy (kBtu) 9,639,515

Energy Intensity5 Site (kBtu/ft2/yr) 133 Source (kBtu/ft2/yr) 248 Emissions (based on site energy use) Greenhouse Gas Emissions (MtCO2e/year) 844 Electric Distribution Utility Jersey Central Power & Lt Co National Average Comparison National Average Site EUI 98 National Average Source EUI 184 % Difference from National Average Source EUI 35% Building Type K-12

School

Stamp of Certifying Professional

Based on the conditions observed at thetime of my visit to this building, I certify that

the information contained within thisstatement is accurate.

Meets Industry Standards6 for Indoor EnvironmentalConditions:Ventilation for Acceptable Indoor Air Quality N/A Acceptable Thermal Environmental Conditions N/A Adequate Illumination N/A

Certifying ProfessionalMatthew Goss15 British American Blvd Latham, NY 12110

Notes: 1. Application for the ENERGY STAR must be submitted to EPA within 4 months of the Period Ending date. Award of the ENERGY STAR is not final until approval is received from EPA.2. The EPA Energy Performance Rating is based on total source energy. A rating of 75 is the minimum to be eligible for the ENERGY STAR.3. Values represent energy consumption, annualized to a 12-month period.4. Natural Gas values in units of volume (e.g. cubic feet) are converted to kBtu with adjustments made for elevation based on Facility zip code.5. Values represent energy intensity, annualized to a 12-month period.6. Based on Meeting ASHRAE Standard 62 for ventilation for acceptable indoor air quality, ASHRAE Standard 55 for thermal comfort, and IESNA Lighting Handbook for lighting quality.

The government estimates the average time needed to fill out this form is 6 hours (includes the time for entering energy data, PE facility inspection, and notarizing the SEP) and welcomessuggestions for reducing this level of effort. Send comments (referencing OMB control number) to the Director, Collection Strategies Division, U.S., EPA (2822T), 1200 Pennsylvania Ave., NW,Washington, D.C. 20460.

EPA Form 5900-16

Page 129: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

In order for a building to qualify for the ENERGY STAR, a Professional Engineer (PE) must validate the accuracy of the data underlying the building's energyperformance rating. This checklist is designed to provide an at-a-glance summary of a property's physical and operating characteristics, as well as its total energyconsumption, to assist the PE in double-checking the information that the building owner or operator has entered into Portfolio Manager.

Please complete and sign this checklist and include it with the stamped, signed Statement of Energy Performance.NOTE: You must check each box to indicate that each value is correct, OR include a note.

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Building Name JJ Catena Elementary

School Is this the official building name to be displayed inthe ENERGY STAR Registry of LabeledBuildings?

Type K-12 School Is this an accurate description of the space inquestion?

Location 275 Burlington Road,Freehold, NJ 07728

Is this address accurate and complete? Correctweather normalization requires an accurate zipcode.

Single Structure Single Facility

Does this SEP represent a single structure? SEPscannot be submitted for multiple-buildingcampuses (with the exception of acute care orchildren's hospitals) nor can they be submitted asrepresenting only a portion of a building

JJ Catena (K-12 School)

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Gross Floor Area 76,045 Sq. Ft.

Does this square footage include all supportingfunctions such as kitchens and break rooms usedby staff, storage areas, administrative areas,elevators, stairwells, atria, vent shafts, etc. Alsonote that existing atriums should only include thebase floor area that it occupies. Interstitial(plenum) space between floors should not beincluded in the total. Finally gross floor area is notthe same as leasable space. Leasable space is asubset of gross floor area.

Open Weekends? Yes

Is this building normally open at all on theweekends? This includes activities beyond thework conducted by maintenance, cleaning, andsecurity personnel. Weekend activity couldinclude any time when the space is used forclasses, performances or other school orcommunity activities. If the building is open on theweekend as part of the standard schedule duringone or more seasons, the building should select?yes? for open weekends. The ?yes? responseshould apply whether the building is open for oneor both of the weekend days.

Number of PCs 337 Is this the number of personal computers in theK12 School?

Number of walk-inrefrigeration/freezer

units 0

Is this the total number of commercial walk-in typefreezers and coolers? These units are typicallyfound in storage and receiving areas.

Presence ofcooking facilities Yes

Does this school have a dedicated space in whichfood is prepared and served to students? If theschool has space in which food for students isonly kept warm and/or served to students, or hasonly a galley that is used by teachers and staffthen the answer is "no".

Percent Cooled 90 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalcooling equipment?

Percent Heated 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalheating equipment?

Page 1 of 4

Page 130: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Months N/A(Optional) Is this school in operation for at least 8 months ofthe year?

High School? No

Is this building a high school (teaching grades 10,11, and/or 12)? If the building teaches to highschool students at all, the user should check 'yes'to 'high school'. For example, if the school teachesto grades K-12 (elementary/middle and highschool), the user should check 'yes' to 'highschool'.

Page 2 of 4

Page 131: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

Energy ConsumptionPower Generation Plant or Distribution Utility: Jersey Central Power & Lt Co

Fuel Type: Electricity

Meter: G16598230 (kWh)Space(s): Entire Facility

Start Date End Date Energy Use (kWh)

11/30/2008 12/29/2008 104,960.00

10/30/2008 11/29/2008 78,720.00

09/30/2008 10/29/2008 87,680.00

08/30/2008 09/29/2008 97,280.00

07/30/2008 08/29/2008 75,200.00

06/30/2008 07/29/2008 85,120.00

05/30/2008 06/29/2008 89,600.00

04/30/2008 05/29/2008 106,240.00

03/30/2008 04/29/2008 88,000.00

03/01/2008 03/29/2008 65,600.00

01/30/2008 02/29/2008 96,320.00

G16598230 Consumption (kWh) 974,720.00

G16598230 Consumption (kBtu) 3,325,744.64

Total Electricity Consumption (kBtu) 3,325,744.64

Is this the total Electricity consumption at this building including all Electricity meters?

Fuel Type: Natural Gas

Meter: 00726426 (therms)Space(s): Entire Facility

Start Date End Date Energy Use (therms)

11/11/2008 12/10/2008 8,153.51

10/11/2008 11/10/2008 4,197.29

09/11/2008 10/10/2008 971.00

08/11/2008 09/10/2008 470.00

07/11/2008 08/10/2008 143.00

06/11/2008 07/10/2008 158.00

05/11/2008 06/10/2008 1,904.00

04/11/2008 05/10/2008 2,500.00

03/11/2008 04/10/2008 6,361.00

02/11/2008 03/10/2008 8,235.00

Page 3 of 4

Page 132: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

01/11/2008 02/10/2008 22,390.00

00726426 Consumption (therms) 55,482.80

00726426 Consumption (kBtu) 5,548,280.00

Total Natural Gas Consumption (kBtu) 5,548,280.00

Is this the total Natural Gas consumption at this building including all Natural Gas meters?

Additional FuelsDo the fuel consumption totals shown above represent the total energy use of this building?Please confirm there are no additional fuels (district energy, generator fuel oil) used in this facility.

Certifying Professional (When applying for the ENERGY STAR, this must be the same PE that signed and stamped the SEP.)

Name: _____________________________________________ Date: _____________

Signature: ______________________________________ Signature is required when applying for the ENERGY STAR.

Page 4 of 4

Page 133: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

FOR YOUR RECORDS ONLY. DO NOT SUBMIT TO EPA.

Please keep this Facility Summary for your own records; do not submit it to EPA. Only the Statement of Energy Performance(SEP), Data Checklist and Letter of Agreement need to be submitted to EPA when applying for the ENERGY STAR.

FacilityJJ Catena Elementary School275 Burlington RoadFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

General InformationJJ Catena Elementary School

Gross Floor Area Excluding Parking: (ft2) 76,045 Year Built 1961 For 12-month Evaluation Period Ending Date: December 31, 2008

Facility Space Use SummaryJJ Catena

Space Type K-12 School

Gross Floor Area(ft2) 76,045

Open Weekends? Yes

Number of PCs 337

Number of walk-in refrigeration/freezerunits 0

Presence of cooking facilities Yes

Percent Cooled 90

Percent Heated 100

Monthso N/A

High School? No

School Districto N/A

Energy Performance ComparisonEvaluation Periods Comparisons

Performance Metrics Current(Ending Date 12/31/2008)

Baseline(Ending Date 12/31/2008) Rating of 75 Target National Average

Energy Performance Rating 19 19 75 N/A 50

Energy Intensity

Site (kBtu/ft2) 133 133 77 N/A 98

Source (kBtu/ft2) 248 248 144 N/A 184

Energy Cost

$/year $ 238,754.42 $ 238,754.42 $ 138,477.56 N/A $ 177,092.71

$/ft2/year $ 3.14 $ 3.14 $ 1.82 N/A $ 2.33

Greenhouse Gas Emissions

MtCO2e/year 844 844 490 N/A 626

kgCO2e/ft2/year 11 11 6 N/A 8

More than 50% of your building is defined as K-12 School. Please note that your rating accounts for all of the spaces listed. The National Average column presentsenergy performance data your building would have if your building had an average rating of 50. Notes:o - This attribute is optional.d - A default value has been supplied by Portfolio Manager.

Page 134: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

OMB No. 2060-0347

STATEMENT OF ENERGY PERFORMANCECT Barkalow Middle School

Building ID: 1765873 For 12-month Period Ending: December 31, 20081

Date SEP becomes ineligible: N/A Date SEP Generated: June 25, 2009

FacilityCT Barkalow Middle School498 Stillwells Corner RoadFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

Year Built: 1964Gross Floor Area (ft2): 110,533

Energy Performance Rating2 (1-100) 29

Site Energy Use Summary3

Electricity (kBtu) 4,792,945 Natural Gas (kBtu)4 6,207,758 Total Energy (kBtu) 11,000,703

Energy Intensity5 Site (kBtu/ft2/yr) 106 Source (kBtu/ft2/yr) 216 Emissions (based on site energy use) Greenhouse Gas Emissions (MtCO2e/year) 1,060 Electric Distribution Utility Jersey Central Power & Lt Co National Average Comparison National Average Site EUI 88 National Average Source EUI 179 % Difference from National Average Source EUI 21% Building Type K-12

School

Stamp of Certifying Professional

Based on the conditions observed at thetime of my visit to this building, I certify that

the information contained within thisstatement is accurate.

Meets Industry Standards6 for Indoor EnvironmentalConditions:Ventilation for Acceptable Indoor Air Quality N/A Acceptable Thermal Environmental Conditions N/A Adequate Illumination N/A

Certifying ProfessionalMatthew Goss15 British American Blvd Latham, NY 12110

Notes: 1. Application for the ENERGY STAR must be submitted to EPA within 4 months of the Period Ending date. Award of the ENERGY STAR is not final until approval is received from EPA.2. The EPA Energy Performance Rating is based on total source energy. A rating of 75 is the minimum to be eligible for the ENERGY STAR.3. Values represent energy consumption, annualized to a 12-month period.4. Natural Gas values in units of volume (e.g. cubic feet) are converted to kBtu with adjustments made for elevation based on Facility zip code.5. Values represent energy intensity, annualized to a 12-month period.6. Based on Meeting ASHRAE Standard 62 for ventilation for acceptable indoor air quality, ASHRAE Standard 55 for thermal comfort, and IESNA Lighting Handbook for lighting quality.

The government estimates the average time needed to fill out this form is 6 hours (includes the time for entering energy data, PE facility inspection, and notarizing the SEP) and welcomessuggestions for reducing this level of effort. Send comments (referencing OMB control number) to the Director, Collection Strategies Division, U.S., EPA (2822T), 1200 Pennsylvania Ave., NW,Washington, D.C. 20460.

EPA Form 5900-16

Page 135: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

In order for a building to qualify for the ENERGY STAR, a Professional Engineer (PE) must validate the accuracy of the data underlying the building's energyperformance rating. This checklist is designed to provide an at-a-glance summary of a property's physical and operating characteristics, as well as its total energyconsumption, to assist the PE in double-checking the information that the building owner or operator has entered into Portfolio Manager.

Please complete and sign this checklist and include it with the stamped, signed Statement of Energy Performance.NOTE: You must check each box to indicate that each value is correct, OR include a note.

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Building Name CT Barkalow Middle School Is this the official building name to be displayed inthe ENERGY STAR Registry of LabeledBuildings?

Type K-12 School Is this an accurate description of the space inquestion?

Location 498 Stillwells Corner Road,

Freehold, NJ 07728 Is this address accurate and complete? Correctweather normalization requires an accurate zipcode.

Single Structure Single Facility

Does this SEP represent a single structure? SEPscannot be submitted for multiple-buildingcampuses (with the exception of acute care orchildren's hospitals) nor can they be submitted asrepresenting only a portion of a building

CT Barkalow Middle School (K-12 School)

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Gross Floor Area 110,533 Sq. Ft.

Does this square footage include all supportingfunctions such as kitchens and break rooms usedby staff, storage areas, administrative areas,elevators, stairwells, atria, vent shafts, etc. Alsonote that existing atriums should only include thebase floor area that it occupies. Interstitial(plenum) space between floors should not beincluded in the total. Finally gross floor area is notthe same as leasable space. Leasable space is asubset of gross floor area.

Open Weekends? Yes

Is this building normally open at all on theweekends? This includes activities beyond thework conducted by maintenance, cleaning, andsecurity personnel. Weekend activity couldinclude any time when the space is used forclasses, performances or other school orcommunity activities. If the building is open on theweekend as part of the standard schedule duringone or more seasons, the building should select?yes? for open weekends. The ?yes? responseshould apply whether the building is open for oneor both of the weekend days.

Number of PCs 337 Is this the number of personal computers in theK12 School?

Number of walk-inrefrigeration/freezer

units 3

Is this the total number of commercial walk-in typefreezers and coolers? These units are typicallyfound in storage and receiving areas.

Presence ofcooking facilities Yes

Does this school have a dedicated space in whichfood is prepared and served to students? If theschool has space in which food for students isonly kept warm and/or served to students, or hasonly a galley that is used by teachers and staffthen the answer is "no".

Percent Cooled 90 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalcooling equipment?

Percent Heated 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalheating equipment?

Page 1 of 4

Page 136: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Months N/A(Optional) Is this school in operation for at least 8 months ofthe year?

High School? No

Is this building a high school (teaching grades 10,11, and/or 12)? If the building teaches to highschool students at all, the user should check 'yes'to 'high school'. For example, if the school teachesto grades K-12 (elementary/middle and highschool), the user should check 'yes' to 'highschool'.

Page 2 of 4

Page 137: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

Energy ConsumptionPower Generation Plant or Distribution Utility: Jersey Central Power & Lt Co

Fuel Type: Electricity

Meter: G16567684 (kWh)Space(s): Entire Facility

Start Date End Date Energy Use (kWh)

11/23/2008 12/22/2008 127,520.00

10/23/2008 11/22/2008 98,080.00

09/23/2008 10/22/2008 104,320.00

08/23/2008 09/22/2008 145,600.00

07/23/2008 08/22/2008 160,160.00

06/23/2008 07/22/2008 125,920.00

05/23/2008 06/22/2008 129,973.00

04/23/2008 05/22/2008 119,680.00

03/23/2008 04/22/2008 117,920.00

02/23/2008 03/22/2008 116,960.00

01/23/2008 02/22/2008 126,240.00

G16567684 Consumption (kWh) 1,372,373.00

G16567684 Consumption (kBtu) 4,682,536.68

Meter: G20066785 (kWh)Space(s): Entire Facility

Start Date End Date Energy Use (kWh)

11/23/2008 12/22/2008 91.00

10/23/2008 11/22/2008 156.00

09/23/2008 10/22/2008 147.00

08/23/2008 09/22/2008 113.00

07/23/2008 08/22/2008 99.00

06/23/2008 07/22/2008 115.00

05/23/2008 06/22/2008 83.00

04/23/2008 05/22/2008 37.00

03/23/2008 04/22/2008 40.00

02/23/2008 03/22/2008 37.00

01/23/2008 02/22/2008 38.00

G20066785 Consumption (kWh) 956.00

G20066785 Consumption (kBtu) 3,261.87

Total Electricity Consumption (kBtu) 4,685,798.55

Page 3 of 4

Page 138: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Is this the total Electricity consumption at this building including all Electricity meters?

Fuel Type: Natural Gas

Meter: 00726428 (therms)Space(s): Entire Facility

Start Date End Date Energy Use (therms)

11/25/2008 12/24/2008 13,061.99

10/25/2008 11/24/2008 5,153.72

09/25/2008 10/24/2008 2,103.00

08/25/2008 09/24/2008 733.00

07/25/2008 08/24/2008 358.00

06/25/2008 07/24/2008 190.00

05/25/2008 06/24/2008 1,328.00

04/25/2008 05/24/2008 4,743.00

03/25/2008 04/24/2008 6,410.00

02/25/2008 03/24/2008 10,346.00

01/25/2008 02/24/2008 14,043.00

00726428 Consumption (therms) 58,469.71

00726428 Consumption (kBtu) 5,846,971.00

Total Natural Gas Consumption (kBtu) 5,846,971.00

Is this the total Natural Gas consumption at this building including all Natural Gas meters?

Additional FuelsDo the fuel consumption totals shown above represent the total energy use of this building?Please confirm there are no additional fuels (district energy, generator fuel oil) used in this facility.

Certifying Professional (When applying for the ENERGY STAR, this must be the same PE that signed and stamped the SEP.)

Name: _____________________________________________ Date: _____________

Signature: ______________________________________ Signature is required when applying for the ENERGY STAR.

Page 4 of 4

Page 139: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

FOR YOUR RECORDS ONLY. DO NOT SUBMIT TO EPA.

Please keep this Facility Summary for your own records; do not submit it to EPA. Only the Statement of Energy Performance(SEP), Data Checklist and Letter of Agreement need to be submitted to EPA when applying for the ENERGY STAR.

FacilityCT Barkalow Middle School498 Stillwells Corner RoadFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

General InformationCT Barkalow Middle School

Gross Floor Area Excluding Parking: (ft2) 110,533 Year Built 1964 For 12-month Evaluation Period Ending Date: December 31, 2008

Facility Space Use SummaryCT Barkalow Middle School

Space Type K-12 School

Gross Floor Area(ft2) 110,533

Open Weekends? Yes

Number of PCs 337

Number of walk-in refrigeration/freezerunits 3

Presence of cooking facilities Yes

Percent Cooled 90

Percent Heated 100

Monthso N/A

High School? No

School Districto N/A

Energy Performance ComparisonEvaluation Periods Comparisons

Performance Metrics Current(Ending Date 12/31/2008)

Baseline(Ending Date 12/31/2008) Rating of 75 Target National Average

Energy Performance Rating 29 29 75 N/A 50

Energy Intensity

Site (kBtu/ft2) 106 106 69 N/A 88

Source (kBtu/ft2) 216 216 140 N/A 179

Energy Cost

$/year $ 328,346.74 $ 328,346.74 $ 212,534.40 N/A $ 271,788.67

$/ft2/year $ 2.97 $ 2.97 $ 1.92 N/A $ 2.46

Greenhouse Gas Emissions

MtCO2e/year 1,060 1,060 686 N/A 877

kgCO2e/ft2/year 10 10 6 N/A 8

More than 50% of your building is defined as K-12 School. Please note that your rating accounts for all of the spaces listed. The National Average column presentsenergy performance data your building would have if your building had an average rating of 50. Notes:o - This attribute is optional.d - A default value has been supplied by Portfolio Manager.

Page 140: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

OMB No. 2060-0347

STATEMENT OF ENERGY PERFORMANCEEarly Childhood Learning Center

Building ID: 1766361 For 12-month Period Ending: December 31, 20081

Date SEP becomes ineligible: N/A Date SEP Generated: June 25, 2009

FacilityEarly Childhood Learning Center510 Stillwells Corner RoadFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

Year Built: 1956Gross Floor Area (ft2): 37,165

Energy Performance Rating2 (1-100) 40

Site Energy Use Summary3

Electricity (kBtu) 1,650,598 Natural Gas (kBtu)4 3,632,905 Total Energy (kBtu) 5,283,503

Energy Intensity5 Site (kBtu/ft2/yr) 151 Source (kBtu/ft2/yr) 267 Emissions (based on site energy use) Greenhouse Gas Emissions (MtCO2e/year) 445 Electric Distribution Utility Jersey Central Power & Lt Co National Average Comparison National Average Site EUI 139 National Average Source EUI 245 % Difference from National Average Source EUI 9% Building Type K-12

School

Stamp of Certifying Professional

Based on the conditions observed at thetime of my visit to this building, I certify that

the information contained within thisstatement is accurate.

Meets Industry Standards6 for Indoor EnvironmentalConditions:Ventilation for Acceptable Indoor Air Quality N/A Acceptable Thermal Environmental Conditions N/A Adequate Illumination N/A

Certifying ProfessionalMatthew Goss15 British American Blvd Latham, NY 12110

Notes: 1. Application for the ENERGY STAR must be submitted to EPA within 4 months of the Period Ending date. Award of the ENERGY STAR is not final until approval is received from EPA.2. The EPA Energy Performance Rating is based on total source energy. A rating of 75 is the minimum to be eligible for the ENERGY STAR.3. Values represent energy consumption, annualized to a 12-month period.4. Natural Gas values in units of volume (e.g. cubic feet) are converted to kBtu with adjustments made for elevation based on Facility zip code.5. Values represent energy intensity, annualized to a 12-month period.6. Based on Meeting ASHRAE Standard 62 for ventilation for acceptable indoor air quality, ASHRAE Standard 55 for thermal comfort, and IESNA Lighting Handbook for lighting quality.

The government estimates the average time needed to fill out this form is 6 hours (includes the time for entering energy data, PE facility inspection, and notarizing the SEP) and welcomessuggestions for reducing this level of effort. Send comments (referencing OMB control number) to the Director, Collection Strategies Division, U.S., EPA (2822T), 1200 Pennsylvania Ave., NW,Washington, D.C. 20460.

EPA Form 5900-16

Page 141: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

In order for a building to qualify for the ENERGY STAR, a Professional Engineer (PE) must validate the accuracy of the data underlying the building's energyperformance rating. This checklist is designed to provide an at-a-glance summary of a property's physical and operating characteristics, as well as its total energyconsumption, to assist the PE in double-checking the information that the building owner or operator has entered into Portfolio Manager.

Please complete and sign this checklist and include it with the stamped, signed Statement of Energy Performance.NOTE: You must check each box to indicate that each value is correct, OR include a note.

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Building Name Early Childhood Learning

Center Is this the official building name to be displayed inthe ENERGY STAR Registry of LabeledBuildings?

Type K-12 School Is this an accurate description of the space inquestion?

Location 510 Stillwells Corner Road,

Freehold, NJ 07728 Is this address accurate and complete? Correctweather normalization requires an accurate zipcode.

Single Structure Single Facility

Does this SEP represent a single structure? SEPscannot be submitted for multiple-buildingcampuses (with the exception of acute care orchildren's hospitals) nor can they be submitted asrepresenting only a portion of a building

Early Chilldhood Learning Center (K-12 School)

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Gross Floor Area 37,165 Sq. Ft.

Does this square footage include all supportingfunctions such as kitchens and break rooms usedby staff, storage areas, administrative areas,elevators, stairwells, atria, vent shafts, etc. Alsonote that existing atriums should only include thebase floor area that it occupies. Interstitial(plenum) space between floors should not beincluded in the total. Finally gross floor area is notthe same as leasable space. Leasable space is asubset of gross floor area.

Open Weekends? Yes

Is this building normally open at all on theweekends? This includes activities beyond thework conducted by maintenance, cleaning, andsecurity personnel. Weekend activity couldinclude any time when the space is used forclasses, performances or other school orcommunity activities. If the building is open on theweekend as part of the standard schedule duringone or more seasons, the building should select?yes? for open weekends. The ?yes? responseshould apply whether the building is open for oneor both of the weekend days.

Number of PCs 337 Is this the number of personal computers in theK12 School?

Number of walk-inrefrigeration/freezer

units 0

Is this the total number of commercial walk-in typefreezers and coolers? These units are typicallyfound in storage and receiving areas.

Presence ofcooking facilities Yes

Does this school have a dedicated space in whichfood is prepared and served to students? If theschool has space in which food for students isonly kept warm and/or served to students, or hasonly a galley that is used by teachers and staffthen the answer is "no".

Percent Cooled 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalcooling equipment?

Percent Heated 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalheating equipment?

Page 1 of 4

Page 142: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Months N/A(Optional) Is this school in operation for at least 8 months ofthe year?

High School? No

Is this building a high school (teaching grades 10,11, and/or 12)? If the building teaches to highschool students at all, the user should check 'yes'to 'high school'. For example, if the school teachesto grades K-12 (elementary/middle and highschool), the user should check 'yes' to 'highschool'.

Page 2 of 4

Page 143: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

Energy ConsumptionPower Generation Plant or Distribution Utility: Jersey Central Power & Lt Co

Fuel Type: Electricity

Meter: G15112462 (kWh)Space(s): Entire Facility

Start Date End Date Energy Use (kWh)

11/23/2008 12/22/2008 45,120.00

10/23/2008 11/22/2008 35,520.00

09/23/2008 10/22/2008 33,280.00

08/23/2008 09/22/2008 48,320.00

07/23/2008 08/22/2008 48,800.00

06/23/2008 07/22/2008 52,000.00

05/23/2008 06/22/2008 48,160.00

04/23/2008 05/22/2008 39,200.00

03/23/2008 04/22/2008 39,520.00

02/23/2008 03/22/2008 39,680.00

01/23/2008 02/22/2008 43,200.00

G15112462 Consumption (kWh) 472,800.00

G15112462 Consumption (kBtu) 1,613,193.60

Total Electricity Consumption (kBtu) 1,613,193.60

Is this the total Electricity consumption at this building including all Electricity meters?

Fuel Type: Natural Gas

Meter: 00850870 (therms)Space(s): Entire Facility

Start Date End Date Energy Use (therms)

11/25/2008 12/24/2008 7,988.80

10/25/2008 11/24/2008 4,113.85

09/25/2008 10/24/2008 2,267.00

08/25/2008 09/24/2008 90.00

07/25/2008 08/24/2008 60.00

06/25/2008 07/24/2008 47.00

05/25/2008 06/24/2008 457.00

04/25/2008 05/24/2008 2,670.00

03/25/2008 04/24/2008 3,458.00

02/25/2008 03/24/2008 5,859.00

Page 3 of 4

Page 144: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

01/25/2008 02/24/2008 7,276.00

00850870 Consumption (therms) 34,286.65

00850870 Consumption (kBtu) 3,428,665.00

Total Natural Gas Consumption (kBtu) 3,428,665.00

Is this the total Natural Gas consumption at this building including all Natural Gas meters?

Additional FuelsDo the fuel consumption totals shown above represent the total energy use of this building?Please confirm there are no additional fuels (district energy, generator fuel oil) used in this facility.

Certifying Professional (When applying for the ENERGY STAR, this must be the same PE that signed and stamped the SEP.)

Name: _____________________________________________ Date: _____________

Signature: ______________________________________ Signature is required when applying for the ENERGY STAR.

Page 4 of 4

Page 145: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

FOR YOUR RECORDS ONLY. DO NOT SUBMIT TO EPA.

Please keep this Facility Summary for your own records; do not submit it to EPA. Only the Statement of Energy Performance(SEP), Data Checklist and Letter of Agreement need to be submitted to EPA when applying for the ENERGY STAR.

FacilityEarly Childhood Learning Center510 Stillwells Corner RoadFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

General InformationEarly Childhood Learning Center

Gross Floor Area Excluding Parking: (ft2) 37,165 Year Built 1956 For 12-month Evaluation Period Ending Date: December 31, 2008

Facility Space Use SummaryEarly Chilldhood Learning Center

Space Type K-12 School

Gross Floor Area(ft2) 37,165

Open Weekends? Yes

Number of PCs 337

Number of walk-in refrigeration/freezerunits 0

Presence of cooking facilities Yes

Percent Cooled 100

Percent Heated 100

Monthso N/A

High School? No

School Districto N/A

Energy Performance ComparisonEvaluation Periods Comparisons

Performance Metrics Current(Ending Date 12/31/2008)

Baseline(Ending Date 12/31/2008) Rating of 75 Target National Average

Energy Performance Rating 40 40 75 N/A 50

Energy Intensity

Site (kBtu/ft2) 151 151 109 N/A 139

Source (kBtu/ft2) 267 267 191 N/A 245

Energy Cost

$/year $ 142,971.93 $ 142,971.93 $ 102,633.93 N/A $ 131,247.19

$/ft2/year $ 3.85 $ 3.85 $ 2.76 N/A $ 3.53

Greenhouse Gas Emissions

MtCO2e/year 445 445 319 N/A 409

kgCO2e/ft2/year 12 12 9 N/A 11

More than 50% of your building is defined as K-12 School. Please note that your rating accounts for all of the spaces listed. The National Average column presentsenergy performance data your building would have if your building had an average rating of 50. Notes:o - This attribute is optional.d - A default value has been supplied by Portfolio Manager.

Page 146: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

OMB No. 2060-0347

STATEMENT OF ENERGY PERFORMANCEMW Errickson Elementary School

Building ID: 1766373 For 12-month Period Ending: December 31, 20081

Date SEP becomes ineligible: N/A Date SEP Generated: June 25, 2009

FacilityMW Errickson Elementary School271 Elton Adelphia RoadFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

Year Built: 1972Gross Floor Area (ft2): 78,130

Energy Performance Rating2 (1-100) 6

Site Energy Use Summary3

Electricity (kBtu) 5,442,061 Natural Gas (kBtu)4 4,395,675 Total Energy (kBtu) 9,837,736

Energy Intensity5 Site (kBtu/ft2/yr) 135 Source (kBtu/ft2/yr) 312 Emissions (based on site energy use) Greenhouse Gas Emissions (MtCO2e/year) 1,063 Electric Distribution Utility Jersey Central Power & Lt Co National Average Comparison National Average Site EUI 81 National Average Source EUI 187 % Difference from National Average Source EUI 67% Building Type K-12

School

Stamp of Certifying Professional

Based on the conditions observed at thetime of my visit to this building, I certify that

the information contained within thisstatement is accurate.

Meets Industry Standards6 for Indoor EnvironmentalConditions:Ventilation for Acceptable Indoor Air Quality N/A Acceptable Thermal Environmental Conditions N/A Adequate Illumination N/A

Certifying ProfessionalMatthew Goss15 British American Blvd Latham, NY 12110

Notes: 1. Application for the ENERGY STAR must be submitted to EPA within 4 months of the Period Ending date. Award of the ENERGY STAR is not final until approval is received from EPA.2. The EPA Energy Performance Rating is based on total source energy. A rating of 75 is the minimum to be eligible for the ENERGY STAR.3. Values represent energy consumption, annualized to a 12-month period.4. Natural Gas values in units of volume (e.g. cubic feet) are converted to kBtu with adjustments made for elevation based on Facility zip code.5. Values represent energy intensity, annualized to a 12-month period.6. Based on Meeting ASHRAE Standard 62 for ventilation for acceptable indoor air quality, ASHRAE Standard 55 for thermal comfort, and IESNA Lighting Handbook for lighting quality.

The government estimates the average time needed to fill out this form is 6 hours (includes the time for entering energy data, PE facility inspection, and notarizing the SEP) and welcomessuggestions for reducing this level of effort. Send comments (referencing OMB control number) to the Director, Collection Strategies Division, U.S., EPA (2822T), 1200 Pennsylvania Ave., NW,Washington, D.C. 20460.

EPA Form 5900-16

Page 147: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

In order for a building to qualify for the ENERGY STAR, a Professional Engineer (PE) must validate the accuracy of the data underlying the building's energyperformance rating. This checklist is designed to provide an at-a-glance summary of a property's physical and operating characteristics, as well as its total energyconsumption, to assist the PE in double-checking the information that the building owner or operator has entered into Portfolio Manager.

Please complete and sign this checklist and include it with the stamped, signed Statement of Energy Performance.NOTE: You must check each box to indicate that each value is correct, OR include a note.

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Building Name MW Errickson Elementary

School Is this the official building name to be displayed inthe ENERGY STAR Registry of LabeledBuildings?

Type K-12 School Is this an accurate description of the space inquestion?

Location 271 Elton Adelphia Road,

Freehold, NJ 07728 Is this address accurate and complete? Correctweather normalization requires an accurate zipcode.

Single Structure Single Facility

Does this SEP represent a single structure? SEPscannot be submitted for multiple-buildingcampuses (with the exception of acute care orchildren's hospitals) nor can they be submitted asrepresenting only a portion of a building

MW Errickson (K-12 School)

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Gross Floor Area 78,130 Sq. Ft.

Does this square footage include all supportingfunctions such as kitchens and break rooms usedby staff, storage areas, administrative areas,elevators, stairwells, atria, vent shafts, etc. Alsonote that existing atriums should only include thebase floor area that it occupies. Interstitial(plenum) space between floors should not beincluded in the total. Finally gross floor area is notthe same as leasable space. Leasable space is asubset of gross floor area.

Open Weekends? Yes

Is this building normally open at all on theweekends? This includes activities beyond thework conducted by maintenance, cleaning, andsecurity personnel. Weekend activity couldinclude any time when the space is used forclasses, performances or other school orcommunity activities. If the building is open on theweekend as part of the standard schedule duringone or more seasons, the building should select?yes? for open weekends. The ?yes? responseshould apply whether the building is open for oneor both of the weekend days.

Number of PCs 337 Is this the number of personal computers in theK12 School?

Number of walk-inrefrigeration/freezer

units 0

Is this the total number of commercial walk-in typefreezers and coolers? These units are typicallyfound in storage and receiving areas.

Presence ofcooking facilities Yes

Does this school have a dedicated space in whichfood is prepared and served to students? If theschool has space in which food for students isonly kept warm and/or served to students, or hasonly a galley that is used by teachers and staffthen the answer is "no".

Percent Cooled 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalcooling equipment?

Percent Heated 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalheating equipment?

Page 1 of 5

Page 148: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Months N/A(Optional) Is this school in operation for at least 8 months ofthe year?

High School? No

Is this building a high school (teaching grades 10,11, and/or 12)? If the building teaches to highschool students at all, the user should check 'yes'to 'high school'. For example, if the school teachesto grades K-12 (elementary/middle and highschool), the user should check 'yes' to 'highschool'.

Page 2 of 5

Page 149: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

Energy ConsumptionPower Generation Plant or Distribution Utility: Jersey Central Power & Lt Co

Fuel Type: Electricity

Meter: G28658723 (kWh)Space(s): Entire Facility

Start Date End Date Energy Use (kWh)

11/25/2008 12/24/2008 57,200.00

10/25/2008 11/24/2008 48,200.00

09/25/2008 10/24/2008 57,600.00

08/25/2008 09/24/2008 84,800.00

07/25/2008 08/24/2008 74,000.00

06/25/2008 07/24/2008 103,800.00

05/25/2008 06/24/2008 97,200.00

04/25/2008 05/24/2008 74,600.00

03/25/2008 04/24/2008 67,600.00

02/25/2008 03/24/2008 60,000.00

01/25/2008 02/24/2008 61,400.00

G28658723 Consumption (kWh) 786,400.00

G28658723 Consumption (kBtu) 2,683,196.80

Meter: G15112467 (kWh)Space(s): Entire Facility

Start Date End Date Energy Use (kWh)

11/25/2008 12/24/2008 57,200.00

10/25/2008 11/24/2008 48,200.00

09/25/2008 10/24/2008 57,600.00

08/25/2008 09/24/2008 84,800.00

07/25/2008 08/24/2008 74,000.00

06/25/2008 07/24/2008 103,800.00

05/25/2008 06/24/2008 97,200.00

04/25/2008 05/24/2008 74,600.00

03/25/2008 04/24/2008 67,600.00

02/25/2008 03/24/2008 60,000.00

01/25/2008 02/24/2008 61,400.00

G15112467 Consumption (kWh) 786,400.00

G15112467 Consumption (kBtu) 2,683,196.80

Meter: G98739834 (kWh)Space(s): Entire Facility

Page 3 of 5

Page 150: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Start Date End Date Energy Use (kWh)

11/25/2008 12/24/2008 135.00

10/25/2008 11/24/2008 13.00

09/25/2008 10/24/2008 13.00

08/25/2008 09/24/2008 12.00

07/25/2008 08/24/2008 11.00

06/25/2008 07/24/2008 10.00

05/25/2008 06/24/2008 12.00

04/25/2008 05/24/2008 19.00

03/25/2008 04/24/2008 19.00

02/25/2008 03/24/2008 20.00

01/25/2008 02/24/2008 25.00

G98739834 Consumption (kWh) 289.00

G98739834 Consumption (kBtu) 986.07

Total Electricity Consumption (kBtu) 5,367,379.67

Is this the total Electricity consumption at this building including all Electricity meters?

Fuel Type: Natural Gas

Meter: 00726118 (therms)Space(s): Entire Facility

Start Date End Date Energy Use (therms)

12/01/2008 12/30/2008 8,045.77

10/31/2008 11/30/2008 5,781.62

10/01/2008 10/30/2008 1,648.02

08/31/2008 09/30/2008 323.00

07/31/2008 08/30/2008 135.00

07/01/2008 07/30/2008 275.00

05/31/2008 06/30/2008 335.00

05/01/2008 05/30/2008 2,321.00

03/31/2008 04/30/2008 2,826.00

03/01/2008 03/30/2008 16,112.00

01/31/2008 02/29/2008 5,820.00

00726118 Consumption (therms) 43,622.41

00726118 Consumption (kBtu) 4,362,241.00

Total Natural Gas Consumption (kBtu) 4,362,241.00

Is this the total Natural Gas consumption at this building including all Natural Gas meters?

Additional FuelsDo the fuel consumption totals shown above represent the total energy use of this building?Please confirm there are no additional fuels (district energy, generator fuel oil) used in this facility.

Certifying Professional (When applying for the ENERGY STAR, this must be the same PE that signed and stamped the SEP.)

Page 4 of 5

Page 151: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Name: _____________________________________________ Date: _____________

Signature: ______________________________________ Signature is required when applying for the ENERGY STAR.

Page 5 of 5

Page 152: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

FOR YOUR RECORDS ONLY. DO NOT SUBMIT TO EPA.

Please keep this Facility Summary for your own records; do not submit it to EPA. Only the Statement of Energy Performance(SEP), Data Checklist and Letter of Agreement need to be submitted to EPA when applying for the ENERGY STAR.

FacilityMW Errickson Elementary School271 Elton Adelphia RoadFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

General InformationMW Errickson Elementary School

Gross Floor Area Excluding Parking: (ft2) 78,130 Year Built 1972 For 12-month Evaluation Period Ending Date: December 31, 2008

Facility Space Use SummaryMW Errickson

Space Type K-12 School

Gross Floor Area(ft2) 78,130

Open Weekends? Yes

Number of PCs 337

Number of walk-in refrigeration/freezerunits 0

Presence of cooking facilities Yes

Percent Cooled 100

Percent Heated 100

Monthso N/A

High School? No

School Districto N/A

Energy Performance ComparisonEvaluation Periods Comparisons

Performance Metrics Current(Ending Date 12/31/2008)

Baseline(Ending Date 12/31/2008) Rating of 75 Target National Average

Energy Performance Rating 6 6 75 N/A 50

Energy Intensity

Site (kBtu/ft2) 135 135 63 N/A 81

Source (kBtu/ft2) 312 312 146 N/A 187

Energy Cost

$/year $ 333,772.25 $ 333,772.25 $ 155,995.28 N/A $ 199,484.73

$/ft2/year $ 4.27 $ 4.27 $ 2.00 N/A $ 2.55

Greenhouse Gas Emissions

MtCO2e/year 1,063 1,063 497 N/A 635

kgCO2e/ft2/year 14 14 7 N/A 8

More than 50% of your building is defined as K-12 School. Please note that your rating accounts for all of the spaces listed. The National Average column presentsenergy performance data your building would have if your building had an average rating of 50. Notes:o - This attribute is optional.d - A default value has been supplied by Portfolio Manager.

Page 153: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 154: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

OMB No. 2060-0347

STATEMENT OF ENERGY PERFORMANCELaura Donovan Elementary School

Building ID: 1766370 For 12-month Period Ending: December 31, 20081

Date SEP becomes ineligible: N/A Date SEP Generated: June 25, 2009

FacilityLaura Donovan Elementary School237 Stonehurst BlvdFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

Year Built: 1968Gross Floor Area (ft2): 76,491

Energy Performance Rating2 (1-100) 34

Site Energy Use Summary3

Natural Gas (kBtu)4 1,687,922 Electricity (kBtu) 4,116,519 Total Energy (kBtu) 5,804,441

Energy Intensity5 Site (kBtu/ft2/yr) 81 Source (kBtu/ft2/yr) 216 Emissions (based on site energy use) Greenhouse Gas Emissions (MtCO2e/year) 717 Electric Distribution Utility Jersey Central Power & Lt Co National Average Comparison National Average Site EUI 70 National Average Source EUI 188 % Difference from National Average Source EUI 15% Building Type K-12

School

Stamp of Certifying Professional

Based on the conditions observed at thetime of my visit to this building, I certify that

the information contained within thisstatement is accurate.

Meets Industry Standards6 for Indoor EnvironmentalConditions:Ventilation for Acceptable Indoor Air Quality N/A Acceptable Thermal Environmental Conditions N/A Adequate Illumination N/A

Certifying ProfessionalMatthew Goss15 British American Blvd Latham, NY 12110

Notes: 1. Application for the ENERGY STAR must be submitted to EPA within 4 months of the Period Ending date. Award of the ENERGY STAR is not final until approval is received from EPA.2. The EPA Energy Performance Rating is based on total source energy. A rating of 75 is the minimum to be eligible for the ENERGY STAR.3. Values represent energy consumption, annualized to a 12-month period.4. Natural Gas values in units of volume (e.g. cubic feet) are converted to kBtu with adjustments made for elevation based on Facility zip code.5. Values represent energy intensity, annualized to a 12-month period.6. Based on Meeting ASHRAE Standard 62 for ventilation for acceptable indoor air quality, ASHRAE Standard 55 for thermal comfort, and IESNA Lighting Handbook for lighting quality.

The government estimates the average time needed to fill out this form is 6 hours (includes the time for entering energy data, PE facility inspection, and notarizing the SEP) and welcomessuggestions for reducing this level of effort. Send comments (referencing OMB control number) to the Director, Collection Strategies Division, U.S., EPA (2822T), 1200 Pennsylvania Ave., NW,Washington, D.C. 20460.

EPA Form 5900-16

Page 155: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

In order for a building to qualify for the ENERGY STAR, a Professional Engineer (PE) must validate the accuracy of the data underlying the building's energyperformance rating. This checklist is designed to provide an at-a-glance summary of a property's physical and operating characteristics, as well as its total energyconsumption, to assist the PE in double-checking the information that the building owner or operator has entered into Portfolio Manager.

Please complete and sign this checklist and include it with the stamped, signed Statement of Energy Performance.NOTE: You must check each box to indicate that each value is correct, OR include a note.

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Building Name Laura Donovan Elementary

School Is this the official building name to be displayed inthe ENERGY STAR Registry of LabeledBuildings?

Type K-12 School Is this an accurate description of the space inquestion?

Location 237 Stonehurst Blvd,Freehold, NJ 07728

Is this address accurate and complete? Correctweather normalization requires an accurate zipcode.

Single Structure Single Facility

Does this SEP represent a single structure? SEPscannot be submitted for multiple-buildingcampuses (with the exception of acute care orchildren's hospitals) nor can they be submitted asrepresenting only a portion of a building

Laura Donovan Elementary School (K-12 School)

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Gross Floor Area 76,491 Sq. Ft.

Does this square footage include all supportingfunctions such as kitchens and break rooms usedby staff, storage areas, administrative areas,elevators, stairwells, atria, vent shafts, etc. Alsonote that existing atriums should only include thebase floor area that it occupies. Interstitial(plenum) space between floors should not beincluded in the total. Finally gross floor area is notthe same as leasable space. Leasable space is asubset of gross floor area.

Open Weekends? Yes

Is this building normally open at all on theweekends? This includes activities beyond thework conducted by maintenance, cleaning, andsecurity personnel. Weekend activity couldinclude any time when the space is used forclasses, performances or other school orcommunity activities. If the building is open on theweekend as part of the standard schedule duringone or more seasons, the building should select?yes? for open weekends. The ?yes? responseshould apply whether the building is open for oneor both of the weekend days.

Number of PCs 337 Is this the number of personal computers in theK12 School?

Number of walk-inrefrigeration/freezer

units 0

Is this the total number of commercial walk-in typefreezers and coolers? These units are typicallyfound in storage and receiving areas.

Presence ofcooking facilities Yes

Does this school have a dedicated space in whichfood is prepared and served to students? If theschool has space in which food for students isonly kept warm and/or served to students, or hasonly a galley that is used by teachers and staffthen the answer is "no".

Percent Cooled 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalcooling equipment?

Percent Heated 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalheating equipment?

Page 1 of 4

Page 156: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Months N/A(Optional) Is this school in operation for at least 8 months ofthe year?

High School? No

Is this building a high school (teaching grades 10,11, and/or 12)? If the building teaches to highschool students at all, the user should check 'yes'to 'high school'. For example, if the school teachesto grades K-12 (elementary/middle and highschool), the user should check 'yes' to 'highschool'.

Page 2 of 4

Page 157: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

Energy ConsumptionPower Generation Plant or Distribution Utility: Jersey Central Power & Lt Co

Fuel Type: Electricity

Meter: G79131174 (kWh)Space(s): Entire Facility

Start Date End Date Energy Use (kWh)

11/24/2008 12/23/2008 159,360.00

10/24/2008 11/23/2008 105,600.00

09/24/2008 10/23/2008 75,840.00

08/24/2008 09/23/2008 87,680.00

07/24/2008 08/23/2008 83,520.00

06/24/2008 07/23/2008 94,400.00

05/24/2008 06/23/2008 96,640.00

04/24/2008 05/23/2008 85,760.00

03/24/2008 04/23/2008 102,080.00

02/24/2008 03/23/2008 106,560.00

01/24/2008 02/23/2008 165,440.00

G79131174 Consumption (kWh) 1,162,880.00

G79131174 Consumption (kBtu) 3,967,746.56

Total Electricity Consumption (kBtu) 3,967,746.56

Is this the total Electricity consumption at this building including all Electricity meters?

Fuel Type: Natural Gas

Meter: 00720776 (therms)Space(s): Entire Facility

Start Date End Date Energy Use (therms)

11/25/2008 12/24/2008 3,517.48

10/25/2008 11/24/2008 1,584.82

09/25/2008 10/24/2008 612.00

08/25/2008 09/24/2008 584.00

07/25/2008 08/24/2008 138.00

06/25/2008 07/24/2008 597.00

05/25/2008 06/24/2008 164.00

04/25/2008 05/24/2008 652.00

03/25/2008 04/24/2008 1,227.00

02/25/2008 03/24/2008 4,162.00

Page 3 of 4

Page 158: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

01/25/2008 02/24/2008 2,783.00

00720776 Consumption (therms) 16,021.30

00720776 Consumption (kBtu) 1,602,130.00

Total Natural Gas Consumption (kBtu) 1,602,130.00

Is this the total Natural Gas consumption at this building including all Natural Gas meters?

Additional FuelsDo the fuel consumption totals shown above represent the total energy use of this building?Please confirm there are no additional fuels (district energy, generator fuel oil) used in this facility.

Certifying Professional (When applying for the ENERGY STAR, this must be the same PE that signed and stamped the SEP.)

Name: _____________________________________________ Date: _____________

Signature: ______________________________________ Signature is required when applying for the ENERGY STAR.

Page 4 of 4

Page 159: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

FOR YOUR RECORDS ONLY. DO NOT SUBMIT TO EPA.

Please keep this Facility Summary for your own records; do not submit it to EPA. Only the Statement of Energy Performance(SEP), Data Checklist and Letter of Agreement need to be submitted to EPA when applying for the ENERGY STAR.

FacilityLaura Donovan Elementary School237 Stonehurst BlvdFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

General InformationLaura Donovan Elementary School

Gross Floor Area Excluding Parking: (ft2) 76,491 Year Built 1968 For 12-month Evaluation Period Ending Date: December 31, 2008

Facility Space Use SummaryLaura Donovan Elementary School

Space Type K-12 School

Gross Floor Area(ft2) 76,491

Open Weekends? Yes

Number of PCs 337

Number of walk-in refrigeration/freezerunits 0

Presence of cooking facilities Yes

Percent Cooled 100

Percent Heated 100

Monthso N/A

High School? No

School Districto N/A

Energy Performance ComparisonEvaluation Periods Comparisons

Performance Metrics Current(Ending Date 12/31/2008)

Baseline(Ending Date 12/31/2008) Rating of 75 Target National Average

Energy Performance Rating 34 34 75 N/A 50

Energy Intensity

Site (kBtu/ft2) 81 81 55 N/A 70

Source (kBtu/ft2) 216 216 147 N/A 188

Energy Cost

$/year $ 228,147.88 $ 228,147.88 $ 155,232.02 N/A $ 198,507.29

$/ft2/year $ 2.98 $ 2.98 $ 2.03 N/A $ 2.59

Greenhouse Gas Emissions

MtCO2e/year 717 717 488 N/A 624

kgCO2e/ft2/year 9 9 6 N/A 8

More than 50% of your building is defined as K-12 School. Please note that your rating accounts for all of the spaces listed. The National Average column presentsenergy performance data your building would have if your building had an average rating of 50. Notes:o - This attribute is optional.d - A default value has been supplied by Portfolio Manager.

Page 160: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

OMB No. 2060-0347

STATEMENT OF ENERGY PERFORMANCEWest Freehold Elementary School

Building ID: 1766389 For 12-month Period Ending: December 31, 20081

Date SEP becomes ineligible: N/A Date SEP Generated: June 25, 2009

FacilityWest Freehold Elementary School100 Castronova WayFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

Year Built: 2004Gross Floor Area (ft2): 90,000

Energy Performance Rating2 (1-100) 3

Site Energy Use Summary3

Electricity (kBtu) 7,220,391 Natural Gas (kBtu)4 3,337,554 Total Energy (kBtu) 10,557,945

Energy Intensity5 Site (kBtu/ft2/yr) 123 Source (kBtu/ft2/yr) 324 Emissions (based on site energy use) Greenhouse Gas Emissions (MtCO2e/year) 1,277 Electric Distribution Utility Jersey Central Power & Lt Co National Average Comparison National Average Site EUI 68 National Average Source EUI 179 % Difference from National Average Source EUI 81% Building Type K-12

School

Stamp of Certifying Professional

Based on the conditions observed at thetime of my visit to this building, I certify that

the information contained within thisstatement is accurate.

Meets Industry Standards6 for Indoor EnvironmentalConditions:Ventilation for Acceptable Indoor Air Quality N/A Acceptable Thermal Environmental Conditions N/A Adequate Illumination N/A

Certifying ProfessionalMatthew Goss15 British American Blvd Latham, NY 12110

Notes: 1. Application for the ENERGY STAR must be submitted to EPA within 4 months of the Period Ending date. Award of the ENERGY STAR is not final until approval is received from EPA.2. The EPA Energy Performance Rating is based on total source energy. A rating of 75 is the minimum to be eligible for the ENERGY STAR.3. Values represent energy consumption, annualized to a 12-month period.4. Natural Gas values in units of volume (e.g. cubic feet) are converted to kBtu with adjustments made for elevation based on Facility zip code.5. Values represent energy intensity, annualized to a 12-month period.6. Based on Meeting ASHRAE Standard 62 for ventilation for acceptable indoor air quality, ASHRAE Standard 55 for thermal comfort, and IESNA Lighting Handbook for lighting quality.

The government estimates the average time needed to fill out this form is 6 hours (includes the time for entering energy data, PE facility inspection, and notarizing the SEP) and welcomessuggestions for reducing this level of effort. Send comments (referencing OMB control number) to the Director, Collection Strategies Division, U.S., EPA (2822T), 1200 Pennsylvania Ave., NW,Washington, D.C. 20460.

EPA Form 5900-16

Page 161: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

In order for a building to qualify for the ENERGY STAR, a Professional Engineer (PE) must validate the accuracy of the data underlying the building's energyperformance rating. This checklist is designed to provide an at-a-glance summary of a property's physical and operating characteristics, as well as its total energyconsumption, to assist the PE in double-checking the information that the building owner or operator has entered into Portfolio Manager.

Please complete and sign this checklist and include it with the stamped, signed Statement of Energy Performance.NOTE: You must check each box to indicate that each value is correct, OR include a note.

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Building Name West Freehold Elementary

School Is this the official building name to be displayed inthe ENERGY STAR Registry of LabeledBuildings?

Type K-12 School Is this an accurate description of the space inquestion?

Location 100 Castronova Way,Freehold, NJ 07728

Is this address accurate and complete? Correctweather normalization requires an accurate zipcode.

Single Structure Single Facility

Does this SEP represent a single structure? SEPscannot be submitted for multiple-buildingcampuses (with the exception of acute care orchildren's hospitals) nor can they be submitted asrepresenting only a portion of a building

West Freehold Elementary School (K-12 School)

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Gross Floor Area 90,000 Sq. Ft.

Does this square footage include all supportingfunctions such as kitchens and break rooms usedby staff, storage areas, administrative areas,elevators, stairwells, atria, vent shafts, etc. Alsonote that existing atriums should only include thebase floor area that it occupies. Interstitial(plenum) space between floors should not beincluded in the total. Finally gross floor area is notthe same as leasable space. Leasable space is asubset of gross floor area.

Open Weekends? Yes

Is this building normally open at all on theweekends? This includes activities beyond thework conducted by maintenance, cleaning, andsecurity personnel. Weekend activity couldinclude any time when the space is used forclasses, performances or other school orcommunity activities. If the building is open on theweekend as part of the standard schedule duringone or more seasons, the building should select?yes? for open weekends. The ?yes? responseshould apply whether the building is open for oneor both of the weekend days.

Number of PCs 337 Is this the number of personal computers in theK12 School?

Number of walk-inrefrigeration/freezer

units 0

Is this the total number of commercial walk-in typefreezers and coolers? These units are typicallyfound in storage and receiving areas.

Presence ofcooking facilities Yes

Does this school have a dedicated space in whichfood is prepared and served to students? If theschool has space in which food for students isonly kept warm and/or served to students, or hasonly a galley that is used by teachers and staffthen the answer is "no".

Percent Cooled 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalcooling equipment?

Percent Heated 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalheating equipment?

Page 1 of 4

Page 162: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Months N/A(Optional) Is this school in operation for at least 8 months ofthe year?

High School? No

Is this building a high school (teaching grades 10,11, and/or 12)? If the building teaches to highschool students at all, the user should check 'yes'to 'high school'. For example, if the school teachesto grades K-12 (elementary/middle and highschool), the user should check 'yes' to 'highschool'.

Page 2 of 4

Page 163: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

Energy ConsumptionPower Generation Plant or Distribution Utility: Jersey Central Power & Lt Co

Fuel Type: Electricity

Meter: G23741645 (kWh)Space(s): Entire Facility

Start Date End Date Energy Use (kWh)

11/23/2008 12/22/2008 207,680.00

10/23/2008 11/22/2008 151,520.00

09/23/2008 10/22/2008 133,600.00

08/23/2008 09/22/2008 190,240.00

07/23/2008 08/22/2008 150,880.00

06/23/2008 07/22/2008 161,120.00

05/23/2008 06/22/2008 205,280.00

04/23/2008 05/22/2008 136,640.00

03/23/2008 04/22/2008 235,520.00

02/23/2008 03/22/2008 220,640.00

01/23/2008 02/22/2008 240,000.00

G23741645 Consumption (kWh) 2,033,120.00

G23741645 Consumption (kBtu) 6,937,005.44

Total Electricity Consumption (kBtu) 6,937,005.44

Is this the total Electricity consumption at this building including all Electricity meters?

Fuel Type: Natural Gas

Meter: 00720782 (therms)Space(s): Entire Facility

Start Date End Date Energy Use (therms)

11/10/2008 12/09/2008 9,826.96

10/10/2008 11/09/2008 1,711.52

09/10/2008 10/09/2008 148.00

08/10/2008 09/09/2008 25.00

07/10/2008 08/09/2008 21.00

06/10/2008 07/09/2008 26.00

05/10/2008 06/09/2008 464.00

04/10/2008 05/09/2008 734.00

03/10/2008 04/09/2008 3,135.00

02/10/2008 03/09/2008 4,929.00

Page 3 of 4

Page 164: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

01/10/2008 02/09/2008 7,252.00

00720782 Consumption (therms) 28,272.48

00720782 Consumption (kBtu) 2,827,248.00

Total Natural Gas Consumption (kBtu) 2,827,248.00

Is this the total Natural Gas consumption at this building including all Natural Gas meters?

Additional FuelsDo the fuel consumption totals shown above represent the total energy use of this building?Please confirm there are no additional fuels (district energy, generator fuel oil) used in this facility.

Certifying Professional (When applying for the ENERGY STAR, this must be the same PE that signed and stamped the SEP.)

Name: _____________________________________________ Date: _____________

Signature: ______________________________________ Signature is required when applying for the ENERGY STAR.

Page 4 of 4

Page 165: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

FOR YOUR RECORDS ONLY. DO NOT SUBMIT TO EPA.

Please keep this Facility Summary for your own records; do not submit it to EPA. Only the Statement of Energy Performance(SEP), Data Checklist and Letter of Agreement need to be submitted to EPA when applying for the ENERGY STAR.

FacilityWest Freehold Elementary School100 Castronova WayFreehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

General InformationWest Freehold Elementary School

Gross Floor Area Excluding Parking: (ft2) 90,000 Year Built 2004 For 12-month Evaluation Period Ending Date: December 31, 2008

Facility Space Use SummaryWest Freehold Elementary School

Space Type K-12 School

Gross Floor Area(ft2) 90,000

Open Weekends? Yes

Number of PCs 337

Number of walk-in refrigeration/freezerunits 0

Presence of cooking facilities Yes

Percent Cooled 100

Percent Heated 100

Monthso N/A

High School? No

School Districto N/A

Energy Performance ComparisonEvaluation Periods Comparisons

Performance Metrics Current(Ending Date 12/31/2008)

Baseline(Ending Date 12/31/2008) Rating of 75 Target National Average

Energy Performance Rating 3 3 75 N/A 50

Energy Intensity

Site (kBtu/ft2) 123 123 53 N/A 68

Source (kBtu/ft2) 324 324 140 N/A 179

Energy Cost

$/year $ 385,690.72 $ 385,690.72 $ 166,357.34 N/A $ 212,719.22

$/ft2/year $ 4.29 $ 4.29 $ 1.85 N/A $ 2.37

Greenhouse Gas Emissions

MtCO2e/year 1,277 1,277 551 N/A 704

kgCO2e/ft2/year 14 14 6 N/A 8

More than 50% of your building is defined as K-12 School. Please note that your rating accounts for all of the spaces listed. The National Average column presentsenergy performance data your building would have if your building had an average rating of 50. Notes:o - This attribute is optional.d - A default value has been supplied by Portfolio Manager.

Page 166: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

OMB No. 2060-0347

STATEMENT OF ENERGY PERFORMANCEApplegate Elementary School

Building ID: 1765846 For 12-month Period Ending: December 31, 20081

Date SEP becomes ineligible: N/A Date SEP Generated: June 25, 2009

FacilityApplegate Elementary School47 Jeanne Brennan Drive Freehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

Year Built: 1975Gross Floor Area (ft2): 81,963

Energy Performance Rating2 (1-100) 57

Site Energy Use Summary3

Natural Gas (kBtu)4 2,740,336 Electricity (kBtu) 3,228,721 Total Energy (kBtu) 5,969,057

Energy Intensity5 Site (kBtu/ft2/yr) 76 Source (kBtu/ft2/yr) 172 Emissions (based on site energy use) Greenhouse Gas Emissions (MtCO2e/year) 637 Electric Distribution Utility Jersey Central Power & Lt Co National Average Comparison National Average Site EUI 82 National Average Source EUI 184 % Difference from National Average Source EUI -7% Building Type K-12

School

Stamp of Certifying Professional

Based on the conditions observed at thetime of my visit to this building, I certify that

the information contained within thisstatement is accurate.

Meets Industry Standards6 for Indoor EnvironmentalConditions:Ventilation for Acceptable Indoor Air Quality N/A Acceptable Thermal Environmental Conditions N/A Adequate Illumination N/A

Certifying ProfessionalMatthew Goss15 British American Blvd Latham, NY 12110

Notes: 1. Application for the ENERGY STAR must be submitted to EPA within 4 months of the Period Ending date. Award of the ENERGY STAR is not final until approval is received from EPA.2. The EPA Energy Performance Rating is based on total source energy. A rating of 75 is the minimum to be eligible for the ENERGY STAR.3. Values represent energy consumption, annualized to a 12-month period.4. Natural Gas values in units of volume (e.g. cubic feet) are converted to kBtu with adjustments made for elevation based on Facility zip code.5. Values represent energy intensity, annualized to a 12-month period.6. Based on Meeting ASHRAE Standard 62 for ventilation for acceptable indoor air quality, ASHRAE Standard 55 for thermal comfort, and IESNA Lighting Handbook for lighting quality.

The government estimates the average time needed to fill out this form is 6 hours (includes the time for entering energy data, PE facility inspection, and notarizing the SEP) and welcomessuggestions for reducing this level of effort. Send comments (referencing OMB control number) to the Director, Collection Strategies Division, U.S., EPA (2822T), 1200 Pennsylvania Ave., NW,Washington, D.C. 20460.

EPA Form 5900-16

Page 167: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

In order for a building to qualify for the ENERGY STAR, a Professional Engineer (PE) must validate the accuracy of the data underlying the building's energyperformance rating. This checklist is designed to provide an at-a-glance summary of a property's physical and operating characteristics, as well as its total energyconsumption, to assist the PE in double-checking the information that the building owner or operator has entered into Portfolio Manager.

Please complete and sign this checklist and include it with the stamped, signed Statement of Energy Performance.NOTE: You must check each box to indicate that each value is correct, OR include a note.

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Building Name Applegate Elementary

School Is this the official building name to be displayed inthe ENERGY STAR Registry of LabeledBuildings?

Type K-12 School Is this an accurate description of the space inquestion?

Location 47 Jeanne Brennan Drive ,

Freehold, NJ 07728 Is this address accurate and complete? Correctweather normalization requires an accurate zipcode.

Single Structure Single Facility

Does this SEP represent a single structure? SEPscannot be submitted for multiple-buildingcampuses (with the exception of acute care orchildren's hospitals) nor can they be submitted asrepresenting only a portion of a building

Applegate Elementary School (K-12 School)

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Gross Floor Area 81,963 Sq. Ft.

Does this square footage include all supportingfunctions such as kitchens and break rooms usedby staff, storage areas, administrative areas,elevators, stairwells, atria, vent shafts, etc. Alsonote that existing atriums should only include thebase floor area that it occupies. Interstitial(plenum) space between floors should not beincluded in the total. Finally gross floor area is notthe same as leasable space. Leasable space is asubset of gross floor area.

Open Weekends? Yes

Is this building normally open at all on theweekends? This includes activities beyond thework conducted by maintenance, cleaning, andsecurity personnel. Weekend activity couldinclude any time when the space is used forclasses, performances or other school orcommunity activities. If the building is open on theweekend as part of the standard schedule duringone or more seasons, the building should select?yes? for open weekends. The ?yes? responseshould apply whether the building is open for oneor both of the weekend days.

Number of PCs 337 Is this the number of personal computers in theK12 School?

Number of walk-inrefrigeration/freezer

units 0

Is this the total number of commercial walk-in typefreezers and coolers? These units are typicallyfound in storage and receiving areas.

Presence ofcooking facilities Yes

Does this school have a dedicated space in whichfood is prepared and served to students? If theschool has space in which food for students isonly kept warm and/or served to students, or hasonly a galley that is used by teachers and staffthen the answer is "no".

Percent Cooled 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalcooling equipment?

Percent Heated 100 % Is this the percentage of the total floor spacewithin the facility that is served by mechanicalheating equipment?

Page 1 of 4

Page 168: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Months N/A(Optional) Is this school in operation for at least 8 months ofthe year?

High School? No

Is this building a high school (teaching grades 10,11, and/or 12)? If the building teaches to highschool students at all, the user should check 'yes'to 'high school'. For example, if the school teachesto grades K-12 (elementary/middle and highschool), the user should check 'yes' to 'highschool'.

Page 2 of 4

Page 169: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

ENERGY STAR®

Data Checklistfor Commercial Buildings

Energy ConsumptionPower Generation Plant or Distribution Utility: Jersey Central Power & Lt Co

Fuel Type: Electricity

Meter: G21139853 (kWh)Space(s): Entire Facility

Start Date End Date Energy Use (kWh)

11/08/2008 12/07/2008 73,600.00

10/08/2008 11/07/2008 75,600.00

09/08/2008 10/07/2008 84,000.00

08/08/2008 09/07/2008 82,000.00

07/08/2008 08/07/2008 80,800.00

06/08/2008 07/07/2008 63,200.00

05/08/2008 06/07/2008 100,800.00

04/08/2008 05/07/2008 78,400.00

03/08/2008 04/07/2008 74,000.00

02/08/2008 03/07/2008 83,200.00

01/08/2008 02/07/2008 87,200.00

G21139853 Consumption (kWh) 882,800.00

G21139853 Consumption (kBtu) 3,012,113.60

Total Electricity Consumption (kBtu) 3,012,113.60

Is this the total Electricity consumption at this building including all Electricity meters?

Fuel Type: Natural Gas

Meter: 00500524 (therms)Space(s): Entire Facility

Start Date End Date Energy Use (therms)

11/30/2008 12/29/2008 6,095.65

10/30/2008 11/29/2008 2,703.45

09/30/2008 10/29/2008 885.00

08/30/2008 09/29/2008 212.00

07/30/2008 08/29/2008 94.00

06/30/2008 07/29/2008 72.00

05/30/2008 06/29/2008 784.00

04/30/2008 05/29/2008 1,154.00

03/30/2008 04/29/2008 3,358.00

03/01/2008 03/29/2008 4,816.00

Page 3 of 4

Page 170: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

01/30/2008 02/29/2008 6,668.00

00500524 Consumption (therms) 26,842.10

00500524 Consumption (kBtu) 2,684,210.00

Total Natural Gas Consumption (kBtu) 2,684,210.00

Is this the total Natural Gas consumption at this building including all Natural Gas meters?

Additional FuelsDo the fuel consumption totals shown above represent the total energy use of this building?Please confirm there are no additional fuels (district energy, generator fuel oil) used in this facility.

Certifying Professional (When applying for the ENERGY STAR, this must be the same PE that signed and stamped the SEP.)

Name: _____________________________________________ Date: _____________

Signature: ______________________________________ Signature is required when applying for the ENERGY STAR.

Page 4 of 4

Page 171: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

FOR YOUR RECORDS ONLY. DO NOT SUBMIT TO EPA.

Please keep this Facility Summary for your own records; do not submit it to EPA. Only the Statement of Energy Performance(SEP), Data Checklist and Letter of Agreement need to be submitted to EPA when applying for the ENERGY STAR.

FacilityApplegate Elementary School47 Jeanne Brennan Drive Freehold, NJ 07728

Facility OwnerFreehold Township School District384 West Main Street Freehold, NJ 07728

Primary Contact for this FacilityIlene Tepper384 West Main Street Freehold, NJ 07728

General InformationApplegate Elementary School

Gross Floor Area Excluding Parking: (ft2) 81,963 Year Built 1975 For 12-month Evaluation Period Ending Date: December 31, 2008

Facility Space Use SummaryApplegate Elementary School

Space Type K-12 School

Gross Floor Area(ft2) 81,963

Open Weekends? Yes

Number of PCs 337

Number of walk-in refrigeration/freezerunits 0

Presence of cooking facilities Yes

Percent Cooled 100

Percent Heated 100

Monthso N/A

High School? No

School Districto N/A

Energy Performance ComparisonEvaluation Periods Comparisons

Performance Metrics Current(Ending Date 12/31/2008)

Baseline(Ending Date 12/31/2008) Rating of 75 Target National Average

Energy Performance Rating 57 57 75 N/A 50

Energy Intensity

Site (kBtu/ft2) 76 76 64 N/A 82

Source (kBtu/ft2) 172 172 144 N/A 184

Energy Cost

$/year $ 209,046.47 $ 209,046.47 $ 175,082.59 N/A $ 223,876.54

$/ft2/year $ 2.55 $ 2.55 $ 2.14 N/A $ 2.73

Greenhouse Gas Emissions

MtCO2e/year 637 637 534 N/A 682

kgCO2e/ft2/year 8 8 7 N/A 9

More than 50% of your building is defined as K-12 School. Please note that your rating accounts for all of the spaces listed. The National Average column presentsenergy performance data your building would have if your building had an average rating of 50. Notes:o - This attribute is optional.d - A default value has been supplied by Portfolio Manager.

Page 172: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

1

Portfolio Manager is an interactive energy management tool that allows you to track and assess energy and water consumption across your entire portfolio of buildings in a secure online environment. Use this Quick Reference Guide to identify opportunities for energy efficiency improvements, track your progress over time, and verify results.

PoRtfolio ManaGeR QUick RefeRence GUide

IdentIfy energy effIcIency projectsUse Portfolio Manager to identify under-performing buildings to target for energy efficiency improvements and establish baselines for setting and measuring progress for energy efficiency improvement projects over time.

step ActIvIty ActIon

access Portfolio Manager. (step not shown)

Visit www.energystar.gov/benchmark.Scroll down to the Login section on the right-hand side in the middle of the page.

access your account: (step not shown)

• Create a new account.• Login to an existing account.

• Click regIster, and follow instructions.• Enter user name and password, and click LogIn.

Review system updates and enter account.(step not shown) click Access My portfoLIo, located below Welcome to portfolio Manager.

add a new facility. (step not shown) click Add a Property, located in the upper right portion of the screen.

Select property type and entergeneral facility information.(step not shown)

Select the option that most closely resembles your facility and click contInUe. enter general data and click sAveAveA . for more information on facility space types, see: www.energystar.gov/index.cfm?c=eligibility.bus_portfoliomanager_space_types.

enter space use data.

from the facility summary page, shown above, go to the space Use section, located half way down the page, and click Add spAspAsp ce.• Enter a facility name. In the select a space typetypet menu, select the appropriate

space type(s) for your building. if your space is not listed, select other. click contInUe.• Enter building characteristics. Click sAveAveA . information required for each space type is listed here: www.energystar.gov/index.cfm?c=eligibility.bus_

portfoliomanager_space_types.• Repeat steps above to add all major spaces in your facility.

Use bulk import service to minimize manual data entry of large sets of facility data (10 or more facilities or campuses are required). • Go back to My portfolio by clicking on the link in the upper left portion of the page.• Click IMport facility data Using templates, located below templates, located below t Add a property.

enter energy use data.

from the facility summary page, go to the energy Meters section, located below the space Use section, and click Add Meter. • Enter meter name, type, and units. Click sAveAveA . • Enter number of months and start date. Click contInUe. • Enter energy use and cost for each month. Click sAveAveA . • Repeat for all energy meters and fuel types.

1

2

3

4

5

ww

w.e

nerg

ysta

r.gov

/ben

chm

ark

6

7

7

6

Page 173: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

2

step ActIvIty ActIon

create custom groups.

organize facilities into groups (e.g., fire Stations, northwest Region). Groups are completely customizable, and each facility may belong to multiple groups.• From the My portfolio page, click creAteAteA groUp, located directly to the right

of the group drop-down menu.• Follow instructions to select buildings and name your group. • Once they have been saved, custom groups will be available in the group drop-

down menu.

View and interpret results.

option 1: Go to My portfolio and view all buildings to compare performance metrics.

Option 2: Export data to Microsoft® Excel.

• On the My portfolio page, select the view, from the view drop-down menu that will display the data you wish to export. The My portfolio page will update to display the selected view. (9a)

• Select the doWnLoAd In exceL link. a file download dialog window will open. Follow the steps provided by Excel. (9b)• Use Excel functionality to view building energy performance graphically . The example below shows a comparison of Energy Use Intensity for a portfolio of fire stations, identifying under-performing buildings to target for energy eficiency improvements.

9

Fire Stations - EUI Comparison

0

50

100

150

200

250

300

350

Fire Statio

n 1

Fire Statio

n 2

Fire Statio

n 3

Fire Statio

n 4

Fire Statio

n 5

Fire Statio

n 6

Fire Statio

n 7

Fire Statio

n 8

Fire Statio

n 9

Fire Statio

n 10

Fire Stations

Curr

ent W

eath

er

Nor

mal

ized

Sou

rce

Ener

gy

Use

Inte

nsity

(k

BTU

/SF)

8

ActIon

8

ww

w.e

nerg

ysta

r.gov

/ben

chm

ark

9b

9a

Page 174: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

3

trAck progress over tIMe Portfolio Manager comes pre-populated with nine standard summary views of facility data, which are displayed on the My Portfolio summary page. these standard views include:

• Summary: Energy Use• Performance: Green House

Gas emissions• Performance: Financial• Performance: Water Use

additionally, users can create and save custom downloadable views by choosing from more than 70 different metrics. the default view set by the user will display automatically after logging into Portfolio Manager, and data from all views can be exported to Microsoft® Excel.

ww

w.e

nerg

ysta

r.gov

/ben

chm

ark

creAte A cUstoM vIeW

step ActIon

from the My portfolio page or the facility summary page, select the create view link, located directly to the right of the view drop-down menu.

Enter a name for the view. To set as the default view, select the box labeled set this view as My portfolio default, located directly to the right of view name. You may include up to 7 (seven) columns in each view.

choose each metric to be included in the view by selecting an order number from the preferred column order drop-down menu to the left of the facility data column.

click sAveAveA at the bottom of the page. You will be returned to the My portfolio page, and your custom view will be available in the view drop-down menu. (step not shown)

4

3

1

2

ww

w.e

nerg

ysta

r.gov

/ben

chm

ark

2

3

1

Page 175: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

4

verIfy And docUMent resULtsUse Portfolio Manager to quickly and accurately document reductions in energy use, greenhouse gas emissions, water use, and energy costs for an individual building or an entire portfolio. this valuable information can be used to provide a level of transparency and accountability to help demonstrate strategic use of funding.

Generate a Statement of energy Performance that includes valuable information about your building’s performance, including:

• Normalized energy use intensity • National average comparisons • Greenhouse gas emissions • Energy performance rating (if available)

in addition, you can also request an energy Performance Report to see the change in performance over time for selected buildings or an entire portfolio. available comparative metrics in this report include:

• Normalized energy use intensity • Total electric use • Total natural gas use • Energy performance rating (if available)

ww

w.e

nerg

ysta

r.gov

/ben

chm

ark

generAte A stAteMent of energy perforMAnce And An energy perforMAnce report

step ActIon

from your selected building’s facility summary page, click generAte A Ate A A stAtAt teAteA Ment of energy perforMAnce.

On the next page, select a period ending date. (step not shown)

click generAteAteA report,report,report located in the bottom right corner of the screen. (step not shown)

Save the Statement of energy Performance, accompanying data checklist, and facility Summary that include information on energy use intensity and greenhouse gas emissions.

from the My portfolio page, click reQUest energy perforMAnce report, located under Work with facilities, which shows reductions in key performance indicators over a user-specified time period. Specify the type of report, the facilities to be included, and the requested report columns. the report will be e-mailed to a user-specified address within one business day. (step not shown)

4

5

3

1

2

1

4

Page 176: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

APPENDIX C

CHVAC MODEL RESULTS

Page 177: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 178: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Applegate Elementary School - Baseline Design Run Date/Time: 06/29/09 @ 16:10

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

20

40

60

80

100

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0

200

400

600

800

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.10 0.99 7.80 24.89 35.34 32.12 14.15 5.64 0.25 0.08 121.37 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 19.34 15.65 13.56 7.72 1.68 0.12 0.06 0.03 0.36 3.29 9.18 16.59 87.59 HP Supp. - - - - - - - - - - - - - Hot Water 2.84 2.75 3.02 2.58 2.60 1.81 1.10 1.03 1.92 2.33 2.24 2.66 26.88 Vent. Fans 5.96 5.24 5.51 5.24 4.74 5.58 6.44 5.88 5.24 5.03 5.08 5.92 65.86 Pumps & Aux. 0.26 0.23 0.24 0.21 0.15 0.17 0.19 0.17 0.16 0.17 0.21 0.26 2.42 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 39.97 37.68 41.66 36.39 39.97 30.96 21.01 20.33 36.38 41.66 36.39 39.97 422.37 Task Lights - - - - - - - - - - - - - Area Lights 21.78 20.54 22.70 19.83 21.78 16.84 11.39 11.03 19.81 22.70 19.83 21.78 230.04 Total 90.14 82.09 86.80 72.97 78.72 80.38 75.53 70.59 78.03 80.83 73.19 87.26 956.53

Gas Consumption (Btu x000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 737.2 597.0 520.1 311.5 85.6 23.9 20.8 15.0 40.5 151.6 353.9 630.2 3,487.5 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 2.2 2.1 2.3 2.0 2.2 1.7 1.0 1.0 2.0 2.3 2.0 2.2 23.2 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 739.4 599.1 522.5 313.6 87.9 25.5 21.8 15.9 42.5 154.0 355.9 632.5 3,510.7

Page 179: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Applegate Elementary School - 1 Run Date/Time: 06/29/09 @ 16:26

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

20

40

60

80

100

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0

200

400

600

800

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.10 0.97 7.66 24.46 34.75 31.60 13.91 5.54 0.25 0.08 119.30 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 19.03 15.43 13.40 7.68 1.70 0.13 0.06 0.03 0.36 3.29 9.09 16.35 86.55 HP Supp. - - - - - - - - - - - - - Hot Water 2.84 2.75 3.02 2.58 2.60 1.81 1.11 1.03 1.92 2.33 2.24 2.66 26.88 Vent. Fans 5.83 5.13 5.40 5.14 4.64 5.47 6.31 5.76 5.14 4.93 4.98 5.81 64.54 Pumps & Aux. 0.26 0.23 0.24 0.20 0.14 0.16 0.18 0.17 0.15 0.17 0.21 0.25 2.37 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 39.97 37.68 41.66 36.39 39.97 30.96 21.01 20.33 36.38 41.66 36.39 39.97 422.37 Task Lights - - - - - - - - - - - - - Area Lights 21.78 20.54 22.70 19.83 21.78 16.84 11.39 11.03 19.81 22.70 19.83 21.78 230.04 Total 89.71 81.75 86.52 72.81 78.49 79.84 74.80 69.94 77.68 80.62 72.99 86.90 952.05

Gas Consumption (Btu x000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 731.0 592.0 515.9 309.5 85.2 23.7 20.5 14.7 40.1 150.5 351.1 624.4 3,458.5 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 2.2 2.1 2.3 2.0 2.2 1.7 1.0 1.0 2.0 2.3 2.0 2.2 23.2 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 733.2 594.1 518.2 311.5 87.5 25.3 21.5 15.6 42.1 152.9 353.1 626.7 3,481.7

AMORK
Text Box
Window Upgrade
Page 180: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Applegate Elementary School - 2 Run Date/Time: 06/29/09 @ 16:27

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

20

40

60

80

100

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0

100

200

300

400

500

600

700

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.10 0.99 7.67 23.91 33.58 30.68 13.89 5.57 0.25 0.08 116.73 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 19.33 15.65 13.56 7.72 1.68 0.12 0.06 0.03 0.36 3.29 9.18 16.59 87.59 HP Supp. - - - - - - - - - - - - - Hot Water 2.84 2.75 3.02 2.58 2.60 1.81 1.10 1.03 1.92 2.33 2.24 2.66 26.88 Vent. Fans 6.87 6.07 6.40 6.02 5.12 6.20 7.27 6.70 5.64 5.55 5.91 6.86 74.62 Pumps & Aux. 0.40 0.36 0.38 0.33 0.21 0.26 0.32 0.30 0.22 0.25 0.34 0.40 3.77 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 39.97 37.68 41.66 36.39 39.97 30.96 21.01 20.33 36.38 41.66 36.39 39.97 422.37 Task Lights - - - - - - - - - - - - - Area Lights 21.78 20.54 22.70 19.83 21.78 16.84 11.39 11.03 19.81 22.70 19.83 21.78 230.04 Total 91.20 83.04 87.82 73.88 79.03 80.11 74.73 70.11 78.23 81.35 74.15 88.34 961.99

Gas Consumption (Btu x000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 678.0 546.3 472.2 279.6 77.7 23.1 20.1 14.8 37.1 137.0 319.2 576.8 3,181.8 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 2.2 2.1 2.3 2.0 2.2 1.7 1.0 1.0 2.0 2.3 2.0 2.2 23.2 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 680.2 548.4 474.5 281.6 79.9 24.8 21.1 15.8 39.1 139.4 321.3 579.0 3,205.0

AMORK
Text Box
ERV Addition
Page 181: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Barkalow Middle School - Baseline Design Run Date/Time: 06/29/09 @ 11:36

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

20

40

60

80

100

120

140

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0.0

0.5

1.0

1.5

2.0

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.5 2.6 17.9 45.5 56.3 50.1 28.9 13.3 0.9 0.4 216.4 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 4.1 3.3 2.8 1.7 0.3 0.0 0.0 0.0 0.1 0.6 1.9 3.6 18.4 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans 9.4 8.2 8.7 8.5 8.3 8.8 9.1 8.3 8.7 8.5 8.1 9.3 104.0 Pumps & Aux. 1.1 1.0 1.1 0.9 0.6 0.5 0.6 0.5 0.6 0.7 0.9 1.1 9.7 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 65.0 61.2 67.7 59.2 65.0 50.5 34.5 33.4 59.2 67.7 59.2 65.0 687.7 Task Lights - - - - - - - - - - - - - Area Lights 32.7 30.8 34.1 29.8 32.7 25.4 17.3 16.7 29.8 34.1 29.8 32.7 345.7 Total 112.3 104.6 114.8 102.6 124.8 130.8 117.8 109.1 127.2 124.9 100.8 112.1 1,381.9

Gas Consumption (Btu x000,000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 1.52 1.22 1.06 0.69 0.21 0.09 0.08 0.07 0.12 0.35 0.79 1.32 7.53 HP Supp. - - - - - - - - - - - - - Hot Water 0.03 0.03 0.03 0.03 0.03 0.02 0.01 0.01 0.02 0.03 0.02 0.03 0.30 Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 1.55 1.26 1.09 0.72 0.24 0.11 0.10 0.08 0.14 0.38 0.82 1.36 7.84

Page 182: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Barkalow Middle School - 1 Run Date/Time: 06/29/09 @ 11:36

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

20

40

60

80

100

120

140

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.5 2.6 17.9 45.5 56.3 50.1 28.9 13.3 0.9 0.4 216.4 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 4.6 3.7 3.2 2.0 0.5 0.2 0.2 0.1 0.2 0.8 2.2 4.0 21.6 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans 9.4 8.2 8.7 8.5 8.3 8.8 9.1 8.3 8.7 8.5 8.1 9.3 104.1 Pumps & Aux. 1.2 1.1 1.1 1.0 0.7 0.6 0.6 0.6 0.6 0.8 1.0 1.2 10.4 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 65.0 61.2 67.7 59.2 65.0 50.5 34.5 33.4 59.2 67.7 59.2 65.0 687.7 Task Lights - - - - - - - - - - - - - Area Lights 32.7 30.8 34.1 29.8 32.7 25.4 17.3 16.7 29.8 34.1 29.8 32.7 345.7 Total 112.8 105.0 115.2 103.0 125.0 131.0 118.1 109.3 127.4 125.2 101.2 112.6 1,385.8

Gas Consumption (Btu x000,000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 1.42 1.14 0.98 0.62 0.17 0.06 0.05 0.04 0.09 0.30 0.72 1.23 6.84 HP Supp. - - - - - - - - - - - - - Hot Water 0.03 0.03 0.03 0.03 0.03 0.02 0.01 0.01 0.02 0.03 0.02 0.03 0.30 Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 1.46 1.17 1.01 0.65 0.20 0.08 0.06 0.05 0.11 0.33 0.75 1.26 7.15

AMORK
Text Box
Boiler Upgrade
Page 183: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Donovan School - Baseline Design Run Date/Time: 06/26/09 @ 11:30

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

50

100

150

200

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0

100

200

300

400

500

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.1 0.8 7.4 23.8 33.7 30.8 14.0 5.1 0.2 0.1 116.0 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 111.1 90.3 77.0 47.4 9.7 0.5 0.0 0.0 2.4 19.0 55.4 97.0 509.7 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans 6.7 6.0 6.4 6.4 6.8 7.7 7.7 7.0 7.6 6.9 6.1 6.8 82.0 Pumps & Aux. 1.1 1.0 1.0 0.7 0.1 0.0 0.0 0.0 0.0 0.3 0.8 1.1 6.2 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 24.1 22.7 26.1 21.9 24.1 26.0 26.1 25.1 24.9 25.1 21.9 24.1 291.9 Task Lights - - - - - - - - - - - - - Area Lights 24.8 23.4 26.9 22.6 24.8 26.8 26.9 25.9 25.7 25.9 22.6 24.8 301.1 Total 167.8 143.3 137.4 99.8 72.9 84.7 94.4 88.7 74.7 82.3 107.0 153.8 1,306.9

Gas Consumption (Btu x000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 428.8 341.2 280.5 169.2 35.7 1.8 0.4 - 8.9 69.6 209.3 360.1 1,905.6 HP Supp. - - - - - - - - - - - - - Hot Water 18.2 17.7 20.3 16.7 16.9 16.8 15.6 14.3 14.3 15.1 14.4 17.1 197.5 Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 3.9 3.7 4.3 3.5 3.9 4.3 4.3 4.1 4.1 4.1 3.5 3.9 47.3 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 450.9 362.6 305.2 189.5 56.6 22.8 20.3 18.4 27.3 88.8 227.2 381.0 2,150.5

Page 184: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Early Childhood Learning Center - Baseline Design Run Date/Time: 06/26/09 @ 10:12

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

10

20

30

40

50

60

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0

200

400

600

800

1000

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.63 2.72 14.48 27.42 32.04 28.51 21.46 12.06 1.00 0.54 140.87 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat - - - - - - - - - - - - - HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans 4.97 4.10 3.94 4.40 8.39 9.28 7.69 6.82 10.97 7.56 3.73 4.57 76.43 Pumps & Aux. 1.71 1.56 1.70 1.66 1.00 0.11 0.02 0.01 0.56 1.27 1.61 1.78 13.00 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 13.03 12.29 13.58 14.07 13.03 4.18 2.05 2.05 6.38 13.58 11.87 13.03 119.15 Task Lights - - - - - - - - - - - - - Area Lights 16.93 15.95 17.63 18.25 16.93 5.51 2.77 2.77 8.34 17.63 15.42 16.93 155.04 Total 36.64 33.89 37.49 41.10 53.84 46.50 44.56 40.15 47.71 52.10 33.63 36.85 504.49

Gas Consumption (Btu x000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 856.7 706.6 623.5 436.9 154.7 9.1 1.0 0.1 62.2 227.2 458.2 736.9 4,273.2 HP Supp. - - - - - - - - - - - - - Hot Water 4.9 4.8 5.3 5.3 4.5 1.4 0.7 0.6 1.9 4.1 3.9 4.6 41.8 Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 2.9 2.8 3.0 3.2 2.9 0.6 0.0 0.0 1.2 3.0 2.6 2.9 25.2 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 864.5 714.1 631.8 445.4 162.2 11.1 1.6 0.8 65.3 234.3 464.7 744.4 4,340.1

Page 185: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Early Childhood Learning Center - 1 Run Date/Time: 06/30/09 @ 10:41

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

10

20

30

40

50

60

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0

200

400

600

800

1000

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.63 2.68 14.25 28.49 32.53 28.91 21.56 11.97 1.01 0.54 142.57 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat - - - - - - - - - - - - - HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans 4.67 3.89 3.80 4.34 8.35 11.52 8.92 7.94 11.65 7.52 3.66 4.37 80.63 Pumps & Aux. 1.71 1.56 1.70 1.66 1.00 0.11 0.02 0.01 0.56 1.27 1.61 1.78 13.00 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 13.03 12.29 13.58 14.07 13.03 4.18 2.05 2.05 6.38 13.58 11.87 13.03 119.15 Task Lights - - - - - - - - - - - - - Area Lights 16.93 15.95 17.63 18.25 16.93 5.51 2.77 2.77 8.34 17.63 15.42 16.93 155.04 Total 36.34 33.69 37.35 41.00 53.56 49.81 46.29 41.68 48.49 51.98 33.57 36.64 510.39

Gas Consumption (Btu x000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 801.8 665.5 588.7 414.3 149.4 9.0 1.0 0.1 60.2 215.4 431.7 690.8 4,027.9 HP Supp. - - - - - - - - - - - - - Hot Water 4.9 4.7 5.2 5.3 4.5 1.4 0.7 0.6 1.9 4.0 3.8 4.6 41.7 Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 2.9 2.8 3.0 3.2 2.9 0.6 0.0 0.0 1.2 3.0 2.6 2.9 25.2 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 809.5 673.0 597.0 422.8 156.8 11.0 1.7 0.8 63.3 222.4 438.2 698.3 4,094.8

AMORK
Text Box
Roof Insulation
Page 186: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Eisenhower Middle School - Baseline Design Run Date/Time: 06/25/09 @ 15:08

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

100

200

300

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0

100

200

300

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.2 2.1 17.8 46.9 58.9 53.5 30.0 12.8 0.4 0.1 222.8 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 116.8 91.9 77.9 47.4 12.2 1.1 0.3 0.0 3.9 20.8 52.6 98.6 523.4 HP Supp. 30.7 17.9 9.0 1.8 - - - - - - 2.1 14.5 76.0 Hot Water 5.5 5.4 6.1 5.1 5.1 3.6 2.2 2.0 3.8 4.6 4.5 5.2 52.9 Vent. Fans 22.5 20.4 22.4 22.3 21.4 22.4 23.3 21.3 22.4 22.3 21.3 23.5 265.5 Pumps & Aux. 1.4 1.3 1.3 1.1 0.8 0.7 0.7 0.7 0.7 0.9 1.2 1.4 12.3 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 48.2 45.4 52.2 43.9 48.2 37.4 25.5 24.7 43.9 50.2 45.9 48.2 513.4 Task Lights - - - - - - - - - - - - - Area Lights 37.7 35.6 40.9 34.4 37.7 29.3 19.9 19.3 34.4 39.3 36.0 37.7 402.1 Total 262.9 217.7 210.1 158.0 143.2 141.3 130.9 121.6 138.9 150.9 164.1 229.0 2,068.5

Gas Consumption (Btu x000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 273.6 223.1 182.1 105.9 22.9 3.6 1.7 0.4 6.3 45.3 137.6 237.3 1,239.9 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 12.0 11.4 13.2 10.8 12.0 8.9 5.4 5.2 10.8 12.6 11.4 12.0 125.6 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 285.6 234.5 195.3 116.7 34.9 12.5 7.1 5.6 17.1 57.9 149.0 249.3 1,365.6

Page 187: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Errickson Elementary - Baseline Design Run Date/Time: 06/29/09 @ 14:56

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

20

40

60

80

100

120

140

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0.0

0.2

0.4

0.6

0.8

1.0

1.2

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.2 1.2 10.3 33.4 47.2 42.1 18.4 7.6 0.3 0.1 160.8 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 23.3 19.2 17.1 10.5 3.2 0.3 0.1 0.0 1.2 4.9 11.7 20.3 111.8 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans 12.6 11.3 12.1 11.4 9.7 9.9 10.6 9.6 9.6 10.4 11.2 12.8 131.1 Pumps & Aux. 0.4 0.4 0.4 0.3 0.2 0.2 0.2 0.2 0.2 0.2 0.3 0.4 3.4 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 47.1 44.4 49.0 42.9 47.1 50.8 51.0 49.0 48.8 49.0 42.9 47.1 569.0 Task Lights - - - - - - - - - - - - - Area Lights 20.2 19.0 21.0 18.4 20.2 21.7 21.8 21.0 20.9 21.0 18.4 20.2 243.7 Total 103.5 94.2 99.8 84.7 90.5 116.3 130.9 121.9 99.1 93.1 84.8 100.8 1,219.8

Gas Consumption (Btu x000,000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 1.02 0.83 0.73 0.48 0.15 0.02 0.01 0.00 0.07 0.24 0.54 0.90 4.99 HP Supp. - - - - - - - - - - - - - Hot Water 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.14 Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. - - - - - - - - - - - - - Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 1.03 0.84 0.74 0.49 0.16 0.04 0.02 0.01 0.08 0.25 0.55 0.91 5.12

Page 188: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Errickson Elementary - 2 Run Date/Time: 06/29/09 @ 14:57

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

20

40

60

80

100

120

140

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0.0

0.2

0.4

0.6

0.8

1.0

1.2

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.1 1.2 9.8 32.4 45.8 40.9 17.8 7.2 0.3 0.1 155.6 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 23.3 19.2 17.1 10.5 3.2 0.3 0.1 0.0 1.2 4.9 11.7 20.3 111.8 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans 11.1 10.0 10.7 10.2 9.2 9.4 9.9 9.0 9.4 9.7 9.9 11.3 120.0 Pumps & Aux. 0.5 0.5 0.5 0.4 0.2 0.2 0.2 0.2 0.2 0.3 0.4 0.5 4.1 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 47.1 44.4 49.0 42.9 47.1 50.8 51.0 49.0 48.8 49.0 42.9 47.1 569.0 Task Lights - - - - - - - - - - - - - Area Lights 20.2 19.0 21.0 18.4 20.2 21.7 21.8 21.0 20.9 21.0 18.4 20.2 243.7 Total 102.2 93.0 98.5 83.5 89.7 114.8 128.9 120.2 98.2 92.2 83.5 99.5 1,204.2

Gas Consumption (Btu x000,000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 0.99 0.81 0.71 0.47 0.15 0.02 0.01 0.00 0.07 0.23 0.52 0.88 4.88 HP Supp. - - - - - - - - - - - - - Hot Water 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.14 Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. - - - - - - - - - - - - - Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 1.00 0.82 0.73 0.48 0.16 0.04 0.02 0.01 0.08 0.24 0.53 0.89 5.01

AMORK
Text Box
ERV Addition
Page 189: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: Errickson Elementary - 1 Run Date/Time: 06/29/09 @ 16:41

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

20

40

60

80

100

120

140

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0.0

0.2

0.4

0.6

0.8

1.0

1.2

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.2 1.2 10.1 33.0 46.7 41.6 18.1 7.4 0.3 0.1 158.7 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 23.1 19.1 17.0 10.5 3.2 0.3 0.1 0.0 1.2 4.9 11.6 20.1 111.1 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans 12.4 11.1 11.9 11.2 9.5 9.8 10.4 9.4 9.5 10.2 11.0 12.6 128.9 Pumps & Aux. 0.4 0.4 0.4 0.3 0.2 0.2 0.2 0.2 0.2 0.2 0.3 0.4 3.4 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 47.1 44.4 49.0 42.9 47.1 50.8 51.0 49.0 48.8 49.0 42.9 47.1 569.0 Task Lights - - - - - - - - - - - - - Area Lights 20.2 19.0 21.0 18.4 20.2 21.7 21.8 21.0 20.9 21.0 18.4 20.2 243.7 Total 103.1 93.9 99.5 84.5 90.2 115.7 130.2 121.3 98.6 92.8 84.5 100.5 1,214.8

Gas Consumption (Btu x000,000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 1.01 0.83 0.73 0.48 0.15 0.02 0.01 0.00 0.07 0.24 0.53 0.89 4.96 HP Supp. - - - - - - - - - - - - - Hot Water 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.14 Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. - - - - - - - - - - - - - Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 1.02 0.84 0.74 0.49 0.16 0.04 0.02 0.01 0.08 0.25 0.54 0.91 5.09

AMORK
Text Box
Window Upgrade
Page 190: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: JJ Catena School - Baseline Design Run Date/Time: 06/29/09 @ 11:15

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

20

40

60

80

100

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0.0

0.2

0.4

0.6

0.8

1.0

1.2

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.6 2.5 14.3 31.4 36.5 32.6 22.6 11.7 1.0 0.5 153.6 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.7 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans 8.7 7.6 8.2 8.0 7.5 7.8 8.2 7.6 7.8 7.9 7.7 8.7 95.8 Pumps & Aux. 2.6 2.3 2.4 1.9 1.1 0.8 0.8 0.7 0.8 1.4 2.1 2.6 19.5 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 47.3 44.6 51.3 51.0 47.3 35.6 23.1 22.4 42.6 49.3 43.1 47.3 504.8 Task Lights - - - - - - - - - - - - - Area Lights 25.7 24.2 27.9 27.7 25.7 19.3 12.4 12.1 23.1 26.8 23.4 25.7 274.2 Total 84.5 78.8 90.3 91.2 95.9 95.0 81.0 75.4 97.0 97.1 77.3 84.9 1,048.6

Gas Consumption (Btu x000,000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 1.09 0.90 0.79 0.45 0.15 0.10 0.10 0.10 0.08 0.21 0.52 0.94 5.43 HP Supp. - - - - - - - - - - - - - Hot Water 0.01 0.01 0.01 0.01 0.01 0.01 0.00 0.00 0.01 0.01 0.01 0.01 0.11 Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 0.01 0.00 0.01 0.01 0.01 0.00 0.00 0.00 0.00 0.01 0.00 0.01 0.05 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 1.10 0.91 0.81 0.47 0.16 0.11 0.11 0.11 0.10 0.22 0.54 0.96 5.60

Page 191: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: JJ Catena School - 1 Run Date/Time: 06/29/09 @ 11:17

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

20

40

60

80

100

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0.0

0.2

0.4

0.6

0.8

1.0

1.2

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.6 2.5 14.3 31.4 36.5 32.6 22.6 11.7 1.0 0.5 153.7 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 0.5 0.5 0.4 0.3 0.2 0.2 0.2 0.2 0.1 0.2 0.3 0.5 3.6 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans 9.4 8.2 8.2 8.0 7.5 7.8 8.2 7.7 7.8 7.9 7.7 9.0 97.4 Pumps & Aux. 2.8 2.5 2.6 2.1 1.2 0.8 0.9 0.8 0.9 1.6 2.3 2.9 21.4 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 47.3 44.6 51.3 51.0 47.3 35.6 23.1 22.4 42.6 49.3 43.1 47.3 504.8 Task Lights - - - - - - - - - - - - - Area Lights 25.7 24.2 27.9 27.7 25.7 19.3 12.4 12.1 23.1 26.8 23.4 25.7 274.2 Total 85.8 79.9 91.0 91.6 96.2 95.2 81.3 75.7 97.3 97.5 77.8 85.9 1,055.1

Gas Consumption (Btu x000,000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 1.00 0.83 0.72 0.39 0.11 0.07 0.08 0.07 0.06 0.17 0.46 0.86 4.83 HP Supp. - - - - - - - - - - - - - Hot Water 0.01 0.01 0.01 0.01 0.01 0.01 0.00 0.00 0.01 0.01 0.01 0.01 0.11 Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 0.01 0.00 0.01 0.01 0.01 0.00 0.00 0.00 0.00 0.01 0.00 0.01 0.05 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 1.02 0.84 0.74 0.41 0.13 0.08 0.08 0.08 0.07 0.18 0.48 0.88 5.00

AMORK
Text Box
Boiler Upgrade
Page 192: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Project/Run: JJ Catena School - 2 Run Date/Time: 06/29/09 @ 11:17

eQUEST 3.63.6500 Monthly Energy Consumption by Enduse Page 1

0

20

40

60

80

100

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Electric Consumption (kWh)

(x000)

0

200

400

600

800

1000

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Gas Consumption (Btu)

(x000,000)

Area LightingTask LightingMisc. Equipment

Exterior UsagePumps & Aux.Ventilation Fans

Water HeatingHt Pump Supp.Space Heating

RefrigerationHeat RejectionSpace Cooling

Electric Consumption (kWh x000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - 0.6 2.5 14.0 30.8 35.0 31.6 22.5 11.7 1.0 0.5 150.1 Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.7 HP Supp. - - - - - - - - - - - - - Hot Water - - - - - - - - - - - - - Vent. Fans 6.5 5.6 5.8 5.6 5.3 5.4 5.6 5.2 5.4 5.6 5.5 6.3 67.7 Pumps & Aux. 2.6 2.3 2.4 1.9 1.1 0.8 0.8 0.7 0.8 1.4 2.1 2.6 19.5 Ext. Usage - - - - - - - - - - - - - Misc. Equip. 47.3 44.6 51.3 51.0 47.3 35.6 23.1 22.4 42.6 49.3 43.1 47.3 504.8 Task Lights - - - - - - - - - - - - - Area Lights 25.7 24.2 27.9 27.7 25.7 19.3 12.4 12.1 23.1 26.8 23.4 25.7 274.2 Total 82.3 76.8 88.0 88.8 93.4 91.9 76.9 72.0 94.5 94.8 75.1 82.6 1,016.9

Gas Consumption (Btu x000,000)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Space Cool - - - - - - - - - - - - - Heat Reject. - - - - - - - - - - - - - Refrigeration - - - - - - - - - - - - - Space Heat 970.5 803.9 713.4 413.8 139.6 99.1 103.3 100.3 83.1 198.4 473.6 840.1 4,939.1 HP Supp. - - - - - - - - - - - - - Hot Water 11.8 11.5 13.2 12.9 11.0 7.5 4.3 4.0 8.0 9.8 9.3 11.0 114.3 Vent. Fans - - - - - - - - - - - - - Pumps & Aux. - - - - - - - - - - - - - Ext. Usage - - - - - - - - - - - - - Misc. Equip. 5.2 4.9 5.7 5.7 5.2 3.9 2.3 2.2 4.7 5.4 4.7 5.2 55.0 Task Lights - - - - - - - - - - - - - Area Lights - - - - - - - - - - - - - Total 987.5 820.3 732.3 432.3 155.8 110.5 109.9 106.5 95.8 213.6 487.5 856.3 5,108.3

AMORK
Text Box
Control Change
Page 193: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 194: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

APPENDIX D

LIGHTING SPREADSHEET - OPTION 1

Page 195: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 196: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

1 D.D. Eisenhower

Lobby Recessed Can Can w/ (2) 13w CF PL 3 26 0.08 3,640 284 No Work Proposed 0 26 0.08 3,640 284 NO SENSOR PROPOSED 0 - - - - -$

2D.D.

EisenhowerLobby

4X4 recessed troffer with (6) F32 T8 Lamps & (2) 3-Light Electronic ballasts

8 178 1.42 3,640 5,183 No Work Proposed 0 178 1.42 3,640 5183 NO SENSOR PROPOSED 0 - - - - -$

3D.D.

EisenhowerCorridor 1

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

9 110 0.99 3,640 3,604 No Work Proposed 0 110 0.99 3,640 3604 NO SENSOR PROPOSED 0 - - - - -$

4 D.D. Eisenhower

Corridor 1 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

5D.D.

EisenhowerCorridor 2

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 3,640 2,803 No Work Proposed 0 110 0.77 3,640 2803 NO SENSOR PROPOSED 0 - - - - -$

6 D.D. Eisenhower

Corridor 2 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

7D.D.

EisenhowerCorridor 3

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

16 110 1.76 3,640 6,406 No Work Proposed 0 110 1.76 3,640 6406 NO SENSOR PROPOSED 0 - - - - -$

8 D.D. Eisenhower

Corridor 3 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

9D.D.

EisenhowerCorridor 4

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

6 110 0.66 3,640 2,402 No Work Proposed 0 110 0.66 3,640 2402 NO SENSOR PROPOSED 0 - - - - -$

10D.D.

EisenhowerCorridor 4

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 No Work Proposed 0 61 0.24 3,640 888 NO SENSOR PROPOSED 0 - - - - -$

11 D.D. Eisenhower

Corridor 4 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

12D.D.

EisenhowerCorridor 5

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

13 110 1.43 3,640 5,205 No Work Proposed 0 110 1.43 3,640 5205 NO SENSOR PROPOSED 0 - - - - -$

13 D.D. Eisenhower

Corridor 5 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

14D.D.

EisenhowerCorridor 6

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

11 110 1.21 3,640 4,404 No Work Proposed 0 110 1.21 3,640 4404 NO SENSOR PROPOSED 0 - - - - -$

15 D.D. Eisenhower

Corridor 6 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

16D.D.

EisenhowerCorridor 7

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

9 110 0.99 3,640 3,604 No Work Proposed 0 110 0.99 3,640 3604 NO SENSOR PROPOSED 0 - - - - -$

17 D.D. Eisenhower

Corridor 7 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

18D.D.

EisenhowerCorridor 8

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

24 110 2.64 3,640 9,610 No Work Proposed 0 110 2.64 3,640 9610 NO SENSOR PROPOSED 0 - - - - -$

19 D.D. Eisenhower

Corridor 8 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

20D.D.

EisenhowerCorridor 9

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

13 110 1.43 3,640 5,205 No Work Proposed 0 110 1.43 3,640 5205 NO SENSOR PROPOSED 0 - - - - -$

21 D.D. Eisenhower

Corridor 9 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

22D.D.

EisenhowerCorridor 10

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

10 110 1.10 3,640 4,004 No Work Proposed 0 110 1.10 3,640 4004 NO SENSOR PROPOSED 0 - - - - -$

23 D.D. Eisenhower

Corridor 10 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

24D.D.

EisenhowerCorridor 11

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

16 110 1.76 3,640 6,406 No Work Proposed 0 110 1.76 3,640 6406 NO SENSOR PROPOSED 0 - - - - -$

25 D.D. Eisenhower

Corridor 11 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

26D.D.

EisenhowerCorridor 12

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

13 110 1.43 3,640 5,205 No Work Proposed 0 110 1.43 3,640 5205 NO SENSOR PROPOSED 0 - - - - -$

27 D.D. Eisenhower

Corridor 12 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

28D.D.

EisenhowerCorridor 13

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

20 110 2.20 3,640 8,008 No Work Proposed 0 110 2.20 3,640 8008 NO SENSOR PROPOSED 0 - - - - -$

29 D.D. Eisenhower

Corridor 13 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

30D.D.

EisenhowerCorridor 14

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

11 110 1.21 3,640 4,404 No Work Proposed 0 110 1.21 3,640 4404 NO SENSOR PROPOSED 0 - - - - -$

31 D.D. Eisenhower

Corridor 14 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

32D.D.

EisenhowerCorridor 15

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

10 110 1.10 3,640 4,004 No Work Proposed 0 110 1.10 3,640 4004 NO SENSOR PROPOSED 0 - - - - -$

33 D.D. Eisenhower

Corridor 15 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

34D.D.

EisenhowerLibrary

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

50 220 11.00 2,400 26,400 No Work Proposed 0 220 11.00 2,400 26400 NO SENSOR PROPOSED 0 - - - - -$

35 D.D. Eisenhower

Library Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

36D.D.

EisenhowerLibrary

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

16 110 1.76 2,400 4,224 No Work Proposed 0 110 1.76 2,400 4224 NO SENSOR PROPOSED 0 - - - - -$

37 D.D. Eisenhower

Library 150w Incandescent S/I 8 150 1.20 2,400 2,880 Re-lamp with 40w Compact Fluorescent 8 40 0.32 2,400 768 NO SENSOR PROPOSED 0 0.88 2,112 - 2,112 343.41$

38D.D.

EisenhowerLibrary

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 2,400 264 No Work Proposed 0 110 0.11 2,400 264 NO SENSOR PROPOSED 0 - - - - -$

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1 of 45

Page 197: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

39 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

40 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

41 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

42 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

43 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

44 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

45 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

40 61 2.44 1,500 3,660 No Work Proposed 0 61 2.44 1,500 3660 NO SENSOR PROPOSED 0 - - - - -$

46 D.D. Eisenhower

Boys 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

10 31 0.31 2,400 744 No Work Proposed 0 31 0.31 2,400 744 NO SENSOR PROPOSED 0 - - - - -$

47 D.D. Eisenhower

Custodian 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

10 31 0.31 1,000 310 No Work Proposed 0 31 0.31 1,000 310 NO SENSOR PROPOSED 0 - - - - -$

48 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 No Work Proposed 0 61 1.71 1,500 2562 NO SENSOR PROPOSED 0 - - - - -$

49 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 No Work Proposed 0 61 1.71 1,500 2562 NO SENSOR PROPOSED 0 - - - - -$

50 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 No Work Proposed 0 61 1.71 1,500 2562 NO SENSOR PROPOSED 0 - - - - -$

51 D.D. Eisenhower

HUB Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

52 D.D. Eisenhower

Book Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

53 D.D. Eisenhower

Electrical Room 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

14 31 0.43 1,000 434 No Work Proposed 0 31 0.43 1,000 434 NO SENSOR PROPOSED 0 - - - - -$

54D.D.

EisenhowerDisplay Case

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 No Work Proposed 0 61 0.06 3,640 222 NO SENSOR PROPOSED 0 - - - - -$

55 D.D. Eisenhower

Corridor To Gym Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 3,640 379 No Work Proposed 0 26 0.10 3,640 379 NO SENSOR PROPOSED 0 - - - - -$

56 D.D. Eisenhower

Girls Locker 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

16 31 0.50 2,400 1,190 No Work Proposed 0 31 0.50 2,400 1190 NO SENSOR PROPOSED 0 - - - - -$

57D.D.

EisenhowerCoach

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 1,500 165 No Work Proposed 0 110 0.11 1,500 165 NO SENSOR PROPOSED 0 - - - - -$

58D.D.

EisenhowerBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

59D.D.

EisenhowerShowers 75w. Incandescent S/I 6 75 0.45 1,500 675

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

6 13 0.08 1,500 117 NO SENSOR PROPOSED 0 0.37 558 - 558 90.73$

60D.D.

EisenhowerToilets

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

61 D.D. Eisenhower

Phys Ed Storage 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

62D.D.

EisenhowerGym

High Bay Fixture with (1) 400w Metal Halide Lamp and (1) Magnetic HID Ballast

18 445 8.01 2,400 19,224

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

18 234 4.21 2,400 10109 NO SENSOR PROPOSED 0 3.80 9,115 - 9,115 1,482.13$

63 D.D. Eisenhower

Corridor To Gym Recessed Can Can w/ (2) 13w CF PL 3 26 0.08 3,640 284 No Work Proposed 0 26 0.08 3,640 284 NO SENSOR PROPOSED 0 - - - - -$

64 D.D. Eisenhower

Boys Locker Room 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

15 31 0.47 2,400 1,116 No Work Proposed 0 31 0.47 2,400 1116 NO SENSOR PROPOSED 0 - - - - -$

65D.D.

EisenhowerCoach

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 1,500 165 No Work Proposed 0 110 0.11 1,500 165 NO SENSOR PROPOSED 0 - - - - -$

66D.D.

EisenhowerBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

67D.D.

EisenhowerToilets

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

68D.D.

EisenhowerShowers 75w. Incandescent S/I 5 75 0.38 1,500 563

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

5 13 0.07 1,500 98 NO SENSOR PROPOSED 0 0.31 465 - 465 75.61$

69 D.D. Eisenhower

Mechanical Room 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

3 61 0.18 1,000 183 No Work Proposed 0 61 0.18 1,000 183 NO SENSOR PROPOSED 0 - - - - -$

70 D.D. Eisenhower

Student Store 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 1,560 190 Wall Switch Occupancy Sensor 1 - - 102 102 16.66$

71D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 No Work Proposed 0 89 0.53 975 521

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 280 280 45.58$

72D.D.

EisenhowerGirls Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 2,400 1,171 No Work Proposed 0 61 0.49 2,400 1171 NO SENSOR PROPOSED 0 - - - - -$

73 D.D. Eisenhower

Custodian 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

4 61 0.24 1,000 244 No Work Proposed 0 61 0.24 1,000 244 NO SENSOR PROPOSED 0 - - - - -$

74 D.D. Eisenhower

Music Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 975 714 Wall Switch Dual Technology Occupancy Sensor

1 - - 384 384 62.49$

75 D.D. Eisenhower

Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

76D.D.

EisenhowerTeachers Lounge

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 2,400 1,709 No Work Proposed 0 89 0.71 1,560 1111

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 598 598 97.25$

77D.D.

EisenhowerFaculty Bathroom

2' Vanity Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2,400 82 NO SENSOR PROPOSED 0 0.03 62 - 62 10.15$

2 of 45

Page 198: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

78 D.D. Eisenhower

Faculty Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

79D.D.

EisenhowerFaculty Bathroom

2' Vanity Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2,400 82 NO SENSOR PROPOSED 0 0.03 62 - 62 10.15$

80 D.D. Eisenhower

Faculty Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

81D.D.

EisenhowerOffice Secretary

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 1,560 343 Wall Switch Occupancy Sensor 1 - - 185 185 30.05$

82D.D.

EisenhowerVice Principal

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

2 220 0.44 2,400 1,056 No Work Proposed 0 220 0.44 1,560 686 Wall Switch Occupancy Sensor 1 - - 370 370 60.10$

83 D.D. Eisenhower

Hallway Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 3,640 379 No Work Proposed 0 26 0.10 3,640 379 NO SENSOR PROPOSED 0 - - - - -$

84D.D.

EisenhowerPrincipal

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 No Work Proposed 0 89 0.36 1,560 555Wall Switch Dual Technology

Occupancy Sensor1 - - 299 299 48.62$

85D.D.

EisenhowerMain Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 No Work Proposed 0 89 0.80 2,400 1922 NO SENSOR PROPOSED 0 - - - - -$

86D.D.

EisenhowerMain Office

2X2 recessed troffer with (4) F17 T8 Lamps & (1) 4-Light Electronic ballast

1 68 0.07 2,400 163 No Work Proposed 0 68 0.07 2,400 163 NO SENSOR PROPOSED 0 - - - - -$

87D.D.

EisenhowerMain Office 60w. Incandescent S/I 7 60 0.42 2,400 1,008

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

7 13 0.09 2,400 218 NO SENSOR PROPOSED 0 0.33 790 - 790 128.39$

88D.D.

EisenhowerStorage

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 500 110 No Work Proposed 0 110 0.22 325 72 Wall Switch Occupancy Sensor 1 - - 39 39 6.26$

89D.D.

EisenhowerBathroom

2' Vanity Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2,400 82 NO SENSOR PROPOSED 0 0.03 62 - 62 10.15$

90 D.D. Eisenhower

Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

91D.D.

EisenhowerNurse's Office

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

10 110 1.10 2,400 2,640 No Work Proposed 0 110 1.10 2,400 2640 NO SENSOR PROPOSED 0 - - - - -$

92D.D.

EisenhowerBathroom

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

2 34 0.07 2,400 163 No Work Proposed 0 34 0.07 2,400 163 NO SENSOR PROPOSED 0 - - - - -$

93 D.D. Eisenhower

Electrical Room #2 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

94 D.D. Eisenhower

Guidence 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

6 61 0.37 2,400 878 No Work Proposed 0 61 0.37 2,400 878 NO SENSOR PROPOSED 0 - - - - -$

95 D.D. Eisenhower

Guidence 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 1,560 381 Wall Switch Occupancy Sensor 1 - - 205 205 33.33$

96 D.D. Eisenhower

Guidence 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

8 61 0.49 2,400 1,171 No Work Proposed 0 61 0.49 1,560 761 Wall Switch Occupancy Sensor 1 - - 410 410 66.65$

97 D.D. Eisenhower

Work Room/Copy Room

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

98D.D.

EisenhowerChild Study Team

Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 No Work Proposed 0 89 0.36 1,560 555

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 299 299 48.62$

99D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 975 1071Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 576 576 93.73$

100D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 975 694

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 374 374 60.78$

101 D.D. Eisenhower

Stage 4' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

29 110 3.19 2,400 7,656 No Work Proposed 0 110 3.19 2,400 7656 NO SENSOR PROPOSED 0 - - - - -$

102 D.D. Eisenhower

Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

103D.D.

EisenhowerStorage Room #4 100w Incandescent S/I 1 100 0.10 500 50

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

1 23 0.02 500 12 NO SENSOR PROPOSED 0 0.08 39 - 39 6.26$

104 D.D. Eisenhower

Storage Room #4 Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8,760 35 NO SENSOR PROPOSED 0 0.08 666 - 666 108.25$

105D.D.

EisenhowerBoys

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

106 D.D. Eisenhower

Boys 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

8 31 0.25 2,400 595 No Work Proposed 0 31 0.25 2,400 595 NO SENSOR PROPOSED 0 - - - - -$

107 D.D. Eisenhower

Boys 4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

108 D.D. Eisenhower

Custodian 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

109 D.D. Eisenhower

Girls 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

10 31 0.31 2,400 744 No Work Proposed 0 31 0.31 2,400 744 NO SENSOR PROPOSED 0 - - - - -$

110 D.D. Eisenhower

Gym Entrance SE corner

Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 2,400 250 No Work Proposed 0 26 0.10 2,400 250 NO SENSOR PROPOSED 0 - - - - -$

111D.D.

EisenhowerHandicapped Classroom

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 No Work Proposed 0 89 0.53 975 521 Wall Switch Occupancy Sensor 1 - - 280 280 45.58$

112 D.D. Eisenhower

Women's Faculty 4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 57 0.23 2,400 547 No Work Proposed 0 57 0.23 2,400 547 NO SENSOR PROPOSED 0 - - - - -$

113 D.D. Eisenhower

Bathroom 4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

114 D.D. Eisenhower

Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

115 D.D. Eisenhower

Electrical Panel Room 4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 57 0.23 1,000 228 No Work Proposed 0 57 0.23 1,000 228 NO SENSOR PROPOSED 0 - - - - -$

3 of 45

Page 199: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

116D.D.

EisenhowerMen's Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

117D.D.

EisenhowerMusic Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

25 61 1.53 1,500 2,288 No Work Proposed 0 61 1.53 1,500 2288 NO SENSOR PROPOSED 0 - - - - -$

118D.D.

EisenhowerPractice Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 2,400 214 No Work Proposed 0 89 0.09 2,400 214 NO SENSOR PROPOSED 0 - - - - -$

119D.D.

EisenhowerOffice

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 1,560 417 Wall Switch Occupancy Sensor 1 - - 224 224 36.47$

120D.D.

EisenhowerInstrument Storage

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

121 D.D. Eisenhower

Instrument Storage 4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

1 57 0.06 500 29 No Work Proposed 0 57 0.06 500 29 NO SENSOR PROPOSED 0 - - - - -$

122D.D.

EisenhowerShowcase

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

123 D.D. Eisenhower

Gym Entrance Recessed Can Can w/ (2) 13w CF PL 3 26 0.08 2,400 187 No Work Proposed 0 26 0.08 2,400 187 NO SENSOR PROPOSED 0 - - - - -$

124D.D.

EisenhowerElevator Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

125D.D.

EisenhowerElevator

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

126 D.D. Eisenhower

Wood Shop 4' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

46 110 5.06 1,500 7,590 No Work Proposed 0 110 5.06 1,500 7590 NO SENSOR PROPOSED 0 - - - - -$

127 D.D. Eisenhower

Stairs 42w. Compact Flourescent S/I 1 42 0.04 3,640 153 No Work Proposed 0 42 0.04 3,640 153 NO SENSOR PROPOSED 0 - - - - -$

128 D.D. Eisenhower

Wood Storage 23w Compact Fluorescent S/I 4 23 0.09 500 46 No Work Proposed 0 23 0.09 500 46 NO SENSOR PROPOSED 0 - - - - -$

129 D.D. Eisenhower

Computer/Tech Room 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

15 61 0.92 1,500 1,373 No Work Proposed 0 61 0.92 1,500 1373 NO SENSOR PROPOSED 0 - - - - -$

130 D.D. Eisenhower

Life Skills 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

40 61 2.44 2,400 5,856 No Work Proposed 0 61 2.44 2,400 5856 NO SENSOR PROPOSED 0 - - - - -$

131 D.D. Eisenhower

Stairs 42w. Compact Flourescent S/I 1 42 0.04 3,640 153 No Work Proposed 0 42 0.04 3,640 153 NO SENSOR PROPOSED 0 - - - - -$

132 D.D. Eisenhower

Storage 23w Compact Fluorescent S/I 4 23 0.09 500 46 No Work Proposed 0 23 0.09 500 46 NO SENSOR PROPOSED 0 - - - - -$

133 D.D. Eisenhower

Art Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

25 61 1.53 1,500 2,288 No Work Proposed 0 61 1.53 1,500 2288 NO SENSOR PROPOSED 0 - - - - -$

134 D.D. Eisenhower

Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - -$

135 D.D. Eisenhower

Kiln 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,500 183 No Work Proposed 0 61 0.12 1,500 183 NO SENSOR PROPOSED 0 - - - - -$

136D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 No Work Proposed 0 61 1.71 975 1665

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 897 897 145.80$

137 D.D. Eisenhower

Chem Storage 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - -$

138D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 No Work Proposed 0 61 1.71 975 1665

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 897 897 145.80$

139 D.D. Eisenhower

Computer Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 No Work Proposed 0 61 1.71 1,500 2562 NO SENSOR PROPOSED 0 - - - - -$

140D.D.

EisenhowerDigital Arts

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

20 89 1.78 1,500 2,670 No Work Proposed 0 89 1.78 1,500 2670 NO SENSOR PROPOSED 0 - - - - -$

141 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

142 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

143 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

144 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

145 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

146 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

147 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

148 D.D. Eisenhower

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 1,500 1830 NO SENSOR PROPOSED 0 - - - - -$

149 D.D. Eisenhower

Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 500 183 No Work Proposed 0 61 0.37 500 183 NO SENSOR PROPOSED 0 - - - - -$

150D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 975 1041

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 561 561 91.17$

151D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 975 1041

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 561 561 91.17$

152D.D.

EisenhowerCafeteria

High Bay Fixture with (1) 400w Metal Halide Lamp and (1) Magnetic HID Ballast

18 445 8.01 3,640 29,156

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

18 234 4.21 3,640 15332 NO SENSOR PROPOSED 0 3.80 13,825 - 13,825 2,247.90$

153 D.D. Eisenhower

Cafeteria Exit Sign w/ (2) 20w Incandescent Lamps 4 40 0.16 8,760 1,402 Remove and Replace existing exit sign with a new LED exit sign.

4 2 0.01 8,760 70 NO SENSOR PROPOSED 0 0.15 1,332 - 1,332 216.51$

4 of 45

Page 200: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

154 D.D. Eisenhower

Cafeteria 150w Incandescent S/I 4 150 0.60 3,640 2,184 Re-lamp with 40w Compact Fluorescent 4 40 0.16 3,640 582 NO SENSOR PROPOSED 0 0.44 1,602 - 1,602 260.42$

155 D.D. Eisenhower

Kitchen 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

26 61 1.59 2,400 3,806 No Work Proposed 0 61 1.59 2,400 3806 NO SENSOR PROPOSED 0 - - - - -$

156 D.D. Eisenhower

Kitchen Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - -$

157 D.D. Eisenhower

Garbage Bins Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 1,560 381 Wall Switch Occupancy Sensor 1 - - 205 205 33.33$

158D.D.

EisenhowerFaculty Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 2,400 2,563 No Work Proposed 0 89 1.07 1,560 1666

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 897 897 145.87$

159D.D.

EisenhowerBoys

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

160 D.D. Eisenhower

Boys 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

161D.D.

EisenhowerBoys

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

162D.D.

EisenhowerGirls

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

163D.D.

EisenhowerGirls

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

164 D.D. Eisenhower

Girls 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

165 D.D. Eisenhower

Men's Room Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

166D.D.

EisenhowerMen's Room

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

167 D.D. Eisenhower

Women's Room Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

168D.D.

EisenhowerWomen's Room

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

169D.D.

EisenhowerElectrical Panel Room

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

2 89 0.18 1,000 178 No Work Proposed 0 89 0.18 1,000 178 NO SENSOR PROPOSED 0 - - - - -$

170D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 1,500 1,469 No Work Proposed 0 89 0.98 975 955

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 514 514 83.57$

171D.D.

EisenhowerClass

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 1,500 51 No Work Proposed 0 34 0.03 1,500 51 NO SENSOR PROPOSED 0 - - - - -$

172D.D.

EisenhowerClass Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350

Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8,760 18 NO SENSOR PROPOSED 0 0.04 333 - 333 54.13$

173D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 1,500 1,469 No Work Proposed 0 89 0.98 975 955

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 514 514 83.57$

174D.D.

EisenhowerClass

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 1,500 51 No Work Proposed 0 34 0.03 1,500 51 NO SENSOR PROPOSED 0 - - - - -$

175 D.D. Eisenhower

Class Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350 Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8,760 18 NO SENSOR PROPOSED 0 0.04 333 - 333 54.13$

176D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 975 1041

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 561 561 91.17$

177D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 975 1041

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 561 561 91.17$

178D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 1,500 1,469 No Work Proposed 0 89 0.98 1,500 1469 NO SENSOR PROPOSED 0 - - - - -$

179D.D.

EisenhowerClass

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 1,500 51 No Work Proposed 0 34 0.03 1,500 51 NO SENSOR PROPOSED 0 - - - - -$

180D.D.

EisenhowerClass

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 1,500 51 No Work Proposed 0 34 0.03 1,500 51 NO SENSOR PROPOSED 0 - - - - -$

181D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 1,500 1,469 No Work Proposed 0 89 0.98 1,500 1469 NO SENSOR PROPOSED 0 - - - - -$

182 D.D. Eisenhower

Electrical Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 1,000 183 No Work Proposed 0 61 0.18 1,000 183 NO SENSOR PROPOSED 0 - - - - -$

183D.D.

EisenhowerSGI

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 975 694

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 374 374 60.78$

184D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 975 1041

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 561 561 91.17$

5 of 45

Page 201: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

185D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

20 89 1.78 1,500 2,670 No Work Proposed 0 89 1.78 975 1736

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

2 - - 935 935 151.95$

186D.D.

EisenhowerPrep Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,500 534 No Work Proposed 0 89 0.36 975 347 Wall Switch Occupancy Sensor 1 - - 187 187 30.39$

187D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

20 89 1.78 1,500 2,670 No Work Proposed 0 89 1.78 975 1736

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

2 - - 935 935 151.95$

188D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 975 1041

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 561 561 91.17$

189D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 975 1041

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 561 561 91.17$

190D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

191D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

192D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

193D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

194D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

195D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

196D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

197D.D.

EisenhowerSGI

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,500 534 No Work Proposed 0 89 0.36 1,500 534 NO SENSOR PROPOSED 0 - - - - -$

198D.D.

EisenhowerGym

High Bay Fixture with (8) 42w Triple Tube PL Fluorescent Lamps

24 336 8.06 2,400 19,354 No Work Proposed 0 336 8.06 2,400 19354 NO SENSOR PROPOSED 0 - - - - -$

199 D.D. Eisenhower

Gym Exit Sign w/ 2w LED 4 2 0.01 8,760 70 No Work Proposed 0 2 0.01 8,760 70 NO SENSOR PROPOSED 0 - - - - -$

200D.D.

EisenhowerStorage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

201D.D.

EisenhowerCoach Office

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 No Work Proposed 0 61 0.12 1,500 183 NO SENSOR PROPOSED 0 - - - - -$

202D.D.

EisenhowerBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 61 0.31 2,400 732 No Work Proposed 0 61 0.31 2,400 732 NO SENSOR PROPOSED 0 - - - - -$

203D.D.

EisenhowerRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

204D.D.

EisenhowerGirls

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 61 0.31 2,400 732 No Work Proposed 0 61 0.31 2,400 732 NO SENSOR PROPOSED 0 - - - - -$

205D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

206D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

207D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

208D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,500 534 No Work Proposed 0 89 0.36 1,500 534 NO SENSOR PROPOSED 0 - - - - -$

209D.D.

EisenhowerCourtyard 2004 wing

Wall Pack Fixture w/ (1) 100w High Pressure Sodium Lamp and Magnetic

Ballast6 120 0.72 3,640 2,621 No Work Proposed 0 120 0.72 3,640 2621 NO SENSOR PROPOSED 0 - - - - -$

210D.D.

EisenhowerCourtyard by office

Wall Pack Fixture w/ (1) 100w High Pressure Sodium Lamp and Magnetic

Ballast4 120 0.48 3,640 1,747 No Work Proposed 0 120 0.48 3,640 1747 NO SENSOR PROPOSED 0 - - - - -$

211D.D.

EisenhowerCourtyard

Wall Pack Fixture w/ (1) 100w High Pressure Sodium Lamp and Magnetic

Ballast3 120 0.36 3,640 1,310 No Work Proposed 0 120 0.36 3,640 1310 NO SENSOR PROPOSED 0 - - - - -$

212D.D.

EisenhowerOutside

Wall Pack Fixture w/ (1) 100w High Pressure Sodium Lamp and Magnetic

Ballast27 120 3.24 3,640 11,794 No Work Proposed 0 120 3.24 3,640 11794 NO SENSOR PROPOSED 0 - - - - -$

213D.D.

EisenhowerOutside

Wall Pack Fixture w/ (1) 70w High Pressure Sodium Lamp and Magnetic

Ballast22 92 2.02 3,640 7,367 No Work Proposed 0 92 2.02 3,640 7367 NO SENSOR PROPOSED 0 - - - - -$

214D.D.

EisenhowerOutside

Wall Pack Fixture with (1) 175w Mercury Vapor Lamp and (1) Magnetic HID Ballast

4 205 0.82 3,640 2,985Remove and Replace Existing Fixture With a New Outdoor Flood Fixture Containing a 150w Pulse

Metal Halide Lamp4 85 0.34 3,640 1238 NO SENSOR PROPOSED 0 0.48 1,747 - 1,747 284.09$

215D.D.

EisenhowerOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 400w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast14 445 6.23 3,640 22,677 No Work Proposed 0 445 6.23 3,640 22677 NO SENSOR PROPOSED 0 - - - - -$

6 of 45

Page 202: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

216D.D.

EisenhowerOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 250w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast5 286 1.43 3,640 5,205 No Work Proposed 0 286 1.43 3,640 5205 NO SENSOR PROPOSED 0 - - - - -$

217D.D.

EisenhowerOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 400w High Pressure Sodium Lamp

and (1) Magnetic HID Ballast5 450 2.25 3,640 8,190 No Work Proposed 0 450 2.25 3,640 8190 NO SENSOR PROPOSED 0 - - - - -$

34.00 10.87 33,102.06 14,903.98 48,006.04 $7,805.78

218 J.J. Catena Corridor 219-2242X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

8 110 0.88 3,640 3,203 No Work Proposed 0 110 0.88 3,640 3203 NO SENSOR PROPOSED 0 - - - - -$

219 J.J. Catena Corridor 219-224 Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350 Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8,760 18 NO SENSOR PROPOSED 0 0.04 333 - 333 54.59$

220 J.J. Catena Corridor 213-2182X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

18 110 1.98 3,640 7,207 No Work Proposed 0 110 1.98 3,640 7207 NO SENSOR PROPOSED 0 - - - - -$

221 J.J. Catena Corridor 213-2182X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 3,640 648 No Work Proposed 0 89 0.18 3,640 648 NO SENSOR PROPOSED 0 - - - - -$

222 J.J. Catena Corridor 213-2182X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 No Work Proposed 0 61 0.12 3,640 444 NO SENSOR PROPOSED 0 - - - - -$

223 J.J. Catena Corridor 213-218 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

1 61 0.06 3,640 222 No Work Proposed 0 61 0.06 3,640 222 NO SENSOR PROPOSED 0 - - - - -$

224 J.J. Catena Corridor 213-218 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

225 J.J. Catena Corridor 210-2122X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

9 110 0.99 3,640 3,604 No Work Proposed 0 110 0.99 3,640 3604 NO SENSOR PROPOSED 0 - - - - -$

226 J.J. Catena Corridor 210-2122X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 No Work Proposed 0 61 0.24 3,640 888 NO SENSOR PROPOSED 0 - - - - -$

227 J.J. Catena Corridor 210-212 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

1 31 0.03 3,640 113 No Work Proposed 0 31 0.03 3,640 113 NO SENSOR PROPOSED 0 - - - - -$

228 J.J. Catena Corridor 210-212 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

229 J.J. Catena Corridor 210-212 Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350 Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8,760 18 NO SENSOR PROPOSED 0 0.04 333 - 333 54.59$

230 J.J. Catena Corridor 200-2092X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

21 110 2.31 3,640 8,408 No Work Proposed 0 110 2.31 3,640 8408 NO SENSOR PROPOSED 0 - - - - -$

231 J.J. Catena Corridor 200-209 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

232 J.J. Catena Corridor Ext. 12X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 3,640 1,776 No Work Proposed 0 61 0.49 3,640 1776 NO SENSOR PROPOSED 0 - - - - -$

233 J.J. Catena Corridor Ext. 1 Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8,760 35 NO SENSOR PROPOSED 0 0.08 666 - 666 109.18$

234 J.J. Catena Corridor Ext. 22X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

235 J.J. Catena Corridor 231-2442X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

25 61 1.53 3,640 5,551 No Work Proposed 0 61 1.53 3,640 5551 NO SENSOR PROPOSED 0 - - - - -$

236 J.J. Catena Corridor 231-244 Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8,760 35 NO SENSOR PROPOSED 0 0.08 666 - 666 109.18$

237 J.J. Catena Corridor 102-1052X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

238 J.J. Catena Corridor 102-105 Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350 Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8,760 18 NO SENSOR PROPOSED 0 0.04 333 - 333 54.59$

239 J.J. Catena Corridor 108-1132X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

10 61 0.61 3,640 2,220 No Work Proposed 0 61 0.61 3,640 2220 NO SENSOR PROPOSED 0 - - - - -$

240 J.J. Catena Corridor 108-113 Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8,760 35 NO SENSOR PROPOSED 0 0.08 666 - 666 109.18$

241 J.J. Catena Corridor 116-1172X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 No Work Proposed 0 61 0.37 3,640 1332 NO SENSOR PROPOSED 0 - - - - -$

242 J.J. Catena Corridor 116-117 Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350 Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8,760 18 NO SENSOR PROPOSED 0 0.04 333 - 333 54.59$

243 J.J. Catena Library High Bay Fixture with (8) 42w Triple Tube PL Fluorescent Lamps

11 336 3.70 2,400 8,870 No Work Proposed 0 336 3.70 2,400 8870 NO SENSOR PROPOSED 0 - - - - -$

244 J.J. Catena Video Storage2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 500 134 No Work Proposed 0 89 0.27 500 134 NO SENSOR PROPOSED 0 - - - - -$

245 J.J. Catena Video Storage2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

246 J.J. Catena Hub Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

247 J.J. Catena Computer Room4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast24 61 1.46 1,500 2,196 No Work Proposed 0 61 1.46 975 1427

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 769 769 126.05$

248 J.J. Catena Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

249 J.J. Catena Restroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

250 J.J. Catena Restroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

251 J.J. Catena Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

252 J.J. Catena Storage 4' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

3 110 0.33 500 165 No Work Proposed 0 110 0.33 500 165 NO SENSOR PROPOSED 0 - - - - -$

253 J.J. Catena Electrical Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at D.D. Eisenhower:

7 of 45

Page 203: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

254 J.J. Catena SGI4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 975 714

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 384 384 63.03$

255 J.J. Catena Art 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

40 61 2.44 1,500 3,660 No Work Proposed 0 61 2.44 1,500 3660 NO SENSOR PROPOSED 0 - - - - -$

256 J.J. Catena Storage2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 500 110 No Work Proposed 0 110 0.22 500 110 NO SENSOR PROPOSED 0 - - - - -$

257 J.J. Catena Boiler Room 4' Indusrtial Hood Fixture w/ (1) F32 T8 Lamps & (1) 1L Electronic Ballast

6 57 0.34 1,000 342 No Work Proposed 0 57 0.34 1,000 342 NO SENSOR PROPOSED 0 - - - - -$

258 J.J. Catena Slop Sink 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

259 J.J. Catena Custodian/ Receiving Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

260 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

261 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

262 J.J. Catena Class/Speech 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

1 31 0.03 1,500 47 No Work Proposed 0 31 0.03 1,500 47 NO SENSOR PROPOSED 0 - - - - -$

263 J.J. Catena Class/Speech Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

6 61 0.37 1,500 549 No Work Proposed 0 61 0.37 1,500 549 NO SENSOR PROPOSED 0 - - - - -$

264 J.J. Catena Women's Room 60w. Incandescent S/I 2 60 0.12 2,400 288Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.09 226 - 226 37.00$

265 J.J. Catena Men's Room 60w. Incandescent S/I 2 60 0.12 2,400 288Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.09 226 - 226 37.00$

266 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

267 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

268 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

269 J.J. Catena Bathroom 60w. Incandescent S/I 2 60 0.12 2,400 288Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.09 226 - 226 37.00$

270 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

271 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

272 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast27 61 1.65 1,500 2,471 No Work Proposed 0 61 1.65 975 1606

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 865 865 141.81$

273 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast30 61 1.83 1,500 2,745 No Work Proposed 0 61 1.83 975 1784

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 961 961 157.56$

274 J.J. Catena Closet 60w. Incandescent S/I 1 60 0.06 500 30Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 500 7 NO SENSOR PROPOSED 0 0.05 24 - 24 3.85$

275 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast30 61 1.83 1,500 2,745 No Work Proposed 0 61 1.83 975 1784

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 961 961 157.56$

276 J.J. Catena Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 1,500 1922 NO SENSOR PROPOSED 0 - - - - -$

277 J.J. Catena Class4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 975 1071

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 576 576 94.54$

278 J.J. Catena Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

279 J.J. Catena Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

280 J.J. Catena Guidence Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 No Work Proposed 0 89 0.53 1,560 833

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 449 449 73.56$

8 of 45

Page 204: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

281 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

282 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

283 J.J. Catena Boys 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 31 0.19 2,400 446 No Work Proposed 0 31 0.19 2,400 446 NO SENSOR PROPOSED 0 - - - - -$

284 J.J. Catena Slop Sink 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

285 J.J. Catena Girls 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 2,400 298 No Work Proposed 0 31 0.12 2,400 298 NO SENSOR PROPOSED 0 - - - - -$

286 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

287 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

288 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

289 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

290 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

291 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

292 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

293 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

294 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 No Work Proposed 0 61 1.28 975 1249

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 110.29$

295 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 89 0.45 1,500 668 No Work Proposed 0 89 0.45 1,500 668 NO SENSOR PROPOSED 0 - - - - -$

296 J.J. Catena Storage/Conference2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 500 178 No Work Proposed 0 89 0.36 325 116 Wall Switch Occupancy Sensor 1 - - 62 62 10.22$

297 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 89 0.45 1,500 668 No Work Proposed 0 89 0.45 1,500 668 NO SENSOR PROPOSED 0 - - - - -$

298 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 No Work Proposed 0 89 0.53 975 521

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 280 280 45.98$

299 J.J. Catena Electrical Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

300 J.J. Catena Nurse's Office2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 2,400 1,056 No Work Proposed 0 110 0.44 2,400 1056 NO SENSOR PROPOSED 0 - - - - -$

301 J.J. Catena Nurse's Office2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

302 J.J. Catena Nurse's Office 4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

303 J.J. Catena Bathroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

304 J.J. Catena Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

305 J.J. Catena Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

306 J.J. Catena Work Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 No Work Proposed 0 89 0.36 2,400 854 NO SENSOR PROPOSED 0 - - - - -$

307 J.J. Catena Bathroom 60w. Incandescent S/I 2 60 0.12 2,400 288Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.09 226 - 226 37.00$

9 of 45

Page 205: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

308 J.J. Catena Main Office2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

309 J.J. Catena Principal2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 1,560 343 Wall Switch Occupancy Sensor 1 - - 185 185 30.31$

310 J.J. Catena Women's Room2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

311 J.J. Catena Women's Room Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

312 J.J. Catena Men's Room2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

313 J.J. Catena Men's Room Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

314 J.J. Catena Vocal Music2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

315 J.J. Catena Vocal Music2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

316 J.J. Catena SGI2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 No Work Proposed 0 89 0.53 975 521

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 280 280 45.98$

317 J.J. Catena SGI2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 No Work Proposed 0 61 0.12 1,500 183 NO SENSOR PROPOSED 0 - - - - -$

318 J.J. Catena Instrumental Music2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 No Work Proposed 0 89 0.80 975 781

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 421 421 68.97$

319 J.J. Catena Gym Office Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 2,400 1,757 No Work Proposed 0 61 0.73 2,400 1757 NO SENSOR PROPOSED 0 - - - - -$

320 J.J. Catena GymHigh Bay Fixture with (1) 400w Metal

Halide Lamp and (1) Magnetic HID Ballast18 445 8.01 2,400 19,224

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

18 234 4.21 2,400 10109 NO SENSOR PROPOSED 0 3.80 9,115 - 9,115 1,494.89$

321 J.J. Catena Gym 250w Quartz 6 250 1.50 2,400 3,600 No Work Proposed 0 250 1.50 2,400 3600 NO SENSOR PROPOSED 0 - - - - -$

322 J.J. Catena Back Stage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

31 61 1.89 2,400 4,538 No Work Proposed 0 61 1.89 2,400 4538 NO SENSOR PROPOSED 0 - - - - -$

323 J.J. Catena Back Stage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

324 J.J. Catena Back Stage 100w Incandescent S/I 10 100 1.00 2,400 2,400Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

10 23 0.23 2,400 552 NO SENSOR PROPOSED 0 0.77 1,848 - 1,848 303.07$

325 J.J. Catena Back Stage Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8,760 35 NO SENSOR PROPOSED 0 0.08 666 - 666 109.18$

326 J.J. Catena Cafeteria Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

4 26 0.10 3,640 379 No Work Proposed 0 26 0.10 3,640 379 NO SENSOR PROPOSED 0 - - - - -$

327 J.J. Catena Cafeteria2x2 Recessed Fixture w/ (1) 250w Metal

Halide Lamp and Magnetic Ballast20 290 5.80 3,640 21,112 No Work Proposed 0 290 5.80 3,640 21112 NO SENSOR PROPOSED 0 - - - - -$

328 J.J. Catena Kitchen 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

23 61 1.40 2,400 3,367 No Work Proposed 0 61 1.40 2,400 3367 NO SENSOR PROPOSED 0 - - - - -$

329 J.J. Catena Kitchen Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

330 J.J. Catena Receiving Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 2,400 1,464 No Work Proposed 0 61 0.61 2,400 1464 NO SENSOR PROPOSED 0 - - - - -$

331 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 No Work Proposed 0 89 0.80 975 781

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 421 421 68.97$

332 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 No Work Proposed 0 61 0.18 1,500 275 NO SENSOR PROPOSED 0 - - - - -$

333 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 No Work Proposed 0 89 0.80 975 781

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 421 421 68.97$

334 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 No Work Proposed 0 61 0.18 1,500 275 NO SENSOR PROPOSED 0 - - - - -$

335 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 No Work Proposed 0 89 0.80 975 781

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 421 421 68.97$

336 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 No Work Proposed 0 61 0.18 1,500 275 NO SENSOR PROPOSED 0 - - - - -$

337 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 975 1041

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 561 561 91.95$

338 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

339 J.J. Catena Boys1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

340 J.J. Catena Boys 4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

341 J.J. Catena Boys Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

10 of 45

Page 206: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

342 J.J. Catena Girls1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

343 J.J. Catena Girls 4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

344 J.J. Catena Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

345 J.J. Catena Custodian 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

346 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 No Work Proposed 0 89 0.80 1,500 1202 NO SENSOR PROPOSED 0 - - - - -$

347 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 No Work Proposed 0 61 0.18 1,500 275 NO SENSOR PROPOSED 0 - - - - -$

348 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 No Work Proposed 0 89 0.80 1,500 1202 NO SENSOR PROPOSED 0 - - - - -$

349 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 No Work Proposed 0 61 0.18 1,500 275 NO SENSOR PROPOSED 0 - - - - -$

350 J.J. Catena Teachers Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 2,400 2,350 No Work Proposed 0 89 0.98 1,560 1527

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 822 822 134.87$

351 J.J. Catena Teachers Room2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

352 J.J. Catena Hub Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

353 J.J. Catena Receiving Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

6 61 0.37 2,400 878 No Work Proposed 0 61 0.37 2,400 878 NO SENSOR PROPOSED 0 - - - - -$

354 J.J. Catena Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

355 J.J. Catena Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

356 J.J. Catena Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

357 J.J. Catena Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

358 J.J. Catena Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

359 J.J. Catena Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

360 J.J. Catena Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

361 J.J. Catena Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

362 J.J. Catena Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

363 J.J. Catena Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

364 J.J. Catena Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

365 J.J. Catena Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

366 J.J. Catena Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

367 J.J. Catena Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

368 J.J. Catena Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

369 J.J. Catena Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

370 J.J. Catena Cafeteria Recessed Can Can w/ (2) 57w CF PL 12 114 1.37 3,640 4,980 No Work Proposed 0 114 1.37 3,640 4980 NO SENSOR PROPOSED 0 - - - - -$

371 J.J. Catena Bathroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

372 J.J. Catena Kitchen2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

373 J.J. Catena Kitchen Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

374 J.J. Catena Closet2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

375 J.J. Catena MPR Recessed Can Can w/ (2) 13w CF PL 13 26 0.34 2,400 811 No Work Proposed 0 26 0.34 2,400 811 NO SENSOR PROPOSED 0 - - - - -$

376 J.J. Catena Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

377 J.J. Catena Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

378 J.J. Catena Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

379 J.J. Catena Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

380 J.J. Catena Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - -$

11 of 45

Page 207: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

381 J.J. Catena Boiler Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 1,000 244 No Work Proposed 0 61 0.24 1,000 244 NO SENSOR PROPOSED 0 - - - - -$

382 J.J. Catena OutsideParking Lot Fixture Mounted on a Pole w/

(1) 250w High Pressure Sodium Lamp and (1) Magnetic HID Ballast

5 300 1.50 3,640 5,460 No Work Proposed 0 300 1.50 3,640 5460 NO SENSOR PROPOSED 0 - - - - -$

383 J.J. Catena OutsideWall Pack Fixture w/ (1) 50w High

Pressure Sodium Lamp and Magnetic Ballast

21 65 1.37 3,640 4,969 No Work Proposed 0 65 1.37 3,640 4969 NO SENSOR PROPOSED 0 - - - - -$

384 J.J. Catena OutsideWall Pack Fixture w/ (1) 100w High

Pressure Sodium Lamp and Magnetic Ballast

17 120 2.04 3,640 7,426 No Work Proposed 0 120 2.04 3,640 7426 NO SENSOR PROPOSED 0 - - - - -$

385 J.J. Catena OutsideWall Pack Fixture with (1) 100w Metal

Halide Lamp and (1) Magnetic HID Ballast12 120 1.44 3,640 5,242 No Work Proposed 0 120 1.44 3,640 5242 NO SENSOR PROPOSED 0 - - - - -$

35.00 5.45 15,883.66 20,942.50 36,826.16 $6,039.49

386 C.T. Barkalow Corridor Fac-3142X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

25 61 1.53 3,640 5,551 No Work Proposed 0 61 1.53 3,640 5551 NO SENSOR PROPOSED 0 - - - - -$

387 C.T. Barkalow Corridor Fac-314 Exit Sign w/ 2w LED 5 2 0.01 8,760 88 No Work Proposed 0 2 0.01 8,760 88 NO SENSOR PROPOSED 0 - - - - -$

388 C.T. Barkalow Corridor 307-3152X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 No Work Proposed 0 61 0.24 3,640 888 NO SENSOR PROPOSED 0 - - - - -$

389 C.T. Barkalow Corridor 307-3151X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

14 61 0.85 3,640 3,109 No Work Proposed 0 61 0.85 3,640 3109 NO SENSOR PROPOSED 0 - - - - -$

390 C.T. Barkalow Corridor 307-315 Exit Sign w/ 2w LED 5 2 0.01 8,760 88 No Work Proposed 0 2 0.01 8,760 88 NO SENSOR PROPOSED 0 - - - - -$

391 C.T. Barkalow Corridor 301-3042X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

19 61 1.16 3,640 4,219 No Work Proposed 0 61 1.16 3,640 4219 NO SENSOR PROPOSED 0 - - - - -$

392 C.T. Barkalow Corridor 301-3042X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 3,640 3,888 No Work Proposed 0 89 1.07 3,640 3888 NO SENSOR PROPOSED 0 - - - - -$

393 C.T. Barkalow Corridor 301-3042X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 No Work Proposed 0 61 0.06 3,640 222 NO SENSOR PROPOSED 0 - - - - -$

394 C.T. Barkalow Corridor 301-304Recessed Can Can w/ (1) 100w Incan.

Screw In5 100 0.50 3,640 1,820

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

5 23 0.12 3,640 419 NO SENSOR PROPOSED 0 0.39 1,401 - 1,401 227.03$

395 C.T. Barkalow Corridor 301-304 Exit Sign w/ 2w LED 4 2 0.01 8,760 70 No Work Proposed 0 2 0.01 8,760 70 NO SENSOR PROPOSED 0 - - - - -$

396 C.T. Barkalow Corridor 3702X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 No Work Proposed 0 61 0.37 3,640 1332 NO SENSOR PROPOSED 0 - - - - -$

397 C.T. Barkalow Corridor 3702X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

9 34 0.31 3,640 1,114 No Work Proposed 0 34 0.31 3,640 1114 NO SENSOR PROPOSED 0 - - - - -$

398 C.T. Barkalow Corridor 370 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

399 C.T. Barkalow Corridor 3151X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

10 61 0.61 3,640 2,220 No Work Proposed 0 61 0.61 3,640 2220 NO SENSOR PROPOSED 0 - - - - -$

400 C.T. Barkalow Corridor 3152X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

5 61 0.31 3,640 1,110 No Work Proposed 0 61 0.31 3,640 1110 NO SENSOR PROPOSED 0 - - - - -$

401 C.T. Barkalow Corridor 315 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

402 C.T. Barkalow Corridor 315-3291X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

19 61 1.16 3,640 4,219 No Work Proposed 0 61 1.16 3,640 4219 NO SENSOR PROPOSED 0 - - - - -$

403 C.T. Barkalow Corridor 315-329 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

404 C.T. Barkalow Corridor Ext.1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

405 C.T. Barkalow Corridor 361-3682X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

13 61 0.79 3,640 2,887 No Work Proposed 0 61 0.79 3,640 2887 NO SENSOR PROPOSED 0 - - - - -$

406 C.T. Barkalow Corridor 361-368 3' Strip Fxiture with (1) F25 T8 Lamps & (1) 1L Electronic Ballast

4 48 0.19 3,640 699 No Work Proposed 0 48 0.19 3,640 699 NO SENSOR PROPOSED 0 - - - - -$

407 C.T. Barkalow Corridor 361-368 3' Strip Fxiture with (1) F25 T8 Lamps & (1) 1L Electronic Ballast

4 48 0.19 3,640 699 No Work Proposed 0 48 0.19 3,640 699 NO SENSOR PROPOSED 0 - - - - -$

408 C.T. Barkalow Corridor 361-368 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

409 C.T. Barkalow Corridor 370-372B Recessed Can Can w/ (2) 13w CF PL 10 26 0.26 3,640 946 No Work Proposed 0 26 0.26 3,640 946 NO SENSOR PROPOSED 0 - - - - -$

410 C.T. Barkalow Corridor 370-372B4X4 recessed troffer with (4) F32 T8

Lamps & (1) 4-Light Electronic ballasts3 110 0.33 3,640 1,201 No Work Proposed 0 110 0.33 3,640 1201 NO SENSOR PROPOSED 0 - - - - -$

411 C.T. Barkalow Corridor 370-372B Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

412 C.T. Barkalow Corridor 380-3832X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 61 0.73 3,640 2,664 No Work Proposed 0 61 0.73 3,640 2664 NO SENSOR PROPOSED 0 - - - - -$

413 C.T. Barkalow Corridor 380-3834X4 recessed troffer with (4) F32 T8

Lamps & (1) 4-Light Electronic ballasts3 110 0.33 3,640 1,201 No Work Proposed 0 110 0.33 3,640 1201 NO SENSOR PROPOSED 0 - - - - -$

414 C.T. Barkalow Corridor 380-383 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

415 C.T. Barkalow Corridor 373-3792X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 61 0.67 3,640 2,442 No Work Proposed 0 61 0.67 3,640 2442 NO SENSOR PROPOSED 0 - - - - -$

416 C.T. Barkalow Corridor 373-379 Recessed Can Can w/ (2) 13w CF PL 8 26 0.21 3,640 757 No Work Proposed 0 26 0.21 3,640 757 NO SENSOR PROPOSED 0 - - - - -$

417 C.T. Barkalow Corridor 373-379 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at J.J. Catena:

12 of 45

Page 208: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

418 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast24 61 1.46 1,500 2,196

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

16 55 0.88 1,500 1320 NO SENSOR PROPOSED 0 0.58 876 - 876 141.91$

419 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast24 61 1.46 1,500 2,196

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

16 55 0.88 1,500 1320 NO SENSOR PROPOSED 0 0.58 876 - 876 141.91$

420 C.T. Barkalow Storage4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast1 50 0.05 500 25

Re-lamp & Re-ballast 4' Fixture with (1) F32 Lamp, NP Ballast.

1 31 0.03 500 16 NO SENSOR PROPOSED 0 0.02 10 - 10 1.54$

421 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast24 61 1.46 1,500 2,196

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

16 55 0.88 1,500 1320 NO SENSOR PROPOSED 0 0.58 876 - 876 141.91$

422 C.T. Barkalow Closet 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

423 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

24 61 1.46 1,500 2,196 No Work Proposed 0 61 1.46 1,500 2196 NO SENSOR PROPOSED 0 - - - - -$

424 C.T. Barkalow Tech Room4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast1 50 0.05 1,500 75

Re-lamp & Re-ballast 4' Fixture with (1) F32 Lamp, NP Ballast.

1 31 0.03 1,500 47 NO SENSOR PROPOSED 0 0.02 29 - 29 4.62$

425 C.T. Barkalow home & life skills 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

34 61 2.07 1,500 3,111 No Work Proposed 0 61 2.07 1,500 3111 NO SENSOR PROPOSED 0 - - - - -$

426 C.T. Barkalow Work Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

427 C.T. Barkalow Office 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

428 C.T. Barkalow Tech Ed. 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

40 61 2.44 1,500 3,660 No Work Proposed 0 61 2.44 1,500 3660 NO SENSOR PROPOSED 0 - - - - -$

429 C.T. Barkalow Tech Lab2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 1,500 732 No Work Proposed 0 61 0.49 1,500 732 NO SENSOR PROPOSED 0 - - - - -$

430 C.T. Barkalow Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

431 C.T. Barkalow Computer Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 89 1.42 1,500 2,136 No Work Proposed 0 89 1.42 1,500 2136 NO SENSOR PROPOSED 0 - - - - -$

432 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

16 61 0.98 1,500 1,464 No Work Proposed 0 61 0.98 1,500 1464 NO SENSOR PROPOSED 0 - - - - -$

433 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

15 55 0.83 1,500 1238 NO SENSOR PROPOSED 0 0.40 593 - 593 95.99$

434 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

15 55 0.83 1,500 1238 NO SENSOR PROPOSED 0 0.40 593 - 593 95.99$

435 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

15 55 0.83 1,500 1238 NO SENSOR PROPOSED 0 0.40 593 - 593 95.99$

436 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

15 55 0.83 1,500 1238 NO SENSOR PROPOSED 0 0.40 593 - 593 95.99$

437 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

15 55 0.83 1,500 1238 NO SENSOR PROPOSED 0 0.40 593 - 593 95.99$

438 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

15 55 0.83 1,500 1238 NO SENSOR PROPOSED 0 0.40 593 - 593 95.99$

439 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

15 55 0.83 1,500 1238 NO SENSOR PROPOSED 0 0.40 593 - 593 95.99$

440 C.T. Barkalow Utility RoomIndustrial Hood 8' Fxiture with (2) F96

Econo-Watt T12 Lamps & (1) 2L EE Magnetic Ballast

1 138 0.14 1,000 138

Rebuild & Kit the existing 8' Industrial fixture with a Miro4 reflector system and (2) F32 T8 lamps and (1) 2L multi-volt low powered electronic

ballast

1 55 0.06 1,000 55 NO SENSOR PROPOSED 0 0.08 83 - 83 13.45$

441 C.T. Barkalow Boiler Room 4' Indusrtial Hood Fixture w/ (1) F32 T8 Lamps & (1) 1L Electronic Ballast

6 57 0.34 1,000 342 No Work Proposed 0 57 0.34 1,000 342 NO SENSOR PROPOSED 0 - - - - -$

442 C.T. Barkalow Boiler RoomIndustrial Hood 8' Fxiture with (2) F96

Econo-Watt T12 Lamps & (1) 2L EE Magnetic Ballast

1 138 0.14 1,000 138

Rebuild & Kit the existing 8' Industrial fixture with a Miro4 reflector system and (2) F32 T8 lamps and (1) 2L multi-volt low powered electronic

ballast

1 55 0.06 1,000 55 NO SENSOR PROPOSED 0 0.08 83 - 83 13.45$

443 C.T. Barkalow Bathroom 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

444 C.T. Barkalow Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

445 C.T. Barkalow Guidence2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 No Work Proposed 0 89 0.80 2,400 1922 NO SENSOR PROPOSED 0 - - - - -$

446 C.T. Barkalow Guidence2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 No Work Proposed 0 89 0.53 2,400 1282 NO SENSOR PROPOSED 0 - - - - -$

13 of 45

Page 209: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

447 C.T. Barkalow CST2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 No Work Proposed 0 89 0.53 2,400 1282 NO SENSOR PROPOSED 0 - - - - -$

448 C.T. Barkalow Nurse's Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 2,400 1,709 No Work Proposed 0 89 0.71 2,400 1709 NO SENSOR PROPOSED 0 - - - - -$

449 C.T. Barkalow Nurse's Office1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

450 C.T. Barkalow Bathroom1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

451 C.T. Barkalow Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

452 C.T. Barkalow Work Room4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast10 61 0.61 2,400 1,464

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

10 55 0.55 2,400 1320 NO SENSOR PROPOSED 0 0.06 144 - 144 23.33$

453 C.T. Barkalow Bathroom 100w Incandescent S/I 2 100 0.20 2,400 480Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

2 23 0.05 2,400 110 NO SENSOR PROPOSED 0 0.15 370 - 370 59.88$

454 C.T. Barkalow Bathroom 100w Incandescent S/I 2 100 0.20 2,400 480Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

2 23 0.05 2,400 110 NO SENSOR PROPOSED 0 0.15 370 - 370 59.88$

455 C.T. Barkalow Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

456 C.T. Barkalow Principal2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 2,400 1,056 No Work Proposed 0 110 0.44 2,400 1056 NO SENSOR PROPOSED 0 - - - - -$

457 C.T. Barkalow Vice Principal4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast4 61 0.24 2,400 586

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

4 55 0.22 2,400 528 NO SENSOR PROPOSED 0 0.02 58 - 58 9.33$

458 C.T. Barkalow Corridor 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 3,640 226 No Work Proposed 0 31 0.06 3,640 226 NO SENSOR PROPOSED 0 - - - - -$

459 C.T. Barkalow Main Office2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

21 61 1.28 2,400 3,074 No Work Proposed 0 61 1.28 2,400 3074 NO SENSOR PROPOSED 0 - - - - -$

460 C.T. Barkalow GymHigh Bay Fixture with (1) 400w Metal

Halide Lamp and (1) Magnetic HID Ballast21 445 9.35 2,400 22,428

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

21 234 4.91 2,400 11794 NO SENSOR PROPOSED 0 4.43 10,634 - 10,634 1,722.77$

461 C.T. Barkalow Gym Exit Sign w/ 2w LED 4 2 0.01 8,760 70 No Work Proposed 0 2 0.01 8,760 70 NO SENSOR PROPOSED 0 - - - - -$

462 C.T. Barkalow Gym2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

2 34 0.07 2,400 163 No Work Proposed 0 34 0.07 2,400 163 NO SENSOR PROPOSED 0 - - - - -$

463 C.T. Barkalow Storage4' Indusrtial Hood Fixture w/ (1) F34 Econo-Watt T12 Lamps & (1) 1L EE

Magnetic Ballast2 50 0.10 500 50

Re-lamp & Re-ballast 4' Fixture with (1) F32 Lamp, NP Ballast.

2 31 0.06 500 31 NO SENSOR PROPOSED 0 0.04 19 - 19 3.08$

464 C.T. Barkalow Entrance1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 No Work Proposed 0 61 0.12 3,640 444 NO SENSOR PROPOSED 0 - - - - -$

465 C.T. Barkalow Boys Locker 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

20 31 0.62 2,400 1,488 No Work Proposed 0 31 0.62 2,400 1488 NO SENSOR PROPOSED 0 - - - - -$

466 C.T. Barkalow Boys Locker2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

467 C.T. Barkalow Boys Locker Recessed Can Can w/ (2) 13w CF PL 6 26 0.16 2,400 374 No Work Proposed 0 26 0.16 2,400 374 NO SENSOR PROPOSED 0 - - - - -$

468 C.T. Barkalow Office 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

469 C.T. Barkalow Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

470 C.T. Barkalow Gym Entrance1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

471 C.T. Barkalow Gym Entrance Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

472 C.T. Barkalow Girls Locker Room 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

16 31 0.50 2,400 1,190 No Work Proposed 0 31 0.50 2,400 1190 NO SENSOR PROPOSED 0 - - - - -$

473 C.T. Barkalow Girls Locker Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

474 C.T. Barkalow Girls Locker Room Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 2,400 250 No Work Proposed 0 26 0.10 2,400 250 NO SENSOR PROPOSED 0 - - - - -$

475 C.T. Barkalow Girls Coach 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

476 C.T. Barkalow Bathroom2' Surface Mounted Wrap Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2,400 82 NO SENSOR PROPOSED 0 0.03 62 - 62 10.11$

477 C.T. Barkalow Storage 60w. Incandescent S/I 2 60 0.12 500 60Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 500 13 NO SENSOR PROPOSED 0 0.09 47 - 47 7.61$

478 C.T. Barkalow Men's Room 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 2,400 298 No Work Proposed 0 31 0.12 2,400 298 NO SENSOR PROPOSED 0 - - - - -$

479 C.T. Barkalow Lounge 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 2,400 149 No Work Proposed 0 31 0.06 2,400 149 NO SENSOR PROPOSED 0 - - - - -$

480 C.T. Barkalow Lounge 4' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

1 110 0.11 2,400 264 No Work Proposed 0 110 0.11 2,400 264 NO SENSOR PROPOSED 0 - - - - -$

481 C.T. Barkalow Bathroom 4' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

1 110 0.11 2,400 264 No Work Proposed 0 110 0.11 2,400 264 NO SENSOR PROPOSED 0 - - - - -$

14 of 45

Page 210: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

482 C.T. Barkalow Bathroom 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 2,400 298 No Work Proposed 0 31 0.12 2,400 298 NO SENSOR PROPOSED 0 - - - - -$

483 C.T. Barkalow Girls 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

10 31 0.31 2,400 744 No Work Proposed 0 31 0.31 2,400 744 NO SENSOR PROPOSED 0 - - - - -$

484 C.T. Barkalow Boys 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

10 31 0.31 2,400 744 No Work Proposed 0 31 0.31 2,400 744 NO SENSOR PROPOSED 0 - - - - -$

485 C.T. Barkalow Custodian 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 1,000 62 No Work Proposed 0 31 0.06 1,000 62 NO SENSOR PROPOSED 0 - - - - -$

486 C.T. Barkalow Storage #2 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

487 C.T. Barkalow Storage #2 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 500 31 No Work Proposed 0 31 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

488 C.T. Barkalow Stage 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 2,400 149 No Work Proposed 0 31 0.06 2,400 149 NO SENSOR PROPOSED 0 - - - - -$

489 C.T. Barkalow Stage 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

6 110 0.66 2,400 1,584 No Work Proposed 0 110 0.66 2,400 1584 NO SENSOR PROPOSED 0 - - - - -$

490 C.T. Barkalow Stage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

10 61 0.61 2,400 1,464 No Work Proposed 0 61 0.61 2,400 1464 NO SENSOR PROPOSED 0 - - - - -$

491 C.T. Barkalow Store room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 1,500 267 No Work Proposed 0 89 0.18 1,500 267 NO SENSOR PROPOSED 0 - - - - -$

492 C.T. Barkalow Office2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

4 34 0.14 2,400 326 No Work Proposed 0 34 0.14 2,400 326 NO SENSOR PROPOSED 0 - - - - -$

493 C.T. Barkalow Class (Vocal Music)2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

15 89 1.34 1,500 2,003 No Work Proposed 0 89 1.34 1,500 2003 NO SENSOR PROPOSED 0 - - - - -$

494 C.T. Barkalow Storage 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 500 31 No Work Proposed 0 31 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

495 C.T. Barkalow Storage4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast2 50 0.10 500 50

Re-lamp & Re-ballast 4' Fixture with (1) F32 Lamp, NP Ballast.

2 31 0.06 500 31 NO SENSOR PROPOSED 0 0.04 19 - 19 3.08$

496 C.T. Barkalow Storage #64' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast2 50 0.10 500 50

Re-lamp & Re-ballast 4' Fixture with (1) F32 Lamp, NP Ballast.

2 31 0.06 500 31 NO SENSOR PROPOSED 0 0.04 19 - 19 3.08$

497 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

15 61 0.92 1,500 1,373 No Work Proposed 0 61 0.92 1,500 1373 NO SENSOR PROPOSED 0 - - - - -$

498 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

16 61 0.98 1,500 1,464 No Work Proposed 0 61 0.98 1,500 1464 NO SENSOR PROPOSED 0 - - - - -$

499 C.T. Barkalow Men's Room 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 2,400 149 No Work Proposed 0 31 0.06 2,400 149 NO SENSOR PROPOSED 0 - - - - -$

500 C.T. Barkalow Men's Room2' Vanity Fxiture with (2) F20 T12 Lamp &

(1) 2L Magnetic Ballast1 60 0.06 2,400 144

Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2,400 82 NO SENSOR PROPOSED 0 0.03 62 - 62 10.11$

501 C.T. Barkalow Women's Room 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 2,400 298 No Work Proposed 0 31 0.12 2,400 298 NO SENSOR PROPOSED 0 - - - - -$

502 C.T. Barkalow Women's Room 4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

503 C.T. Barkalow Prep Room 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

9 110 0.99 1,500 1,485 No Work Proposed 0 110 0.99 1,500 1485 NO SENSOR PROPOSED 0 - - - - -$

504 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 1,500 1980 NO SENSOR PROPOSED 0 - - - - -$

505 C.T. Barkalow Prep Room4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast2 50 0.10 1,500 150

Re-lamp & Re-ballast 4' Fixture with (1) F32 Lamp, NP Ballast.

2 31 0.06 1,500 93 NO SENSOR PROPOSED 0 0.04 57 - 57 9.23$

506 C.T. Barkalow Park Room4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast2 50 0.10 2,400 240

Re-lamp & Re-ballast 4' Fixture with (1) F32 Lamp, NP Ballast.

2 31 0.06 2,400 149 NO SENSOR PROPOSED 0 0.04 91 - 91 14.77$

507 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 1,500 1980 NO SENSOR PROPOSED 0 - - - - -$

508 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 1,500 1980 NO SENSOR PROPOSED 0 - - - - -$

509 C.T. Barkalow Prep Room 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 1,500 93 No Work Proposed 0 31 0.06 1,500 93 NO SENSOR PROPOSED 0 - - - - -$

510 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 1,500 1980 NO SENSOR PROPOSED 0 - - - - -$

511 C.T. Barkalow Storage4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast1 50 0.05 500 25

Re-lamp & Re-ballast 4' Fixture with (1) F32 Lamp, NP Ballast.

1 31 0.03 500 16 NO SENSOR PROPOSED 0 0.02 10 - 10 1.54$

512 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 1,500 1980 NO SENSOR PROPOSED 0 - - - - -$

513 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

514 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

515 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

516 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

517 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

518 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

519 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

520 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

521 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

522 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

523 C.T. Barkalow Custodian4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast1 50 0.05 1,000 50

Re-lamp & Re-ballast 4' Fixture with (1) F32 Lamp, NP Ballast.

1 31 0.03 1,000 31 NO SENSOR PROPOSED 0 0.02 19 - 19 3.08$

524 C.T. Barkalow Girls 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

12 31 0.37 2,400 893 No Work Proposed 0 31 0.37 2,400 893 NO SENSOR PROPOSED 0 - - - - -$

525 C.T. Barkalow Boys 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

11 31 0.34 2,400 818 No Work Proposed 0 31 0.34 2,400 818 NO SENSOR PROPOSED 0 - - - - -$

15 of 45

Page 211: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

526 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

527 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

528 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

529 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

530 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

531 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

532 C.T. Barkalow Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

533 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

534 C.T. Barkalow Computer Lab2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

535 C.T. Barkalow Library2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

42 110 4.62 2,400 11,088 No Work Proposed 0 110 4.62 2,400 11088 NO SENSOR PROPOSED 0 - - - - -$

536 C.T. Barkalow Library2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

14 61 0.85 2,400 2,050 No Work Proposed 0 61 0.85 2,400 2050 NO SENSOR PROPOSED 0 - - - - -$

537 C.T. Barkalow Work Room2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 2,400 1,056 No Work Proposed 0 110 0.44 2,400 1056 NO SENSOR PROPOSED 0 - - - - -$

538 C.T. Barkalow Librarian2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 2,400 528 NO SENSOR PROPOSED 0 - - - - -$

539 C.T. Barkalow Audio/Visual2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 No Work Proposed 0 110 0.44 1,500 660 NO SENSOR PROPOSED 0 - - - - -$

540 C.T. Barkalow Showcase 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

541 C.T. Barkalow Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

16 61 0.98 1,500 1,464 No Work Proposed 0 61 0.98 1,500 1464 NO SENSOR PROPOSED 0 - - - - -$

542 C.T. Barkalow Girls1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

543 C.T. Barkalow Girls 4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

544 C.T. Barkalow Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

545 C.T. Barkalow Custodian 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

546 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

547 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

548 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

549 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

550 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 89 1.42 1,500 2,136 No Work Proposed 0 89 1.42 1,500 2136 NO SENSOR PROPOSED 0 - - - - -$

551 C.T. Barkalow Prep Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,500 534 No Work Proposed 0 89 0.36 1,500 534 NO SENSOR PROPOSED 0 - - - - -$

552 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 89 1.42 1,500 2,136 No Work Proposed 0 89 1.42 1,500 2136 NO SENSOR PROPOSED 0 - - - - -$

553 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 89 1.42 1,500 2,136 No Work Proposed 0 89 1.42 1,500 2136 NO SENSOR PROPOSED 0 - - - - -$

554 C.T. Barkalow Electrical Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 1,000 366 No Work Proposed 0 61 0.37 1,000 366 NO SENSOR PROPOSED 0 - - - - -$

555 C.T. Barkalow Electrical Room Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

556 C.T. Barkalow Faculty Bath2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

557 C.T. Barkalow Faculty Bath Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

558 C.T. Barkalow Faculty Women2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

559 C.T. Barkalow Faculty Women Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

560 C.T. Barkalow Faculty Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

10 89 0.89 2,400 2,136 No Work Proposed 0 89 0.89 2,400 2136 NO SENSOR PROPOSED 0 - - - - -$

561 C.T. Barkalow CafeteriaHigh Bay Fixture with (1) 400w Metal

Halide Lamp and (1) Magnetic HID Ballast18 445 8.01 3,640 29,156

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

18 234 4.21 3,640 15332 NO SENSOR PROPOSED 0 3.80 13,825 - 13,825 2,239.60$

562 C.T. Barkalow Cafeteria 250w Quartz 6 250 1.50 3,640 5,460 No Work Proposed 0 250 1.50 3,640 5460 NO SENSOR PROPOSED 0 - - - - -$

563 C.T. Barkalow Kitchen Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

564 C.T. Barkalow Kitchen Storage2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 500 89 No Work Proposed 0 89 0.18 500 89 NO SENSOR PROPOSED 0 - - - - -$

16 of 45

Page 212: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

565 C.T. Barkalow Kitchen4' Vapor & Moisture Resistant Fixture w/

(2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

32 61 1.95 2,400 4,685 No Work Proposed 0 61 1.95 2,400 4685 NO SENSOR PROPOSED 0 - - - - -$

566 C.T. Barkalow Kitchen 100w Incandescent S/I 6 100 0.60 2,400 1,440Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

6 23 0.14 2,400 331 NO SENSOR PROPOSED 0 0.46 1,109 - 1,109 179.63$

567 C.T. Barkalow Kitchen Recessed Can Can w/ (2) 13w CF PL 2 26 0.05 2,400 125 No Work Proposed 0 26 0.05 2,400 125 NO SENSOR PROPOSED 0 - - - - -$

568 C.T. Barkalow Locker 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

569 C.T. Barkalow Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

570 C.T. Barkalow Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

571 C.T. Barkalow Cafeteria Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

5 61 0.31 500 153 No Work Proposed 0 61 0.31 500 153 NO SENSOR PROPOSED 0 - - - - -$

572 C.T. Barkalow HW Heater 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

573 C.T. Barkalow Art Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

20 89 1.78 1,500 2,670 No Work Proposed 0 89 1.78 1,500 2670 NO SENSOR PROPOSED 0 - - - - -$

574 C.T. Barkalow Sprinkler Valve2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,000 356 No Work Proposed 0 89 0.36 1,000 356 NO SENSOR PROPOSED 0 - - - - -$

575 C.T. Barkalow Gym High Bay Fixture with (8) 42w Triple Tube PL Fluorescent Lamps

24 336 8.06 2,400 19,354 No Work Proposed 0 336 8.06 2,400 19354 NO SENSOR PROPOSED 0 - - - - -$

576 C.T. Barkalow Gym Exit Sign w/ 2w LED 4 2 0.01 8,760 70 No Work Proposed 0 2 0.01 8,760 70 NO SENSOR PROPOSED 0 - - - - -$

577 C.T. Barkalow Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - -$

578 C.T. Barkalow Office2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

579 C.T. Barkalow Electrical2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

580 C.T. Barkalow Stairs 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

5 61 0.31 3,640 1,110 No Work Proposed 0 61 0.31 3,640 1110 NO SENSOR PROPOSED 0 - - - - -$

581 C.T. Barkalow Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

582 C.T. Barkalow mechanical Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 1,000 244 No Work Proposed 0 61 0.24 1,000 244 NO SENSOR PROPOSED 0 - - - - -$

583 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

584 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

585 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

586 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

587 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

588 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

589 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

590 C.T. Barkalow Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

591 C.T. Barkalow Hub Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

592 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

593 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

594 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

595 C.T. Barkalow Digital Arts2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 89 1.42 1,500 2,136 No Work Proposed 0 89 1.42 1,500 2136 NO SENSOR PROPOSED 0 - - - - -$

596 C.T. Barkalow Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

597 C.T. Barkalow Girls2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

598 C.T. Barkalow Custodial Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

599 C.T. Barkalow Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

600 C.T. Barkalow Boys Recessed Can Can w/ (2) 13w CF PL 2 26 0.05 2,400 125 No Work Proposed 0 26 0.05 2,400 125 NO SENSOR PROPOSED 0 - - - - -$

601 C.T. Barkalow Boys2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

602 C.T. Barkalow Faculty Conference2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

17 of 45

Page 213: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

603 C.T. Barkalow OutsideWall Pack Fixture w/ (1) 50w High

Pressure Sodium Lamp and Magnetic Ballast

33 65 2.15 3,640 7,808 No Work Proposed 0 65 2.15 3,640 7808 NO SENSOR PROPOSED 0 - - - - -$

604 C.T. Barkalow OutsideWall Pack Fixture w/ (1) 100w High

Pressure Sodium Lamp and Magnetic Ballast

43 120 5.16 3,640 18,782 No Work Proposed 0 120 5.16 3,640 18782 NO SENSOR PROPOSED 0 - - - - -$

605 C.T. Barkalow Outside Recessed Can Can w/ (2) 13w CF PL 5 26 0.13 3,640 473 No Work Proposed 0 26 0.13 3,640 473 NO SENSOR PROPOSED 0 - - - - -$

606 C.T. Barkalow OutsideParking Lot Fixture Mounted on a Pole w/ (1) 400w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast18 445 8.01 3,640 29,156 No Work Proposed 0 445 8.01 3,640 29156 NO SENSOR PROPOSED 0 - - - - -$

607 C.T. Barkalow Outside 100w Incandescent S/I 1 100 0.10 3,640 364Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

1 23 0.02 3,640 84 NO SENSOR PROPOSED 0 0.08 280 - 280 45.41$

- 14.64 35,575.40 - 35,575.40 $5,763.21

608 E.C.L.C. Corridor 3842X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 61 0.31 3,640 1,110 No Work Proposed 0 61 0.31 3,640 1110 NO SENSOR PROPOSED 0 - - - - -$

609 E.C.L.C. Corridor 384 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

610 E.C.L.C. Corridor 3852X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 3,640 666 No Work Proposed 0 61 0.18 3,640 666 NO SENSOR PROPOSED 0 - - - - -$

611 E.C.L.C. Corridor 385 4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 57 0.11 3,640 415 No Work Proposed 0 57 0.11 3,640 415 NO SENSOR PROPOSED 0 - - - - -$

612 E.C.L.C. Corridor 385 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

613 E.C.L.C. Entrance 2402X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

614 E.C.L.C. Entrance 240 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

2 61 0.12 3,640 444 No Work Proposed 0 61 0.12 3,640 444 NO SENSOR PROPOSED 0 - - - - -$

615 E.C.L.C. Entrance 240 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

616 E.C.L.C. Corridor 8802X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 3,640 666 No Work Proposed 0 61 0.18 3,640 666 NO SENSOR PROPOSED 0 - - - - -$

617 E.C.L.C. Corridor 880 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

618 E.C.L.C. Corridor 11522X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 61 0.55 3,640 1,998 No Work Proposed 0 61 0.55 3,640 1998 NO SENSOR PROPOSED 0 - - - - -$

619 E.C.L.C. Corridor 1152 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

620 E.C.L.C. Elevator2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

621 E.C.L.C. Corridor 5362X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 89 0.62 3,640 2,268 No Work Proposed 0 89 0.62 3,640 2268 NO SENSOR PROPOSED 0 - - - - -$

622 E.C.L.C. Corridor 536 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

623 E.C.L.C. Corridor 20442X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

17 89 1.51 3,640 5,507 No Work Proposed 0 89 1.51 3,640 5507 NO SENSOR PROPOSED 0 - - - - -$

624 E.C.L.C. Corridor 2044 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

625 E.C.L.C. Corridor 3522X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 3,640 972 No Work Proposed 0 89 0.27 3,640 972 NO SENSOR PROPOSED 0 - - - - -$

626 E.C.L.C. Corridor 352 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

627 E.C.L.C. Stairs 354 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 3,640 222 No Work Proposed 0 61 0.06 3,640 222 NO SENSOR PROPOSED 0 - - - - -$

628 E.C.L.C. Stairs 354 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 3,640 222 No Work Proposed 0 61 0.06 3,640 222 NO SENSOR PROPOSED 0 - - - - -$

629 E.C.L.C. Elevator2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

630 E.C.L.C. Corridor 576 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 3,640 1,332 No Work Proposed 0 61 0.37 3,640 1332 NO SENSOR PROPOSED 0 - - - - -$

631 E.C.L.C. Corridor 576 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

632 E.C.L.C. Stairs 3552X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 No Work Proposed 0 61 0.24 3,640 888 NO SENSOR PROPOSED 0 - - - - -$

633 E.C.L.C. Stairs 355 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

634 E.C.L.C. Corridor 512 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

5 61 0.31 3,640 1,110 No Work Proposed 0 61 0.31 3,640 1110 NO SENSOR PROPOSED 0 - - - - -$

635 E.C.L.C. Stairs 356 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 3,640 444 No Work Proposed 0 61 0.12 3,640 444 NO SENSOR PROPOSED 0 - - - - -$

636 E.C.L.C. Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 975 714

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 384 384 62.56$

637 E.C.L.C. Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 975 714

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 384 384 62.56$

638 E.C.L.C. Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

18 89 1.60 1,500 2,403 No Work Proposed 0 89 1.60 1,500 2403 NO SENSOR PROPOSED 0 - - - - -$

639 E.C.L.C. Bathroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

640 E.C.L.C. Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

641 E.C.L.C. Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

18 89 1.60 1,500 2,403 No Work Proposed 0 89 1.60 1,500 2403 NO SENSOR PROPOSED 0 - - - - -$

642 E.C.L.C. Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at C.T. Barkalow:

18 of 45

Page 214: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

643 E.C.L.C. Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

644 E.C.L.C. Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

18 89 1.60 1,500 2,403 No Work Proposed 0 89 1.60 1,500 2403 NO SENSOR PROPOSED 0 - - - - -$

645 E.C.L.C. Bathroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

646 E.C.L.C. Bathroom Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

647 E.C.L.C. Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

16 89 1.42 1,500 2,136 No Work Proposed 0 89 1.42 1,500 2136 NO SENSOR PROPOSED 0 - - - - -$

648 E.C.L.C. Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

649 E.C.L.C. Girls 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

650 E.C.L.C. Faculty Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

12 61 0.73 2,400 1,757 No Work Proposed 0 61 0.73 2,400 1757 NO SENSOR PROPOSED 0 - - - - -$

651 E.C.L.C. Faculty Room 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 2,400 149 No Work Proposed 0 31 0.06 2,400 149 NO SENSOR PROPOSED 0 - - - - -$

652 E.C.L.C. Conference Room 2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

8 110 0.88 2,400 2,112 No Work Proposed 0 110 0.88 2,400 2112 NO SENSOR PROPOSED 0 - - - - -$

653 E.C.L.C. Conference Room Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

654 E.C.L.C. Boys 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

655 E.C.L.C. Electrical2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

656 E.C.L.C. Kitchen2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 No Work Proposed 0 110 0.33 2,400 792 NO SENSOR PROPOSED 0 - - - - -$

657 E.C.L.C. Hub2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

658 E.C.L.C. Asst. Super/Admin2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

28 89 2.49 2,400 5,981 No Work Proposed 0 89 2.49 2,400 5981 NO SENSOR PROPOSED 0 - - - - -$

659 E.C.L.C. Asst. Super/Admin Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

660 E.C.L.C. SGI/Copy Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 89 0.45 1,500 668 No Work Proposed 0 89 0.45 975 434

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 234 234 38.03$

661 E.C.L.C. Kiln Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 No Work Proposed 0 61 0.06 1,500 92 NO SENSOR PROPOSED 0 - - - - -$

662 E.C.L.C. Janitor 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

1 31 0.03 1,000 31 No Work Proposed 0 31 0.03 1,000 31 NO SENSOR PROPOSED 0 - - - - -$

663 E.C.L.C. Storage 60w. Incandescent S/I 1 60 0.06 500 30Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 500 7 NO SENSOR PROPOSED 0 0.05 24 - 24 3.83$

664 E.C.L.C. Faculty Bath2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

665 E.C.L.C. Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 No Work Proposed 0 89 0.80 1,500 1202 NO SENSOR PROPOSED 0 - - - - -$

666 E.C.L.C. Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

667 E.C.L.C. Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 No Work Proposed 0 89 0.80 975 781

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 421 421 68.46$

668 E.C.L.C. Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

18 89 1.60 1,500 2,403 No Work Proposed 0 89 1.60 1,500 2403 NO SENSOR PROPOSED 0 - - - - -$

669 E.C.L.C. Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

670 E.C.L.C. Class2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 No Work Proposed 0 61 0.18 1,500 275 NO SENSOR PROPOSED 0 - - - - -$

671 E.C.L.C. Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

14 89 1.25 1,500 1,869 No Work Proposed 0 89 1.25 1,500 1869 NO SENSOR PROPOSED 0 - - - - -$

672 E.C.L.C. Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 No Work Proposed 0 61 0.06 1,500 92 NO SENSOR PROPOSED 0 - - - - -$

673 E.C.L.C. Restroom2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

674 E.C.L.C. Restroom Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

675 E.C.L.C. Nurse's Office2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 2,400 528 NO SENSOR PROPOSED 0 - - - - -$

676 E.C.L.C. Nurse's Office2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

7 34 0.24 2,400 571 No Work Proposed 0 34 0.24 2,400 571 NO SENSOR PROPOSED 0 - - - - -$

677 E.C.L.C. Nurse's Office 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

1 31 0.03 2,400 74 No Work Proposed 0 31 0.03 2,400 74 NO SENSOR PROPOSED 0 - - - - -$

678 E.C.L.C. Nurse's Office 60w. Incandescent S/I 2 60 0.12 2,400 288Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.09 226 - 226 36.73$

679 E.C.L.C. Main Office2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 2,400 1,848 No Work Proposed 0 110 0.77 2,400 1848 NO SENSOR PROPOSED 0 - - - - -$

19 of 45

Page 215: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

680 E.C.L.C. Copy Room2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 2,400 1,056 No Work Proposed 0 110 0.44 2,400 1056 NO SENSOR PROPOSED 0 - - - - -$

681 E.C.L.C. Storage1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

682 E.C.L.C. Building Admin2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

8 110 0.88 2,400 2,112 No Work Proposed 0 110 0.88 2,400 2112 NO SENSOR PROPOSED 0 - - - - -$

683 E.C.L.C. Bathroom 60w. Incandescent S/I 4 60 0.24 2,400 576Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

4 13 0.05 2,400 125 NO SENSOR PROPOSED 0 0.19 451 - 451 73.46$

684 E.C.L.C. Bathroom 23w Compact Fluorescent S/I 2 23 0.05 2,400 110 No Work Proposed 0 23 0.05 2,400 110 NO SENSOR PROPOSED 0 - - - - -$

685 E.C.L.C. Boys2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 No Work Proposed 0 110 0.33 1,560 515

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9'

High-(1) PP-20 per sensor

1 - - 277 277 45.13$

686 E.C.L.C. Girls2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 No Work Proposed 0 110 0.33 1,560 515

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9'

High-(1) PP-20 per sensor

1 - - 277 277 45.13$

687 E.C.L.C. Child Study4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 975 714

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9'

High-(1) PP-20 per sensor

2 - - 384 384 62.56$

688 E.C.L.C. Child Study Team2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

18 89 1.60 1,500 2,403 No Work Proposed 0 89 1.60 1,500 2403 NO SENSOR PROPOSED 0 - - - - -$

689 E.C.L.C. Office2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

690 E.C.L.C. Director/Super2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 2,400 528 NO SENSOR PROPOSED 0 - - - - -$

691 E.C.L.C. Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 No Work Proposed 0 89 0.53 1,560 833

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9'

High-(1) PP-20 per sensor

1 - - 449 449 73.03$

692 E.C.L.C. Conference2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 No Work Proposed 0 89 0.36 1,560 555 Wall Switch Occupancy Sensor 1 - - 299 299 48.68$

693 E.C.L.C. Storage 60w. Incandescent S/I 2 60 0.12 500 60Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 500 13 NO SENSOR PROPOSED 0 0.09 47 - 47 7.65$

694 E.C.L.C. Health Services2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 1,560 417 Wall Switch Occupancy Sensor 1 - - 224 224 36.51$

695 E.C.L.C. Coordinator Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 No Work Proposed 0 89 0.53 1,560 833

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 449 449 73.03$

696 E.C.L.C. Elevator B 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

697 E.C.L.C. Elevator B2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 2,400 214 No Work Proposed 0 89 0.09 2,400 214 NO SENSOR PROPOSED 0 - - - - -$

698 E.C.L.C. Paper Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

699 E.C.L.C. Custodian 60w. Incandescent S/I 1 60 0.06 1,000 60Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 1,000 13 NO SENSOR PROPOSED 0 0.05 47 - 47 7.65$

700 E.C.L.C. Technology Staff4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 975 833

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

2 - - 448 448 72.99$

701 E.C.L.C. Men's Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

702 E.C.L.C. Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

703 E.C.L.C. Business Admin2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 2,400 1,848 No Work Proposed 0 110 0.77 1,560 1201

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9'

High-(1) PP-20 per sensor

1 - - 647 647 105.30$

704 E.C.L.C. Office2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 2,400 528 NO SENSOR PROPOSED 0 - - - - -$

705 E.C.L.C. Kitchen2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 2,400 528 NO SENSOR PROPOSED 0 - - - - -$

706 E.C.L.C. Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

707 E.C.L.C. office 22X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 2,400 528 NO SENSOR PROPOSED 0 - - - - -$

20 of 45

Page 216: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

708 E.C.L.C. Office 32X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 2,400 1,171 No Work Proposed 0 61 0.49 2,400 1171 NO SENSOR PROPOSED 0 - - - - -$

709 E.C.L.C. conference2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

6 110 0.66 2,400 1,584 No Work Proposed 0 110 0.66 1,560 1030

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 554 554 90.26$

710 E.C.L.C. Copy Room2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 1,560 343 Wall Switch Occupancy Sensor 1 - - 185 185 30.09$

711 E.C.L.C. Secretary2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 2,400 528 NO SENSOR PROPOSED 0 - - - - -$

712 E.C.L.C. HR Department2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 2,400 1,171 No Work Proposed 0 61 0.49 2,400 1171 NO SENSOR PROPOSED 0 - - - - -$

713 E.C.L.C. Secretary2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 No Work Proposed 0 110 0.33 1,560 515 Wall Switch Occupancy Sensor 1 - - 277 277 45.13$

714 E.C.L.C. Office2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 No Work Proposed 0 110 0.33 1,560 515Wall Switch Dual Technology

Occupancy Sensor1 - - 277 277 45.13$

715 E.C.L.C. Super of Schools2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 No Work Proposed 0 110 0.33 2,400 792 NO SENSOR PROPOSED 0 - - - - -$

716 E.C.L.C. Super of Schools2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 2,400 1,056 No Work Proposed 0 110 0.44 2,400 1056 NO SENSOR PROPOSED 0 - - - - -$

717 E.C.L.C. Office 12X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 No Work Proposed 0 110 0.33 1,560 515Wall Switch Dual Technology

Occupancy Sensor1 - - 277 277 45.13$

718 E.C.L.C. Office 22X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

13 61 0.79 2,400 1,903 No Work Proposed 0 61 0.79 2,400 1903 NO SENSOR PROPOSED 0 - - - - -$

719 E.C.L.C. Restroom2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

720 E.C.L.C. Women's Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

721 E.C.L.C. Conference2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

9 110 0.99 2,400 2,376 No Work Proposed 0 110 0.99 2,400 2376 NO SENSOR PROPOSED 0 - - - - -$

722 E.C.L.C. Closet2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

723 E.C.L.C. storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

724 E.C.L.C. storage 75w. Incandescent S/I 6 75 0.45 500 225Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

6 13 0.08 500 39 NO SENSOR PROPOSED 0 0.37 186 - 186 30.28$

725 E.C.L.C. Meeting Room2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

9 110 0.99 2,400 2,376 No Work Proposed 0 110 0.99 2,400 2376 NO SENSOR PROPOSED 0 - - - - -$

726 E.C.L.C. Meeting Room 75w. Incandescent S/I 6 75 0.45 2,400 1,080Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

6 13 0.08 2,400 187 NO SENSOR PROPOSED 0 0.37 893 - 893 145.35$

727 E.C.L.C. GymHigh Bay Fixture with (1) 400w Metal

Halide Lamp and (1) Magnetic HID Ballast8 445 3.56 2,400 8,544

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

8 234 1.87 2,400 4493 NO SENSOR PROPOSED 0 1.69 4,051 - 4,051 659.54$

728 E.C.L.C. Closet Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

729 E.C.L.C. Closet Exit Sign w/ 2w LED 5 2 0.01 8,760 88 No Work Proposed 0 2 0.01 8,760 88 NO SENSOR PROPOSED 0 - - - - -$

730 E.C.L.C. Stage2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

8 110 0.88 2,400 2,112 No Work Proposed 0 110 0.88 2,400 2112 NO SENSOR PROPOSED 0 - - - - -$

731 E.C.L.C. Stage 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 2,400 298 No Work Proposed 0 31 0.12 2,400 298 NO SENSOR PROPOSED 0 - - - - -$

732 E.C.L.C. Electrical Room 60w. Incandescent S/I 2 60 0.12 1,000 120Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 1,000 26 NO SENSOR PROPOSED 0 0.09 94 - 94 15.30$

733 E.C.L.C. Attic 150w Incandescent S/I 9 150 1.35 500 675 Re-lamp with 40w Compact Fluorescent 9 40 0.36 500 180 NO SENSOR PROPOSED 0 0.99 495 - 495 80.59$

734 E.C.L.C. Attic 150w Incandescent S/I 8 150 1.20 500 600 Re-lamp with 40w Compact Fluorescent 8 40 0.32 500 160 NO SENSOR PROPOSED 0 0.88 440 - 440 71.63$

735 E.C.L.C. Stairs to Basement 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

1 31 0.03 3,640 113 No Work Proposed 0 31 0.03 3,640 113 NO SENSOR PROPOSED 0 - - - - -$

736 E.C.L.C. Stairs to Basement 2' Wrap Fixture w/ (2) F17 T8 Lamps & (1) 2L Electronic Ballast

1 31 0.03 3,640 113 No Work Proposed 0 31 0.03 3,640 113 NO SENSOR PROPOSED 0 - - - - -$

737 E.C.L.C. Computer Storage 4' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

14 110 1.54 500 770 No Work Proposed 0 110 1.54 500 770 NO SENSOR PROPOSED 0 - - - - -$

738 E.C.L.C. Computer Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

739 E.C.L.C. Storage Room #2 4' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

4 110 0.44 500 220 No Work Proposed 0 110 0.44 500 220 NO SENSOR PROPOSED 0 - - - - -$

740 E.C.L.C. Storage Room #24' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast2 50 0.10 500 50

Re-lamp & Re-ballast 4' Fixture with (1) F32 Lamp, NP Ballast.

2 31 0.06 500 31 NO SENSOR PROPOSED 0 0.04 19 - 19 3.09$

741 E.C.L.C. Electrical Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

742 E.C.L.C. Crawlspace 100w Incandescent S/I 8 100 0.80 1,000 800Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

8 23 0.18 1,000 184 NO SENSOR PROPOSED 0 0.62 616 - 616 100.28$

743 E.C.L.C. Storage Room #34' Wrap Fixture w/ (2) F34 Econo-Watt

T12 Lamps & (1) 2-Light Magnetic Ballast2 80 0.16 500 80

Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 4' T8

Energy Saving Lamps, New Lamp Sockets.2 61 0.12 500 61 NO SENSOR PROPOSED 0 0.04 19 - 19 3.09$

21 of 45

Page 217: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

744 E.C.L.C. Storage Room #4 100w Incandescent S/I 1 100 0.10 500 50 New 4' Wrap Fixture, (2) F32 Lamps, NP Ballast, Miro4 Reflector.

1 55 0.06 500 28 NO SENSOR PROPOSED 0 0.05 23 - 23 3.66$

745 E.C.L.C. head Custodian1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

746 E.C.L.C. head Custodian Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

747 E.C.L.C. Boiler Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 1,000 244 No Work Proposed 0 61 0.24 1,000 244 NO SENSOR PROPOSED 0 - - - - -$

748 E.C.L.C. Boiler Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

749 E.C.L.C. Old Lunch Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

14 89 1.25 2,400 2,990 No Work Proposed 0 89 1.25 2,400 2990 NO SENSOR PROPOSED 0 - - - - -$

750 E.C.L.C. Old Lunch Room2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

751 E.C.L.C. Old Lunch Room 4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

8 61 0.49 2,400 1,171 No Work Proposed 0 61 0.49 2,400 1171 NO SENSOR PROPOSED 0 - - - - -$

752 E.C.L.C. Kitchen2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

753 E.C.L.C. Kitchen2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 No Work Proposed 0 89 0.80 2,400 1922 NO SENSOR PROPOSED 0 - - - - -$

754 E.C.L.C. Electrical Panel 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

755 E.C.L.C. School Services2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 2,400 1,848 No Work Proposed 0 110 0.77 2,400 1848 NO SENSOR PROPOSED 0 - - - - -$

756 E.C.L.C. Electrical Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

757 E.C.L.C. OutsideWall Pack Fixture w/ (1) 50w High

Pressure Sodium Lamp and Magnetic Ballast

19 65 1.24 3,640 4,495 No Work Proposed 0 65 1.24 3,640 4495 NO SENSOR PROPOSED 0 - - - - -$

758 E.C.L.C. OutsideWall Pack Fixture w/ (1) 100w High

Pressure Sodium Lamp and Magnetic Ballast

7 120 0.84 3,640 3,058 No Work Proposed 0 120 0.84 3,640 3058 NO SENSOR PROPOSED 0 - - - - -$

759 E.C.L.C. Outside 60w. Incandescent S/I 5 60 0.30 3,640 1,092Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

5 13 0.07 3,640 237 NO SENSOR PROPOSED 0 0.24 855 - 855 139.26$

760 E.C.L.C. OutsideParking Lot Fixture Mounted on a Pole w/ (1) 400w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast5 445 2.23 3,640 8,099 No Work Proposed 0 445 2.23 3,640 8099 NO SENSOR PROPOSED 0 - - - - -$

20.00 5.84 8,485.20 6,447.84 14,933.04 $2,431.10

761M.W.

ErricksonCorridor 4-8

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 3,640 666 No Work Proposed 0 61 0.18 3,640 666 NO SENSOR PROPOSED 0 - - - - -$

762 M.W. Errickson

Corridor 4-8 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

763M.W.

ErricksonCorridor 10-11

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 61 0.73 3,640 2,664 No Work Proposed 0 61 0.73 3,640 2664 NO SENSOR PROPOSED 0 - - - - -$

764 M.W. Errickson

Corridor 10-11 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

765M.W.

ErricksonCorridor 31

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 No Work Proposed 0 61 0.24 3,640 888 NO SENSOR PROPOSED 0 - - - - -$

766M.W.

ErricksonCorridor Main

2X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballast

3 220 0.66 3,640 2,402 No Work Proposed 0 220 0.66 3,640 2402 NO SENSOR PROPOSED 0 - - - - -$

767 M.W. Errickson

Corridor Main Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 3,640 379 No Work Proposed 0 26 0.10 3,640 379 NO SENSOR PROPOSED 0 - - - - -$

768 M.W. Errickson

Corridor Main Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 3,640 379 No Work Proposed 0 26 0.10 3,640 379 NO SENSOR PROPOSED 0 - - - - -$

769M.W.

ErricksonCorridor 39-40

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 61 0.98 3,640 3,553 No Work Proposed 0 61 0.98 3,640 3553 NO SENSOR PROPOSED 0 - - - - -$

770 M.W. Errickson

Corridor 39-40 Exit Sign w/ 2w LED 5 2 0.01 8,760 88 No Work Proposed 0 2 0.01 8,760 88 NO SENSOR PROPOSED 0 - - - - -$

771 M.W. Errickson

Corridor 39-40 Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 3,640 95 No Work Proposed 0 26 0.03 3,640 95 NO SENSOR PROPOSED 0 - - - - -$

772M.W.

ErricksonCorridor 44-50

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

23 61 1.40 3,640 5,107 No Work Proposed 0 61 1.40 3,640 5107 NO SENSOR PROPOSED 0 - - - - -$

773 M.W. Errickson

Corridor 44-50 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

774M.W.

ErricksonCorridor 81-85

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

775 M.W. Errickson

Corridor 81-85 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

776M.W.

ErricksonCorridor 67-72

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

17 61 1.04 3,640 3,775 No Work Proposed 0 61 1.04 3,640 3775 NO SENSOR PROPOSED 0 - - - - -$

777 M.W. Errickson

Corridor 67-72 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

778M.W.

ErricksonKitchen

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 2,400 3,168 No Work Proposed 0 110 1.32 2,400 3168 NO SENSOR PROPOSED 0 - - - - -$

779M.W.

ErricksonKitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

780M.W.

ErricksonCafeteria

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

47 110 5.17 3,640 18,819 No Work Proposed 0 110 5.17 3,640 18819 NO SENSOR PROPOSED 0 - - - - -$

781 M.W. Errickson

Cafeteria Exit Sign w/ 2w LED 4 2 0.01 8,760 70 No Work Proposed 0 2 0.01 8,760 70 NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at the ECLC:

22 of 45

Page 218: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

782M.W.

ErricksonStage

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

22 110 2.42 2,400 5,808 No Work Proposed 0 110 2.42 2,400 5808 NO SENSOR PROPOSED 0 - - - - -$

783 M.W. Errickson

Stage Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

784M.W.

ErricksonGym

Industrial Hood 8' Fxiture with (2) F32 T8 Lamps & (2) 2L Electronic Ballast

56 61 3.42 2,400 8,198 No Work Proposed 0 61 3.42 2,400 8198 NO SENSOR PROPOSED 0 - - - - -$

785 M.W. Errickson

Gym Exit Sign w/ 2w LED 4 2 0.01 8,760 70 No Work Proposed 0 2 0.01 8,760 70 NO SENSOR PROPOSED 0 - - - - -$

786M.W.

ErricksonPrincipal

4X4 recessed troffer with (6) F32 T8 Lamps & (2) 3-Light Electronic ballasts

1 178 0.18 2,400 427 No Work Proposed 0 178 0.18 1,560 278Wall Switch Dual Technology

Occupancy Sensor1 - - 150 150 24.88$

787M.W.

ErricksonNurse's Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 No Work Proposed 0 89 0.53 2,400 1282 NO SENSOR PROPOSED 0 - - - - -$

788 M.W. Errickson

Nurse's Office Recessed Can Can w/ (2) 13w CF PL 2 26 0.05 2,400 125 No Work Proposed 0 26 0.05 2,400 125 NO SENSOR PROPOSED 0 - - - - -$

789 M.W. Errickson

Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

790M.W.

ErricksonBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

791M.W.

ErricksonBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

792 M.W. Errickson

Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

793M.W.

ErricksonWork Room

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 2,400 528 NO SENSOR PROPOSED 0 - - - - -$

794 M.W. Errickson

Corridor Recessed Can Can w/ (2) 13w CF PL 2 26 0.05 3,640 189 No Work Proposed 0 26 0.05 3,640 189 NO SENSOR PROPOSED 0 - - - - -$

795M.W.

ErricksonMain Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 No Work Proposed 0 89 0.80 2,400 1922 NO SENSOR PROPOSED 0 - - - - -$

796M.W.

ErricksonLobby (1-8)

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

8 220 1.76 3,640 6,406 No Work Proposed 0 220 1.76 3,640 6406 NO SENSOR PROPOSED 0 - - - - -$

797M.W.

ErricksonLobby (1-8)

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 3,640 1,602 No Work Proposed 0 110 0.44 3,640 1602 NO SENSOR PROPOSED 0 - - - - -$

798M.W.

ErricksonLobby (1-8)

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 No Work Proposed 0 61 0.12 3,640 444 NO SENSOR PROPOSED 0 - - - - -$

799M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

800M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

801M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

802M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

803M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

804M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

805M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

806M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

807M.W.

ErricksonBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

808M.W.

ErricksonBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

809 M.W. Errickson

Custodian 1 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 1,000 62 No Work Proposed 0 31 0.06 1,000 62 NO SENSOR PROPOSED 0 - - - - -$

810 M.W. Errickson

Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

811M.W.

ErricksonGirls

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

812 M.W. Errickson

Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

23 of 45

Page 219: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

813 M.W. Errickson

Mechanical 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

814M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 975 535

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 0.44 662 288 950 158.03$

815M.W.

ErricksonComputer

4' Fxiture with Egg Style Lens with (2) F32 T8 Lamps & (1) 2L Electonic Ballast

5 61 0.31 1,500 458

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

5 55 0.28 975 268

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

2 0.03 45 144 189 31.51$

816M.W.

ErricksonComputer

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

817M.W.

ErricksonLibrary

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

8 110 0.88 2,400 2,112 No Work Proposed 0 110 0.88 2,400 2112 NO SENSOR PROPOSED 0 - - - - -$

818M.W.

ErricksonLibrary

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts27 110 2.97 2,400 7,128

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

27 61 1.65 2,400 3953 NO SENSOR PROPOSED 0 1.32 3,175 - 3,175 528.35$

819M.W.

ErricksonAudio Visual

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 No Work Proposed 0 110 0.44 1,500 660 NO SENSOR PROPOSED 0 - - - - -$

820M.W.

ErricksonMedia Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 No Work Proposed 0 89 0.36 2,400 854 NO SENSOR PROPOSED 0 - - - - -$

821M.W.

ErricksonCST

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts4 110 0.44 2,400 1,056

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

4 61 0.24 2,400 586 NO SENSOR PROPOSED 0 0.20 470 - 470 78.27$

822M.W.

ErricksonSpeech

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 1,500 495 No Work Proposed 0 110 0.33 975 322

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 173 173 28.83$

823M.W.

ErricksonArt Class

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts6 110 0.66 1,500 990

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

6 61 0.37 1,500 549 NO SENSOR PROPOSED 0 0.29 441 - 441 73.38$

824M.W.

ErricksonArt Class

4' Fxiture with Egg Style Lens with (2) F32 T8 Lamps & (1) 2L Electonic Ballast

5 61 0.31 1,500 458

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Low Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

5 55 0.28 1,500 413 NO SENSOR PROPOSED 0 0.03 45 - 45 7.49$

825M.W.

ErricksonKiln

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 No Work Proposed 0 61 0.12 1,500 183 NO SENSOR PROPOSED 0 - - - - -$

826M.W.

ErricksonArt Storage

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts2 110 0.22 500 110

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

2 61 0.12 500 61 NO SENSOR PROPOSED 0 0.10 49 - 49 8.15$

827M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

828M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

829M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

830M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

831M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

832M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

833M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

834M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

24 of 45

Page 220: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

835M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts4 110 0.44 1,500 660

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

4 61 0.24 1,500 366 NO SENSOR PROPOSED 0 0.20 294 - 294 48.92$

836 M.W. Errickson

Girls 4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

5 57 0.29 2,400 684 No Work Proposed 0 57 0.29 2,400 684 NO SENSOR PROPOSED 0 - - - - -$

837 M.W. Errickson

Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

838 M.W. Errickson

Custodian 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 1,000 183 No Work Proposed 0 61 0.18 650 119 Wall Switch Occupancy Sensor 1 - - 64 64 10.66$

839 M.W. Errickson

Boys 4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

5 57 0.29 2,400 684 No Work Proposed 0 57 0.29 2,400 684 NO SENSOR PROPOSED 0 - - - - -$

840 M.W. Errickson

Boys Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

841M.W.

ErricksonSupervisor

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 1,560 381

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 205 205 34.11$

842 M.W. Errickson

Storage 10 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

843 M.W. Errickson

Attic 23w Compact Fluorescent S/I 9 23 0.21 500 104 No Work Proposed 0 23 0.21 500 104 NO SENSOR PROPOSED 0 - - - - -$

844M.W.

ErricksonElevator

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

845M.W.

ErricksonElevator

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 2,400 264 No Work Proposed 0 110 0.11 2,400 264 NO SENSOR PROPOSED 0 - - - - -$

846M.W.

ErricksonOffice

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 1,560 343 Wall Switch Occupancy Sensor 1 - - 185 185 30.75$

847M.W.

ErricksonSpeech

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

10 110 1.10 1,500 1,650 No Work Proposed 0 110 1.10 975 1073

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

2 - - 578 578 96.10$

848 M.W. Errickson

Storage 7 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

849 M.W. Errickson

Storage 7 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

850 M.W. Errickson

Storage 150w Incandescent S/I 3 150 0.45 500 225 Re-lamp with 40w Compact Fluorescent 3 40 0.12 500 60 NO SENSOR PROPOSED 0 0.33 165 - 165 27.46$

851M.W.

ErricksonSGI

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 No Work Proposed 0 110 0.44 975 429 Wall Switch Occupancy Sensor 1 - - 231 231 38.44$

852M.W.

ErricksonStorage 5

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 500 55 No Work Proposed 0 110 0.11 500 55 NO SENSOR PROPOSED 0 - - - - -$

853M.W.

ErricksonKitchen

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 2,400 3,168 No Work Proposed 0 110 1.32 2,400 3168 NO SENSOR PROPOSED 0 - - - - -$

854M.W.

ErricksonOffice

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

855M.W.

ErricksonChair Storage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

856 M.W. Errickson

Outside Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

857 M.W. Errickson

Receiving Room 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 2,400 298 No Work Proposed 0 31 0.12 2,400 298 NO SENSOR PROPOSED 0 - - - - -$

858 M.W. Errickson

Emergency Generator 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 2,400 298 No Work Proposed 0 31 0.12 2,400 298 NO SENSOR PROPOSED 0 - - - - -$

859 M.W. Errickson

Panel Room 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 1,000 124 No Work Proposed 0 31 0.12 1,000 124 NO SENSOR PROPOSED 0 - - - - -$

860 M.W. Errickson

Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

861 M.W. Errickson

Outside Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

862M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

863M.W.

ErricksonLobby

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 3,640 400 No Work Proposed 0 110 0.11 3,640 400 NO SENSOR PROPOSED 0 - - - - -$

864M.W.

ErricksonCoat Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 No Work Proposed 0 61 0.06 1,500 92 NO SENSOR PROPOSED 0 - - - - -$

865 M.W. Errickson

Coat Room 23w Compact Fluorescent S/I 2 23 0.05 1,500 69 No Work Proposed 0 23 0.05 1,500 69 NO SENSOR PROPOSED 0 - - - - -$

866M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

867 M.W. Errickson

Toilet 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 No Work Proposed 0 23 0.02 2,400 55 NO SENSOR PROPOSED 0 - - - - -$

868M.W.

ErricksonStorage

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 500 45 No Work Proposed 0 89 0.09 500 45 NO SENSOR PROPOSED 0 - - - - -$

869M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts6 110 0.66 1,500 990

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

6 61 0.37 1,500 549 NO SENSOR PROPOSED 0 0.29 441 - 441 73.38$

25 of 45

Page 221: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

870M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 1,500 495 No Work Proposed 0 110 0.33 1,500 495 NO SENSOR PROPOSED 0 - - - - -$

871 M.W. Errickson

Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

872M.W.

ErricksonToilet

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

873M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

874M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

875M.W.

ErricksonBathroom

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

876M.W.

ErricksonLobby

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 3,640 400 No Work Proposed 0 110 0.11 3,640 400 NO SENSOR PROPOSED 0 - - - - -$

877M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

878M.W.

ErricksonStorage Alcove

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 500 55 No Work Proposed 0 110 0.11 500 55 NO SENSOR PROPOSED 0 - - - - -$

879M.W.

ErricksonStorage Alcove

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 500 55 No Work Proposed 0 110 0.11 500 55 NO SENSOR PROPOSED 0 - - - - -$

880M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

881 M.W. Errickson

Bathroom 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 No Work Proposed 0 23 0.02 2,400 55 NO SENSOR PROPOSED 0 - - - - -$

882M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

883M.W.

ErricksonCoat Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 No Work Proposed 0 61 0.06 1,500 92 NO SENSOR PROPOSED 0 - - - - -$

884M.W.

ErricksonToilet 75w. Incandescent S/I 1 75 0.08 2,400 180

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 2,400 31 NO SENSOR PROPOSED 0 0.06 149 - 149 24.76$

885M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485

Remove and Replace Existing Fixture With a New 1x8 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' T8 Energy Saving Lamps.

9 61 0.55 1,500 824 NO SENSOR PROPOSED 0 0.44 662 - 662 110.07$

886 M.W. Errickson

Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

887 M.W. Errickson

Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

888 M.W. Errickson

Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

889M.W.

ErricksonBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

890M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

891 M.W. Errickson

Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

892 M.W. Errickson

Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

893 M.W. Errickson

Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

894M.W.

ErricksonBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

895M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

896 M.W. Errickson

Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

897 M.W. Errickson

Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - -$

898 M.W. Errickson

Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

899 M.W. Errickson

Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

900M.W.

ErricksonBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

901M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

902 M.W. Errickson

Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

903M.W.

ErricksonMPR Recessed Can Can w/ (2) 57w CF PL 13 114 1.48 2,400 3,557 No Work Proposed 0 114 1.48 2,400 3557 NO SENSOR PROPOSED 0 - - - - -$

26 of 45

Page 222: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

904 M.W. Errickson

Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

905M.W.

ErricksonRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

906M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

907M.W.

ErricksonKitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

908M.W.

ErricksonKitchen Storage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

909 M.W. Errickson

Cafeteria Recessed Can Can w/ (2) 57w CF PL 12 114 1.37 3,640 4,980 No Work Proposed 0 114 1.37 3,640 4980 NO SENSOR PROPOSED 0 - - - - -$

910 M.W. Errickson

Cafeteria Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

911M.W.

ErricksonRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

912 M.W. Errickson

Custodian Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 650 40 Wall Switch Occupancy Sensor 1 - - 21 21 3.55$

913 M.W. Errickson

Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

914 M.W. Errickson

Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

915M.W.

ErricksonBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

916M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

917 M.W. Errickson

Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

918 M.W. Errickson

Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

919 M.W. Errickson

Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

920M.W.

ErricksonBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

921M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

922 M.W. Errickson

Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

923M.W.

ErricksonGirls

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

924 M.W. Errickson

Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

925 M.W. Errickson

Custodian 3 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

926M.W.

ErricksonBoys

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

927 M.W. Errickson

Boys Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 No Work Proposed 0 26 0.03 2,400 62 NO SENSOR PROPOSED 0 - - - - -$

928M.W.

ErricksonMen's Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

929M.W.

ErricksonMen's Room

2' Vanity Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2,400 82 NO SENSOR PROPOSED 0 0.03 62 - 62 10.38$

930M.W.

ErricksonTeachers Room

4X4 recessed troffer with (6) F32 T8 Lamps & (2) 3-Light Electronic ballasts

4 178 0.71 2,400 1,709 No Work Proposed 0 178 0.71 1,560 1111

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 598 598 99.52$

931M.W.

ErricksonTeachers Room 60w. Incandescent S/I 2 60 0.12 2,400 288

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.09 226 - 226 37.54$

932M.W.

ErricksonTeachers Room 25w. Incandescent S/I A-Lamp 2 25 0.05 2,400 120

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.02 58 - 58 9.58$

933M.W.

ErricksonFaculty Work Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 2,400 878 No Work Proposed 0 61 0.37 2,400 878 NO SENSOR PROPOSED 0 - - - - -$

934 M.W. Errickson

Electrical Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

935 M.W. Errickson

Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

936M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 975 1287

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 693 693 115.32$

937M.W.

ErricksonInstrumental Music

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 1,500 1,155 No Work Proposed 0 110 0.77 975 751

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 404 404 67.27$

938M.W.

ErricksonInstrumental Music

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 No Work Proposed 0 61 0.06 1,500 92 NO SENSOR PROPOSED 0 - - - - -$

939M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

11 110 1.21 1,500 1,815 No Work Proposed 0 110 1.32 1,500 1980 NO SENSOR PROPOSED 0 (0.11) (165) - (165) (27.46)$

27 of 45

Page 223: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

940M.W.

ErricksonClass

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 No Work Proposed 0 61 0.06 975 59

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 32 32 5.33$

941M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 975 1287

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 693 693 115.32$

942M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 1,500 1980 NO SENSOR PROPOSED 0 - - - - -$

943M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 1,500 1980 NO SENSOR PROPOSED 0 - - - - -$

944M.W.

ErricksonBoys

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

945M.W.

ErricksonBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

946 M.W. Errickson

Janitors Closet 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

947M.W.

ErricksonGirls

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

948M.W.

ErricksonGirls

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

949M.W.

ErricksonOutside

Wall Pack Fixture w/ (1) 50w High Pressure Sodium Lamp and Magnetic

Ballast15 65 0.98 3,640 3,549 No Work Proposed 0 65 0.98 3,640 3549 NO SENSOR PROPOSED 0 - - - - -$

950M.W.

ErricksonOutside

Wall Pack Fixture w/ (1) 70w High Pressure Sodium Lamp and Magnetic

Ballast3 92 0.28 3,640 1,005 No Work Proposed 0 92 0.28 3,640 1005 NO SENSOR PROPOSED 0 - - - - -$

951M.W.

ErricksonOutside

Wal Pack Fixture with (1) 250w Metal Halide Lamp and (1) Magnetic HID Ballast

15 295 4.43 3,640 16,107 No Work Proposed 0 295 4.43 3,640 16107 NO SENSOR PROPOSED 0 - - - - -$

952M.W.

ErricksonOutside

Wall Pack Fixture with (1) 100w Metal Halide Lamp and (1) Magnetic HID Ballast

15 120 1.80 3,640 6,552 No Work Proposed 0 120 1.80 3,640 6552 NO SENSOR PROPOSED 0 - - - - -$

953M.W.

ErricksonOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 250w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast4 286 1.14 3,640 4,164 No Work Proposed 0 286 1.14 3,640 4164 NO SENSOR PROPOSED 0 - - - - -$

17 13.91 21,992.50 4,459.39 26,451.89 $4,401.59

954Laura

DonovanCorridor 400-403

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 No Work Proposed 0 61 0.37 3,640 1332 NO SENSOR PROPOSED 0 - - - - -$

955Laura

DonovanCorridor 400-403

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 3,640 400 No Work Proposed 0 110 0.11 3,640 400 NO SENSOR PROPOSED 0 - - - - -$

956Laura

DonovanCorridor 400-403

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 No Work Proposed 0 61 0.37 3,640 1332 NO SENSOR PROPOSED 0 - - - - -$

957 Laura Donovan

Corridor 400-403 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

958Laura

DonovanCorridor 404-412

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 61 0.73 3,640 2,664 No Work Proposed 0 61 0.73 3,640 2664 NO SENSOR PROPOSED 0 - - - - -$

959Laura

DonovanCorridor 402-404

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

13 61 0.79 3,640 2,887 No Work Proposed 0 61 0.79 3,640 2887 NO SENSOR PROPOSED 0 - - - - -$

960Laura

DonovanCorridor 402-404

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 No Work Proposed 0 61 0.12 3,640 444 NO SENSOR PROPOSED 0 - - - - -$

961Laura

DonovanCorridor 402-404 Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 3,640 95 No Work Proposed 0 26 0.03 3,640 95 NO SENSOR PROPOSED 0 - - - - -$

962 Laura Donovan

Corridor 402-404 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

963Laura

DonovanCorridor 413-420

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 61 0.73 3,640 2,664 No Work Proposed 0 61 0.73 3,640 2664 NO SENSOR PROPOSED 0 - - - - -$

964Laura

DonovanCorridor 413-420

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 No Work Proposed 0 61 0.06 3,640 222 NO SENSOR PROPOSED 0 - - - - -$

965 Laura Donovan

Corridor 413-420 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

966Laura

DonovanCorridor 412A

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 No Work Proposed 0 61 0.37 3,640 1332 NO SENSOR PROPOSED 0 - - - - -$

967 Laura Donovan

Corridor 412A Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

968Laura

DonovanCorridor Main

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 61 0.67 3,640 2,442 No Work Proposed 0 61 0.67 3,640 2442 NO SENSOR PROPOSED 0 - - - - -$

969 Laura Donovan

Corridor Main Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

970Laura

DonovanCorridor 421-424

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 61 0.73 3,640 2,664 No Work Proposed 0 61 0.73 3,640 2664 NO SENSOR PROPOSED 0 - - - - -$

971 Laura Donovan

Corridor 421-424 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

972Laura

DonovanCorridor 432-435

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

10 61 0.61 3,640 2,220 No Work Proposed 0 61 0.61 3,640 2220 NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at M.W. Errickson:

28 of 45

Page 224: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

973Laura

DonovanCorridor 432-435

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 No Work Proposed 0 61 0.06 3,640 222 NO SENSOR PROPOSED 0 - - - - -$

974 Laura Donovan

Corridor 432-435 Exit Sign w/ 2w LED 4 2 0.01 8,760 70 No Work Proposed 0 2 0.01 8,760 70 NO SENSOR PROPOSED 0 - - - - -$

975Laura

DonovanCorridor 5-8

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 3,640 1,944 No Work Proposed 0 89 0.53 3,640 1944 NO SENSOR PROPOSED 0 - - - - -$

976Laura

DonovanCorridor 5-8

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

13 61 0.79 3,640 2,887 No Work Proposed 0 61 0.79 3,640 2887 NO SENSOR PROPOSED 0 - - - - -$

977 Laura Donovan

Corridor 5-8 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

978Laura

DonovanCorridor 427-430

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

979Laura

DonovanCorridor 110-113

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 No Work Proposed 0 61 0.37 3,640 1332 NO SENSOR PROPOSED 0 - - - - -$

980Laura

DonovanMedia Center 435

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

46 110 5.06 2,400 12,144 No Work Proposed 0 110 5.06 2,400 12144 NO SENSOR PROPOSED 0 - - - - -$

981Laura

DonovanComm. - MC

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 1,500 330 No Work Proposed 0 110 0.22 1,500 330 NO SENSOR PROPOSED 0 - - - - -$

982 Laura Donovan

Comm. - MC Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

983Laura

DonovanCafeteria

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

45 110 4.95 3,640 18,018 No Work Proposed 0 110 4.95 3,640 18018 NO SENSOR PROPOSED 0 - - - - -$

984 Laura Donovan

Storage - Caf 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - -$

985Laura

DonovanRoom 44 - Caf

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 2,400 264 No Work Proposed 0 110 0.11 2,400 264 NO SENSOR PROPOSED 0 - - - - -$

986Laura

DonovanKitchen

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

10 110 1.10 2,400 2,640 No Work Proposed 0 110 1.10 2,400 2640 NO SENSOR PROPOSED 0 - - - - -$

987Laura

DonovanKitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

988 Laura Donovan

Kitchen Exit Sign w/ 2w LED 4 2 0.01 8,760 70 No Work Proposed 0 2 0.01 8,760 70 NO SENSOR PROPOSED 0 - - - - -$

989Laura

DonovanGym

High Bay Fixture with (1) 400w Metal Halide Lamp and (1) Magnetic HID Ballast

20 445 8.90 2,400 21,360

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

20 234 4.68 2,400 11232 NO SENSOR PROPOSED 0 4.22 10,128 - 10,128 1,716.70$

990Laura

DonovanStorage - Gym

4' Industrail Hood Fixture with (2) F34 Econo-Watt T12 Lamps & (1) 2L Magnetic

Ballast1 80 0.08 500 40

Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Low Power Ballast, (2) 4' T8 Energy Saving Lamps, New Lamp Sockets.

1 55 0.06 500 28 NO SENSOR PROPOSED 0 0.03 13 - 13 2.12$

991 Laura Donovan

Storage - Gym Recessed Can Can w/ (2) 13w CF PL 2 26 0.05 500 26 No Work Proposed 0 26 0.05 500 26 NO SENSOR PROPOSED 0 - - - - -$

992 Laura Donovan

Office - Gym 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

993Laura

DonovanBR - Gym

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

994Laura

DonovanGym - Stair Recessed Can Can w/ (2) 13w CF PL 3 26 0.08 2,400 187 No Work Proposed 0 26 0.08 2,400 187 NO SENSOR PROPOSED 0 - - - - -$

995 Laura Donovan

Gym - Stair Exit Sign w/ (2) 20w Incandescent Lamps 6 40 0.24 8,760 2,102 Remove and Replace existing exit sign with a new LED exit sign.

6 2 0.01 8,760 105 NO SENSOR PROPOSED 0 0.23 1,997 - 1,997 338.54$

996 Laura Donovan

Stage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

30 61 1.83 2,400 4,392 No Work Proposed 0 61 1.83 2,400 4392 NO SENSOR PROPOSED 0 - - - - -$

997 Laura Donovan

Stage 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 2,400 298 No Work Proposed 0 31 0.12 2,400 298 NO SENSOR PROPOSED 0 - - - - -$

998 Laura Donovan

Stage Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

999Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

11 110 1.21 1,500 1,815 No Work Proposed 0 110 1.21 975 1180

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 635 635 107.67$

1000 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1001Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1002Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 975 858

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 462 462 78.31$

1003 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1004Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 975 858

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 462 462 78.31$

1005 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1006Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 975 858

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 462 462 78.31$

29 of 45

Page 225: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1007 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1008Laura

DonovanSupervisors Office

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

4 110 0.44 2,400 1,056 No Work Proposed 0 110 0.44 1,560 686

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 370 370 62.65$

1009 Laura Donovan

Supervisors Office 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

1010Laura

DonovanStorage #1 100w Incandescent S/I 4 100 0.40 500 200

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

4 23 0.09 500 46 NO SENSOR PROPOSED 0 0.31 154 - 154 26.10$

1011 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1012 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1013 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1014 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1015 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1016 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1017 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1018 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1019 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1020 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1021Laura

DonovanElectric Service 100w Incandescent S/I 4 100 0.40 1,000 400

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

4 23 0.09 1,000 92 NO SENSOR PROPOSED 0 0.31 308 - 308 52.21$

1022 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1023 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1024 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1025 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1026 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1027 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1028 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1029 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1030 Laura Donovan

Girls 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 31 0.19 2,400 446 No Work Proposed 0 31 0.19 2,400 446 NO SENSOR PROPOSED 0 - - - - -$

1031 Laura Donovan

Storage 23w Compact Fluorescent S/I 4 23 0.09 500 46 No Work Proposed 0 23 0.09 500 46 NO SENSOR PROPOSED 0 - - - - -$

1032 Laura Donovan

Boys 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 31 0.19 2,400 446 No Work Proposed 0 31 0.19 2,400 446 NO SENSOR PROPOSED 0 - - - - -$

1033 Laura Donovan

Storage 23w Compact Fluorescent S/I 3 23 0.07 500 35 No Work Proposed 0 23 0.07 500 35 NO SENSOR PROPOSED 0 - - - - -$

1034 Laura Donovan

Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1035Laura

DonovanExit Vestibule

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 No Work Proposed 0 61 0.06 3,640 222 NO SENSOR PROPOSED 0 - - - - -$

1036Laura

DonovanArt Room

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

15 110 1.65 1,500 2,475 No Work Proposed 0 110 1.65 975 1609

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

2 - - 866 866 146.83$

1037 Laura Donovan

Kiln Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 1,500 549 No Work Proposed 0 61 0.37 975 357 Wall Switch Occupancy Sensor 1 - - 192 192 32.57$

1038Laura

DonovanCST

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 2,400 878 No Work Proposed 0 61 0.37 1,560 571

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 307 307 52.11$

1039 Laura Donovan

Boys 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 31 0.19 2,400 446 No Work Proposed 0 31 0.19 2,400 446 NO SENSOR PROPOSED 0 - - - - -$

1040Laura

DonovanCustodian 100w Incandescent S/I 2 100 0.20 1,000 200

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

2 23 0.05 1,000 46 NO SENSOR PROPOSED 0 0.15 154 - 154 26.10$

1041Laura

DonovanSprinkler Valve 100w Incandescent S/I 4 100 0.40 1,000 400

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

4 23 0.09 1,000 92 NO SENSOR PROPOSED 0 0.31 308 - 308 52.21$

1042 Laura Donovan

Girls 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 31 0.19 2,400 446 No Work Proposed 0 31 0.19 2,400 446 NO SENSOR PROPOSED 0 - - - - -$

1043 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1044 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1045 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1046 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1047 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1048 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

30 of 45

Page 226: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1049Laura

DonovanComputer Class

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

27 61 1.65 1,500 2,471 No Work Proposed 0 61 1.65 975 1606

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

2 - - 865 865 146.56$

1050Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 975 714

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 384 384 65.14$

1051Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 975 833

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 448 448 76.00$

1052Laura

DonovanEnrichment Class

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 975 833

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 448 448 76.00$

1053Laura

DonovanStorage

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 500 110 No Work Proposed 0 110 0.22 500 110 NO SENSOR PROPOSED 0 - - - - -$

1054 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 No Work Proposed 0 110 0.88 1,500 1320 NO SENSOR PROPOSED 0 - - - - -$

1055 Laura Donovan

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 No Work Proposed 0 61 0.24 1,500 366 NO SENSOR PROPOSED 0 - - - - -$

1056Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 975 1287

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 693 693 117.46$

1057Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 975 1287

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 693 693 117.46$

1058Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 975 1287

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 693 693 117.46$

1059Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 975 1287

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 693 693 117.46$

1060 Laura Donovan

Custodian 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

4 61 0.24 1,000 244 No Work Proposed 0 61 0.24 1,000 244 NO SENSOR PROPOSED 0 - - - - -$

1061Laura

DonovanStorage 100w Incandescent S/I 4 100 0.40 500 200

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

4 23 0.09 500 46 NO SENSOR PROPOSED 0 0.31 154 - 154 26.10$

1062Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 975 1287

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 693 693 117.46$

1063Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1064 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 1,500 1980 NO SENSOR PROPOSED 0 - - - - -$

1065Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1066 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 1,500 1980 NO SENSOR PROPOSED 0 - - - - -$

1067Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1068 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 1,500 1980 NO SENSOR PROPOSED 0 - - - - -$

1069Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1070 Laura Donovan

Class 8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

16 110 1.76 1,500 2,640 No Work Proposed 0 110 1.76 1,500 2640 NO SENSOR PROPOSED 0 - - - - -$

1071Laura

DonovanStorage 75w. Incandescent S/I 2 75 0.15 500 75

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 500 13 NO SENSOR PROPOSED 0 0.12 62 - 62 10.51$

1072Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1073Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

16 110 1.76 1,500 2,640 No Work Proposed 0 110 1.76 975 1716

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 924 924 156.62$

1074Laura

DonovanStorage 75w. Incandescent S/I 2 75 0.15 500 75

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 500 13 NO SENSOR PROPOSED 0 0.12 62 - 62 10.51$

1075Laura

DonovanRestroom 40w. Incandescent S/I 2 40 0.08 2,400 192

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1076Laura

DonovanElectric Room 75w. Incandescent S/I 2 75 0.15 1,000 150

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 1,000 26 NO SENSOR PROPOSED 0 0.12 124 - 124 21.02$

1077Laura

DonovanNurse's Office

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

8 89 0.71 2,400 1,709 No Work Proposed 0 89 0.71 2,400 1709 NO SENSOR PROPOSED 0 - - - - -$

31 of 45

Page 227: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1078Laura

DonovanStorage 100w Incandescent S/I 1 100 0.10 500 50

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

1 23 0.02 500 12 NO SENSOR PROPOSED 0 0.08 39 - 39 6.53$

1079Laura

DonovanBathroom 60w. Incandescent S/I 2 60 0.12 2,400 288

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.09 226 - 226 38.24$

1080Laura

DonovanMain Office

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

12 89 1.07 2,400 2,563 No Work Proposed 0 89 1.07 2,400 2563 NO SENSOR PROPOSED 0 - - - - -$

1081Laura

DonovanPrincipal

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

6 89 0.53 2,400 1,282 No Work Proposed 0 89 0.53 1,560 833

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 449 449 76.03$

1082Laura

DonovanWork Room

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 1,560 417 Wall Switch Occupancy Sensor 1 - - 224 224 38.02$

1083Laura

DonovanBathroom 60w. Incandescent S/I 2 60 0.12 2,400 288

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.09 226 - 226 38.24$

1084Laura

DonovanClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

11 110 1.21 1,500 1,815 No Work Proposed 0 110 1.21 975 1180

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

2 - - 635 635 107.67$

1085 Laura Donovan

Electric Panel 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

1086Laura

DonovanSmall Group

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 No Work Proposed 0 61 0.12 1,500 183 NO SENSOR PROPOSED 0 - - - - -$

1087 Laura Donovan

Small Group 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 1,500 549 No Work Proposed 0 61 0.37 1,500 549 NO SENSOR PROPOSED 0 - - - - -$

1088Laura

DonovanRestroom

2' Vanity Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2,400 82 NO SENSOR PROPOSED 0 0.03 62 - 62 10.58$

1089Laura

DonovanRestroom 60w. Incandescent S/I 2 60 0.12 2,400 288

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.09 226 - 226 38.24$

1090Laura

DonovanWomen's Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1091 Laura Donovan

Women's Room 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 2,400 149 No Work Proposed 0 31 0.06 2,400 149 NO SENSOR PROPOSED 0 - - - - -$

1092 Laura Donovan

Restroom 4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 2,400 149 No Work Proposed 0 31 0.06 2,400 149 NO SENSOR PROPOSED 0 - - - - -$

1093Laura

DonovanRestroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - -$

1094Laura

DonovanMusic Room

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

9 89 0.80 1,500 1,202 No Work Proposed 0 89 0.80 975 781 Wall Switch Occupancy Sensor 1 - - 421 421 71.28$

1095 Laura Donovan

Speech 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1096Laura

DonovanSpeech

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 No Work Proposed 0 61 0.06 1,500 92 NO SENSOR PROPOSED 0 - - - - -$

1097Laura

DonovanStorage 75w. Incandescent S/I 1 75 0.08 500 38

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 500 7 NO SENSOR PROPOSED 0 0.06 31 - 31 5.25$

1098Laura

DonovanBathroom 60w. Incandescent S/I 2 60 0.12 2,400 288

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2,400 62 NO SENSOR PROPOSED 0 0.09 226 - 226 38.24$

1099 Laura Donovan

Hub room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

1100Laura

DonovanTeachers Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

10 89 0.89 2,400 2,136 No Work Proposed 0 89 0.89 1,560 1388

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 748 748 126.72$

1101Laura

DonovanGirls

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 No Work Proposed 0 89 0.18 2,400 427 NO SENSOR PROPOSED 0 - - - - -$

1102Laura

DonovanBoys

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 No Work Proposed 0 89 0.18 2,400 427 NO SENSOR PROPOSED 0 - - - - -$

1103Laura

DonovanSmall Group C

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 89 0.62 1,500 935 No Work Proposed 0 89 0.62 1,500 935 NO SENSOR PROPOSED 0 - - - - -$

1104Laura

DonovanStorage #6

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 500 45 No Work Proposed 0 89 0.09 500 45 NO SENSOR PROPOSED 0 - - - - -$

1105Laura

DonovanClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 975 1041

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 561 561 95.04$

1106Laura

DonovanClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 975 1041

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 561 561 95.04$

1107Laura

DonovanClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

1108Laura

DonovanClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

32 of 45

Page 228: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1109Laura

DonovanClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 975 694

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 374 374 63.36$

1110 Laura Donovan

Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

1111 Laura Donovan

Class Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1112Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1113Laura

DonovanStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1114Laura

DonovanClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 975 694

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 374 374 63.36$

1115 Laura Donovan

Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

1116 Laura Donovan

Class Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1117Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1118Laura

DonovanStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1119Laura

DonovanClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 975 694

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 374 374 63.36$

1120 Laura Donovan

Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

1121 Laura Donovan

Class Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1122Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1123Laura

DonovanStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1124Laura

DonovanClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 975 694

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 374 374 63.36$

1125 Laura Donovan

Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

1126 Laura Donovan

Class Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1127Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1128Laura

DonovanStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1129 Laura Donovan

Lunch Room Recessed Can Can w/ (2) 57w CF PL 12 114 1.37 2,400 3,283 No Work Proposed 0 114 1.37 2,400 3283 NO SENSOR PROPOSED 0 - - - - -$

1130 Laura Donovan

Lunch Room Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1131Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1132Laura

DonovanHW Heater

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1133Laura

DonovanKitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

1134Laura

DonovanKitchen Storage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1135 Laura Donovan

MPR Recessed Can Can w/ (2) 57w CF PL 13 114 1.48 2,400 3,557 No Work Proposed 0 114 1.48 2,400 3557 NO SENSOR PROPOSED 0 - - - - -$

1136 Laura Donovan

MPR Exit Sign w/ 2w LED 13 2 0.03 8,760 228 No Work Proposed 0 2 0.03 8,760 228 NO SENSOR PROPOSED 0 - - - - -$

1137 Laura Donovan

Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1138 Laura Donovan

Custodian 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

1139Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1140 Laura Donovan

Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

1141 Laura Donovan

Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - -$

1142 Laura Donovan

Class Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1143Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1144Laura

DonovanStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

33 of 45

Page 229: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1145 Laura Donovan

Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - -$

1146Laura

DonovanOutside

Wall Pack Fixture w/ (1) 100w High Pressure Sodium Lamp and Magnetic

Ballast14 120 1.68 3,640 6,115 No Work Proposed 0 120 1.68 3,640 6115 NO SENSOR PROPOSED 0 - - - - -$

1147Laura

DonovanOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 400w High Pressure Sodium Lamp

and (1) Magnetic HID Ballast5 450 2.25 3,640 8,190 No Work Proposed 0 450 2.25 3,640 8190 NO SENSOR PROPOSED 0 - - - - -$

1148Laura

DonovanOutside

Wall Pack Fixture w/ (1) 50w High Pressure Sodium Lamp and Magnetic

Ballast6 65 0.39 3,640 1,420 No Work Proposed 0 65 0.39 3,640 1420 NO SENSOR PROPOSED 0 - - - - -$

1149Laura

DonovanOutside

Wal Pack Fixture with (1) 250w Metal Halide Lamp and (1) Magnetic HID Ballast

7 295 2.07 3,640 7,517 No Work Proposed 0 295 2.07 3,640 7517 NO SENSOR PROPOSED 0 - - - - -$

1150Laura

DonovanOutside

Wall Pack Fixture with (1) 100w Metal Halide Lamp and (1) Magnetic HID Ballast

15 120 1.80 3,640 6,552 No Work Proposed 0 120 1.80 3,640 6552 NO SENSOR PROPOSED 0 - - - - -$

32 7.15 15,405.28 15,384.18 30,789.46 $5,218.81

1151 West Freehold Corridor 262 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

27 61 1.65 3,640 5,995 No Work Proposed 0 61 1.65 3,640 5995 NO SENSOR PROPOSED 0 - - - - -$

1152 West Freehold Corridor 262 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

4 26 0.10 3,640 379 No Work Proposed 0 26 0.10 3,640 379 NO SENSOR PROPOSED 0 - - - - -$

1153 West Freehold Corridor 262 Exit Sign w/ 2w LED 4 2 0.01 8,760 70 No Work Proposed 0 2 0.01 8,760 70 NO SENSOR PROPOSED 0 - - - - -$

1154 West Freehold Corridor 261 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 No Work Proposed 0 61 0.61 3,640 2220 NO SENSOR PROPOSED 0 - - - - -$

1155 West Freehold Corridor 261 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

1 26 0.03 3,640 95 No Work Proposed 0 26 0.03 3,640 95 NO SENSOR PROPOSED 0 - - - - -$

1156 West Freehold Corridor 259,200-201 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

51 61 3.11 3,640 11,324 No Work Proposed 0 61 3.11 3,640 11324 NO SENSOR PROPOSED 0 - - - - -$

1157 West Freehold Corridor 259,200-201 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

5 26 0.13 3,640 473 No Work Proposed 0 26 0.13 3,640 473 NO SENSOR PROPOSED 0 - - - - -$

1158 West Freehold Corridor 259,200-201 Exit Sign w/ 2w LED 8 2 0.02 8,760 140 No Work Proposed 0 2 0.02 8,760 140 NO SENSOR PROPOSED 0 - - - - -$

1159 West Freehold Corridor 202 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

24 61 1.46 3,640 5,329 No Work Proposed 0 61 1.46 3,640 5329 NO SENSOR PROPOSED 0 - - - - -$

1160 West Freehold Corridor 202 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

4 26 0.10 3,640 379 No Work Proposed 0 26 0.10 3,640 379 NO SENSOR PROPOSED 0 - - - - -$

1161 West Freehold Corridor 260 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 No Work Proposed 0 61 0.61 3,640 2220 NO SENSOR PROPOSED 0 - - - - -$

1162 West Freehold Corridor 260 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

1 26 0.03 3,640 95 No Work Proposed 0 26 0.03 3,640 95 NO SENSOR PROPOSED 0 - - - - -$

1163 West Freehold Corridor 263 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

15 61 0.92 3,640 3,331 No Work Proposed 0 61 0.92 3,640 3331 NO SENSOR PROPOSED 0 - - - - -$

1164 West Freehold Corridor 263 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

1165 West Freehold Corridor 263 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

2 26 0.05 3,640 189 No Work Proposed 0 26 0.05 3,640 189 NO SENSOR PROPOSED 0 - - - - -$

1166 West Freehold Corridor 2632X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 No Work Proposed 0 61 0.12 3,640 444 NO SENSOR PROPOSED 0 - - - - -$

1167 West Freehold Corridor 103 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 No Work Proposed 0 61 0.61 3,640 2220 NO SENSOR PROPOSED 0 - - - - -$

1168 West Freehold Corridor 103 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

1169 West Freehold Corridor 104 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

13 61 0.79 3,640 2,887 No Work Proposed 0 61 0.79 3,640 2887 NO SENSOR PROPOSED 0 - - - - -$

1170 West Freehold Corridor 1042X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 No Work Proposed 0 61 0.06 3,640 222 NO SENSOR PROPOSED 0 - - - - -$

1171 West Freehold Corridor 1021X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 3,640 1,776 No Work Proposed 0 61 0.49 3,640 1776 NO SENSOR PROPOSED 0 - - - - -$

1172 West Freehold Corridor 102 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

1173 West Freehold Corridor 1012X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

1174 West Freehold Corridor 101 Recessed Can Can w/ (2) 13w CF PL 11 26 0.29 3,640 1,041 No Work Proposed 0 26 0.29 3,640 1041 NO SENSOR PROPOSED 0 - - - - -$

1175 West Freehold Corridor 101 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

1176 West Freehold Vest. 100 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

4 26 0.10 2,400 250 No Work Proposed 0 26 0.10 2,400 250 NO SENSOR PROPOSED 0 - - - - -$

1177 West Freehold Vest. 100Wall Pack Fixture with (2) 26w Compact

Fluorescent Lamps and (1) Magnetic Ballast

1 52 0.05 2,400 125 No Work Proposed 0 52 0.05 2,400 125 NO SENSOR PROPOSED 0 - - - - -$

1178 West Freehold Corridor 1051X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

1179 West Freehold Corridor 105 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1180 West Freehold Commons2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

12 34 0.41 2,400 979 No Work Proposed 0 34 0.41 2,400 979 NO SENSOR PROPOSED 0 - - - - -$

1181 West Freehold Commons Recessed Can Can w/ (2) 13w CF PL 18 26 0.47 2,400 1,123 No Work Proposed 0 26 0.47 2,400 1123 NO SENSOR PROPOSED 0 - - - - -$

1182 West Freehold Corridor 1071X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

1183 West Freehold Corridor 1072X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

8 34 0.27 3,640 990 No Work Proposed 0 34 0.27 3,640 990 NO SENSOR PROPOSED 0 - - - - -$

1184 West Freehold Corridor 1081X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

1185 West Freehold Corridor 108 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 No Work Proposed 0 61 0.61 3,640 2220 NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at Laura Donovan:

34 of 45

Page 230: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1186 West Freehold Corridor 108 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

1187 West Freehold Corridor 109 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

22 61 1.34 3,640 4,885 No Work Proposed 0 61 1.34 3,640 4885 NO SENSOR PROPOSED 0 - - - - -$

1188 West Freehold Corridor 109 Recessed Can Can w/ (2) 13w CF PL 3 26 0.08 3,640 284 No Work Proposed 0 26 0.08 3,640 284 NO SENSOR PROPOSED 0 - - - - -$

1189 West Freehold Corridor 109 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

1190 West Freehold Corridor 302 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

18 61 1.10 3,640 3,997 No Work Proposed 0 61 1.10 3,640 3997 NO SENSOR PROPOSED 0 - - - - -$

1191 West Freehold Corridor 3022X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 No Work Proposed 0 61 0.12 3,640 444 NO SENSOR PROPOSED 0 - - - - -$

1192 West Freehold Corridor 302 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1193 West Freehold Corridor 303 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

30 61 1.83 3,640 6,661 No Work Proposed 0 61 1.83 3,640 6661 NO SENSOR PROPOSED 0 - - - - -$

1194 West Freehold Corridor 303 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

2 26 0.05 3,640 189 No Work Proposed 0 26 0.05 3,640 189 NO SENSOR PROPOSED 0 - - - - -$

1195 West Freehold Corridor 303 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1196 West Freehold Corridor 304 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 No Work Proposed 0 61 0.61 3,640 2220 NO SENSOR PROPOSED 0 - - - - -$

1197 West Freehold Corridor 304 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

1 26 0.03 3,640 95 No Work Proposed 0 26 0.03 3,640 95 NO SENSOR PROPOSED 0 - - - - -$

1198 West Freehold Corridor 304 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

1199 West Freehold Corridor 305 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

30 61 1.83 3,640 6,661 No Work Proposed 0 61 1.83 3,640 6661 NO SENSOR PROPOSED 0 - - - - -$

1200 West Freehold Corridor 305 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

3 26 0.08 3,640 284 No Work Proposed 0 26 0.08 3,640 284 NO SENSOR PROPOSED 0 - - - - -$

1201 West Freehold Corridor 305 Exit Sign w/ 2w LED 4 2 0.01 8,760 70 No Work Proposed 0 2 0.01 8,760 70 NO SENSOR PROPOSED 0 - - - - -$

1202 West Freehold Corridor 306 4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 No Work Proposed 0 61 0.61 3,640 2220 NO SENSOR PROPOSED 0 - - - - -$

1203 West Freehold Corridor 306 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

1 26 0.03 3,640 95 No Work Proposed 0 26 0.03 3,640 95 NO SENSOR PROPOSED 0 - - - - -$

1204 West Freehold Corridor 306 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

1205 West Freehold Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 975 868

Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 467 467 74.39$

1206 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1207 West Freehold Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 975 868

Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 467 467 74.39$

1208 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1209 West Freehold Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 975 868

Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 467 467 74.39$

1210 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1211 West Freehold Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 975 868

Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 467 467 74.39$

1212 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1213 West Freehold Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 975 868

Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 467 467 74.39$

1214 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1215 West Freehold Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 975 868

Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 467 467 74.39$

1216 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1217 West Freehold Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 975 868

Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 467 467 74.39$

1218 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1219 West Freehold Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 975 868

Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 467 467 74.39$

1220 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1221 West Freehold Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 975 868

Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 467 467 74.39$

1222 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1223 West Freehold Storage Shed Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

1224 West Freehold Sprinkler Valve Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

1225 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

1226 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 1,500 1098 NO SENSOR PROPOSED 0 - - - - -$

1227 West Freehold -Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1228 West Freehold -Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1229 West Freehold MPR 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

15 61 0.92 2,400 2,196 No Work Proposed 0 61 0.92 2,400 2196 NO SENSOR PROPOSED 0 - - - - -$

35 of 45

Page 231: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1230 West Freehold Cafeteria A 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

11 89 0.98 3,640 3,564 No Work Proposed 0 89 0.98 3,640 3564 NO SENSOR PROPOSED 0 - - - - -$

1231 West Freehold Cafeteria A 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 3,640 2,664 No Work Proposed 0 61 0.73 3,640 2664 NO SENSOR PROPOSED 0 - - - - -$

1232 West Freehold -Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1233 West Freehold -Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1234 West Freehold -Serving Kitchen2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

1235 West Freehold -Kitchen Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1236 West Freehold Janitor Closet2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1237 West Freehold Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1238 West Freehold Class/Kindergarten 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

1239 West Freehold Class/Kindergarten 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 1,500 1098 NO SENSOR PROPOSED 0 - - - - -$

1240 West Freehold -Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1241 West Freehold -Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1242 West Freehold Class/Kindergarten 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

1243 West Freehold Class/Kindergarten 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 1,500 1098 NO SENSOR PROPOSED 0 - - - - -$

1244 West Freehold -Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1245 West Freehold -Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1246 West Freehold Class/Kindergarten 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

1247 West Freehold Class/Kindergarten 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 1,500 1098 NO SENSOR PROPOSED 0 - - - - -$

1248 West Freehold -Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1249 West Freehold -Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1250 West Freehold Class/Kindergarten 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

1251 West Freehold Class/Kindergarten 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 1,500 1098 NO SENSOR PROPOSED 0 - - - - -$

1252 West Freehold -Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1253 West Freehold -Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1254 West Freehold Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 975 868

Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 467 467 74.39$

1255 West Freehold Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 975 868

Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range

(8-15' Mtg Height) 1 - - 467 467 74.39$

1256 West Freehold Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 1,560 95Wall Switch Dual Technology

Occupancy Sensor1 - - 51 51 8.16$

1257 West Freehold Women's Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

1258 West Freehold Men's Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

1259 West Freehold IDF Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 No Work Proposed 0 61 0.12 1,500 183 NO SENSOR PROPOSED 0 - - - - -$

1260 West Freehold Electrical Closet2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1261 West Freehold SGI 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 975 595 Wall Switch Occupancy Sensor 1 - - 320 320 50.98$

1262 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1263 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1264 West Freehold Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1265 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1266 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1267 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1268 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1269 West Freehold SGI2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

1270 West Freehold SGI2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 No Work Proposed 0 89 0.71 1,500 1068 NO SENSOR PROPOSED 0 - - - - -$

36 of 45

Page 232: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1271 West Freehold SGI 22X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 No Work Proposed 0 89 0.53 1,500 801 NO SENSOR PROPOSED 0 - - - - -$

1272 West Freehold Girls2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 2,400 641 NO SENSOR PROPOSED 0 - - - - -$

1273 West Freehold Boys2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 2,400 641 NO SENSOR PROPOSED 0 - - - - -$

1274 West Freehold SGI 32X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 89 0.45 1,500 668 No Work Proposed 0 89 0.45 1,500 668 NO SENSOR PROPOSED 0 - - - - -$

1275 West Freehold Nurse's Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 89 0.45 2,400 1,068 No Work Proposed 0 89 0.45 2,400 1068 NO SENSOR PROPOSED 0 - - - - -$

1276 West Freehold Nurse's Office2X2 recessed troffer with (3) F17 T8 Lamps & (1) 3-Light Electronic ballast

4 50 0.20 2,400 480 No Work Proposed 0 50 0.20 2,400 480 NO SENSOR PROPOSED 0 - - - - -$

1277 West Freehold Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1278 West Freehold Main Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 2,400 2,350 No Work Proposed 0 89 0.98 2,400 2350 NO SENSOR PROPOSED 0 - - - - -$

1279 West Freehold Main Office2X2 recessed troffer with (3) F17 T8 Lamps & (1) 3-Light Electronic ballast

1 50 0.05 2,400 120 No Work Proposed 0 50 0.05 2,400 120 NO SENSOR PROPOSED 0 - - - - -$

1280 West Freehold Work Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 No Work Proposed 0 89 0.18 2,400 427 NO SENSOR PROPOSED 0 - - - - -$

1281 West Freehold Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1282 West Freehold Conference Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 2,400 641 NO SENSOR PROPOSED 0 - - - - -$

1283 West Freehold Principal2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 2,400 641 NO SENSOR PROPOSED 0 - - - - -$

1284 West Freehold Library 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

32 89 2.85 2,400 6,835 No Work Proposed 0 89 2.85 2,400 6835 NO SENSOR PROPOSED 0 - - - - -$

1285 West Freehold Library 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

38 61 2.32 2,400 5,563 No Work Proposed 0 61 2.32 2,400 5563 NO SENSOR PROPOSED 0 - - - - -$

1286 West Freehold Library2X2 recessed troffer with (3) F17 T8 Lamps & (1) 3-Light Electronic ballast

22 50 1.10 2,400 2,640 No Work Proposed 0 50 1.10 2,400 2640 NO SENSOR PROPOSED 0 - - - - -$

1287 West Freehold Library Recessed Can Can w/ (2) 57w CF PL 3 114 0.34 2,400 821 No Work Proposed 0 114 0.34 2,400 821 NO SENSOR PROPOSED 0 - - - - -$

1288 West Freehold Work Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 No Work Proposed 0 89 0.18 2,400 427 NO SENSOR PROPOSED 0 - - - - -$

1289 West Freehold Library Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - -$

1290 West Freehold Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1291 West Freehold Computer Lab 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

34 61 2.07 1,500 3,111 No Work Proposed 0 61 2.07 1,500 3111 NO SENSOR PROPOSED 0 - - - - -$

1292 West Freehold Art Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 No Work Proposed 0 89 1.07 1,500 1602 NO SENSOR PROPOSED 0 - - - - -$

1293 West Freehold Kiln Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 No Work Proposed 0 61 0.12 1,500 183 NO SENSOR PROPOSED 0 - - - - -$

1294 West Freehold Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1295 West Freehold Vice Principal2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 1,560 417

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 224 224 35.71$

1296 West Freehold MDF Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

1297 West FreeholdComputer Training

Room4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast20 61 1.22 1,500 1,830 No Work Proposed 0 61 1.22 975 1190

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 641 641 101.97$

1298 West Freehold Electrical Closet Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1299 West Freehold Guidence Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 1,560 417

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 224 224 35.71$

1300 West Freehold Testing2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 1,500 401 No Work Proposed 0 89 0.27 975 260

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 140 140 22.32$

1301 West Freehold CST2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 1,560 417

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 224 224 35.71$

37 of 45

Page 233: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1302 West Freehold Girls2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 1,560 285

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9'

High-(1) PP-20 per sensor

1 - - 154 154 24.47$

1303 West Freehold Boys2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 1,560 285

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9'

High-(1) PP-20 per sensor

1 - - 154 154 24.47$

1304 West Freehold Instrumental Music2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 No Work Proposed 0 89 0.53 975 521

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 280 280 44.63$

1305 West Freehold Instrumental Music Recessed Can Can w/ (2) 13w CF PL 12 26 0.31 1,500 468 No Work Proposed 0 26 0.31 1,500 468 NO SENSOR PROPOSED 0 - - - - -$

1306 West Freehold Choral Music2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

14 89 1.25 1,500 1,869 No Work Proposed 0 89 1.25 975 1215

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 654 654 104.14$

1307 West Freehold Stage Alvoce2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 2,400 214 No Work Proposed 0 89 0.09 2,400 214 NO SENSOR PROPOSED 0 - - - - -$

1308 West Freehold Stage 4' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

10 110 1.10 2,400 2,640 No Work Proposed 0 110 1.10 2,400 2640 NO SENSOR PROPOSED 0 - - - - -$

1309 West Freehold Stage Alvoce2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 2,400 641 NO SENSOR PROPOSED 0 - - - - -$

1310 West Freehold Gym High Bay Fixture with (8) 42w Triple Tube PL Fluorescent Lamps

30 336 10.08 2,400 24,192 No Work Proposed 0 336 10.08 2,400 24192 NO SENSOR PROPOSED 0 - - - - -$

1311 West Freehold Gym 250w Quartz 10 250 2.50 2,400 6,000 No Work Proposed 0 250 2.50 2,400 6000 NO SENSOR PROPOSED 0 - - - - -$

1312 West Freehold PE Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 No Work Proposed 0 89 0.18 2,400 427 NO SENSOR PROPOSED 0 - - - - -$

1313 West Freehold Closet2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1314 West Freehold Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

1315 West Freehold Gym Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1316 West Freehold Cafeteria 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

44 61 2.68 3,640 9,770 No Work Proposed 0 61 2.68 3,640 9770 NO SENSOR PROPOSED 0 - - - - -$

1317 West Freehold Cafeteria 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

44 89 3.92 3,640 14,254 No Work Proposed 0 89 3.92 3,640 14254 NO SENSOR PROPOSED 0 - - - - -$

1318 West Freehold Cafeteria2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 3,640 666 No Work Proposed 0 61 0.18 3,640 666 NO SENSOR PROPOSED 0 - - - - -$

1319 West Freehold Kitchen2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

19 61 1.16 2,400 2,782 No Work Proposed 0 61 1.16 2,400 2782 NO SENSOR PROPOSED 0 - - - - -$

1320 West Freehold Kitchen2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - -$

1321 West Freehold PTO Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

1322 West Freehold Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

1323 West Freehold Locker Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

1324 West Freehold Janitor Closet2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1325 West Freehold Janitor Closet2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

1326 West Freehold Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 500 61 No Work Proposed 0 61 0.12 500 61 NO SENSOR PROPOSED 0 - - - - -$

1327 West Freehold Boys2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 1,560 285

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9'

High-(1) PP-20 per sensor

1 - - 154 154 24.47$

1328 West Freehold Girls2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 1,560 285

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9'

High-(1) PP-20 per sensor

1 - - 154 154 24.47$

1329 West Freehold Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - -$

1330 West Freehold Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

1331 West Freehold Men's Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1332 West Freehold Women's Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 1,560 95Wall Switch Dual Technology

Occupancy Sensor1 - - 51 51 8.16$

38 of 45

Page 234: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1333 West Freehold Custodial Closet2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - -$

1334 West Freehold Faculty Work Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 No Work Proposed 0 89 0.80 1,560 1250

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 673 673 107.12$

1335 West Freehold Copy Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 No Work Proposed 0 89 0.80 1,560 1250 Wall Switch Occupancy Sensor 1 - - 673 673 107.12$

1336 West Freehold Receiving Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 2,400 1,709 No Work Proposed 0 89 0.71 2,400 1709 NO SENSOR PROPOSED 0 - - - - -$

1337 West Freehold Boiler Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

6 61 0.37 1,000 366 No Work Proposed 0 61 0.37 1,000 366 NO SENSOR PROPOSED 0 - - - - -$

1338 West Freehold Electrical Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 1,000 183 No Work Proposed 0 61 0.18 1,000 183 NO SENSOR PROPOSED 0 - - - - -$

1339 West Freehold Assistant Principal2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 No Work Proposed 0 89 0.27 2,400 641 NO SENSOR PROPOSED 0 - - - - -$

1340 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1341 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1342 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1343 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1344 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1345 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1346 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1347 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1348 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1349 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1350 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1351 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1352 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1353 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1354 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1355 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1356 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1357 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1358 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1359 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1360 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1361 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1362 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1363 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1364 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1365 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1366 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1367 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1368 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1369 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1370 West Freehold Class 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - -$

1371 West Freehold Class 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 No Work Proposed 0 61 0.61 1,500 915 NO SENSOR PROPOSED 0 - - - - -$

1372 West Freehold Women's Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1373 West Freehold Men's Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - -$

1374 West Freehold Girls2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 1,560 190

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9'

High-(1) PP-20 per sensor

1 - - 102 102 16.31$

1375 West Freehold Janitor Closet Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - -$

39 of 45

Page 235: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1376 West Freehold Boys2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - -$

1377 West Freehold Mechanical Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

1378 West Freehold Electrical Room Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - -$

1379 West Freehold IDF Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

2 61 0.12 1,500 183 No Work Proposed 0 61 0.12 1,500 183 NO SENSOR PROPOSED 0 - - - - -$

1380 West Freehold Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 500 122 No Work Proposed 0 61 0.24 500 122 NO SENSOR PROPOSED 0 - - - - -$

1381 West Freehold Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

15 89 1.34 1,500 2,003 No Work Proposed 0 89 1.34 975 1302

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

2 - - 701 701 111.58$

1382 West Freehold SGI2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,500 534 No Work Proposed 0 89 0.36 1,500 534 NO SENSOR PROPOSED 0 - - - - -$

1383 West Freehold Courtyard 1Wal Pack Fixture with (1) 150w Metal

Halide Lamp and (1) Magnetic HID Ballast1 195 0.20 3,640 710 No Work Proposed 0 195 0.20 3,640 710 NO SENSOR PROPOSED 0 - - - - -$

1384 West Freehold Courtyard by 256Wal Pack Fixture with (1) 150w Metal

Halide Lamp and (1) Magnetic HID Ballast3 195 0.59 3,640 2,129 No Work Proposed 0 195 0.59 3,640 2129 NO SENSOR PROPOSED 0 - - - - -$

1385 West Freehold Courtyard by 332Wal Pack Fixture with (1) 150w Metal

Halide Lamp and (1) Magnetic HID Ballast4 195 0.78 3,640 2,839 No Work Proposed 0 195 0.78 3,640 2839 NO SENSOR PROPOSED 0 - - - - -$

1386 West Freehold OutsideWall Pack Fixture with (2) 26w Compact

Fluorescent Lamps and (1) Magnetic Ballast

9 52 0.47 3,640 1,704 No Work Proposed 0 52 0.47 3,640 1704 NO SENSOR PROPOSED 0 - - - - -$

1387 West Freehold OutsideWal Pack Fixture with (1) 150w Metal

Halide Lamp and (1) Magnetic HID Ballast79 195 15.41 3,640 56,074 No Work Proposed 0 195 15.41 3,640 56074 NO SENSOR PROPOSED 0 - - - - -$

1388 West Freehold OutsideParking Lot Fixture Mounted on a Pole w/ (1) 400w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast20 445 8.90 3,640 32,396 No Work Proposed 0 445 8.90 3,640 32396 NO SENSOR PROPOSED 0 - - - - -$

30 - - 10,714.41 10,714.41 $1,705.73

1389C.R.

ApplegateCorridor 10-18

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 61 0.55 3,640 1,998 No Work Proposed 0 61 0.55 3,640 1998 NO SENSOR PROPOSED 0 - - - - -$

1390C.R.

ApplegateCorridor 10-18

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 3,640 400 No Work Proposed 0 110 0.11 3,640 400 NO SENSOR PROPOSED 0 - - - - -$

1391 C.R. Applegate

Corridor 10-18 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1392C.R.

ApplegateCorridor 29

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 No Work Proposed 0 61 0.24 3,640 888 NO SENSOR PROPOSED 0 - - - - -$

1393 C.R. Applegate

Corridor 29 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

1394C.R.

ApplegateCorridor 31

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 3,640 1,201 No Work Proposed 0 110 0.33 3,640 1201 NO SENSOR PROPOSED 0 - - - - -$

1395 C.R. Applegate

Corridor 31 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 No Work Proposed 0 2 0.01 8,760 53 NO SENSOR PROPOSED 0 - - - - -$

1396C.R.

ApplegateCorridor 36-39

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

1397 C.R. Applegate

Corridor 36-39 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 No Work Proposed 0 2 0.00 8,760 18 NO SENSOR PROPOSED 0 - - - - -$

1398C.R.

ApplegateCorridor 40

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 No Work Proposed 0 61 0.43 3,640 1554 NO SENSOR PROPOSED 0 - - - - -$

1399C.R.

ApplegateCorridor 40

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 3,640 400 No Work Proposed 0 110 0.11 3,640 400 NO SENSOR PROPOSED 0 - - - - -$

1400 C.R. Applegate

Corridor 40 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1401C.R.

ApplegateCorridor 44-50

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 61 0.98 3,640 3,553 No Work Proposed 0 61 0.98 3,640 3553 NO SENSOR PROPOSED 0 - - - - -$

1402 C.R. Applegate

Corridor 44-50 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1403C.R.

ApplegateCorridor 59

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 61 0.98 3,640 3,553 No Work Proposed 0 61 0.98 3,640 3553 NO SENSOR PROPOSED 0 - - - - -$

1404 C.R. Applegate

Corridor 59 Exit Sign w/ 2w LED 4 2 0.01 8,760 70 No Work Proposed 0 2 0.01 8,760 70 NO SENSOR PROPOSED 0 - - - - -$

1405 C.R. Applegate

Corridor 59 Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8,760 35 NO SENSOR PROPOSED 0 0.08 666 - 666 109.58$

1406C.R.

ApplegateCorridor 102-112

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

13 61 0.79 3,640 2,887 No Work Proposed 0 61 0.79 3,640 2887 NO SENSOR PROPOSED 0 - - - - -$

1407 C.R. Applegate

Corridor 102-112 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1408C.R.

ApplegateMedic Center Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 No Work Proposed 0 89 0.36 2,400 854 NO SENSOR PROPOSED 0 - - - - -$

1409C.R.

ApplegateHub Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 No Work Proposed 0 89 0.36 2,400 854 NO SENSOR PROPOSED 0 - - - - -$

1410 C.R. Applegate

Library 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

54 61 3.29 2,400 7,906 No Work Proposed 0 61 3.29 2,400 7906 NO SENSOR PROPOSED 0 - - - - -$

1411C.R.

ApplegateLibrary

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

5 110 0.55 2,400 1,320 No Work Proposed 0 110 0.55 2,400 1320 NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at West Freehold:

40 of 45

Page 236: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1412 C.R. Applegate

Storage Room #1 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 500 183 No Work Proposed 0 61 0.37 500 183 NO SENSOR PROPOSED 0 - - - - -$

1413C.R.

ApplegateLobby

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 No Work Proposed 0 61 0.24 3,640 888 NO SENSOR PROPOSED 0 - - - - -$

1414 C.R. Applegate

Lobby Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - -$

1415C.R.

ApplegateLobby

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

8 220 1.76 3,640 6,406 No Work Proposed 0 220 1.76 3,640 6406 NO SENSOR PROPOSED 0 - - - - -$

1416 C.R. Applegate

Classroom 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - -$

1417 C.R. Applegate

Classroom 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - -$

1418 C.R. Applegate

Classroom 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - -$

1419 C.R. Applegate

Classroom 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - -$

1420 C.R. Applegate

Classroom 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - -$

1421 C.R. Applegate

Classroom 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - -$

1422 C.R. Applegate

Classroom 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - -$

1423 C.R. Applegate

Classroom 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - -$

1424C.R.

ApplegateGirls

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - -$

1425 C.R. Applegate

Girls 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 No Work Proposed 0 23 0.02 2,400 55 NO SENSOR PROPOSED 0 - - - - -$

1426 C.R. Applegate

Sprinkler Valve 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 No Work Proposed 0 61 0.12 1,000 122 NO SENSOR PROPOSED 0 - - - - -$

1427C.R.

ApplegateBoys

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - $0

1428 C.R. Applegate

Boys 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 No Work Proposed 0 23 0.02 2,400 55 NO SENSOR PROPOSED 0 - - - - $0

1429C.R.

ApplegateClassroom

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 975 1071

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 576 576 $95

1430C.R.

ApplegateClassroom

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

2 220 0.44 1,500 660 No Work Proposed 0 220 0.44 1,500 660 NO SENSOR PROPOSED 0 - - - - $0

1431 C.R. Applegate

Classroom 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1432C.R.

ApplegateKiln

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 No Work Proposed 0 89 0.53 1,500 801 NO SENSOR PROPOSED 0 - - - - $0

1433 C.R. Applegate

Art Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

22 61 1.34 1,500 2,013 No Work Proposed 0 61 1.34 1,500 2013 NO SENSOR PROPOSED 0 - - - - $0

1434C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 No Work Proposed 0 110 0.44 975 429

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 231 231 $38

1435 C.R. Applegate

Girls 4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 57 0.34 2,400 821 No Work Proposed 0 57 0.34 2,400 821 NO SENSOR PROPOSED 0 - - - - $0

1436 C.R. Applegate

Girls 23w Compact Fluorescent S/I 2 23 0.05 2,400 110 No Work Proposed 0 23 0.05 2,400 110 NO SENSOR PROPOSED 0 - - - - $0

1437C.R.

ApplegateLobby 22-29

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 No Work Proposed 0 61 0.24 3,640 888 NO SENSOR PROPOSED 0 - - - - $0

1438C.R.

ApplegateLobby 22-29

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

8 220 1.76 3,640 6,406 No Work Proposed 0 220 1.76 3,640 6406 NO SENSOR PROPOSED 0 - - - - $0

1439 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1440 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1441 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1442 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1443 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1444 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1445 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1446 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1447 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

12 61 0.73 1,500 1,098 No Work Proposed 0 61 0.73 1,500 1098 NO SENSOR PROPOSED 0 - - - - $0

1448C.R.

ApplegateClass

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 No Work Proposed 0 61 0.12 1,500 183 NO SENSOR PROPOSED 0 - - - - $0

1449 C.R. Applegate

Custodian Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - $0

1450 C.R. Applegate

Boys 4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 57 0.34 2,400 821 No Work Proposed 0 57 0.34 2,400 821 NO SENSOR PROPOSED 0 - - - - $0

1451 C.R. Applegate

Boys 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 No Work Proposed 0 23 0.02 2,400 55 NO SENSOR PROPOSED 0 - - - - $0

1452C.R.

ApplegateMain Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 No Work Proposed 0 89 0.80 2,400 1922 NO SENSOR PROPOSED 0 - - - - $0

41 of 45

Page 237: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1453C.R.

ApplegateCopy Room

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 No Work Proposed 0 110 0.22 2,400 528 NO SENSOR PROPOSED 0 - - - - $0

1454C.R.

ApplegatePrincipal

4X4 recessed troffer with (6) F32 T8 Lamps & (2) 3-Light Electronic ballasts

1 178 0.18 2,400 427 No Work Proposed 0 178 0.18 2,400 427 NO SENSOR PROPOSED 0 - - - - $0

1455 C.R. Applegate

Corridor 23w Compact Fluorescent S/I 2 23 0.05 3,640 167 No Work Proposed 0 23 0.05 3,640 167 NO SENSOR PROPOSED 0 - - - - $0

1456C.R.

ApplegateBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - $0

1457C.R.

ApplegateBathroom 60w. Incandescent S/I 1 60 0.06 2,400 144

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 2,400 31 NO SENSOR PROPOSED 0 0.05 113 - 113 $19

1458C.R.

ApplegateNurse's Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 No Work Proposed 0 89 0.53 2,400 1282 NO SENSOR PROPOSED 0 - - - - $0

1459 C.R. Applegate

Corridor 23w Compact Fluorescent S/I 2 23 0.05 3,640 167 No Work Proposed 0 23 0.05 3,640 167 NO SENSOR PROPOSED 0 - - - - $0

1460C.R.

ApplegateBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - $0

1461C.R.

ApplegateBathroom 60w. Incandescent S/I 1 60 0.06 2,400 144

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 2,400 31 NO SENSOR PROPOSED 0 0.05 113 - 113 $19

1462C.R.

ApplegateGuidence Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 No Work Proposed 0 89 0.18 2,400 427 NO SENSOR PROPOSED 0 - - - - $0

1463C.R.

ApplegateFaculty room

4X4 recessed troffer with (6) F32 T8 Lamps & (2) 3-Light Electronic ballasts

4 178 0.71 2,400 1,709 No Work Proposed 0 178 0.71 1,560 1111

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 598 598 $98

1464C.R.

ApplegateKitchen

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 No Work Proposed 0 89 0.53 1,560 833 Wall Switch Occupancy Sensor 1 - - 449 449 $74

1465C.R.

ApplegateMen's Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - $0

1466C.R.

ApplegateMen's Room

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 No Work Proposed 0 34 0.03 2,400 82 NO SENSOR PROPOSED 0 - - - - $0

1467C.R.

ApplegateBoys

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 No Work Proposed 0 61 0.18 2,400 439 NO SENSOR PROPOSED 0 - - - - $0

1468 C.R. Applegate

Boys 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 No Work Proposed 0 23 0.02 2,400 55 NO SENSOR PROPOSED 0 - - - - $0

1469C.R.

ApplegateWomen's Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - $0

1470 C.R. Applegate

Women's Room 4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - $0

1471 C.R. Applegate

Women's Room 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 No Work Proposed 0 23 0.02 2,400 55 NO SENSOR PROPOSED 0 - - - - $0

1472 C.R. Applegate

Custodian 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - $0

1473C.R.

ApplegateGirls

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - $0

1474 C.R. Applegate

Girls 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 No Work Proposed 0 23 0.02 2,400 55 NO SENSOR PROPOSED 0 - - - - $0

1475 C.R. Applegate

Custodians Office 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - $0

1476 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1477C.R.

ApplegateClass

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 1,500 165 No Work Proposed 0 110 0.11 1,500 165 NO SENSOR PROPOSED 0 - - - - $0

1478C.R.

ApplegateBathroom

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1479 C.R. Applegate

Bathroom 150w Incandescent S/I 1 150 0.15 2,400 360 Re-lamp with 40w Compact Fluorescent 1 40 0.04 2,400 96 NO SENSOR PROPOSED 0 0.11 264 - 264 $43

1480 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1481C.R.

ApplegateClass

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 1,500 165 No Work Proposed 0 110 0.11 1,500 165 NO SENSOR PROPOSED 0 - - - - $0

1482C.R.

ApplegateBathroom 60w. Incandescent S/I 1 60 0.06 2,400 144

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 2,400 31 NO SENSOR PROPOSED 0 0.05 113 - 113 $19

1483C.R.

ApplegateClass

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 No Work Proposed 0 61 0.06 1,500 92 NO SENSOR PROPOSED 0 - - - - $0

1484 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1485C.R.

ApplegateClass

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 1,500 165 No Work Proposed 0 110 0.11 1,500 165 NO SENSOR PROPOSED 0 - - - - $0

1486C.R.

ApplegateBathroom

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1487 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1488 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1489 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

26 61 1.59 1,500 2,379 No Work Proposed 0 61 1.59 1,500 2379 NO SENSOR PROPOSED 0 - - - - $0

42 of 45

Page 238: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1490C.R.

ApplegateStorage

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 500 45 No Work Proposed 0 89 0.09 500 45 NO SENSOR PROPOSED 0 - - - - $0

1491C.R.

ApplegateRestroom 100w Incandescent S/I 1 100 0.10 2,400 240

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

1 23 0.02 2,400 55 NO SENSOR PROPOSED 0 0.08 185 - 185 $30

1492C.R.

ApplegateCoat Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 No Work Proposed 0 61 0.06 1,500 92 NO SENSOR PROPOSED 0 - - - - $0

1493 C.R. Applegate

Bathroom 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 No Work Proposed 0 23 0.02 2,400 55 NO SENSOR PROPOSED 0 - - - - $0

1494 C.R. Applegate

Storage 23w Compact Fluorescent S/I 1 23 0.02 500 12 No Work Proposed 0 23 0.02 500 12 NO SENSOR PROPOSED 0 - - - - $0

1495 C.R. Applegate

Class 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 No Work Proposed 0 61 1.10 1,500 1647 NO SENSOR PROPOSED 0 - - - - $0

1496 C.R. Applegate

Custodian Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

8 61 0.49 500 244 No Work Proposed 0 61 0.49 500 244 NO SENSOR PROPOSED 0 - - - - $0

1497C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 No Work Proposed 0 110 0.44 1,500 660 NO SENSOR PROPOSED 0 - - - - $0

1498C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 No Work Proposed 0 110 0.44 975 429 Wall Switch Occupancy Sensor 1 - - 231 231 $38

1499C.R.

ApplegateStorage 100w Incandescent S/I 1 100 0.10 500 50

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

1 23 0.02 500 12 NO SENSOR PROPOSED 0 0.08 39 - 39 $6

1500 C.R. Applegate

Electrical Equipment 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,000 244 No Work Proposed 0 61 0.24 1,000 244 NO SENSOR PROPOSED 0 - - - - $0

1501 C.R. Applegate

Storage 100w Incandescent S/I 3 100 0.30 500 150 New 4' Wrap Fixture, (2) F32 Lamps, NP Ballast, Miro4 Reflector.

2 55 0.11 500 55 NO SENSOR PROPOSED 0 0.19 95 - 95 $16

1502C.R.

ApplegateStage

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

33 110 3.63 2,400 8,712 No Work Proposed 0 110 3.63 2,400 8712 NO SENSOR PROPOSED 0 - - - - $0

1503C.R.

ApplegateStage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - $0

1504 C.R. Applegate

Stage Exit Sign w/ 2w LED 2 2 0.00 8,760 35 No Work Proposed 0 2 0.00 8,760 35 NO SENSOR PROPOSED 0 - - - - $0

1505 C.R. Applegate

Gym Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 500 92 No Work Proposed 0 61 0.18 500 92 NO SENSOR PROPOSED 0 - - - - $0

1506C.R.

ApplegateGirls Locker

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1507 C.R. Applegate

Girls Locker 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - $0

1508C.R.

ApplegateGym

High Bay Fixture with (1) 400w Metal Halide Lamp and (1) Magnetic HID Ballast

12 445 5.34 2,400 12,816

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

12 234 2.81 2,400 6739 NO SENSOR PROPOSED 0 2.53 6,077 - 6,077 $1,000

1509C.R.

ApplegateClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 No Work Proposed 0 89 0.53 975 521

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 280 280 $46

1510C.R.

ApplegateVice Principal

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 No Work Proposed 0 89 0.53 1,560 833

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 449 449 $74

1511C.R.

ApplegateGym Entrances

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - $0

1512 C.R. Applegate

Gym Office 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - $0

1513 C.R. Applegate

Gym Office 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 No Work Proposed 0 23 0.02 2,400 55 NO SENSOR PROPOSED 0 - - - - $0

1514C.R.

ApplegateGym Office

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1515C.R.

ApplegateBoys Gym Storage

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 500 55 No Work Proposed 0 110 0.11 500 55 NO SENSOR PROPOSED 0 - - - - $0

1516 C.R. Applegate

Mechanical Mezzanine 23w Compact Fluorescent S/I 10 23 0.23 1,000 230 No Work Proposed 0 23 0.23 1,000 230 NO SENSOR PROPOSED 0 - - - - $0

1517 C.R. Applegate

Electrical Room 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - $0

1518C.R.

ApplegateClass SGI

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

6 110 0.66 1,500 990 No Work Proposed 0 110 0.66 975 644

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 347 347 $57

1519C.R.

ApplegateSGI

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

6 110 0.66 1,500 990 No Work Proposed 0 110 0.66 975 644

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 347 347 $57

1520C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 975 1287

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 693 693 $114

1521 C.R. Applegate

Sprinkler Valve Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 1,000 183 No Work Proposed 0 61 0.18 1,000 183 NO SENSOR PROPOSED 0 - - - - $0

1522C.R.

ApplegateBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 1,560 95 Wall Switch Occupancy Sensor 1 - - 51 51 $8

43 of 45

Page 239: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1523C.R.

ApplegateInstrumental Music

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 1,500 1,155 No Work Proposed 0 110 0.77 975 751

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 404 404 $67

1524C.R.

ApplegateInstrumental Music

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 No Work Proposed 0 61 0.06 1,500 92 NO SENSOR PROPOSED 0 - - - - $0

1525C.R.

ApplegateVocal Music

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

11 110 1.21 1,500 1,815 No Work Proposed 0 110 1.21 975 1180

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 635 635 $105

1526C.R.

ApplegateVocal Music

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 No Work Proposed 0 61 0.06 1,500 92 NO SENSOR PROPOSED 0 - - - - $0

1527C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 975 1287

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 693 693 $114

1528C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 975 1287

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 693 693 $114

1529C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 No Work Proposed 0 110 1.32 975 1287

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height)

360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High

1 - - 693 693 $114

1530C.R.

ApplegateGirls

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - $0

1531C.R.

ApplegateGirls

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1532 C.R. Applegate

Custodian Storage 4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - $0

1533C.R.

ApplegateBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 No Work Proposed 0 61 0.12 2,400 293 NO SENSOR PROPOSED 0 - - - - $0

1534C.R.

ApplegateBoys

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1535 C.R. Applegate

Classroom 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - $0

1536 C.R. Applegate

Classroom 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - $0

1537C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - $0

1538C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1539 C.R. Applegate

Classroom 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - $0

1540 C.R. Applegate

Classroom 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - $0

1541C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - $0

1542C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1543 C.R. Applegate

Classroom 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - $0

1544 C.R. Applegate

Classroom 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - $0

1545C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - $0

1546C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1547 C.R. Applegate

Classroom 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - $0

1548 C.R. Applegate

Classroom 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - $0

1549C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - $0

1550C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1551 C.R. Applegate

Cafeteria Recessed Can Can w/ (2) 57w CF PL 12 114 1.37 3,640 4,980 No Work Proposed 0 114 1.37 3,640 4980 NO SENSOR PROPOSED 0 - - - - $0

1552C.R.

ApplegateCloset

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - $0

1553C.R.

ApplegateKitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 No Work Proposed 0 61 0.24 2,400 586 NO SENSOR PROPOSED 0 - - - - $0

1554C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - $0

1555 C.R. Applegate

MPR Recessed Can Can w/ (2) 57w CF PL 13 114 1.48 2,400 3,557 No Work Proposed 0 114 1.48 2,400 3557 NO SENSOR PROPOSED 0 - - - - $0

1556 C.R. Applegate

Storage Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - $0

44 of 45

Page 240: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Sensor DescriptionSensor Qtys

Total kW

Saved

kWh Saved Lighting Only

kWh Saved Sensors Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 1

1557C.R.

ApplegateBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1558 C.R. Applegate

Custodian Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 1,000 61 No Work Proposed 0 61 0.06 1,000 61 NO SENSOR PROPOSED 0 - - - - $0

1559C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1560 C.R. Applegate

Classroom 4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 No Work Proposed 0 89 0.89 1,500 1335 NO SENSOR PROPOSED 0 - - - - $0

1561 C.R. Applegate

Classroom 4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 No Work Proposed 0 61 0.85 1,500 1281 NO SENSOR PROPOSED 0 - - - - $0

1562C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 No Work Proposed 0 61 0.06 500 31 NO SENSOR PROPOSED 0 - - - - $0

1563C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 No Work Proposed 0 61 0.06 2,400 146 NO SENSOR PROPOSED 0 - - - - $0

1564 C.R. Applegate

Sprinkler Valve Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 1,000 183 No Work Proposed 0 61 0.18 1,000 183 NO SENSOR PROPOSED 0 - - - - $0

1565C.R.

ApplegateOutside 100w Incandescent S/I 8 100 0.80 3,640 2,912

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

8 23 0.18 3,640 670 NO SENSOR PROPOSED 0 0.62 2,242 - 2,242 $369

1566C.R.

ApplegateOutside

Wall Pack Fixture with (1) 175w Mercury Vapor Lamp and (1) Magnetic HID Ballast

38 205 7.79 3,640 28,356Remove and Replace Existing Fixture With a New Outdoor Flood Fixture Containing a 150w Pulse

Metal Halide Lamp38 85 3.23 3,640 11757 NO SENSOR PROPOSED 0 4.56 16,598 - 16,598 $2,732

1567C.R.

ApplegateOutside

Wall Pack Fixture with (1) 100w Metal Halide Lamp and (1) Magnetic HID Ballast

22 120 2.64 3,640 9,610 No Work Proposed 0 120 2.64 3,640 9610 NO SENSOR PROPOSED 0 - - - - $0

1568C.R.

ApplegateOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 400w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast4 445 1.78 3,640 6,479 No Work Proposed 0 445 1.78 3,640 6479 NO SENSOR PROPOSED 0 - - - - $0

1569C.R.

ApplegateOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 250w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast2 286 0.57 3,640 2,082 No Work Proposed 0 286 0.57 3,640 2082 NO SENSOR PROPOSED 0 - - - - $0

16 8.38 26504 7370 33874 $5,576

Overall Totals: 11,127 962.32 2,179,177 877 896.09 1,942,007 184 66.23 156,948 80,222 237,170 $38,941

Totals for Lighting System Upgrades at C.R. Applegate:

45 of 45

Page 241: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 242: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

APPENDIX E

LIGHTING SPREADSHEET - OPTION 2

Page 243: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 244: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

1 D.D. Eisenhower

Lobby Recessed Can Can w/ (2) 13w CF PL 3 26 0.08 3,640 284 46$ No Work Proposed 0 26 0.08 3640 284 46$ NO SENSOR PROPOSED 0 - - - - -$

2D.D.

EisenhowerLobby

4X4 recessed troffer with (6) F32 T8 Lamps & (2) 3-Light Electronic ballasts

8 178 1.42 3,640 5,183 843$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 63 1.01 3640 3669 597$ NO SENSOR PROPOSED 0 0.42 1,514 - 1,514 246.22$

3D.D.

EisenhowerCorridor 1

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

9 110 0.99 3,640 3,604 586$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 84 0.76 3640 2752 447$ NO SENSOR PROPOSED 0 0.23 852 - 852 138.50$

4 D.D. Eisenhower

Corridor 1 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

5D.D.

EisenhowerCorridor 2

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 3,640 2,803 456$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 84 0.59 3640 2140 348$ NO SENSOR PROPOSED 0 0.18 662 - 662 -$

6 D.D. Eisenhower

Corridor 2 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

7D.D.

EisenhowerCorridor 3

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

16 110 1.76 3,640 6,406 1,042$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 84 1.34 3640 4892 795$ NO SENSOR PROPOSED 0 0.42 1,514 - 1,514 246.22$

8 D.D. Eisenhower

Corridor 3 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

9D.D.

EisenhowerCorridor 4

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

6 110 0.66 3,640 2,402 391$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 84 0.50 3640 1835 298$ NO SENSOR PROPOSED 0 0.16 568 - 568 92.33$

10D.D.

EisenhowerCorridor 4

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 144$ No Work Proposed 0 61 0.24 3640 888 144$ NO SENSOR PROPOSED 0 - - - - -$

11 D.D. Eisenhower

Corridor 4 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

12D.D.

EisenhowerCorridor 5

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

13 110 1.43 3,640 5,205 846$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

13 84 1.09 3640 3975 646$ NO SENSOR PROPOSED 0 0.34 1,230 - 1,230 200.05$

13 D.D. Eisenhower

Corridor 5 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

14D.D.

EisenhowerCorridor 6

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

11 110 1.21 3,640 4,404 716$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 84 0.92 3640 3363 547$ NO SENSOR PROPOSED 0 0.29 1,041 - 1,041 169.27$

15 D.D. Eisenhower

Corridor 6 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

16D.D.

EisenhowerCorridor 7

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

9 110 0.99 3,640 3,604 586$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 84 0.76 3640 2752 447$ NO SENSOR PROPOSED 0 0.23 852 - 852 138.50$

17 D.D. Eisenhower

Corridor 7 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

18D.D.

EisenhowerCorridor 8

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

24 110 2.64 3,640 9,610 1,563$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

24 84 2.02 3640 7338 1,193$ NO SENSOR PROPOSED 0 0.62 2,271 - 2,271 369.32$

19 D.D. Eisenhower

Corridor 8 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

20D.D.

EisenhowerCorridor 9

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

13 110 1.43 3,640 5,205 846$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

13 84 1.09 3640 3975 646$ NO SENSOR PROPOSED 0 0.34 1,230 - 1,230 200.05$

21 D.D. Eisenhower

Corridor 9 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

22D.D.

EisenhowerCorridor 10

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

10 110 1.10 3,640 4,004 651$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 84 0.84 3640 3058 497$ NO SENSOR PROPOSED 0 0.26 946 - 946 153.88$

23 D.D. Eisenhower

Corridor 10 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

24D.D.

EisenhowerCorridor 11

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

16 110 1.76 3,640 6,406 1,042$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 84 1.34 3640 4892 795$ NO SENSOR PROPOSED 0 0.42 1,514 - 1,514 246.22$

25 D.D. Eisenhower

Corridor 11 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

26D.D.

EisenhowerCorridor 12

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

13 110 1.43 3,640 5,205 846$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

13 84 1.09 3640 3975 646$ NO SENSOR PROPOSED 0 0.34 1,230 - 1,230 200.05$

27 D.D. Eisenhower

Corridor 12 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

28D.D.

EisenhowerCorridor 13

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

20 110 2.20 3,640 8,008 1,302$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 84 1.68 3640 6115 994$ NO SENSOR PROPOSED 0 0.52 1,893 - 1,893 307.77$

29 D.D. Eisenhower

Corridor 13 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

30D.D.

EisenhowerCorridor 14

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

11 110 1.21 3,640 4,404 716$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 84 0.92 3640 3363 547$ NO SENSOR PROPOSED 0 0.29 1,041 - 1,041 169.27$

31 D.D. Eisenhower

Corridor 14 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

32D.D.

EisenhowerCorridor 15

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

10 110 1.10 3,640 4,004 651$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 84 0.84 3640 3058 497$ NO SENSOR PROPOSED 0 0.26 946 - 946 153.88$

33 D.D. Eisenhower

Corridor 15 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

34D.D.

EisenhowerLibrary

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

50 220 11.00 2,400 26,400 4,293$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

100 84 8.40 2400 20160 3,278$ NO SENSOR PROPOSED 0 2.60 6,240 - 6,240 1,014.62$

35 D.D. Eisenhower

Library Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1 of 52

Page 245: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

36D.D.

EisenhowerLibrary

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

16 110 1.76 2,400 4,224 687$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 84 1.34 2400 3226 524$ NO SENSOR PROPOSED 0 0.42 998 - 998 162.34$

37 D.D. Eisenhower

Library 150w Incandescent S/I 8 150 1.20 2,400 2,880 468$ Re-lamp with 40w Compact Fluorescent 8 40 0.32 2400 768 125$ NO SENSOR PROPOSED 0 0.88 2,112 - 2,112 343.41$

38D.D.

EisenhowerLibrary

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 2,400 264 43$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 2400 202 33$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.15$

39D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

40D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

41D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

42D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

43D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

44D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

45D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

40 61 2.44 1,500 3,660 595$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

40 44 1.76 1500 2640 429$ NO SENSOR PROPOSED 0 0.68 1,020 - 1,020 165.85$

46D.D.

EisenhowerBoys

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

10 31 0.31 2,400 744 121$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 25 0.25 2400 600 98$ NO SENSOR PROPOSED 0 0.06 144 - 144 23.41$

47D.D.

EisenhowerCustodian

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

10 31 0.31 1,000 310 50$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 25 0.25 1000 250 41$ NO SENSOR PROPOSED 0 0.06 60 - 60 9.76$

48D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 417$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

28 44 1.23 1500 1848 300$ NO SENSOR PROPOSED 0 0.48 714 - 714 116.10$

49D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 417$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

28 44 1.23 1500 1848 300$ NO SENSOR PROPOSED 0 0.48 714 - 714 116.10$

50D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 417$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

28 44 1.23 1500 1848 300$ NO SENSOR PROPOSED 0 0.48 714 - 714 116.10$

51D.D.

EisenhowerHUB Room

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.27$

52D.D.

EisenhowerBook Storage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 500 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 500 88 14$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.53$

53D.D.

EisenhowerElectrical Room

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

14 31 0.43 1,000 434 71$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 25 0.35 1000 350 57$ NO SENSOR PROPOSED 0 0.08 84 - 84 13.66$

54D.D.

EisenhowerDisplay Case

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 36$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 3640 160 26$ NO SENSOR PROPOSED 0 0.02 62 - 62 10.06$

55 D.D. Eisenhower

Corridor To Gym Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 3,640 379 62$ No Work Proposed 0 26 0.10 3640 379 62$ NO SENSOR PROPOSED 0 - - - - -$

56D.D.

EisenhowerGirls Locker

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

16 31 0.50 2,400 1,190 194$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 25 0.40 2400 960 156$ NO SENSOR PROPOSED 0 0.10 230 - 230 37.46$

57D.D.

EisenhowerCoach

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 1,500 165 27$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 1500 126 20$ NO SENSOR PROPOSED 0 0.03 39 - 39 6.34$

58D.D.

EisenhowerBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

59D.D.

EisenhowerShowers 75w. Incandescent S/I 6 75 0.45 1,500 675 110$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

6 13 0.08 1500 117 19$ NO SENSOR PROPOSED 0 0.37 558 - 558 90.73$

60D.D.

EisenhowerToilets

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.27$

61D.D.

EisenhowerPhys Ed Storage

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

2 61 0.12 500 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.76$

62D.D.

EisenhowerGym

High Bay Fixture with (1) 400w Metal Halide Lamp and (1) Magnetic HID Ballast

18 445 8.01 2,400 19,224 3,126$

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

18 234 4.21 2400 10109 1,644$ NO SENSOR PROPOSED 0 3.80 9,115 - 9,115 1,482.13$

63 D.D. Eisenhower

Corridor To Gym Recessed Can Can w/ (2) 13w CF PL 3 26 0.08 3,640 284 46$ No Work Proposed 0 26 0.08 3640 284 46$ NO SENSOR PROPOSED 0 - - - - -$

64D.D.

EisenhowerBoys Locker Room

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

15 31 0.47 2,400 1,116 181$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

15 25 0.38 2400 900 146$ NO SENSOR PROPOSED 0 0.09 216 - 216 35.12$

2 of 52

Page 246: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

65D.D.

EisenhowerCoach

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 1,500 165 27$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 1500 126 20$ NO SENSOR PROPOSED 0 0.03 39 - 39 6.34$

66D.D.

EisenhowerBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

67D.D.

EisenhowerToilets

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.27$

68D.D.

EisenhowerShowers 75w. Incandescent S/I 5 75 0.38 1,500 563 91$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

5 13 0.07 1500 98 16$ NO SENSOR PROPOSED 0 0.31 465 - 465 75.61$

69D.D.

EisenhowerMechanical Room

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

3 61 0.18 1,000 183 30$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 1000 132 21$ NO SENSOR PROPOSED 0 0.05 51 - 51 8.29$

70D.D.

EisenhowerStudent Store

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1560 137 22$ Wall Switch Occupancy Sensor 1 0.03 82 74 156 25.29$

71D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 130$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 975 369 60$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 234 198 432 70.32$

72D.D.

EisenhowerGirls Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 2,400 1,171 190$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 44 0.35 2400 845 137$ NO SENSOR PROPOSED 0 0.14 326 - 326 53.07$

73D.D.

EisenhowerCustodian

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

4 61 0.24 1,000 244 40$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1000 176 29$ NO SENSOR PROPOSED 0 0.07 68 - 68 11.06$

74D.D.

EisenhowerMusic Room

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

12 61 0.73 1,500 1,098 179$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 975 515 84$ Wall Switch Dual Technology

Occupancy Sensor1 0.20 306 277 583 94.83$

75D.D.

EisenhowerStorage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 500 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 500 88 14$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.53$

76D.D.

EisenhowerTeachers Lounge

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 2,400 1,709 278$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1560 786 128$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 499 423 923 150.01$

77D.D.

EisenhowerFaculty Bathroom

2' Vanity Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144 23$ Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.15$

78 D.D. Eisenhower

Faculty Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

79D.D.

EisenhowerFaculty Bathroom

2' Vanity Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144 23$ Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.15$

80 D.D. Eisenhower

Faculty Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

81D.D.

EisenhowerOffice Secretary

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 86$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 1560 262 43$ Wall Switch Occupancy Sensor 1 0.05 125 141 266 43.24$

82D.D.

EisenhowerVice Principal

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

2 220 0.44 2,400 1,056 172$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 1560 524 85$ Wall Switch Occupancy Sensor 1 0.10 250 282 532 86.48$

83 D.D. Eisenhower

Hallway Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 3,640 379 62$ No Work Proposed 0 26 0.10 3640 379 62$ NO SENSOR PROPOSED 0 - - - - -$

84D.D.

EisenhowerPrincipal

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 139$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 1560 393 64$ Wall Switch Dual Technology

Occupancy Sensor1 0.10 250 212 461 75.00$

85D.D.

EisenhowerMain Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 313$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 2400 1361 221$ NO SENSOR PROPOSED 0 0.23 562 - 562 91.32$

86D.D.

EisenhowerMain Office

2X2 recessed troffer with (4) F17 T8 Lamps & (1) 4-Light Electronic ballast

1 68 0.07 2,400 163 27$ No Work Proposed 0 68 0.07 2400 163 27$ NO SENSOR PROPOSED 0 - - - - -$

87D.D.

EisenhowerMain Office 60w. Incandescent S/I 7 60 0.42 2,400 1,008 164$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

7 13 0.09 2400 218 36$ NO SENSOR PROPOSED 0 0.33 790 - 790 128.39$

88D.D.

EisenhowerStorage

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 500 110 18$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 325 55 9$ Wall Switch Occupancy Sensor 1 0.05 26 29 55 9.01$

89D.D.

EisenhowerBathroom

2' Vanity Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144 23$ Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.15$

90 D.D. Eisenhower

Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

91D.D.

EisenhowerNurse's Office

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

10 110 1.10 2,400 2,640 429$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 84 0.84 2400 2016 328$ NO SENSOR PROPOSED 0 0.26 624 - 624 101.46$

92D.D.

EisenhowerBathroom

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

2 34 0.07 2,400 163 27$ No Work Proposed 0 34 0.07 2400 163 27$ NO SENSOR PROPOSED 0 - - - - -$

93D.D.

EisenhowerElectrical Room #2

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

1 61 0.06 1,000 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.76$

94D.D.

EisenhowerGuidence

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

6 61 0.37 2,400 878 143$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 2400 634 103$ NO SENSOR PROPOSED 0 0.10 245 - 245 39.80$

95D.D.

EisenhowerGuidence

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 2,400 586 95$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1560 275 45$ Wall Switch Occupancy Sensor 1 0.07 163 148 311 50.58$

3 of 52

Page 247: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

96D.D.

EisenhowerGuidence

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

8 61 0.49 2,400 1,171 190$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 44 0.35 1560 549 89$ Wall Switch Occupancy Sensor 1 0.14 326 296 622 101.15$

97D.D.

EisenhowerWork Room/Copy

Room4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast4 61 0.24 2,400 586 95$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 2400 422 69$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.54$

98D.D.

EisenhowerChild Study Team

Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 139$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 1560 393 64$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.10 250 212 461 75.00$

99D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 268$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 975 772 126$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.31 459 416 875 142.24$

100D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 174$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 975 491 80$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 312 265 577 93.76$

101D.D.

EisenhowerStage

4' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

29 110 3.19 2,400 7,656 1,245$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

29 84 2.44 2400 5846 951$ NO SENSOR PROPOSED 0 0.75 1,810 - 1,810 294.24$

102D.D.

EisenhowerStorage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 500 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 500 88 14$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.53$

103D.D.

EisenhowerStorage Room #4 100w Incandescent S/I 1 100 0.10 500 50 8$

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

1 23 0.02 500 12 2$ NO SENSOR PROPOSED 0 0.08 39 - 39 6.26$

104 D.D. Eisenhower

Storage Room #4 Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 114$ Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 0.08 666 - 666 108.25$

105D.D.

EisenhowerBoys

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.63$

106D.D.

EisenhowerBoys

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

8 31 0.25 2,400 595 97$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 25 0.20 2400 480 78$ NO SENSOR PROPOSED 0 0.05 115 - 115 18.73$

107D.D.

EisenhowerBoys

4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.27$

108D.D.

EisenhowerCustodian

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

2 61 0.12 1,000 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1000 88 14$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.53$

109D.D.

EisenhowerGirls

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

10 31 0.31 2,400 744 121$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 25 0.25 2400 600 98$ NO SENSOR PROPOSED 0 0.06 144 - 144 23.41$

110 D.D. Eisenhower

Gym Entrance SE corner

Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 2,400 250 41$ No Work Proposed 0 26 0.10 2400 250 41$ NO SENSOR PROPOSED 0 - - - - -$

111D.D.

EisenhowerHandicapped Classroom

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 130$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 975 369 60$ Wall Switch Occupancy Sensor 1 0.16 234 198 432 70.32$

112D.D.

EisenhowerWomen's Faculty

4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 57 0.23 2,400 547 89$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 25 0.10 2400 240 39$ NO SENSOR PROPOSED 0 0.13 307 - 307 49.95$

113D.D.

EisenhowerBathroom

4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.63$

114 D.D. Eisenhower

Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

115D.D.

EisenhowerElectrical Panel Room

4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 57 0.23 1,000 228 37$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 25 0.10 1000 100 16$ NO SENSOR PROPOSED 0 0.13 128 - 128 20.81$

116D.D.

EisenhowerMen's Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.63$

117D.D.

EisenhowerMusic Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

25 61 1.53 1,500 2,288 372$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

25 44 1.10 1500 1650 268$ NO SENSOR PROPOSED 0 0.43 638 - 638 103.66$

118D.D.

EisenhowerPractice Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 2,400 214 35$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 63 0.06 2400 151 25$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.15$

119D.D.

EisenhowerOffice

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 104$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 1560 295 48$ Wall Switch Occupancy Sensor 1 0.08 187 159 346 56.25$

120D.D.

EisenhowerInstrument Storage

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 500 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.76$

121D.D.

EisenhowerInstrument Storage

4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

1 57 0.06 500 29 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 25 0.03 500 13 2$ NO SENSOR PROPOSED 0 0.03 16 - 16 2.60$

122D.D.

EisenhowerShowcase

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.63$

123 D.D. Eisenhower

Gym Entrance Recessed Can Can w/ (2) 13w CF PL 3 26 0.08 2,400 187 30$ No Work Proposed 0 26 0.08 2400 187 30$ NO SENSOR PROPOSED 0 - - - - -$

124D.D.

EisenhowerElevator Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,000 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.76$

125D.D.

EisenhowerElevator

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

4 of 52

Page 248: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

126D.D.

EisenhowerWood Shop

4' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

46 110 5.06 1,500 7,590 1,234$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

46 84 3.86 1500 5796 942$ NO SENSOR PROPOSED 0 1.20 1,794 - 1,794 291.70$

127 D.D. Eisenhower

Stairs 42w. Compact Flourescent S/I 1 42 0.04 3,640 153 25$ No Work Proposed 0 42 0.04 3640 153 25$ NO SENSOR PROPOSED 0 - - - - -$

128 D.D. Eisenhower

Wood Storage 23w Compact Fluorescent S/I 4 23 0.09 500 46 7$ No Work Proposed 0 23 0.09 500 46 7$ NO SENSOR PROPOSED 0 - - - - -$

129D.D.

EisenhowerComputer/Tech Room

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

15 61 0.92 1,500 1,373 223$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

15 44 0.66 1500 990 161$ NO SENSOR PROPOSED 0 0.26 383 - 383 62.19$

130D.D.

EisenhowerLife Skills

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

40 61 2.44 2,400 5,856 952$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

40 44 1.76 2400 4224 687$ NO SENSOR PROPOSED 0 0.68 1,632 - 1,632 265.36$

131 D.D. Eisenhower

Stairs 42w. Compact Flourescent S/I 1 42 0.04 3,640 153 25$ No Work Proposed 0 42 0.04 3640 153 25$ NO SENSOR PROPOSED 0 - - - - -$

132 D.D. Eisenhower

Storage 23w Compact Fluorescent S/I 4 23 0.09 500 46 7$ No Work Proposed 0 23 0.09 500 46 7$ NO SENSOR PROPOSED 0 - - - - -$

133D.D.

EisenhowerArt Room

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

25 61 1.53 1,500 2,288 372$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

25 44 1.10 1500 1650 268$ NO SENSOR PROPOSED 0 0.43 638 - 638 103.66$

134D.D.

EisenhowerStorage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.15$

135D.D.

EisenhowerKiln

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,500 183 30$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1500 132 21$ NO SENSOR PROPOSED 0 0.03 51 - 51 8.29$

136D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 417$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

28 44 1.23 975 1201 195$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.48 714 647 1,361 221.27$

137D.D.

EisenhowerChem Storage

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

3 61 0.18 500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.15$

138D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 417$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

28 44 1.23 975 1201 195$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.48 714 647 1,361 221.27$

139D.D.

EisenhowerComputer Class

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

28 61 1.71 1,500 2,562 417$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

28 44 1.23 1500 1848 300$ NO SENSOR PROPOSED 0 0.48 714 - 714 116.10$

140D.D.

EisenhowerDigital Arts

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

20 89 1.78 1,500 2,670 434$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 63 1.26 1500 1890 307$ NO SENSOR PROPOSED 0 0.52 780 - 780 126.83$

141D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

142D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

143D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

144D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

145D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

146D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

147D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

148D.D.

EisenhowerClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

20 61 1.22 1,500 1,830 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 44 0.88 1500 1320 215$ NO SENSOR PROPOSED 0 0.34 510 - 510 82.93$

149D.D.

EisenhowerStorage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 500 183 30$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 500 132 21$ NO SENSOR PROPOSED 0 0.10 51 - 51 8.29$

150D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 975 737 120$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 397 865 140.63$

151D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 975 737 120$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 397 865 140.63$

152D.D.

EisenhowerCafeteria

High Bay Fixture with (1) 400w Metal Halide Lamp and (1) Magnetic HID Ballast

18 445 8.01 3,640 29,156 4,741$

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

18 234 4.21 3640 15332 2,493$ NO SENSOR PROPOSED 0 3.80 13,825 - 13,825 2,247.90$

153 D.D. Eisenhower

Cafeteria Exit Sign w/ (2) 20w Incandescent Lamps 4 40 0.16 8,760 1,402 228$ Remove and Replace existing exit sign with a new LED exit sign.

4 2 0.01 8760 70 11$ NO SENSOR PROPOSED 0 0.15 1,332 - 1,332 216.51$

154 D.D. Eisenhower

Cafeteria 150w Incandescent S/I 4 150 0.60 3,640 2,184 355$ Re-lamp with 40w Compact Fluorescent 4 40 0.16 3640 582 95$ NO SENSOR PROPOSED 0 0.44 1,602 - 1,602 260.42$

155D.D.

EisenhowerKitchen

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

26 61 1.59 2,400 3,806 619$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

26 44 1.14 2400 2746 446$ NO SENSOR PROPOSED 0 0.44 1,061 - 1,061 172.49$

5 of 52

Page 249: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

156D.D.

EisenhowerKitchen Storage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.15$

157D.D.

EisenhowerGarbage Bins

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 2,400 586 95$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1560 275 45$ Wall Switch Occupancy Sensor 1 0.07 163 148 311 50.58$

158D.D.

EisenhowerFaculty Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 2,400 2,563 417$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1560 1179 192$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 749 635 1,384 225.01$

159D.D.

EisenhowerBoys

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 95$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 69$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.54$

160D.D.

EisenhowerBoys

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.63$

161D.D.

EisenhowerBoys

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

162D.D.

EisenhowerGirls

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 95$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 69$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.54$

163D.D.

EisenhowerGirls

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

164D.D.

EisenhowerGirls

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.27$

165 D.D. Eisenhower

Men's Room Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

166D.D.

EisenhowerMen's Room

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

167 D.D. Eisenhower

Women's Room Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

168D.D.

EisenhowerWomen's Room

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

169D.D.

EisenhowerElectrical Panel Room

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

2 89 0.18 1,000 178 29$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 1000 126 20$ NO SENSOR PROPOSED 0 0.05 52 - 52 8.46$

170D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 1,500 1,469 239$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 63 0.69 975 676 110$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.29 429 364 793 128.91$

171D.D.

EisenhowerClass

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 1,500 51 8$ No Work Proposed 0 34 0.03 1500 51 8$ NO SENSOR PROPOSED 0 - - - - -$

172 D.D. Eisenhower

Class Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350 57$ Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 0.04 333 - 333 54.13$

173D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 1,500 1,469 239$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 63 0.69 975 676 110$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.29 429 364 793 128.91$

174D.D.

EisenhowerClass

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 1,500 51 8$ No Work Proposed 0 34 0.03 1500 51 8$ NO SENSOR PROPOSED 0 - - - - -$

175 D.D. Eisenhower

Class Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350 57$ Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 0.04 333 - 333 54.13$

176D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 975 737 120$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 397 865 140.63$

177D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 975 737 120$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 397 865 140.63$

178D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 1,500 1,469 239$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 63 0.69 1500 1040 169$ NO SENSOR PROPOSED 0 0.29 429 - 429 69.76$

179D.D.

EisenhowerClass

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 1,500 51 8$ No Work Proposed 0 34 0.03 1500 51 8$ NO SENSOR PROPOSED 0 - - - - -$

180D.D.

EisenhowerClass

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

1 34 0.03 1,500 51 8$ No Work Proposed 0 34 0.03 1500 51 8$ NO SENSOR PROPOSED 0 - - - - -$

181D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 1,500 1,469 239$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 63 0.69 1500 1040 169$ NO SENSOR PROPOSED 0 0.29 429 - 429 69.76$

182D.D.

EisenhowerElectrical Room

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 1,000 183 30$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 1000 132 21$ NO SENSOR PROPOSED 0 0.05 51 - 51 8.29$

183D.D.

EisenhowerSGI

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 174$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 975 491 80$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 312 265 577 93.76$

184D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 975 737 120$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 397 865 140.63$

185D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

20 89 1.78 1,500 2,670 434$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 63 1.26 975 1229 200$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

2 0.52 780 662 1,442 234.39$

186D.D.

EisenhowerPrep Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,500 534 87$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 975 246 40$ Wall Switch Occupancy Sensor 1 0.10 156 132 288 46.88$

187D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

20 89 1.78 1,500 2,670 434$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 63 1.26 975 1229 200$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

2 0.52 780 662 1,442 234.39$

6 of 52

Page 250: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

188D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 975 737 120$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 397 865 140.63$

189D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 975 737 120$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 397 865 140.63$

190D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 76.10$

191D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 76.10$

192D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 76.10$

193D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 76.10$

194D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 76.10$

195D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 76.10$

196D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 76.10$

197D.D.

EisenhowerSGI

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,500 534 87$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 1500 378 61$ NO SENSOR PROPOSED 0 0.10 156 - 156 25.37$

198 D.D. Eisenhower

Gym High Bay Fixture with (8) 42w Triple Tube PL Fluorescent Lamps

24 336 8.06 2,400 19,354 3,147$ No Work Proposed 0 336 8.06 2400 19354 3,147$ NO SENSOR PROPOSED 0 - - - - -$

199 D.D. Eisenhower

Gym Exit Sign w/ 2w LED 4 2 0.01 8,760 70 11$ No Work Proposed 0 2 0.01 8760 70 11$ NO SENSOR PROPOSED 0 - - - - -$

200D.D.

EisenhowerStorage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 500 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 500 88 14$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.53$

201D.D.

EisenhowerCoach Office

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 30$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1500 132 21$ NO SENSOR PROPOSED 0 0.03 51 - 51 8.29$

202D.D.

EisenhowerBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 61 0.31 2,400 732 119$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

5 44 0.22 2400 528 86$ NO SENSOR PROPOSED 0 0.09 204 - 204 33.17$

203D.D.

EisenhowerRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.63$

204D.D.

EisenhowerGirls

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 61 0.31 2,400 732 119$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

5 44 0.22 2400 528 86$ NO SENSOR PROPOSED 0 0.09 204 - 204 33.17$

205D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 76.10$

206D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 76.10$

207D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 76.10$

208D.D.

EisenhowerClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,500 534 87$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 1500 378 61$ NO SENSOR PROPOSED 0 0.10 156 - 156 25.37$

209D.D.

EisenhowerCourtyard 2004 wing

Wall Pack Fixture w/ (1) 100w High Pressure Sodium Lamp and Magnetic

Ballast6 120 0.72 3,640 2,621 426$ No Work Proposed 0 120 0.72 3640 2621 426$ NO SENSOR PROPOSED 0 - - - - -$

210D.D.

EisenhowerCourtyard by office

Wall Pack Fixture w/ (1) 100w High Pressure Sodium Lamp and Magnetic

Ballast4 120 0.48 3,640 1,747 284$ No Work Proposed 0 120 0.48 3640 1747 284$ NO SENSOR PROPOSED 0 - - - - -$

211D.D.

EisenhowerCourtyard

Wall Pack Fixture w/ (1) 100w High Pressure Sodium Lamp and Magnetic

Ballast3 120 0.36 3,640 1,310 213$ No Work Proposed 0 120 0.36 3640 1310 213$ NO SENSOR PROPOSED 0 - - - - -$

212D.D.

EisenhowerOutside

Wall Pack Fixture w/ (1) 100w High Pressure Sodium Lamp and Magnetic

Ballast27 120 3.24 3,640 11,794 1,918$ No Work Proposed 0 120 3.24 3640 11794 1,918$ NO SENSOR PROPOSED 0 - - - - -$

213D.D.

EisenhowerOutside

Wall Pack Fixture w/ (1) 70w High Pressure Sodium Lamp and Magnetic

Ballast22 92 2.02 3,640 7,367 1,198$ No Work Proposed 0 92 2.02 3640 7367 1,198$ NO SENSOR PROPOSED 0 - - - - -$

214D.D.

EisenhowerOutside

Wall Pack Fixture with (1) 175w Mercury Vapor Lamp and (1) Magnetic HID Ballast

4 205 0.82 3,640 2,985 485$ Remove and Replace Existing Fixture With a New Outdoor Flood Fixture Containing a 150w Pulse

Metal Halide Lamp4 85 0.34 3640 1238 201$ NO SENSOR PROPOSED 0 0.48 1,747 - 1,747 284.09$

215D.D.

EisenhowerOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 400w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast14 445 6.23 3,640 22,677 3,687$ No Work Proposed 0 445 6.23 3640 22677 3,687$ NO SENSOR PROPOSED 0 - - - - -$

216D.D.

EisenhowerOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 250w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast5 286 1.43 3,640 5,205 846$ No Work Proposed 0 286 1.43 3640 5205 846$ NO SENSOR PROPOSED 0 - - - - -$

217D.D.

EisenhowerOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 400w High Pressure Sodium Lamp

and (1) Magnetic HID Ballast5 450 2.25 3,640 8,190 1,332$ No Work Proposed 0 450 2.25 3640 8190 1,332$ NO SENSOR PROPOSED 0 - - - - -$

34 46 103157 10633 113790 $18,395Totals for Lighting System Upgrades at D.D. Eisenhower:

7 of 52

Page 251: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

218 J.J. Catena Corridor 219-2242X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

8 110 0.88 3,640 3,203 525$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 3640 2446 401$ NO SENSOR PROPOSED 0 0.21 757 - 757 124.17$

219 J.J. Catena Corridor 219-224 Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350 57$ Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 0.04 333 - 333 54.59$

220 J.J. Catena Corridor 213-2182X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

18 110 1.98 3,640 7,207 1,182$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 84 1.51 3640 5504 903$ NO SENSOR PROPOSED 0 0.47 1,704 - 1,704 279.38$

221 J.J. Catena Corridor 213-2182X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 3,640 648 106$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 3640 459 75$ NO SENSOR PROPOSED 0 0.05 189 - 189 31.04$

222 J.J. Catena Corridor 213-2182X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 73$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 3640 320 53$ NO SENSOR PROPOSED 0 0.03 124 - 124 20.30$

223 J.J. Catena Corridor 213-2184' Strip Fxiture with (2) F32 T8 Lamps &

(1) 2L Electronic Ballast1 61 0.06 3,640 222 36$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 3640 160 26$ NO SENSOR PROPOSED 0 0.02 62 - 62 10.15$

224 J.J. Catena Corridor 213-218 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

225 J.J. Catena Corridor 210-2122X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

9 110 0.99 3,640 3,604 591$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 84 0.76 3640 2752 451$ NO SENSOR PROPOSED 0 0.23 852 - 852 139.69$

226 J.J. Catena Corridor 210-2122X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 3640 641 105$ NO SENSOR PROPOSED 0 0.07 248 - 248 40.59$

227 J.J. Catena Corridor 210-2124' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast1 31 0.03 3,640 113 19$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 25 0.03 3640 91 15$ NO SENSOR PROPOSED 0 0.01 22 - 22 3.58$

228 J.J. Catena Corridor 210-212 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

229 J.J. Catena Corridor 210-212 Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350 57$ Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 0.04 333 - 333 54.59$

230 J.J. Catena Corridor 200-2092X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

21 110 2.31 3,640 8,408 1,379$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

21 84 1.76 3640 6421 1,053$ NO SENSOR PROPOSED 0 0.55 1,987 - 1,987 325.94$

231 J.J. Catena Corridor 200-209 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

232 J.J. Catena Corridor Ext. 12X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 3,640 1,776 291$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 44 0.35 3640 1281 210$ NO SENSOR PROPOSED 0 0.14 495 - 495 81.19$

233 J.J. Catena Corridor Ext. 1 Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 115$ Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 0.08 666 - 666 109.18$

234 J.J. Catena Corridor Ext. 22X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 255$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 44 0.31 3640 1121 184$ NO SENSOR PROPOSED 0 0.12 433 - 433 71.04$

235 J.J. Catena Corridor 231-2442X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

25 61 1.53 3,640 5,551 910$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

25 44 1.10 3640 4004 657$ NO SENSOR PROPOSED 0 0.43 1,547 - 1,547 253.71$

236 J.J. Catena Corridor 231-244 Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 115$ Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 0.08 666 - 666 109.18$

237 J.J. Catena Corridor 102-1052X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 255$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 44 0.31 3640 1121 184$ NO SENSOR PROPOSED 0 0.12 433 - 433 71.04$

238 J.J. Catena Corridor 102-105 Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350 57$ Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 0.04 333 - 333 54.59$

239 J.J. Catena Corridor 108-1132X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

10 61 0.61 3,640 2,220 364$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 3640 1602 263$ NO SENSOR PROPOSED 0 0.17 619 - 619 101.48$

240 J.J. Catena Corridor 108-113 Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 115$ Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 0.08 666 - 666 109.18$

241 J.J. Catena Corridor 116-1172X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 218$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 3640 961 158$ NO SENSOR PROPOSED 0 0.10 371 - 371 60.89$

242 J.J. Catena Corridor 116-117 Exit Sign w/ (2) 20w Incandescent Lamps 1 40 0.04 8,760 350 57$ Remove and Replace existing exit sign with a new LED exit sign.

1 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 0.04 333 - 333 54.59$

243 J.J. Catena Library High Bay Fixture with (8) 42w Triple Tube PL Fluorescent Lamps

11 336 3.70 2,400 8,870 1,455$ No Work Proposed 0 336 3.70 2400 8870 1,455$ NO SENSOR PROPOSED 0 - - - - -$

244 J.J. Catena Video Storage2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 500 134 22$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 500 95 15$ NO SENSOR PROPOSED 0 0.08 39 - 39 6.40$

245 J.J. Catena Video Storage2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ No Work Proposed 0 61 0.06 500 31 5$ NO SENSOR PROPOSED 0 - - - - -$

246 J.J. Catena Hub Room4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast2 61 0.12 2,400 293 48$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.38$

247 J.J. Catena Computer Room4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast24 61 1.46 1,500 2,196 360$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place24 44 1.06 975 1030 169$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.41 612 554 1,166 191.29$

248 J.J. Catena Storage4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 500 31 5$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.39$

249 J.J. Catena Restroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

250 J.J. Catena Restroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

251 J.J. Catena Storage4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 500 31 5$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.39$

252 J.J. Catena Storage4' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast3 110 0.33 500 165 27$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place3 84 0.25 500 126 21$ NO SENSOR PROPOSED 0 0.08 39 - 39 6.40$

8 of 52

Page 252: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

253 J.J. Catena Electrical Room4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast2 61 0.12 1,000 122 20$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 1000 88 14$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.58$

254 J.J. Catena SGI4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast12 61 0.73 1,500 1,098 180$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 44 0.53 975 515 84$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.20 306 277 583 95.64$

255 J.J. Catena Art4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast40 61 2.44 1,500 3,660 600$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place40 44 1.76 1500 2640 433$ NO SENSOR PROPOSED 0 0.68 1,020 - 1,020 167.28$

256 J.J. Catena Storage2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 500 110 18$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 500 84 14$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.26$

257 J.J. Catena Boiler Room4' Indusrtial Hood Fixture w/ (1) F32 T8

Lamps & (1) 1L Electronic Ballast6 57 0.34 1,000 342 56$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place6 25 0.15 1000 150 25$ NO SENSOR PROPOSED 0 0.19 192 - 192 31.49$

258 J.J. Catena Slop Sink4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 1,000 61 10$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.79$

259 J.J. Catena Custodian/ ReceivingIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast4 61 0.24 2,400 586 96$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 2400 422 69$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.76$

260 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

261 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

262 J.J. Catena Class/Speech4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast1 31 0.03 1,500 47 8$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 25 0.03 1500 38 6$ NO SENSOR PROPOSED 0 0.01 9 - 9 1.48$

263 J.J. Catena Class/SpeechIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast6 61 0.37 1,500 549 90$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place6 44 0.26 1500 396 65$ NO SENSOR PROPOSED 0 0.10 153 - 153 25.09$

264 J.J. Catena Women's Room 60w. Incandescent S/I 2 60 0.12 2,400 288 47$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 10$ NO SENSOR PROPOSED 0 0.09 226 - 226 37.00$

265 J.J. Catena Men's Room 60w. Incandescent S/I 2 60 0.12 2,400 288 47$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 10$ NO SENSOR PROPOSED 0 0.09 226 - 226 37.00$

266 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

267 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

268 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

269 J.J. Catena Bathroom 60w. Incandescent S/I 2 60 0.12 2,400 288 47$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 10$ NO SENSOR PROPOSED 0 0.09 226 - 226 37.00$

270 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

271 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

272 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast27 61 1.65 1,500 2,471 405$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place27 44 1.19 975 1158 190$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.46 689 624 1,312 215.20$

273 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast30 61 1.83 1,500 2,745 450$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place30 44 1.32 975 1287 211$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.51 765 693 1,458 239.11$

274 J.J. Catena Closet 60w. Incandescent S/I 1 60 0.06 500 30 5$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 500 7 1$ NO SENSOR PROPOSED 0 0.05 24 - 24 3.85$

275 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast30 61 1.83 1,500 2,745 450$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place30 44 1.32 975 1287 211$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.51 765 693 1,458 239.11$

276 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 1500 1386 227$ NO SENSOR PROPOSED 0 0.36 536 - 536 87.82$

277 J.J. Catena Class4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast18 61 1.10 1,500 1,647 270$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place18 44 0.79 975 772 127$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 459 416 875 143.47$

278 J.J. Catena Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

279 J.J. Catena Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

280 J.J. Catena Guidence Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 210$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 1560 590 97$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 374 318 692 113.47$

281 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

9 of 52

Page 253: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

282 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

283 J.J. Catena Boys4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast6 31 0.19 2,400 446 73$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place6 25 0.15 2400 360 59$ NO SENSOR PROPOSED 0 0.04 86 - 86 14.17$

284 J.J. Catena Slop Sink4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 1,000 61 10$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.79$

285 J.J. Catena Girls4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast4 31 0.12 2,400 298 49$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 25 0.10 2400 240 39$ NO SENSOR PROPOSED 0 0.02 58 - 58 9.45$

286 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

287 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

288 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

289 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

290 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

291 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

292 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

293 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

294 J.J. Catena Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast21 61 1.28 1,500 1,922 315$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place21 44 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 536 485 1,021 167.38$

295 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 89 0.45 1,500 668 109$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

5 63 0.32 1500 473 77$ NO SENSOR PROPOSED 0 0.13 195 - 195 31.98$

296 J.J. Catena Storage/Conference2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 500 178 29$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 325 82 13$ Wall Switch Occupancy Sensor 1 0.10 52 44 96 15.76$

297 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 89 0.45 1,500 668 109$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

5 63 0.32 1500 473 77$ NO SENSOR PROPOSED 0 0.13 195 - 195 31.98$

298 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 131$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 975 369 60$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 234 198 432 70.92$

299 J.J. Catena Electrical RoomIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast1 61 0.06 1,000 61 10$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.79$

300 J.J. Catena Nurse's Office2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 2,400 1,056 173$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 2400 806 132$ NO SENSOR PROPOSED 0 0.10 250 - 250 40.93$

301 J.J. Catena Nurse's Office2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - -$

302 J.J. Catena Nurse's Office4' Vanity Fxiture with (2) F32 T8 Lamps &

(1) 2L Electronic Ballast2 61 0.12 2,400 293 48$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.38$

303 J.J. Catena Bathroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.69$

304 J.J. Catena Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

305 J.J. Catena Storage4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 500 31 5$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.39$

306 J.J. Catena Work Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 140$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 2400 605 99$ NO SENSOR PROPOSED 0 0.10 250 - 250 40.93$

307 J.J. Catena Bathroom 60w. Incandescent S/I 2 60 0.12 2,400 288 47$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 10$ NO SENSOR PROPOSED 0 0.09 226 - 226 37.00$

308 J.J. Catena Main Office2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 96$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 69$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.76$

309 J.J. Catena Principal2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 87$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 1560 262 43$ Wall Switch Occupancy Sensor 1 0.05 125 141 266 43.61$

310 J.J. Catena Women's Room2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

10 of 52

Page 254: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

311 J.J. Catena Women's Room Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

312 J.J. Catena Men's Room2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

313 J.J. Catena Men's Room Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

314 J.J. Catena Vocal Music2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 263$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 186$ NO SENSOR PROPOSED 0 0.31 468 - 468 76.75$

315 J.J. Catena Vocal Music2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 1,500 366 60$ No Work Proposed 0 61 0.24 1500 366 60$ NO SENSOR PROPOSED 0 - - - - -$

316 J.J. Catena SGI2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 131$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 975 369 60$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 234 198 432 70.92$

317 J.J. Catena SGI2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 30$ No Work Proposed 0 61 0.12 1500 183 30$ NO SENSOR PROPOSED 0 - - - - -$

318 J.J. Catena Instrumental Music2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 197$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 975 553 91$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.23 351 298 649 106.38$

319 J.J. Catena Gym OfficeIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast12 61 0.73 2,400 1,757 288$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 44 0.53 2400 1267 208$ NO SENSOR PROPOSED 0 0.20 490 - 490 80.29$

320 J.J. Catena GymHigh Bay Fixture with (1) 400w Metal

Halide Lamp and (1) Magnetic HID Ballast18 445 8.01 2,400 19,224 3,153$

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

18 234 4.21 2400 10109 1,658$ NO SENSOR PROPOSED 0 3.80 9,115 - 9,115 1,494.89$

321 J.J. Catena Gym 250w Quartz 6 250 1.50 2,400 3,600 590$ No Work Proposed 0 250 1.50 2400 3600 590$ NO SENSOR PROPOSED 0 - - - - -$

322 J.J. Catena Back StageIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast31 61 1.89 2,400 4,538 744$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place31 44 1.36 2400 3274 537$ NO SENSOR PROPOSED 0 0.53 1,265 - 1,265 207.43$

323 J.J. Catena Back Stage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

324 J.J. Catena Back Stage 100w Incandescent S/I 10 100 1.00 2,400 2,400 394$ Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

10 23 0.23 2400 552 91$ NO SENSOR PROPOSED 0 0.77 1,848 - 1,848 303.07$

325 J.J. Catena Back Stage Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 115$ Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 0.08 666 - 666 109.18$

326 J.J. Catena Cafeteria Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

4 26 0.10 3,640 379 62$ No Work Proposed 0 26 0.10 3640 379 62$ NO SENSOR PROPOSED 0 - - - - -$

327 J.J. Catena Cafeteria2x2 Recessed Fixture w/ (1) 250w Metal

Halide Lamp and Magnetic Ballast20 290 5.80 3,640 21,112 3,462$ No Work Proposed 0 290 5.80 3640 21112 3,462$ NO SENSOR PROPOSED 0 - - - - -$

328 J.J. Catena Kitchen4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast23 61 1.40 2,400 3,367 552$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place23 44 1.01 2400 2429 398$ NO SENSOR PROPOSED 0 0.39 938 - 938 153.90$

329 J.J. Catena Kitchen StorageIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast2 61 0.12 500 61 10$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.79$

330 J.J. Catena Receiving RoomIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast10 61 0.61 2,400 1,464 240$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place10 44 0.44 2400 1056 173$ NO SENSOR PROPOSED 0 0.17 408 - 408 66.91$

331 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 197$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 975 553 91$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.23 351 298 649 106.38$

332 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 45$ No Work Proposed 0 61 0.18 1500 275 45$ NO SENSOR PROPOSED 0 - - - - -$

333 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 197$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 975 553 91$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.23 351 298 649 106.38$

334 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 45$ No Work Proposed 0 61 0.18 1500 275 45$ NO SENSOR PROPOSED 0 - - - - -$

335 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 197$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 975 553 91$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.23 351 298 649 106.38$

336 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 45$ No Work Proposed 0 61 0.18 1500 275 45$ NO SENSOR PROPOSED 0 - - - - -$

337 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 263$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 975 737 121$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 397 865 141.84$

338 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 1,500 366 60$ No Work Proposed 0 61 0.24 1500 366 60$ NO SENSOR PROPOSED 0 - - - - -$

339 J.J. Catena Boys1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 96$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 69$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.76$

340 J.J. Catena Boys4' Vanity Fxiture with (2) F32 T8 Lamps &

(1) 2L Electronic Ballast3 61 0.18 2,400 439 72$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place3 44 0.13 2400 317 52$ NO SENSOR PROPOSED 0 0.05 122 - 122 20.07$

341 J.J. Catena Boys Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

342 J.J. Catena Girls1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 96$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 69$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.76$

343 J.J. Catena Girls4' Vanity Fxiture with (2) F32 T8 Lamps &

(1) 2L Electronic Ballast3 61 0.18 2,400 439 72$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place3 44 0.13 2400 317 52$ NO SENSOR PROPOSED 0 0.05 122 - 122 20.07$

344 J.J. Catena Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

345 J.J. Catena Custodian4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast2 61 0.12 1,000 122 20$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 1000 88 14$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.58$

11 of 52

Page 255: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

346 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 197$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 1500 851 139$ NO SENSOR PROPOSED 0 0.23 351 - 351 57.56$

347 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 45$ No Work Proposed 0 61 0.18 1500 275 45$ NO SENSOR PROPOSED 0 - - - - -$

348 J.J. Catena Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 197$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 1500 851 139$ NO SENSOR PROPOSED 0 0.23 351 - 351 57.56$

349 J.J. Catena Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 45$ No Work Proposed 0 61 0.18 1500 275 45$ NO SENSOR PROPOSED 0 - - - - -$

350 J.J. Catena Teachers Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 2,400 2,350 385$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 63 0.69 1560 1081 177$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.29 686 582 1,269 208.04$

351 J.J. Catena Teachers Room2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 72$ No Work Proposed 0 61 0.18 2400 439 72$ NO SENSOR PROPOSED 0 - - - - -$

352 J.J. Catena Hub RoomIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast2 61 0.12 2,400 293 48$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.38$

353 J.J. Catena Receiving RoomIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast6 61 0.37 2,400 878 144$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place6 44 0.26 2400 634 104$ NO SENSOR PROPOSED 0 0.10 245 - 245 40.15$

354 J.J. Catena Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 219$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place10 63 0.63 1500 945 155$ NO SENSOR PROPOSED 0 0.26 390 - 390 63.96$

355 J.J. Catena Class4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast14 61 0.85 1,500 1,281 210$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place14 44 0.62 1500 924 152$ NO SENSOR PROPOSED 0 0.24 357 - 357 58.55$

356 J.J. Catena Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.69$

357 J.J. Catena Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.39$

358 J.J. Catena Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 219$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place10 63 0.63 1500 945 155$ NO SENSOR PROPOSED 0 0.26 390 - 390 63.96$

359 J.J. Catena Class4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast14 61 0.85 1,500 1,281 210$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place14 44 0.62 1500 924 152$ NO SENSOR PROPOSED 0 0.24 357 - 357 58.55$

360 J.J. Catena Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.69$

361 J.J. Catena Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.39$

362 J.J. Catena Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 219$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place10 63 0.63 1500 945 155$ NO SENSOR PROPOSED 0 0.26 390 - 390 63.96$

363 J.J. Catena Class4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast14 61 0.85 1,500 1,281 210$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place14 44 0.62 1500 924 152$ NO SENSOR PROPOSED 0 0.24 357 - 357 58.55$

364 J.J. Catena Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.69$

365 J.J. Catena Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.39$

366 J.J. Catena Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 219$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place10 63 0.63 1500 945 155$ NO SENSOR PROPOSED 0 0.26 390 - 390 63.96$

367 J.J. Catena Class4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast14 61 0.85 1,500 1,281 210$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place14 44 0.62 1500 924 152$ NO SENSOR PROPOSED 0 0.24 357 - 357 58.55$

368 J.J. Catena Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.69$

369 J.J. Catena Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.39$

370 J.J. Catena Cafeteria Recessed Can Can w/ (2) 57w CF PL 12 114 1.37 3,640 4,980 817$ No Work Proposed 0 114 1.37 3640 4980 817$ NO SENSOR PROPOSED 0 - - - - -$

371 J.J. Catena Bathroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.69$

372 J.J. Catena Kitchen2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 96$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 69$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.76$

373 J.J. Catena Kitchen Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.39$

374 J.J. Catena Closet2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.39$

375 J.J. Catena MPR Recessed Can Can w/ (2) 13w CF PL 13 26 0.34 2,400 811 133$ No Work Proposed 0 26 0.34 2400 811 133$ NO SENSOR PROPOSED 0 - - - - -$

12 of 52

Page 256: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

376 J.J. Catena Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast10 89 0.89 1,500 1,335 219$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place10 63 0.63 1500 945 155$ NO SENSOR PROPOSED 0 0.26 390 - 390 63.96$

377 J.J. Catena Class4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast14 61 0.85 1,500 1,281 210$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place14 44 0.62 1500 924 152$ NO SENSOR PROPOSED 0 0.24 357 - 357 58.55$

378 J.J. Catena Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.69$

379 J.J. Catena Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.39$

380 J.J. Catena StorageIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast3 61 0.18 500 92 15$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.18$

381 J.J. Catena Boiler RoomIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast4 61 0.24 1,000 244 40$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1000 176 29$ NO SENSOR PROPOSED 0 0.07 68 - 68 11.15$

382 J.J. Catena OutsideParking Lot Fixture Mounted on a Pole w/

(1) 250w High Pressure Sodium Lamp and (1) Magnetic HID Ballast

5 300 1.50 3,640 5,460 895$ No Work Proposed 0 300 1.50 3640 5460 895$ NO SENSOR PROPOSED 0 - - - - -$

383 J.J. Catena OutsideWall Pack Fixture w/ (1) 50w High

Pressure Sodium Lamp and Magnetic Ballast

21 65 1.37 3,640 4,969 815$ No Work Proposed 0 65 1.37 3640 4969 815$ NO SENSOR PROPOSED 0 - - - - -$

384 J.J. Catena OutsideWall Pack Fixture w/ (1) 100w High

Pressure Sodium Lamp and Magnetic Ballast

17 120 2.04 3,640 7,426 1,218$ No Work Proposed 0 120 2.04 3640 7426 1,218$ NO SENSOR PROPOSED 0 - - - - -$

385 J.J. Catena OutsideWall Pack Fixture with (1) 100w Metal

Halide Lamp and (1) Magnetic HID Ballast12 120 1.44 3,640 5,242 860$ No Work Proposed 0 120 1.44 3640 5242 860$ NO SENSOR PROPOSED 0 - - - - -$

35 27 55741 15058 70800 $11,611

386 C.T. Barkalow Corridor Fac-3142X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

25 61 1.53 3,640 5,551 899$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

25 44 1.10 3640 4004 649$ NO SENSOR PROPOSED 0 0.43 1,547 - 1,547 250.61$

387 C.T. Barkalow Corridor Fac-314 Exit Sign w/ 2w LED 5 2 0.01 8,760 88 14$ No Work Proposed 0 2 0.01 8760 88 14$ NO SENSOR PROPOSED 0 - - - - -$

388 C.T. Barkalow Corridor 307-3152X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 144$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 3640 641 104$ NO SENSOR PROPOSED 0 0.07 248 - 248 40.10$

389 C.T. Barkalow Corridor 307-3151X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

14 61 0.85 3,640 3,109 504$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 3640 2242 363$ NO SENSOR PROPOSED 0 0.24 866 - 866 140.34$

390 C.T. Barkalow Corridor 307-315 Exit Sign w/ 2w LED 5 2 0.01 8,760 88 14$ No Work Proposed 0 2 0.01 8760 88 14$ NO SENSOR PROPOSED 0 - - - - -$

391 C.T. Barkalow Corridor 301-3042X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

19 61 1.16 3,640 4,219 683$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

19 44 0.84 3640 3043 493$ NO SENSOR PROPOSED 0 0.32 1,176 - 1,176 190.47$

392 C.T. Barkalow Corridor 301-3042X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 3,640 3,888 630$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 3640 2752 446$ NO SENSOR PROPOSED 0 0.31 1,136 - 1,136 183.98$

393 C.T. Barkalow Corridor 301-3042X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 36$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 3640 160 26$ NO SENSOR PROPOSED 0 0.02 62 - 62 10.02$

394 C.T. Barkalow Corridor 301-304Recessed Can Can w/ (1) 100w Incan.

Screw In5 100 0.50 3,640 1,820 295$

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

5 23 0.12 3640 419 68$ NO SENSOR PROPOSED 0 0.39 1,401 - 1,401 227.03$

395 C.T. Barkalow Corridor 301-304 Exit Sign w/ 2w LED 4 2 0.01 8,760 70 11$ No Work Proposed 0 2 0.01 8760 70 11$ NO SENSOR PROPOSED 0 - - - - -$

396 C.T. Barkalow Corridor 3702X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 216$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 3640 961 156$ NO SENSOR PROPOSED 0 0.10 371 - 371 60.15$

397 C.T. Barkalow Corridor 3702X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

9 34 0.31 3,640 1,114 180$ No Work Proposed 0 34 0.31 3640 1114 180$ NO SENSOR PROPOSED 0 - - - - -$

398 C.T. Barkalow Corridor 370 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

399 C.T. Barkalow Corridor 3151X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

10 61 0.61 3,640 2,220 360$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 3640 1602 259$ NO SENSOR PROPOSED 0 0.17 619 - 619 100.25$

400 C.T. Barkalow Corridor 3152X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

5 61 0.31 3,640 1,110 180$ No Work Proposed 0 61 0.31 3640 1110 180$ NO SENSOR PROPOSED 0 - - - - -$

401 C.T. Barkalow Corridor 315 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

402 C.T. Barkalow Corridor 315-3291X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

19 61 1.16 3,640 4,219 683$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

19 44 0.84 3640 3043 493$ NO SENSOR PROPOSED 0 0.32 1,176 - 1,176 190.47$

403 C.T. Barkalow Corridor 315-329 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

404 C.T. Barkalow Corridor Ext.1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 252$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 44 0.31 3640 1121 182$ NO SENSOR PROPOSED 0 0.12 433 - 433 70.17$

405 C.T. Barkalow Corridor 361-3682X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

13 61 0.79 3,640 2,887 468$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

13 44 0.57 3640 2082 337$ NO SENSOR PROPOSED 0 0.22 804 - 804 130.32$

406 C.T. Barkalow Corridor 361-368 3' Strip Fxiture with (1) F25 T8 Lamps & (1) 1L Electronic Ballast

4 48 0.19 3,640 699 113$ No Work Proposed 0 48 0.19 3640 699 113$ NO SENSOR PROPOSED 0 - - - - -$

407 C.T. Barkalow Corridor 361-368 3' Strip Fxiture with (1) F25 T8 Lamps & (1) 1L Electronic Ballast

4 48 0.19 3,640 699 113$ No Work Proposed 0 48 0.19 3640 699 113$ NO SENSOR PROPOSED 0 - - - - -$

408 C.T. Barkalow Corridor 361-368 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

409 C.T. Barkalow Corridor 370-372B Recessed Can Can w/ (2) 13w CF PL 10 26 0.26 3,640 946 153$ No Work Proposed 0 26 0.26 3640 946 153$ NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at J.J. Catena:

13 of 52

Page 257: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

410 C.T. Barkalow Corridor 370-372B4X4 recessed troffer with (4) F32 T8

Lamps & (1) 4-Light Electronic ballasts3 110 0.33 3,640 1,201 195$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place3 84 0.25 3640 917 149$ NO SENSOR PROPOSED 0 0.08 284 - 284 46.00$

411 C.T. Barkalow Corridor 370-372B Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

412 C.T. Barkalow Corridor 380-3832X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 61 0.73 3,640 2,664 432$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 3640 1922 311$ NO SENSOR PROPOSED 0 0.20 743 - 743 120.29$

413 C.T. Barkalow Corridor 380-3834X4 recessed troffer with (4) F32 T8

Lamps & (1) 4-Light Electronic ballasts3 110 0.33 3,640 1,201 195$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place3 84 0.25 3640 917 149$ NO SENSOR PROPOSED 0 0.08 284 - 284 46.00$

414 C.T. Barkalow Corridor 380-383 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

415 C.T. Barkalow Corridor 373-3792X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 61 0.67 3,640 2,442 396$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 44 0.48 3640 1762 285$ NO SENSOR PROPOSED 0 0.19 681 - 681 110.27$

416 C.T. Barkalow Corridor 373-379 Recessed Can Can w/ (2) 13w CF PL 8 26 0.21 3,640 757 123$ No Work Proposed 0 26 0.21 3640 757 123$ NO SENSOR PROPOSED 0 - - - - -$

417 C.T. Barkalow Corridor 373-379 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

418 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast24 61 1.46 1,500 2,196 356$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

16 54 0.86 1500 1296 210$ NO SENSOR PROPOSED 0 0.60 900 - 900 145.80$

419 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast24 61 1.46 1,500 2,196 356$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

16 54 0.86 1500 1296 210$ NO SENSOR PROPOSED 0 0.60 900 - 900 145.80$

420 C.T. Barkalow Storage4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast1 50 0.05 500 25 4$

Re-lamp & Re-ballast existing fixture. Install a 1-Lamp Electronic Low Power Ballast, (1) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.1 25 0.03 500 13 2$ NO SENSOR PROPOSED 0 0.03 13 - 13 2.03$

421 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast24 61 1.46 1,500 2,196 356$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

16 54 0.86 1500 1296 210$ NO SENSOR PROPOSED 0 0.60 900 - 900 145.80$

422 C.T. Barkalow Closet4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 500 31 5$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.38$

423 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast24 61 1.46 1,500 2,196 356$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place24 44 1.06 1500 1584 257$ NO SENSOR PROPOSED 0 0.41 612 - 612 99.14$

424 C.T. Barkalow Tech Room4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast1 50 0.05 1,500 75 12$

Re-lamp & Re-ballast existing fixture. Install a 1-Lamp Electronic Low Power Ballast, (1) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.1 25 0.03 1500 38 6$ NO SENSOR PROPOSED 0 0.03 38 - 38 6.08$

425 C.T. Barkalow home & life skills4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast34 61 2.07 1,500 3,111 504$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place34 44 1.50 1500 2244 364$ NO SENSOR PROPOSED 0 0.58 867 - 867 140.45$

426 C.T. Barkalow Work Room4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 2,400 586 95$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 2400 422 68$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.44$

427 C.T. Barkalow Office4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 2,400 586 95$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 2400 422 68$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.44$

428 C.T. Barkalow Tech Ed.4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast40 61 2.44 1,500 3,660 593$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place40 44 1.76 1500 2640 428$ NO SENSOR PROPOSED 0 0.68 1,020 - 1,020 165.24$

429 C.T. Barkalow Tech Lab2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 1,500 732 119$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 44 0.35 1500 528 86$ NO SENSOR PROPOSED 0 0.14 204 - 204 33.05$

430 C.T. Barkalow Storage4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 500 31 5$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.38$

431 C.T. Barkalow Computer Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 89 1.42 1,500 2,136 346$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 63 1.01 1500 1512 245$ NO SENSOR PROPOSED 0 0.42 624 - 624 101.09$

432 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast16 61 0.98 1,500 1,464 237$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place16 44 0.70 1500 1056 171$ NO SENSOR PROPOSED 0 0.27 408 - 408 66.10$

433 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830 296$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

15 54 0.81 1500 1215 197$ NO SENSOR PROPOSED 0 0.41 615 - 615 99.63$

434 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830 296$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

15 54 0.81 1500 1215 197$ NO SENSOR PROPOSED 0 0.41 615 - 615 99.63$

435 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830 296$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

15 54 0.81 1500 1215 197$ NO SENSOR PROPOSED 0 0.41 615 - 615 99.63$

436 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830 296$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

15 54 0.81 1500 1215 197$ NO SENSOR PROPOSED 0 0.41 615 - 615 99.63$

437 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830 296$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

15 54 0.81 1500 1215 197$ NO SENSOR PROPOSED 0 0.41 615 - 615 99.63$

14 of 52

Page 258: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

438 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830 296$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

15 54 0.81 1500 1215 197$ NO SENSOR PROPOSED 0 0.41 615 - 615 99.63$

439 C.T. Barkalow Class4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast20 61 1.22 1,500 1,830 296$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

15 54 0.81 1500 1215 197$ NO SENSOR PROPOSED 0 0.41 615 - 615 99.63$

440 C.T. Barkalow Utility RoomIndustrial Hood 8' Fxiture with (2) F96

Econo-Watt T12 Lamps & (1) 2L EE Magnetic Ballast

1 138 0.14 1,000 138 22$

Rebuild an 8' Fixture. Install a 2-Lamp Electronic Low Power Ballast, Reflector, Sub to Measure

Channel, Socket Bracket, (2) 4' 28w T8 Energy Saving Lamps, New Lamp Sockets.

1 42 0.04 1000 42 7$ NO SENSOR PROPOSED 0 0.10 96 - 96 15.55$

441 C.T. Barkalow Boiler Room4' Indusrtial Hood Fixture w/ (1) F32 T8

Lamps & (1) 1L Electronic Ballast6 57 0.34 1,000 342 55$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place6 25 0.15 1000 150 24$ NO SENSOR PROPOSED 0 0.19 192 - 192 31.10$

442 C.T. Barkalow Boiler RoomIndustrial Hood 8' Fxiture with (2) F96

Econo-Watt T12 Lamps & (1) 2L EE Magnetic Ballast

1 138 0.14 1,000 138 22$

Rebuild an 8' Fixture. Install a 2-Lamp Electronic Low Power Ballast, Reflector, Sub to Measure

Channel, Socket Bracket, (2) 4' 28w T8 Energy Saving Lamps, New Lamp Sockets.

1 42 0.04 1000 42 7$ NO SENSOR PROPOSED 0 0.10 96 - 96 15.55$

443 C.T. Barkalow Bathroom4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 2,400 146 24$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.61$

444 C.T. Barkalow Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

445 C.T. Barkalow Guidence2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 311$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 2400 1361 220$ NO SENSOR PROPOSED 0 0.23 562 - 562 90.98$

446 C.T. Barkalow Guidence2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 208$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 2400 907 147$ NO SENSOR PROPOSED 0 0.16 374 - 374 60.65$

447 C.T. Barkalow CST2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 208$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 2400 907 147$ NO SENSOR PROPOSED 0 0.16 374 - 374 60.65$

448 C.T. Barkalow Nurse's Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 2,400 1,709 277$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 2400 1210 196$ NO SENSOR PROPOSED 0 0.21 499 - 499 80.87$

449 C.T. Barkalow Nurse's Office1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.61$

450 C.T. Barkalow Bathroom1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.61$

451 C.T. Barkalow Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

452 C.T. Barkalow Work Room4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast10 61 0.61 2,400 1,464 237$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

10 54 0.54 2400 1296 210$ NO SENSOR PROPOSED 0 0.07 168 - 168 27.22$

453 C.T. Barkalow Bathroom 100w Incandescent S/I 2 100 0.20 2,400 480 78$ Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

2 23 0.05 2400 110 18$ NO SENSOR PROPOSED 0 0.15 370 - 370 59.88$

454 C.T. Barkalow Bathroom 100w Incandescent S/I 2 100 0.20 2,400 480 78$ Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

2 23 0.05 2400 110 18$ NO SENSOR PROPOSED 0 0.15 370 - 370 59.88$

455 C.T. Barkalow Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

456 C.T. Barkalow Principal2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 2,400 1,056 171$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 2400 806 131$ NO SENSOR PROPOSED 0 0.10 250 - 250 40.44$

457 C.T. Barkalow Vice Principal4' Fxiture with Egg Style Lens with (2)

F32 T8 Lamps & (1) 2L Electonic Ballast4 61 0.24 2,400 586 95$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

4 54 0.22 2400 518 84$ NO SENSOR PROPOSED 0 0.03 67 - 67 10.89$

458 C.T. Barkalow Corridor4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast2 31 0.06 3,640 226 37$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 25 0.05 3640 182 29$ NO SENSOR PROPOSED 0 0.01 44 - 44 7.08$

459 C.T. Barkalow Main Office2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

21 61 1.28 2,400 3,074 498$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

21 44 0.92 2400 2218 359$ NO SENSOR PROPOSED 0 0.36 857 - 857 138.80$

460 C.T. Barkalow GymHigh Bay Fixture with (1) 400w Metal

Halide Lamp and (1) Magnetic HID Ballast21 445 9.35 2,400 22,428 3,633$

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

21 234 4.91 2400 11794 1,911$ NO SENSOR PROPOSED 0 4.43 10,634 - 10,634 1,722.77$

461 C.T. Barkalow Gym Exit Sign w/ 2w LED 4 2 0.01 8,760 70 11$ No Work Proposed 0 2 0.01 8760 70 11$ NO SENSOR PROPOSED 0 - - - - -$

462 C.T. Barkalow Gym2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

2 34 0.07 2,400 163 26$ No Work Proposed 0 34 0.07 2400 163 26$ NO SENSOR PROPOSED 0 - - - - -$

463 C.T. Barkalow Storage4' Indusrtial Hood Fixture w/ (1) F34 Econo-Watt T12 Lamps & (1) 1L EE

Magnetic Ballast2 50 0.10 500 50 8$

Re-lamp & Re-ballast existing fixture. Install a 1-Lamp Electronic Low Power Ballast, (1) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.2 25 0.05 500 25 4$ NO SENSOR PROPOSED 0 0.05 25 - 25 4.05$

464 C.T. Barkalow Entrance1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 72$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 3640 320 52$ NO SENSOR PROPOSED 0 0.03 124 - 124 20.05$

465 C.T. Barkalow Boys Locker4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast20 31 0.62 2,400 1,488 241$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place20 25 0.50 2400 1200 194$ NO SENSOR PROPOSED 0 0.12 288 - 288 46.66$

15 of 52

Page 259: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

466 C.T. Barkalow Boys Locker2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 47$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.22$

467 C.T. Barkalow Boys Locker Recessed Can Can w/ (2) 13w CF PL 6 26 0.16 2,400 374 61$ No Work Proposed 0 26 0.16 2400 374 61$ NO SENSOR PROPOSED 0 - - - - -$

468 C.T. Barkalow Office4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 2,400 146 24$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.61$

469 C.T. Barkalow Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

470 C.T. Barkalow Gym Entrance1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 47$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.22$

471 C.T. Barkalow Gym Entrance Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

472 C.T. Barkalow Girls Locker Room4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast16 31 0.50 2,400 1,190 193$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place16 25 0.40 2400 960 156$ NO SENSOR PROPOSED 0 0.10 230 - 230 37.32$

473 C.T. Barkalow Girls Locker Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.61$

474 C.T. Barkalow Girls Locker Room Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 2,400 250 40$ No Work Proposed 0 26 0.10 2400 250 40$ NO SENSOR PROPOSED 0 - - - - -$

475 C.T. Barkalow Girls Coach4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 2,400 146 24$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.61$

476 C.T. Barkalow Bathroom2' Surface Mounted Wrap Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144 23$ Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.11$

477 C.T. Barkalow Storage 60w. Incandescent S/I 2 60 0.12 500 60 10$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 500 13 2$ NO SENSOR PROPOSED 0 0.09 47 - 47 7.61$

478 C.T. Barkalow Men's Room4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast4 31 0.12 2,400 298 48$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 25 0.10 2400 240 39$ NO SENSOR PROPOSED 0 0.02 58 - 58 9.33$

479 C.T. Barkalow Lounge4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast2 31 0.06 2,400 149 24$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 25 0.05 2400 120 19$ NO SENSOR PROPOSED 0 0.01 29 - 29 4.67$

480 C.T. Barkalow Lounge4' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast1 110 0.11 2,400 264 43$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 84 0.08 2400 202 33$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.11$

481 C.T. Barkalow Bathroom4' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast1 110 0.11 2,400 264 43$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 84 0.08 2400 202 33$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.11$

482 C.T. Barkalow Bathroom4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast4 31 0.12 2,400 298 48$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 25 0.10 2400 240 39$ NO SENSOR PROPOSED 0 0.02 58 - 58 9.33$

483 C.T. Barkalow Girls4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast10 31 0.31 2,400 744 121$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place10 25 0.25 2400 600 97$ NO SENSOR PROPOSED 0 0.06 144 - 144 23.33$

484 C.T. Barkalow Boys4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast10 31 0.31 2,400 744 121$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place10 25 0.25 2400 600 97$ NO SENSOR PROPOSED 0 0.06 144 - 144 23.33$

485 C.T. Barkalow Custodian4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast2 31 0.06 1,000 62 10$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 25 0.05 1000 50 8$ NO SENSOR PROPOSED 0 0.01 12 - 12 1.94$

486 C.T. Barkalow Storage #24' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast2 61 0.12 500 61 10$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.75$

487 C.T. Barkalow Storage #24' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast2 31 0.06 500 31 5$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 25 0.05 500 25 4$ NO SENSOR PROPOSED 0 0.01 6 - 6 0.97$

488 C.T. Barkalow Stage4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast2 31 0.06 2,400 149 24$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 25 0.05 2400 120 19$ NO SENSOR PROPOSED 0 0.01 29 - 29 4.67$

489 C.T. Barkalow Stage8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast6 110 0.66 2,400 1,584 257$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place6 84 0.50 2400 1210 196$ NO SENSOR PROPOSED 0 0.16 374 - 374 60.65$

490 C.T. Barkalow Stage4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast10 61 0.61 2,400 1,464 237$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place10 44 0.44 2400 1056 171$ NO SENSOR PROPOSED 0 0.17 408 - 408 66.10$

491 C.T. Barkalow Store room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 1,500 267 43$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 1500 189 31$ NO SENSOR PROPOSED 0 0.05 78 - 78 12.64$

492 C.T. Barkalow Office2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

4 34 0.14 2,400 326 53$ No Work Proposed 0 34 0.14 2400 326 53$ NO SENSOR PROPOSED 0 - - - - -$

493 C.T. Barkalow Class (Vocal Music)2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

15 89 1.34 1,500 2,003 324$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

15 63 0.95 1500 1418 230$ NO SENSOR PROPOSED 0 0.39 585 - 585 94.77$

494 C.T. Barkalow Storage4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast2 31 0.06 500 31 5$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 25 0.05 500 25 4$ NO SENSOR PROPOSED 0 0.01 6 - 6 0.97$

495 C.T. Barkalow Storage4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast2 50 0.10 500 50 8$

Re-lamp & Re-ballast existing fixture. Install a 1-Lamp Electronic Low Power Ballast, (1) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.2 25 0.05 500 25 4$ NO SENSOR PROPOSED 0 0.05 25 - 25 4.05$

16 of 52

Page 260: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

496 C.T. Barkalow Storage #64' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast2 50 0.10 500 50 8$

Re-lamp & Re-ballast existing fixture. Install a 1-Lamp Electronic Low Power Ballast, (1) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.2 25 0.05 500 25 4$ NO SENSOR PROPOSED 0 0.05 25 - 25 4.05$

497 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast15 61 0.92 1,500 1,373 222$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place15 44 0.66 1500 990 160$ NO SENSOR PROPOSED 0 0.26 383 - 383 61.97$

498 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast16 61 0.98 1,500 1,464 237$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place16 44 0.70 1500 1056 171$ NO SENSOR PROPOSED 0 0.27 408 - 408 66.10$

499 C.T. Barkalow Men's Room4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast2 31 0.06 2,400 149 24$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 25 0.05 2400 120 19$ NO SENSOR PROPOSED 0 0.01 29 - 29 4.67$

500 C.T. Barkalow Men's Room2' Vanity Fxiture with (2) F20 T12 Lamp &

(1) 2L Magnetic Ballast1 60 0.06 2,400 144 23$

Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.11$

501 C.T. Barkalow Women's Room4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast4 31 0.12 2,400 298 48$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 25 0.10 2400 240 39$ NO SENSOR PROPOSED 0 0.02 58 - 58 9.33$

502 C.T. Barkalow Women's Room4' Vanity Fxiture with (2) F32 T8 Lamps &

(1) 2L Electronic Ballast1 61 0.06 2,400 146 24$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.61$

503 C.T. Barkalow Prep Room8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast9 110 0.99 1,500 1,485 241$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place9 84 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.23 351 - 351 56.86$

504 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast12 110 1.32 1,500 1,980 321$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 84 1.01 1500 1512 245$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

505 C.T. Barkalow Prep Room4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast2 50 0.10 1,500 150 24$

Re-lamp & Re-ballast existing fixture. Install a 1-Lamp Electronic Low Power Ballast, (1) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.2 25 0.05 1500 75 12$ NO SENSOR PROPOSED 0 0.05 75 - 75 12.15$

506 C.T. Barkalow Park Room4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast2 50 0.10 2,400 240 39$

Re-lamp & Re-ballast existing fixture. Install a 1-Lamp Electronic Low Power Ballast, (1) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.2 25 0.05 2400 120 19$ NO SENSOR PROPOSED 0 0.05 120 - 120 19.44$

507 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast12 110 1.32 1,500 1,980 321$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 84 1.01 1500 1512 245$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

508 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast12 110 1.32 1,500 1,980 321$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 84 1.01 1500 1512 245$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

509 C.T. Barkalow Prep Room4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast2 31 0.06 1,500 93 15$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 25 0.05 1500 75 12$ NO SENSOR PROPOSED 0 0.01 18 - 18 2.92$

510 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast12 110 1.32 1,500 1,980 321$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 84 1.01 1500 1512 245$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

511 C.T. Barkalow Storage4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast1 50 0.05 500 25 4$

Re-lamp & Re-ballast existing fixture. Install a 1-Lamp Electronic Low Power Ballast, (1) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.1 25 0.03 500 13 2$ NO SENSOR PROPOSED 0 0.03 13 - 13 2.03$

512 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast12 110 1.32 1,500 1,980 321$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 84 1.01 1500 1512 245$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

513 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast8 110 0.88 1,500 1,320 214$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place8 84 0.67 1500 1008 163$ NO SENSOR PROPOSED 0 0.21 312 - 312 50.54$

514 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 1,500 366 59$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1500 264 43$ NO SENSOR PROPOSED 0 0.07 102 - 102 16.52$

515 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast8 110 0.88 1,500 1,320 214$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place8 84 0.67 1500 1008 163$ NO SENSOR PROPOSED 0 0.21 312 - 312 50.54$

516 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 1,500 366 59$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1500 264 43$ NO SENSOR PROPOSED 0 0.07 102 - 102 16.52$

517 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast8 110 0.88 1,500 1,320 214$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place8 84 0.67 1500 1008 163$ NO SENSOR PROPOSED 0 0.21 312 - 312 50.54$

518 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 1,500 366 59$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1500 264 43$ NO SENSOR PROPOSED 0 0.07 102 - 102 16.52$

519 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast8 110 0.88 1,500 1,320 214$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place8 84 0.67 1500 1008 163$ NO SENSOR PROPOSED 0 0.21 312 - 312 50.54$

520 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 1,500 366 59$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1500 264 43$ NO SENSOR PROPOSED 0 0.07 102 - 102 16.52$

521 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast8 110 0.88 1,500 1,320 214$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place8 84 0.67 1500 1008 163$ NO SENSOR PROPOSED 0 0.21 312 - 312 50.54$

522 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 1,500 366 59$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1500 264 43$ NO SENSOR PROPOSED 0 0.07 102 - 102 16.52$

523 C.T. Barkalow Custodian4' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast1 50 0.05 1,000 50 8$

Re-lamp & Re-ballast existing fixture. Install a 1-Lamp Electronic Low Power Ballast, (1) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.1 25 0.03 1000 25 4$ NO SENSOR PROPOSED 0 0.03 25 - 25 4.05$

17 of 52

Page 261: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

524 C.T. Barkalow Girls4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast12 31 0.37 2,400 893 145$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 25 0.30 2400 720 117$ NO SENSOR PROPOSED 0 0.07 173 - 173 27.99$

525 C.T. Barkalow Boys4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast11 31 0.34 2,400 818 133$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place11 25 0.28 2400 660 107$ NO SENSOR PROPOSED 0 0.07 158 - 158 25.66$

526 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast8 110 0.88 1,500 1,320 214$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place8 84 0.67 1500 1008 163$ NO SENSOR PROPOSED 0 0.21 312 - 312 50.54$

527 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 1,500 366 59$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1500 264 43$ NO SENSOR PROPOSED 0 0.07 102 - 102 16.52$

528 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast8 110 0.88 1,500 1,320 214$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place8 84 0.67 1500 1008 163$ NO SENSOR PROPOSED 0 0.21 312 - 312 50.54$

529 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 1,500 366 59$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1500 264 43$ NO SENSOR PROPOSED 0 0.07 102 - 102 16.52$

530 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast8 110 0.88 1,500 1,320 214$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place8 84 0.67 1500 1008 163$ NO SENSOR PROPOSED 0 0.21 312 - 312 50.54$

531 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 1,500 366 59$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1500 264 43$ NO SENSOR PROPOSED 0 0.07 102 - 102 16.52$

532 C.T. Barkalow Class8' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast8 110 0.88 1,500 1,320 214$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place8 84 0.67 1500 1008 163$ NO SENSOR PROPOSED 0 0.21 312 - 312 50.54$

533 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 1,500 366 59$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1500 264 43$ NO SENSOR PROPOSED 0 0.07 102 - 102 16.52$

534 C.T. Barkalow Computer Lab2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

535 C.T. Barkalow Library2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

42 110 4.62 2,400 11,088 1,796$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

42 84 3.53 2400 8467 1,372$ NO SENSOR PROPOSED 0 1.09 2,621 - 2,621 424.57$

536 C.T. Barkalow Library2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

14 61 0.85 2,400 2,050 332$ No Work Proposed 0 61 0.85 2400 2050 332$ NO SENSOR PROPOSED 0 - - - - -$

537 C.T. Barkalow Work Room2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 2,400 1,056 171$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 2400 806 131$ NO SENSOR PROPOSED 0 0.10 250 - 250 40.44$

538 C.T. Barkalow Librarian2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 86$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 2400 403 65$ NO SENSOR PROPOSED 0 0.05 125 - 125 20.22$

539 C.T. Barkalow Audio/Visual2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 107$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 1500 504 82$ NO SENSOR PROPOSED 0 0.10 156 - 156 25.27$

540 C.T. Barkalow Showcase4' Strip Fxiture with (2) F32 T8 Lamps &

(1) 2L Electronic Ballast2 61 0.12 2,400 293 47$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.22$

541 C.T. Barkalow Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast16 61 0.98 1,500 1,464 237$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place16 44 0.70 1500 1056 171$ NO SENSOR PROPOSED 0 0.27 408 - 408 66.10$

542 C.T. Barkalow Girls1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 47$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.22$

543 C.T. Barkalow Girls4' Vanity Fxiture with (2) F32 T8 Lamps &

(1) 2L Electronic Ballast1 61 0.06 2,400 146 24$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.61$

544 C.T. Barkalow Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

545 C.T. Barkalow Custodian4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 1,000 61 10$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.75$

546 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

547 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

548 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

549 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

550 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 89 1.42 1,500 2,136 346$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 63 1.01 1500 1512 245$ NO SENSOR PROPOSED 0 0.42 624 - 624 101.09$

551 C.T. Barkalow Prep Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,500 534 87$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 1500 378 61$ NO SENSOR PROPOSED 0 0.10 156 - 156 25.27$

18 of 52

Page 262: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

552 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 89 1.42 1,500 2,136 346$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 63 1.01 1500 1512 245$ NO SENSOR PROPOSED 0 0.42 624 - 624 101.09$

553 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 89 1.42 1,500 2,136 346$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 63 1.01 1500 1512 245$ NO SENSOR PROPOSED 0 0.42 624 - 624 101.09$

554 C.T. Barkalow Electrical Room4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast6 61 0.37 1,000 366 59$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place6 44 0.26 1000 264 43$ NO SENSOR PROPOSED 0 0.10 102 - 102 16.52$

555 C.T. Barkalow Electrical Room Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

556 C.T. Barkalow Faculty Bath2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

557 C.T. Barkalow Faculty Bath Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

558 C.T. Barkalow Faculty Women2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

559 C.T. Barkalow Faculty Women Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

560 C.T. Barkalow Faculty Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

10 89 0.89 2,400 2,136 346$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 2400 1512 245$ NO SENSOR PROPOSED 0 0.26 624 - 624 101.09$

561 C.T. Barkalow CafeteriaHigh Bay Fixture with (1) 400w Metal

Halide Lamp and (1) Magnetic HID Ballast18 445 8.01 3,640 29,156 4,723$

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

18 234 4.21 3640 15332 2,484$ NO SENSOR PROPOSED 0 3.80 13,825 - 13,825 2,239.60$

562 C.T. Barkalow Cafeteria 250w Quartz 6 250 1.50 3,640 5,460 885$ No Work Proposed 0 250 1.50 3640 5460 885$ NO SENSOR PROPOSED 0 - - - - -$

563 C.T. Barkalow Kitchen Storage4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast4 61 0.24 500 122 20$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 500 88 14$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.51$

564 C.T. Barkalow Kitchen Storage2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 500 89 14$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 500 63 10$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.21$

565 C.T. Barkalow Kitchen4' Vapor & Moisture Resistant Fixture w/

(2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

32 61 1.95 2,400 4,685 759$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

32 44 1.41 2400 3379 547$ NO SENSOR PROPOSED 0 0.54 1,306 - 1,306 211.51$

566 C.T. Barkalow Kitchen 100w Incandescent S/I 6 100 0.60 2,400 1,440 233$ Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

6 23 0.14 2400 331 54$ NO SENSOR PROPOSED 0 0.46 1,109 - 1,109 179.63$

567 C.T. Barkalow Kitchen Recessed Can Can w/ (2) 13w CF PL 2 26 0.05 2,400 125 20$ No Work Proposed 0 26 0.05 2400 125 20$ NO SENSOR PROPOSED 0 - - - - -$

568 C.T. Barkalow Locker4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 2,400 146 24$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.61$

569 C.T. Barkalow Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

570 C.T. Barkalow Bathroom2' Vanity Fixture with (2) F17 T8 Lamps &

(1) 2-Light Electronic Ballast1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - -$

571 C.T. Barkalow Cafeteria Storage4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast5 61 0.31 500 153 25$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place5 44 0.22 500 110 18$ NO SENSOR PROPOSED 0 0.09 43 - 43 6.89$

572 C.T. Barkalow HW Heater4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast2 61 0.12 2,400 293 47$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.22$

573 C.T. Barkalow Art Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

20 89 1.78 1,500 2,670 433$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

20 63 1.26 1500 1890 306$ NO SENSOR PROPOSED 0 0.52 780 - 780 126.36$

574 C.T. Barkalow Sprinkler Valve2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,000 356 58$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 1000 252 41$ NO SENSOR PROPOSED 0 0.10 104 - 104 16.85$

575 C.T. Barkalow Gym High Bay Fixture with (8) 42w Triple Tube PL Fluorescent Lamps

24 336 8.06 2,400 19,354 3,135$ No Work Proposed 0 336 8.06 2400 19354 3,135$ NO SENSOR PROPOSED 0 - - - - -$

576 C.T. Barkalow Gym Exit Sign w/ 2w LED 4 2 0.01 8,760 70 11$ No Work Proposed 0 2 0.01 8760 70 11$ NO SENSOR PROPOSED 0 - - - - -$

577 C.T. Barkalow StorageIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast3 61 0.18 500 92 15$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.13$

578 C.T. Barkalow Office2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 47$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.22$

579 C.T. Barkalow Electrical2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,000 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1000 88 14$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.51$

580 C.T. Barkalow Stairs4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast5 61 0.31 3,640 1,110 180$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place5 44 0.22 3640 801 130$ NO SENSOR PROPOSED 0 0.09 309 - 309 50.12$

581 C.T. Barkalow StorageIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast4 61 0.24 500 122 20$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 500 88 14$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.51$

582 C.T. Barkalow mechanicalIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast4 61 0.24 1,000 244 40$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1000 176 29$ NO SENSOR PROPOSED 0 0.07 68 - 68 11.02$

583 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

19 of 52

Page 263: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

584 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

585 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

586 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

587 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

588 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

589 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

590 C.T. Barkalow Storage4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 500 31 5$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.38$

591 C.T. Barkalow Hub Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.61$

592 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 260$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 184$ NO SENSOR PROPOSED 0 0.31 468 - 468 75.82$

593 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 173$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 122$ NO SENSOR PROPOSED 0 0.21 312 - 312 50.54$

594 C.T. Barkalow Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 173$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 122$ NO SENSOR PROPOSED 0 0.21 312 - 312 50.54$

595 C.T. Barkalow Digital Arts2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 89 1.42 1,500 2,136 346$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 63 1.01 1500 1512 245$ NO SENSOR PROPOSED 0 0.42 624 - 624 101.09$

596 C.T. Barkalow Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

597 C.T. Barkalow Girls2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 95$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 68$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.44$

598 C.T. Barkalow Custodial Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,000 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.75$

599 C.T. Barkalow Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.61$

600 C.T. Barkalow Boys Recessed Can Can w/ (2) 13w CF PL 2 26 0.05 2,400 125 20$ No Work Proposed 0 26 0.05 2400 125 20$ NO SENSOR PROPOSED 0 - - - - -$

601 C.T. Barkalow Boys2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 95$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 68$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.44$

602 C.T. Barkalow Faculty Conference2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 71$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 2400 317 51$ NO SENSOR PROPOSED 0 0.05 122 - 122 19.83$

603 C.T. Barkalow OutsideWall Pack Fixture w/ (1) 50w High

Pressure Sodium Lamp and Magnetic Ballast

33 65 2.15 3,640 7,808 1,265$ No Work Proposed 0 65 2.15 3640 7808 1,265$ NO SENSOR PROPOSED 0 - - - - -$

604 C.T. Barkalow OutsideWall Pack Fixture w/ (1) 100w High

Pressure Sodium Lamp and Magnetic Ballast

43 120 5.16 3,640 18,782 3,043$ No Work Proposed 0 120 5.16 3640 18782 3,043$ NO SENSOR PROPOSED 0 - - - - -$

605 C.T. Barkalow Outside Recessed Can Can w/ (2) 13w CF PL 5 26 0.13 3,640 473 77$ No Work Proposed 0 26 0.13 3640 473 77$ NO SENSOR PROPOSED 0 - - - - -$

606 C.T. Barkalow OutsideParking Lot Fixture Mounted on a Pole w/ (1) 400w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast18 445 8.01 3,640 29,156 4,723$ No Work Proposed 0 445 8.01 3640 29156 4,723$ NO SENSOR PROPOSED 0 - - - - -$

607 C.T. Barkalow Outside 100w Incandescent S/I 1 100 0.10 3,640 364 59$ Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

1 23 0.02 3640 84 14$ NO SENSOR PROPOSED 0 0.08 280 - 280 45.41$

0 39 81804 0 81804 $13,252

608 E.C.L.C. Corridor 3842X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 61 0.31 3,640 1,110 181$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

5 44 0.22 3640 801 130$ NO SENSOR PROPOSED 0 0.09 309 - 309 50.37$

609 E.C.L.C. Corridor 384 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

610 E.C.L.C. Corridor 3852X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 3,640 666 108$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 3640 480 78$ NO SENSOR PROPOSED 0 0.05 186 - 186 30.22$

611 E.C.L.C. Corridor 3854' Strip Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast2 57 0.11 3,640 415 68$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 25 0.05 3640 182 30$ NO SENSOR PROPOSED 0 0.06 233 - 233 37.93$

612 E.C.L.C. Corridor 385 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

613 E.C.L.C. Entrance 2402X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 253$ No Work Proposed 0 61 0.43 3640 1554 253$ NO SENSOR PROPOSED 0 - - - - -$

614 E.C.L.C. Entrance 2404' Strip Fxiture with (2) F32 T8 Lamps &

(1) 2L Electronic Ballast2 61 0.12 3,640 444 72$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 3640 320 52$ NO SENSOR PROPOSED 0 0.03 124 - 124 20.15$

615 E.C.L.C. Entrance 240 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at C.T. Barkalow:

20 of 52

Page 264: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

616 E.C.L.C. Corridor 8802X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 3,640 666 108$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 3640 480 78$ NO SENSOR PROPOSED 0 0.05 186 - 186 30.22$

617 E.C.L.C. Corridor 880 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

618 E.C.L.C. Corridor 11522X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 61 0.55 3,640 1,998 325$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 44 0.40 3640 1441 235$ NO SENSOR PROPOSED 0 0.15 557 - 557 90.67$

619 E.C.L.C. Corridor 1152 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

620 E.C.L.C. Elevator2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - -$

621 E.C.L.C. Corridor 5362X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 89 0.62 3,640 2,268 369$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 63 0.44 3640 1605 261$ NO SENSOR PROPOSED 0 0.18 662 - 662 107.85$

622 E.C.L.C. Corridor 536 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

623 E.C.L.C. Corridor 20442X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

17 89 1.51 3,640 5,507 897$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

17 63 1.07 3640 3898 635$ NO SENSOR PROPOSED 0 0.44 1,609 - 1,609 261.93$

624 E.C.L.C. Corridor 2044 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

625 E.C.L.C. Corridor 3522X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 3,640 972 158$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 3640 688 112$ NO SENSOR PROPOSED 0 0.08 284 - 284 46.22$

626 E.C.L.C. Corridor 352 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

627 E.C.L.C. Stairs 3544' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 3,640 222 36$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 3640 160 26$ NO SENSOR PROPOSED 0 0.02 62 - 62 10.07$

628 E.C.L.C. Stairs 3544' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 3,640 222 36$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 3640 160 26$ NO SENSOR PROPOSED 0 0.02 62 - 62 10.07$

629 E.C.L.C. Elevator2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - -$

630 E.C.L.C. Corridor 5764' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast6 61 0.37 3,640 1,332 217$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place6 44 0.26 3640 961 156$ NO SENSOR PROPOSED 0 0.10 371 - 371 60.44$

631 E.C.L.C. Corridor 576 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

632 E.C.L.C. Stairs 3552X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 145$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 3640 641 104$ NO SENSOR PROPOSED 0 0.07 248 - 248 40.30$

633 E.C.L.C. Stairs 355 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

634 E.C.L.C. Corridor 5124' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast5 61 0.31 3,640 1,110 181$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place5 44 0.22 3640 801 130$ NO SENSOR PROPOSED 0 0.09 309 - 309 50.37$

635 E.C.L.C. Stairs 3564' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast2 61 0.12 3,640 444 72$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 3640 320 52$ NO SENSOR PROPOSED 0 0.03 124 - 124 20.15$

636 E.C.L.C. Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast12 61 0.73 1,500 1,098 179$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 44 0.53 975 515 84$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.20 306 277 583 94.94$

637 E.C.L.C. Class4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast12 61 0.73 1,500 1,098 179$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 44 0.53 975 515 84$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.20 306 277 583 94.94$

638 E.C.L.C. Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast18 89 1.60 1,500 2,403 391$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place18 63 1.13 1500 1701 277$ NO SENSOR PROPOSED 0 0.47 702 - 702 114.29$

639 E.C.L.C. Bathroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.64$

640 E.C.L.C. Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.38$

641 E.C.L.C. Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast18 89 1.60 1,500 2,403 391$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place18 63 1.13 1500 1701 277$ NO SENSOR PROPOSED 0 0.47 702 - 702 114.29$

642 E.C.L.C. Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.64$

643 E.C.L.C. Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.38$

644 E.C.L.C. Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast18 89 1.60 1,500 2,403 391$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place18 63 1.13 1500 1701 277$ NO SENSOR PROPOSED 0 0.47 702 - 702 114.29$

645 E.C.L.C. Bathroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.64$

646 E.C.L.C. Bathroom Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

647 E.C.L.C. Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast16 89 1.42 1,500 2,136 348$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place16 63 1.01 1500 1512 246$ NO SENSOR PROPOSED 0 0.42 624 - 624 101.59$

648 E.C.L.C. Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.64$

21 of 52

Page 265: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

649 E.C.L.C. Girls4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast3 61 0.18 2,400 439 72$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place3 44 0.13 2400 317 52$ NO SENSOR PROPOSED 0 0.05 122 - 122 19.93$

650 E.C.L.C. Faculty Room4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast12 61 0.73 2,400 1,757 286$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 44 0.53 2400 1267 206$ NO SENSOR PROPOSED 0 0.20 490 - 490 79.71$

651 E.C.L.C. Faculty Room4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast2 31 0.06 2,400 149 24$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 25 0.05 2400 120 20$ NO SENSOR PROPOSED 0 0.01 29 - 29 4.69$

652 E.C.L.C. Conference Room 2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

8 110 0.88 2,400 2,112 344$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 2400 1613 263$ NO SENSOR PROPOSED 0 0.21 499 - 499 81.27$

653 E.C.L.C. Conference Room Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

654 E.C.L.C. Boys4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast3 61 0.18 2,400 439 72$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place3 44 0.13 2400 317 52$ NO SENSOR PROPOSED 0 0.05 122 - 122 19.93$

655 E.C.L.C. Electrical2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,000 61 10$ No Work Proposed 0 61 0.06 1000 61 10$ NO SENSOR PROPOSED 0 - - - - -$

656 E.C.L.C. Kitchen2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 129$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 84 0.25 2400 605 98$ NO SENSOR PROPOSED 0 0.08 187 - 187 30.48$

657 E.C.L.C. Hub2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.64$

658 E.C.L.C. Asst. Super/Admin2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

28 89 2.49 2,400 5,981 974$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

28 63 1.76 2400 4234 689$ NO SENSOR PROPOSED 0 0.73 1,747 - 1,747 284.44$

659 E.C.L.C. Asst. Super/Admin Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

660 E.C.L.C. SGI/Copy Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 89 0.45 1,500 668 109$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

5 63 0.32 975 307 50$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.13 195 165 360 58.67$

661 E.C.L.C. Kiln Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1500 66 11$ NO SENSOR PROPOSED 0 0.02 26 - 26 4.15$

662 E.C.L.C. Janitor4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast1 31 0.03 1,000 31 5$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 25 0.03 1000 25 4$ NO SENSOR PROPOSED 0 0.01 6 - 6 0.98$

663 E.C.L.C. Storage 60w. Incandescent S/I 1 60 0.06 500 30 5$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 500 7 1$ NO SENSOR PROPOSED 0 0.05 24 - 24 3.83$

664 E.C.L.C. Faculty Bath2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - -$

665 E.C.L.C. Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 196$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 1500 851 138$ NO SENSOR PROPOSED 0 0.23 351 - 351 57.14$

666 E.C.L.C. Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.38$

667 E.C.L.C. Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 1,500 1,202 196$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 975 553 90$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.23 351 298 649 105.60$

668 E.C.L.C. Class4' Direct/Indirect Fxiture with (3) F32 T8

Lamps & (1) 3L Electronic Ballast18 89 1.60 1,500 2,403 391$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place18 63 1.13 1500 1701 277$ NO SENSOR PROPOSED 0 0.47 702 - 702 114.29$

669 E.C.L.C. Restroom2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.64$

670 E.C.L.C. Class2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 1,500 275 45$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 1500 198 32$ NO SENSOR PROPOSED 0 0.05 77 - 77 12.45$

671 E.C.L.C. Class2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

14 89 1.25 1,500 1,869 304$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 63 0.88 1500 1323 215$ NO SENSOR PROPOSED 0 0.36 546 - 546 88.89$

672 E.C.L.C. Class2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 15$ No Work Proposed 0 61 0.06 1500 92 15$ NO SENSOR PROPOSED 0 - - - - -$

673 E.C.L.C. Restroom2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - -$

674 E.C.L.C. Restroom Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

675 E.C.L.C. Nurse's Office2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 86$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 2400 403 66$ NO SENSOR PROPOSED 0 0.05 125 - 125 20.32$

676 E.C.L.C. Nurse's Office2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

7 34 0.24 2,400 571 93$ No Work Proposed 0 34 0.24 2400 571 93$ NO SENSOR PROPOSED 0 - - - - -$

677 E.C.L.C. Nurse's Office4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast1 31 0.03 2,400 74 12$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 25 0.03 2400 60 10$ NO SENSOR PROPOSED 0 0.01 14 - 14 2.34$

678 E.C.L.C. Nurse's Office 60w. Incandescent S/I 2 60 0.12 2,400 288 47$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 10$ NO SENSOR PROPOSED 0 0.09 226 - 226 36.73$

679 E.C.L.C. Main Office2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 2,400 1,848 301$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 84 0.59 2400 1411 230$ NO SENSOR PROPOSED 0 0.18 437 - 437 71.11$

22 of 52

Page 266: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

680 E.C.L.C. Copy Room2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 2,400 1,056 172$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 2400 806 131$ NO SENSOR PROPOSED 0 0.10 250 - 250 40.63$

681 E.C.L.C. Storage1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.38$

682 E.C.L.C. Building Admin2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

8 110 0.88 2,400 2,112 344$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 2400 1613 263$ NO SENSOR PROPOSED 0 0.21 499 - 499 81.27$

683 E.C.L.C. Bathroom 60w. Incandescent S/I 4 60 0.24 2,400 576 94$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

4 13 0.05 2400 125 20$ NO SENSOR PROPOSED 0 0.19 451 - 451 73.46$

684 E.C.L.C. Bathroom 23w Compact Fluorescent S/I 2 23 0.05 2,400 110 18$ No Work Proposed 0 23 0.05 2400 110 18$ NO SENSOR PROPOSED 0 - - - - -$

685 E.C.L.C. Boys2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 129$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 84 0.25 1560 393 64$

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg.

Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High-(1)

PP-20 per sensor

1 0.08 187 212 399 64.94$

686 E.C.L.C. Girls2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 129$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 84 0.25 1560 393 64$

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg.

Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High-(1)

PP-20 per sensor

1 0.08 187 212 399 64.94$

687 E.C.L.C. Child Study4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast12 61 0.73 1,500 1,098 179$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place12 44 0.53 975 515 84$

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg.

Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High-(1)

PP-20 per sensor

2 0.20 306 277 583 94.94$

688 E.C.L.C. Child Study Team2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

18 89 1.60 1,500 2,403 391$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 63 1.13 1500 1701 277$ NO SENSOR PROPOSED 0 0.47 702 - 702 114.29$

689 E.C.L.C. Office2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.28$

690 E.C.L.C. Director/Super2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 86$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 2400 403 66$ NO SENSOR PROPOSED 0 0.05 125 - 125 20.32$

691 E.C.L.C. Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 209$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 1560 590 96$

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg.

Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High-(1)

PP-20 per sensor

1 0.16 374 318 692 112.64$

692 E.C.L.C. Conference2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 139$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 1560 393 64$ Wall Switch Occupancy Sensor 1 0.10 250 212 461 75.10$

693 E.C.L.C. Storage 60w. Incandescent S/I 2 60 0.12 500 60 10$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 500 13 2$ NO SENSOR PROPOSED 0 0.09 47 - 47 7.65$

694 E.C.L.C. Health Services2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 104$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 1560 295 48$ Wall Switch Occupancy Sensor 1 0.08 187 159 346 56.32$

695 E.C.L.C. Coordinator Office2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 209$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 1560 590 96$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 374 318 692 112.64$

696 E.C.L.C. Elevator B4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast3 61 0.18 2,400 439 72$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place3 44 0.13 2400 317 52$ NO SENSOR PROPOSED 0 0.05 122 - 122 19.93$

697 E.C.L.C. Elevator B2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 2,400 214 35$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 63 0.06 2400 151 25$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.16$

698 E.C.L.C. Paper Storage4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast2 61 0.12 500 61 10$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.77$

699 E.C.L.C. Custodian 60w. Incandescent S/I 1 60 0.06 1,000 60 10$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 1000 13 2$ NO SENSOR PROPOSED 0 0.05 47 - 47 7.65$

700 E.C.L.C. Technology Staff4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast14 61 0.85 1,500 1,281 209$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place14 44 0.62 975 601 98$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

2 0.24 357 323 680 110.77$

701 E.C.L.C. Men's Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.28$

702 E.C.L.C. Storage4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 500 31 5$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.38$

703 E.C.L.C. Business Admin2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 2,400 1,848 301$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 84 0.59 1560 917 149$

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg.

Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High-(1)

PP-20 per sensor

1 0.18 437 494 931 151.52$

704 E.C.L.C. Office2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 86$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 2400 403 66$ NO SENSOR PROPOSED 0 0.05 125 - 125 20.32$

705 E.C.L.C. Kitchen2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 86$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 2400 403 66$ NO SENSOR PROPOSED 0 0.05 125 - 125 20.32$

706 E.C.L.C. Storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.38$

707 E.C.L.C. office 22X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 86$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 2400 403 66$ NO SENSOR PROPOSED 0 0.05 125 - 125 20.32$

23 of 52

Page 267: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

708 E.C.L.C. Office 32X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 2,400 1,171 191$ No Work Proposed 0 61 0.49 2400 1171 191$ NO SENSOR PROPOSED 0 - - - - -$

709 E.C.L.C. conference2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

6 110 0.66 2,400 1,584 258$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 84 0.50 1560 786 128$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 374 423 798 129.88$

710 E.C.L.C. Copy Room2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 86$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 1560 262 43$ Wall Switch Occupancy Sensor 1 0.05 125 141 266 43.29$

711 E.C.L.C. Secretary2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 86$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 2400 403 66$ NO SENSOR PROPOSED 0 0.05 125 - 125 20.32$

712 E.C.L.C. HR Department2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 2,400 1,171 191$ No Work Proposed 0 61 0.49 2400 1171 191$ NO SENSOR PROPOSED 0 - - - - -$

713 E.C.L.C. Secretary2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 129$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 84 0.25 1560 393 64$ Wall Switch Occupancy Sensor 1 0.08 187 212 399 64.94$

714 E.C.L.C. Office2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 129$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 84 0.25 1560 393 64$ Wall Switch Dual Technology

Occupancy Sensor1 0.08 187 212 399 64.94$

715 E.C.L.C. Super of Schools2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 129$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 84 0.25 2400 605 98$ NO SENSOR PROPOSED 0 0.08 187 - 187 30.48$

716 E.C.L.C. Super of Schools2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 2,400 1,056 172$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 2400 806 131$ NO SENSOR PROPOSED 0 0.10 250 - 250 40.63$

717 E.C.L.C. Office 12X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 2,400 792 129$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 84 0.25 1560 393 64$ Wall Switch Dual Technology

Occupancy Sensor1 0.08 187 212 399 64.94$

718 E.C.L.C. Office 22X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

13 61 0.79 2,400 1,903 310$ No Work Proposed 0 61 0.79 2400 1903 310$ NO SENSOR PROPOSED 0 - - - - -$

719 E.C.L.C. Restroom2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - -$

720 E.C.L.C. Women's Room2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.28$

721 E.C.L.C. Conference2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

9 110 0.99 2,400 2,376 387$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 84 0.76 2400 1814 295$ NO SENSOR PROPOSED 0 0.23 562 - 562 91.43$

722 E.C.L.C. Closet2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ No Work Proposed 0 61 0.06 500 31 5$ NO SENSOR PROPOSED 0 - - - - -$

723 E.C.L.C. storage2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.38$

724 E.C.L.C. storage 75w. Incandescent S/I 6 75 0.45 500 225 37$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

6 13 0.08 500 39 6$ NO SENSOR PROPOSED 0 0.37 186 - 186 30.28$

725 E.C.L.C. Meeting Room2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

9 110 0.99 2,400 2,376 387$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 84 0.76 2400 1814 295$ NO SENSOR PROPOSED 0 0.23 562 - 562 91.43$

726 E.C.L.C. Meeting Room 75w. Incandescent S/I 6 75 0.45 2,400 1,080 176$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

6 13 0.08 2400 187 30$ NO SENSOR PROPOSED 0 0.37 893 - 893 145.35$

727 E.C.L.C. GymHigh Bay Fixture with (1) 400w Metal

Halide Lamp and (1) Magnetic HID Ballast8 445 3.56 2,400 8,544 1,391$

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

8 234 1.87 2400 4493 731$ NO SENSOR PROPOSED 0 1.69 4,051 - 4,051 659.54$

728 E.C.L.C. ClosetIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast4 61 0.24 500 122 20$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 500 88 14$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.54$

729 E.C.L.C. Closet Exit Sign w/ 2w LED 5 2 0.01 8,760 88 14$ No Work Proposed 0 2 0.01 8760 88 14$ NO SENSOR PROPOSED 0 - - - - -$

730 E.C.L.C. Stage2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

8 110 0.88 2,400 2,112 344$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 2400 1613 263$ NO SENSOR PROPOSED 0 0.21 499 - 499 81.27$

731 E.C.L.C. Stage4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast4 31 0.12 2,400 298 48$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 25 0.10 2400 240 39$ NO SENSOR PROPOSED 0 0.02 58 - 58 9.38$

732 E.C.L.C. Electrical Room 60w. Incandescent S/I 2 60 0.12 1,000 120 20$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 1000 26 4$ NO SENSOR PROPOSED 0 0.09 94 - 94 15.30$

733 E.C.L.C. Attic 150w Incandescent S/I 9 150 1.35 500 675 110$ Re-lamp with 40w Compact Fluorescent 9 40 0.36 500 180 29$ NO SENSOR PROPOSED 0 0.99 495 - 495 80.59$

734 E.C.L.C. Attic 150w Incandescent S/I 8 150 1.20 500 600 98$ Re-lamp with 40w Compact Fluorescent 8 40 0.32 500 160 26$ NO SENSOR PROPOSED 0 0.88 440 - 440 71.63$

735 E.C.L.C. Stairs to Basement4' Wrap Fxiture with (1) F32 T12 Lamp &

(1) 1L Magnetic Ballast1 31 0.03 3,640 113 18$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 25 0.03 3640 91 15$ NO SENSOR PROPOSED 0 0.01 22 - 22 3.56$

736 E.C.L.C. Stairs to Basement 2' Wrap Fixture w/ (2) F17 T8 Lamps & (1) 2L Electronic Ballast

1 31 0.03 3,640 113 18$ No Work Proposed 0 31 0.03 3640 113 18$ NO SENSOR PROPOSED 0 - - - - -$

737 E.C.L.C. Computer Storage4' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast14 110 1.54 500 770 125$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place14 84 1.18 500 588 96$ NO SENSOR PROPOSED 0 0.36 182 - 182 29.63$

738 E.C.L.C. Computer Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

739 E.C.L.C. Storage Room #24' Wrap Fxiture with (4) F32 T8 Lamps &

(1) 4L Electronic Ballast4 110 0.44 500 220 36$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 84 0.34 500 168 27$ NO SENSOR PROPOSED 0 0.10 52 - 52 8.47$

24 of 52

Page 268: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

740 E.C.L.C. Storage Room #24' Wrap Fixture w/ (1) F34 Econo-Watt

T12 Lamp & (1) 1-Light Magnetic Ballast2 50 0.10 500 50 8$

Re-lamp & Re-ballast existing fixture. Install a 1-Lamp Electronic Low Power Ballast, (1) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.2 25 0.05 500 25 4$ NO SENSOR PROPOSED 0 0.05 25 - 25 4.07$

741 E.C.L.C. Electrical Room4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast2 61 0.12 1,000 122 20$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 1000 88 14$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.54$

742 E.C.L.C. Crawlspace 100w Incandescent S/I 8 100 0.80 1,000 800 130$ Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

8 23 0.18 1000 184 30$ NO SENSOR PROPOSED 0 0.62 616 - 616 100.28$

743 E.C.L.C. Storage Room #34' Wrap Fixture w/ (2) F34 Econo-Watt

T12 Lamps & (1) 2-Light Magnetic Ballast2 80 0.16 500 80 13$

Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Low Power Ballast, (2) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.07 36 - 36 5.86$

744 E.C.L.C. Storage Room #4 100w Incandescent S/I 1 100 0.10 500 50 8$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 1-Lamp Electronic Normal Power Ballast, Reflector

and (1) 4' 28W T8 Energy Saving Lamp.

1 28 0.03 500 14 2$ NO SENSOR PROPOSED 0 0.07 36 - 36 5.86$

745 E.C.L.C. head Custodian1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 95$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 69$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.57$

746 E.C.L.C. head CustodianIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast1 61 0.06 2,400 146 24$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.64$

747 E.C.L.C. Boiler RoomIndustrial Hood 4' Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast4 61 0.24 1,000 244 40$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place4 44 0.18 1000 176 29$ NO SENSOR PROPOSED 0 0.07 68 - 68 11.07$

748 E.C.L.C. Boiler Room4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast2 61 0.12 1,000 122 20$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 1000 88 14$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.54$

749 E.C.L.C. Old Lunch Room2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

14 89 1.25 2,400 2,990 487$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 63 0.88 2400 2117 345$ NO SENSOR PROPOSED 0 0.36 874 - 874 142.22$

750 E.C.L.C. Old Lunch Room2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ No Work Proposed 0 61 0.12 2400 293 48$ NO SENSOR PROPOSED 0 - - - - -$

751 E.C.L.C. Old Lunch Room4' Vanity Fxiture with (2) F32 T8 Lamps &

(1) 2L Electronic Ballast8 61 0.49 2,400 1,171 191$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place8 44 0.35 2400 845 138$ NO SENSOR PROPOSED 0 0.14 326 - 326 53.14$

752 E.C.L.C. Kitchen2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - -$

753 E.C.L.C. Kitchen2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 313$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 2400 1361 222$ NO SENSOR PROPOSED 0 0.23 562 - 562 91.43$

754 E.C.L.C. Electrical Panel4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast2 61 0.12 1,000 122 20$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place2 44 0.09 1000 88 14$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.54$

755 E.C.L.C. School Services2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 2,400 1,848 301$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 84 0.59 2400 1411 230$ NO SENSOR PROPOSED 0 0.18 437 - 437 71.11$

756 E.C.L.C. Electrical Room4' Wrap Fixture w/ (2) F32 T8 Lamps &

(1) 2-Light Electronic Ballast1 61 0.06 1,000 61 10$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.77$

757 E.C.L.C. OutsideWall Pack Fixture w/ (1) 50w High

Pressure Sodium Lamp and Magnetic Ballast

19 65 1.24 3,640 4,495 732$ No Work Proposed 0 65 1.24 3640 4495 732$ NO SENSOR PROPOSED 0 - - - - -$

758 E.C.L.C. OutsideWall Pack Fixture w/ (1) 100w High

Pressure Sodium Lamp and Magnetic Ballast

7 120 0.84 3,640 3,058 498$ No Work Proposed 0 120 0.84 3640 3058 498$ NO SENSOR PROPOSED 0 - - - - -$

759 E.C.L.C. Outside 60w. Incandescent S/I 5 60 0.30 3,640 1,092 178$ Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

5 13 0.07 3640 237 39$ NO SENSOR PROPOSED 0 0.24 855 - 855 139.26$

760 E.C.L.C. OutsideParking Lot Fixture Mounted on a Pole w/ (1) 400w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast5 445 2.23 3,640 8,099 1,319$ No Work Proposed 0 445 2.23 3640 8099 1,319$ NO SENSOR PROPOSED 0 - - - - -$

20 18 34757 4740 39497 $6,430

761M.W.

ErricksonCorridor 4-8

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 3,640 666 111$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 3640 480 80$ NO SENSOR PROPOSED 0 0.05 186 - 186 30.89$

762 M.W. Errickson

Corridor 4-8 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

763M.W.

ErricksonCorridor 10-11

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 61 0.73 3,640 2,664 443$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 3640 1922 320$ NO SENSOR PROPOSED 0 0.20 743 - 743 123.56$

764 M.W. Errickson

Corridor 10-11 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

765M.W.

ErricksonCorridor 31

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 148$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 3640 641 107$ NO SENSOR PROPOSED 0 0.07 248 - 248 41.19$

766M.W.

ErricksonCorridor Main

2X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballast

3 220 0.66 3,640 2,402 400$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 84 0.50 3640 1835 305$ NO SENSOR PROPOSED 0 0.16 568 - 568 94.49$

767 M.W. Errickson

Corridor Main Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 3,640 379 63$ No Work Proposed 0 26 0.10 3640 379 63$ NO SENSOR PROPOSED 0 - - - - -$

768 M.W. Errickson

Corridor Main Recessed Can Can w/ (2) 13w CF PL 4 26 0.10 3,640 379 63$ No Work Proposed 0 26 0.10 3640 379 63$ NO SENSOR PROPOSED 0 - - - - -$

769M.W.

ErricksonCorridor 39-40

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 61 0.98 3,640 3,553 591$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 44 0.70 3640 2563 426$ NO SENSOR PROPOSED 0 0.27 990 - 990 164.75$

770 M.W. Errickson

Corridor 39-40 Exit Sign w/ 2w LED 5 2 0.01 8,760 88 15$ No Work Proposed 0 2 0.01 8760 88 15$ NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at the ECLC:

25 of 52

Page 269: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

771 M.W. Errickson

Corridor 39-40 Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 3,640 95 16$ No Work Proposed 0 26 0.03 3640 95 16$ NO SENSOR PROPOSED 0 - - - - -$

772M.W.

ErricksonCorridor 44-50

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

23 61 1.40 3,640 5,107 850$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

23 44 1.01 3640 3684 613$ NO SENSOR PROPOSED 0 0.39 1,423 - 1,423 236.83$

773 M.W. Errickson

Corridor 44-50 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

774M.W.

ErricksonCorridor 81-85

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 259$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 44 0.31 3640 1121 187$ NO SENSOR PROPOSED 0 0.12 433 - 433 72.08$

775 M.W. Errickson

Corridor 81-85 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

776M.W.

ErricksonCorridor 67-72

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

17 61 1.04 3,640 3,775 628$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

17 44 0.75 3640 2723 453$ NO SENSOR PROPOSED 0 0.29 1,052 - 1,052 175.05$

777 M.W. Errickson

Corridor 67-72 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

778M.W.

ErricksonKitchen

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 2,400 3,168 527$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 2400 2419 403$ NO SENSOR PROPOSED 0 0.31 749 - 749 124.60$

779M.W.

ErricksonKitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 73$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 2400 317 53$ NO SENSOR PROPOSED 0 0.05 122 - 122 20.37$

780M.W.

ErricksonCafeteria

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

47 110 5.17 3,640 18,819 3,131$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

47 84 3.95 3640 14371 2,391$ NO SENSOR PROPOSED 0 1.22 4,448 - 4,448 740.16$

781 M.W. Errickson

Cafeteria Exit Sign w/ 2w LED 4 2 0.01 8,760 70 12$ No Work Proposed 0 2 0.01 8760 70 12$ NO SENSOR PROPOSED 0 - - - - -$

782M.W.

ErricksonStage

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

22 110 2.42 2,400 5,808 966$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

22 84 1.85 2400 4435 738$ NO SENSOR PROPOSED 0 0.57 1,373 - 1,373 228.43$

783 M.W. Errickson

Stage Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

784M.W.

ErricksonGym

Industrial Hood 8' Fxiture with (2) F32 T8 Lamps & (2) 2L Electronic Ballast

56 61 3.42 2,400 8,198 1,364$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

56 44 2.46 2400 5914 984$ NO SENSOR PROPOSED 0 0.95 2,285 - 2,285 380.19$

785 M.W. Errickson

Gym Exit Sign w/ 2w LED 4 2 0.01 8,760 70 12$ No Work Proposed 0 2 0.01 8760 70 12$ NO SENSOR PROPOSED 0 - - - - -$

786M.W.

ErricksonPrincipal

4X4 recessed troffer with (6) F32 T8 Lamps & (2) 3-Light Electronic ballasts

1 178 0.18 2,400 427 71$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 1560 197 33$ Wall Switch Dual Technology

Occupancy Sensor1 0.05 125 106 231 38.38$

787M.W.

ErricksonNurse's Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 2400 907 151$ NO SENSOR PROPOSED 0 0.16 374 - 374 62.30$

788 M.W. Errickson

Nurse's Office Recessed Can Can w/ (2) 13w CF PL 2 26 0.05 2,400 125 21$ No Work Proposed 0 26 0.05 2400 125 21$ NO SENSOR PROPOSED 0 - - - - -$

789 M.W. Errickson

Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

790M.W.

ErricksonBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 14$ No Work Proposed 0 34 0.03 2400 82 14$ NO SENSOR PROPOSED 0 - - - - -$

791M.W.

ErricksonBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 14$ No Work Proposed 0 34 0.03 2400 82 14$ NO SENSOR PROPOSED 0 - - - - -$

792 M.W. Errickson

Bathroom Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

793M.W.

ErricksonWork Room

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 88$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 2400 403 67$ NO SENSOR PROPOSED 0 0.05 125 - 125 20.77$

794 M.W. Errickson

Corridor Recessed Can Can w/ (2) 13w CF PL 2 26 0.05 3,640 189 31$ No Work Proposed 0 26 0.05 3640 189 31$ NO SENSOR PROPOSED 0 - - - - -$

795M.W.

ErricksonMain Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 320$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 2400 1361 226$ NO SENSOR PROPOSED 0 0.23 562 - 562 93.45$

796M.W.

ErricksonLobby (1-8)

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

8 220 1.76 3,640 6,406 1,066$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 84 1.34 3640 4892 814$ NO SENSOR PROPOSED 0 0.42 1,514 - 1,514 251.97$

797M.W.

ErricksonLobby (1-8)

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 3,640 1,602 267$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 3640 1223 204$ NO SENSOR PROPOSED 0 0.10 379 - 379 62.99$

798M.W.

ErricksonLobby (1-8)

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 74$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 3640 320 53$ NO SENSOR PROPOSED 0 0.03 124 - 124 20.59$

799M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

800M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

801M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

802M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

26 of 52

Page 270: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

803M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

804M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

805M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

806M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

807M.W.

ErricksonBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.79$

808M.W.

ErricksonBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 97$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 70$ NO SENSOR PROPOSED 0 0.07 163 - 163 27.16$

809M.W.

ErricksonCustodian 1

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 1,000 62 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 25 0.05 1000 50 8$ NO SENSOR PROPOSED 0 0.01 12 - 12 2.00$

810 M.W. Errickson

Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

811M.W.

ErricksonGirls

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 97$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 70$ NO SENSOR PROPOSED 0 0.07 163 - 163 27.16$

812M.W.

ErricksonStorage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 500 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 500 88 15$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.66$

813M.W.

ErricksonMechanical

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1000 88 15$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.66$

814M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 975 737 123$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.23 351 397 748 124.45$

815M.W.

ErricksonComputer

4' Fxiture with Egg Style Lens with (2) F32 T8 Lamps & (1) 2L Electonic Ballast

5 61 0.31 1,500 458 76$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

5 54 0.27 975 263 44$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

2 0.04 53 142 194 32.32$

816M.W.

ErricksonComputer

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

817M.W.

ErricksonLibrary

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

8 110 0.88 2,400 2,112 351$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 2400 1613 268$ NO SENSOR PROPOSED 0 0.21 499 - 499 83.07$

818M.W.

ErricksonLibrary

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts27 110 2.97 2,400 7,128 1,186$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

27 84 2.27 2400 5443 906$ NO SENSOR PROPOSED 0 0.70 1,685 - 1,685 280.35$

819M.W.

ErricksonAudio Visual

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 110$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 1500 504 84$ NO SENSOR PROPOSED 0 0.10 156 - 156 25.96$

820M.W.

ErricksonMedia Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 142$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 2400 605 101$ NO SENSOR PROPOSED 0 0.10 250 - 250 41.53$

821M.W.

ErricksonCST

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts4 110 0.44 2,400 1,056 176$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

4 84 0.34 2400 806 134$ NO SENSOR PROPOSED 0 0.10 250 - 250 41.53$

822M.W.

ErricksonSpeech

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 1,500 495 82$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 84 0.25 975 246 41$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.08 117 132 249 41.48$

823M.W.

ErricksonArt Class

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts6 110 0.66 1,500 990 165$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

6 84 0.50 1500 756 126$ NO SENSOR PROPOSED 0 0.16 234 - 234 38.94$

824M.W.

ErricksonArt Class

4' Fxiture with Egg Style Lens with (2) F32 T8 Lamps & (1) 2L Electonic Ballast

5 61 0.31 1,500 458 76$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 2-

Lamp Electronic Normal Power Ballast, Miro4 Reflector, and (2) 4' 28w T8 Energy Saving

Lamps

5 54 0.27 1500 405 67$ NO SENSOR PROPOSED 0 0.04 53 - 53 8.74$

825M.W.

ErricksonKiln

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 30$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1500 132 22$ NO SENSOR PROPOSED 0 0.03 51 - 51 8.49$

826M.W.

ErricksonArt Storage

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts2 110 0.22 500 110 18$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

2 84 0.17 500 84 14$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.33$

827M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

27 of 52

Page 271: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

828M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

829M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

830M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

831M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

832M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

833M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

834M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

835M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts4 110 0.44 1,500 660 110$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

4 84 0.34 1500 504 84$ NO SENSOR PROPOSED 0 0.10 156 - 156 25.96$

836M.W.

ErricksonGirls

4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

5 57 0.29 2,400 684 114$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

5 25 0.13 2400 300 50$ NO SENSOR PROPOSED 0 0.16 384 - 384 63.90$

837 M.W. Errickson

Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

838M.W.

ErricksonCustodian

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 1,000 183 30$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 650 86 14$ Wall Switch Occupancy Sensor 1 0.05 51 46 97 16.17$

839M.W.

ErricksonBoys

4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

5 57 0.29 2,400 684 114$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

5 25 0.13 2400 300 50$ NO SENSOR PROPOSED 0 0.16 384 - 384 63.90$

840 M.W. Errickson

Boys Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

841M.W.

ErricksonSupervisor

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 2,400 586 97$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1560 275 46$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.07 163 148 311 51.76$

842M.W.

ErricksonStorage 10

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

843 M.W. Errickson

Attic 23w Compact Fluorescent S/I 9 23 0.21 500 104 17$ No Work Proposed 0 23 0.21 500 104 17$ NO SENSOR PROPOSED 0 - - - - -$

844M.W.

ErricksonElevator

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 49$ No Work Proposed 0 61 0.12 2400 293 49$ NO SENSOR PROPOSED 0 - - - - -$

845M.W.

ErricksonElevator

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 2,400 264 44$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 2400 202 34$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.38$

846M.W.

ErricksonOffice

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 88$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 1560 262 44$ Wall Switch Occupancy Sensor 1 0.05 125 141 266 44.25$

847M.W.

ErricksonSpeech

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

10 110 1.10 1,500 1,650 275$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 84 0.84 975 819 136$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

2 0.26 390 441 831 138.28$

848M.W.

ErricksonStorage 7

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

849M.W.

ErricksonStorage 7

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

850 M.W. Errickson

Storage 150w Incandescent S/I 3 150 0.45 500 225 37$ Re-lamp with 40w Compact Fluorescent 3 40 0.12 500 60 10$ NO SENSOR PROPOSED 0 0.33 165 - 165 27.46$

851M.W.

ErricksonSGI

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 110$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 975 328 55$ Wall Switch Occupancy Sensor 1 0.10 156 176 332 55.31$

852M.W.

ErricksonStorage 5

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 500 55 9$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 500 42 7$ NO SENSOR PROPOSED 0 0.03 13 - 13 2.16$

853M.W.

ErricksonKitchen

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 2,400 3,168 527$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 2400 2419 403$ NO SENSOR PROPOSED 0 0.31 749 - 749 124.60$

854M.W.

ErricksonOffice

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 49$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.58$

855M.W.

ErricksonChair Storage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

28 of 52

Page 272: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

856M.W.

ErricksonOutside Storage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

857M.W.

ErricksonReceiving Room

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 2,400 298 50$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 25 0.10 2400 240 40$ NO SENSOR PROPOSED 0 0.02 58 - 58 9.58$

858M.W.

ErricksonEmergency Generator

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 2,400 298 50$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 25 0.10 2400 240 40$ NO SENSOR PROPOSED 0 0.02 58 - 58 9.58$

859M.W.

ErricksonPanel Room

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 1,000 124 21$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 25 0.10 1000 100 17$ NO SENSOR PROPOSED 0 0.02 24 - 24 3.99$

860M.W.

ErricksonStorage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 500 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 500 88 15$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.66$

861M.W.

ErricksonOutside Storage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 500 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.83$

862M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

863M.W.

ErricksonLobby

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 3,640 400 67$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 3640 306 51$ NO SENSOR PROPOSED 0 0.03 95 - 95 15.75$

864M.W.

ErricksonCoat Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1500 66 11$ NO SENSOR PROPOSED 0 0.02 26 - 26 4.24$

865 M.W. Errickson

Coat Room 23w Compact Fluorescent S/I 2 23 0.05 1,500 69 11$ No Work Proposed 0 23 0.05 1500 69 11$ NO SENSOR PROPOSED 0 - - - - -$

866M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

867 M.W. Errickson

Toilet 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 9$ No Work Proposed 0 23 0.02 2400 55 9$ NO SENSOR PROPOSED 0 - - - - -$

868M.W.

ErricksonStorage

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 500 45 7$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 63 0.06 500 32 5$ NO SENSOR PROPOSED 0 0.03 13 - 13 2.16$

869M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts6 110 0.66 1,500 990 165$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

6 84 0.50 1500 756 126$ NO SENSOR PROPOSED 0 0.16 234 - 234 38.94$

870M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 1,500 495 82$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 84 0.25 1500 378 63$ NO SENSOR PROPOSED 0 0.08 117 - 117 19.47$

871M.W.

ErricksonStorage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 500 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.83$

872M.W.

ErricksonToilet

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - -$

873M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

874M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

875M.W.

ErricksonBathroom

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - -$

876M.W.

ErricksonLobby

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 3,640 400 67$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 3640 306 51$ NO SENSOR PROPOSED 0 0.03 95 - 95 15.75$

877M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

878M.W.

ErricksonStorage Alcove

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 500 55 9$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 500 42 7$ NO SENSOR PROPOSED 0 0.03 13 - 13 2.16$

879M.W.

ErricksonStorage Alcove

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 500 55 9$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 500 42 7$ NO SENSOR PROPOSED 0 0.03 13 - 13 2.16$

880M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

881 M.W. Errickson

Bathroom 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 9$ No Work Proposed 0 23 0.02 2400 55 9$ NO SENSOR PROPOSED 0 - - - - -$

882M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

883M.W.

ErricksonCoat Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1500 66 11$ NO SENSOR PROPOSED 0 0.02 26 - 26 4.24$

29 of 52

Page 273: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

884M.W.

ErricksonToilet 75w. Incandescent S/I 1 75 0.08 2,400 180 30$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 2400 31 5$ NO SENSOR PROPOSED 0 0.06 149 - 149 24.76$

885M.W.

ErricksonClass

8' Fixture with Egg Style Metal Lens w/ (4) F32 T8 Lamps & (1) 4-Light Electronic

Ballasts9 110 0.99 1,500 1,485 247$

Remove and Replace Existing Fixture With a New Industrial Fixture Containing a 4-Lamp Low

Powered Electronic T8 Ballast, and (4) 4' T8 F28 Energy Saving Lamps, and Miro4 Reflector.

9 84 0.76 1500 1134 189$ NO SENSOR PROPOSED 0 0.23 351 - 351 58.41$

886M.W.

ErricksonStorage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 500 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 500 88 15$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.66$

887M.W.

ErricksonClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 178$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 126$ NO SENSOR PROPOSED 0 0.21 312 - 312 51.92$

888M.W.

ErricksonClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 154$ NO SENSOR PROPOSED 0 0.24 357 - 357 59.40$

889M.W.

ErricksonBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.79$

890M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

891 M.W. Errickson

Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

892M.W.

ErricksonClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 178$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 126$ NO SENSOR PROPOSED 0 0.21 312 - 312 51.92$

893M.W.

ErricksonClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 154$ NO SENSOR PROPOSED 0 0.24 357 - 357 59.40$

894M.W.

ErricksonBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.79$

895M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

896 M.W. Errickson

Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

897M.W.

ErricksonStorage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.24$

898M.W.

ErricksonClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 178$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 126$ NO SENSOR PROPOSED 0 0.21 312 - 312 51.92$

899M.W.

ErricksonClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 154$ NO SENSOR PROPOSED 0 0.24 357 - 357 59.40$

900M.W.

ErricksonBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.79$

901M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

902 M.W. Errickson

Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

903M.W.

ErricksonMPR Recessed Can Can w/ (2) 57w CF PL 13 114 1.48 2,400 3,557 592$ No Work Proposed 0 114 1.48 2400 3557 592$ NO SENSOR PROPOSED 0 - - - - -$

904M.W.

ErricksonStorage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

905M.W.

ErricksonRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.79$

906M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

907M.W.

ErricksonKitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 97$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 70$ NO SENSOR PROPOSED 0 0.07 163 - 163 27.16$

908M.W.

ErricksonKitchen Storage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

909 M.W. Errickson

Cafeteria Recessed Can Can w/ (2) 57w CF PL 12 114 1.37 3,640 4,980 829$ No Work Proposed 0 114 1.37 3640 4980 829$ NO SENSOR PROPOSED 0 - - - - -$

910 M.W. Errickson

Cafeteria Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

911M.W.

ErricksonRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.79$

912M.W.

ErricksonCustodian

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 1,000 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 650 29 5$ Wall Switch Occupancy Sensor 1 0.02 17 15 32 5.39$

913M.W.

ErricksonClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 178$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 126$ NO SENSOR PROPOSED 0 0.21 312 - 312 51.92$

30 of 52

Page 274: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

914M.W.

ErricksonClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 154$ NO SENSOR PROPOSED 0 0.24 357 - 357 59.40$

915M.W.

ErricksonBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.79$

916M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

917 M.W. Errickson

Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

918M.W.

ErricksonClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 178$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 126$ NO SENSOR PROPOSED 0 0.21 312 - 312 51.92$

919M.W.

ErricksonClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 154$ NO SENSOR PROPOSED 0 0.24 357 - 357 59.40$

920M.W.

ErricksonBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.79$

921M.W.

ErricksonStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

922 M.W. Errickson

Storage Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

923M.W.

ErricksonGirls

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 49$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.58$

924 M.W. Errickson

Girls Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

925M.W.

ErricksonCustodian 3

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.83$

926M.W.

ErricksonBoys

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 73$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 2400 317 53$ NO SENSOR PROPOSED 0 0.05 122 - 122 20.37$

927 M.W. Errickson

Boys Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 2,400 62 10$ No Work Proposed 0 26 0.03 2400 62 10$ NO SENSOR PROPOSED 0 - - - - -$

928M.W.

ErricksonMen's Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 49$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.58$

929M.W.

ErricksonMen's Room

2' Vanity Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144 24$ Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2400 82 14$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.38$

930M.W.

ErricksonTeachers Room

4X4 recessed troffer with (6) F32 T8 Lamps & (2) 3-Light Electronic ballasts

4 178 0.71 2,400 1,709 284$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1560 786 131$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 499 423 923 153.51$

931M.W.

ErricksonTeachers Room 60w. Incandescent S/I 2 60 0.12 2,400 288 48$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 10$ NO SENSOR PROPOSED 0 0.09 226 - 226 37.54$

932M.W.

ErricksonTeachers Room 25w. Incandescent S/I A-Lamp 2 25 0.05 2,400 120 20$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 10$ NO SENSOR PROPOSED 0 0.02 58 - 58 9.58$

933M.W.

ErricksonFaculty Work Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 2,400 878 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 2400 634 105$ NO SENSOR PROPOSED 0 0.10 245 - 245 40.73$

934M.W.

ErricksonElectrical Room

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1000 88 15$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.66$

935M.W.

ErricksonStorage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 500 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 500 88 15$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.66$

936M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 329$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 975 983 164$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 529 997 165.93$

937M.W.

ErricksonInstrumental Music

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 1,500 1,155 192$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 84 0.59 975 573 95$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.18 273 309 582 96.79$

938M.W.

ErricksonInstrumental Music

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 15$ No Work Proposed 0 61 0.06 1500 92 15$ NO SENSOR PROPOSED 0 - - - - -$

939M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

11 110 1.21 1,500 1,815 302$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 1500 1512 252$ NO SENSOR PROPOSED 0 0.20 303 - 303 50.42$

940M.W.

ErricksonClass

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 15$ No Work Proposed 0 61 0.06 975 59 10$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 - - 32 32 5.33$

941M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 329$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 975 983 164$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 529 997 165.93$

942M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 329$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 1500 1512 252$ NO SENSOR PROPOSED 0 0.31 468 - 468 77.88$

943M.W.

ErricksonClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 329$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 1500 1512 252$ NO SENSOR PROPOSED 0 0.31 468 - 468 77.88$

944M.W.

ErricksonBoys

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - -$

31 of 52

Page 275: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

945M.W.

ErricksonBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 49$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.58$

946M.W.

ErricksonJanitors Closet

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.41$

947M.W.

ErricksonGirls

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - -$

948M.W.

ErricksonGirls

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 49$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 13.58$

949M.W.

ErricksonOutside

Wall Pack Fixture w/ (1) 50w High Pressure Sodium Lamp and Magnetic

Ballast15 65 0.98 3,640 3,549 591$ No Work Proposed 0 65 0.98 3640 3549 591$ NO SENSOR PROPOSED 0 - - - - -$

950M.W.

ErricksonOutside

Wall Pack Fixture w/ (1) 70w High Pressure Sodium Lamp and Magnetic

Ballast3 92 0.28 3,640 1,005 167$ No Work Proposed 0 92 0.28 3640 1005 167$ NO SENSOR PROPOSED 0 - - - - -$

951M.W.

ErricksonOutside

Wal Pack Fixture with (1) 250w Metal Halide Lamp and (1) Magnetic HID Ballast

15 295 4.43 3,640 16,107 2,680$ No Work Proposed 0 295 4.43 3640 16107 2,680$ NO SENSOR PROPOSED 0 - - - - -$

952M.W.

ErricksonOutside

Wall Pack Fixture with (1) 100w Metal Halide Lamp and (1) Magnetic HID Ballast

15 120 1.80 3,640 6,552 1,090$ No Work Proposed 0 120 1.80 3640 6552 1,090$ NO SENSOR PROPOSED 0 - - - - -$

953M.W.

ErricksonOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 250w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast4 286 1.14 3,640 4,164 693$ No Work Proposed 0 286 1.14 3640 4164 693$ NO SENSOR PROPOSED 0 - - - - -$

17 21 42351 3567 45918 $7,641

954Laura

DonovanCorridor 400-403

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 226$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 3640 961 163$ NO SENSOR PROPOSED 0 0.10 371 - 371 62.93$

955Laura

DonovanCorridor 400-403

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 3,640 400 68$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 3640 306 52$ NO SENSOR PROPOSED 0 0.03 95 - 95 16.04$

956Laura

DonovanCorridor 400-403

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 226$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 3640 961 163$ NO SENSOR PROPOSED 0 0.10 371 - 371 62.93$

957 Laura Donovan

Corridor 400-403 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

958Laura

DonovanCorridor 404-412

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 61 0.73 3,640 2,664 452$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 3640 1922 326$ NO SENSOR PROPOSED 0 0.20 743 - 743 125.86$

959Laura

DonovanCorridor 402-404

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

13 61 0.79 3,640 2,887 489$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

13 44 0.57 3640 2082 353$ NO SENSOR PROPOSED 0 0.22 804 - 804 136.35$

960Laura

DonovanCorridor 402-404

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 75$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 3640 320 54$ NO SENSOR PROPOSED 0 0.03 124 - 124 20.98$

961Laura

DonovanCorridor 402-404 Recessed Can Can w/ (2) 13w CF PL 1 26 0.03 3,640 95 16$ No Work Proposed 0 26 0.03 3640 95 16$ NO SENSOR PROPOSED 0 - - - - -$

962 Laura Donovan

Corridor 402-404 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

963Laura

DonovanCorridor 413-420

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 61 0.73 3,640 2,664 452$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 3640 1922 326$ NO SENSOR PROPOSED 0 0.20 743 - 743 125.86$

964Laura

DonovanCorridor 413-420

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 38$ No Work Proposed 0 61 0.06 3640 222 38$ NO SENSOR PROPOSED 0 - - - - -$

965 Laura Donovan

Corridor 413-420 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

966Laura

DonovanCorridor 412A

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 226$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 3640 961 163$ NO SENSOR PROPOSED 0 0.10 371 - 371 62.93$

967 Laura Donovan

Corridor 412A Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

968Laura

DonovanCorridor Main

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 61 0.67 3,640 2,442 414$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 44 0.48 3640 1762 299$ NO SENSOR PROPOSED 0 0.19 681 - 681 115.38$

969 Laura Donovan

Corridor Main Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

970Laura

DonovanCorridor 421-424

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 61 0.73 3,640 2,664 452$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 3640 1922 326$ NO SENSOR PROPOSED 0 0.20 743 - 743 125.86$

971 Laura Donovan

Corridor 421-424 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

972Laura

DonovanCorridor 432-435

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

10 61 0.61 3,640 2,220 376$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 3640 1602 271$ NO SENSOR PROPOSED 0 0.17 619 - 619 104.89$

973Laura

DonovanCorridor 432-435

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 38$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 3640 160 27$ NO SENSOR PROPOSED 0 0.02 62 - 62 10.49$

974 Laura Donovan

Corridor 432-435 Exit Sign w/ 2w LED 4 2 0.01 8,760 70 12$ No Work Proposed 0 2 0.01 8760 70 12$ NO SENSOR PROPOSED 0 - - - - -$

975Laura

DonovanCorridor 5-8

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 3,640 1,944 329$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 3640 1376 233$ NO SENSOR PROPOSED 0 0.16 568 - 568 96.25$

976Laura

DonovanCorridor 5-8

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

13 61 0.79 3,640 2,887 489$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

13 44 0.57 3640 2082 353$ NO SENSOR PROPOSED 0 0.22 804 - 804 136.35$

977 Laura Donovan

Corridor 5-8 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at M.W. Errickson:

32 of 52

Page 276: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

978Laura

DonovanCorridor 427-430

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 263$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 44 0.31 3640 1121 190$ NO SENSOR PROPOSED 0 0.12 433 - 433 73.42$

979Laura

DonovanCorridor 110-113

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 61 0.37 3,640 1,332 226$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 3640 961 163$ NO SENSOR PROPOSED 0 0.10 371 - 371 62.93$

980Laura

DonovanMedia Center 435

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

46 110 5.06 2,400 12,144 2,058$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

46 84 3.86 2400 9274 1,572$ NO SENSOR PROPOSED 0 1.20 2,870 - 2,870 486.53$

981Laura

DonovanComm. - MC

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 1,500 330 56$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 1500 252 43$ NO SENSOR PROPOSED 0 0.05 78 - 78 13.22$

982 Laura Donovan

Comm. - MC Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

983Laura

DonovanCafeteria

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

45 110 4.95 3,640 18,018 3,054$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

45 84 3.78 3640 13759 2,332$ NO SENSOR PROPOSED 0 1.17 4,259 - 4,259 721.87$

984Laura

DonovanStorage - Caf

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 500 92 16$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.32$

985Laura

DonovanRoom 44 - Caf

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 2,400 264 45$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 2400 202 34$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.58$

986Laura

DonovanKitchen

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

10 110 1.10 2,400 2,640 447$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 84 0.84 2400 2016 342$ NO SENSOR PROPOSED 0 0.26 624 - 624 105.77$

987Laura

DonovanKitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.92$

988 Laura Donovan

Kitchen Exit Sign w/ 2w LED 4 2 0.01 8,760 70 12$ No Work Proposed 0 2 0.01 8760 70 12$ NO SENSOR PROPOSED 0 - - - - -$

989Laura

DonovanGym

High Bay Fixture with (1) 400w Metal Halide Lamp and (1) Magnetic HID Ballast

20 445 8.90 2,400 21,360 3,621$

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

20 234 4.68 2400 11232 1,904$ NO SENSOR PROPOSED 0 4.22 10,128 - 10,128 1,716.70$

990Laura

DonovanStorage - Gym

4' Industrail Hood Fixture with (2) F34 Econo-Watt T12 Lamps & (1) 2L Magnetic

Ballast1 80 0.08 500 40 7$

Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Low Power Ballast, (2) 4' 28w T8

Energy Saving Lamps, New Lamp Sockets.1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.04 18 - 18 3.05$

991 Laura Donovan

Storage - Gym Recessed Can Can w/ (2) 13w CF PL 2 26 0.05 500 26 4$ No Work Proposed 0 26 0.05 500 26 4$ NO SENSOR PROPOSED 0 - - - - -$

992Laura

DonovanOffice - Gym

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 2,400 146 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.92$

993Laura

DonovanBR - Gym

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 14$ No Work Proposed 0 34 0.03 2400 82 14$ NO SENSOR PROPOSED 0 - - - - -$

994Laura

DonovanGym - Stair Recessed Can Can w/ (2) 13w CF PL 3 26 0.08 2,400 187 32$ No Work Proposed 0 26 0.08 2400 187 32$ NO SENSOR PROPOSED 0 - - - - -$

995 Laura Donovan

Gym - Stair Exit Sign w/ (2) 20w Incandescent Lamps 6 40 0.24 8,760 2,102 356$ Remove and Replace existing exit sign with a new LED exit sign.

6 2 0.01 8760 105 18$ NO SENSOR PROPOSED 0 0.23 1,997 - 1,997 338.54$

996Laura

DonovanStage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

30 61 1.83 2,400 4,392 744$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

30 44 1.32 2400 3168 537$ NO SENSOR PROPOSED 0 0.51 1,224 - 1,224 207.47$

997Laura

DonovanStage

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

4 31 0.12 2,400 298 50$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 25 0.10 2400 240 41$ NO SENSOR PROPOSED 0 0.02 58 - 58 9.76$

998 Laura Donovan

Stage Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

999Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

11 110 1.21 1,500 1,815 308$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 84 0.92 975 901 153$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.29 429 485 914 154.94$

1000Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1001Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192 33$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 11$ NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1002Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 975 655 111$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 312 353 665 112.68$

1003Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1004Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 975 655 111$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 312 353 665 112.68$

1005Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1006Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 975 655 111$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 312 353 665 112.68$

1007Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1008Laura

DonovanSupervisors Office

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

4 110 0.44 2,400 1,056 179$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 1560 524 89$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.10 250 282 532 90.15$

33 of 52

Page 277: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1009Laura

DonovanSupervisors Office

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 2,400 586 99$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 72$ NO SENSOR PROPOSED 0 0.07 163 - 163 27.66$

1010Laura

DonovanStorage #1 100w Incandescent S/I 4 100 0.40 500 200 34$

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

4 23 0.09 500 46 8$ NO SENSOR PROPOSED 0 0.31 154 - 154 26.10$

1011Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1012Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1013Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1014Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1015Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1016Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1017Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1018Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1019Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1020Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1021Laura

DonovanElectric Service 100w Incandescent S/I 4 100 0.40 1,000 400 68$

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

4 23 0.09 1000 92 16$ NO SENSOR PROPOSED 0 0.31 308 - 308 52.21$

1022Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1023Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1024Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1025Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1026Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1027Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1028Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1029Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1030Laura

DonovanGirls

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 31 0.19 2,400 446 76$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 25 0.15 2400 360 61$ NO SENSOR PROPOSED 0 0.04 86 - 86 14.64$

1031 Laura Donovan

Storage 23w Compact Fluorescent S/I 4 23 0.09 500 46 8$ No Work Proposed 0 23 0.09 500 46 8$ NO SENSOR PROPOSED 0 - - - - -$

1032Laura

DonovanBoys

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 31 0.19 2,400 446 76$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 25 0.15 2400 360 61$ NO SENSOR PROPOSED 0 0.04 86 - 86 14.64$

1033 Laura Donovan

Storage 23w Compact Fluorescent S/I 3 23 0.07 500 35 6$ No Work Proposed 0 23 0.07 500 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1034Laura

DonovanStorage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.44$

1035Laura

DonovanExit Vestibule

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 38$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 3640 160 27$ NO SENSOR PROPOSED 0 0.02 62 - 62 10.49$

1036Laura

DonovanArt Room

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

15 110 1.65 1,500 2,475 420$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

15 84 1.26 975 1229 208$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

2 0.39 585 662 1,247 211.28$

1037Laura

DonovanKiln Room

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 1,500 549 93$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 975 257 44$ Wall Switch Occupancy Sensor 1 0.10 153 139 292 49.43$

34 of 52

Page 278: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1038Laura

DonovanCST

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 2,400 878 149$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 1560 412 70$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.10 245 222 467 79.08$

1039Laura

DonovanBoys

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 31 0.19 2,400 446 76$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 25 0.15 2400 360 61$ NO SENSOR PROPOSED 0 0.04 86 - 86 14.64$

1040Laura

DonovanCustodian 100w Incandescent S/I 2 100 0.20 1,000 200 34$

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

2 23 0.05 1000 46 8$ NO SENSOR PROPOSED 0 0.15 154 - 154 26.10$

1041Laura

DonovanSprinkler Valve 100w Incandescent S/I 4 100 0.40 1,000 400 68$

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

4 23 0.09 1000 92 16$ NO SENSOR PROPOSED 0 0.31 308 - 308 52.21$

1042Laura

DonovanGirls

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 31 0.19 2,400 446 76$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 25 0.15 2400 360 61$ NO SENSOR PROPOSED 0 0.04 86 - 86 14.64$

1043Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1044Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1045Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1046Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1047Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1048Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1049Laura

DonovanComputer Class

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

27 61 1.65 1,500 2,471 419$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

27 44 1.19 975 1158 196$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

2 0.46 689 624 1,312 222.42$

1050Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

12 61 0.73 1,500 1,098 186$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 975 515 87$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.20 306 277 583 98.85$

1051Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

14 61 0.85 1,500 1,281 217$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 975 601 102$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.24 357 323 680 115.33$

1052Laura

DonovanEnrichment Class

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

14 61 0.85 1,500 1,281 217$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 975 601 102$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.24 357 323 680 115.33$

1053Laura

DonovanStorage

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 500 110 19$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 500 84 14$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.41$

1054Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

8 110 0.88 1,500 1,320 224$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 84 0.67 1500 1008 171$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1055Laura

DonovanClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,500 366 62$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1500 264 45$ NO SENSOR PROPOSED 0 0.07 102 - 102 17.29$

1056Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 336$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 975 983 167$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 529 997 169.03$

1057Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 336$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 975 983 167$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 529 997 169.03$

1058Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 336$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 975 983 167$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 529 997 169.03$

1059Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 336$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 975 983 167$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 529 997 169.03$

1060Laura

DonovanCustodian

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

4 61 0.24 1,000 244 41$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1000 176 30$ NO SENSOR PROPOSED 0 0.07 68 - 68 11.53$

1061Laura

DonovanStorage 100w Incandescent S/I 4 100 0.40 500 200 34$

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

4 23 0.09 500 46 8$ NO SENSOR PROPOSED 0 0.31 154 - 154 26.10$

1062Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 336$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 975 983 167$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 529 997 169.03$

1063Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192 33$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 11$ NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1064Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 336$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 1500 1512 256$ NO SENSOR PROPOSED 0 0.31 468 - 468 79.33$

1065Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192 33$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 11$ NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1066Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 336$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 1500 1512 256$ NO SENSOR PROPOSED 0 0.31 468 - 468 79.33$

35 of 52

Page 279: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1067Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192 33$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 11$ NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1068Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

12 110 1.32 1,500 1,980 336$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 1500 1512 256$ NO SENSOR PROPOSED 0 0.31 468 - 468 79.33$

1069Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192 33$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 11$ NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1070Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

16 110 1.76 1,500 2,640 447$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 84 1.34 1500 2016 342$ NO SENSOR PROPOSED 0 0.42 624 - 624 105.77$

1071Laura

DonovanStorage 75w. Incandescent S/I 2 75 0.15 500 75 13$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 500 13 2$ NO SENSOR PROPOSED 0 0.12 62 - 62 10.51$

1072Laura

DonovanBathroom 40w. Incandescent S/I 2 40 0.08 2,400 192 33$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 11$ NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1073Laura

DonovanClass

8' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

16 110 1.76 1,500 2,640 447$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 84 1.34 975 1310 222$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.42 624 706 1,330 225.37$

1074Laura

DonovanStorage 75w. Incandescent S/I 2 75 0.15 500 75 13$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 500 13 2$ NO SENSOR PROPOSED 0 0.12 62 - 62 10.51$

1075Laura

DonovanRestroom 40w. Incandescent S/I 2 40 0.08 2,400 192 33$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 11$ NO SENSOR PROPOSED 0 0.05 130 - 130 21.97$

1076Laura

DonovanElectric Room 75w. Incandescent S/I 2 75 0.15 1,000 150 25$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 1000 26 4$ NO SENSOR PROPOSED 0 0.12 124 - 124 21.02$

1077Laura

DonovanNurse's Office

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

8 89 0.71 2,400 1,709 290$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 2400 1210 205$ NO SENSOR PROPOSED 0 0.21 499 - 499 84.61$

1078Laura

DonovanStorage 100w Incandescent S/I 1 100 0.10 500 50 8$

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

1 23 0.02 500 12 2$ NO SENSOR PROPOSED 0 0.08 39 - 39 6.53$

1079Laura

DonovanBathroom 60w. Incandescent S/I 2 60 0.12 2,400 288 49$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 11$ NO SENSOR PROPOSED 0 0.09 226 - 226 38.24$

1080Laura

DonovanMain Office

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

12 89 1.07 2,400 2,563 434$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 2400 1814 308$ NO SENSOR PROPOSED 0 0.31 749 - 749 126.92$

1081Laura

DonovanPrincipal

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

6 89 0.53 2,400 1,282 217$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 1560 590 100$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 374 318 692 117.28$

1082Laura

DonovanWork Room

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

3 89 0.27 2,400 641 109$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 1560 295 50$ Wall Switch Occupancy Sensor 1 0.08 187 159 346 58.64$

1083Laura

DonovanBathroom 60w. Incandescent S/I 2 60 0.12 2,400 288 49$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 11$ NO SENSOR PROPOSED 0 0.09 226 - 226 38.24$

1084Laura

DonovanClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

11 110 1.21 1,500 1,815 308$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 84 0.92 975 901 153$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

2 0.29 429 485 914 154.94$

1085Laura

DonovanElectric Panel

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 21$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1000 88 15$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.76$

1086Laura

DonovanSmall Group

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 31$ No Work Proposed 0 61 0.12 1500 183 31$ NO SENSOR PROPOSED 0 - - - - -$

1087Laura

DonovanSmall Group

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 1,500 549 93$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 1500 396 67$ NO SENSOR PROPOSED 0 0.10 153 - 153 25.93$

1088Laura

DonovanRestroom

2' Vanity Fxiture with (2) F20 T12 Lamp & (1) 2L Magnetic Ballast

1 60 0.06 2,400 144 24$ Re-lamp & Re-ballast existing fixture. Install a 2-Lamp Electronic Normal Power Ballast, (2) 2' T8

Energy Saving Lamps, New Lamp Sockets.1 34 0.03 2400 82 14$ NO SENSOR PROPOSED 0 0.03 62 - 62 10.58$

1089Laura

DonovanRestroom 60w. Incandescent S/I 2 60 0.12 2,400 288 49$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 11$ NO SENSOR PROPOSED 0 0.09 226 - 226 38.24$

1090Laura

DonovanWomen's Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.92$

1091Laura

DonovanWomen's Room

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 2,400 149 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 25 0.05 2400 120 20$ NO SENSOR PROPOSED 0 0.01 29 - 29 4.88$

1092Laura

DonovanRestroom

4' Wrap Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

2 31 0.06 2,400 149 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 25 0.05 2400 120 20$ NO SENSOR PROPOSED 0 0.01 29 - 29 4.88$

1093Laura

DonovanRestroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 14$ No Work Proposed 0 34 0.03 2400 82 14$ NO SENSOR PROPOSED 0 - - - - -$

1094Laura

DonovanMusic Room

4' Wrap Fixture w/ (3) F32w T8 Lamps & (1) 3-Light Electronic ballast

9 89 0.80 1,500 1,202 204$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 975 553 94$ Wall Switch Occupancy Sensor 1 0.23 351 298 649 109.95$

1095Laura

DonovanSpeech

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

10 61 0.61 1,500 915 155$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 112$ NO SENSOR PROPOSED 0 0.17 255 - 255 43.22$

1096Laura

DonovanSpeech

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 16$ No Work Proposed 0 61 0.06 1500 92 16$ NO SENSOR PROPOSED 0 - - - - -$

1097Laura

DonovanStorage 75w. Incandescent S/I 1 75 0.08 500 38 6$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 500 7 1$ NO SENSOR PROPOSED 0 0.06 31 - 31 5.25$

1098Laura

DonovanBathroom 60w. Incandescent S/I 2 60 0.12 2,400 288 49$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

2 13 0.03 2400 62 11$ NO SENSOR PROPOSED 0 0.09 226 - 226 38.24$

36 of 52

Page 280: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1099Laura

DonovanHub room

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 2,400 439 74$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 2400 317 54$ NO SENSOR PROPOSED 0 0.05 122 - 122 20.75$

1100Laura

DonovanTeachers Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

10 89 0.89 2,400 2,136 362$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1560 983 167$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.26 624 529 1,153 195.47$

1101Laura

DonovanGirls

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 72$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 2400 302 51$ NO SENSOR PROPOSED 0 0.05 125 - 125 21.15$

1102Laura

DonovanBoys

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 72$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 2400 302 51$ NO SENSOR PROPOSED 0 0.05 125 - 125 21.15$

1103Laura

DonovanSmall Group C

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 89 0.62 1,500 935 158$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 63 0.44 1500 662 112$ NO SENSOR PROPOSED 0 0.18 273 - 273 46.27$

1104Laura

DonovanStorage #6

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 500 45 8$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 63 0.06 500 32 5$ NO SENSOR PROPOSED 0 0.03 13 - 13 2.20$

1105Laura

DonovanClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 272$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 975 737 125$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 397 865 146.60$

1106Laura

DonovanClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 272$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 975 737 125$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 397 865 146.60$

1107Laura

DonovanClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 272$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 192$ NO SENSOR PROPOSED 0 0.31 468 - 468 79.33$

1108Laura

DonovanClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 272$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 192$ NO SENSOR PROPOSED 0 0.31 468 - 468 79.33$

1109Laura

DonovanClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 181$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 975 491 83$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 312 265 577 97.73$

1110Laura

DonovanClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 217$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 157$ NO SENSOR PROPOSED 0 0.24 357 - 357 60.51$

1111 Laura Donovan

Class Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1112Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.92$

1113Laura

DonovanStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.44$

1114Laura

DonovanClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 181$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 975 491 83$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 312 265 577 97.73$

1115Laura

DonovanClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 217$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 157$ NO SENSOR PROPOSED 0 0.24 357 - 357 60.51$

1116 Laura Donovan

Class Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1117Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.92$

1118Laura

DonovanStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.44$

1119Laura

DonovanClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 181$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 975 491 83$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 312 265 577 97.73$

1120Laura

DonovanClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 217$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 157$ NO SENSOR PROPOSED 0 0.24 357 - 357 60.51$

1121 Laura Donovan

Class Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1122Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.92$

1123Laura

DonovanStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.44$

1124Laura

DonovanClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 181$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 975 491 83$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 312 265 577 97.73$

1125Laura

DonovanClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 217$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 157$ NO SENSOR PROPOSED 0 0.24 357 - 357 60.51$

1126 Laura Donovan

Class Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1127Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.92$

1128Laura

DonovanStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.44$

37 of 52

Page 281: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1129 Laura Donovan

Lunch Room Recessed Can Can w/ (2) 57w CF PL 12 114 1.37 2,400 3,283 557$ No Work Proposed 0 114 1.37 2400 3283 557$ NO SENSOR PROPOSED 0 - - - - -$

1130 Laura Donovan

Lunch Room Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1131Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.92$

1132Laura

DonovanHW Heater

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.92$

1133Laura

DonovanKitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 99$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 72$ NO SENSOR PROPOSED 0 0.07 163 - 163 27.66$

1134Laura

DonovanKitchen Storage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.44$

1135 Laura Donovan

MPR Recessed Can Can w/ (2) 57w CF PL 13 114 1.48 2,400 3,557 603$ No Work Proposed 0 114 1.48 2400 3557 603$ NO SENSOR PROPOSED 0 - - - - -$

1136 Laura Donovan

MPR Exit Sign w/ 2w LED 13 2 0.03 8,760 228 39$ No Work Proposed 0 2 0.03 8760 228 39$ NO SENSOR PROPOSED 0 - - - - -$

1137Laura

DonovanStorage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.44$

1138Laura

DonovanCustodian

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.88$

1139Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.92$

1140Laura

DonovanClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 181$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 128$ NO SENSOR PROPOSED 0 0.21 312 - 312 52.88$

1141Laura

DonovanClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 217$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 157$ NO SENSOR PROPOSED 0 0.24 357 - 357 60.51$

1142 Laura Donovan

Class Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1143Laura

DonovanRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 25$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 18$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.92$

1144Laura

DonovanStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.44$

1145Laura

DonovanStorage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 500 92 16$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.32$

1146Laura

DonovanOutside

Wall Pack Fixture w/ (1) 100w High Pressure Sodium Lamp and Magnetic

Ballast14 120 1.68 3,640 6,115 1,037$ No Work Proposed 0 120 1.68 3640 6115 1,037$ NO SENSOR PROPOSED 0 - - - - -$

1147Laura

DonovanOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 400w High Pressure Sodium Lamp

and (1) Magnetic HID Ballast5 450 2.25 3,640 8,190 1,388$ No Work Proposed 0 450 2.25 3640 8190 1,388$ NO SENSOR PROPOSED 0 - - - - -$

1148Laura

DonovanOutside

Wall Pack Fixture w/ (1) 50w High Pressure Sodium Lamp and Magnetic

Ballast6 65 0.39 3,640 1,420 241$ No Work Proposed 0 65 0.39 3640 1420 241$ NO SENSOR PROPOSED 0 - - - - -$

1149Laura

DonovanOutside

Wal Pack Fixture with (1) 250w Metal Halide Lamp and (1) Magnetic HID Ballast

7 295 2.07 3,640 7,517 1,274$ No Work Proposed 0 295 2.07 3640 7517 1,274$ NO SENSOR PROPOSED 0 - - - - -$

1150Laura

DonovanOutside

Wall Pack Fixture with (1) 100w Metal Halide Lamp and (1) Magnetic HID Ballast

15 120 1.80 3,640 6,552 1,111$ No Work Proposed 0 120 1.80 3640 6552 1,111$ NO SENSOR PROPOSED 0 - - - - -$

32 29 58577 11387 69965 $11,859

1151West

FreeholdCorridor 262

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

27 61 1.65 3,640 5,995 954$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

27 44 1.19 3640 4324 688$ NO SENSOR PROPOSED 0 0.46 1,671 - 1,671 265.98$

1152 West Freehold

Corridor 262 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

4 26 0.10 3,640 379 60$ No Work Proposed 0 26 0.10 3640 379 60$ NO SENSOR PROPOSED 0 - - - - -$

1153 West Freehold

Corridor 262 Exit Sign w/ 2w LED 4 2 0.01 8,760 70 11$ No Work Proposed 0 2 0.01 8760 70 11$ NO SENSOR PROPOSED 0 - - - - -$

1154West

FreeholdCorridor 261

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 353$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 3640 1602 255$ NO SENSOR PROPOSED 0 0.17 619 - 619 98.51$

1155 West Freehold

Corridor 261 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

1 26 0.03 3,640 95 15$ No Work Proposed 0 26 0.03 3640 95 15$ NO SENSOR PROPOSED 0 - - - - -$

1156West

FreeholdCorridor 259,200-201

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

51 61 3.11 3,640 11,324 1,803$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

51 44 2.24 3640 8168 1,300$ NO SENSOR PROPOSED 0 0.87 3,156 - 3,156 502.42$

1157 West Freehold

Corridor 259,200-201 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

5 26 0.13 3,640 473 75$ No Work Proposed 0 26 0.13 3640 473 75$ NO SENSOR PROPOSED 0 - - - - -$

1158 West Freehold

Corridor 259,200-201 Exit Sign w/ 2w LED 8 2 0.02 8,760 140 22$ No Work Proposed 0 2 0.02 8760 140 22$ NO SENSOR PROPOSED 0 - - - - -$

1159West

FreeholdCorridor 202

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

24 61 1.46 3,640 5,329 848$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

24 44 1.06 3640 3844 612$ NO SENSOR PROPOSED 0 0.41 1,485 - 1,485 236.43$

1160 West Freehold

Corridor 202 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

4 26 0.10 3,640 379 60$ No Work Proposed 0 26 0.10 3640 379 60$ NO SENSOR PROPOSED 0 - - - - -$

1161West

FreeholdCorridor 260

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 353$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 3640 1602 255$ NO SENSOR PROPOSED 0 0.17 619 - 619 98.51$

1162 West Freehold

Corridor 260 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

1 26 0.03 3,640 95 15$ No Work Proposed 0 26 0.03 3640 95 15$ NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at Laura Donovan:

38 of 52

Page 282: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1163West

FreeholdCorridor 263

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

15 61 0.92 3,640 3,331 530$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

15 44 0.66 3640 2402 382$ NO SENSOR PROPOSED 0 0.26 928 - 928 147.77$

1164 West Freehold

Corridor 263 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 8$ No Work Proposed 0 2 0.01 8760 53 8$ NO SENSOR PROPOSED 0 - - - - -$

1165 West Freehold

Corridor 263 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

2 26 0.05 3,640 189 30$ No Work Proposed 0 26 0.05 3640 189 30$ NO SENSOR PROPOSED 0 - - - - -$

1166West

FreeholdCorridor 263

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 71$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 3640 320 51$ NO SENSOR PROPOSED 0 0.03 124 - 124 19.70$

1167West

FreeholdCorridor 103

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 353$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 3640 1602 255$ NO SENSOR PROPOSED 0 0.17 619 - 619 98.51$

1168 West Freehold

Corridor 103 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

1169West

FreeholdCorridor 104

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

13 61 0.79 3,640 2,887 460$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

13 44 0.57 3640 2082 331$ NO SENSOR PROPOSED 0 0.22 804 - 804 128.07$

1170West

FreeholdCorridor 104

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 3,640 222 35$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 3640 160 25$ NO SENSOR PROPOSED 0 0.02 62 - 62 9.85$

1171West

FreeholdCorridor 102

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 61 0.49 3,640 1,776 283$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 44 0.35 3640 1281 204$ NO SENSOR PROPOSED 0 0.14 495 - 495 78.81$

1172 West Freehold

Corridor 102 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

1173West

FreeholdCorridor 101

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 247$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 44 0.31 3640 1121 178$ NO SENSOR PROPOSED 0 0.12 433 - 433 68.96$

1174 West Freehold

Corridor 101 Recessed Can Can w/ (2) 13w CF PL 11 26 0.29 3,640 1,041 166$ No Work Proposed 0 26 0.29 3640 1041 166$ NO SENSOR PROPOSED 0 - - - - -$

1175 West Freehold

Corridor 101 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 8$ No Work Proposed 0 2 0.01 8760 53 8$ NO SENSOR PROPOSED 0 - - - - -$

1176 West Freehold

Vest. 100 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

4 26 0.10 2,400 250 40$ No Work Proposed 0 26 0.10 2400 250 40$ NO SENSOR PROPOSED 0 - - - - -$

1177West

FreeholdVest. 100

Wall Pack Fixture with (2) 26w Compact Fluorescent Lamps and (1) Magnetic

Ballast1 52 0.05 2,400 125 20$ No Work Proposed 0 52 0.05 2400 125 20$ NO SENSOR PROPOSED 0 - - - - -$

1178West

FreeholdCorridor 105

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 247$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 44 0.31 3640 1121 178$ NO SENSOR PROPOSED 0 0.12 433 - 433 68.96$

1179 West Freehold

Corridor 105 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1180West

FreeholdCommons

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

12 34 0.41 2,400 979 156$ No Work Proposed 0 34 0.41 2400 979 156$ NO SENSOR PROPOSED 0 - - - - -$

1181 West Freehold

Commons Recessed Can Can w/ (2) 13w CF PL 18 26 0.47 2,400 1,123 179$ No Work Proposed 0 26 0.47 2400 1123 179$ NO SENSOR PROPOSED 0 - - - - -$

1182West

FreeholdCorridor 107

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 247$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 44 0.31 3640 1121 178$ NO SENSOR PROPOSED 0 0.12 433 - 433 68.96$

1183West

FreeholdCorridor 107

2X2 recessed troffer with (2) F17 T8 Lamps & (1) 2-Light Electronic ballast

8 34 0.27 3,640 990 158$ No Work Proposed 0 34 0.27 3640 990 158$ NO SENSOR PROPOSED 0 - - - - -$

1184West

FreeholdCorridor 108

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 247$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 44 0.31 3640 1121 178$ NO SENSOR PROPOSED 0 0.12 433 - 433 68.96$

1185West

FreeholdCorridor 108

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 353$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 3640 1602 255$ NO SENSOR PROPOSED 0 0.17 619 - 619 98.51$

1186 West Freehold

Corridor 108 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 8$ No Work Proposed 0 2 0.01 8760 53 8$ NO SENSOR PROPOSED 0 - - - - -$

1187West

FreeholdCorridor 109

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

22 61 1.34 3,640 4,885 778$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

22 44 0.97 3640 3524 561$ NO SENSOR PROPOSED 0 0.37 1,361 - 1,361 216.73$

1188 West Freehold

Corridor 109 Recessed Can Can w/ (2) 13w CF PL 3 26 0.08 3,640 284 45$ No Work Proposed 0 26 0.08 3640 284 45$ NO SENSOR PROPOSED 0 - - - - -$

1189 West Freehold

Corridor 109 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

1190West

FreeholdCorridor 302

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

18 61 1.10 3,640 3,997 636$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 3640 2883 459$ NO SENSOR PROPOSED 0 0.31 1,114 - 1,114 177.32$

1191West

FreeholdCorridor 302

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 3,640 444 71$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 3640 320 51$ NO SENSOR PROPOSED 0 0.03 124 - 124 19.70$

1192 West Freehold

Corridor 302 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1193West

FreeholdCorridor 303

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

30 61 1.83 3,640 6,661 1,060$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

30 44 1.32 3640 4805 765$ NO SENSOR PROPOSED 0 0.51 1,856 - 1,856 295.54$

1194 West Freehold

Corridor 303 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

2 26 0.05 3,640 189 30$ No Work Proposed 0 26 0.05 3640 189 30$ NO SENSOR PROPOSED 0 - - - - -$

1195 West Freehold

Corridor 303 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1196West

FreeholdCorridor 304

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 353$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 3640 1602 255$ NO SENSOR PROPOSED 0 0.17 619 - 619 98.51$

1197 West Freehold

Corridor 304 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

1 26 0.03 3,640 95 15$ No Work Proposed 0 26 0.03 3640 95 15$ NO SENSOR PROPOSED 0 - - - - -$

1198 West Freehold

Corridor 304 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

1199West

FreeholdCorridor 305

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

30 61 1.83 3,640 6,661 1,060$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

30 44 1.32 3640 4805 765$ NO SENSOR PROPOSED 0 0.51 1,856 - 1,856 295.54$

39 of 52

Page 283: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1200 West Freehold

Corridor 305 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

3 26 0.08 3,640 284 45$ No Work Proposed 0 26 0.08 3640 284 45$ NO SENSOR PROPOSED 0 - - - - -$

1201 West Freehold

Corridor 305 Exit Sign w/ 2w LED 4 2 0.01 8,760 70 11$ No Work Proposed 0 2 0.01 8760 70 11$ NO SENSOR PROPOSED 0 - - - - -$

1202West

FreeholdCorridor 306

4' Strip Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

10 61 0.61 3,640 2,220 353$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 3640 1602 255$ NO SENSOR PROPOSED 0 0.17 619 - 619 98.51$

1203 West Freehold

Corridor 306 Wall Sconce w/ (2) PL 13 Compact Fluorescent Lamps

1 26 0.03 3,640 95 15$ No Work Proposed 0 26 0.03 3640 95 15$ NO SENSOR PROPOSED 0 - - - - -$

1204 West Freehold

Corridor 306 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

1205West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 975 614 98$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.26 390 331 721 114.74$

1206West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1207West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 975 614 98$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.26 390 331 721 114.74$

1208West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1209West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 975 614 98$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.26 390 331 721 114.74$

1210West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1211West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 975 614 98$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.26 390 331 721 114.74$

1212West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1213West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 975 614 98$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.26 390 331 721 114.74$

1214West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1215West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 975 614 98$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.26 390 331 721 114.74$

1216West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1217West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 975 614 98$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.26 390 331 721 114.74$

1218West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1219West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 975 614 98$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.26 390 331 721 114.74$

1220West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1221West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 975 614 98$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.26 390 331 721 114.74$

1222West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1223West

FreeholdStorage Shed

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

2 61 0.12 500 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.71$

1224West

FreeholdSprinkler Valve

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

2 61 0.12 1,000 122 19$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1000 88 14$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.41$

1225West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 170$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 120$ NO SENSOR PROPOSED 0 0.21 312 - 312 49.67$

1226West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 1,500 1,098 175$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 1500 792 126$ NO SENSOR PROPOSED 0 0.20 306 - 306 48.72$

1227West

Freehold-Storage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1228West

Freehold-Restroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1229West

FreeholdMPR

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

15 61 0.92 2,400 2,196 350$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

15 44 0.66 2400 1584 252$ NO SENSOR PROPOSED 0 0.26 612 - 612 97.43$

40 of 52

Page 284: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1230West

FreeholdCafeteria A

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

11 89 0.98 3,640 3,564 567$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 63 0.69 3640 2523 402$ NO SENSOR PROPOSED 0 0.29 1,041 - 1,041 165.73$

1231West

FreeholdCafeteria A

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 3,640 2,664 424$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 3640 1922 306$ NO SENSOR PROPOSED 0 0.20 743 - 743 118.22$

1232West

Freehold-Restroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1233West

Freehold-Storage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1234West

Freehold-Serving Kitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 93$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 67$ NO SENSOR PROPOSED 0 0.07 163 - 163 25.98$

1235West

Freehold-Kitchen Storage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1236West

FreeholdJanitor Closet

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ No Work Proposed 0 61 0.06 500 31 5$ NO SENSOR PROPOSED 0 - - - - -$

1237West

FreeholdRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1238West

FreeholdClass/Kindergarten

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 170$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 120$ NO SENSOR PROPOSED 0 0.21 312 - 312 49.67$

1239West

FreeholdClass/Kindergarten

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 1,500 1,098 175$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 1500 792 126$ NO SENSOR PROPOSED 0 0.20 306 - 306 48.72$

1240West

Freehold-Restroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1241West

Freehold-Storage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1242West

FreeholdClass/Kindergarten

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 170$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 120$ NO SENSOR PROPOSED 0 0.21 312 - 312 49.67$

1243West

FreeholdClass/Kindergarten

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 1,500 1,098 175$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 1500 792 126$ NO SENSOR PROPOSED 0 0.20 306 - 306 48.72$

1244West

Freehold-Restroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1245West

Freehold-Storage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1246West

FreeholdClass/Kindergarten

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 170$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 120$ NO SENSOR PROPOSED 0 0.21 312 - 312 49.67$

1247West

FreeholdClass/Kindergarten

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 1,500 1,098 175$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 1500 792 126$ NO SENSOR PROPOSED 0 0.20 306 - 306 48.72$

1248West

Freehold-Restroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1249West

Freehold-Storage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1250West

FreeholdClass/Kindergarten

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

8 89 0.71 1,500 1,068 170$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 120$ NO SENSOR PROPOSED 0 0.21 312 - 312 49.67$

1251West

FreeholdClass/Kindergarten

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

12 61 0.73 1,500 1,098 175$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 1500 792 126$ NO SENSOR PROPOSED 0 0.20 306 - 306 48.72$

1252West

Freehold-Restroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1253West

Freehold-Storage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1254West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 975 614 98$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.26 390 331 721 114.74$

1255West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 975 614 98$ Wide View Low Voltage (w/PP-20) Wall Mounted Sensor-40' Range (8-15' Mtg.

Height) 1 0.26 390 331 721 114.74$

1256West

FreeholdRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1560 69 11$ Wall Switch Dual Technology

Occupancy Sensor1 0.02 41 37 78 12.38$

1257West

FreeholdWomen's Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 47$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 12.99$

41 of 52

Page 285: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1258West

FreeholdMen's Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 47$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 12.99$

1259West

FreeholdIDF Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 29$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1500 132 21$ NO SENSOR PROPOSED 0 0.03 51 - 51 8.12$

1260West

FreeholdElectrical Closet

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1261West

FreeholdSGI

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 975 429 68$ Wall Switch Occupancy Sensor 1 0.17 255 231 486 77.37$

1262West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1263West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1264West

FreeholdRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1265West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1266West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1267West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1268West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1269West

FreeholdSGI

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 170$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 120$ NO SENSOR PROPOSED 0 0.21 312 - 312 49.67$

1270West

FreeholdSGI

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 1,500 1,068 170$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1500 756 120$ NO SENSOR PROPOSED 0 0.21 312 - 312 49.67$

1271West

FreeholdSGI 2

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 128$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 1500 567 90$ NO SENSOR PROPOSED 0 0.16 234 - 234 37.25$

1272West

FreeholdGirls

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 102$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 2400 454 72$ NO SENSOR PROPOSED 0 0.08 187 - 187 29.80$

1273West

FreeholdBoys

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 102$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 2400 454 72$ NO SENSOR PROPOSED 0 0.08 187 - 187 29.80$

1274West

FreeholdSGI 3

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 89 0.45 1,500 668 106$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

5 63 0.32 1500 473 75$ NO SENSOR PROPOSED 0 0.13 195 - 195 31.04$

1275West

FreeholdNurse's Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

5 89 0.45 2,400 1,068 170$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

5 63 0.32 2400 756 120$ NO SENSOR PROPOSED 0 0.13 312 - 312 49.67$

1276West

FreeholdNurse's Office

2X2 recessed troffer with (3) F17 T8 Lamps & (1) 3-Light Electronic ballast

4 50 0.20 2,400 480 76$ No Work Proposed 0 50 0.20 2400 480 76$ NO SENSOR PROPOSED 0 - - - - -$

1277West

FreeholdRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1278West

FreeholdMain Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

11 89 0.98 2,400 2,350 374$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 63 0.69 2400 1663 265$ NO SENSOR PROPOSED 0 0.29 686 - 686 109.27$

1279West

FreeholdMain Office

2X2 recessed troffer with (3) F17 T8 Lamps & (1) 3-Light Electronic ballast

1 50 0.05 2,400 120 19$ No Work Proposed 0 50 0.05 2400 120 19$ NO SENSOR PROPOSED 0 - - - - -$

1280West

FreeholdWork Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 68$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 2400 302 48$ NO SENSOR PROPOSED 0 0.05 125 - 125 19.87$

1281West

FreeholdRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1282West

FreeholdConference Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 102$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 2400 454 72$ NO SENSOR PROPOSED 0 0.08 187 - 187 29.80$

1283West

FreeholdPrincipal

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 102$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 2400 454 72$ NO SENSOR PROPOSED 0 0.08 187 - 187 29.80$

1284West

FreeholdLibrary

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

32 89 2.85 2,400 6,835 1,088$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

32 63 2.02 2400 4838 770$ NO SENSOR PROPOSED 0 0.83 1,997 - 1,997 317.89$

1285West

FreeholdLibrary

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

38 61 2.32 2,400 5,563 886$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

38 44 1.67 2400 4013 639$ NO SENSOR PROPOSED 0 0.65 1,550 - 1,550 246.82$

42 of 52

Page 286: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1286West

FreeholdLibrary

2X2 recessed troffer with (3) F17 T8 Lamps & (1) 3-Light Electronic ballast

22 50 1.10 2,400 2,640 420$ No Work Proposed 0 50 1.10 2400 2640 420$ NO SENSOR PROPOSED 0 - - - - -$

1287 West Freehold

Library Recessed Can Can w/ (2) 57w CF PL 3 114 0.34 2,400 821 131$ No Work Proposed 0 114 0.34 2400 821 131$ NO SENSOR PROPOSED 0 - - - - -$

1288West

FreeholdWork Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 68$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 2400 302 48$ NO SENSOR PROPOSED 0 0.05 125 - 125 19.87$

1289West

FreeholdLibrary Storage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.06$

1290West

FreeholdRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1291West

FreeholdComputer Lab

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

34 61 2.07 1,500 3,111 495$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

34 44 1.50 1500 2244 357$ NO SENSOR PROPOSED 0 0.58 867 - 867 138.03$

1292West

FreeholdArt Class

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

12 89 1.07 1,500 1,602 255$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 63 0.76 1500 1134 181$ NO SENSOR PROPOSED 0 0.31 468 - 468 74.51$

1293West

FreeholdKiln Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 29$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1500 132 21$ NO SENSOR PROPOSED 0 0.03 51 - 51 8.12$

1294West

FreeholdStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1295West

FreeholdVice Principal

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 102$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 1560 295 47$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.08 187 159 346 55.08$

1296West

FreeholdMDF

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 2,400 439 70$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 2400 317 50$ NO SENSOR PROPOSED 0 0.05 122 - 122 19.49$

1297West

FreeholdComputer Training

Room4' Direct/Indirect Fixture w/ (2) F32 T/

Lamps & (1) 2L Electronic Ballast20 61 1.22 1,500 1,830 291$

Re-lamp existing fixture with an Energy Saving 28w Lamp to standardize lamp types for

maintenance. Existing Ballast stays in place20 44 0.88 975 858 137$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.34 510 462 972 154.74$

1298West

FreeholdElectrical Closet

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1299West

FreeholdGuidence Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 102$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 1560 295 47$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.08 187 159 346 55.08$

1300West

FreeholdTesting

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 1,500 401 64$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 975 184 29$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.08 117 99 216 34.42$

1301West

FreeholdCST

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 102$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 1560 295 47$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.08 187 159 346 55.08$

1302West

FreeholdGirls

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 70$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 1560 206 33$

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg.

Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High-(1)

PP-20 per sensor

1 0.05 122 111 233 37.14$

1303West

FreeholdBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 70$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 1560 206 33$

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg.

Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High-(1)

PP-20 per sensor

1 0.05 122 111 233 37.14$

1304West

FreeholdInstrumental Music

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 128$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 975 369 59$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 234 198 432 68.85$

1305 West Freehold

Instrumental Music Recessed Can Can w/ (2) 13w CF PL 12 26 0.31 1,500 468 75$ No Work Proposed 0 26 0.31 1500 468 75$ NO SENSOR PROPOSED 0 - - - - -$

1306West

FreeholdChoral Music

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

14 89 1.25 1,500 1,869 298$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 63 0.88 975 860 137$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.36 546 463 1,009 160.64$

1307West

FreeholdStage Alvoce

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 2,400 214 34$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 63 0.06 2400 151 24$ NO SENSOR PROPOSED 0 0.03 62 - 62 9.93$

1308West

FreeholdStage

4' Wrap Fxiture with (4) F32 T8 Lamps & (1) 4L Electronic Ballast

10 110 1.10 2,400 2,640 420$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 84 0.84 2400 2016 321$ NO SENSOR PROPOSED 0 0.26 624 - 624 99.34$

1309West

FreeholdStage Alvoce

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 102$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 2400 454 72$ NO SENSOR PROPOSED 0 0.08 187 - 187 29.80$

1310 West Freehold

Gym High Bay Fixture with (8) 42w Triple Tube PL Fluorescent Lamps

30 336 10.08 2,400 24,192 3,851$ No Work Proposed 0 336 10.08 2400 24192 3,851$ NO SENSOR PROPOSED 0 - - - - -$

1311 West Freehold

Gym 250w Quartz 10 250 2.50 2,400 6,000 955$ No Work Proposed 0 250 2.50 2400 6000 955$ NO SENSOR PROPOSED 0 - - - - -$

1312West

FreeholdPE Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 68$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 2400 302 48$ NO SENSOR PROPOSED 0 0.05 125 - 125 19.87$

1313West

FreeholdCloset

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1314West

FreeholdStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 500 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.71$

43 of 52

Page 287: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1315West

FreeholdGym Storage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1316West

FreeholdCafeteria

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

44 61 2.68 3,640 9,770 1,555$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

44 44 1.94 3640 7047 1,122$ NO SENSOR PROPOSED 0 0.75 2,723 - 2,723 433.46$

1317West

FreeholdCafeteria

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

44 89 3.92 3,640 14,254 2,269$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

44 63 2.77 3640 10090 1,606$ NO SENSOR PROPOSED 0 1.14 4,164 - 4,164 662.93$

1318West

FreeholdCafeteria

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 3,640 666 106$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 3640 480 76$ NO SENSOR PROPOSED 0 0.05 186 - 186 29.55$

1319West

FreeholdKitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

19 61 1.16 2,400 2,782 443$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

19 44 0.84 2400 2006 319$ NO SENSOR PROPOSED 0 0.32 775 - 775 123.41$

1320West

FreeholdKitchen

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 70$ No Work Proposed 0 61 0.18 2400 439 70$ NO SENSOR PROPOSED 0 - - - - -$

1321West

FreeholdPTO Storage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 500 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.71$

1322West

FreeholdStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 500 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.71$

1323West

FreeholdLocker Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 47$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 12.99$

1324West

FreeholdJanitor Closet

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1325West

FreeholdJanitor Closet

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1326West

FreeholdStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 500 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 500 44 7$ NO SENSOR PROPOSED 0 0.03 17 - 17 2.71$

1327West

FreeholdBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 70$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 1560 206 33$

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg.

Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High-(1)

PP-20 per sensor

1 0.05 122 111 233 37.14$

1328West

FreeholdGirls

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 70$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 1560 206 33$

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg.

Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High-(1)

PP-20 per sensor

1 0.05 122 111 233 37.14$

1329West

FreeholdStorage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.06$

1330West

FreeholdStorage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

4 61 0.24 500 122 19$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 500 88 14$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.41$

1331West

FreeholdMen's Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1332West

FreeholdWomen's Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1560 69 11$ Wall Switch Dual Technology

Occupancy Sensor1 0.02 41 37 78 12.38$

1333West

FreeholdCustodial Closet

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 4.06$

1334West

FreeholdFaculty Work Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 306$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 1560 885 141$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.23 562 476 1,038 165.23$

1335West

FreeholdCopy Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 306$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 1560 885 141$ Wall Switch Occupancy Sensor 1 0.23 562 476 1,038 165.23$

1336West

FreeholdReceiving Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

8 89 0.71 2,400 1,709 272$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 2400 1210 193$ NO SENSOR PROPOSED 0 0.21 499 - 499 79.47$

1337West

FreeholdBoiler Room

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

6 61 0.37 1,000 366 58$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 1000 264 42$ NO SENSOR PROPOSED 0 0.10 102 - 102 16.24$

1338West

FreeholdElectrical Room

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 1,000 183 29$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 1000 132 21$ NO SENSOR PROPOSED 0 0.05 51 - 51 8.12$

1339West

FreeholdAssistant Principal

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 89 0.27 2,400 641 102$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 63 0.19 2400 454 72$ NO SENSOR PROPOSED 0 0.08 187 - 187 29.80$

1340West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1341West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

44 of 52

Page 288: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1342West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1343West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1344West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1345West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1346West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1347West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1348West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1349West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1350West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1351West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1352West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1353West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1354West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1355West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1356West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1357West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1358West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1359West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1360West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1361West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1362West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1363West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1364West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1365West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1366West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1367West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1368West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1369West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

45 of 52

Page 289: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1370West

FreeholdClass

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 213$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 150$ NO SENSOR PROPOSED 0 0.26 390 - 390 62.09$

1371West

FreeholdClass

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

10 61 0.61 1,500 915 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 44 0.44 1500 660 105$ NO SENSOR PROPOSED 0 0.17 255 - 255 40.60$

1372West

FreeholdWomen's Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1373West

FreeholdMen's Room

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 23$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 6.50$

1374West

FreeholdGirls

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 47$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1560 137 22$

Low Voltage (w/ PP-20) Dual Technology Ceiling Sensor (8-15' Mtg.

Height) 360 Deg. Coverage 12' Circulur Viewing Pattern @ 9' High-(1)

PP-20 per sensor

1 0.03 82 74 156 24.76$

1375West

FreeholdJanitor Closet

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 1.35$

1376West

FreeholdBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 47$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 34$ NO SENSOR PROPOSED 0 0.03 82 - 82 12.99$

1377West

FreeholdMechanical Room

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 1,000 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.71$

1378West

FreeholdElectrical Room

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 1,000 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 2.71$

1379West

FreeholdIDF

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

2 61 0.12 1,500 183 29$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1500 132 21$ NO SENSOR PROPOSED 0 0.03 51 - 51 8.12$

1380West

FreeholdStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 500 122 19$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 500 88 14$ NO SENSOR PROPOSED 0 0.07 34 - 34 5.41$

1381West

FreeholdClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

15 89 1.34 1,500 2,003 319$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

15 63 0.95 975 921 147$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

2 0.39 585 496 1,081 172.12$

1382West

FreeholdSGI

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 1,500 534 85$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 1500 378 60$ NO SENSOR PROPOSED 0 0.10 156 - 156 24.84$

1383West

FreeholdCourtyard 1

Wal Pack Fixture with (1) 150w Metal Halide Lamp and (1) Magnetic HID Ballast

1 195 0.20 3,640 710 113$ No Work Proposed 0 195 0.20 3640 710 113$ NO SENSOR PROPOSED 0 - - - - -$

1384West

FreeholdCourtyard by 256

Wal Pack Fixture with (1) 150w Metal Halide Lamp and (1) Magnetic HID Ballast

3 195 0.59 3,640 2,129 339$ No Work Proposed 0 195 0.59 3640 2129 339$ NO SENSOR PROPOSED 0 - - - - -$

1385West

FreeholdCourtyard by 332

Wal Pack Fixture with (1) 150w Metal Halide Lamp and (1) Magnetic HID Ballast

4 195 0.78 3,640 2,839 452$ No Work Proposed 0 195 0.78 3640 2839 452$ NO SENSOR PROPOSED 0 - - - - -$

1386West

FreeholdOutside

Wall Pack Fixture with (2) 26w Compact Fluorescent Lamps and (1) Magnetic

Ballast9 52 0.47 3,640 1,704 271$ No Work Proposed 0 52 0.47 3640 1704 271$ NO SENSOR PROPOSED 0 - - - - -$

1387West

FreeholdOutside

Wal Pack Fixture with (1) 150w Metal Halide Lamp and (1) Magnetic HID Ballast

79 195 15.41 3,640 56,074 8,927$ No Work Proposed 0 195 15.41 3640 56074 8,927$ NO SENSOR PROPOSED 0 - - - - -$

1388West

FreeholdOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 400w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast20 445 8.90 3,640 32,396 5,157$ No Work Proposed 0 445 8.90 3640 32396 5,157$ NO SENSOR PROPOSED 0 - - - - -$

30 32 68927 7608 76536 $12,184

1389C.R.

ApplegateCorridor 10-18

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 61 0.55 3,640 1,998 329$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 44 0.40 3640 1441 237$ NO SENSOR PROPOSED 0 0.15 557 - 557 91.67$

1390C.R.

ApplegateCorridor 10-18

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 3,640 400 66$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 3640 306 50$ NO SENSOR PROPOSED 0 0.03 95 - 95 15.58$

1391 C.R. Applegate

Corridor 10-18 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1392C.R.

ApplegateCorridor 29

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 3640 641 105$ NO SENSOR PROPOSED 0 0.07 248 - 248 40.74$

1393 C.R. Applegate

Corridor 29 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

1394C.R.

ApplegateCorridor 31

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

3 110 0.33 3,640 1,201 198$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 84 0.25 3640 917 151$ NO SENSOR PROPOSED 0 0.08 284 - 284 46.73$

1395 C.R. Applegate

Corridor 31 Exit Sign w/ 2w LED 3 2 0.01 8,760 53 9$ No Work Proposed 0 2 0.01 8760 53 9$ NO SENSOR PROPOSED 0 - - - - -$

1396C.R.

ApplegateCorridor 36-39

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 256$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 44 0.31 3640 1121 185$ NO SENSOR PROPOSED 0 0.12 433 - 433 71.30$

1397 C.R. Applegate

Corridor 36-39 Exit Sign w/ 2w LED 1 2 0.00 8,760 18 3$ No Work Proposed 0 2 0.00 8760 18 3$ NO SENSOR PROPOSED 0 - - - - -$

1398C.R.

ApplegateCorridor 40

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

7 61 0.43 3,640 1,554 256$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 44 0.31 3640 1121 185$ NO SENSOR PROPOSED 0 0.12 433 - 433 71.30$

1399C.R.

ApplegateCorridor 40

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 3,640 400 66$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 3640 306 50$ NO SENSOR PROPOSED 0 0.03 95 - 95 15.58$

1400 C.R. Applegate

Corridor 40 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

Totals for Lighting System Upgrades at West Freehold:

46 of 52

Page 290: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1401C.R.

ApplegateCorridor 44-50

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 61 0.98 3,640 3,553 585$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 44 0.70 3640 2563 422$ NO SENSOR PROPOSED 0 0.27 990 - 990 162.97$

1402 C.R. Applegate

Corridor 44-50 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1403C.R.

ApplegateCorridor 59

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

16 61 0.98 3,640 3,553 585$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 44 0.70 3640 2563 422$ NO SENSOR PROPOSED 0 0.27 990 - 990 162.97$

1404 C.R. Applegate

Corridor 59 Exit Sign w/ 2w LED 4 2 0.01 8,760 70 12$ No Work Proposed 0 2 0.01 8760 70 12$ NO SENSOR PROPOSED 0 - - - - -$

1405 C.R. Applegate

Corridor 59 Exit Sign w/ (2) 20w Incandescent Lamps 2 40 0.08 8,760 701 115$ Remove and Replace existing exit sign with a new LED exit sign.

2 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 0.08 666 - 666 109.58$

1406C.R.

ApplegateCorridor 102-112

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

13 61 0.79 3,640 2,887 475$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

13 44 0.57 3640 2082 343$ NO SENSOR PROPOSED 0 0.22 804 - 804 132.41$

1407 C.R. Applegate

Corridor 102-112 Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1408C.R.

ApplegateMedic Center Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 141$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 2400 605 100$ NO SENSOR PROPOSED 0 0.10 250 - 250 41.08$

1409C.R.

ApplegateHub Room

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 89 0.36 2,400 854 141$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 63 0.25 2400 605 100$ NO SENSOR PROPOSED 0 0.10 250 - 250 41.08$

1410C.R.

ApplegateLibrary

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

54 61 3.29 2,400 7,906 1,301$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

54 44 2.38 2400 5702 939$ NO SENSOR PROPOSED 0 0.92 2,203 - 2,203 362.65$

1411C.R.

ApplegateLibrary

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

5 110 0.55 2,400 1,320 217$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

5 84 0.42 2400 1008 166$ NO SENSOR PROPOSED 0 0.13 312 - 312 51.36$

1412C.R.

ApplegateStorage Room #1

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

6 61 0.37 500 183 30$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 44 0.26 500 132 22$ NO SENSOR PROPOSED 0 0.10 51 - 51 8.39$

1413C.R.

ApplegateLobby

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 3640 641 105$ NO SENSOR PROPOSED 0 0.07 248 - 248 40.74$

1414 C.R. Applegate

Lobby Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - -$

1415C.R.

ApplegateLobby

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

8 220 1.76 3,640 6,406 1,054$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 84 1.34 3640 4892 805$ NO SENSOR PROPOSED 0 0.42 1,514 - 1,514 249.24$

1416C.R.

ApplegateClassroom

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 75.55$

1417C.R.

ApplegateClassroom

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 75.55$

1418C.R.

ApplegateClassroom

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 75.55$

1419C.R.

ApplegateClassroom

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 75.55$

1420C.R.

ApplegateClassroom

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 75.55$

1421C.R.

ApplegateClassroom

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 75.55$

1422C.R.

ApplegateClassroom

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 75.55$

1423C.R.

ApplegateClassroom

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 75.55$

1424C.R.

ApplegateGirls

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 96$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 70$ NO SENSOR PROPOSED 0 0.07 163 - 163 26.86$

1425 C.R. Applegate

Girls 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 9$ No Work Proposed 0 23 0.02 2400 55 9$ NO SENSOR PROPOSED 0 - - - - -$

1426C.R.

ApplegateSprinkler Valve

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 1,000 122 20$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1000 88 14$ NO SENSOR PROPOSED 0 0.03 34 - 34 5.60$

1427C.R.

ApplegateBoys

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 96$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 70$ NO SENSOR PROPOSED 0 0.07 163 - 163 $27

1428 C.R. Applegate

Boys 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 9$ No Work Proposed 0 23 0.02 2400 55 9$ NO SENSOR PROPOSED 0 - - - - $0

1429C.R.

ApplegateClassroom

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 975 772 127$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 459 416 875 $144

1430C.R.

ApplegateClassroom

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

2 220 0.44 1,500 660 109$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 1500 504 83$ NO SENSOR PROPOSED 0 0.10 156 - 156 $26

1431C.R.

ApplegateClassroom

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

47 of 52

Page 291: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1432C.R.

ApplegateKiln

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 132$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 1500 567 93$ NO SENSOR PROPOSED 0 0.16 234 - 234 $39

1433C.R.

ApplegateArt Class

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

22 61 1.34 1,500 2,013 331$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

22 44 0.97 1500 1452 239$ NO SENSOR PROPOSED 0 0.37 561 - 561 $92

1434C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 109$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 975 328 54$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.10 156 176 332 $55

1435C.R.

ApplegateGirls

4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 57 0.34 2,400 821 135$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 25 0.15 2400 360 59$ NO SENSOR PROPOSED 0 0.19 461 - 461 $76

1436 C.R. Applegate

Girls 23w Compact Fluorescent S/I 2 23 0.05 2,400 110 18$ No Work Proposed 0 23 0.05 2400 110 18$ NO SENSOR PROPOSED 0 - - - - $0

1437C.R.

ApplegateLobby 22-29

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 3,640 888 146$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 3640 641 105$ NO SENSOR PROPOSED 0 0.07 248 - 248 $41

1438C.R.

ApplegateLobby 22-29

4X4 recessed troffer with (8) F32 T8 Lamps & (2) 4-Light Electronic ballasts

8 220 1.76 3,640 6,406 1,054$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

16 84 1.34 3640 4892 805$ NO SENSOR PROPOSED 0 0.42 1,514 - 1,514 $249

1439C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1440C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1441C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1442C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1443C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1444C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1445C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1446C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1447C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

12 61 0.73 1,500 1,098 181$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 44 0.53 1500 792 130$ NO SENSOR PROPOSED 0 0.20 306 - 306 $50

1448C.R.

ApplegateClass

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 1,500 183 30$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 1500 132 22$ NO SENSOR PROPOSED 0 0.03 51 - 51 $8

1449C.R.

ApplegateCustodian Storage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 $4

1450C.R.

ApplegateBoys

4' Strip Fxiture with (1) F32 T12 Lamp & (1) 1L Magnetic Ballast

6 57 0.34 2,400 821 135$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 25 0.15 2400 360 59$ NO SENSOR PROPOSED 0 0.19 461 - 461 $76

1451 C.R. Applegate

Boys 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 9$ No Work Proposed 0 23 0.02 2400 55 9$ NO SENSOR PROPOSED 0 - - - - $0

1452C.R.

ApplegateMain Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

9 89 0.80 2,400 1,922 316$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

9 63 0.57 2400 1361 224$ NO SENSOR PROPOSED 0 0.23 562 - 562 $92

1453C.R.

ApplegateCopy Room

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

2 110 0.22 2,400 528 87$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 84 0.17 2400 403 66$ NO SENSOR PROPOSED 0 0.05 125 - 125 $21

1454C.R.

ApplegatePrincipal

4X4 recessed troffer with (6) F32 T8 Lamps & (2) 3-Light Electronic ballasts

1 178 0.18 2,400 427 70$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 2400 302 50$ NO SENSOR PROPOSED 0 0.05 125 - 125 $21

1455 C.R. Applegate

Corridor 23w Compact Fluorescent S/I 2 23 0.05 3,640 167 28$ No Work Proposed 0 23 0.05 3640 167 28$ NO SENSOR PROPOSED 0 - - - - $0

1456C.R.

ApplegateBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - $0

1457C.R.

ApplegateBathroom 60w. Incandescent S/I 1 60 0.06 2,400 144 24$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 2400 31 5$ NO SENSOR PROPOSED 0 0.05 113 - 113 $19

1458C.R.

ApplegateNurse's Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 211$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 2400 907 149$ NO SENSOR PROPOSED 0 0.16 374 - 374 $62

1459 C.R. Applegate

Corridor 23w Compact Fluorescent S/I 2 23 0.05 3,640 167 28$ No Work Proposed 0 23 0.05 3640 167 28$ NO SENSOR PROPOSED 0 - - - - $0

1460C.R.

ApplegateBathroom

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - $0

1461C.R.

ApplegateBathroom 60w. Incandescent S/I 1 60 0.06 2,400 144 24$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 2400 31 5$ NO SENSOR PROPOSED 0 0.05 113 - 113 $19

1462C.R.

ApplegateGuidence Office

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 89 0.18 2,400 427 70$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 63 0.13 2400 302 50$ NO SENSOR PROPOSED 0 0.05 125 - 125 $21

48 of 52

Page 292: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1463C.R.

ApplegateFaculty room

4X4 recessed troffer with (6) F32 T8 Lamps & (2) 3-Light Electronic ballasts

4 178 0.71 2,400 1,709 281$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 63 0.50 1560 786 129$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.21 499 423 923 $152

1464C.R.

ApplegateKitchen

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 211$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 1560 590 97$ Wall Switch Occupancy Sensor 1 0.16 374 318 692 $114

1465C.R.

ApplegateMen's Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 $13

1466C.R.

ApplegateMen's Room

2' Vanity Fixture with (2) F17 T8 Lamps & (1) 2-Light Electronic Ballast

1 34 0.03 2,400 82 13$ No Work Proposed 0 34 0.03 2400 82 13$ NO SENSOR PROPOSED 0 - - - - $0

1467C.R.

ApplegateBoys

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

3 61 0.18 2,400 439 72$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 2400 317 52$ NO SENSOR PROPOSED 0 0.05 122 - 122 $20

1468 C.R. Applegate

Boys 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 9$ No Work Proposed 0 23 0.02 2400 55 9$ NO SENSOR PROPOSED 0 - - - - $0

1469C.R.

ApplegateWomen's Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 $13

1470C.R.

ApplegateWomen's Room

4' Vanity Fxiture with (2) F32 T8 Lamps & (1) 2L Electronic Ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 $13

1471 C.R. Applegate

Women's Room 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 9$ No Work Proposed 0 23 0.02 2400 55 9$ NO SENSOR PROPOSED 0 - - - - $0

1472C.R.

ApplegateCustodian

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 $3

1473C.R.

ApplegateGirls

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 $13

1474 C.R. Applegate

Girls 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 9$ No Work Proposed 0 23 0.02 2400 55 9$ NO SENSOR PROPOSED 0 - - - - $0

1475C.R.

ApplegateCustodians Office

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 2,400 586 96$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 70$ NO SENSOR PROPOSED 0 0.07 163 - 163 $27

1476C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1477C.R.

ApplegateClass

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 1,500 165 27$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 1500 126 21$ NO SENSOR PROPOSED 0 0.03 39 - 39 $6

1478C.R.

ApplegateBathroom

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 $7

1479 C.R. Applegate

Bathroom 150w Incandescent S/I 1 150 0.15 2,400 360 59$ Re-lamp with 40w Compact Fluorescent 1 40 0.04 2400 96 16$ NO SENSOR PROPOSED 0 0.11 264 - 264 $43

1480C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1481C.R.

ApplegateClass

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 1,500 165 27$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 1500 126 21$ NO SENSOR PROPOSED 0 0.03 39 - 39 $6

1482C.R.

ApplegateBathroom 60w. Incandescent S/I 1 60 0.06 2,400 144 24$

Remove and Replace Existing Lamp With a New 13w Compact Fluorescent Two Piece Screw-In.

1 13 0.01 2400 31 5$ NO SENSOR PROPOSED 0 0.05 113 - 113 $19

1483C.R.

ApplegateClass

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1500 66 11$ NO SENSOR PROPOSED 0 0.02 26 - 26 $4

1484C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1485C.R.

ApplegateClass

4X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballasts

1 110 0.11 1,500 165 27$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 1500 126 21$ NO SENSOR PROPOSED 0 0.03 39 - 39 $6

1486C.R.

ApplegateBathroom

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - $0

1487C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1488C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1489C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

26 61 1.59 1,500 2,379 392$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

26 44 1.14 1500 1716 282$ NO SENSOR PROPOSED 0 0.44 663 - 663 $109

1490C.R.

ApplegateStorage

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 89 0.09 500 45 7$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 63 0.06 500 32 5$ NO SENSOR PROPOSED 0 0.03 13 - 13 $2

1491C.R.

ApplegateRestroom 100w Incandescent S/I 1 100 0.10 2,400 240 40$

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

1 23 0.02 2400 55 9$ NO SENSOR PROPOSED 0 0.08 185 - 185 $30

1492C.R.

ApplegateCoat Room

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1500 66 11$ NO SENSOR PROPOSED 0 0.02 26 - 26 $4

1493 C.R. Applegate

Bathroom 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 9$ No Work Proposed 0 23 0.02 2400 55 9$ NO SENSOR PROPOSED 0 - - - - $0

1494 C.R. Applegate

Storage 23w Compact Fluorescent S/I 1 23 0.02 500 12 2$ No Work Proposed 0 23 0.02 500 12 2$ NO SENSOR PROPOSED 0 - - - - $0

49 of 52

Page 293: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1495C.R.

ApplegateClass

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

18 61 1.10 1,500 1,647 271$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

18 44 0.79 1500 1188 196$ NO SENSOR PROPOSED 0 0.31 459 - 459 $76

1496C.R.

ApplegateCustodian Storage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

8 61 0.49 500 244 40$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

8 44 0.35 500 176 29$ NO SENSOR PROPOSED 0 0.14 68 - 68 $11

1497C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 109$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 1500 504 83$ NO SENSOR PROPOSED 0 0.10 156 - 156 $26

1498C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

4 110 0.44 1,500 660 109$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 84 0.34 975 328 54$ Wall Switch Occupancy Sensor 1 0.10 156 176 332 $55

1499C.R.

ApplegateStorage 100w Incandescent S/I 1 100 0.10 500 50 8$

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

1 23 0.02 500 12 2$ NO SENSOR PROPOSED 0 0.08 39 - 39 $6

1500C.R.

ApplegateElectrical Equipment

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

4 61 0.24 1,000 244 40$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 1000 176 29$ NO SENSOR PROPOSED 0 0.07 68 - 68 $11

1501C.R.

ApplegateStorage 100w Incandescent S/I 3 100 0.30 500 150 25$

Remove and Replace Existing Fixture With a New 1x4 Surface Mounted Wrap Fixture Containing a 1-Lamp Electronic Normal Power Ballast, Reflector

and (1) 4' 28W T8 Energy Saving Lamp.

2 28 0.06 500 28 5$ NO SENSOR PROPOSED 0 0.24 122 - 122 $20

1502C.R.

ApplegateStage

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

33 110 3.63 2,400 8,712 1,434$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

33 84 2.77 2400 6653 1,095$ NO SENSOR PROPOSED 0 0.86 2,059 - 2,059 $339

1503C.R.

ApplegateStage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 $13

1504 C.R. Applegate

Stage Exit Sign w/ 2w LED 2 2 0.00 8,760 35 6$ No Work Proposed 0 2 0.00 8760 35 6$ NO SENSOR PROPOSED 0 - - - - $0

1505C.R.

ApplegateGym Storage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

3 61 0.18 500 92 15$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 500 66 11$ NO SENSOR PROPOSED 0 0.05 26 - 26 $4

1506C.R.

ApplegateGirls Locker

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 $7

1507C.R.

ApplegateGirls Locker

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 $13

1508C.R.

ApplegateGym

High Bay Fixture with (1) 400w Metal Halide Lamp and (1) Magnetic HID Ballast

12 445 5.34 2,400 12,816 2,110$

Remove and Replace Existing Fixture With a New 2x4 Troffer Fixture Containing a 4-Lamp Hi

Output T5 Dimming Ballast, and (4) 4' T5 F54 HO Energy Saving Lamps. Wire Guard Included.

12 234 2.81 2400 6739 1,109$ NO SENSOR PROPOSED 0 2.53 6,077 - 6,077 $1,000

1509C.R.

ApplegateClass

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 1,500 801 132$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 975 369 61$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 234 198 432 $71

1510C.R.

ApplegateVice Principal

2X4 recessed troffer with (3) F32 T8 Lamps & (1) 2-Light Electronic ballast

6 89 0.53 2,400 1,282 211$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 63 0.38 1560 590 97$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 374 318 692 $114

1511C.R.

ApplegateGym Entrances

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 96$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 70$ NO SENSOR PROPOSED 0 0.07 163 - 163 $27

1512C.R.

ApplegateGym Office

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 $13

1513 C.R. Applegate

Gym Office 23w Compact Fluorescent S/I 1 23 0.02 2,400 55 9$ No Work Proposed 0 23 0.02 2400 55 9$ NO SENSOR PROPOSED 0 - - - - $0

1514C.R.

ApplegateGym Office

1X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 $7

1515C.R.

ApplegateBoys Gym Storage

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

1 110 0.11 500 55 9$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 84 0.08 500 42 7$ NO SENSOR PROPOSED 0 0.03 13 - 13 $2

1516 C.R. Applegate

Mechanical Mezzanine 23w Compact Fluorescent S/I 10 23 0.23 1,000 230 38$ No Work Proposed 0 23 0.23 1000 230 38$ NO SENSOR PROPOSED 0 - - - - $0

1517C.R.

ApplegateElectrical Room

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 1,000 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 $3

1518C.R.

ApplegateClass SGI

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

6 110 0.66 1,500 990 163$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 84 0.50 975 491 81$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 234 265 499 $82

1519C.R.

ApplegateSGI

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

6 110 0.66 1,500 990 163$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

6 84 0.50 975 491 81$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.16 234 265 499 $82

1520C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 326$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 975 983 162$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 529 997 $164

1521C.R.

ApplegateSprinkler Valve

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 1,000 183 30$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 1000 132 22$ NO SENSOR PROPOSED 0 0.05 51 - 51 $8

1522C.R.

ApplegateBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1560 69 11$ Wall Switch Occupancy Sensor 1 0.02 41 37 78 $13

1523C.R.

ApplegateInstrumental Music

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

7 110 0.77 1,500 1,155 190$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

7 84 0.59 975 573 94$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.18 273 309 582 $96

50 of 52

Page 294: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1524C.R.

ApplegateInstrumental Music

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 15$ No Work Proposed 0 61 0.06 1500 92 15$ NO SENSOR PROPOSED 0 - - - - $0

1525C.R.

ApplegateVocal Music

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

11 110 1.21 1,500 1,815 299$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

11 84 0.92 975 901 148$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.29 429 485 914 $150

1526C.R.

ApplegateVocal Music

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 1,500 92 15$ No Work Proposed 0 61 0.06 1500 92 15$ NO SENSOR PROPOSED 0 - - - - $0

1527C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 326$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 975 983 162$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 529 997 $164

1528C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 326$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 975 983 162$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 529 997 $164

1529C.R.

ApplegateClass

2X4 recessed troffer with (4) F32 T8 Lamps & (1) 4-Light Electronic ballast

12 110 1.32 1,500 1,980 326$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

12 84 1.01 975 983 162$

Low Voltage (w/ PP-20) PIR Ceiling Sensor (8-15' Mtg. Height) 360 Deg. Coverage 12' Circulur Viewing Pattern

@ 9' High

1 0.31 468 529 997 $164

1530C.R.

ApplegateGirls

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 $13

1531C.R.

ApplegateGirls

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - $0

1532C.R.

ApplegateCustodian Storage

4' Wrap Fixture w/ (2) F32 T8 Lamps & (1) 2-Light Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 $1

1533C.R.

ApplegateBoys

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

2 61 0.12 2,400 293 48$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

2 44 0.09 2400 211 35$ NO SENSOR PROPOSED 0 0.03 82 - 82 $13

1534C.R.

ApplegateBoys

2X2 recessed troffer with (2) F32 T8 U6 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ No Work Proposed 0 61 0.06 2400 146 24$ NO SENSOR PROPOSED 0 - - - - $0

1535C.R.

ApplegateClassroom

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 220$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 156$ NO SENSOR PROPOSED 0 0.26 390 - 390 $64

1536C.R.

ApplegateClassroom

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 211$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 152$ NO SENSOR PROPOSED 0 0.24 357 - 357 $59

1537C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 $1

1538C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 $7

1539C.R.

ApplegateClassroom

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 220$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 156$ NO SENSOR PROPOSED 0 0.26 390 - 390 $64

1540C.R.

ApplegateClassroom

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 211$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 152$ NO SENSOR PROPOSED 0 0.24 357 - 357 $59

1541C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 $1

1542C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 $7

1543C.R.

ApplegateClassroom

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 220$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 156$ NO SENSOR PROPOSED 0 0.26 390 - 390 $64

1544C.R.

ApplegateClassroom

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 211$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 152$ NO SENSOR PROPOSED 0 0.24 357 - 357 $59

1545C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 $1

1546C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 $7

1547C.R.

ApplegateClassroom

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 220$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 156$ NO SENSOR PROPOSED 0 0.26 390 - 390 $64

1548C.R.

ApplegateClassroom

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 211$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 152$ NO SENSOR PROPOSED 0 0.24 357 - 357 $59

1549C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 $1

1550C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 $7

1551 C.R. Applegate

Cafeteria Recessed Can Can w/ (2) 57w CF PL 12 114 1.37 3,640 4,980 820$ No Work Proposed 0 114 1.37 3640 4980 820$ NO SENSOR PROPOSED 0 - - - - $0

1552C.R.

ApplegateCloset

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 $1

51 of 52

Page 295: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Seq. # Building Location Existing Fixture DescriptionExist. Qty of Fix.

Exist. Watts

Exist. kW

Base

Exsit. Oper. Hrs.

Exist. kWh Annual Cost

of Energy Existing

Proposed Fixture DescriptionProp. Qty of

Fixtures

Prop. Watts

Prop. kW Base

Prop. Oper. Hrs.

w/ Sensors

Prop. kWh Annual Cost

of Energy Proposed

Sensor DescriptionSensor Qtys

Total kW Saved

kWh Saved Lighting

Only

kWh Saved Sensors

Only

Total kWh Saved

Energy Cost Savings

Summary of Existing Lighting Systems & Recommended Retrofits under Option 2

1553C.R.

ApplegateKitchen

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

4 61 0.24 2,400 586 96$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

4 44 0.18 2400 422 70$ NO SENSOR PROPOSED 0 0.07 163 - 163 $27

1554C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 $1

1555 C.R. Applegate

MPR Recessed Can Can w/ (2) 57w CF PL 13 114 1.48 2,400 3,557 585$ No Work Proposed 0 114 1.48 2400 3557 585$ NO SENSOR PROPOSED 0 - - - - $0

1556C.R.

ApplegateStorage

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 $1

1557C.R.

ApplegateBathroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 $7

1558C.R.

ApplegateCustodian

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

1 61 0.06 1,000 61 10$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 1000 44 7$ NO SENSOR PROPOSED 0 0.02 17 - 17 $3

1559C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 $7

1560C.R.

ApplegateClassroom

4' Direct/Indirect Fxiture with (3) F32 T8 Lamps & (1) 3L Electronic Ballast

10 89 0.89 1,500 1,335 220$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

10 63 0.63 1500 945 156$ NO SENSOR PROPOSED 0 0.26 390 - 390 $64

1561C.R.

ApplegateClassroom

4' Direct/Indirect Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

14 61 0.85 1,500 1,281 211$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

14 44 0.62 1500 924 152$ NO SENSOR PROPOSED 0 0.24 357 - 357 $59

1562C.R.

ApplegateStorage

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 500 31 5$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 500 22 4$ NO SENSOR PROPOSED 0 0.02 9 - 9 $1

1563C.R.

ApplegateRestroom

2X4 recessed troffer with (2) F32 T8 Lamps & (1) 2-Light Electronic ballast

1 61 0.06 2,400 146 24$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

1 44 0.04 2400 106 17$ NO SENSOR PROPOSED 0 0.02 41 - 41 $7

1564C.R.

ApplegateSprinkler Valve

Industrial Hood 4' Fixture w/ (2) F32 T/ Lamps & (1) 2L Electronic Ballast

3 61 0.18 1,000 183 30$ Re-lamp existing fixture with an Energy Saving

28w Lamp to standardize lamp types for maintenance. Existing Ballast stays in place

3 44 0.13 1000 132 22$ NO SENSOR PROPOSED 0 0.05 51 - 51 $8

1565C.R.

ApplegateOutside 100w Incandescent S/I 8 100 0.80 3,640 2,912 479$

Remove and Replace Existing Lamp With a New 23w Compact Fluorescent Two Piece Screw-In.

8 23 0.18 3640 670 110$ NO SENSOR PROPOSED 0 0.62 2,242 - 2,242 $369

1566C.R.

ApplegateOutside

Wall Pack Fixture with (1) 175w Mercury Vapor Lamp and (1) Magnetic HID Ballast

38 205 7.79 3,640 28,356 4,667$ Remove and Replace Existing Fixture With a New Outdoor Flood Fixture Containing a 150w Pulse

Metal Halide Lamp38 85 3.23 3640 11757 1,935$ NO SENSOR PROPOSED 0 4.56 16,598 - 16,598 $2,732

1567C.R.

ApplegateOutside

Wall Pack Fixture with (1) 100w Metal Halide Lamp and (1) Magnetic HID Ballast

22 120 2.64 3,640 9,610 1,582$ No Work Proposed 0 120 2.64 3640 9610 1,582$ NO SENSOR PROPOSED 0 - - - - $0

1568C.R.

ApplegateOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 400w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast4 445 1.78 3,640 6,479 1,066$ No Work Proposed 0 445 1.78 3640 6479 1,066$ NO SENSOR PROPOSED 0 - - - - $0

1569C.R.

ApplegateOutside

Parking Lot Fixture Mounted on a Pole w/ (1) 250w Probe Start Metal Halide Lamp

and (1) Magnetic HID Ballast2 286 0.57 3,640 2,082 343$ No Work Proposed 0 286 0.57 3640 2082 343$ NO SENSOR PROPOSED 0 - - - - $0

16 30 66820 5502 72322 $11,904

11,127 962.32 2,179,177 356,050$ 9,703 720.58 1,608,546 262,665$ 184 241.73 512,135 58,496 570,631 $93,276

Totals for Lighting System Upgrades at C.R. Applegate:

52 of 52

Page 296: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

APPENDIX F

SOLAR ENERGY FINANCING WORKSHEET

Page 297: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 298: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

District Owns System Pro FormaSize of PV System (kW dc) 974.85Total System Cost 6,331,000$ NJCEP Rebate NoneCost of System After Rebate 6,331,000$ Variables and Assumptions:kWh ac generated Year 1 1,103,332 Percentage of annual degradation 0.50%Today's Cost Per Unit of Grid Electricity $0.160Annual inflation rate 4.00%Value of SRECs per kWh at current price Conservative Forecast based on % of cap15 Year Bond Rate 4.00%Debt Service Aid Percentage (% of System Cost After Rebate) 40%Term (Years) 15

EstAnnual Price Annual 1 2 3 4 5 6 7 8 9

Year kWh per kWh Maint. Avoided Cost Solar Project 15 Year Yearly Plus Yearly Plus YearlyCost of Grid Energy RECs Income G.O. Bond Balance DSA Balance CREB Award Balance

1 1,103,332 $0.1600 -$22,067 $176,533 $539,529 $693,996 -$561,956 $132,040 $224,782 $356,822 $31,050 $387,8732 1,097,815 $0.1664 -$21,956 $182,676 $520,364 $681,085 -$561,956 $119,129 $224,782 $343,911 $29,443 $373,3553 1,092,326 $0.1731 -$21,847 $189,034 $502,470 $669,657 -$561,956 $107,701 $224,782 $332,484 $27,771 $360,2544 1,086,865 $0.1800 -$21,737 $195,612 $484,742 $658,616 -$561,956 $96,661 $224,782 $321,443 $26,030 $347,4735 1,081,430 $0.1872 -$21,629 $202,419 $468,259 $649,050 -$561,956 $87,094 $224,782 $311,877 $24,218 $336,0956 1,076,023 $0.1947 -$21,520 $209,463 $423,953 $611,896 -$561,956 $49,940 $224,782 $274,723 $22,333 $297,0567 1,070,643 $0.2025 -$21,413 $216,753 $408,986 $604,326 -$561,956 $42,370 $224,782 $267,152 $20,371 $287,5238 1,065,290 $0.2105 -$21,306 $224,296 $395,223 $598,213 -$561,956 $36,257 $224,782 $261,039 $18,329 $279,3689 1,059,963 $0.2190 -$21,199 $232,101 $380,527 $591,429 -$561,956 $29,473 $224,782 $254,255 $16,203 $270,459

10 1,054,664 $0.2277 -$21,093 $240,178 $369,132 $588,217 -$561,956 $26,262 $224,782 $251,044 $13,991 $265,03511 1,049,390 $0.2368 -$20,988 $248,537 $367,287 $594,835 -$561,956 $32,880 $224,782 $257,662 $11,689 $269,35112 1,044,143 $0.2463 -$20,883 $257,186 $365,450 $601,753 -$561,956 $39,797 $224,782 $264,580 $9,293 $273,87313 1,038,923 $0.2562 -$20,778 $266,136 $363,623 $608,980 -$561,956 $47,025 $224,782 $271,807 $6,800 $278,60714 1,033,728 $0.2664 -$20,675 $275,397 $361,805 $616,528 -$561,956 $54,572 $224,782 $279,354 $4,205 $283,55915 1,028,559 $0.2771 -$20,571 $284,981 $359,996 $624,406 -$561,956 $62,450 $224,782 $287,232 $1,504 $288,73616 1,023,417 $0.2882 -$20,468 $294,898 $274,430 $274,430 $0 $274,430 $274,43017 1,018,299 $0.2997 -$20,366 $305,161 $284,795 $284,795 $0 $284,795 $284,79518 1,013,208 $0.3117 -$20,264 $315,781 $295,516 $295,516 $0 $295,516 $295,51619 1,008,142 $0.3241 -$20,163 $326,770 $306,607 $306,607 $0 $306,607 $306,60720 1,003,101 $0.3371 -$20,062 $338,141 $318,079 $318,079 $0 $318,079 $318,07921 998,086 $0.3506 -$19,962 $349,909 $329,947 $329,947 $0 $329,947 $329,94722 993,095 $0.3646 -$19,862 $362,085 $342,223 $342,223 $0 $342,223 $342,22323 988,130 $0.3792 -$19,763 $374,686 $354,923 $354,923 $0 $354,923 $354,92324 983,189 $0.3944 -$19,664 $387,725 $368,061 $368,061 $0 $368,061 $368,06125 978,273 $0.4101 -$19,565 $401,218 $381,652 $381,652 $0 $381,652 $381,652

-$519,801 $6,857,676 $6,311,345 $12,649,221 -$8,429,336 $4,219,886 $3,371,734 $7,591,620 $263,231 $7,854,851

Preliminary Solar Power Financing Worksheet - Freehold Township School District(Projections assume project will be implemented in accordance with NJBPU guidelines; however actual future SREC values will vary depending on market conditions)

Clean Renewable Energy Bond (CREB) is based on federal program guidelines which have not yet been approved for 2009.

Project Cashflows Possible Financing Options Addl CREB Benefits If Applicable

Financing – strategies and options

Page 299: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 300: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

APPENDIX G

GLACIAL ENERGY – ALTERNATIVE ELECTRIC SUPPLIER QUOTE

Page 301: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 302: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Secure your savings today!

Contract Summary - Forecasted Price Comparison

Company Name: Freehold Board of Education - DD Eisenhower

Billing Address: 279 Burlington Rd, Freehold, NJ 07728

Forecasted Customer Usage Data Summary

Start Month: Jul-09

Number of LDC Accounts: 1 Usage (kwh): 1,926,165

Retail Margin Adder: N/A Avg Monthly Usage (kwh): 160,514

Peak Monthly kw: 720

Peak Load Factor: 31%

Estimated Rate Comparison over the next 12 months Capacity PLC: 345

Transmission PLC: 336

Avg Rate ($/kwh)*: 0.11874$

Annual Utility Charges: 228,706$ Savings Summary

Glacial Energy Index: 0.09628$ Estimated Savings vs. Utility 43,253$

Glacial Charges: 185,453$ Savings (Glacial vs. Utility) 19%

0.1250

0.1500

Rate

s (

$/k

wh

)

Glacial Energy Index - Forecast Rate Comparison

Glacial Index Includes:

a. Estimated weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above) LDC Account No: Physical Address:

c. Unaccounted for Energy (UFE) 1 '08018704390000435756

1. The Glacial Index price is based in large part on forecasted ISO charges and estimated future zonal energy prices.

2. The forward tariff rates are based on the latest, pending or estimated utility rates (inclusive of NJ SUT), applicable for this rate schedule(s).

Rate listed is an average over the next 12 months. Your current average utility rate for July 2009 is $0.12615/kwh.

graph above, beyond 7/31/2009 reflect published rate changes and/or rate estimations.

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Board of Education - DD Eisenhower

279 Burlington Rd, Freehold, NJ 07728

0.0500

0.0750

0.1000

0.1250

0.1500

Jul-09 Aug-09 Sep-09 Oct-09 Nov-09 Dec-09 Jan-10 Feb-10 Mar-10 Apr-10 May-10 Jun-10

Rate

s (

$/k

wh

)

Billing Month

Glacial Energy Index - Forecast Rate Comparison

Glacial Index

JCP&L Rate

-

100,000

200,000

300,000

kw

h

Historical Customer Usage Data

Page 303: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Contract Summary - Historical Utility Charges

Company Name: Freehold Board of Education - DD Eisenhower

Billing Address: 279 Burlington Rd, Freehold, NJ 07728

Historical Timeframe (mo.): 6

Start Month: Dec-08 6 month Period Summary

Number of LDC Accounts: 1

Usage (kwh): 1,296,008

Estimated Historical Utility Charges Avg Monthly Usage (kwh): 216,001

Peak Monthly kw: 720

Peak Load Factor: 41%

Avg Rate ($/kwh): 0.11132$ Capacity PLC: 345

Annual Utility Charges: 144,278$ Transmission PLC: 336

Glacial Energy Index: 0.09363$ Savings Summary

Glacial Charges: 121,349$

Estimated Savings vs. Utility 22,928$

Savings (Glacial vs. Utility) 16%

0.1500Glacial Energy Index - Estimated Historical Rate Comparison

Glacial Index Includes:

a. Estimated Weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT Taxes

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above)

c. Unaccounted for Energy (UFE)

1. The historic tariff rate comparison is based on historical usage and current, pending or estimated utility rates (inclusive of NJ SUT) for the appropriate rate schedule(s).

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Board of Education - DD Eisenhower

0.0500

0.0750

0.1000

0.1250

0.1500

Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09

Rate

s (

$/k

wh

)

Billing Months

Glacial Energy Index - Estimated Historical Rate Comparison

JCPL Rate

Glacial Index

Page 304: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Secure your savings today!

Contract Summary - Forecasted Price Comparison

Company Name: Freehold Township Board of Education - JJ Catena

Billing Address: 275 Burlington Rd, Freehold, NJ 07728

Forecasted Customer Usage Data Summary

Start Month: Jul-09

Number of LDC Accounts: 1 Usage (kwh): 1,034,978

Retail Margin Adder: N/A Avg Monthly Usage (kwh): 86,248

Peak Monthly kw: 374

Peak Load Factor: 32%

Estimated Rate Comparison over the next 12 months Capacity PLC: 220

Transmission PLC: 214

Avg Rate ($/kwh)*: 0.12204$

Annual Utility Charges: 126,310$ Savings Summary

Glacial Energy Index: 0.09680$ Estimated Savings vs. Utility 26,123$

Glacial Charges: 100,187$ Savings (Glacial vs. Utility) 21%

0.1250

0.1500

Rate

s (

$/k

wh

)

Glacial Energy Index - Forecast Rate Comparison

Glacial Index Includes:

a. Estimated weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above) LDC Account No: Physical Address:

c. Unaccounted for Energy (UFE) 1 '08018704390000435755

1. The Glacial Index price is based in large part on forecasted ISO charges and estimated future zonal energy prices.

2. The forward tariff rates are based on the latest, pending or estimated utility rates (inclusive of NJ SUT), applicable for this rate schedule(s).

Rate listed is an average over the next 12 months. Your current average utility rate for July 2009 is $0.13824/kwh.

graph above, beyond 7/31/2009 reflect published rate changes and/or rate estimations.

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - JJ Catena

275 Burlington Rd, Freehold, NJ 07728

0.0500

0.0750

0.1000

0.1250

0.1500

Jul-09 Aug-09 Sep-09 Oct-09 Nov-09 Dec-09 Jan-10 Feb-10 Mar-10 Apr-10 May-10 Jun-10

Rate

s (

$/k

wh

)

Billing Month

Glacial Energy Index - Forecast Rate Comparison

Glacial Index

JCP&L Rate

-

30,000

60,000

90,000

120,000

kw

h

Historical Customer Usage Data

Page 305: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Contract Summary - Historical Utility Charges

Company Name: Freehold Township Board of Education - JJ Catena

Billing Address: 275 Burlington Rd, Freehold, NJ 07728

Historical Timeframe (mo.): 6

Start Month: Dec-08 6 month Period Summary

Number of LDC Accounts: 1

Usage (kwh): 594,524

Estimated Historical Utility Charges Avg Monthly Usage (kwh): 99,087

Peak Monthly kw: 374

Peak Load Factor: 36%

Avg Rate ($/kwh): 0.11082$ Capacity PLC: 220

Annual Utility Charges: 65,886$ Transmission PLC: 214

Glacial Energy Index: 0.09176$ Savings Summary

Glacial Charges: 54,555$

Estimated Savings vs. Utility 11,331$

Savings (Glacial vs. Utility) 17%

0.1500Glacial Energy Index - Estimated Historical Rate Comparison

Glacial Index Includes:

a. Estimated Weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT Taxes

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above)

c. Unaccounted for Energy (UFE)

1. The historic tariff rate comparison is based on historical usage and current, pending or estimated utility rates (inclusive of NJ SUT) for the appropriate rate schedule(s).

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - JJ Catena

0.0500

0.0750

0.1000

0.1250

0.1500

Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09

Rate

s (

$/k

wh

)

Billing Months

Glacial Energy Index - Estimated Historical Rate Comparison

JCPL Rate

Glacial Index

Page 306: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Secure your savings today!

Contract Summary - Forecasted Price Comparison

Company Name: Freehold Township Board of Education - Barkalow

Billing Address: 498 Stillwells Corner Rd, Freehold, NJ 07728

Forecasted Customer Usage Data Summary

Start Month: Jul-09

Number of LDC Accounts: 1 Usage (kwh): 1,454,940

Retail Margin Adder: N/A Avg Monthly Usage (kwh): 121,245

Peak Monthly kw: 514

Peak Load Factor: 32%

Estimated Rate Comparison over the next 12 months Capacity PLC: 353

Transmission PLC: 343

Avg Rate ($/kwh)*: 0.12221$

Annual Utility Charges: 177,815$ Savings Summary

Glacial Energy Index: 0.09911$ Estimated Savings vs. Utility 33,613$

Glacial Charges: 144,202$ Savings (Glacial vs. Utility) 19%

0.1250

0.1500

Rate

s (

$/k

wh

)

Glacial Energy Index - Forecast Rate Comparison

Glacial Index Includes:

a. Estimated weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above) LDC Account No: Physical Address:

c. Unaccounted for Energy (UFE) 1 '08018704390000658762

1. The Glacial Index price is based in large part on forecasted ISO charges and estimated future zonal energy prices.

2. The forward tariff rates are based on the latest, pending or estimated utility rates (inclusive of NJ SUT), applicable for this rate schedule(s).

Rate listed is an average over the next 12 months. Your current average utility rate for July 2009 is $0.13037/kwh.

graph above, beyond 7/31/2009 reflect published rate changes and/or rate estimations.

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - Barkalow

498 Stillwells Corner Rd, Freehold, NJ 07728

0.0500

0.0750

0.1000

0.1250

0.1500

Jul-09 Aug-09 Sep-09 Oct-09 Nov-09 Dec-09 Jan-10 Feb-10 Mar-10 Apr-10 May-10 Jun-10

Rate

s (

$/k

wh

)

Billing Month

Glacial Energy Index - Forecast Rate Comparison

Glacial Index

JCP&L Rate

-

50,000

100,000

150,000

200,000

kw

h

Historical Customer Usage Data

Page 307: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Contract Summary - Historical Utility Charges

Company Name: Freehold Township Board of Education - Barkalow

Billing Address: 498 Stillwells Corner Rd, Freehold, NJ 07728

Historical Timeframe (mo.): 6

Start Month: Dec-08 6 month Period Summary

Number of LDC Accounts: 1

Usage (kwh): 792,554

Estimated Historical Utility Charges Avg Monthly Usage (kwh): 132,092

Peak Monthly kw: 514

Peak Load Factor: 35%

Avg Rate ($/kwh): 0.11087$ Capacity PLC: 353

Annual Utility Charges: 87,873$ Transmission PLC: 343

Glacial Energy Index: 0.09298$ Savings Summary

Glacial Charges: 73,694$

Estimated Savings vs. Utility 14,179$

Savings (Glacial vs. Utility) 16%

0.1500Glacial Energy Index - Estimated Historical Rate Comparison

Glacial Index Includes:

a. Estimated Weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT Taxes

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above)

c. Unaccounted for Energy (UFE)

1. The historic tariff rate comparison is based on historical usage and current, pending or estimated utility rates (inclusive of NJ SUT) for the appropriate rate schedule(s).

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - Barkalow

0.0500

0.0750

0.1000

0.1250

0.1500

Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09

Rate

s (

$/k

wh

)

Billing Months

Glacial Energy Index - Estimated Historical Rate Comparison

JCPL Rate

Glacial Index

Page 308: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Secure your savings today!

Contract Summary - Forecasted Price Comparison

Company Name: Freehold Township Board of Education - Early Ed

Billing Address: 384 West Main Street, Freehold, NJ 07728

Forecasted Customer Usage Data Summary

Start Month: Jul-09

Number of LDC Accounts: 1 Usage (kwh): 500,736

Retail Margin Adder: N/A Avg Monthly Usage (kwh): 41,728

Peak Monthly kw: 182

Peak Load Factor: 31%

Estimated Rate Comparison over the next 12 months Capacity PLC: 123

Transmission PLC: 120

Avg Rate ($/kwh)*: 0.12232$

Annual Utility Charges: 61,249$ Savings Summary

Glacial Energy Index: 0.09946$ Estimated Savings vs. Utility 11,444$

Glacial Charges: 49,805$ Savings (Glacial vs. Utility) 19%

0.1250

0.1500

Rate

s (

$/k

wh

)

Glacial Energy Index - Forecast Rate Comparison

Glacial Index Includes:

a. Estimated weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above) LDC Account No: Physical Address:

c. Unaccounted for Energy (UFE) 1 '08018704390000388850

1. The Glacial Index price is based in large part on forecasted ISO charges and estimated future zonal energy prices.

2. The forward tariff rates are based on the latest, pending or estimated utility rates (inclusive of NJ SUT), applicable for this rate schedule(s).

Rate listed is an average over the next 12 months. Your current average utility rate for July 2009 is $0.13352/kwh.

graph above, beyond 7/31/2009 reflect published rate changes and/or rate estimations.

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - Early Ed

384 West Main Street, Freehold, NJ 07728

0.0500

0.0750

0.1000

0.1250

0.1500

Jul-09 Aug-09 Sep-09 Oct-09 Nov-09 Dec-09 Jan-10 Feb-10 Mar-10 Apr-10 May-10 Jun-10

Rate

s (

$/k

wh

)

Billing Month

Glacial Energy Index - Forecast Rate Comparison

Glacial Index

JCP&L Rate

-

10,000

20,000

30,000

40,000

50,000

60,000

kw

h

Historical Customer Usage Data

Page 309: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Contract Summary - Historical Utility Charges

Company Name: Freehold Township Board of Education - Early Ed

Billing Address: 384 West Main Street, Freehold, NJ 07728

Historical Timeframe (mo.): 6

Start Month: Dec-08 6 month Period Summary

Number of LDC Accounts: 1

Usage (kwh): 276,036

Estimated Historical Utility Charges Avg Monthly Usage (kwh): 46,006

Peak Monthly kw: 182

Peak Load Factor: 35%

Avg Rate ($/kwh): 0.11087$ Capacity PLC: 123

Annual Utility Charges: 30,604$ Transmission PLC: 120

Glacial Energy Index: 0.09321$ Savings Summary

Glacial Charges: 25,728$

Estimated Savings vs. Utility 4,876$

Savings (Glacial vs. Utility) 16%

0.1500Glacial Energy Index - Estimated Historical Rate Comparison

Glacial Index Includes:

a. Estimated Weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT Taxes

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above)

c. Unaccounted for Energy (UFE)

1. The historic tariff rate comparison is based on historical usage and current, pending or estimated utility rates (inclusive of NJ SUT) for the appropriate rate schedule(s).

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - Early Ed

0.0500

0.0750

0.1000

0.1250

0.1500

Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09

Rate

s (

$/k

wh

)

Billing Months

Glacial Energy Index - Estimated Historical Rate Comparison

JCPL Rate

Glacial Index

Page 310: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Secure your savings today!

Contract Summary - Forecasted Price Comparison

Company Name: Freehold Township Board of Education - MW Erikson

Billing Address: 271 Elton Adephia Rd, Freehold, NJ 07728

Forecasted Customer Usage Data Summary

Start Month: Jul-09

Number of LDC Accounts: 1 Usage (kwh): 759,925

Retail Margin Adder: N/A Avg Monthly Usage (kwh): 63,327

Peak Monthly kw: 323

Peak Load Factor: 27%

Estimated Rate Comparison over the next 12 months Capacity PLC: 263

Transmission PLC: 255

Avg Rate ($/kwh)*: 0.12385$

Annual Utility Charges: 94,120$ Savings Summary

Glacial Energy Index: 0.10198$ Estimated Savings vs. Utility 16,626$

Glacial Charges: 77,494$ Savings (Glacial vs. Utility) 18%

0.1250

0.1500

Rate

s (

$/k

wh

)

Glacial Energy Index - Forecast Rate Comparison

Glacial Index Includes:

a. Estimated weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above) LDC Account No: Physical Address:

c. Unaccounted for Energy (UFE) 1 '08018704390000658424

1. The Glacial Index price is based in large part on forecasted ISO charges and estimated future zonal energy prices.

2. The forward tariff rates are based on the latest, pending or estimated utility rates (inclusive of NJ SUT), applicable for this rate schedule(s).

Rate listed is an average over the next 12 months. Your current average utility rate for July 2009 is $0.13249/kwh.

graph above, beyond 7/31/2009 reflect published rate changes and/or rate estimations.

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - MW Erikson

271 Elton Adephia Rd, Freehold, NJ 07728

0.0500

0.0750

0.1000

0.1250

0.1500

Jul-09 Aug-09 Sep-09 Oct-09 Nov-09 Dec-09 Jan-10 Feb-10 Mar-10 Apr-10 May-10 Jun-10

Rate

s (

$/k

wh

)

Billing Month

Glacial Energy Index - Forecast Rate Comparison

Glacial Index

JCP&L Rate

-

25,000

50,000

75,000

100,000

125,000

kw

h

Historical Customer Usage Data

Page 311: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Contract Summary - Historical Utility Charges

Company Name: Freehold Township Board of Education - MW Erikson

Billing Address: 271 Elton Adephia Rd, Freehold, NJ 07728

Historical Timeframe (mo.): 6

Start Month: Dec-08 6 month Period Summary

Number of LDC Accounts: 1

Usage (kwh): 375,956

Estimated Historical Utility Charges Avg Monthly Usage (kwh): 62,659

Peak Monthly kw: 323

Peak Load Factor: 27%

Avg Rate ($/kwh): 0.11085$ Capacity PLC: 263

Annual Utility Charges: 41,674$ Transmission PLC: 255

Glacial Energy Index: 0.09272$ Savings Summary

Glacial Charges: 34,859$

Estimated Savings vs. Utility 6,815$

Savings (Glacial vs. Utility) 16%

0.1500Glacial Energy Index - Estimated Historical Rate Comparison

Glacial Index Includes:

a. Estimated Weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT Taxes

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above)

c. Unaccounted for Energy (UFE)

1. The historic tariff rate comparison is based on historical usage and current, pending or estimated utility rates (inclusive of NJ SUT) for the appropriate rate schedule(s).

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - MW Erikson

0.0500

0.0750

0.1000

0.1250

0.1500

Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09

Rate

s (

$/k

wh

)

Billing Months

Glacial Energy Index - Estimated Historical Rate Comparison

JCPL Rate

Glacial Index

Page 312: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Secure your savings today!

Contract Summary - Forecasted Price Comparison

Company Name: Freehold Township Board of Education - Laura Donovan

Billing Address: 237 Stonehurst Blvd, Freehold, NJ 07728

Forecasted Customer Usage Data Summary

Start Month: Jul-09

Number of LDC Accounts: 1 Usage (kwh): 1,344,566

Retail Margin Adder: N/A Avg Monthly Usage (kwh): 112,047

Peak Monthly kw: 587

Peak Load Factor: 26%

Estimated Rate Comparison over the next 12 months Capacity PLC: 242

Transmission PLC: 235

Avg Rate ($/kwh)*: 0.12055$

Annual Utility Charges: 162,083$ Savings Summary

Glacial Energy Index: 0.09879$ Estimated Savings vs. Utility 29,258$

Glacial Charges: 132,825$ Savings (Glacial vs. Utility) 18%

0.1250

0.1500

Rate

s (

$/k

wh

)

Glacial Energy Index - Forecast Rate Comparison

Glacial Index Includes:

a. Estimated weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above) LDC Account No: Physical Address:

c. Unaccounted for Energy (UFE) 1 '08018704390000474310

1. The Glacial Index price is based in large part on forecasted ISO charges and estimated future zonal energy prices.

2. The forward tariff rates are based on the latest, pending or estimated utility rates (inclusive of NJ SUT), applicable for this rate schedule(s).

Rate listed is an average over the next 12 months. Your current average utility rate for July 2009 is $0.13745/kwh.

graph above, beyond 7/31/2009 reflect published rate changes and/or rate estimations.

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - Laura Donovan

237 Stonehurst Blvd, Freehold, NJ 07728

0.0500

0.0750

0.1000

0.1250

0.1500

Jul-09 Aug-09 Sep-09 Oct-09 Nov-09 Dec-09 Jan-10 Feb-10 Mar-10 Apr-10 May-10 Jun-10

Rate

s (

$/k

wh

)

Billing Month

Glacial Energy Index - Forecast Rate Comparison

Glacial Index

JCP&L Rate

25,000

75,000

125,000

175,000

kw

h

Historical Customer Usage Data

Page 313: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Contract Summary - Historical Utility Charges

Company Name: Freehold Township Board of Education - Laura Donovan

Billing Address: 237 Stonehurst Blvd, Freehold, NJ 07728

Historical Timeframe (mo.): 6

Start Month: Dec-08 6 month Period Summary

Number of LDC Accounts: 1

Usage (kwh): 901,222

Estimated Historical Utility Charges Avg Monthly Usage (kwh): 150,204

Peak Monthly kw: 587

Peak Load Factor: 35%

Avg Rate ($/kwh): 0.11122$ Capacity PLC: 242

Annual Utility Charges: 100,232$ Transmission PLC: 235

Glacial Energy Index: 0.09458$ Savings Summary

Glacial Charges: 85,240$

Estimated Savings vs. Utility 14,992$

Savings (Glacial vs. Utility) 15%

0.1500Glacial Energy Index - Estimated Historical Rate Comparison

Glacial Index Includes:

a. Estimated Weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT Taxes

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above)

c. Unaccounted for Energy (UFE)

1. The historic tariff rate comparison is based on historical usage and current, pending or estimated utility rates (inclusive of NJ SUT) for the appropriate rate schedule(s).

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - Laura Donovan

0.0500

0.0750

0.1000

0.1250

0.1500

Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09

Rate

s (

$/k

wh

)

Billing Months

Glacial Energy Index - Estimated Historical Rate Comparison

JCPL Rate

Glacial Index

Page 314: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Secure your savings today!

Contract Summary - Forecasted Price Comparison

Company Name: Freehold Township Board of Education - W Freehold

Billing Address: W Main Street, Freehold, NJ 07728

Forecasted Customer Usage Data Summary

Start Month: Jul-09

Number of LDC Accounts: 1 Usage (kwh): 2,398,673

Retail Margin Adder: N/A Avg Monthly Usage (kwh): 199,889

Peak Monthly kw: 862

Peak Load Factor: 32%

Estimated Rate Comparison over the next 12 months Capacity PLC: 436

Transmission PLC: 424

Avg Rate ($/kwh)*: 0.12390$

Annual Utility Charges: 297,198$ Savings Summary

Glacial Energy Index: 0.09849$ Estimated Savings vs. Utility 60,953$

Glacial Charges: 236,246$ Savings (Glacial vs. Utility) 21%

0.1250

0.1500

Rate

s (

$/k

wh

)

Glacial Energy Index - Forecast Rate Comparison

Glacial Index Includes:

a. Estimated weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above) LDC Account No: Physical Address:

c. Unaccounted for Energy (UFE) 1 '08018704390006269062

1. The Glacial Index price is based in large part on forecasted ISO charges and estimated future zonal energy prices.

2. The forward tariff rates are based on the latest, pending or estimated utility rates (inclusive of NJ SUT), applicable for this rate schedule(s).

Rate listed is an average over the next 12 months. Your current average utility rate for July 2009 is $0.13111/kwh.

graph above, beyond 7/31/2009 reflect published rate changes and/or rate estimations.

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - W Freehold

W Main Street, Freehold, NJ 07728

0.0500

0.0750

0.1000

0.1250

0.1500

Jul-09 Aug-09 Sep-09 Oct-09 Nov-09 Dec-09 Jan-10 Feb-10 Mar-10 Apr-10 May-10 Jun-10

Rate

s (

$/k

wh

)

Billing Month

Glacial Energy Index - Forecast Rate Comparison

Glacial Index

JCP&L Rate

-

100,000

200,000

300,000

kw

h

Historical Customer Usage Data

Page 315: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Contract Summary - Historical Utility Charges

Company Name: Freehold Township Board of Education - W Freehold

Billing Address: W Main Street, Freehold, NJ 07728

Historical Timeframe (mo.): 6

Start Month: Dec-08 6 month Period Summary

Number of LDC Accounts: 1

Usage (kwh): 1,561,341

Estimated Historical Utility Charges Avg Monthly Usage (kwh): 260,224

Peak Monthly kw: 862

Peak Load Factor: 41%

Avg Rate ($/kwh): 0.11656$ Capacity PLC: 436

Annual Utility Charges: 181,990$ Transmission PLC: 424

Glacial Energy Index: 0.09518$ Savings Summary

Glacial Charges: 148,609$

Estimated Savings vs. Utility 33,382$

Savings (Glacial vs. Utility) 18%

0.1500Glacial Energy Index - Estimated Historical Rate Comparison

Glacial Index Includes:

a. Estimated Weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT Taxes

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above)

c. Unaccounted for Energy (UFE)

1. The historic tariff rate comparison is based on historical usage and current, pending or estimated utility rates (inclusive of NJ SUT) for the appropriate rate schedule(s).

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - W Freehold

0.0500

0.0750

0.1000

0.1250

0.1500

Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09

Rate

s (

$/k

wh

)

Billing Months

Glacial Energy Index - Estimated Historical Rate Comparison

JCPL Rate

Glacial Index

Page 316: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Secure your savings today!

Contract Summary - Forecasted Price Comparison

Company Name: Freehold Township Board of Education - Applegate

Billing Address: 47 Brennan Drive, Freehold, NJ 07728

Forecasted Customer Usage Data Summary

Start Month: Jul-09

Number of LDC Accounts: 1 Usage (kwh): 940,879

Retail Margin Adder: N/A Avg Monthly Usage (kwh): 78,407

Peak Monthly kw: 508

Peak Load Factor: 21%

Estimated Rate Comparison over the next 12 months Capacity PLC: 209

Transmission PLC: 203

Avg Rate ($/kwh)*: 0.12686$

Annual Utility Charges: 119,359$ Savings Summary

Glacial Energy Index: 0.09757$ Estimated Savings vs. Utility 27,553$

Glacial Charges: 91,806$ Savings (Glacial vs. Utility) 23%

0.1750

Rate

s (

$/k

wh

)

Glacial Energy Index - Forecast Rate Comparison

Glacial Index Includes:

a. Estimated weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above) LDC Account No: Physical Address:

c. Unaccounted for Energy (UFE) 1 '08018704390000389177

1. The Glacial Index price is based in large part on forecasted ISO charges and estimated future zonal energy prices.

2. The forward tariff rates are based on the latest, pending or estimated utility rates (inclusive of NJ SUT), applicable for this rate schedule(s).

Rate listed is an average over the next 12 months. Your current average utility rate for July 2009 is $0.15138/kwh.

graph above, beyond 7/31/2009 reflect published rate changes and/or rate estimations.

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - Applegate

47 Brennan Drive, Freehold, NJ 07728

0.0250

0.0750

0.1250

0.1750

Jul-09 Aug-09 Sep-09 Oct-09 Nov-09 Dec-09 Jan-10 Feb-10 Mar-10 Apr-10 May-10 Jun-10

Rate

s (

$/k

wh

)

Billing Month

Glacial Energy Index - Forecast Rate Comparison

Glacial Index

JCP&L Rate

-

20,000

40,000

60,000

80,000

100,000

kw

h

Historical Customer Usage Data

Page 317: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Savings Analysis Proposal - JCP&L

This proposal illustrates how you can maximize your energy cost savings by choosing Glacial Energy as your preferred electricity supplier.

This proposal is based on your organization's estimated usage (kwh) and demand (kw) over the coming year.

Contract Summary - Historical Utility Charges

Company Name: Freehold Township Board of Education - Applegate

Billing Address: 47 Brennan Drive, Freehold, NJ 07728

Historical Timeframe (mo.): 6

Start Month: Dec-08 6 month Period Summary

Number of LDC Accounts: 1

Usage (kwh): 538,566

Estimated Historical Utility Charges Avg Monthly Usage (kwh): 89,761

Peak Monthly kw: 508

Peak Load Factor: 24%

Avg Rate ($/kwh): 0.11091$ Capacity PLC: 209

Annual Utility Charges: 59,732$ Transmission PLC: 203

Glacial Energy Index: 0.09128$ Savings Summary

Glacial Charges: 49,162$

Estimated Savings vs. Utility 10,569$

Savings (Glacial vs. Utility) 18%

0.1750Glacial Energy Index - Estimated Historical Rate Comparison

Glacial Index Includes:

a. Estimated Weighted average Wholesale Energy price

b. Ancillary Services & requirements

c. Zonal Congestion

d. Market Scheduling and Forecasting Fees

e. PJM ISO Fees

f. Transmission Losses & Charges

g. Capacity Charges

h. NJ SUT Taxes

Glacial Index Excludes:

a. Any charges from the LDC companies - Wires

b. Non NJ SUT Taxes (SUT rates & charges noted above)

c. Unaccounted for Energy (UFE)

1. The historic tariff rate comparison is based on historical usage and current, pending or estimated utility rates (inclusive of NJ SUT) for the appropriate rate schedule(s).

Estimated_Rate Comparison_New Jersey_June 09,2009_Freehold Township Board of Education - Applegate

0.0250

0.0750

0.1250

0.1750

Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09

Rate

s (

$/k

wh

)

Billing Months

Glacial Energy Index - Estimated Historical Rate Comparison

JCPL Rate

Glacial Index

Page 318: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

APPENDIX H

NJ SMARTSTART INCENTIVES INFORMATION AND WORKSHEETS

Page 319: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 320: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

2009 Prescriptive Lighting Application

Prescriptive Lighting Information

Total Incentives (per attached Worksheet calculations):

$__________ Note: Prescriptive Lighting Worksheet must accompany this application.

Customer InformationCompany Electric Utility Serving Applicant Electric Account No. Installation Date

Facility Address City State Zip

Type of Project Size of Building

❑ New Construction ❑ Renovation ❑ Equipment Replacement ❑ School

Company Mailing Address City State Zip

Contact Person (Name/Title) Telephone No. Fax No. ( ) ( )

Incorporated? ❑ Yes ❑ No ❑ Exempt Federal Tax ID# or SSN Email Address

Incentive Payment to Please assign payment to contractor/vendor/other indicated below

❑ Customer ❑ Contractor ❑ Other Customer Signature

003-02/09

Payee Information (Must submit W-9 form with application)

Contractor/Vendor Information (if different from Payee)

Company Contact Name Incorporated? Federal Tax ID# ❑ Yes ❑ NoStreet Address City State Zip Telephone No. ( )

Company Contact Name Incorporated? Federal Tax ID# ❑ Yes ❑ NoStreet Address City State Zip Telephone No. ( )

Email Address

Email Address

Page 321: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Recessed and Surface-Mounted Compact Fluorescents(New Fixtures Replacing Incandescent Fixtures Only): Only available for hard-wired, electronically ballasted new fixtures with rare earth phosphor lamps and 4-pin based tubes (including: twin tube, quad tube, triple tube, 2D or circline lamps), THD<33% and BF>0.9

High-Efficiency Fluorescent Fixtures:For retrofit of T-12 fixtures to T-5 or T-8 with electronic ballasts

For replacement of fixtures with new T-5 or T-8 fixtures

Specific Program Requirements* These requirements are in addition to the Program Terms and Conditions.

Visit our web site: www.NJCleanEnergy.com

Mail or fax your application package dIRECTLy to the Commercial/Industrial Market Manager.

Type of Fixture Incentive

$25 per 1-lamp fixture$30 per 2-lamp or more fixture

$10 per fixture (1 & 2 lamps retrofit) $20 per fixture (3 & 4 lamps retrofit)

Prescriptive Lighting Measures and Incentives*

1. Please refer to the program guide for additional applicable technical requirements.

2. Include the manufacturer’s specification sheet with the application package and mail or fax directly to the Commercial/Industrial Market Manager.

3. Incentives for T-5 and T-8 lamps with electronic ballasts are available only for fixtures with a Total Harmonic Distortion of ≤ 20%.

4. All eligible lighting devices must be UL listed. 5. R equirements for CFL fixtures (must meet all requirements): ■ Fixtures must be new and Energy Star qualified ■ Fixtures must have replaceable electronic ballasts ■ Total Harmonic Distortion (THD) must not exceed 33% ■ Power factor of the ballast must be no less than 90% ■ The manufacturer must warrant all fixtures for a minimum of

3 years. Warranty does not pertain to lamps or photocells not physically part of the fixture.

■ The installer must warrant installation of fixtures for a minimum of 1 year.

6. Pulse Start Metal Halide (including pole-mounted parking lot lighting) must have a 12% minimum wattage reduction.

7. T-5 or T-8 Fixtures replacing incandescent or T-12 fluorescent fixtures greater than 250 watt or High Intensity Discharge shall comply as follows:

7.1 T-5 fixtures replacing T-12 fluorescent or incandescent fixtures 250 watts or greater, or HID fixtures shall have a ballast factor greater than or equal to 1.0; have reflectivity greater than or equal to 91%; have a minimum 2 lamps; and be designated as F54T5 HO.

7.2 T-8 fixtures replacing T-12 fluorescent or incandescent fixtures 250 watts or greater, or HID fixtures shall have a ballast factor greater than or equal to 1.14; have reflectivity greater than or equal to 91%; have a minimum of 4 lamps; and be designated as F32T8, minimum 32 watts.

7.3 T-8 to T-8 replacement requires delamping and new reflectors resulting in a more efficient light system with maintained light levels.

New Jersey SmartStart Buildings® is a registered trademark. Use of the mark without the permission of the New Jersey Board of Public Utilities, Office of Clean Energy is prohibited. *Incentives/Requirements subject to change.

New Jersey's Clean Energy Programc/o TRC Energy Services

900 Route 9 North, Suite 104 · Woodbridge, NJ 07095

Phone: 866-657-6278 · Fax: 732-855-0422

HID, T-12, IncandescentHID, T-12, IncandescentHID, T-12, Incandescent

HID onlyHID onlyHID onlyT-12 only T-12 only

≥ 1000 Watts400-999 Watt250-399 Watt175-249 Watt100-174 Watt75-99 Watt <250 Watt<250 Watt

T-5, T-8T-5, T-8T-5, T-8T-5, T-8T-5, T-8T-5, T-8

T-5, T-8 (1 & 2 lamp)T-5, T-8 (3 & 4 lamp)

$284$100$50$43$30$16$25$30

Type of Old Fixture Wattage of Old Fixture Type of New Fixture Incentive Per Fixture Removed

For retrofit of T-8 fixtures by permanent delamping & new reflectorsNew Construction & Complete RenovationLED Exit Signs (new fixtures only): For existing facilities with connected load ≤75 kWFor existing facilities with connected load ≥ 75 kWPulse Start Metal Halide (for fixtures ≥ 150 watts)Parking lot low bay - LED

T-12 to T-8 fixtures by permanent delamping & new reflectors

$20 per fixturePerformance based only$20 per fixture$10 per fixture$25 per fixture (includes parking lot lighting)$43 per fixture$30 per fixture

ACkNOWLEDgEMENT

CUSTOMER'S SIgNATURE ___________________________________________________________________________

By signing, I certify that I have read, understand and agree to the Specific Program Requirements/Terms and Conditions listed on this application form, I will also submit for approval a properly completed application package, which includes this signed application, worksheet (if applicable), manufacturer’s specification sheets and complete utility bill (name and address on utility bill must match name and address on application).

Page 322: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Program Terms and Conditions

Definitions:

Design Incentives – Incentives that may be offered to design professionals by the Program.

Design Services – Services that may be offered to design professionals under the Program.

Energy-Efficient Measures – Any device eligible to receive a Program Incentive payment through the NJ Clean Energy Commercial and Industrial Program (New Jersey SmartStart Buildings).

New Jersey Utilities – The regulated electric and/or gas utilities in the State of New Jersey. They are: Atlantic City Electric, Jersey Central Power & Light, Rockland Electric Company, New Jersey Natural Gas, Elizabethtown Gas, PSE&G, and South Jersey Gas.

Administrator – New Jersey Board of Public Utilities, Office of Clean Energy

Participating Customers – Those non-residential electric and/or gas service customers of the New Jersey Utilities who participate in this Program.

Product Installation or Equipment Installation – Installation of the Energy-Efficient Measures.

Market Manager – TRC Energy Services (see below). The NJ Board of Public Utilities has transferred responsibility for the NJ SmartStart Buildings Program from the NJ Utilities to TRC.

Program – The Commercial and Industrial Energy-Efficient Construction Program (New Jersey SmartStart Buildings) offered herein by the New Jersey Board of Public Utilities, Office of Clean Energy pursuant to state regulatory approval under the New Jersey Electric Discount and Energy Competition Act, NJSA 48:3-49, et seq.

Program Incentives – Refers to the amount or level of incentive that the Program provides to participating customers pursuant to the Program offered herein (see description below under “Incentive Amount” heading).

Program Offer – Program Incentives are available to non-residential retail electric and/or gas service customers of the New Jersey Utilities identified above. Program Incentives for new construction are available only for projects in areas designated for growth in the State Plan. Public school (K-12) new construction projects are exempted from this restriction and are eligible for new Program incentives throughout the State. Customers, or their trade allies, can determine if a location is in a designated growth area by referring to the Smart Growth Locator available from the HMFA website or contact the Market Manager if you are uncertain about project eligibility.

Application and Eligibility Process – The Program pays incentives after the installation of qualified energy efficient measures that were pre-approved (for exceptions to this condition, please refer to “exceptions for approval”.) In order to be eligible for Program Incentives, a Customer, or an agent (contractor/vendor) authorized by a Customer, must submit a properly completed application package. The package must include an application signed by the customer; a complete (current) utility bill; and technology worksheet and manufacturer’s cut sheets (where appropriate). This information must be submitted to the Market Manager before equipment is installed. Applications for measures that are self installed by customers must be submitted by the customer and not the sales vendor of the measure, however, the customer may elect to assign payment of the incentives to the sales vendor. This application package must be received by the Market Manager on or before December 31, 2009 in order to be eligible for 2009 incentives. The Market Manager will review the application package to determine if the project is eligible for a Program Incentive. If eligible, the Customer will receive an approval letter with the estimated authorized incentive amount and the date by which the equipment must be installed in order for the approval to remain in effect. Upon receipt of an approval letter, the Customer may then proceed to install the equipment listed on the approved application. Equipment installed prior to the date of the Market Manager’s approval letter is not eligible for an incentive. The Market Manager reserves the right to conduct a pre-inspection of the facility prior to the installation of equipment. This will be done prior to the issuance of the approval letter. All equipment must be purchased within 12 months of date of application. Any Customer and/or Agent who purchases equipment prior to the receipt of an incentive approval letter does so at his/her own risk.

Exceptions for Approval – The Application and Eligibility Process pertains to all projects except for those involving either Unitary HVAC or Motors having an incentive amount less than $5,000. These measures, at this incentive level, may be installed without prior approval. In addition, but at the sole discretion of the Market Manager, emergency replacement of equipment may not require a prior approval determination and letter. In such cases, please notify the Market Manager of such emergencies as early as possible, that an application will soon be sent in that was not pre-approved.

Post Installation Approval – After installation is completed, the Customer, or an agent authorized by the Customer, must finalize and submit an invoice for the purchase of the equipment (material cost must be broken out from labor costs), and any other required documentation as specified on the equipment application or in the Market Manager’s initial approval letter.

NJ SmartStart Buildings®

Page 323: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Please refer to the Program Guide on the NJCleanEnergy.com/ssb website for the complete Application and Eligibility Process.

The Market Manager reserves the right to verify sales transactions and to have reasonable access to Participating Customer’s facility to inspect both pre-existing product or equipment (if applicable) and the Energy-Efficient Measures installed under this Program, either prior to issuing incentives or at a later time.

Energy-Efficient Measures must be installed in buildings located within a New Jersey Utilities’ service territory and designated on the Participating Customer’s incentive application. Program Incentives are available for qualified Energy-Efficient Measures as listed and described in the Program materials and incentive applications. The Participating Customer must ultimately own the equipment, either through an up-front purchase or at the end of a short-term lease. (Design Incentives are available to design professionals as described in the Program materials and applications. A different and separate agreement must be executed by participating design professionals to be eligible for this type of incentive. The design professional does not need to be based in New Jersey.)

Equipment procured by Participating Customers through another program offered by New Jersey's Clean Energy Program or the New Jersey Utilities, as applicable, is not eligible for incentives through this program. Customers who have not contributed to the Societal Benefits Charge of the applicable New Jersey Utility are not be eligible for incentives offered through this program.

Incentive Amount – Program Incentives will equal either: a) the approved Program Incentive amount, or b) the actual equipment cost of the Energy-Efficient Measure, whichever is less, as determined by the Market Manager. Products offered at no direct cost to the customer are ineligible. Incomplete application submissions, applications requiring inspections and unanticipated high volume of activities may cause processing delays. Program Incentives are limited to $500,000 per utility account in a calendar year. Contact the Market Manager regarding any questions.

Tax Liability – The Market Manager will not be responsible for any tax liability that may be imposed on any Participating Customer as a result of the payment of Program Incentives. All Participating Customers must supply their Federal Tax Identification number or social security number to the Market Manager on the application form in order to receive a Program Incentive. In addition, Participating Customers must also provide a Tax Clearance Form (Business Assistance or Incentive Clearance Certificate) that is dated within 90 days of equipment installation

Endorsement – The Market Manager and Administrator do not endorse, support or recommend any particular manufacturer, product or system design in promoting this Program.

Warranties – THE MARKET MANAGER AND ADMINISTRATOR DO NOT WARRANT THE PERFORMANCE OF INSTALLED EQUIPMENT, AND/OR SERVICES RENDERED AS PART OF THIS PROGRAM, EITHER EXPRESSLY OR IMPLICITLY. NO WARRANTIES OR REPRESENTATIONS OF ANY KIND, WHETHER STATUTORY, EXPRESSED, OR IMPLIED, INCLUDING, WITHOUT LIMITATIONS, WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE REGARDING EQUIPMENT OR SERVICES PROVIDED BY A MANUFACTURER OR VENDOR. CONTACT YOUR VENDOR/SERVICES PROVIDER FOR DETAILS REGARDING PERFORMANCE AND WARRANTIES.

Limitation of Liability – By virtue of participating in this Program, Participating Customers agree to waive any and all claims or damages against the Market Manager or the Administrator, except the receipt of the Program Incentive. Participating Customers agree that the Market Manager’s and Administrator’s liability, in connection with this Program, is limited to paying the Program Incentive specified. Under no circumstances shall the Market Manager, its representatives, or subcontractors, or the Administrator, be liable for any lost profits, special, punitive, consequential or incidental damages or for any other damages or claims connected with or resulting from participation in this Program. Further, any liability attributed to the Market Manager under this Program shall be individual, and not joint and/or several.

Assignment – The Participating Customer may assign Program Incentive payments to a specified vendor.

Participating Customer’s Certification – Participating Customer certifies that he/she purchased and installed the equipment listed in their application at their defined New Jersey location. Participating Customer agrees that all information is true and that he/she has conformed to all of the Program and equipment requirements listed in the application.

Termination – The New Jersey Board of Public Utilities reserves the right to extend, modify (this includes modification of Program Incentive levels) or terminate this Program without prior or further notice.

Acknowledgement – I have read, understood and am in compliance with all rules and regulations concerning this incentive program. I certify that all information provided is correct to the best of my knowledge, and I give the Market Manager permission to share my records with the New Jersey Board of Public Utilities, and contractors it selects to manage, coordinate or evaluate the NJ SmartStart Buildings Program. Additionally, I allow reasonable access to my property to inspect the installation and performance of the technologies and installations that are eligible for incentives under the guidelines of New Jersey’s Clean Energy Program.

Page 324: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

2009 Prescriptive Lighting Incentive WorksheetCustomer InformationCompany

Check here if multiple worksheets are being submitted for one project/building.

Facility Address

Prescriptive Lighting Information

Total (including additional sheets)

For additional fixtures, attach additional sheets and check here

Date Submitted

Reason Fixture Type Fixture Type Location Size of A B Total Incentives N–New Installed Removed (Bldg/Rm) Replaced Incentive # of (AxB) R–Replaced Lamps Per Fixture Units in Watts (Table) (Examples) R 2x4 3L T-5 2x4 3L T-12 Office $20 8 $20 x 8 = $160

R 2x2 2L T-8 2x2 2L T-12 Office $10 10 $10 x 10 = $100

R 28w CFL 100w Incan. Supply Room $25 3 $25 x 3 = $75

R 250w Pulse Start Metal Halide 400w Mercury Vapor Warehouse $45 3 $45 x 3 = $135

002–02/09

Page 325: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Recessed and Surface-Mounted Compact Fluorescents(New Fixtures Replacing Incandescent Fixtures Only): Only available for hard-wired, electronically ballasted new fixtures with rare earth phosphor lamps and 4-pin based tubes (including: twin tube, quad tube, triple tube, 2D or circline lamps), THD<33% and BF>0.9

High-Efficiency Fluorescent Fixtures:For retrofit of T-12 fixtures to T-5 or T-8 with electronic ballasts

For replacement of fixtures with new T-5 or T-8 fixtures

Specific Program Requirements* These requirements are in addition to the Program Terms and Conditions.

Visit our web site: www.NJCleanEnergy.com

Mail or fax your application package dIRECTLy to the Commercial/Industrial Market Manager.

Type of Fixture Incentive

$25 per 1-lamp fixture$30 per 2-lamp or more fixture

$10 per fixture (1 & 2 lamps retrofit) $20 per fixture (3 & 4 lamps retrofit)

Prescriptive Lighting Measures and Incentives*

1. Please refer to the program guide for additional applicable technical requirements.

2. Include the manufacturer’s specification sheet with the application package and mail or fax directly to the Commercial/Industrial Market Manager.

3. Incentives for T-5 and T-8 lamps with electronic ballasts are available only for fixtures with a Total Harmonic Distortion of ≤ 20%.

4. All eligible lighting devices must be UL listed. 5. R equirements for CFL fixtures (must meet all requirements): ■ Fixtures must be new and Energy Star qualified ■ Fixtures must have replaceable electronic ballasts ■ Total Harmonic Distortion (THD) must not exceed 33% ■ Power factor of the ballast must be no less than 90% ■ The manufacturer must warrant all fixtures for a minimum of

3 years. Warranty does not pertain to lamps or photocells not physically part of the fixture.

■ The installer must warrant installation of fixtures for a minimum of 1 year.

6. Pulse Start Metal Halide (including pole-mounted parking lot lighting) must have a 12% minimum wattage reduction.

7. T-5 or T-8 Fixtures replacing incandescent or T-12 fluorescent fixtures greater than 250 watt or High Intensity Discharge shall comply as follows:

7.1 T-5 fixtures replacing T-12 fluorescent or incandescent fixtures 250 watts or greater, or HID fixtures shall have a ballast factor greater than or equal to 1.0; have reflectivity greater than or equal to 91%; have a minimum 2 lamps; and be designated as F54T5 HO.

7.2 T-8 fixtures replacing T-12 fluorescent or incandescent fixtures 250 watts or greater, or HID fixtures shall have a ballast factor greater than or equal to 1.14; have reflectivity greater than or equal to 91%; have a minimum of 4 lamps; and be designated as F32T8, minimum 32 watts.

7.3 T-8 to T-8 replacement requires delamping and new reflectors resulting in a more efficient light system with maintained light levels.

New Jersey SmartStart Buildings® is a registered trademark. Use of the mark without the permission of the New Jersey Board of Public Utilities, Office of Clean Energy is prohibited. *Incentives/Requirements subject to change.

New Jersey's Clean Energy Programc/o TRC Energy Services

900 Route 9 North, Suite 104 · Woodbridge, NJ 07095

Phone: 866-657-6278 · Fax: 732-855-0422

HID, T-12, IncandescentHID, T-12, IncandescentHID, T-12, Incandescent

HID onlyHID onlyHID onlyT-12 only T-12 only

≥ 1000 Watts400-999 Watt250-399 Watt175-249 Watt100-174 Watt75-99 Watt <250 Watt<250 Watt

T-5, T-8T-5, T-8T-5, T-8T-5, T-8T-5, T-8T-5, T-8

T-5, T-8 (1 & 2 lamp)T-5, T-8 (3 & 4 lamp)

$284$100$50$43$30$16$25$30

Type of Old Fixture Wattage of Old Fixture Type of New Fixture Incentive Per Fixture Removed

For retrofit of T-8 fixtures by permanent delamping & new reflectorsNew Construction & Complete RenovationLED Exit Signs (new fixtures only): For existing facilities with connected load ≤75 kWFor existing facilities with connected load ≥ 75 kWPulse Start Metal Halide (for fixtures ≥ 150 watts)Parking lot low bay - LED

T-12 to T-8 fixtures by permanent delamping & new reflectors

$20 per fixturePerformance based only$20 per fixture$10 per fixture$25 per fixture (includes parking lot lighting)$43 per fixture$30 per fixture

ACkNOWLEDgEMENT

CUSTOMER'S SIgNATURE ___________________________________________________________________________

By signing, I certify that I have read, understand and agree to the Specific Program Requirements/Terms and Conditions listed on this application form, I will also submit for approval a properly completed application package, which includes this signed application, worksheet (if applicable), manufacturer’s specification sheets and complete utility bill (name and address on utility bill must match name and address on application).

Page 326: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Program Terms and Conditions

Definitions:

Design Incentives – Incentives that may be offered to design professionals by the Program.

Design Services – Services that may be offered to design professionals under the Program.

Energy-Efficient Measures – Any device eligible to receive a Program Incentive payment through the NJ Clean Energy Commercial and Industrial Program (New Jersey SmartStart Buildings).

New Jersey Utilities – The regulated electric and/or gas utilities in the State of New Jersey. They are: Atlantic City Electric, Jersey Central Power & Light, Rockland Electric Company, New Jersey Natural Gas, Elizabethtown Gas, PSE&G, and South Jersey Gas.

Administrator – New Jersey Board of Public Utilities, Office of Clean Energy

Participating Customers – Those non-residential electric and/or gas service customers of the New Jersey Utilities who participate in this Program.

Product Installation or Equipment Installation – Installation of the Energy-Efficient Measures.

Market Manager – TRC Energy Services (see below). The NJ Board of Public Utilities has transferred responsibility for the NJ SmartStart Buildings Program from the NJ Utilities to TRC.

Program – The Commercial and Industrial Energy-Efficient Construction Program (New Jersey SmartStart Buildings) offered herein by the New Jersey Board of Public Utilities, Office of Clean Energy pursuant to state regulatory approval under the New Jersey Electric Discount and Energy Competition Act, NJSA 48:3-49, et seq.

Program Incentives – Refers to the amount or level of incentive that the Program provides to participating customers pursuant to the Program offered herein (see description below under “Incentive Amount” heading).

Program Offer – Program Incentives are available to non-residential retail electric and/or gas service customers of the New Jersey Utilities identified above. Program Incentives for new construction are available only for projects in areas designated for growth in the State Plan. Public school (K-12) new construction projects are exempted from this restriction and are eligible for new Program incentives throughout the State. Customers, or their trade allies, can determine if a location is in a designated growth area by referring to the Smart Growth Locator available from the HMFA website or contact the Market Manager if you are uncertain about project eligibility.

Application and Eligibility Process – The Program pays incentives after the installation of qualified energy efficient measures that were pre-approved (for exceptions to this condition, please refer to “exceptions for approval”.) In order to be eligible for Program Incentives, a Customer, or an agent (contractor/vendor) authorized by a Customer, must submit a properly completed application package. The package must include an application signed by the customer; a complete (current) utility bill; and technology worksheet and manufacturer’s cut sheets (where appropriate). This information must be submitted to the Market Manager before equipment is installed. Applications for measures that are self installed by customers must be submitted by the customer and not the sales vendor of the measure, however, the customer may elect to assign payment of the incentives to the sales vendor. This application package must be received by the Market Manager on or before December 31, 2009 in order to be eligible for 2009 incentives. The Market Manager will review the application package to determine if the project is eligible for a Program Incentive. If eligible, the Customer will receive an approval letter with the estimated authorized incentive amount and the date by which the equipment must be installed in order for the approval to remain in effect. Upon receipt of an approval letter, the Customer may then proceed to install the equipment listed on the approved application. Equipment installed prior to the date of the Market Manager’s approval letter is not eligible for an incentive. The Market Manager reserves the right to conduct a pre-inspection of the facility prior to the installation of equipment. This will be done prior to the issuance of the approval letter. All equipment must be purchased within 12 months of date of application. Any Customer and/or Agent who purchases equipment prior to the receipt of an incentive approval letter does so at his/her own risk.

Exceptions for Approval – The Application and Eligibility Process pertains to all projects except for those involving either Unitary HVAC or Motors having an incentive amount less than $5,000. These measures, at this incentive level, may be installed without prior approval. In addition, but at the sole discretion of the Market Manager, emergency replacement of equipment may not require a prior approval determination and letter. In such cases, please notify the Market Manager of such emergencies as early as possible, that an application will soon be sent in that was not pre-approved.

Post Installation Approval – After installation is completed, the Customer, or an agent authorized by the Customer, must finalize and submit an invoice for the purchase of the equipment (material cost must be broken out from labor costs), and any other required documentation as specified on the equipment application or in the Market Manager’s initial approval letter.

NJ SmartStart Buildings®

Page 327: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Please refer to the Program Guide on the NJCleanEnergy.com/ssb website for the complete Application and Eligibility Process.

The Market Manager reserves the right to verify sales transactions and to have reasonable access to Participating Customer’s facility to inspect both pre-existing product or equipment (if applicable) and the Energy-Efficient Measures installed under this Program, either prior to issuing incentives or at a later time.

Energy-Efficient Measures must be installed in buildings located within a New Jersey Utilities’ service territory and designated on the Participating Customer’s incentive application. Program Incentives are available for qualified Energy-Efficient Measures as listed and described in the Program materials and incentive applications. The Participating Customer must ultimately own the equipment, either through an up-front purchase or at the end of a short-term lease. (Design Incentives are available to design professionals as described in the Program materials and applications. A different and separate agreement must be executed by participating design professionals to be eligible for this type of incentive. The design professional does not need to be based in New Jersey.)

Equipment procured by Participating Customers through another program offered by New Jersey's Clean Energy Program or the New Jersey Utilities, as applicable, is not eligible for incentives through this program. Customers who have not contributed to the Societal Benefits Charge of the applicable New Jersey Utility are not be eligible for incentives offered through this program.

Incentive Amount – Program Incentives will equal either: a) the approved Program Incentive amount, or b) the actual equipment cost of the Energy-Efficient Measure, whichever is less, as determined by the Market Manager. Products offered at no direct cost to the customer are ineligible. Incomplete application submissions, applications requiring inspections and unanticipated high volume of activities may cause processing delays. Program Incentives are limited to $500,000 per utility account in a calendar year. Contact the Market Manager regarding any questions.

Tax Liability – The Market Manager will not be responsible for any tax liability that may be imposed on any Participating Customer as a result of the payment of Program Incentives. All Participating Customers must supply their Federal Tax Identification number or social security number to the Market Manager on the application form in order to receive a Program Incentive. In addition, Participating Customers must also provide a Tax Clearance Form (Business Assistance or Incentive Clearance Certificate) that is dated within 90 days of equipment installation

Endorsement – The Market Manager and Administrator do not endorse, support or recommend any particular manufacturer, product or system design in promoting this Program.

Warranties – THE MARKET MANAGER AND ADMINISTRATOR DO NOT WARRANT THE PERFORMANCE OF INSTALLED EQUIPMENT, AND/OR SERVICES RENDERED AS PART OF THIS PROGRAM, EITHER EXPRESSLY OR IMPLICITLY. NO WARRANTIES OR REPRESENTATIONS OF ANY KIND, WHETHER STATUTORY, EXPRESSED, OR IMPLIED, INCLUDING, WITHOUT LIMITATIONS, WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE REGARDING EQUIPMENT OR SERVICES PROVIDED BY A MANUFACTURER OR VENDOR. CONTACT YOUR VENDOR/SERVICES PROVIDER FOR DETAILS REGARDING PERFORMANCE AND WARRANTIES.

Limitation of Liability – By virtue of participating in this Program, Participating Customers agree to waive any and all claims or damages against the Market Manager or the Administrator, except the receipt of the Program Incentive. Participating Customers agree that the Market Manager’s and Administrator’s liability, in connection with this Program, is limited to paying the Program Incentive specified. Under no circumstances shall the Market Manager, its representatives, or subcontractors, or the Administrator, be liable for any lost profits, special, punitive, consequential or incidental damages or for any other damages or claims connected with or resulting from participation in this Program. Further, any liability attributed to the Market Manager under this Program shall be individual, and not joint and/or several.

Assignment – The Participating Customer may assign Program Incentive payments to a specified vendor.

Participating Customer’s Certification – Participating Customer certifies that he/she purchased and installed the equipment listed in their application at their defined New Jersey location. Participating Customer agrees that all information is true and that he/she has conformed to all of the Program and equipment requirements listed in the application.

Termination – The New Jersey Board of Public Utilities reserves the right to extend, modify (this includes modification of Program Incentive levels) or terminate this Program without prior or further notice.

Acknowledgement – I have read, understood and am in compliance with all rules and regulations concerning this incentive program. I certify that all information provided is correct to the best of my knowledge, and I give the Market Manager permission to share my records with the New Jersey Board of Public Utilities, and contractors it selects to manage, coordinate or evaluate the NJ SmartStart Buildings Program. Additionally, I allow reasonable access to my property to inspect the installation and performance of the technologies and installations that are eligible for incentives under the guidelines of New Jersey’s Clean Energy Program.

Page 328: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

2009 Lighting Controls Application

Lighting Control Information

Total Incentives (per attached Worksheet calculations):

$__________

Use Lighting Controls Incentive Worksheet.

002-02/09

Customer InformationCompany Electric Utility Serving Applicant Electric Account No. Installation Date

Facility Address City State Zip

Type of Project Size of Building

❑ New Construction ❑ Renovation ❑ Equipment Replacement ❑ School

Company Mailing Address City State Zip

Contact Person (Name/Title) Telephone No. Fax No. ( ) ( )

Incorporated? ❑ Yes ❑ No ❑ Exempt Federal Tax ID# or SSN Email Address

Incentive Payment to Please assign payment to contractor/vendor/other indicated below

❑ Customer ❑ Contractor ❑ Other Customer Signature

Payee Information (Must submit W-9 form with application)

Contractor/Vendor Information (if different from Payee)

Company Contact Name Incorporated? Federal Tax ID# ❑ Yes ❑ NoStreet Address City State Zip Telephone No. ( )

Company Contact Name Incorporated? Federal Tax ID# ❑ Yes ❑ NoStreet Address City State Zip Telephone No. ( )

Email Address

Email Address

Page 329: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Specific Program Requirements* These requirements are in addition to the Program Terms and Conditions.

Visit our web site: www.NJCleanEnergy.com

Mail or fax your application package dIRECTLy to the Commercial/Industrial Market Manager.

Lighting Control Prescriptive Incentives* Control device Type Incentive per Unit

OSW – Occupancy Sensor Wall Mounted (Existing facilities only) $20 per control

OSR – Occupancy Sensor Remote Mounted (Existing facilities only) $35 per control

DLD – Fluorescent Daylight Dimming $25 per fixture controlled

OHLF – Occupancy Controlled High-Low with Step Ballast $25 per fixture controlled

OSRH – Occupancy Sensor Remote Mounted $35 per control

OHLH – Occupancy Controlled High-Low with Step Ballast $75 per fixture controlled

DDH – Daylight Dimming $75 per fixture controlled

1. Please refer to the program guide for additional applicable technical requirements, including special requirements for lighting controls.

2. Include the manufacturer’s specification sheet with the application package and mail or fax directly to the Commercial/Industrial Market Manager.

3. All lighting controls eligible for incentives must be UL listed.4. Lighting control incentives are only available for control of eligible

energy efficient lighting fixtures.5. If more than one eligible lighting control device is associated with

the same eligible fixture, the incentive paid will be for the lighting control device that yields the largest incentive only.

6. Occupancy Sensor Controls (Existing Facilities Only): ■ There is no incentive available for occupancy sensors installed in a

space where they are prohibited by state or local building or safety code. Additionally, no incentive is eligible for occupancy sensors in the following specific spaces in all cases: stairways, restrooms (remote mounted only allowed), elevators, corridors/hallways, lobbies, and closets/storage areas.

■ Incentives will only be paid for eligible occupancy sensors (OSW & OSR) controlling at least 2 eligible lighting fixtures and, for OSR installations, a minimum total connected load of 180 watts.

■ Incentives will only be paid for eligible OSRH occupancy sensors controlling eligible fixtures when the controlled wattage is greater than 180 watts.

■ Occupancy sensors with manual override to the “ON” position are ineligible for incentive.

7. High-Low Controls (OHLF and OHLH): ■ Incentives will not be paid for high-low controls on eligible

fluorescent fixtures where daylight dimming controls can be effectively employed.

■ Incentives will not be paid for spaces where the bottom of the fixture does not comply with the appropriate Prescriptive Lighting 2008 incentives, nor in spaces smaller than 250 square feet.

■ Incentives available only when “low level” is no more than 60% of “high level.”

■ Incentives are not available for the following spaces: stairways, elevators, corridors/hallways, or lobbies.

■ OHLF will control fixtures that have a ballast factor less than 1.0 for T-5s and 1.14 for T-8s. ■ OHLH will control fixtures that have a ballast factor greater than or equal to 1.0 for T-5s and 1.14 for T-8s.8. Daylight Dimming Controls for Eligible Fixtures: ■ Incentives will only be paid for eligible daylight dimming controls

operating at least 4 eligible ballasts with a minimum total connected load of 240 watts.

■ Dimming shall be continuous or stepped at 4 or more levels. ■ Incentives will be paid only for eligible daylight dimming control

systems designed in accordance with IESNA practice as delineated in “RP-5-99, IESNA Recommended Practice of Daylighting.”

■ DLD will control fixtures that have a ballast factor less than 1.0 for T-5s and 1.14 for T-8s.

■ DDH will control fixtures that have a ballast factor greater than or equal to 1.0 for T-5s and 1.14 for T-8s.

New Jersey SmartStart Buildings® is a registered trademark. Use of the mark without the permission of the New Jersey Board of Public Utilities, Office of Clean Energy is prohibited. *Incentives/Requirements subject to change.

New Jersey's Clean Energy Programc/o TRC Energy Services

900 Route 9 North, Suite 104Woodbridge, NJ 07095

Phone: 866-657-6278Fax: 732-855-0422

Acknowledgement

cUStomeR'S SignAtURe ___________________________________________________________________________

By signing, I certify that I have read, understand and agree to the Specific Program Requirements/Terms and Conditions listed on this application form, I will also submit for approval a properly completed application package, which includes this signed application, worksheet (if applicable), manufacturer’s specification sheets and complete utility bill (name and address on utility bill must match name and address on application).

Page 330: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Program Terms and Conditions

definitions:

design incentives – Incentives that may be offered to design professionals by the Program.

design Services – Services that may be offered to design professionals under the Program.

energy-efficient measures – Any device eligible to receive a Program Incentive payment through the NJ Clean Energy Commercial and Industrial Program (New Jersey SmartStart Buildings).

new Jersey Utilities – The regulated electric and/or gas utilities in the State of New Jersey. They are: Atlantic City Electric, Jersey Central Power & Light, Rockland Electric Company, New Jersey Natural Gas, Elizabethtown Gas, PSE&G, and South Jersey Gas.

Administrator – New Jersey Board of Public Utilities, Office of Clean Energy

Participating customers – Those non-residential electric and/or gas service customers of the New Jersey Utilities who participate in this Program.

Product installation or equipment installation – Installation of the Energy-Efficient Measures.

market manager – TRC Energy Services (see below). The NJ Board of Public Utilities has transferred responsibility for the NJ SmartStart Buildings Program from the NJ Utilities to TRC.

Program – The Commercial and Industrial Energy-Efficient Construction Program (New Jersey SmartStart Buildings) offered herein by the New Jersey Board of Public Utilities, Office of Clean Energy pursuant to state regulatory approval under the New Jersey Electric Discount and Energy Competition Act, NJSA 48:3-49, et seq.

Program incentives – Refers to the amount or level of incentive that the Program provides to participating customers pursuant to the Program offered herein (see description below under “Incentive Amount” heading).

Program offer – Program Incentives are available to non-residential retail electric and/or gas service customers of the New Jersey Utilities identified above. Program Incentives for new construction are available only for projects in areas designated for growth in the State Plan. Public school (K-12) new construction projects are exempted from this restriction and are eligible for new Program incentives throughout the State. Customers, or their trade allies, can determine if a location is in a designated growth area by referring to the Smart Growth Locator available from the HMFA website or contact the Market Manager if you are uncertain about project eligibility.

Application and eligibility Process – The Program pays incentives after the installation of qualified energy efficient measures that were pre-approved (for exceptions to this condition, please refer to “exceptions for approval”.) In order to be eligible for Program Incentives, a Customer, or an agent (contractor/vendor) authorized by a Customer, must submit a properly completed application package. The package must include an application signed by the customer; a complete (current) utility bill; and technology worksheet and manufacturer’s cut sheets (where appropriate). This information must be submitted to the Market Manager before equipment is installed. Applications for measures that are self installed by customers must be submitted by the customer and not the sales vendor of the measure, however, the customer may elect to assign payment of the incentives to the sales vendor. This application package must be received by the Market Manager on or before December 31, 2009 in order to be eligible for 2009 incentives. The Market Manager will review the application package to determine if the project is eligible for a Program Incentive. If eligible, the Customer will receive an approval letter with the estimated authorized incentive amount and the date by which the equipment must be installed in order for the approval to remain in effect. Upon receipt of an approval letter, the Customer may then proceed to install the equipment listed on the approved application. Equipment installed prior to the date of the Market Manager’s approval letter is not eligible for an incentive. The Market Manager reserves the right to conduct a pre-inspection of the facility prior to the installation of equipment. This will be done prior to the issuance of the approval letter. All equipment must be purchased within 12 months of date of application. Any customer and/or Agent who purchases equipment prior to the receipt of an incentive approval letter does so at his/her own risk.

exceptions for Approval – The Application and Eligibility Process pertains to all projects except for those involving either Unitary HVAC or Motors having an incentive amount less than $5,000. These measures, at this incentive level, may be installed without prior approval. In addition, but at the sole discretion of the Market Manager, emergency replacement of equipment may not require a prior approval determination and letter. in such cases, please notify the market manager of such emergencies as early as possible, that an application will soon be sent in that was not pre-approved.

Post installation Approval – After installation is completed, the Customer, or an agent authorized by the Customer, must finalize and submit an invoice for the purchase of the equipment (material cost must be broken out from labor costs), and any other required documentation as specified on the equipment application or in the Market Manager’s initial approval letter.

NJ SmartStart Buildings®

Page 331: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Please refer to the Program Guide on the NJCleanEnergy.com/ssb website for the complete Application and Eligibility Process.

The Market Manager reserves the right to verify sales transactions and to have reasonable access to Participating Customer’s facility to inspect both pre-existing product or equipment (if applicable) and the Energy-Efficient Measures installed under this Program, either prior to issuing incentives or at a later time.

Energy-Efficient Measures must be installed in buildings located within a New Jersey Utilities’ service territory and designated on the Participating Customer’s incentive application. Program Incentives are available for qualified Energy-Efficient Measures as listed and described in the Program materials and incentive applications. The Participating Customer must ultimately own the equipment, either through an up-front purchase or at the end of a short-term lease. (Design Incentives are available to design professionals as described in the Program materials and applications. A different and separate agreement must be executed by participating design professionals to be eligible for this type of incentive. The design professional does not need to be based in New Jersey.)

Equipment procured by Participating Customers through another program offered by New Jersey's Clean Energy Program or the New Jersey Utilities, as applicable, is not eligible for incentives through this program. Customers who have not contributed to the Societal Benefits Charge of the applicable New Jersey Utility are not be eligible for incentives offered through this program.

incentive Amount – Program Incentives will equal either: a) the approved Program Incentive amount, or b) the actual equipment cost of the Energy-Efficient Measure, whichever is less, as determined by the Market Manager. Products offered at no direct cost to the customer are ineligible. Incomplete application submissions, applications requiring inspections and unanticipated high volume of activities may cause processing delays. Program Incentives are limited to $500,000 per utility account in a calendar year. Contact the Market Manager regarding any questions.

tax liability – The Market Manager will not be responsible for any tax liability that may be imposed on any Participating Customer as a result of the payment of Program Incentives. All Participating Customers must supply their Federal Tax Identification number or social security number to the Market Manager on the application form in order to receive a Program Incentive. In addition, Participating Customers must also provide a Tax Clearance Form (Business Assistance or Incentive Clearance Certificate) that is dated within 90 days of equipment installation

endorsement – The Market Manager and Administrator do not endorse, support or recommend any particular manufacturer, product or system design in promoting this Program.

warranties – THE MARKET MANAGER AND ADMINISTRATOR DO NOT WARRANT THE PERFORMANCE OF INSTALLED EQUIPMENT, AND/OR SERVICES RENDERED AS PART OF THIS PROGRAM, EITHER EXPRESSLY OR IMPLICITLY. NO WARRANTIES OR REPRESENTATIONS OF ANY KIND, WHETHER STATUTORY, EXPRESSED, OR IMPLIED, INCLUDING, WITHOUT LIMITATIONS, WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE REGARDING EQUIPMENT OR SERVICES PROVIDED BY A MANUFACTURER OR VENDOR. CONTACT YOUR VENDOR/SERVICES PROVIDER FOR DETAILS REGARDING PERFORMANCE AND WARRANTIES.

limitation of liability – By virtue of participating in this Program, Participating Customers agree to waive any and all claims or damages against the Market Manager or the Administrator, except the receipt of the Program Incentive. Participating Customers agree that the Market Manager’s and Administrator’s liability, in connection with this Program, is limited to paying the Program Incentive specified. Under no circumstances shall the Market Manager, its representatives, or subcontractors, or the Administrator, be liable for any lost profits, special, punitive, consequential or incidental damages or for any other damages or claims connected with or resulting from participation in this Program. Further, any liability attributed to the Market Manager under this Program shall be individual, and not joint and/or several.

Assignment – The Participating Customer may assign Program Incentive payments to a specified vendor.

Participating customer’s certification – Participating Customer certifies that he/she purchased and installed the equipment listed in their application at their defined New Jersey location. Participating Customer agrees that all information is true and that he/she has conformed to all of the Program and equipment requirements listed in the application.

termination – The New Jersey Board of Public Utilities reserves the right to extend, modify (this includes modification of Program Incentive levels) or terminate this Program without prior or further notice.

Acknowledgement – I have read, understood and am in compliance with all rules and regulations concerning this incentive program. I certify that all information provided is correct to the best of my knowledge, and I give the Market Manager permission to share my records with the New Jersey Board of Public Utilities, and contractors it selects to manage, coordinate or evaluate the NJ SmartStart Buildings Program. Additionally, I allow reasonable access to my property to inspect the installation and performance of the technologies and installations that are eligible for incentives under the guidelines of New Jersey’s Clean Energy Program.

Page 332: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

2009 Lighting Controls Incentive WorksheetCustomer InformationCompany

Check here if multiple worksheets are being submitted for one project/building.

Facility Address

Lighting Controls Information

Total(including additional sheets)

For additional fixtures, attach additional sheets and check here

*For OSW and OSR, insert number of control devices; for DLD and OHLF, insert total number of ballasts controlled; for OHLH and DDH, insert total number of fixtures controlled.

Date Submitted

Location Reason Control Fixture Type Watts A B C N–New Device Controlled Controlled # of Fixtures # of Units* Incentive Total R–Replaced Type per Device Controlled per Unit Incentive per Device (B x C)

(Examples)

R OSW 4-lamp, T8 2 4 $20 4 x $20 = $80

R OSR 2-lamp, T8 6 2 $35 2 x $35 = $70

R DLD 2-lamp, T8 6 $25 6 x $25 = $150

R OHLF 4-lamp, T8 12 $25 12 x $25 = $300

R OHLH 150w MH 10 5 $75 5 x $75 = $375

R DDH 250w HPS 12 4 $75 4 x $75 = $300

001-01/09

Page 333: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Specific Program Requirements* These requirements are in addition to the Program Terms and Conditions.

Visit our web site: www.NJCleanEnergy.com

Mail or fax your application package DIRECTLy to the Commercial/Industrial Market Manager.

Lighting Control Prescriptive Incentives* Control Device Type Incentive per Unit

OSW – Occupancy Sensor Wall Mounted (Existing facilities only) $20 per control

OSR – Occupancy Sensor Remote Mounted (Existing facilities only) $35 per control

DLD – Fluorescent Daylight Dimming $25 per fixture controlled

OHLF – Occupancy Controlled High-Low with Step Ballast $25 per fixture controlled

OSRH – Occupancy Sensor Remote Mounted $35 per control

OHLH – Occupancy Controlled High-Low with Step Ballast $75 per fixture controlled

DDH – Daylight Dimming $75 per fixture controlled

1. Please refer to the program guide for additional applicable technical requirements, including special requirements for lighting controls.

2. Include the manufacturer’s specification sheet with the application package and mail or fax directly to the Commercial/Industrial Market Manager.

3. All lighting controls eligible for incentives must be UL listed.4. Lighting control incentives are only available for control of eligible

energy efficient lighting fixtures.5. If more than one eligible lighting control device is associated with

the same eligible fixture, the incentive paid will be for the lighting control device that yields the largest incentive only.

6. Occupancy Sensor Controls (Existing Facilities Only): ■ There is no incentive available for occupancy sensors installed in a

space where they are prohibited by state or local building or safety code. Additionally, no incentive is eligible for occupancy sensors in the following specific spaces in all cases: stairways, restrooms (remote mounted only allowed), elevators, corridors/hallways, lobbies, and closets/storage areas.

■ Incentives will only be paid for eligible occupancy sensors (OSW & OSR) controlling at least 2 eligible lighting fixtures and, for OSR installations, a minimum total connected load of 180 watts.

■ Incentives will only be paid for eligible OSRH occupancy sensors controlling eligible fixtures when the controlled wattage is greater than 180 watts.

■ Occupancy sensors with manual override to the “ON” position are ineligible for incentive.

7. High-Low Controls (OHLF and OHLH): ■ Incentives will not be paid for high-low controls on eligible

fluorescent fixtures where daylight dimming controls can be effectively employed.

■ Incentives will not be paid for spaces where the bottom of the fixture does not comply with the appropriate Prescriptive Lighting 2008 incentives, nor in spaces smaller than 250 square feet.

■ Incentives available only when “low level” is no more than 60% of “high level.”

■ Incentives are not available for the following spaces: stairways, elevators, corridors/hallways, or lobbies.

■ OHLF will control fixtures that have a ballast factor less than 1.0 for T-5s and 1.14 for T-8s.

■ OHLH will control fixtures that have a ballast factor greater than or equal to 1.0 for T-5s and 1.14 for T-8s.

8. Daylight Dimming Controls for Eligible Fixtures: ■ Incentives will only be paid for eligible daylight dimming controls

operating at least 4 eligible ballasts with a minimum total connected load of 240 watts.

■ Dimming shall be continuous or stepped at 4 or more levels. ■ Incentives will be paid only for eligible daylight dimming control

systems designed in accordance with IESNA practice as delineated in “RP-5-99, IESNA Recommended Practice of Daylighting.”

■ DLD will control fixtures that have a ballast factor less than 1.0 for T-5s and 1.14 for T-8s.

■ DDH will control fixtures that have a ballast factor greater than or equal to 1.0 for T-5s and 1.14 for T-8s.

New Jersey SmartStart Buildings® is a registered trademark. Use of the mark without the permission of the New Jersey Board of Public Utilities, Office of Clean Energy is prohibited. *Incentives/Requirements subject to change.

New Jersey's Clean Energy Programc/o TRC Energy Services

900 Route 9 North, Suite 104Woodbridge, NJ 07095

Phone: 866-657-6278Fax: 732-855-0422

Page 334: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Program Terms and Conditions

Definitions:

Design Incentives – Incentives that may be offered to design professionals by the Program.

Design Services – Services that may be offered to design professionals under the Program.

Energy-Efficient Measures – Any device eligible to receive a Program Incentive payment through the NJ Clean Energy Commercial and Industrial Program (New Jersey SmartStart Buildings).

New Jersey Utilities – The regulated electric and/or gas utilities in the State of New Jersey. They are: Atlantic City Electric, Jersey Central Power & Light, Rockland Electric Company, New Jersey Natural Gas, Elizabethtown Gas, PSE&G, and South Jersey Gas.

Administrator – New Jersey Board of Public Utilities, Office of Clean Energy

Participating Customers – Those non-residential electric and/or gas service customers of the New Jersey Utilities who participate in this Program.

Product Installation or Equipment Installation – Installation of the Energy-Efficient Measures.

Market Manager – TRC Energy Services (see below). The NJ Board of Public Utilities has transferred responsibility for the NJ SmartStart Buildings Program from the NJ Utilities to TRC.

Program – The Commercial and Industrial Energy-Efficient Construction Program (New Jersey SmartStart Buildings) offered herein by the New Jersey Board of Public Utilities, Office of Clean Energy pursuant to state regulatory approval under the New Jersey Electric Discount and Energy Competition Act, NJSA 48:3-49, et seq.

Program Incentives – Refers to the amount or level of incentive that the Program provides to participating customers pursuant to the Program offered herein (see description below under “Incentive Amount” heading).

Program Offer – Program Incentives are available to non-residential retail electric and/or gas service customers of the New Jersey Utilities identified above. Program Incentives for new construction are available only for projects in areas designated for growth in the State Plan. Public school (K-12) new construction projects are exempted from this restriction and are eligible for new Program incentives throughout the State. Customers, or their trade allies, can determine if a location is in a designated growth area by referring to the Smart Growth Locator available from the HMFA website or contact the Market Manager if you are uncertain about project eligibility.

Application and Eligibility Process – The Program pays incentives after the installation of qualified energy efficient measures that were pre-approved (for exceptions to this condition, please refer to “exceptions for approval”.) In order to be eligible for Program Incentives, a Customer, or an agent (contractor/vendor) authorized by a Customer, must submit a properly completed application package. The package must include an application signed by the customer; a complete (current) utility bill; and technology worksheet and manufacturer’s cut sheets (where appropriate). This information must be submitted to the Market Manager before equipment is installed. Applications for measures that are self installed by customers must be submitted by the customer and not the sales vendor of the measure, however, the customer may elect to assign payment of the incentives to the sales vendor. This application package must be received by the Market Manager on or before December 31, 2009 in order to be eligible for 2009 incentives. The Market Manager will review the application package to determine if the project is eligible for a Program Incentive. If eligible, the Customer will receive an approval letter with the estimated authorized incentive amount and the date by which the equipment must be installed in order for the approval to remain in effect. Upon receipt of an approval letter, the Customer may then proceed to install the equipment listed on the approved application. Equipment installed prior to the date of the Market Manager’s approval letter is not eligible for an incentive. The Market Manager reserves the right to conduct a pre-inspection of the facility prior to the installation of equipment. This will be done prior to the issuance of the approval letter. All equipment must be purchased within 12 months of date of application. Any Customer and/or Agent who purchases equipment prior to the receipt of an incentive approval letter does so at his/her own risk.

Exceptions for Approval – The Application and Eligibility Process pertains to all projects except for those involving either Unitary HVAC or Motors having an incentive amount less than $5,000. These measures, at this incentive level, may be installed without prior approval. In addition, but at the sole discretion of the Market Manager, emergency replacement of equipment may not require a prior approval determination and letter. In such cases, please notify the Market Manager of such emergencies as early as possible, that an application will soon be sent in that was not pre-approved.

Post Installation Approval – After installation is completed, the Customer, or an agent authorized by the Customer, must finalize and submit an invoice for the purchase of the equipment (material cost must be broken out from labor costs), and any other required documentation as specified on the equipment application or in the Market Manager’s initial approval letter.

NJ SmartStart Buildings®

Page 335: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Please refer to the Program Guide on the NJCleanEnergy.com/ssb website for the complete Application and Eligibility Process.

The Market Manager reserves the right to verify sales transactions and to have reasonable access to Participating Customer’s facility to inspect both pre-existing product or equipment (if applicable) and the Energy-Efficient Measures installed under this Program, either prior to issuing incentives or at a later time.

Energy-Efficient Measures must be installed in buildings located within a New Jersey Utilities’ service territory and designated on the Participating Customer’s incentive application. Program Incentives are available for qualified Energy-Efficient Measures as listed and described in the Program materials and incentive applications. The Participating Customer must ultimately own the equipment, either through an up-front purchase or at the end of a short-term lease. (Design Incentives are available to design professionals as described in the Program materials and applications. A different and separate agreement must be executed by participating design professionals to be eligible for this type of incentive. The design professional does not need to be based in New Jersey.)

Equipment procured by Participating Customers through another program offered by New Jersey's Clean Energy Program or the New Jersey Utilities, as applicable, is not eligible for incentives through this program. Customers who have not contributed to the Societal Benefits Charge of the applicable New Jersey Utility are not be eligible for incentives offered through this program.

Incentive Amount – Program Incentives will equal either: a) the approved Program Incentive amount, or b) the actual equipment cost of the Energy-Efficient Measure, whichever is less, as determined by the Market Manager. Products offered at no direct cost to the customer are ineligible. Incomplete application submissions, applications requiring inspections and unanticipated high volume of activities may cause processing delays. Program Incentives are limited to $500,000 per utility account in a calendar year. Contact the Market Manager regarding any questions.

Tax Liability – The Market Manager will not be responsible for any tax liability that may be imposed on any Participating Customer as a result of the payment of Program Incentives. All Participating Customers must supply their Federal Tax Identification number or social security number to the Market Manager on the application form in order to receive a Program Incentive. In addition, Participating Customers must also provide a Tax Clearance Form (Business Assistance or Incentive Clearance Certificate) that is dated within 90 days of equipment installation

Endorsement – The Market Manager and Administrator do not endorse, support or recommend any particular manufacturer, product or system design in promoting this Program.

Warranties – THE MARKET MANAGER AND ADMINISTRATOR DO NOT WARRANT THE PERFORMANCE OF INSTALLED EQUIPMENT, AND/OR SERVICES RENDERED AS PART OF THIS PROGRAM, EITHER EXPRESSLY OR IMPLICITLY. NO WARRANTIES OR REPRESENTATIONS OF ANY KIND, WHETHER STATUTORY, EXPRESSED, OR IMPLIED, INCLUDING, WITHOUT LIMITATIONS, WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE REGARDING EQUIPMENT OR SERVICES PROVIDED BY A MANUFACTURER OR VENDOR. CONTACT YOUR VENDOR/SERVICES PROVIDER FOR DETAILS REGARDING PERFORMANCE AND WARRANTIES.

Limitation of Liability – By virtue of participating in this Program, Participating Customers agree to waive any and all claims or damages against the Market Manager or the Administrator, except the receipt of the Program Incentive. Participating Customers agree that the Market Manager’s and Administrator’s liability, in connection with this Program, is limited to paying the Program Incentive specified. Under no circumstances shall the Market Manager, its representatives, or subcontractors, or the Administrator, be liable for any lost profits, special, punitive, consequential or incidental damages or for any other damages or claims connected with or resulting from participation in this Program. Further, any liability attributed to the Market Manager under this Program shall be individual, and not joint and/or several.

Assignment – The Participating Customer may assign Program Incentive payments to a specified vendor.

Participating Customer’s Certification – Participating Customer certifies that he/she purchased and installed the equipment listed in their application at their defined New Jersey location. Participating Customer agrees that all information is true and that he/she has conformed to all of the Program and equipment requirements listed in the application.

Termination – The New Jersey Board of Public Utilities reserves the right to extend, modify (this includes modification of Program Incentive levels) or terminate this Program without prior or further notice.

Acknowledgement – I have read, understood and am in compliance with all rules and regulations concerning this incentive program. I certify that all information provided is correct to the best of my knowledge, and I give the Market Manager permission to share my records with the New Jersey Board of Public Utilities, and contractors it selects to manage, coordinate or evaluate the NJ SmartStart Buildings Program. Additionally, I allow reasonable access to my property to inspect the installation and performance of the technologies and installations that are eligible for incentives under the guidelines of New Jersey’s Clean Energy Program.

Page 336: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

New Jersey Clean Energy Program Technical Worksheet – Solar Electric Equipment Information

Please carefully read all of the following information. With the help of your Installation Contractor, fully complete Sections A through D, as applicable, of the attached Technical Worksheet for Solar Electric Equipment, as well as the New Jersey Clean Energy Program Rebate Application Form.

Rebates will be processed based on the date the New Jersey Clean Energy Program (NJCEP) approves the Final Application Form, not on the purchase date of the equipment. Program procedures and rebates are subject to change or cancellation without notice. To qualify for a rebate, Applicant must comply with all Program Eligibility Requirements, Terms and Conditions, and Installation Requirements, and submit a completed Pre-Installation Application Form. For more information about the New Jersey Clean Energy Program, or for assistance in completing applications or forms, please see www.njcleanenergy.com or call 866-NJSMART

Equipment installation must meet the following minimum requirements in order to qualify for payment under the provisions of the New Jersey Clean Energy Program; proposed changes to the requirements will be considered, but they must be documented by the Applicant or Installation Contractor and approved by the NJCEP. These requirements are not all-encompassing and are intended only to address certain minimum safety and efficiency standards.

1. The installation must comply with the provisions of the National Electrical Code and all other applicable local, state and federal codes or practices. 2. All required permits must be properly obtained and posted. 3. The NJCEP Inspection must be performed before the local Building Code Enforcement Office. If not, this may delay the processing of the rebate 4. All required inspections must be performed (i.e., Electrical/NEC, Local Building Codes Enforcement Office, etc.). Note: In order to ensure compliance with provisions of the NEC, an inspection by a state-licensed electrical inspector is mandatory.

1. Modules must be UL Listed and must be properly installed according to manufacturer’s instructions. 2. The maximum amount of sunlight available year-round on a daily basis should not be obstructed. All applications must include documentation of the impact from any obstruction on the annual performance of the solar electric array. This analysis can be performed by using the New Jersey Clean Power Estimator on the program website www.njcep.com. 3. In order to qualify for program incentives, the solar electric system must adhere to a minimum design threshold, relative to the estimated system production using PVWATTS:

• Solar electric array orientations require that the calculated system output must be at least 80% of the default output calculated by PVWatts. Additionally, all individual series strings of modules output must be at least 70% of the default output calculated by PVWatts. • For building integrated solar electric systems (i.e., part of the building envelope materials are comprised of solar electric components), the estimated system output must be 40% of the default output estimated by PVWATTS.

4. System wiring must be installed in accordance with the provisions of the NEC. 5. All modules installed in a series string must be installed in the same plane.

1. The inverter and controls must be properly installed according to manufacturer’s instructions. 2. The inverter must be certified as compliant with the requirements of IEEE 929 for small photovoltaic systems and with UL 1741. 3. The system should be equipped with the following visual indicators and/or controls:

• On/off switch • Operating mode setting indicator • AC/DC over current protection • Operating status indicator 4. Warning labels must be posted on the control panels and junction boxes indicating that the circuits are energized by an alternate power source independent of utility-provided power. 5. Operating instructions must be posted on or near the system, or on file with facilities operation and maintenance documents. 6. Systems must have monitoring capability that is readily accessible to the owner. This monitor (meter or display) must at minimum display instantaneous and cumulative production. All projects greater than 10kW must have an output meter that meets ANSI C.12 standards

1. Areas where wiring passes through ceilings, walls or other areas of the building must be properly restored, booted and sealed. 2. All interconnecting wires must be copper. (Some provisions may be made for aluminum wiring; approval must be received from utility engineering departments prior to acceptance.) 3. Thermal insulation in areas where wiring is installed must be replaced to “as found or better condition.” Access doors to these areas must be properly sealed and gasketed. 4. Wiring connections must be properly made, insulated and weather-protected. 5. All wiring must be attached to the system components by the use of strain relief’s or cable clamps, unless enclosed in conduit. 6. All outside wiring must be rated for wet conditions and/or encased in liquid-tight conduit. 7. Insulation on any wiring located in areas with potential high ambient temperature must be rated at 90° C or higher. 8. All wiring splices must be contained in UL-approved workboxes.

1. The batteries must be installed according to the manufacturer’s instructions. 2. Battery terminals must be adequately protected from accidental contact. 3. DC-rated over current protection must be provided in accordance with the provisions of the NEC.

Revised January 2009

GENERAL TERMS AND CONDITIONS

INSTALLATION REQUIREMENTS

A: Code Requirements

B: Solar Electric Module Array

C: Inverter and Controls

D: Control Panel to Solar Electric Array Wire Runs

E: Batteries (If Applicable)

Page 337: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

New Jersey Clean Energy Program Technical Worksheet – Solar Electric Equipment Information

Original Application Date: _________________ Revised Application Date: ______________________ Customer Name: _______________________________ Application Number: _________________ (Corresponding to Rebate Application Form) (Assigned by the NJBPU) A: EQUIPMENT INFORMATION 1. Solar Electric Module Manufacturer: ________________________ Module Model Number: _____________________________ 2. Power Rating per Module: ________ DC Watts (Refer to STC conditions) Number of Modules: _____________________________ 3. Total Array Output: _______ _ DC Watts (No. of Modules x Power Rating) 4. Inverter Manufacturer: __________________________________ Inverter Model Number: _____________________ 5. Inverter’s Continuous AC Rating: _________________________ AC Watts Number of Inverters: _____________________ 6. Total Inverter Output: ________ AC Watts (Inverter Continuous AC Rating x Number of Inverters) 7. Inverter’s Peak Efficiency: ______ _ _ (Refer to manufacturer’s peak efficiency rating)

1. Solar Electric Array Location: _ Rooftop _ Pole Mount or Ground Mount Location: 2. Solar Electric Module Orientation: __________ degrees (e.g., 180 degrees magnetic south)

Note: in Central New Jersey, magnetic south compass reading is 10 degrees east of true south. 3. Solar Electric Module Tilt: ___________ degrees (e.g., flat mount = 0 degrees; vertical mount = 90 degrees) 4. Solar Electric Module Tracking: _Fixed _Single-axis _Double-axis 5. Inverter Location: _ Indoor _ Outdoor Location: _________________________________________________________________ 6. Utility-Accessible AC Disconnect Switch Location: ________________________________________________________________ 7. System Type and Mode of Operation:

_ Utility interactive (parallel/capable of back feeding the meter) (_ with battery backup) _ Dedicated circuit, utility power as backup (transfer switch) (_ with battery charging) _ Stand-alone (system confined to an independent circuit, no utility backup) (_ with battery charging)

1. System rated output (Section A, line 3 above): ____________ DC Watts 2. Incentive Calculation (Calculate appropriate incentive based on System Rated Output):

Residential Applicants that perform Energy Efficiency Audit a. 0 to 10,000 Watts x $1.75/Watt = $___________________+

Commercial, Farm, Public and Non-Profit 0 to 50,000 Watts x $1.00/Watt = $_____________________+

Residential Applicants that do not perform Energy Efficiency Audit b. 0 to 10,000 Watts x $1.55/Watt = $___________________+

Large PV Project Applications > 50,000 Watts = $____Not eligible for rebates____________

d. Total Rebate Calculation: $__________________________

Total Rebate Calculation: $____________________________

3. School Applicants: Maximum Annual School Rebate: $________________ (For Public School applicants, enter the lesser value from no. 6 on the School Application form or $50,000) 4. Total Installed System Cost: $_____________________________

(Eligible installed system cost includes all equipment, installation, and applicable interconnection costs before the New Jersey Clean Energy Program incentive.)

5. Requested Incentive (Enter the appropriate value from C2. b or c): $___________________________________

1. Module: _____ Years at _____ Percent of Rated Power Output 2. Inverter:_____ Years 3. Installation: _____ Years Revised January 2009

B: PROPOSED INSTALLATION/INTERCONNECTION INFORMATION

C: INCENTIVE REQUEST CALCULATION

D: WARRANTY INFORMATION

Page 338: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

APPENDIX I

CONSTRUCTION ESTIMATES

Page 339: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 340: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Page 1 of 3

CDM PROJECT CONSTRUCTION COST ESTIMATE

100 Crossways Park West, Suite 415 Location: Freehold Township School DistrictWoodbury, NY 11797 Estimate by: BRPhone (516) 496-8400 Checked by: MGFax (516) 496-8864

ITEM DESCRIPTION QTY UNIT MATERIAL MATERIAL QTY UNIT LABOR LABOR TOTALUNIT COST SUBTOTAL COST SUBTOTAL

D.D. Eisenhower Middle School 1 Lamps, fixtures, ballasts, etc. 1 ea. 9,839.00$ 9,839.00$ 1 ea. 3,529.00$ 3,529.00$ 19,005.00$

Occupancy sensors 1 ea. 3,345.00$ 3,345.00$ 1 ea. 2,292.00$ 2,292.00$ Subtotal 13,184.00 5,821.00

J.J. Catena Elementary School 2 Lamps, fixtures, ballasts, etc. 1 ea. 4,759.00$ 4,759.00$ 1 ea. 1,921.00$ 1,921.00$ 13,782.00$

Occupancy sensors 1 ea. 4,080.00$ 4,080.00$ 1 ea. 3,022.00$ 3,022.00$ Subtotal 8,839.00 4,943.00

C.T. Barkalow Middle School 3 Lamps, fixtures, ballasts, etc. 1 ea. 18,943.00$ 18,943.00$ 1 ea. 12,061.00$ 12,061.00$ 31,004.00$

Occupancy sensors 1 ea. - - 1 ea. - -Subtotal 18,943.00 12,061.00

Early Childhood Learning Center4 Lamps, fixtures, ballasts, etc. 1 ea. 2,681.00$ 2,681.00$ 1 ea. 1,348.00$ 1,348.00$ 7,625.00$

Occupancy sensors 1 ea. 2,180.00$ 2,180.00$ 1 ea. 1,416.00$ 1,416.00$ Subtotal 4,861.00 2,764.00

M.W. Errickson5 Lamps, fixtures, ballasts, etc. 1 ea. 15,448.00$ 15,448.00$ 1 ea. 20,164.00$ 20,164.00$ 38,572.00$

Occupancy sensors 1 ea. 1,750.00$ 1,750.00$ 1 ea. 1,210.00$ 1,210.00$ Subtotal 17,198.00 21,374.00

Laura Donovan Elementary School 6 Lamps, fixtures, ballasts, etc. 1 ea. 5,395.00$ 5,395.00$ 1 ea. 2,233.00$ 2,233.00$ 13,976.00$

Occupancy sensors 1 ea. 3,660.00$ 3,660.00$ 1 ea. 2,688.00$ 2,688.00$ Subtotal 9,055.00 4,921.00

West Freehold Elementary School 7 Lamps, fixtures, ballasts, etc. 1 ea. - - 1 ea. - - 5,539.00$

Occupancy sensors 1 ea. 3,095.00$ 3,095.00$ 1 ea. 2,444.00$ 2,444.00$ Subtotal 3,095.00 2,444.00

C.R. Applegate Elementary School 8 Lamps, fixtures, ballasts, etc. 1 ea. 8,577.00$ 8,577.00$ 1 ea. 3,487.00$ 3,487.00$ 15,052.00$

Occupancy sensors 1 ea. 1,740.00$ 1,740.00$ 1 ea. 1,248.00$ 1,248.00$ Subtotal 10,317.00 4,735.00

SUBTOTAL = 144,555.00$ MARKUP % = 0.43$

MARKUP = 62,158.65$ BUDGET COST ESTIMATE = 206,713.65$

Lighting System Improvements - Option 1

5:08 PM 6/30/2009

Page 341: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Page 2 of 3

CDM PROJECT CONSTRUCTION COST ESTIMATE

100 Crossways Park West, Suite 415 Location: Freehold Township School DistrictWoodbury, NY 11797 Estimate by: BRPhone (516) 496-8400 Checked by: MGFax (516) 496-8864

ITEM DESCRIPTION QTY UNIT MATERIAL MATERIAL QTY UNIT LABOR LABOR TOTALUNIT COST SUBTOTAL COST SUBTOTAL

D.D. Eisenhower Middle School 1 28W T8s & Option 1 improvements 1 ea. 21,868.00$ 21,868.00$ 1 ea. 18,012.00$ 18,012.00$ 45,517.00$

Occupancy sensors 1 ea. 3,345.00$ 3,345.00$ 1 ea. 2,292.00$ 2,292.00$ Subtotal 25,213.00 20,304.00

J.J. Catena Elementary School 2 28W T8s & Option 1 improvements 1 ea. 12,053.00$ 12,053.00$ 1 ea. 11,795.00$ 11,795.00$ 30,950.00$

Occupancy sensors 1 ea. 4,080.00$ 4,080.00$ 1 ea. 3,022.00$ 3,022.00$ Subtotal 16,133.00 14,817.00

C.T. Barkalow Middle School 3 28W T8s & Option 1 improvements 1 ea. 27,166.00$ 27,166.00$ 1 ea. 25,034.00$ 25,034.00$ 52,200.00$

Occupancy sensors 1 ea. - - 1 ea. - -Subtotal 27,166.00 25,034.00

Early Childhood Learning Center4 28W T8s & Option 1 improvements 1 ea. 6,810.00$ 6,810.00$ 1 ea. 5,982.00$ 5,982.00$ 16,388.00$

Occupancy sensors 1 ea. 2,180.00$ 2,180.00$ 1 ea. 1,416.00$ 1,416.00$ Subtotal 8,990.00 7,398.00

M.W. Errickson5 28W T8s & Option 1 improvements 1 ea. 37,579.00$ 37,579.00$ 1 ea. 21,872.00$ 21,872.00$ 62,411.00$

Occupancy sensors 1 ea. 1,750.00$ 1,750.00$ 1 ea. 1,210.00$ 1,210.00$ Subtotal 39,329.00 23,082.00

Laura Donovan Elementary School 6 28W T8s & Option 1 improvements 1 ea. 13,180.00$ 13,180.00$ 1 ea. 10,951.00$ 10,951.00$ 30,479.00$

Occupancy sensors 1 ea. 3,660.00$ 3,660.00$ 1 ea. 2,688.00$ 2,688.00$ Subtotal 16,840.00 13,639.00

West Freehold Elementary School 7 28W T8s & Option 1 improvements 1 ea. 10,417.00$ 10,417.00$ 1 ea. 13,757.00$ 13,757.00$ 29,713.00$

Occupancy sensors 1 ea. 3,095.00$ 3,095.00$ 1 ea. 2,444.00$ 2,444.00$ Subtotal 13,512.00 16,201.00

C.R. Applegate Elementary School 8 28W T8s & Option 1 improvements 1 ea. 15,867.00$ 15,867.00$ 1 ea. 12,911.00$ 12,911.00$ 31,766.00$

Occupancy sensors 1 ea. 1,740.00$ 1,740.00$ 1 ea. 1,248.00$ 1,248.00$ Subtotal 17,607.00 14,159.00

SUBTOTAL = 299,424.00$ MARKUP % = 0.43$

MARKUP = 128,752.32$ BUDGET COST ESTIMATE = 428,176.32$

Lighting System Improvements - Option 2

5:08 PM 6/30/2009

Page 342: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Page 1 of 1

CDM PROJECT CONSTRUCTION COST ESTIMATE

15 British American Blvd Location: Freehold TownshipLatham, NY 12110 Estimate by: RKAPhone (518) 782-4500 Checked by: MGFax (518) 786-3810

ITEM DESCRIPTION QTY UNIT MATERIAL MATERIAL QTY UNIT LABOR LABOR TOTALUNIT COST SUBTOTAL COST SUBTOTAL

C.R. Applegate

1Enthalpy Recovery Wheel - 2,000 Max CFM

6 ea. 10,000.00$ 60,000.00$ 6 ea. 680.00$ 4,080.00$ 64,080.00$ Subtotal 60,000.00 4,080.00

SUBTOTAL = 64,080.00$ MARKUP % = 0.15$

MARKUP = 9,612.00$ SUB-TOTAL w/ OH & P = 73,692.00$

CONTINGENCY % = 0.25CONTINGENCY = 18,423.00$

BUDGET COST ESTIMATE = 92,115.00$

9:41 AM 7/1/2009

Page 343: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Page 1 of 1

CDM PROJECT CONSTRUCTION COST ESTIMATE

15 British American Blvd Location: Freehold TownshipLatham, NY 12110 Estimate by: RKAPhone (518) 782-4500 Checked by: MGFax (518) 786-3810

ITEM DESCRIPTION QTY UNIT MATERIAL MATERIAL QTY UNIT LABOR LABOR TOTALUNIT COST SUBTOTAL COST SUBTOTAL

CT Barkalow School

1Boiler, Gas-Fired, Condensing High Efficiency2,000 MBH 2 ea. 68,000.00$ 2 ea. 5,750.00$ 11,500.00$ 79,500.00$ Subtotal 68,000.00 11,500.00

SUBTOTAL = 79,500.00$ MARKUP % = 0.15$

MARKUP = 11,925.00$ SUB-TOTAL w/ OH & P = 91,425.00$

CONTINGENCY % = 0.25CONTINGENCY = 22,856.25$

BUDGET COST ESTIMATE = 114,281.25$

3:51 PM 6/30/2009

Page 344: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Page 1 of 1

CDM PROJECT CONSTRUCTION COST ESTIMATE

15 British American Blvd Location: Freehold TownshipLatham, NY 12110 Estimate by: RKAPhone (518) 782-4500 Checked by: MGFax (518) 786-3810

ITEM DESCRIPTION QTY UNIT MATERIAL MATERIAL QTY UNIT LABOR LABOR TOTALUNIT COST SUBTOTAL COST SUBTOTAL

Early Childhood Learning Center1 R21 15" Wide 37,156 SF 0.50$ 18,578.00$ 37,156 SF 0.24$ 8,917.44$ 27,495.44$

Subtotal 18,578.00 8,917.44SUBTOTAL = 27,495.44$ MARKUP % = 0.15$

MARKUP = 4,124.32$ SUB-TOTAL w/ OH & P = 31,619.76$

CONTINGENCY % = 0.25CONTINGENCY = 7,904.94$

BUDGET COST ESTIMATE = 39,524.70$

3:52 PM 6/30/2009

Page 345: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Page 1 of 1

CDM PROJECT CONSTRUCTION COST ESTIMATE

15 British American Blvd Location: Freehold TownshipLatham, NY 12110 Estimate by: RKAPhone (518) 782-4500 Checked by: MGFax (518) 786-3810

ITEM DESCRIPTION QTY UNIT MATERIAL MATERIAL QTY UNIT LABOR LABOR TOTALUNIT COST SUBTOTAL COST SUBTOTAL

J.J. Catena School

1Boiler, Gas-Fired, Condensing High Efficiency2,000 MBH 2 ea. 68,000.00$ 2 ea. 5,750.00$ 11,500.00$ 79,500.00$ Subtotal 68,000.00 11,500.00

SUBTOTAL = 79,500.00$ MARKUP % = 0.15$

MARKUP = 11,925.00$ SUB-TOTAL w/ OH & P = 91,425.00$

CONTINGENCY % = 0.25CONTINGENCY = 22,856.25$

BUDGET COST ESTIMATE = 114,281.25$

3:52 PM 6/30/2009

Page 346: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Page 1 of 1

CDM PROJECT CONSTRUCTION COST ESTIMATE

15 British American Blvd Location: Freehold TownshipLatham, NY 12110 Estimate by: RKAPhone (518) 782-4500 Checked by: MGFax (518) 786-3810

ITEM DESCRIPTION QTY UNIT MATERIAL MATERIAL QTY UNIT LABOR LABOR TOTALUNIT COST SUBTOTAL COST SUBTOTAL

J.J. Catena School

1Thermostat, Manual, 1 set back, electric, timed 11 ea. 95.00$ 1,045.00$ 11 ea. 47.00$ 517.00$ 1,562.00$ Subtotal 1,045.00 517.00

SUBTOTAL = 1,562.00$ MARKUP % = 0.15$

MARKUP = 234.30$ SUB-TOTAL w/ OH & P = 1,796.30$

CONTINGENCY % = 0.25CONTINGENCY = 449.08$

BUDGET COST ESTIMATE = 2,245.38$

9:24 AM 7/1/2009

Page 347: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Page 1 of 1

CDM PROJECT CONSTRUCTION COST ESTIMATE

15 British American Blvd Location: Freehold TownshipLatham, NY 12110 Estimate by: RKAPhone (518) 782-4500 Checked by: MGFax (518) 786-3810

ITEM DESCRIPTION QTY UNIT MATERIAL MATERIAL QTY UNIT LABOR LABOR TOTALUNIT COST SUBTOTAL COST SUBTOTAL

M.W. Errickson

1Enthalpy Recovery Wheel - 2,000 Max CFM

4 ea. 10,000.00$ 40,000.00$ 4 ea. 680.00$ 2,720.00$ 42,720.00$ Subtotal 40,000.00 2,720.00

SUBTOTAL = 42,720.00$ MARKUP % = 0.15$

MARKUP = 6,408.00$ SUB-TOTAL w/ OH & P = 49,128.00$

CONTINGENCY % = 0.25CONTINGENCY = 12,282.00$

BUDGET COST ESTIMATE = 61,410.00$

9:42 AM 7/1/2009

Page 348: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

Page 3 of 3

CDM PROJECT CONSTRUCTION COST ESTIMATE

100 Crossways Park West, Suite 415 Location: Freehold Township School DistrictWoodbury, NY 11797 Estimate by: BRPhone (516) 496-8400 Checked by: MGFax (516) 496-8864

ITEM DESCRIPTION QTY UNIT MATERIAL MATERIAL QTY UNIT LABOR LABOR TOTALUNIT COST SUBTOTAL COST SUBTOTAL

D.D. Eisenhower Middle School 1 Solar Energy System 1 ea. 928,700.00$ 928,700.00$ 1 ea. 476,900.00$ 476,900.00$ 1,405,600.00$

Subtotal 928,700.00 476,900.00

J.J. Catena Elementary School 2 Solar Energy System 1 ea. 349,400.00$ 349,400.00$ 1 ea. 172,900.00$ 172,900.00$ 522,300.00$

Subtotal 349,400.00 172,900.00

C.T. Barkalow Middle School 3 Solar Energy System 1 ea. 446,600.00$ 446,600.00$ 1 ea. 224,200.00$ 224,200.00$ 670,800.00$

Subtotal 446,600.00 224,200.00

Early Childhood Learning Center4 Solar Energy System 1 ea. 259,000.00$ 259,000.00$ 1 ea. 133,000.00$ 133,000.00$ 392,000.00$

Subtotal 259,000.00 133,000.00

M.W. Errickson5 Solar Energy System 1 ea. 388,497.00$ 388,497.00$ 1 ea. 199,500.00$ 199,500.00$ 587,997.00$

Subtotal 388,497.00 199,500.00

Laura Donovan Elementary School 6 Solar Energy System 1 ea. 583,920.00$ 583,920.00$ 1 ea. 300,200.00$ 300,200.00$ 884,120.00$

Subtotal 583,920.00 300,200.00

West Freehold Elementary School 7 Solar Energy System 1 ea. 223,500.00$ 223,500.00$ 1 ea. 104,500.00$ 104,500.00$ 328,000.00$

Subtotal 223,500.00 104,500.00

C.R. Applegate Elementary School 8 Solar Energy System 1 ea. 478,800.00$ 478,800.00$ 1 ea. 235,600.00$ 235,600.00$ 714,400.00$

Subtotal 478,800.00 235,600.00SUBTOTAL = 5,505,217.00$ MARKUP % = 0.15$

MARKUP = 825,782.55$ BUDGET COST ESTIMATE = 6,331,000$

5:08 PM 6/30/2009

Page 349: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 350: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

APPENDIX J

FACILITY DATA FORMS

Page 351: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey

 

Page 352: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 353: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 354: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 355: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 356: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 357: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 358: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 359: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 360: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 361: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 362: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 363: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 364: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 365: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 366: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey
Page 367: Enery Audit Final Report 8-11-09 - Amazon S3Twp+BOE+E… · CDM’s energy audit for the Freehold Township Board of Education. ... C.E.M., C.E.A., LEED®AP ... Appendix H New Jersey