Energy Labs Inc Test Report FLNG ARCHITECTUAL LQF-CC
Transcript of Energy Labs Inc Test Report FLNG ARCHITECTUAL LQF-CC
9651Cactus Road San Diego CA 92154Ph. (619) 671 0100 Fax. (619) 671 0160
Energy Labs:Job Number 9486
Sales Agency Hunton Group - HoustonTest Date 1/10/2017
Energy Labs Inc
Test Report FLNG ARCHITECTUAL LQF-CCB
TEST REPORT INDEX
SECC Page
1 TEST PROCEDURE……………………………………………………….... 3
2 INSTRUMENT LIST…………………………………………………………. 6
3 SUBMITTAL DATA………………………………………………………….. 8
4 LEAK TEST RESULTS…………………………….………………….......… 11
5 SETUP PICTURES………………………………………………………….. 14
Section 1 Test Procedure
Section 2 Instrument List
Serial #Dwyer Digital Manometer, Model 477AV-2 N/A
INSTRUMENT LIST
LEAKAGE Serial #McGill AirFlow Orifice Tube #6090-5 6090-5
PRESSURE
Section 3 Submittal Data
FLNG - Architectual Bldgs - 3.25.16 MMJob Number:0Unit Tag:17AHU004B
FAN CURVE Ver. 6.24 May, 2010
Fan Duty: Supply Wheel Type: ELPF-ALUMFan Size: 222 Manufacturer: Energy LabsFan Model: Plenum Fan Maximum RPM: 3065Fan Class: 3 Qty of Fans: 1Wheel Width: 100%
Operating:
Standard:
CFM SP BHP DrHP RPM ALT TEMP SE 6050 3.43
3.43
4.55
4.55
N/A 1556 0
0
70
70
71.8
AMCA International Licensed for Sound and Air Performance•Energy Labs Inc. certifies that the model ELPF shown herein is licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311, and comply with the requirements of the AMCA certified ratings program.•Operating performance and Sound information is for individual fans•Power rating (BHP) does not include transmission losses.•Performance ratings do not include the effects of appurtenances (accessories)•Performance certified is for installation type A: Free inlet, Free outlet•The sound power level ratings shown are in decibels, referred to 1E-12 watts, calculated per AMCA Standard 301.•Sound power levels shown are for installation type A: Free inlet, Free outlet•Only outlet sound power levels (Lwo) are certified in accordance with AMCA 311
Section 4 Leak Test Results
JOB NAME: FLNG ARCHITECTUAL LQF-CCB UNIT TSP: 3.430 In.WCJOB NUMBER 9486 UNIT CFM: 6050
DATE: 1/10/2017 TEST PRESSURE: 8.00 In.WCUNIT TAG: 17AHU-004B
LEAKAGE (1% of Total CFM OR 100 Wichever is greater)
PD (In.Wc.) CFM %Submitted: 0.42 100.00 1.65%
Actual: 0.39 96.48 1.59%
LEAKAGE TEST REPORT
Adrian Ramirez Otto Alvarado
POSITIVE PRESSURE
Tested by: Verified by:
10
100
1000
10000
0.1 1.0 10.0 100.0
CF
M
MANOMETER READINGS "PD", INCHES OF WATER
United McGill Orifice Tube # 6090-S CFM=154.261*PD0.4984
ACTUAL 1% OF DESIGN FLOW
JOB NAME: FLNG ARCHITECTUAL LQF-CCB UNIT TSP: 3.430 In.WCJOB NUMBER 9486 UNIT CFM: 6050
DATE: 1/10/2017 TEST PRESSURE: 8.00 In.WCUNIT TAG: 17AHU-004B
LEAKAGE (1% of Total CFM OR 100 Wichever is greater)
PD (In.Wc.) CFM %Submitted: 0.42 100.00 1.65%
Actual: 0.39 96.48 1.59%
LEAKAGE TEST REPORT
Adrian Ramirez Otto Alvarado
NEGATIVE PRESSURE
Tested by: Verified by:
10
100
1000
10000
0.1 1.0 10.0 100.0
CF
M
MANOMETER READINGS "PD", INCHES OF WATER
United McGill Orifice Tube # 6090-S CFM=154.261*PD0.4984
ACTUAL 1% OF DESIGN FLOW