ENERGY EFFICIENCY AWARENESS SEMINAR 2010 Building Code of Australia Regulatory Measures
-
Upload
hoyt-mcknight -
Category
Documents
-
view
24 -
download
0
description
Transcript of ENERGY EFFICIENCY AWARENESS SEMINAR 2010 Building Code of Australia Regulatory Measures
DEPARTMENT OF LANDS AND PLANNING
www.nt.gov.au
ENERGY EFFICIENCY ENERGY EFFICIENCY
AWARENESS SEMINAR AWARENESS SEMINAR
20102010
Building Code of AustraliaBuilding Code of AustraliaRegulatory MeasuresRegulatory Measures
Commencing 1 May 2010Commencing 1 May 2010
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
PURPOSE• To provide an overview of the changes to the energy efficiency provisions in the Building Code of Australia 2010 (NT variation)
• On 1st May 2010, energy efficiency requirements will be increased: – New homes & extensions (Class I and 10
buildings) will move from 3.5 stars to 5 stars equivalent
– Apartments/flats and caretakers residences (Class 2 and 4 buildings) will move from currently no stars to 3.5 stars equivalent
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
CONTENT• Background
• Building Code of Australia structure
• Session 1 - Energy efficiency measures for houses and garages
• Break
• Session 2 - Energy efficiency measures for apartments, flats and caretaker’s residences
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
BACKGROUND• For housing - NT adopted 3.5 star measures in 2003
• BCA 2005 introduced 3.5 stars apartments and flats
• BCA 2006 increased the stringency to 5 Stars
• The NT is now adopting 5 star as 1 May 2010
• COAG proposed new 6 star provisions and increased stringency for commercial buildings for BCA 2010
– Territory has not adopted
– Further consideration after 5 star commences
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
Building SolutionBuilding Solution
Performance RequirementsPerformance Requirements
Functional StatementFunctional Statement
ObjectiveObjective
Alternative SolutionAlternative SolutionDTS ProvisionsDTS Provisions
Guidance
Mandatory
Methods of achieving compliance
Documentary EvidenceDocumentary Evidence
Verification Method Verification Method
Expert Judgement Expert Judgement
Comparative Analysis Comparative Analysis
Ass
essm
ent
Ass
essm
ent
met
ho
ds
met
ho
ds
BCA HIERARCHY
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
5 STAR ENERGY5 STAR ENERGYEFFICIENCY PROVISIONSEFFICIENCY PROVISIONS
BCA VOLUME TWOBCA VOLUME TWO
HOUSESHOUSES
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
BUILDING CODE OF AUSTRALIAOBJECTIVE
The Object is to reduce greenhouse gas emissions by efficiently using energy
FUNCTIONAL STATEMENTTo reduce greenhouse gas emissions, a building, including its domestic services, is to be capable of efficiently using energy
PERFORMANCE REQUIREMENTA building and its domestic services must have a level of thermal performance and features to facilitate the efficient use of energy for artificial heating and cooling appropriate to the function and use of the building etc………….
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ZONES APPLICABLE
NEWOLD
Climate zone 1 Climate zone 1
Climate zone 3Climate zone 3
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
BCA VOLUME TWO SCOPEFive distinct aspects addressed:
1. Building Fabric• Thermal Insulation• Roof• External Walls• Floors
2. Glazing
3. Building Sealing
4. Air Movement
5. Domestic Services
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
THERMAL INSULATION• Comply with AS/NZS 4859.1
• Needs to abut or overlap adjoining insulation
• Needs to form a continuous thermal barrier
• Abuts supporting members such as rafters, purlins, noggings, joists and the like
• Must be installed so as to not affect the safe and effective operation of a domestic service or fitting
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
BCA EXPLANATORY INFORMATION
The BCA & Guide contain explanatory informationon possible increased risk if inappropriate solutions are chosen by designers or builders.
These include:
• Fire resulting from insulation being close to downlights
• Condensation damage (See CSIRO & DEWHA publications)
• Plaster sagging under the weight of insulation & lights
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
• R-Value or material R-Value is the thermal resistance of an individual building material or component
• Total R-Value is the sum of all the R-Values of individual components in a composite building assembly e.g. roof
THERMAL INSULATIONPRINCIPLE OF R-VALUES
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
• R-Value or material R-Value is the thermal resistance of an individual building material or component
• Total R-Value is the sum of all the R-Values of individual components in a composite building assembly e.g. roof
THERMAL INSULATION
R-Valueor material
R-Value
Total R-Value
PRINCIPLE OF R-VALUES
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
• Thermal break - A thermal break restricts the conductance of heat via metal framing members of:– Roofs
– Walls
THERMAL INSULATION
Lining
Insulation
Cladding
Metal frame
Heat transfer area
PRINCIPLE OF THERMAL BREAK
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
THERMAL INSULATIONPRINCIPLE OF THERMAL BREAK
• Thermal break - A thermal break restricts the conductance of heat via metal framing members of:– Roofs
– Walls Lining
InsulationCladding
Metal frame
Heat transfer area
Thermal break
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
THERMAL INSULATIONPRINCIPLE OF THERMAL BREAK
Thermal breaks for Roofs and Walls can be:
– Timber - Minimum 20mm thick OR
– Expanded polystyrene strips - 12mm thick OR
– Compressed bulk insulation providing a minimum R-Value of 0.2
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ROOFS
Current New
3.5 Star 5.0 Star
Total R-Value 2.2 Total R-Value 2.7
Total R-Value is increased by 0.5
CLIMATE ZONE 1 & 3 INSULATION
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
Location of insulationInsulation can be added at the roof sheeting level or ceiling level or a combination of both
ConcessionsThe Total R-Value of a roof may be reduced by 0.5 for each:• Light Coloured Roof - The dwelling has a light coloured roof
installed e.g. zincalume, galvanised, light grey, off white, light cream or the like
• Ventilated Roof Space - The design of the dwelling has: - a pitched roof; and- a flat ceiling; and - a ventilated roof space
ROOFS
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
Required Total R-Value 2.7
Light coloured roof concession - 0.5
Ventilated pitched roof concession - 0.5
Adjusted Total R-Value = 1.7
ROOFS
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
DOWNLIGHTS & EXHAUST FANS
• Ceiling insulation must comply with the minimum clearances as specified by the wiring rules
ROOFS
AS
/NZ
S 3
00
0 e
xtra
ct
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
• The minimum clearances as specified by the wiring rule will result in a loss of insulation
• A reduction of the area of insulation that does not exceed 1% of the ceiling area requires no change
• A reduction that exceeds 1% requires an increase in the R-Value over the rest of the ceiling as per the BCA
ROOFSDOWN LIGHTS AND EXHAUST FANS
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ROOF LIGHTS
• Roof lights area:
– If 1.5% of room floor area - no requirements(no change)
– Can now go up to 10% of room floor area BUT
• Cannot exceed 3% of the floor area of the storey (no change)
• Increase thermal performance depending upon size of each roof light & length of light shaft
ROOFS
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ROOF LIGHTS
ROOFS
Shaft diameter O
Ceiling level
Roof cladding
Roof light Shaft
1/2
1/2
Roof light
Shaft length L
Roof light shaft index = L O
• Desirable outcome:– Long shaft OR– Small diameter OR– Higher performing
roof lights
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
SUMMARY
• Increase of 0.5 in Total R-Value
• Light coloured & ventilated roof concessions
• Thermal break requirements
• Higher R-Value ceiling insulation where downlights and exhaust fans exceed 1%
• Increased stringency of roof lights
ROOFS
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
EXTERNAL WALLS
Current New
3.5 Star 5.0 Star
Total R-Value 1.4 Total R-Value 1.9
This is an increase in the total R-value of 0.5
CLIMATE ZONE 1 & 3 INSULATION
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
Solutions for climate zone 1:
• Insulate to Total R-Value of 1.9
– Reduce to R1.4 with slab-on-ground
• Shading options
– For sheet cladding construction
– For high mass walls (not less than220 kg/m2)
EXTERNAL WALLS
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
Sheet cladding (metal, cement, weather board):
• Reflective insulation e.g. reflective foil laminate, foil bonded to batts or the like AND
• Slab-on-ground AND
• Shading at 15° projected from the floor to underside of eave or gutter (e.g. 2360mm wall height will require a min 750mm overhang based on a 22° roof pitch)
EXTERNAL WALLS SHADING OPTIONS - CLIMATE ZONE 1 ONLY
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
Masonry with not less than 220 kg/m2 of wall:
• Nth & Sth orientation 15° projected from the floor to underside of eave or gutter (e.g. 2360mm wall height will require a min 750mm overhang based on a 22° roof pitch)
• All other orientations 45° projected from the floor (e.g. 2360mm wall height will require a min 2000mm overhang based on a 22° roof pitch)
EXTERNAL WALLS SHADING OPTIONS - CLIMATE ZONE 1 ONLY
NORTH SECTOR
NORTH EAST SECTOR
EAST SECTOR
SOUTH SECTOR
SOUTH WEST SECTOR
WEST SECTOR
NORTH WEST SECTOR
SOUTH EAST SECTOR
Tru
e N
ort
h (
0°)
NORTH SECTOR
NORTH EAST SECTOR
EAST SECTOR
SOUTH SECTOR
SOUTH WEST SECTOR
WEST SECTOR
NORTH WEST SECTOR
SOUTH EAST SECTOR
Tru
e N
ort
h (
0°)
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
North & South only
EXTERNAL WALLS
E, W, NE, SE, NW & SWNORTH SECTOR
NORTH EAST SECTOR
EAST SECTOR
SOUTH SECTOR
SOUTH WEST SECTOR
WEST SECTOR
NORTH WEST SECTOR
SOUTH EAST SECTOR
Tru
e N
ort
h (
0°)
NORTH SECTOR
NORTH EAST SECTOR
EAST SECTOR
SOUTH SECTOR
SOUTH WEST SECTOR
WEST SECTOR
NORTH WEST SECTOR
SOUTH EAST SECTOR
Tru
e N
ort
h (
0°)
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
EXTERNAL WALLS • Solutions for climate zone 3:
• Insulate to Total R-Value of 1.9
– Reduce to R1.4 with slab-on-ground
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
• Increase of 0.5 in Total R-value (R1.4 to R1.9)
• Reduced to R1.4 with slab-on-ground
• Other options for climate zone 1:
– Masonry wall: insulate & shade
– Sheet cladding wall: foil,slab-on-ground & shade
• Again, thermal breaks required forsome metal framed walls
SUMMARY
EXTERNAL WALLS
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
FLOORS
Climate Zones 1 and 3
No insulation requirements
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
• 3.5 Star glazing was based on % of glazingto floor area with only north consideration
• 5 Star glazing sets an allowance for conductance & solar heat gain taking into account the orientation, floor type & air movement rate
• For compliance there are two calculations (conductance and solar heat gain) which considers each window and glass door; their orientation, thermal performance & shading
GLAZING
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
• 3.5 Star glazing was also based on generic glass and frame systems whereas 5 Star is based on the glass & frame combined thermal performance
• Also shading which can take the form of an eave, awning, veranda, carport or permanent external shading device e.g. shutters, blinds, screens etc
• The ABCB has developed Glazing calculators (Excel 2003 & 2007) to assist in performing the calculations and determining compliance
GLAZING
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
GLAZINGIMPORTANT TERMINOLOGY
Solar Heat gain
SHGC for clear glazing 0.81SHGC for best glazing 0.21
Conductance
Insulation: R-ValueGlazing: U-ValueU-Value for clear glazing 7.9U-Value for best glazing 2.1
25OC 35OC
http://www.wers.net
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
BUILDING SEALING
• No change from what is currently required
• Applies to conditioned spaces and requires:
– Roof light being sealed or capable of being sealed
– Openings (including windows and external doors) having edge seals
– Exhaust fans fitted with self closing dampers or a high density filter
– Internal lining systems sealed at all junctions
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
AIR MOVEMENT• No Change from what is currently required• Habitable rooms to have ventilation openings to
allow air movement to limit artificial cooling• Opening sizes are a percentage of the area of the
habitable room’s floor• Ventilation openings percentages:
– Climate zone 1 15% of floor area without fans
12.5% of floor area with fans– Climate zone 3 12.5% of floor area without fans
7.5% of floor area with fans
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
Openings providing ventilation to a habitableroom in climate zones 1 & 3 must either:
1. Connect a ventilation opening to another in another room via a breeze path- – passing through not more than two opening in an internal wall each
opening having an area of not less than 1.5 m2; and– have a distance along the breeze path between ventilation
openings of not more than 20m OR
2. Provide a minimum of two ventilation openings in the same habitable room-– with each ventilation opening having an area of not less than 25%
of the required area
AIR MOVEMENT
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
To qualify as a fan it must:• Be permanently fixed to the ceiling• Have a blade rotation diameter of at least 900mm• Have a speed controller
AIR MOVEMENT
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
SERVICES• No Change from what is currently required
• See AS/NZS 3500.4 or .5:– Cold water supply pipe - insulate last 500mm to achieve
minimum R-Value of 0.3
– Hot water supply pipe - insulate last 500mm to achieve minimum R-value of 0.3
– External pipes from the water heater to primary kitchen sink to achieve a minimum R-Value of 0.3
• Does not apply to Solar hot water heaters in the NT
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ALTERNATIVE SOLUTIONS• So far we have covered the BCA Deemed-to-
Satisfy Provisions. They are one way to comply.
• Alternative ways to comply are:
– A Verification Method: A NatHERS rating of 5 star for the dwelling
– Expert Judgement: Peer review
• Note that the domestic services provisionsstill apply
Methods of achieving compliance
Building SolutionBuilding Solution
Performance RequirementsPerformance Requirements
Functional StatementFunctional Statement
ObjectiveObjective
Alternative SolutionAlternative SolutionDTS ProvisionsDTS Provisions
Guidance
Mandatory
Documentary EvidenceDocumentary Evidence
Verification Method Verification Method
Expert Judgement Expert Judgement
Comparative Analysis Comparative Analysis
Ass
essm
ent
Ass
essm
ent
met
ho
ds
met
ho
ds
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ALTERNATIVE SOLUTIONS
Verification Method: • Computer software - more flexible solution
• NatHERS approved software
• Achieve a 5 star rating
• DEWHA Protocol for Assessor Accrediting Organisations
• No NT registration
• AccuRate Training in April
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ALTERNATIVE SOLUTIONS
Expert Judgement:
• Free running houses
• Queensland Peer Review Process
• NT recognition of Queensland Experts
• Private contractual arrangements
DEPARTMENT OF LANDS AND PLANNING
www.nt.gov.au
END OF SESSION 1 - HOUSINGEND OF SESSION 1 - HOUSING
ANY QUESTIONS?ANY QUESTIONS?
www.nt.gov/lands/building
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
3.5 STARS3.5 STARS ENERGY ENERGYEFFICIENCY PROVISIONSEFFICIENCY PROVISIONS
SESSION 2 - SESSION 2 - BCA VOLUME ONEBCA VOLUME ONE
APARTMENTS, FLATS AND APARTMENTS, FLATS AND CARETAKER’S RESIDENCECARETAKER’S RESIDENCE
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
BCA VOLUME ONE SCOPEEight distinct aspects addressed:
1. Building Fabric (similar items to Housing)2. Glazing (similar to Housing)3. Building Sealing (similar to Housing)4. Air Movement (similar to Housing)5. Air-Conditioning & Ventilation6. Artificial Light & power7. Hot Water Supply (similar to Housing)8. Access for Maintenance
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
NEW CONCEPTENVELOPE
Envelope means the parts of a building’s fabric that separate aconditioned space or habitable room from— (a) the exterior of the building; or(b) a non-conditioned space including—
(i) the floor of a rooftop plant room, lift-machine room etc and(ii) the floor above a carpark or warehouse and(iii) the common walls with a carpark, warehouse or the like,
other than a non-conditioned space through which conditionedair is being exhausted or relieved such as an internal corridor,cleaner’s room, chemical storage room or exhaust riser.
i.e. the envelope is the boundary of the “conditioned” space
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
NEW CONCEPTENVELOPE
Plan
Plant room
Bedroom
Apartment Two
Ensuite
Access stair
Apartment One
EnsuiteStair
Plant room
Apartment 1
Apartment 2
Car park
Elevation
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
THERMAL INSULATION
• Same as Volume Two:
• Testing Standard
• Installation
• Thermal breaks
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ROOFS
Total R-Value
Roof or ceiling generally 2.2
Roof of a light colour ( reduction of R0.5) 1.7
Ceiling below a non-conditioned space 1.1
CLIMATE ZONE 1 & 3 INSULATION
Plant room
Apartment 1
Apartment 2
Car park
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
DOWNLIGHTS & EXHAUST FANS
• No requirement for apartments, flats and caretaker’s residences under BCA
ROOFS
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ROOF LIGHTS
ROOFS
• Same as Volume Two
Shaft diameter O
Ceiling level
Roof cladding
Roof light Shaft
1/2
1/2
Roof light
Shaft length L
Roof light shaft index = L O
• Desirable outcome:– Long shaft OR– Small diameter OR– Higher performing
roof lights
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
SUMMARY
• Total R-Values for roofs R2.2
• Total R-Values for internal ceilings undernon-conditioned spaces R1.1
• Thermal break
• Roof lights
ROOFS
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
WALLS CLIMATE ZONE 1 & 3 INSULATION
Solutions:
(a) External wall that is part of an envelope, insulateto a Total R-Value of 1.4 OR
(b) Shade external wall to 15° projected from the floor to underside of eave or gutter (e.g. 2360mm wall height will require a min 750mm overhang based on a 22° roof pitch)
• South facing wall exemption below Tennant Creek
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
• If external and part of an envelope:
– Total R-value of 1.4 OR
– Shade
• Thermal break
SUMMARY
WALLS
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
FLOORS • Climate Zones 1 and 3 insulation
– No requirements generally
– Only if a floor heating or floor cooling system installed
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
• Same calculations as Housing
• Fewer combinations than Housing e.g. floor type
• Only need to calculate the glazing for each “unique” apartment
• Glazing calculators available(Excel 2003 & 2007)
GLAZING
√
√√
√√
√
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
GLAZINGEXAMPLE – WITH WORST CASE TINTING & 200 mm PROJECTION
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
BUILDING SEALING
• The same as Housing
• Plus a self-closing door, airlock, revolving door or the like at the main entrance leading to a conditioned space– Exemptions include:
• a conditioned space with afloor area of not more than 50 m2 OR
• a café, restaurant, open front shop or the like with a 3 m deep un-conditioned zone and door closers elsewhere
Conditioned space > 50m2
Conditioned space > 50m2
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
AIR MOVEMENT
• The same as Housing
– Air movement
– Ventilation openings (for low rise)
– Ceiling fans & evaporative coolers
Plus
• May reduce opening area progressively up the building
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
AIR-CONDITIONING & VENTILATION
• All air-conditioning and ventilating systems: – Shut-down controls– Outdoor air economy cycle (large units in climate
zone 3)– Closing of system dampers on shut-down– Insulate ductwork, heating & chilling pipework– Limit re-heat (not in a SOU)– Limit the amount of outside air to no more than
50% above the BCA Section F requires
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
AIR-CONDITIONING & VENTILATION
– A maximum fan & pump power allowance
– Time clocks (not for systems of individual apartments)
– Variable speed chilled water & hot water pumps
– Minimum efficiency of:• Central boilers• Refrigerant chillers• Heat rejection plant• Large package air-conditioning units
• All air-conditioning and ventilating systems:
Note: Most requirements do not apply to small package units serving individual apartments
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ARTIFICIAL LIGHTING & POWER
• Only in common areas of an apartment building (e.g. foyer, corridors, lounge areas, gym etc):
• Internal provisions include:
– Individual light switches
– A maximum lamp power allowance
– Common area bathrooms etc – high efficiency lamps
– Internal display lighting separate switching & time clocked
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ARTIFICIAL LIGHTING & POWER
• External lighting provisions include:
– If for movement:
• Be control by daylight sensor or time clock
AND
• Be efficient or motion detector controlled
– If for decorative purposes, be separately time switched
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
HOT WATER SUPPLY• Same as for Housing
ACCESS FOR MAINTENANCE• Does not apply
www.nt.gov.auDEPARTMENT OF LANDS AND PLANNING
ALTERNATIVE SOLUTIONS• So far we have covered the BCA Deemed-to-
Satisfy Provisions. They are one way to comply.• Alternative ways to comply are:
– A NatHERS rating:• Each residence - 3 stars minimum• All residences - 3.5 stars average
• Note that the servicesprovisions still apply
Methods of achieving compliance
Building SolutionBuilding Solution
Performance RequirementsPerformance Requirements
Functional StatementFunctional Statement
ObjectiveObjective
Alternative SolutionAlternative SolutionDTS ProvisionsDTS Provisions
Guidance
Mandatory
Documentary EvidenceDocumentary Evidence
Verification Method Verification Method
Expert Judgement Expert Judgement
Comparative Analysis Comparative Analysis
Ass
essm
ent
Ass
essm
ent
met
ho
ds
met
ho
ds
DEPARTMENT OF LANDS AND PLANNING
www.nt.gov.au
END OF SESSION 2END OF SESSION 2
APARTMENTS, FLATS & APARTMENTS, FLATS & CARETAKER’S RESIDENCESCARETAKER’S RESIDENCES
ANY QUESTIONS?ANY QUESTIONS?www.nt.gov/lands/building