Enea Detectors Range
Introducing new devices
ENEAis a range of analog addressable detectors and ancillaries for hi end applications
ED100 – SMOKE DETECTORED200 – HEAT DETECTORED300 – COMBINED SMOKE AND HEAT DETECTOR
Introducing new devices
Designed and manufactured at Inim electronics, it is a 100% italian product
Introducing new devices
Each device of the new ranges has been approved by LPCB which is one of the most prestigious notification body in fire detection
EN54-5 : Heat Detectors
EN54-7 : Smoke Detectors
EN54-17 : Short Circuit Isolator
EN54-18 : Input/Output devices
KEY FEATURES
Optical Smoke detectors are based on th eprinciple of the light scattering, to avoid false alarm it is important to avoid contaminations in the analysis chamber
Introducing new devices
Top side completely sealed to avoid dust or water condensation to reach the chamber
One of the most common false alarm or fault reason is the dust coming from the pipes or condensating water dropping from the top side
Introducing new devices
Metal mash agains insect wit less than 500um holes diameter
One of the biggest problems of optical smoke detectors is dust or insect entering in the chamber
Introducing new devices
Electronic circuit completely WAX coated to avoid any contamination
Moisture or environmental pollution may affect the behaviour of hi sensitive electronics circuits in the detector
Introducing new devices
Sensitive part of the circuit completely shielded by a metal cage
Electromagnetic noise may affect the measurement of the hi gain amplifier generating false alarms
Introducing new devices
Last generation CPU inside each detector whith hi false alarm rejection algorithm
The measurement of the smoke chamber and thermal probe are evaluated by the internal CPU and by means of the algorithm designed from the Inim R&D department an hi rejection to false alarm is achieved
Introducing new devices
Smoke chamber easy to open for clean up operations
In case of detector’s chamber contamination detector can be easily opened and cleaned with some air or a soft brush
Introducing new devices
Each Detector is Full tested with automatic test equipment which measure each single component and verify each electrical connection
Introducing new devices
Each Detector is Calibrated with a two stage process : one in free air and another one in a smoke tunnel to ensure the same response from each sample
Introducing new devices
Each Detector is subjected to a «Burn IN test» of 24 hours: the 80% of electronic components failure occur during the first 24 hours of theyr life, detectors live theyr first 24 hours in our burn in test!
Introducing new devices
Universal mounting base for every detector model
Clip for line continuity restore in case of detector removal
Introducing new devices
Relay base available direct driving of any type of external device
Introducing new devices
Each device is identifyed by a serial number
The serial number is reported on the back label and on two small detachable labels : this allow to stick a serial number to map and a serial number to mounting base
Introducing new devices
Thanks to LOOPMAP technology, which is the ultimate technology in loop addressing and fault finding, no any address operation is required
Introducing new devices
After the loop has been wired up, by using the panel and its configuration software or using the EDRV1000 driver with the included FireGenius software…
Introducing new devices
The loop wiring is automatically detected and a graphic report (including any T junction etc) is available:
Introducing new devices
Diagnostic features using Smartleague configuration software:
Introducing new devices
Contamination analysis using Smartleague configuration software:
Introducing new devices
The interactive graph show where there is a short circuit (each device include a short circuit isolator)
If some divice is not responding
Allow to Manually activate the 3 colour leds, the outputs etc. in order to test the loop
Right button mouse click
Introducing new devices
For each detector Smoke and heat sensitivity can be adjusted and are available early warning threshold for Smoke and heat level