End circuit terminaon of HTSX, KSX, KSR, USX self-regulang, HPT power-liming, and FP constant wa heang cables. ET-8C End Terminaon Kit INSTALLATION PROCEDURES

Transcript of End Termination Kit INSTALLATION PROCEDURES · 2020-06-30 · The ET-8C Kit is used for end circuit...

Page 1: End Termination Kit INSTALLATION PROCEDURES · 2020-06-30 · The ET-8C Kit is used for end circuit termination of HTSX, KSX, KSR, USX self-regulating, HPT power-limiting, and FP

End circuit termination of HTSX, KSX, KSR, USX self-regulating, HPT power-limiting, and FP constant watt heating cables.

ET-8C End Termination Kit

INSTALLATION PROCEDURES

Page 2: End Termination Kit INSTALLATION PROCEDURES · 2020-06-30 · The ET-8C Kit is used for end circuit termination of HTSX, KSX, KSR, USX self-regulating, HPT power-limiting, and FP

2

Tools Required

The ET-8C Kit is used for end circuit termination of HTSX, KSX, KSR, USX self-regulating, HPT power-limiting, and FP constant watt heating cables.

Receiving, Storing and Handling 1. Inspect materials for damage incurred during shipping.2. Report damages to the carrier for settlement.3. Identify parts against the packing list to ensure the proper

type and quantity has been received.4. Store in a dry location.

Warnings

• Due to the risk of electrical shock, arcing and fire caused by product damage or improper usage, installation or maintenance, a ground-fault protection device is required.

• Installation must comply with Thermon requirements (including form PN 50207U for Ex systems) and be installed in accordance with the NEC, CEC, or any other applicable national and local codes.

• Component approvals and performance ratings are based on the use of Thermon specified parts only.

• Keep ends of heating cable and kit components dry before and during installation.

Item Quantity Description

1 1 End Cap

2 2 Tape Strips

3 1 RTV Tube

A4. Fill the end cap with RTV sealant and apply a circumferential bead to cable [minimum of 3 mm (0.12”) wide]. Slide end cap onto end of cable.

A1. Cut off end of cable. A2. Cut and remove overjacket. A3. Trim away exposed braid from cable.

Kit Contents

Certifications/Approvals See heating cable installation procedures for additional Certification/Approvals information.

1 2

3

Installation Instructions for HTSX, KSX, KSR, USX

ET-8C End Termination KitINSTALLATION PROCEDURES

Page 3: End Termination Kit INSTALLATION PROCEDURES · 2020-06-30 · The ET-8C Kit is used for end circuit termination of HTSX, KSX, KSR, USX self-regulating, HPT power-limiting, and FP

3

INSTALLATION PROCEDURES

B10. Apply RTV sealant to cable to cover distance of at least 3mm and slide boot onto the end of the cable.

B1. Cut the cable 3” from the bus connection. B2. Cut and remove overjacket. B3. Trim away exposed braid from cable.

B4. Cut and remove primary insulation jacket. B5. Cut and remove fiberglass braid. Omit this step for FP cable.

B6. Cut and remove heating element and fiberglass overlay (FP cable only). Push any remaining heating element wire under the primary insulation jacket.

B7. Cut and remove pairing jacket. Do not cut bus wire insulation.

B8. Stagger cut one of the bus wires. B9. Tape bus wires individually and then together. Continue taping to cover overjacket.

Installation Instructions for HPT-OJ, FP-OJ

Page 4: End Termination Kit INSTALLATION PROCEDURES · 2020-06-30 · The ET-8C Kit is used for end circuit termination of HTSX, KSX, KSR, USX self-regulating, HPT power-limiting, and FP

Thermon • 100 Thermon Dr • PO Box 609 San Marcos, TX 78667-0609 • Phone: 512-396-5801 • 1-800-820-4328 For the Thermon office nearest you visit us at . . . www.thermon.com

© Thermon, Inc. • Printed in U.S.A. • Information subject to change.Form No. PN50072 -0320

Cable Take-off for HTSX, KSX, KSR, and USX Cable Take-off for HPT-OJ and FP-OJ