Enabling High Enabling High Efficiency Power Efficiency Power Supplies for Supplies for Servers : Servers : Update on industry, government and Update on industry, government and utility initiativesutility initiatives
Brian GriffithBrian GriffithSystem Power Architect System Power Architect
Intel CorporationIntel Corporation
Chris CalwellChris CalwellPolicy & Research DirectorPolicy & Research Director
Ecos ConsultingEcos Consulting
2*Third party marks and brands are the property of their respective owners
AgendaAgenda
Importance of power supply efficiencyImportance of power supply efficiency Server System Infrastructure (SSI) power Server System Infrastructure (SSI) power
supply efficiency requirementssupply efficiency requirements Government & market programs to Government & market programs to
improve power supply efficiencyimprove power supply efficiency
3*Third party marks and brands are the property of their respective owners
Why Is It Important to Reduce Why Is It Important to Reduce Computer Energy Use?Computer Energy Use?
IT equipment consumes $8 billion of IT equipment consumes $8 billion of electricity every year (100 billion kWh)electricity every year (100 billion kWh)
Computer electricity use is growing over Computer electricity use is growing over twice as fast (3.2%/yr) as total electricity twice as fast (3.2%/yr) as total electricity use (1.4%/yr)use (1.4%/yr)
Reducing power saves money, reduces Reducing power saves money, reduces heat and noise, and improves reliabilityheat and noise, and improves reliability
4*Third party marks and brands are the property of their respective owners
Power Supply, 129 W
Distribution, 9 WUPS, 49 W
1U System, 300 W
Cooling, 486 W
Data Center Power ChallengeData Center Power Challenge
EffectEffect Partially populated racksPartially populated racks Increasing energy billsIncreasing energy bills
CauseCause Poor power delivery Poor power delivery
efficiencyefficiency Poor cooling efficiencyPoor cooling efficiency Increasing component Increasing component
power consumptionpower consumption
Focus of presentation
Power Consumed by a typical 1U System
Total AC power consumed by a 300W DC system = 973W
Note: See PTMS010; Optimizing Data Centers with Intel’s Platform Power Tools, for more details
5*Third party marks and brands are the property of their respective owners
Power Supply Efficiency Power Supply Efficiency MeasurementsMeasurements
Suppliers close to 80 plus and recommended SSI levels
6*Third party marks and brands are the property of their respective owners
Power Supply Efficiency Power Supply Efficiency MeasurementsMeasurements
Rack efficiency higher to help data centers
7*Third party marks and brands are the property of their respective owners
Power Supply Efficiency
40.0%
45.0%
50.0%
55.0%
60.0%
65.0%
70.0%
75.0%
80.0%
85.0%
90.0%
0.0% 20.0% 40.0% 60.0% 80.0% 100.0%
% Output Loading
PS
U E
ffic
ien
cy
Importance of proper power supplyImportance of proper power supplySystem Input Power
W
50 W
100 W
150 W
200 W
250 W
300 W
350 W
400 W
450 W
0.0% 20.0% 40.0% 60.0% 80.0% 100.0%
% Output Loading
Inp
ut
Po
wer
(W
)
Proper power supply sizing has a significant impact on system power consumption
Efficiency varies 55% to 84% depending upon loading condition and Efficiency varies 55% to 84% depending upon loading condition and capabilities capabilities
Input power reduces by 15% - 24%Input power reduces by 15% - 24% N+1 redundant power supplies run lighter loads & lower efficiencyN+1 redundant power supplies run lighter loads & lower efficiency
8*Third party marks and brands are the property of their respective owners
Full Rack Wattage
12.7
15.2
11.8
15.0
18.0
14.0
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
2005 2006 2007
Kil
ow
atts
/ R
ack
83% Efficiency
70% efficiency
Importance of Power Supply Importance of Power Supply EfficiencyEfficiency How much power per rack?How much power per rack?
Typical low cost PSU = 70%High efficient PSU = 83%Typical usage = 50% of max
rack max wattage range
2.2 kW - 2.8 kW / Rack savings
9*Third party marks and brands are the property of their respective owners
Full Rack Energy Cost
$9,200
$11,000
$8,600
$7,200
$9,300
$7,800
$0
$2,000
$4,000
$6,000
$8,000
$10,000
$12,000
2005 2006 2007
$ /
Yea
r /
Rac
k
83% Efficiency
70% efficiency
Importance of Power Supply Importance of Power Supply EfficiencyEfficiencyHow much is paid for energy?How much is paid for energy?
Energy cost = $0.07 / KWhFull 42U Rack
Typical low cost PSU = 70%High efficient PSU = 83%Typical usage = 50% of max
Note:Does not include HVAC or UPS energy losses for cooling and backup conversion. Multiply by ~2x for data center level energy cost.
$1,700 - $1,400 / rack energy bill savings
10*Third party marks and brands are the property of their respective owners
10KW Rack Utilization
35
27
3330
23
28
0
5
10
15
20
25
30
35
40
2005 2006 2007
Sys
tem
s /
Rac
k
83% Efficiency
70% efficiency
Importance of Power Supply Importance of Power Supply EfficiencyEfficiencyHow many systems can fit?How many systems can fit?
Typical low cost PSU = 70%High efficient PSU = 83%Typical usage = 50% of max
4-5 more systems per rack
11*Third party marks and brands are the property of their respective owners
The Business Case for Increasing The Business Case for Increasing Server PSU EfficiencyServer PSU Efficiency
$0.00$0.10$0.20$0.30$0.40$0.50$0.60
70% 75% 80% 85% 90% 95% 100%
PSU Efficiency (baseline 70%)
NP
V S
avi
ng
s ($
/PS
U R
ated
Wa
tt)
Power Supply Price Range
83% Efficiency ≈ $90 per power supply 83% Efficiency ≈ $90 per power supply savings annually on a 600W supplysavings annually on a 600W supply
Note: Assumes 50% PSU loading and includes data center losses (UPS, distribution, cooling)
12*Third party marks and brands are the property of their respective owners
Why is Efficiency Important to Why is Efficiency Important to Promote?Promote? Power supply efficiencyPower supply efficiency
–Most running at 65% to 75% efficiencyMost running at 65% to 75% efficiency–Technology for 90% efficiency exists todayTechnology for 90% efficiency exists today–Price impacts easily pay for themselvesPrice impacts easily pay for themselves
EffectsEffects– Improve data center rack utilizationImprove data center rack utilization–Lower energy bill per systemLower energy bill per system
Reducing power meets customer needs; Reducing power meets customer needs; cooler, lower TCO, more reliablecooler, lower TCO, more reliable
13*Third party marks and brands are the property of their respective owners
AgendaAgenda
Importance of power supply efficiencyImportance of power supply efficiency Server System Infrastructure (SSI) power Server System Infrastructure (SSI) power
supply efficiency requirementssupply efficiency requirements Government & market programs to Government & market programs to
improve power supply efficiencyimprove power supply efficiency
14*Third party marks and brands are the property of their respective owners
Server System InfrastructureServer System Infrastructure
SSI will be promoting high efficient & SSI will be promoting high efficient & power managed (PSMI) power suppliespower managed (PSMI) power supplies
Testing conditions align with ATX12VTesting conditions align with ATX12V Required and recommended levelsRequired and recommended levels
–20%, 50%, and 100% loading20%, 50%, and 100% loading
Visit the SSI booth #46 and PTMS007 Visit the SSI booth #46 and PTMS007 for more detailsfor more details
15*Third party marks and brands are the property of their respective owners
SSI Efficiency levels (proposed)SSI Efficiency levels (proposed)
LoadingLoading 20%20% 50%50% 100%100%
RequiredRequired 65%65% 72%72% 70%70%
RecommendedRecommended 75%75% 80%80% 77%77%
Rack efficiency at 20-50% loading critical to Rack efficiency at 20-50% loading critical to improve data center facility utilizationimprove data center facility utilization
LoadingLoading 20%20% 50%50% 100%100%
RequiredRequired 65%65% 72%72% 70%70%
RecommendedRecommended 78%78% 83%83% 80%80%
ATX & SSI pedestal (EPS12V, ERP12V) SSI Rack (EPS1U, ERP2U)
SSI Industry specifications introduced to SSI Industry specifications introduced to encourage more efficient power suppliesencourage more efficient power supplies
16*Third party marks and brands are the property of their respective owners
AgendaAgenda
Importance of power supply efficiencyImportance of power supply efficiency Server System Infrastructure (SSI) power Server System Infrastructure (SSI) power
supply efficiency requirementssupply efficiency requirements Government & market programs to Government & market programs to
improve power supply efficiencyimprove power supply efficiency
17*Third party marks and brands are the property of their respective owners
Desktop and Server Power Desktop and Server Power Supply DevelopmentsSupply Developments
CEC’s PIER program: CEC’s PIER program: –Test procedureTest procedure
–Efficiency measurementsEfficiency measurements
–www.efficientpowersupplies.orgwww.efficientpowersupplies.org
Server and UPS efficiency researchServer and UPS efficiency research–http://hightech.lbl.govhttp://hightech.lbl.gov
60 power supplies tested60 power supplies tested In-use power measurements conductedIn-use power measurements conducted
18*Third party marks and brands are the property of their respective owners
Comparing Server Power Supply Comparing Server Power Supply Efficiency SpecificationsEfficiency Specifications
PS Electricity PS Electricity Use Per YearUse Per Year
SpecificationSpecification 20% 20% LoadLoad
50% 50% LoadLoad
100% 100% LoadLoad
kWhkWh $$
Typical ServerTypical Server 61%61% 71%71% 72%72% 360360 $36$36
SSI RequiredSSI Required
(2005 proposed)(2005 proposed)65%65% 72%72% 70%70% 345345 $35$35
SSI RecommendedSSI Recommended
(2005 proposed)(2005 proposed)78%78% 83%83% 80%80% 181181 $18$18
80 Plus80 Plus 80%80% 80%80% 80%80% 140140 $14$14
Note: assumes loading in the 20% to 50% load range for 425 WNote: assumes loading in the 20% to 50% load range for 425 WEPS1U power supply.EPS1U power supply.
19*Third party marks and brands are the property of their respective owners
ENERGY STARENERGY STAR
ITS 2004: EPA announces changes to desktop ITS 2004: EPA announces changes to desktop spec in upcoming Tier 1 revisions:spec in upcoming Tier 1 revisions:– Revised “Sleep” and “Off” power levelsRevised “Sleep” and “Off” power levels– Likely addition of “Idle” mode power requirementLikely addition of “Idle” mode power requirement– Power supply efficiency requirementsPower supply efficiency requirements
February 2005: EPA publishes first draft of Tier February 2005: EPA publishes first draft of Tier 1 revisions1 revisions
““Computers” section on Computers” section on www.energystar.govwww.energystar.gov contains latest information on draft spec.contains latest information on draft spec.
20*Third party marks and brands are the property of their respective owners
Desktop and Server Power Desktop and Server Power Supply Developments TimelineSupply Developments Timeline
2004 2005 2006 2008
80 Plusrecruitment begins
ENERGY STAR spec takes effect
2007
ENERGY STARITS announcement
Expected 80 Plusprogram duration
ENERGY STAR spec revision ?
Grandfatheringperiod ?
First 80 Plusqualifying unitsannounced
21*Third party marks and brands are the property of their respective owners
80 Plus: the Opportunity80 Plus: the Opportunity
Manufacturers can get paid now to be Manufacturers can get paid now to be compliant with future ENERGY STAR levelscompliant with future ENERGY STAR levels
Create market differentiation and profit Create market differentiation and profit opportunities for innovators other than opportunities for innovators other than expanding power supply wattageexpanding power supply wattage
Escape from the “commodity trap” of the Escape from the “commodity trap” of the power supply businesspower supply business
Third party validation of efficiency & power Third party validation of efficiency & power factor to help market products in U.S. and factor to help market products in U.S. and internationallyinternationally
22*Third party marks and brands are the property of their respective owners
80 Plus Program Concept80 Plus Program Concept
Manufacturer buy-down program for efficient Manufacturer buy-down program for efficient power supplies in desktop PCs and desktop-power supplies in desktop PCs and desktop-derived serversderived servers
$5 per computer incentive for PCs, $10 for $5 per computer incentive for PCs, $10 for non-redundant servers (EPS12V and EPS1U)non-redundant servers (EPS12V and EPS1U)
$3 per computer for marketing support$3 per computer for marketing support
80 Plus power supply qualifications80 Plus power supply qualifications
–80% efficiency at 20%, 50% and 100% load80% efficiency at 20%, 50% and 100% load
–True PF greater than 0.9 at 100% loadTrue PF greater than 0.9 at 100% load
23*Third party marks and brands are the property of their respective owners
80 Plus Funding Support80 Plus Funding Support
24*Third party marks and brands are the property of their respective owners
80 Plus Qualifying Power 80 Plus Qualifying Power SuppliesSupplies First 80 Plus compliant PSFirst 80 Plus compliant PS
–Seasonic SS - 400HTSeasonic SS - 400HT
–400W, ATX12V, PFC400W, ATX12V, PFC
More qualifying desktop power supplies More qualifying desktop power supplies expected in March and Aprilexpected in March and April
No qualifying server units to dateNo qualifying server units to date Visit Visit 80Plus.org80Plus.org for more details. for more details.
25*Third party marks and brands are the property of their respective owners
80 Plus Benefits for 80 Plus Benefits for ManufacturersManufacturers Reduce heat and noiseReduce heat and noise Better rack and space utilizationBetter rack and space utilization Demonstrate industry leadershipDemonstrate industry leadership Reduce TCO for customerReduce TCO for customer Positive environmental publicityPositive environmental publicity Tap into utilities’ $1.5 billion/yr of energy Tap into utilities’ $1.5 billion/yr of energy
efficiency programs to promote productsefficiency programs to promote products
80 Plus and labeling programs help 80 Plus and labeling programs help manufacturers market more efficient computers manufacturers market more efficient computers
and overcome price premiumsand overcome price premiums
26*Third party marks and brands are the property of their respective owners
2003-Early 2004 2003-Early 2004 MeasurementsMeasurements
27*Third party marks and brands are the property of their respective owners
Industry and Utility Industry and Utility SpecificationsSpecifications
28*Third party marks and brands are the property of their respective owners
2004-2005 Measurements2004-2005 Measurements
29*Third party marks and brands are the property of their respective owners
SummarySummary
Reducing power meets customer needs; Reducing power meets customer needs; cooler, lower TCO, more reliablecooler, lower TCO, more reliable
SSI Industry specifications introduced to SSI Industry specifications introduced to encourage more efficient power suppliesencourage more efficient power supplies
80 Plus and labeling programs help 80 Plus and labeling programs help manufacturers market more efficient manufacturers market more efficient computerscomputers
Desktop experience so far illustrates Desktop experience so far illustrates what is possible with serverswhat is possible with servers