2008 Eaton Corporation. All rights reserved.
This is a photographic template yourphotograph should fit precisely within this rectangle.
Eaton Energy Management System(EMS) Upgrade Kit
Jonathan Rodriguez
Product Manager
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
2/20
22
Why do customers need this product?
41.7% of data centers will run out
of power capacity in 2009.
-Uptime Institute
Energy capacity management is a critical
business need, and Eatoncan provide you with
a premier solution.
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
3/20
33
EMS applications summary
Power distribution units (PDUs)
Remote power panels (RPPs)
Power distribution racks (PDRs) Wall-mount panel boards
Rack power modules (RPMs)
Eaton EMS Upgrade Kit for legacy/third-party equipment
Integrated power management for any existing infrastructure.
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
4/20
44
Importance of energy management
1. Is your rack power density continuously going up?
2. How often do you add/change breakers?
How do you achieve load balancing at the branch breaker level
in such an environment?
3. Can you identify trends in power consumption due to
applications, seasonality or period?
How do you ensure your breakers dont experience overload?
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
5/20
55
EMS
Metering parameters Input voltage: L-L
Output voltage: L-L & L-N
Phase output current
Neutral and ground
current
Total harmonic distortion
(THD)
kVA, kW
Frequency
Power factor/phase
Percent load/phase Branch level load
w/adjustable warning
and alarm levels
Alarms Over and under voltage
(input and output) High current (3 phases, N,
G) Phase rotation (Input &
Output)
Phase loss Voltage THD Current THD Over/under frequency Output overload (three
levels) Building alarms (four
programmable) Real time stamp on all
events
Connectivity Integrates with Power XpertEnterprise Monitoring Platform
Power Xpert Gateway Series 1000 card
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
6/20
66
Load profiling
Unique differentiating feature Localized load profiling data storage
On-board real-time clock on all time-stamped events
Monthly profiling
Min and max V, I, Hz, kW
Highest readings captured monthly over 24 months Long term load trends
Help power optimization and data center planning
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
7/207
7
EMS Upgrade Kit
Key features
Monitor energy usage in existing PDUs,RPPs or panel boards
Self contained packaging
Up to two 42-pole panels per unit No disconnection of branch circuits
required
Flexible mounting options
Remote communication
Clamp-on CTs
Set-up CD enables user configurablesettings
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
8/20
88
EMS Upgrade Kitwhats included? EMS control module and mounting bracket
Connection and wiring harnesses for one or two panelboards Power Xpert Gateway 1000 remote monitoring card
Voltage monitoring taps (also powers the control unit)
Split-core branch circuit CTs
Optional Ground and neutral CTs
Optional main input CTs
Optional subfeed monitoring CTs Optional conduit boxes
Optional LCD
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
9/20
99
EMS Upgrade Kitother features
75A or 100A clamp onCTs for BCMS
Every kit includes PowerXpert Gateway 1000Card standard
Terminal connections forfour building alarms (N.O.or N.C.)
Summary alarm contact
DB-9 serial service portto configure firmware(configuration toolincluded on CD)
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
10/20
1010
How does it work?
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
11/20
1111
Connection overview
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
12/20
1212
Main and branch circuit CTs
Split-core CTs can be
installed without
disconnecting the branch
circuit or panel main wiring
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
13/20
1313
Voltage and current sensors
Voltage taps can beadded to existingbranch circuitwiring, or wired into3-pole breaker in
panel
Split-core CTseasily clamp overbranch circuit wiring
All CTs can beadded withoutdisconnecting wiringto loads
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
14/20
1414
Power Xpert Gateway Series 1000
Feature overview
Real time power monitoring presented how you need it Standard on-board Web pages Integration with Power Xpert Software Interface with third party network or building management systems
Enables remote configuration of your EMS
Independent, redundant Ethernet ports support high-reliability systems
Supports Eatons Environmental Monitoring Probe
Customized e-mail messaging Event notification and periodic status updates
Easy integration into existing Ethernet infrastructure
Communication protocols supported: Web server Modbus TCP/IP SNMP, SMTP, NTP
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
15/20
1515
All parameters, including real-time values andalarm status, are readily available via a pull downmenu.
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
16/20
1616
View the 42-pole breakerpanel layout and associateddata via the pull downmenu.
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
17/20
1717
Managing the data and event logs is simple.View and save logs for power qualityanalysis, load management and trending.
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
18/20
1818
Easily configure breakers in panelsfrom a browser. Save and restore
panel configurations in multiple units.
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
19/20
1919
Quickly reference the Web site or supporting MIBdocumentation to facilitate integration into third-
party building management and networkmanagement systems.
-
8/3/2019 EMS UGK End User Presentation JW EDITS 10-15-08
20/20
2020
Best monitoring package!
The most complete monitoring package in the market today
Ability to monitor alarm parameters at all levels:
Main inputs/outputs, subfeeds, panel main and branch breakers
Load profiling as standard feature
Power management and capacity planning tool 24-month profile log Best-in-class communication capabilities
Integrate all of your power distribution equipment into one
EMSeven third party and legacy equipment!