Free Space of 500 kV Transmission Line
L H IC
D
9 m
15 m
15 m
30.5 m
Notes: L = Distance from pole tower/conductor pole vertical axis H = Horizontal distance caused by conductor swing I = Switching impulse free distance
17.0 m
Minimum Vertical Free Distance from Conductor (C)SNI 04.6918 – 2002
No Location of
Minimum free
distance
(m)
1. Open Field or open areaa 12.5
2. Area with certain condition
2.1 Building, bridgea 9.5
2.2 Plants, forest, plantation 9.5
2.3 Road/highway/railwaya 15.0
2.4 Public fielda 18.0
2.5 Other EHV/LV/MV transmission line, telecommunication network, antenna,
and cable carb
8.5
2.6 Highest point of boat pole at the position of high/highest tide at water wayb 8.5
NOTES:
a : Minimum vertical free distance measured from land surface or road/railway surface
b : Minimum vertical free distance measured until highest/nearest point
Minimum Horizontal Free Distance from Axis of Tower/PoleSNI 04.6918 – 2002
No Aerial network
Distance from tower/pole
vertical axis to conductor
Horizontal distance
caused by conductor
swing
Switching impulse free
distance
Total distance
Rounded distance
L(m)
H(m)
I(m)
L+H+I (m) (m)
1. 500 kV transmission - single circuit
12.00 6.16 3.10 21.26 22.00
2. 500 kV transmission -double circuit
7.30 6.16 3.10 16.56 17.00