Features> Fully compliant DALI, self-contained emergency lighting device (type 1)
> Intelligent, automatic self-test scheduling for non-DALI applications
> Integralstatus/identificationsounderwithuser-override
> Input for optional low-voltageemergencytestinitiationswitch
> Bi-colourred/greenstatusindicatorLEDwith500mm leads supplied as standard > User-selectable 1 or 3 hour autonomy
> Emergencyoutputpower(Typical):1.5W(2-cell),3W(3-cell), 4W(55V4-cell),3.5W(90V4-cell)and3W(200V4-cell)
> 3-poleswitchingprovidesfullisolationoflampconnectionsandmainsdriver’spowersupplyduringemergencyoperation(Compatiblewithmost driver types up to 2A)
> Constant-currentchargerwithreverse polarity and short- circuit protection
> Designed and manufactured in Great Britain
> Complieswith:EN60598-2-22,EN61347-1,EN61347-2-7,EN61347-2-13,EN62034,EN62386,EN55015,EN61000-3-2,EN61547
www.one-lux.com 1
Common Technical Data
InputSupplyVoltage 230V+/-10%
Supply Frequency 50/60Hz
OutputVoltageoftheRange 3-200Vdc
MaximumTCPoint 70°C
AmbientTemperatureRange 0°C-50°C
BatteryChargeTime 24Hours
EarthLeakageCurrent <0.5mA
IPRating IP20
Weight 90g
Model NumberLED Voltage
RangeNumber of
Battery Cells
OL12/2/M3/DST 3-12V 2
OL55/3/M3/DST 9-55V 3
OL55/4/M3/DST 9-55V 4
OL90/4/M3/DST 55-90V 4
OL200/4/M3/DST 90-200V 4
OL12andOL55productsareSELVcompliant.Allversionssuppliedinstandardpackquantitiesof50weighing5.0Kg
AccessoriesSeepages5to7forourrangeofbatteriesandbatteryaccessories.
Productspecificationsmaybesubjecttochangewithoutpriornotice.
Issue_7aJune2020
Product descriptionOmni-LEDDSTTMisarangeofDALISelf-Testemergencylightingconversionmoduleshousedinacompactlow-profileenclosure,andsuitableforusewithmaintained,self-containedLEDluminaires.Theirconstant-powerdrivertechnologyhasaSELVisolatedoutputandavailableinarangefrom3Vto200VDC.TheywillrunalmostanyLEDlamporarray(includingsomeGU10andLineartubes),so making it easy to produce a self-testing and addressable, emergencyversionofyourexistingLEDluminairewithouttheneedfor separate ‘emergency’ LEDs or connectors. Theyareavailablein2,3and4cellversionsforusewithNiCdorNiMHbatteries.
EMERGENCY | ONE-LEDTM OMNI-LED DSTTM | LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST
184mm (l)
37mm (w)
169mm (Fixing centres)
21.5mm (h)13mm
www.one-lux.com 2
Model NumberInput Characteristics - Charging Mode
Duration selection CircuitWatts* InputCurrent InrushCurrent PowerFactor
OL12/2/M3/DST1Hour 2.8W 0.03A 5Apk 0.45
3Hour 3W 0.03A 5Apk 0.45
OL55/3/M3/DST1Hour 2.8W 0.03A 5Apk 0.44
3Hour 4.2W 0.04A 5Apk 0.47
OL55/4/M3/DST,OL90/4/M3/DST,OL200/4/M3/DST
1Hour 3.4W 0.04A 5Apk 0.45
3Hour 4.8W 0.05A 5Apk 0.45
TECHNICAL INFORMATION
*ThisfiguremaybeusedforLENI‘ParasiticPower’calculations.
Model Number
Battery & Emergency Output Characteristics
Autonomy Setting
Battery Type
NumberofBatteryCells
Battery Capacity
BatteryVoltsRange(ChargeMode)
BatteryChargeCurrent
BatteryVoltsRange(Discharge Mode)
BatteryDischargeCurrentNominal/Range
DDPVoltage
LEDVoltageRange
MaxOutput Power**
Uout Max (openCircuit)
OL12/2/M3/DST1 hour
NiCd/NiMH
2 1.6Ah 1.5-4V 75-95mA 2-2.8V 1.05A/(0.8-1.2A) 1.8V(min) 3-12V 2W 50V
3 hours 2 4Ah 1.5-4V 140-260mA 2-2.8V 1.05A/(0.8-1.2A) 1.8V(min) 3-12V 2W 50V
OL55/3/M3/DST1 hour 3 1.6Ah 1.5-6V 75-95mA 3-4.2V 1.05A/(0.8-1.2A) 2.5V(min) 9-55V 3.4W 80V
3 hours 3 4Ah 1.5-6V 140-260mA 3-4.2V 1.05A/(0.8-1.2A) 2.5V(min) 9-55V 3.4W 80V
OL55/4/M3/DST1 hour 4 1.6Ah 1.5-8V 75-95mA 4-5.6V 1.05A/(0.8-1.2A) 3.5V(min) 9-55V 4.5W 80V
3 hours 4 4Ah 1.5-8V 140-260mA 4-5.6V 1.05A/(0.8-1.2A) 3.5V(min) 9-55V 4.5W 80V
OL90/4/M3/DST1 hour 4 1.6Ah 1.5-8V 75-95mA 4-5.6V 1.05A/(0.8-1.2A) 3.5V(min) 55-90V 4W 100V
3 hours 4 4Ah 1.5-8V 140-260mA 4-5.6V 1.05A/(0.8-1.2A) 3.5V(min) 55-90V 4W 100V
OL200/4/M3/DST1 hour 4 1.6Ah 1.5-8V 75-95mA 4-5.6V 1.05A/(0.8-1.2A) 3.5V(min) 90-200V 4W 220V
3 hours 4 4Ah 1.5-8V 140-260mA 4-5.6V 1.05A/(0.8-1.2A) 3.5V(min) 90-200V 4W 220V
EMERGENCY | ONE-LEDTM OMNI-LED DSTTM | LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST
**Seegraphsonpages3and4foroutputcharacteristics.
www.one-lux.com 3
TECHNICAL INFORMATION
LED lamp output - Shaded area indicates typical forward voltage (Vf ) vs forward current (If ) expected throughout discharge duration.
4W - OL55/4/DST
0
100
200
300
400
500
600
3 6 8 11 14
LED
cur
rent
[mA
]
LED voltage [V]
1.5W - OL12/2/DST3W - OL55/3/DST
050
100150200250300350400450500550600
9 11 14 17 19 22 25 27 30 33 35 38 41 43 46 48 51 54
LED
curr
ent [
mA]
LED voltage [V]
050
100150200250300350400450500550600
9 11 14 17 19 22 25 27 30 33 35 38 41 43 46 48 51 54
LED
curr
ent [
mA]
LED voltage [V]
EMERGENCY | ONE-LEDTM OMNI-LED DSTTM | LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST
www.one-lux.com 4
TECHNICAL INFORMATION
EMERGENCY | ONE-LEDTM OMNI-LED DSTTM | LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST
LED lamp output - Shaded area indicates typical forward voltage (Vf ) vs forward current (If ) expected throughout discharge duration.
30
40
50
60
70
80
55 60 65 70 75 79.5 84.7 89.8
LED
curre
nt [m
A]
LED voltage [V]
3.5W - OL90/4/DST
0
10
20
30
40
50
60
70
80
90 101.3 109.2 117 124.8 132.6 140.4 148.1 155.9 163.7 171.4 179.1 186.8 200
LED
curre
nt [m
A]
LED voltage [V]
3.0W - OL200/4/DST
www.one-lux.com 5
Model Number
NiCd Batteries NiMH Batteries
Duration selection NCD24SS NCD24BS NCD34SS NCD34BS NCD44SS NCD44BS NCD216SS NCD316SS NCD416SS NMH24SS NMH34SS NMH44SS
ApplicableEndCaps(2 required per battery)
E - E - E - E/SubC E/SubC E/SubC E/18700 E/18700 E/18700
OL12/2/M3/DST
1Hour 4
3Hour 4 4 4
OL55/3/M3/DST
1Hour 4
3Hour 4 4 4
OL55/4/M3/DST,OL90/4/M3/DST,OL200/4/M3/DST
1Hour 4
3Hour 4 4 4
BATTERY AND END CAP ACCESSORY ASSIGNMENT
Applicable Battery Packs and End Caps to OMNI-LEDTM models
EMERGENCY | ONE-LEDTM OMNI-LED DSTTM | LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST
Product description> Endcapssuitableforusewith‘stick’Dsizebatteries> Endcapsuitableforusewith‘stick’SubCbatteries> Endcapsuitableforusewith‘stick’18700NickelMetalHydridebatteries
Properties> Providesaconvenientandsecuremountingoptionforcylindricalbatteries> MouldedinUL94-V0ratedplastic> ‘E’versionoffersslidetogetherfeaturetoproducesecureside-bysideconfiguration> Linkwiresavailableseparately> Slotted for tag connection or outlet for pre-soldered connections
BATTERY END CAPS NiCd Batteries - Ordering Information
ProductCode E E/Slotted E/18700 E/SubC
FixingCenterswhenfitted
Battery Length (L) +20mm
Battery Length (L) +17mm
Battery Length (L) +16mm
Battery Length (L) +19mm
Maximum Lengthwhen
fitted
Battery Length (L) +37mm
Battery Length (L) +34mm
Battery Length (L) +23mm
Battery Length (L) +40mm
www.one-lux.com 6
ACCESSORIES | NICKEL CADMIUM (NiCd) BATTERIES
Product description> HightemperatureNickelCadmiumbatteries
for Emergency Lighting use > SuitableforusewithallOne-LUXproducts> 1-yearwarranty
Properties> Ratedforcontinuousoperationat55°Cand
meets the 4 year design life as per Annex A of EN60598-2-22
> ComplieswithIEC61951-1> Suppliedwithsuitableconnectors> Availableincustomconfigurations> 4Ah‘D’sizecells> Other capacities available> Refertobatterydatasheetforfurther
information
Common Technical Data
AbsoluteMaximumTemperature 70˚C
MaximumContinuousTemperature 55˚C
MinimumAmbientTemperature 5˚C
ChargeRequirements C/20for24hoursConstantCurrent(CC)
Storage 0-25˚Cfor12months
Disposal at registered treatment facility only
Table of Dimensions
Dimensions NCD24SS NCD24BS NCD34SS NCD34BS NCD44SS NCD44BS NCD216SS NCD316SS NCD416SS
Length (L) 116mm 68mm 175mm 102mm 234mm 136mm 86mm 131mm 175mm
Width(W) 34mm 63mm 34mm 63mm 34mm 63mm 23mm 23mm 23mm
Height(H) 34mm 36mm 34mm 36mm 34mm 36mm 23mm 23mm 23mm
Fixing (l) n/a 32mm 64mm
Fixing(w) 40mm 40mm 40mm
IECCellSize ‘D’ ‘Sub-C’(SC/Cs)
NiCd Cable Assemblies Connector Type Wire Length Connector Dimensions
CAS031requiredwithpacks(BS)(Sold separately)
MiniJSTplugtoAmp ‘mate-n-lok’ (male)
250mm N/A N/A
CAS020requiredwithsticks(SS) (Sold separately)
MiniJSTplugtoRed&Blackwireswithsockets
500mm 4.8mmx0.8mm 6.3mmx0.8mm
CAS012-linkwire (Sold separately)
Whitewire (female/female) 100mm 6.3mmx0.8mm(positive)
4.8mmx0.8mm(negative)
NiCd Batteries - Ordering Information
ProductCode NCD24SS NCD34SS NCD34BS NCD44SS NCD44BS NCD216SS NCD316SS NCD416SS
Box Quantity 40 30 30 20 22 140 60 60
Weight 11kg 12kg 13kg 10.8kg 12kg 14.5kg 10kg 12kg
Positive Negative
Length (L)
Height(H)
Length (L)
Fixing (l)
Fixing(w)
Height(H)
Width(W)
EMERGENCY | ONE-LEDTM OMNI-LED DSTTM | LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST
www.one-lux.com 7
ACCESSORIES | NICKEL METAL HYDRIDE (NiMH) BATTERIES
Product description> HightemperatureNickelMetalHydride
batteries for emergency lighting use > SuitableforusewithallOne-LUXproducts> 1-yearwarranty
Properties> Ratedforcontinuousoperationat50°Cand
meets the 4 year design life as per Annex A of EN60598-2-22
> ComplieswithIEC61951-2> Suppliedwithsuitableconnectors> Availableincustomconfigurations> 4Ah‘18700’sizecells> Other capacities available> Refertobatterydatasheetforfurther
information
Common Technical Data
AbsoluteMaximumTemperature 70˚C
MaximumContinuousTemperature 50˚C
MinimumAmbientTemperature 5˚C
ChargeRequirements C/20for24hoursConstantCurrent(CC)
Storage 0-25˚Cfor6months
Disposal at registered treatment facility only
Table of Dimensions
Dimensions NMH24SS NMH34SS NMH44SS
Length (L) 140.5mm 214.5mm 284mm
Diameter (D) 20mm 20mm 20mm
IECCellSize ‘18700’
NiMH Cable Assemblies Connector Type Wire Length Connector Dimensions
CAS024/JST-wireset (Sold separately)
MiniJSTplugtoRed&Blackwireswithspade&socket 700mm Red4mm(socket)
Black3.5mm(spade)
CAS070-linkwire(Sold separately) Blackwire(male/female) 300mm 3.5mm&4mm(spade&
socket)
NiMH Batteries - Ordering Information
ProductCode NMH24SS NMH34SS NMH44SS
Box Quantity 50 45 54
Weight 7kg 11kg 14.5kg
Length (L)
Diameter (D)
NickelMetalHydride(Ni-MH)
EMERGENCY | ONE-LEDTM OMNI-LED DSTTM | LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST
www.one-lux.com 8
DisclaimersOmni-LEDDSTTM module and its associated accessory products have been manufacturedanddesignedtocomplywiththerequirementsofEN60598-2-22in addition to the standards detailed on page 1 of this document. Operation beyondtheparametersspecifiedinthisdocumentandtheassociatedstandards may result in reduced performance and ultimate premature failure,withthewarrantymadevoid.ItistheusersresponsibilitytoensurefullcompatibilityoftheOmni-LEDDSTproductfortheintendedapplicationand for compliance of the emergency conversion to relevant Standards. Thespecifier/systemdesignershouldfollowtheluminairemanufacturer’sspecificationsandbeawareoftheenvironmenttowhichtheluminaireandthesecomponentsareusedandensurecompatibilityofOne-LUXproductswithothercomponentsinthelighting/DALIsystem.Installationshouldbeinlinewiththefollowingguides.PleasecontactourTechnicaldepartmentifyouare in any doubt.
Precautions Omni-LEDDSTTMmoduleshouldbeinstalledasperthefollowingguidelines,electric shock or damage to the product may result if incorrectly installed. Theluminaireshouldbeinstalledbyaqualifiedandcompetentelectrician.If the luminaire is to be mounted in an external location, consider the battery astemperaturesbelow0°Cmaybefrequentincoldmonths.Inthiscase,thedesignlifeof4yearswillbecompromisedandmorefrequentbatteryreplacementsmaybeneeded.Likewise,iftheluminaireissituatedinahotenvironmentwherethetemperatureismaintainedat25°Corabove,orsitednexttolargepanesofglassinwhichcaseitmaybeexposedtothermalmagnification.ItisrecommendedthatIP65luminairesareavoidedforuseininternalapplications as undue thermal stress may result.
Installation notesWirePreparation:maximumstriplength10mm(recommended6mm)Min/maxConductorsizes:0.5-1.5mm2.
BesteffortshouldbemadetokeeptheOmni-LEDDSTTM module and battery awayfromdirectsourcesofheat,i.e.mainsLEDdriversandLEDlamps.AvoidobstructingairflowaroundthesidesoftheOmni-LEDDSTTM module and other electronicproducts.Allowaclearanceof10mmormorewhereverpossible.
LampConnectionsshouldbekeptasshortaspossibleandundernocircumstances exceed 1m for self-contained luminaires. TheOmni-LEDDSTTMmoduleshouldbesecuredusingbothfixingpointsandtheuseofM4x6mmscrewsarerecommendedformostapplications.
Test Switch input (Optional accessory)TheOmni-LEDDSTTM module offers the facility for the user to perform a multiplefunctionswithaswitchconnectedtothe‘TESTSWITCH’input.Anon-latchingpush-to-makeswitchshouldbeusedasshowninthewiringdiagramsonPage11.Seebelowfordetailsofuse.
EMCconsiderations:Mainsinputconnectionsshouldbeasfarfromthelampleadsaspossibleandnoideallylessthan10cm.Mainsinputwiresshouldbeas short as possible and run direct from input terminations to the Omni-LED DSTTM product; they should not run alongside the case.
OtherEMCtips:> Keepthelampwiresraisedoffanyearthedmetalwork> Twistmainsleadstogetherwhen‘looping’or‘throughwiring’Theswitchedandun-switchedlivesmaybejoinedtogetherforcontinuousoperation(un-switched)applications.TheOmni-LEDDSTTMmoduleprovidesSELVreinforcedinsulationbetweenthe mains supply and battery charging circuit and employs self-resetting
INSTALLATION
EMERGENCY | ONE-LEDTM OMNI-LED DSTTM | LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST
protectionagainstshort-circuitofbatteryterminals.Normalchargingwillresumeautomaticallyonceafaultisremoved.Themainssupplyshouldalwaysbedisconnectedwhenservicingtheluminaire.
Ifotherdevicesareconnectedtotheun-switchedsupply,pleasebeawarethattomaintaincompliancewithEN60598-2-22thatineventofitsfailureitwillnotaffectotherdevicesonthesamecircuit.Inthiscasewerecommendtheuseofseparate fused terminal blocks to each device.
InternalfusesusedwithinOmni-LEDDSTTM module product are not user serviceable.
CAUTION! Ensure the jumper setting located in the product lid is configured correctly for the intended application and the associated battery is of the correct capacity. See battery selection guide on page 5.
Autonomy Selection Information
Emergency Duration Required Jumper Setting
3Hours(DefaultSetting)
1Hour
Test Switch Information
Function Test Switch Action
Disable Sounder Pressandholdforlongerthan5seconds(Sounderbleepsonceforconfirmation)
Enable Sounder Pressandholdforlongerthan5seconds(Sounderbleepstwiceforconfirmation)
StartaFunctionTest* Pressandrelease2timeswithin5seconds
Confirmphysicalselection Pressonceduringphysicalselectionmodeinitiated by DALI system
StopIdentification Pressonceduringidentificationmodeto exit.
EMERGENCY | ONE-LEDTM OMNI-LED DSTTM | LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST
www.one-lux.com 9
INSTALLATION & OPERATION
Automatic TestingIfStandaloneSelf-Testmodeisdetected,themodulewillestablishrandomised delay times to ensure the next scheduled tests do not coincide withthesametestofadjacentluminaires.(Seetablebelowfordetailsof‘TestDelayTime’ranges).Subsequentroutinetestingwillthentakeplaceaccordingtothe‘TestInterval’timesdetailedinthetablebelow.Whenascheduledtestisdue,theOmni-LEDDSTTMmodulewillcheckstatusofthe‘ControlSwitchLiveLin’totryanddetermineifthelampisalreadyinuseandavoiddisruptiontotheuserforupto36hourswhereverpossible.
IftheOmni-LEDDSTTMmodulehasdetecteditisinstalledonaDALInetwork,itwillconfigureitselfaccordingtothedefaultDALIspecification. (See table below).It is important to note that in DALI mode, randomisation will not be set and it will await test delay times to be configured by the DALI master.
IntheeventoflossofcommunicationwiththeDALImaster,automatictestingwillrevertbacktotheSelf-Test‘TestIntervals’,but‘TestDelayTimes’willremainasconfiguredbytheDALImaster.
Automatic Testing Information
Test Type Mode Duration Test Delay time Test Interval / Occurrence Notes
CommissioningTestSelf-Test 1or3Hours* 24Hours Once* ThemodulewillcarryoutaDurationTest24hoursafterinitialpowerup.*Thistestcyclewillberepeatedifun-successfull
DALI 1or3Hours* N/A N/A Caution!AninitialDurationTestmustbeinitiatedbytheDALIMastertocommissionanewinstallation.
FunctionTestSelf-Test 20Seconds 1-15Days Every28Days -
DALI 20Seconds 0 Every7Days Caution!FactorydefaultofzerotestdelaytimeissetforDALIMode
DurationTestSelf-Test 1or3Hours* 1-51Weeks Every51Weeks Themodulechecksifthelampisinusebeforeinitiatingatesttoavoiddisruption.Maximumtestdelayis36hours
DALI 1or3Hours* 0 Every52Weeks Caution!FactorydefaultofzerotestdelaytimeissetforDALIMode
Commissioning:Oncetheluminairehasbeeninstalledandavailabilityoftheun-switchedsupply is deemed stable, connect the battery, then apply mains power. Afterapplyingpower,theOmni-LEDDSTTMwilldetermineifthereisaDALIbuspresentandornot.Withnobuspresent,theindicatorLEDwillflashredthengreenandthemodulewillautomaticallycarryoutaninitial24hourchargeandathenafullDurationTest.Oncethiscommissioningtestiscomplete,afurther24hourswillbeneededtorechargethebatterybeforenormal use. If a DALI bus ispresent,themodulewillbeginstandby/chargemodeandawaitfurtherinstructionfromtheDALImaster.Thedurationofstand-aloneselftests,andcapabilityoftheproductrecognisedbyaDALImasterwillbedeterminedbytheconfigurationlink,whichisaccessiblethroughtheenclosurelid.(Seepage8fordetails).Caution should be taken to ensure the battery charge current compatibility before adjusting configuration. Ifitisanticipatedthattheun-switchedsupplymaybeinterruptedbeforenormaluse,weadvisethatthebatteryisleftdisconnectedandcommissioning is delayed until the supply is stable. If mains is not applied afterconnectingthebattery,theunitwillcontinuetodrawaminimalamountofpowerfromthebatterywhilstinstandbymode.Continued use in this state in excess of several months can cause permanent damage to some batteries. It may be necessary to repeat the initial charge/discharge process several times to re-condition the battery and achieve full rated emergency duration. Thiscanbeinitiatedbycyclingtheunswitchedmainssupplyoffandon,oractivatingthetestswitchtwicewithin5seconds.Aftersuccessfulcommissioning,thebatteryshouldbemarkedwiththedateofcommission.
AnOmni-LEDDSTTM module can be returned to standalone self test at any timebydisconnectingitfromtheDALInetworkandforcingaFunctionTestfromthetestswitchorbycyclingtheun-switchedmainssupply.(Seepage10fordetails).
Tofullyresetalltesttimes,disconnectthemains,batterypowerandDALIconnections.Oncepowerisrestored,thecommissioningcycleandrandomisationprocesswillbere-initiated.
ShortdischargeperiodseachmonthfortheFunctionTestwillnotadverselyaffectOne-LUXbatteriesandshouldbeconsideredasamaintenanceexerciseforthebattery.Regularfulldischargecycleswillhoweveradverselyaffect the design life of the battery, so excessive testing should be avoided whereverpossible.
Afullsummaryofautomatictesttimingscanbeseeninthetablebelow.
ThestatusoftheOmni-LEDDSTTM module can be determined at any time from the indicator LED. Details of the indicator LED status conditions and optionaltestswitchfunctionalitycanbefoundonpage10.
INSTALLATION & OPERATION Continued
EMERGENCY | ONE-LEDTM OMNI-LED DSTTM | LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST
www.one-lux.com 10
Module Status Information
LED Colour LED Status On Time (Seconds)
Off Time (Seconds)
Sounder Purpose Action required
Green
VerySlowFlash 10 0.5 - Normalstatuswithfullychargedbattery(Commissionedunit) None-Instandbymodeandoperatingasnormal
SlowFlash 1.5 0.5 - First24hourchargeandDurationTest.(Non-Commissionedunit) None-Awaitcommissioningprocesstocomplete
Fast Flash 0.5 0.5 - FunctionTestorDurationTestinprogress.(Commissionedunit) None-Awaitcurrenttesttocomplete
Varied On Off On Off Purpose Action required
Green Long‘On’thenflash 10 0.5 0.5 0.5 - Batterybeingcharged(CommissionedorDALIbuspresentunit) None-Awaitbatterytocharge(Normally24Hours)
Red&Green(alternate) Fast Flash 0.5 0.5 0.5 0.5 - PhysicalselectenabledbyDALIsystemonly ConfirmPhysicalselectwithoptionalTestSwitch
Module Status Information (Fault Conditions) *A function test can also be initiated at anytime whilst mains power is present by cycling the un-switched mains supply or test switch off-on, 2 times within 5 seconds.
LED Colour LED Status On Time (Seconds) Off Time (Seconds) Sounder Cause Suggested action required
Red
SlowFlash 0.5 1.5 Yes 1)Possibleinitialcommissioningdurationtestfailed:
2)Possiblebatteryconnectionfault:
3)Possibleopencircuitorshortcircuitbattery:
4)Possiblebatterycapacityfault:
1)Ifitisanewinstallation,youcandetermineiftheOmni-LEDDSTTM passed the initial commissioning durationtestbycyclingthemainspoweroffthenon,whilstobservingtheindicatorLED.
a)IftheindicatorLEDflashesredthengreenatpoweron,theOmni-LEDDSTTM module did not pass itsinitialcommissioningdurationtestandwasawaitingfurtherinstruction.Cyclingthepowerasperabovehasnowresettheprocessandanewtestwillbeattemptedin24hstime.(Aslongasthemainssupplyisnotinterrupted).Thisprocessmayneedtoberepeatedseveraltimestore-conditionnewbatteriestorestorefull capacity, especially if they have been in storage for some time.
b)Ifaftercyclingthemainspoweroffthenon,theredindicatorremains,theunithaspasseditscommissioningtest,butmayhavefailedaroutinefunctionordurationtestbecauseofthecausesbelow.
2)Whilstthemainssupplyremainson,checkthebatteryconnectionsandrepair/replacefaultypartsifnecessary. Initiate a function test to try and clear the fault indication. If the fault indication does not clear, proceed to 3).
3)Whilstthemainssupplyremainson,disconnectthebatteryandmeasureifitsvoltageisbetween0.8-1.6VDCpercell.Ifitsoutsidethisrange,thebatteryisfaultysoitshouldbereplaced.Ifanewoneisinstalled,cyclethemainspoweroffthenonbeforereconnectingtoinitiatethecommissioningprocess.Ifthevoltageiswithin the range, proceed to next step.
4)Totestthebatterycapacity,ensureithashad24hoursuninterruptedcharge,thenturnoffthemainspowerandobserveiftheratedemergencydurationisachieved.Ifitexceedstheratedduration,youcanreinstatepowerandinitiateafunctiontesttoclearthefaultindication.Iftherateddurationisnotachieved,anditwasacommissionedbatterybefore,replacethebatteryandturnthemainspowerontoinitiateanewcommissioningtest.(Seepage9).
Fast Flash 0.5 0.5 Yes 1)Possiblelampfault:
2)Possibleinternalcircuitfault:
1)Checkthelampandwiringforfaultsordamage.Repair/replaceasnecessary.Initiateafunctiontesttoseeifthe fault has cleared. If the fault does not clear, proceed to step 2) Caution, high voltages can be present at the lamp when the battery is connected even if the mains power is turned off!!
2)Ifrepairing/replacingthelamporwiringdoesnotclearthefault,theremaybeaproblemwiththeOmni-LEDDSTTM. Turnoffmainspower,replacethemoduleandreinstatepowertocommissionthenewmodule.
www.one-lux.com 11
INSTALLATION
EMERGENCY | ONE-LEDTM OMNI-LED DSTTM | LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST
+ -Battery
Non-Maintained
+
LED Module+
-
Test switch
Maintained
+ -Battery
+Test switch
Mains LED Driver -
+
L
N
Switched Live
E
Charge/ StatusIndicator
NeutralUnswitched Live
DALI-DADALI-DA
LED Module+
-
Charge/ StatusIndicator
NeutralUnswitched Live
DALI-DADALI-DA
Test switch
-
+
Mains LED Driver
L
NE
Mains LEDLamp
Emergency LEDLamp
LED Module+
-
LED Module+
-
+- Battery
+
Switched Live
NeutralUnswitched Live
DALI-DADALI-DA
Charge/ StatusIndicator