Em6438 6436 Dual Quick Start Guide

10
& EM 6436 Dual EM 6438 & EM 6436 Dual Meter Products List of Safety symbols used Caution - Risk of danger and documentation should be consulted wherever the symbol is used. Caution - Risk of electric shock which can cause severe injury or even death. User accessible area is protected throughout by DOUBLE INSULATION. Measurement Category III Direct and alternating currents www.conzerv.com ISO 14001:2004 Certified ISO 9001:2000 Certified

Transcript of Em6438 6436 Dual Quick Start Guide

& EM 6436 Dual

Products

EM 6438 & EM 6436 Dual Meter

List of Safety symbols usedCaution - Risk of danger and documentation should be consulted wherever the symbol is used. Caution - Risk of electric shock which can cause severe injury or even death. User accessible area is protected throughout by DOUBLE INSULATION. Measurement Category III Direct and alternating currentsISO 14001:2004 Certified ISO 9001:2000 Certified

www.conzerv.com

www.conzerv.com [email protected]

Use CT1

2 4

Use CT2 Use CT3

Use PT1 Use PT2 Use PT3

3 1

RS 485

Schneider Electric Conzerv

G.Sense

%A FS

EM6438

www.conzerv.com

5

Input current terminals A1, A3, A3

Input voltage terminals V1, V2, V3, VN Auxiliary supply (control power) terminals RS 485 comm terminals

- Measurement category III To Auto scroll within a page group Go to a particular page in the desired page group. Press key continuously for 3 seconds. The display will flash AUTO and start auto scroll within the page group To Auto scroll down the entire column of pages Go to the desired page. Press key continuously for 3 seconds. The display will flash AUTO and start auto scroll down the pages. To Auto scroll through TURBO pages: Press key continuously for 3 seconds. The display will flash AUTO and start auto scroll down the TURBO pages. - Double insulation at User accessible area

Protection against dust & Water

Front panel - IP 51 & Rear panel - IP 40

2 of 9

3.3Terminal connection using lugsTerminal connection using U lugsLug: Insulated sleeved U lug Cross-section: 2.5 mm2/14 AWG It is simple and easy to connect the terminals using U lugs. The following steps explains how to connect the terminals using U lugs.

1

2

0.25 to 1 N.m 1 N.m 1.2 N.m

3

3.2

Mechanical dimensions, Panel cut-out and Mounting Mechanical dimensions and panel cut-out1. Loosen the terminal screw. 2. Connect the wire with the U lug to the meter terminal. 3. Tighten the terminal screw.83.0 3.26 8.0 0.31

90.0 3.54

Terminal connection using ring lugs Lug: Ring lug Cross-section: 2.5 mm2/14 AWG96.0 3.78

The following steps explain how to connect the terminals using ring lugs.

1Mounting

2

3

1

24 5

3

1. Remove the mounting clamps from the meter. 2. Gently slide the meter through the cut-out. 3. Put the mounting clamps back in the meter and tighten the mounting clamps screws.

1. 2. 3. 4.

Remove the protective cover from the meter. Remove the terminal screw from the meter. Connect the wire with the ring lug to the meter terminal. Place the terminal screw back in the terminal and tighten the terminal screw. 5. Place the protective cover back and tighten the protective cover.

3 of 9

3.4WYE

Wiring Diagrams

3-Phase 3-Wire Open Delta connection (SYS - dltA)L1 L2 L3

Supported system typesSystem type Delta, Open Delta 2-phase 1-phase Meter configuration StAR/WyE dLtA 2 Ph 1 PhS2 S1 CT

LINE

PT if Vac LL 601 V

*

V1 V2 V3

0.25 A

Wiring diagram symbolsSymbol Description Current transformer (CT)CT S1

VNOther Meters

*FuseS2

44 to 300 Vac/dc Aux Supply (Control power)

LOAD

RS485

Communication

*Other Meters

(In Series)

3-Phase 4-Wire Star/Wye connection (SYS - Star/Wye)L1 L2 L3 N

2-Phase 3-Wire connection (SYS - 2 Ph)L1 L2 N

LINE

LINE

S1 CT

PT if Vac LL

601 VS1

PT if Vac LL 601 V CT 0.25 A

*S2 S1 CT

V1 V2

0.25 A

*S2 CT S1

V1 V2* Other Meters(In Series)

*S2 S1 CT

V3 VNOther MetersS2

*

V3 VNOther Meters

*S2

44 to 300 Vac/dc Aux Supply (Control power)

44 to 300 Vac/dc Aux Supply (Control power)

LOAD

RS485

LOADCommunication

RS485

Communication

* Other Meters

(In Series)

3-Phase 3-Wire Delta connection (SYS - dltA)L1 L2 L3

Single Phase connection (SYS - 1 Ph)L1 N

LINE

LINE

PT if Vac LL 601 V S1 CT

CT S1 0.25 A

*S2

V1 V2 V3

0.25 A

*S2

V1 V2 V3 VN

* Other Meters (In Series)

CT S1

VNOther Meters

Other Meters

*S2

44 to 300 Vac/dc Aux Supply (Control power)

44 to 300 Vac/dc Aux Supply (Control power)

LOAD

RS485(In Series)

Communication

LOAD

*Other Meters

RS485

Communication

4 of 9

NOTE:

indicates blinking / editable 1 means blinking 1

SET

VIEW CODE 2 000 CODE 1 000

RMS

EDIT

PASS

for more than 2 seconds.VIEW MODE VIEW A.PRI 100.0 VIEW A.SEC 5.000 VIEW V.PRI 415.0 VIEW V.SEC 415.0 VIEW SYS STAR VIEW LABL 123 VIEW VA.Fn 3D VIEW BAUD 9600 VIEW PRTY EVn1 VIEW ID 1.000 VIEW F.S% 100.0 VIEW OFLo Wh VIEW PAR Wh VIEW R1.R2 U G EDIT MODE EDIT A.PRI 100.0 EDIT A.SEC 5.000 EDIT V.PRI 415.0 EDIT V.SEC 415.0 EDIT SYS STAR EDIT LABL 123 EDIT VA.Fn 3D EDIT BAUD 9600 EDIT PRTY EVn1 EDIT ID 1.000 EDIT F.S% 100.0 EDIT OFLo Wh EDIT PAR Wh EDIT R1.R2 U GA.PRI= Current primary winding (CT)* Input range: 1 A to 99 kA (100.0) A.SEC= Current secondary winding (CT) (5.000)

V.PRI= Voltage primary winding (PT), line-line* Input range: 100 V to 999 kV (415.0) V.SEC= Voltage secondary winding (PT), line-line* Input range: 80 V to 600 V (415.0) SYS= Power system's configuration*: STAR , DELTA, 2phase, 1phase, WYE LABL= Phase labeling Choose from: 123, RYB, RST, PQR, ABC

SET

VIEW

VA.FN= VA function selection* Set the VA function to: 3D, ARTH

VIEW A.PRI 100.0

BAUD= Baud rate : 1200, 2400, 4800, 9600, 19200.

RMS

PRTY= Parity & Stop bit settings: EVN.1, EVN.2, ODD.1, ODD.2, no.1, no.2 ID = RS485 Device ID number: 001 to 247. (Evn.1 = Even.1 stop bit) F.S%= Full scale % Set the full scale between1 to 100: 100 O.F = Overflow parameter selection :Wh, Vah INTG clears when 9999 Run hours ( almost 13.88 months)

Parameter selection : Wh / Vah

R1.R2 = User-programmable dual source names (U G) Select any alpha-numeric from A-Y (except X) and 0-9

Default Setup values are give in BOLD *Changing these values while the device is in use, is not recommended.

5 of 9

A.PRI value from 100.0 to 220.0 EM 6438 & EM 6436 Dual.

SET

EDIT

PASS

SAVE y

EDIT A.PRI 220.0

EDIT A.PRI 220.0 EDIT A.PRI 210.0 EDIT A.PRI 200.0

FAIL EDIT A.PRI 220.00

SAVE n

NOTE:

indicates blinking / editable

E.g. y means blinking y

SET

VIEW EDIT A.PRI 100.0NOTE:

RMS

EDIT

EDIT A.PRI 200.0 EDIT A.PRI 100.0

indicates blinking / editable

E.g. 2 means blinking 2

4.3

6 of 9

through ConPAD or due to overflow) the energy values stored in the integrator will be transferred to OLD register

Clearing integrators is possible only through communication. eg: ConPAD.

[email protected]

7 of 9

- EM 6436 Dual

W1 = Watts, phase 1 W2 = Watts, phase 2 W3 = Watts, phase 3

2

- EM 6438

8 of 9

Warranty as per company warranty policy

Statement of Calibration Our instruments are inspected and tested in accordance with specifications published by an independent testing facility. The accuracy and calibration of our instruments are traceable to the National Institute of Standards and Technology through equipment that is calibrated at planned intervals by comparison to certified standards. Disclaimer The information presented in this publication has been carefully checked for reliability; however, no responsibility is assumed for inaccuracies. Schneider Electric Conzerv Strives for continuous product innovation. Product specifications are therefore subject to change without notice.

9 of 9