Em-II Manual Final
-
Upload
arunfriends -
Category
Documents
-
view
7.717 -
download
4
Transcript of Em-II Manual Final
ELECTRICAL MACHINES LAB - II
LABORATORY MANUAL
(III YEAR B.E. – EEE)
Prepared by
Mr. K. Balasubramaniam
Mr. M. Vijayakumar
Mr. K. Prakasam
Mr. A. Gowrishankar
DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING
K.S.R. COLLEGE OF ENGINEERING,
TIRUCHENGODE – 637 215
K.S.R. COLLEGE OF ENGINEERING
TIRUCHENGODE – 637 215
Reg. No.
Certified that this is the work done by Selvan / Selvi ………………….
…………………………………………... of the fifth semester Electrical & Electronics Engineering
branch during the year 2009 – 2010 in the Electrical Machines -II Laboratory.
Staff – in – charge HoD
OBSERVATION NOTE BOOK
INSTRUCTION TO THE STUDENTS
The students must read the instructions carefully and follow the same throughout
the semester.
1. Students have to go to respective lab classes according to the lab time table.
2. They have to wear the shoes and the prescribed uniform.
3. They have to know about the procedure of the experiment before start doing the
Experiment. It will be checked by the staff members.
4. After the Circuit correction in the observation note book and viva voce, they have
to get the indent slip from stores and get the required apparatus.
5. They have to give the circuit connections by involving themselves in their batch.
6. They have to take readings in proper manner without any error and get verified
from the staff.
7. They have to get signature in result within two days after completion of the
experiment.
8. They have to submit their completed previous experiment record at the time of
entering the laboratory and they should enter the mark in the log book with the
lab in-charge.
9. After completing the experiment, they have to return all the apparatus to the
stores and get back the indent slip.
10. Strict discipline is solicited inside the laboratory.
CONTENTS
S.No Date ExperimentPageNo.
MarksSign with
Date
CONTENTS
S.No Date ExperimentPageNo.
MarksSign with
Date
SYLLABUS
ELECTRICAL MACHINES - II LABORATORY
LIST OF EXPERIMENTS
1. Regulation of three-phase alternator by EMF, MMF and ZPF methods.
2. Load test on three-phase alternator.
3. Regulation of three-phase salient pole alternator by slip test.
4. V and Inverted V curves of Three Phase Synchronous Motor.
5. Load test on three-phase squirrel cage induction motor.
6. Load test on three-phase slip ring induction motor.
7. No load and blocked rotor test on three-phase induction motor.
8. Separation of No-load losses of three-phase induction motor.
9. Loss summation method on three-phase induction motor.
10. Load test on single-phase induction motor
11. Determination of Equivalent circuit of single-phase induction motor
12. Speed control of three phase induction motor by V/f method
Exp. No: Date:
REGULATION OF THREE-PHASE ALTERNATOR BY EMF METHOD
AIM:
To predetermine the voltage regulation of a three phase non-salient pole alternator by EMF method.
APPARATUS REQUIRED:
S.No. Apparatus Name Range Type Quantity
1 Voltmeter(0-600)V MI 1
(0-30)V MC 1
2 Ammeter(0-2)A MC 1
(0-10)A MI 1
3 Rheostat 300Ω/1.2 A Variable 34 Tachometer - Digital 1
PRECAUTIONS:1. All the switches should be in open position while making the connection.2. Check the fuse and meters are in required specifications.3. Check all the load terminals are in off position at the time of starting.4. Keep the prime-mover filed rheostat at minimum resistance position and
alternator field rheostat at maximum resistance position at the time of starting.
PROCEDURE:
Open Circuit Test
1. Circuit connections are given as per the circuit diagram.2. Field rheostat of motor is kept at its minimum position at the time of starting.3. DPST Switch is closed. The motor is started by means of starter.4. The motor is set to run at rated speed of the alternator by varying the field
rheostat of the motor.5. The residual emf of the alternator is noted for the zero field current of the
alternator.6. Field rheostat of the alternator is gradually varied and the corresponding
induced emf and the field current is noted between 0 to 120 % of rated voltage.7. Then the field rheostat of the alternator is brought back to its original position.
i.e., the induced emf is brought back to almost zero voltage. 8. Open circuit characteristic is drawn for the above values i.e., between Eg per
phase and If .
Isc OCC
Vph rated
Field current (If) Amps
Arm
ature current , (Ia) Am
ps
SCC
Generated voltage V
ph , Volts
TABULATION
OPEN CIRCUIT CHARACTERISTICS
S.No.Field current(If) in Amps
Line voltage(Vl) in Volts
Phase voltage(Vph) in Volts
SHORT CIRCUIT CHARACTERISTICS
S.No.Field current(If) in Amps
Short circuit current(Isc) in Amps
MODEL GRAPH
OPEN CIRCUIT AND SHORT CIRCUIT CHARACTERISTICS:
Short Circuit Test
1. In short circuit test alternator output terminals short circuited as per circuit diagram.
2. For Short circuit test TPST switch is closed.
3. Field rheostat of the alternator is varied slowly up to the rated current (short circuit current) of the alternator.
4. The corresponding field current is tabulated.
5. Short circuit characteristic is drawn for the noted values i.e., between Isc and If .
Synchronous impedance =
V ph rated
I sc for the same field current.
6. Various power factors are assumed and the phasor diagrams are drawn for both lagging and leading power factors. The voltage induced is obtained from the phasor diagrams and the voltage regulation corresponding to the power factors are calculated using the formulae.
7. Regulation characteristics i.e., power factor Vs voltage regulation are drawn for the various load currents.
FORMULAE USED
i. Synchronous impedance = Zs =
V ph rated
I sc for the same field current. Where, Voc = Rated Open circuit voltage for face, (V) Isc = Short circuit current, (A) at a Field current corresponding to the rated Voltage
ii. Synchronous reactance (Xs)
Xs = √ (Zs2−Rac2) Where, Rac = Ra (dc) X (1.6)
iii. % voltage regulation = (Eg -VT) / VT X 100
Ia
IaRaVT IaXs
Eg
φ
COMPUTATION OF ARMATURE RESISTANCE (Ra):
TABULATION TO FIND Ra
S.No.
Voltage drop across the armature
(Va) in voltsArmature Current
(Ia ) in Amps
Armature Resistance
(Ra = Va/ Ia) in ohm
Mean Ra
MODEL PHASOR DIAGRAM
(i) Lagging current
Ia
φ
VTIaRa
IaXsEg
(ii) Leading current:
VT = Rated voltage
S.No. Sin φ Cos φGenerated Voltage Eg
% Voltage Regulation
Lag Lead Lag Lead
REGULATION CHARACTERISTICS
VIVA QUESTIONS:
1. What is meant by voltage regulation?2. What is meant by Synchronous Impedance?3. What is OC test ?4. What is SC test?5. What is meant by mmf or field ampere turns?
RESULT:
Exp. No: Date:
REGULATION OF ALTERNATOR BY MMF METHOD
AIM:
To predetermine the voltage regulation of a three phase non-salient pole alternator by
MMF method.
APPARATUS REQUIRED:
S.No. Apparatus Name Range Type Quantity
1 Voltmeter (0-600)V MI 1
2 Voltmeter (0-30)V MC 1
3 Ammeter (0-2)A MC 1
4 Ammeter (0-10)A MI 1
5 Rheostat 220Ω/1.2 A Variable 3
6 Tachometer - Digital 1
PRECAUTIONS:1. All the switches should be in open position while making the connection.2. Check the fuse and meters are in required specifications.3. Check all the load terminals are in off position at the time of starting.4. Keep the prime-mover filed rheostat at minimum resistance position and alternator field
rheostat at maximum resistance position at the time of starting.
FORMULA:
% Voltage Regulation = (Eg -Vt ) / Vt X 100
PROCEDURE:1. Circuit connections are given as per the circuit diagram.
2. Field rheostat of motor is kept at its minimum position at the time of starting.
3. DPST Switch is closed. The motor is started by means of starter.
4. The motor is set to run at rated speed by varying the field rheostat of the motor.
5. The residual emf of the alternator is noted for the field current of zero value.
6. Field rheostat of the alternator is varied and the corresponding emf induced and the field currents are noted.
7. Step 6 is repeated till the emf reaches 25% more than rated voltage.
8. Open circuit characteristics are drawn for the above values i.e., between Eg per phase and If .
COMPUTATION OF ARMATURE RESISTANCE (RA):
TABULATION TO FIND Ra:
S.No.Voltage drop across
the Armature(Va) in volts
Armature Current(Ia) in Amps
Armature Resistance
(Ra = Va/ Ia) in ohm
Mean Ra
9. Then the field rheostat of the alternator is brought back to its original position. i.e., the induced emf is brought back to minimum voltage.
10. For Short circuit test TPST switch is closed.
11. Field rheostat of the alternator is varied and the rated current (short circuit current) is made to flow.
12. The corresponding field current is noted.
13. Short circuit characteristic is drawn for the noted values i.e., Between Isc and If . For various power factors the voltage regulations are calculated and voltage regulation characteristic is drawn.
SCC
OCC
Field current (If) Amps
TABULATION:(ii) Open Circuit Characteristics:
S.No.Field current(If) in Amps
Generated line voltage
Vl (volts)
Generated per phase voltage
Vph (volts)
(iii) Short Circuit Characteristics:
S.No. Field Current (If) in Amps Short Circuit Current (Isc) in Amps
MODEL GRAPH :
OPEN CIRCUIT AND SHORT CIRCUIT CHARACTERISTICS
Ia
IaRaVt
Etφ
Eg
If2
If1
If
If1 – Field current corresponding to EtIf2 – Field current corresponding to IaIf – Resultant field current of If1 and If2Eg – Generated voltage per phase corresponding to field current If
O
Vt
IaRa
Et
Eg
If1
Ia
If
φ
MODEL PHASOR DIAGRAM:
1. Draw rated voltage (Vt) per phase as reference vector and then draw Ia with an angle of +
(+ for lagging power factor and – for leading power factor). φ
2. Draw a line IaRa, parallel to Ia, then join point ‘O’ and the end point of IaRa and it is known as
Et.
3. From OCC curve, find If1 for the corresponding value of Et and draw If1 normal to Et.
4. From SC curve find If2 for the value of Ia and draw If2 in phase opposition to Ia.
5. Add the current vectors If1 and If2, get the resultant field current vectors If.
6. From OCC curve find Eg for the value of If and draw Eg normal to If.
(i) Lagging power factor
(ii)
Leading power factor
Rated current = A Rated voltage per phase = V
S.No.Power Factor
Induced voltage per phase
Eg volts% Voltage Regulation
Lagging Leading Lagging Leading
REGULATION CHARACTERISTICS
MODEL CALCULATIONS
RESULT:
EXP.NO. DATE:
REGULATION OF 3-PHASE ALTERNATOR BY POTIER TRIANGULAR METHOD
AIM:To predetermine the regulation of three phase alternator by ZPF method and draw the
vector diagrams.
APPARATURS REQUIRED:
S.NO Name of the Apparatus Type Range Quantity
1 Ammeter MC 0 – 1/2 A 12 Ammeter MI 0 – 5/10 A 13 Voltmeter MC 0 – 10 V 14 Voltmeter MI 0 – 600 V 15 Rheostat Wire wound 250 Ω, 1.5 A 16 Rheostat Wire wound 1200Ω, 0.8 A 17 Tachometer Digital --- 18 TPST knife switch -- -- 1
FORMULAE USED:
Percentage Regulation=Eo−V Rated
V Rated
X 100
PRECAUTIONS:(i) All the switches should be in open position while making the connection.(ii) Check the fuse and meters are in required specifications.(iii) Check all the load terminals are in off position at the time of starting.(iv) Keep the prime-mover filed rheostat at minimum resistance position and alternator
field rheostat at maximum resistance position at the time of starting.
PROCEDURE TO DRAW THE POTIER TRIANGLE (ZPF METHOD): (All the quantities are in per phase value)
1. Draw the Open Circuit Characteristics (Generated Voltage per phase VS Field Current)2. Mark the point A at X-axis, which is obtained from short circuit test with full load armature
current.3. From the ZPF test, mark the point B for the field current to the corresponding rated
armature current and the rated voltage.4. Draw the ZPF curve which passing through the point A and B in such a way parallel to the
open circuit characteristics curve.5. Draw the tangent for the OCC curve from the origin (i.e.) air gap line.6. Draw the line BC from B towards Y-axis, which is parallel and equal to OA.7. Draw the parallel line for the tangent from C to the OCC curve.
OPEN CIRCUIT TEST:
S.No.Field
Current(If)in amps
Open circuit lineVoltage (vol)
in volts
Open circuit phase voltage (voph)in volts
8. Join the points B and D also drop the perpendicular line DE to BC, where the line DE represents armature leakage reactance drop (IXL) BE represents armature reaction excitation (Ifa).
PROCEDURE TO DRAW THE VECTOR DIAGRAM (ZPF METHOD)
1. Select the suitable voltage and current scale.2. For the corresponding power angle ( Lag, Lead, Unity) draw the voltage vector and current
vector OB.3. Draw the vector AC with the magnitude of IRa drop, which should be parallel to the vector
OB.4. Draw the perpendicular CD to AC from the point C with the magnitude of IXL drop.5. Join the points O and D, which will be equal to the air gap voltage (Eair). 6. Find out the field current (Ifc) for the corresponding air gap voltage (Eair) from the OCC
curve.7. Draw the vector OF with the magnitude of Ifc which should be perpendicular to the vector
OD.8. Draw the vector FG from F with the magnitude Ifa in such a way it is parallel to the current
vector OB.9. Join the points O and G, which will be equal to the field excitation current (If).10. Draw the perpendicular line to the vector OG from the point O and extend CD in such a
manner to intersect the perpendicular line at the point H.11. Find out the open circuit voltage (Eo) for the corresponding field excitation current (If)
from the OCC curve.12. Find out the regulation from the suitable formula.
SHORT CIRCUIT AND ZPF TEST:
S.No
Short Circuit Test ZPF Test
Field current(If)
in Amps
Rated Armature
Current (Ia) in Amps
Field current (If)
in Amps
Rated Armature
Current (Ia) Amps
Rated Armature
Voltage (Va) in Volts
W1 in Watts W2 in WattsTotal Power in Watts
Act. = (Obs. X MF)
Act. = (Obs. X MF)
(W1+W2)
MF
VIVA QUESTIONS:
1. What is meant by ZPF Test?
2. What is Poitier reactance? How is it determined by Poitier triangle?
3. What is meant by armature reaction reactance?
4. What is the significance of the ASA modification of MMF method?
5. What is air gap line in Poitier method?
RESULT:
Exp. No: Date:
LOAD TEST ON THREE-PHASE ALTERNATORAIM:
To conduct a load test on three phase alternator and to draw the following
characteristics
a) voltage regulation curve b) output Vs efficiency curve
APPARATUS REQUIRED:
Serial No.
Name of the apparatus
Range Type Quantity
1.
2.
3.
4.
5.
Voltmeter
Ammeter
Rheostat
Tachometer
Three phase Loading Unit
(0-600V)
(0-250V)
(0-50A)
(0-2A)
(0-10A)
220 /1.2AΩ
-
5KW
MI
MC
MC
MC
MI
Variable
Digital
Resistive
1
1
1
1
1
3
1
1
PRECAUTIONS:1. All the switches should be in open position while making the connection.2. Check the fuse and meters are in required specifications.3. Check all the load terminals are in off position at the time of starting.4. Keep the prime-mover filed rheostat at minimum resistance position and alternator field
rheostat at maximum resistance position at the time of starting.PROCEDURE:
1. The connections are made as per the circuit diagram and the DPST is closed.2. Start the motor with the help of three point starter.3. By adjusting the field rheostat of motor, run the alternator at synchronous speed.4. The alternator field rheostat resistance is adjusted and set the voltmeter reading to rated
voltage of the alternator.5. At no load take the readings of voltmeter, ammeter.6. Now, close the TPST switch and apply the load. Look for any change in the speed and
voltage if so brings back to the previous values. Now take the corresponding reading of ammeter.
7. Now open TPST switch and note down the alternator side voltage reading as Eg and immediately the TPST is closed.
8. Repeat the above procedure until the machine is loaded up to 120% of rated current.
TABULATION:
S.No
MOTOR ALTERNATOR
Input voltage (Vm) in Volts
InputCurrent(Im) inAmps
Input power(Wmi)
in Watts
Output power (Wmo)
inWatts
Load voltage (VA) in Volts
Load current
IA in Amps
Output power
=√3VLIL
Cosφ in
watts
Field winding voltage (Vf) inVolts
Field winding current
(If) in Amps
Field winding
input(VLIL)
In Watts
Input to the
alternator in watts
% Efficiency
η
% Voltage regulation(Eg-Vr)/Vr
*100
FORMULA USED:
Motor Input Power = Vm Im
Motor Output Power = ηmVmIm [Assume motor efficiency]
Input to the Field Winding = Vf If
Alternator Input Power = Motor Output Power + Input to the Field Winding
Alternator Output Power = √3VLILCos [Where Cos = 1]φ φ
% of Alternator Efficiency (ηA) = (Output Power/ Input Power)X100
% Voltage Regulation = [(Eg1-Vr) / Vr]X100 %
MODEL CALCULATION:
VIVA QUESTIONS:
1. What is meant by direct axis reactance?
2. What is meant by quadrature axis reactance?
3. How the regulation of alternator is predetermined?
4. What is the difference between salient pole alternator and cylindrical rotor type alternator?
5. What is the purpose of damper winding?
RESULT:
Exp. No: Date:
REGULATION OF THREE-PHASE SALIENT POLE ALTERNATOR BY SLIP TEST
AIM:To predetermine the voltage regulation of the given three-phase alternator by slip
test.
APPARATUS REQUIRED:
S.No.Apparatus
NameRange Type Quantity
1 Voltmeter
(0-600) V MI 1
(0-100) V MI 1
(0-30) V MC 1
2 Ammeter (0-10) A MC 1
(0-10) A MI 1
3 Rheostat 220 / 2.2 AΩ Variable 1
PRECAUTIONS:1. All the switches should be in open position while making the connection.2. Check the fuse and meters are in required specifications.3. Check all the load terminals are in off position at the time of starting.
PROCEDURE:
1. Circuit connections are given as per the circuit diagram.
2. After closing the DPST switch, the motor is started by using three point starters.
3. Now the alternator is made to run at a speed slightly less than synchronous speed using field rheostat of the motor.
4. By using the three phase auto transformer, a low voltage is applied across the stator of the alternator. Suppose, if the voltmeter across the field winding, reads some value, then change the direction of rotation of the alternator or if the same voltmeter reads zero, then the speed of the alternator and voltage applied are slightly adjusted in such a manner that the pointer in the voltmeter and ammeter of the alternator oscillates with maximum and minimum amplitude.
5. The maximum and minimum values of the readings of both the meters are noted.
TABULATION
Minimum Voltage in
Volts
Maximum voltage in
Volts
Minimum current in
Amps
Maximum current in
Amps
Xsd inΩ
Xsq in Ω Xsd/Xsq
Ia = Amps
Sl.No. Power factorEo in Volts % Regulation
Lagging Leading Lagging Leading
Ia = Amps
Sl.No. Power factorEo in Volts % Regulation
Lagging Leading Lagging Leading
MODEL CALCULATION
Maximum voltage/ph. = Vmax /√3
Minimum voltage/ph. = Vmin /√3
Synchronous reactance of direct axis Xsd = (Max. voltage/Ph.) / (Min.current/ph.)
Synchronous reactance of quatrature axis Xsq = (min. voltage/ph) / (max.current/ph.)
% Regulation = (E0 – Vph.) / Vph. X 100
COMPUTATION OF ARMATURE RESISTANCE (RA):
TABULATION TO FIND Ra:
S.No.
Voltage drop across the Armature(Va) in Volts
Armature Current
(Ia) in Amps
Armature Resistance
(Ra = Va/ Ia) in ohm
Mean Ra
Average value of Ra = --------- Ω Ra.c = Rd.c * 1.1 = ------- Ω
REGULATION CHARACTERISTICS:
PROCEDURE TO DRAW THE VECTOR
DIAGRAM
Assume rated voltage ‘V’ per phase as the reference vector and mark the endpoint as ‘a’.
Draw a line ‘la’ lags the voltage ‘V’ by an angle ‘’.
From point ‘a’ draw a drop ‘laRa’ in parallel with ‘la’ and mark it as point ‘b’.
From point ‘b’ draw a drop ‘laXq’ in quadrature with ‘la’ and mark it as point ‘c’
Join the points ‘o’ & ‘c’.
The angle between oc & ‘V’ is ‘’ and the angle between oc & ‘la’ is’ ’.
Draw the currents ‘Iq’ & ‘Id’ where ‘Iq‘ & ‘Id’ are quadrature & direct components of Ia
where Iq =la cos, Id = la sin
From point ‘b’ draw a line IdXd in quadrature with ‘Id’ and mark it as point‘d’. From point‘d’ draw a line IqXq in quadrature with ‘Iq’ and mark it as point ‘e’.
Join the points ‘o’ and ‘e’ it will give the value of the generated voltage ‘Eo’ per phase
Ф
Ia Xq
IdXd
e
d
cEo
bIaRa
aVPhδ
Iq
IaId
o
VECTOR DIAGRAM FOR 0.8 PF LAGGING
VIVA QUESTIONS:
1. What is the purpose of slip test on 3 phase alternator?
2. Define Slip
3. How is the regulation of alternator predetermined by slip test?
4. What is the purpose of damper winding?
RESULT
Exp. No: Date:
V AND INVERTED V CURVES OF THREE PHASE SYNCHRONOUS MOTOR
AIM:
To draw ‘V’ and inverted ‘V’ curves of a given three phase synchronous machine.
APPARATUS REQUIRED:
S.No. Apparatus Name Range Type Quantity
1. Voltmeter (0 – 300 V) MC 1
(0 – 600 V) MI 1
2. Ammeter
(0 – 2A) MC 1
(0 – 20A) MC 1
(0 – 10A) MI 1
3.Rheostat 50Ω/4.9A Variable 1
360 Ω / 1.1A Variable 3
4. Watt meter 300V/10A UPF 1
5. Power Factor meter 600V/10A Analog 1
6. Synchronizing switch - Manual 1
PRECAUTIONS:1. All the switches should be in open position while making the connection.2. Check the fuse and meters are in required specifications.3. Check all the load terminals are in off position at the time of starting.
PROCEDURE
1. Connections are made as per the circuit diagram.
2. DPST switch is closed and DPDT switch is thrown to position – 1.
3. Now the armature rheostat of the motor is brought to its minimum resistance position. At this instant the SPST switch is closed.
TABULATION
1. at no load condition
S.No.Vdc in Volts
Field current
(If) in Amps
Vac in Volts
Iac in Amps
Wattmeter reading W1
in Watts
Power W1 x MF
in Watts
Power Factor
* MF is the watt meter multiplication factor
2. at any load condition
S.No.Vdc in Volts
IL in Amps
Field current
If in Amps
Vac in Volts
Iac in Amps
Wattmeter reading W2
in Watts
PowerW2 x MF
in Watts
Power Factor
* Where MF is the watt meter constant
4. The field rheostat resistance of the motor is adjusted so that the motor runs at nearly to its synchronous speed.
5. The supply voltage on the alternator side is measured.
6. By varying the filed rheostat resistance of the alternator the generated voltage is made equal to the supply voltage of the three phase side.
7. Now the TPST switch is closed and the lamp flickers. By adjusting the filed rheostat of the motor, bring the frequency of the flickering to very minimum. During the dark period, the synchronous switch is closed. Now the synchronous machine is synchronized with the main supply.
8. Now the DPDT switch is opened.
9. By varying the field rheostat resistance of the alternator, find the point where the field current is low and armature current in approximately 110% of the full load current. Note down all the meter readings.
10. Gradually move the rheostat resistance position such that, the field current increases and the alternator armature current decreases. Note down the readings for various armature currents. At one stage, the field current will still increase and the armature current will also increase. Take the readings up to the 110% of rated current of the armature.
11. Now DPDT switch is thrown to position – 2. Apply some load on the DC generator.
12. Repeat the previous procedure.
13. Draw the curves between field current Vs power factor and field current Vs armature current.
MODEL GRAPH:
VIVA QUESTIONS:
1. Why Synchronous motor is not self starting?
2. What are the starting methods used for synchronous motor?
3. List the application of Synchronous motor?
4. What are the readings considered for inverted V curve?
5. What is synchronous condenser?
RESULT:
Exp. No: Date:
LOAD TEST ON THREE-PHASE SQUIRREL CAGE INDUCTION MOTOR
AIM:
To conduct the load test on the given three phase squirrel cage induction motor and
to draw its performance characteristics.
APPARATUS REQUIRED:
S.No. Apparatus Range Type Quantity
1. Voltmeter (0-600)V Ml 1
2. Ammeter (0-10) A Ml 1
3. Wattmeter 600 V, 10A UPF 2
4. Tachometer -- Digital 1
PRECAUTIONS:1. All the switches should be in open position while making the connection.2. Check the fuse and meters are in required specifications.3. Check all the load terminals are in off position at the time of starting.
PROCEDURE
1. Circuit connections are given as per the circuit diagram.
2. After closing the TPST switch, motor is started by using star-delta starter.
3. Note down the no load readings of V1, I1, W1, W2, S1, S2 and N.
4. By applying the load, take different readings till the current reaches 120% of the rated current.
5. Using the formula, efficiency, torque, power factor and slip are calculated and the curves are plotted.
TABULATION
S. No
.
Line Voltage (VL) inVolts
Load current (IL) inAmps
Spring balance Readings (Kg)
Speed (N) in
RPM
Wattmeter readings
Input power (Pt) in
Watts
Torque (T) in
N-m
Output power (Po) in
Watts
Power factor
% Slip (S)
% Efficiency
()S1 S2 S1~ S2 W1xMF W2xMF
FORMULAE USED
1. Input Power (Pi) = (MF x W1 + MF x W2) watts
2. Torque (T) = 9.81 * (S1 ~ S2) * Reff N-m
3. Output Power (Po) = 2 N T / 60 wattsπ
4. Efficiency () = (Output Power / Input Power)* 100
5. % of Slip (S) = (Ns – N / Ns) X 100
6. Power Factor = Input Power / (√3
* VL *IL)
Where,
S1, S2 Spring balance readings in Kg.
Reff Effective radius of the brake drum in meters.
Reff = (Brake drum radius in cm + ½ of thickness of belt in cm)
T Torque in N-m
N Speed in RPM
Ns Synchronous speed in RPM
MF Multiplication factors of wattmeter
MODEL GRAPH
MODEL CALCULATION
VIVA QUESTIONS:
1. What is meant by RMF?2. Why an induction motor is called rotating transformer?3. Why an induction motor will never run at its synchronous speed?4. What are slip rings?5. What are the advantages of cage motor?6. What is meant by magnetic logging?
RESULT
Exp. No: Date:
LOAD TEST ON THREE-PHASE SLIP RING INDUCTION MOTOR
AIMTo conduct a load test on slip ring induction motor and draw its performance characteristics.
APPARATUS REQUIRED
S.No.Name of the apparatus
Range Type Quantity
1. Voltmeter (0 -600)V MI 1
2. Ammeter (0-10A) MI 1
3. Wattmeter 600V/10A UPF 2
4. Tachometer ---- Digital 1
PROCEDURE
The connections are made as per the circuit diagram.
The rotor resistance starter should be at the maximum resistance position.
The TPST switch is closed.
The rotor resistance starter is adjusted by means of step by step and bring it in to
minimum resistance position.
At no load take the readings of voltmeter, ammeter and wattmeter and also the speed in
RPM
Load the machine up to 120% of full load and note down all the meter readings.
TABULATION:
S.No
Line voltage (VL) in Volts
Line current (IL) in Amps
Speed (N) in rpm
Wattmeter readings in Watts
Spring balance readingin kgs. Torque
(T) in N-m
% slip(S)
Power factor
Output power
inWatts
% Efficiency
( )ηW1 x MF
W2 x MF
W1+W2 S1 S2 S1~S2
Without External
Resistance
With External
Resistance
Release the load fully and bring the machine to off position.
Repeat the above procedure when external resistance is included in the rotor circuit.
FORMULA:
i). Input power Pin = W1 + W2 in watts
Where,
W1, W2 - wattmeter readings in watts
ii). Torque T = 9.81x (S1~S2) x Reff. N-m
Where, S1, S2 - Spring balance readings in Kgs
Reff - Effective radius of brake drum in m
iii). Output power Po= (2 NT) / 60 in wattsπ
Where, N - Speed of rotor in rpm T - Torque in N-m
iv). % Slip = ((NS-N) / NS) x100
Where,
Ns - Synchronous speed in rpm
v). % efficiency ( ) = (Output power / Input power) x 100η
vi). Power factor (cos ) = Input power / (√3Vφ L IL)
Where,
VL - Supply voltage in volts IL - Line current in amps
VIVA QUESTIONS:
1. Mention different types of speed control of slip ring induction motor?2. What is meant by crawling of induction motor?3. What are the advantages of 3-phase induction motor?4. What is the difference between slip ring and split ring?5. What is reason for inserting additional resistance in rotor circuit of a slip ring induction
Motor?
RESULT:
Exp. No: Date:
NO LOAD AND BLOCKED ROTOR TEST ON THREE-PHASE INDUCTION MOTOR
AIM
To predetermine the performance characteristics of a three phase squirrel cage
induction motor from equivalent circuit and circle diagram approach.
APPARATUS REQUIRED
S.No.Apparatus
NameRange Type Quantity
1. Ammeter
0-5A MI 1
0-15A MI 1
0-15A MC 1
2. Voltmeter
0-600V MI 1
0-150V MI 1
0-30V MC 1
3. Wattmeter600V/5A LPF 2
150V/20A UPF 2
PRECAUTIONS
TPST should be opened before verifying the circuit connections
Autotransformer should be in the minimum voltage position
TABULATIONS
NO LOAD TEST
Line Voltage
(VL)in Volts
Line Current
(Ia)in Amps
Wattmeter reading in Watts No load input
Power in Watts= W1 +W2
Speed (N)in rpm
W1 x MF W2 x MF
BLOCKED ROTOR TEST
Line Voltage(VL) in Volts
Line Current
(Ia)in Amps
Wattmeter reading in Watts Copper loss in
Watts= (W1 + W2)W1 X M.F W2 X M.F
TO FIND STATOR RESISTANCE
S.No.
Voltage drop in the stator
(V)in Volts
Stator current (Is)
in Amps
Stator resistance(Rs = V / Is)
in Ω
Mean (Rac)
Stator resistance R1 = Rac x 1.6 in Ω
PROCEDURE
NO LOAD TEST
The connection are made as shown in the circuit diagram
After observing all precautions the TPST switch is closed
By adjusting autotransformer bring the voltmeter reading to rated voltage of the motor
then note down voltmeter, the ammeter and the wattmeter readings.
BLOCKED ROTOR TEST
Block the rotor by applying a load
After observing all the precautions the TPST switch is closed
By gradually adjusting the auto transformer bring the ammeter reading to the rated current of the motor then note down ammeter, voltmeter and wattmeter readings
TO FIND THE STATOR RÉSISTANCE
The connection are made as shown in the circuit diagram
Apply different voltage to stator winding up to the full load current note down the ammeter and the voltmeter readings
FORMULAE
NO LOAD TEST
No load line voltage = V0 in Volts
No load line current = I0 in Amps
No load power = W0 in Watts
BLOCKED ROTOR TEST
Blocked rotor line voltage = Vsc in Volts
Blocked rotor line current = Isc in Amps
Blocked rotor power = Wsc in Watts
No load voltage per phase V0 = VL0 in V
No load current per phase I0 = IL0 / √3 in A
No load power per phase W0 = WL0 / 3 in W
Blocked rotor voltage per phase Vsc= VLsc in V
Blocked rotor current per phase Isc = ILsc / √3 in A
Blocked rotor power per phase Wsc = WLsc / 3 in W
Cos ф0 = Wo / V0 I0
ф0 = Cos -1(Wo / V0 I0)
Find Sin ф0
Magnetizing branch resistance R0 = V0 / (I0 Cos ф0) in Ω
Magnetizing branch reactance X0 = V0 / (I0 Sin ф0) in Ω
Total resistance Rsc = Wsc / Isc2 in Ω
Total impedance Zsc = Vsc / Isc in Ω
Total reactance Xsc = √ Zsc2- Rsc
2 in Ω
X1 = X21 = Xsc / 2 in Ω
R21 = Rsc – R1 in Ω
Where
X1 - Stator reactance in Ω
X21 - Rotor reactance referred to stator in Ω
R1 - Stator resistance in Ω
R21 - Rotor resistance referred to stator in Ω
For any slip ‘S’, RL = R21 (1 - s) / s in Ω
Z = (R1+ R21 / s) + j(X1 + X2
1 /s) in Ω
I11∟ф1 = (V∠0 ° / Z) in A
No load current per phase = I0∟ф in A
TABULATION FOR EQUIVALENT CIRCUIT METHOD
MODEL GRAPH (EQUIVALENT CIRCUIT)
S. No.
Line Voltage (VL) in Volts
% Slip(assume)
Speed(N) in RPM
Phase current(IPh) in Amps
Line current(IL) in Amps
Input power(Pt) in Watts
Output power(Po) in Watts
Torque (T) inN-m
Power Factor
% Efficiency
( )η
I1 = I0∟ф+ I11∟ф1
= I ∟ in Aф
Line current IL = √3 I in A
Power factor = Cos ф
Speed = NS (1 - s) in rpm
Input power = 3 x Vph x Iph x Cos in Wф
Output power = 3 x (I’1)2 x RL in W
%Efficiency=Output PowerInput Power
X 100
Torque=(I ¿¿11 x R21/s )/(2 x π xns)∈Nm¿
Where ns – synchronous speed in rps
Repeat the above calculation for various slips.
MODEL GRAPH (CIRCLE DIAGRAM)
VIVA QUESTIONS:
1. What is purpose of Equivalent circuit?2. What is meant by crawling of induction motor?3. How will you calculate Cu loss of 3-phase induction motor?4. How will you calculate core loss of 3-phase induction motor?5. List out the starting methods for 3 phase induction motor.
RESULT:
Exp. No: Date:
SEPARATION OF NO-LOAD LOSSES OF THREE-PHASE INDUCTION MOTOR
AIM
To separate the no load losses of a three-phase induction motor to its components
a) Iron loss
b) Mechanical loss
APPARATUS REQUIRED
S.No Apparatus Range Type Quantity
1. Voltmeter0-600 V MI 1
0-30 V MC 1
2. Ammeter 0-5 A MI 1
0-10 A MC 1
3. Watt meter 600 V/5 A LPF 2
PRECAUTIONS:1. All the switches should be in open position while making the connection.2. Check the fuse and meters are in required specifications.3. Check all the load terminals are in off position at the time of starting.
PROCEDURE
The connections are made as per the circuit diagram.
By adjusting the autotransformer, the rated voltage is applied.
The readings of Voltmeter, Ammeter and Watt meters (W1W2) are noted.
By adjusting the autotransformer, apply slightly less than the previous voltage and the meter readings are noted.
Repeat the above procedure until the voltmeter reads the minimum voltage.
A graph connecting Vph2 Vs No Load Loss is drawn. From the curve mechanical loss and iron loss at rated voltage are calculated.
S.No
Line voltage (VL) in Volts
Line current (IL) in Amps
Phase current (Iph) in Amps
Vph2
Watt meter reading in
Watts No load input Power in Watts
( W1+ W2)
Copper loss in Watts
No load loss in Watts
Mechanical loss (Wm) in
Watts
Iron loss (Wi )
in WattsW
1xMF W
2xMF
TABULATION – SEPARATION OF NO LOAD LOSSES
FORMULA
No load losses = No load input – No load Cu loss
NoLoad Losses=K1W 1+K2W 2−3 I o2 x Ra
VIVA QUESTIONS:
1. What are losses in 3-Phase induction motor?2. How will you separate losses of induction motor?3. What is meant by Hysteresis loss?4. What is meant by Eddy Current loss?5. How to minimize the eddy current and hysteresis losses?
RESULT:
Exp. No: Date:
LOSS SUMMATION METHOD ON THREE-PHASE INDUCTION MOTOR
AIM
To predetermine the performance characteristics of a given 3 phase induction
motor by loss summation method.
APPRATUS REQUIRED
S.No. Apparatus Name Range Type Quantity
1. Voltmeter
0 – 600 V MI 1
0 – 150 V MI 1
0 – 30 V MC 1
2. Ammeter 0 – 10 A MI 1
0 – 10 A MC 1
3.Wattmeter 600 V / 10 A UPF 2
150 V / 10 A UPF 2
PRECAUTIONS:1. All the switches should be in open position while making the connection.2. Check the fuse and meters are in required specifications.3. Check all the load terminals are in off position at the time of starting.
PROCEDURE
NO LOAD & LOAD TEST
Connections are made as per the circuit diagram.
By adjusting the autotransformer the rated voltage is applied.
The NO LOAD readings of Voltmeter, Ammeter and Watt meters (W1, W2) are noted.
Now the motor is gradually loaded and the corresponding readings are noted.
This procedure is repeated till 125% of rated current is obtained.
Note: The brake drum spring balance readings are ignored.
BLOCKED ROTOR TEST
Connections are made as per the circuit diagram.
The rotor is blocked.
The autotransformer is adjusted such that the ammeter reads the same value of current as in the load test (i.e. rated current) and the corresponding readings of Voltmeter and Watt meters (W3, W4) are noted.
TABULATION – LOSS SUMMATION METHOD
S. No
Line voltage (VL)
in Volts
Line Current
(IL) in Amps
Speed (N) in rpm
Wattmeter readings in watts
Input power (W)
(W1+ W2) in Watts
Cu loss (W)
(W3+ W4) in Watts
Output power in
Watts
Torque (T) in N-
m
Power factor
% Slip
% Efficienc
yMF x W1
MF x W2
MF x W3
MF x W4
FORMULAE
Constant losses (Wo) = No load input – No load Cu loss
No load input – 3 I02 * Ra
Input power = W1 + W2
Cu loss = W3 + W4
Output power = Input power – Cu loss – Constant loss
= (W1 + W2) – (W3 + W4) – W0
Torque (T) = (Output / 2N) * 60 N – m
Slip (%) = (Ns – N) / Ns * 100
Power Factor = Input / (3 VL *IL)
Efficiency (%) = (Output / Input) * 100
VIVA QUESTIONS:
1. Why the three phase induction motor is called as rotating transformer?2. How will you separate losses of induction motor?3. What is the relationship between load current and loss?4. Why the induction motors are generally called as asynchronous motor?5. Name the applications of 3 phase squ. Cage induction motor?
RESULT
Exp. No: Date:
LOAD TEST ON SINGLE-PHASE INDUCTION MOTOR
AIM
To conduct the load test on single phase capacitor start induction motor and to
draw the performance characteristics curve.
APPARATUS REQUIRED
S.No. Apparatus Name Range Type Quantity
1. Voltmeter 0-300V MI 1
2. Ammeter 0-20A MI 1
3. Wattmeter 300V/20A UPF 1
4. Single Phase Auto Transformer230V/(0-270)V,
20AVariable 1
5. Tachometer - Digital 1
PRECAUTIONS:1. All the switches should be in open position while making the connection.2. Check the fuse and meters are in required specifications.3. Check all the load terminals are in off position at the time of starting.
PROCEDURE
The connections are made as shown in the circuit diagram.
The supply is given and the DPST switch is closed.
By adjusting autotransformer, bring the voltmeter reading to rated voltage of the motor.
Under no load condition note down all the meters reading.
Now apply the load in step by step up to the 125% of rated current, note down all the readings of the meters.
TABULATION
S.No.
Supply voltage (Vs) in
Volts
Line current (IL) in
Amps
Input power
(W1xMF)
(Watts)
Speed
(N) in rpm
Spring balance reading in kg
Torque
(T) in N-m
Output power
(Po) in Watts
% Slip
Power Factor
% Efficiency
S1 S2 S1~ S2
FORMULAE
1. Torque = 9.81 (S1 ~ S2) * Reff in N-m
Where S1, S2 - Spring balance reading in Kg
Reff - Effective radius of the brake drum in metre.
2. Output power = 2 NT / 60 in wattsπ
3. % Slip = (Ns – N) / Ns * 100
Where Ns - Synchronous speed of the machine.
N - Rotor sped of the machine.
4. Power Factor = Input power / VLIL
5. % Efficiency = (Output power / Input power) * 100
VIVA QUESTIONS:
1. What are the various methods available for making a single-phase motor self-starting?
2. What is the function of capacitor in a single-phase induction motor?
3. State any four use of single-phase induction motor.
4. State the advantages of capacitor start- run motor over capacitor start motor.
RESULT
Exp. No: Date:
DETERMINATION OF EQUIVALENT CIRCUIT OF SINGLE-PHASE INDUCTION MOTOR
AIM:To draw the performance characteristics of a single phase induction motor by
conducting the no-load and blocked rotor test.
APPARATUS REQUIRED:
S.NoName of
ApparatusRange Type Quantity
1 Voltmeter(0-300)V
MI1
(0-150)V 1
2 Ammeter(0-10)A 1(0-2)A 1
3 Wattmeter(330V,10A) UPF 1(300V,5A) LPF 1
THEORY:
A 1- induction motor consists of stator, rotor and other associated parts. In theФ
rotor of a single phase winding is provided. The windings of a 1- winding(provided) areФ
displaced in space by 120º.A single phase current is fed to the windings so that a resultant
rotating magnetic flux is generated. The rotor starts rotating due to the induction effect
produced due to the relative velocity between the rotor winding and the rotating flux.
PRECAUTIONS:NO LOAD TEST:
Initially DPST Switch is kept open. Autotransformer is kept at minimum potential position. The machines must be started on no load.
BLOCKED ROTOR TEST:
Initially the DPST Switch is kept open. Autotransformer is kept at minimum potential position. The machine must be started at full load(blocked rotor).
PROCEDURE:
NO LOAD TEST:
1. Connections are given as per the circuit diagram.2. Precautions are observed and the motor is started at no load.3. Autotransformer is varied to have a rated voltage applied.
BLOCKED ROTOR TEST:
1. Connections are given as per the circuit diagram.2. Precautions are observed and motor is started on full load or blocked rotor
position. 3. Autotransformer is varied to have rated current flowing in motor.4. Meter readings are the noted.
Reff = 1.5*Rdc
FORMULAE-
NO LOAD TEST- cos = Wo/VoIo Ф Iw = Io cosФ Im = Io sin Ф Ro = Vo/Iw Xo = Vo/Im
BLOCKED ROTOR TEST-
Zsc = Vsc/Isc ΩRsc = Wsc/Isc2 ΩXsc = √(Zsc2 – Rsc2) Ω
TABULATION
NO LOAD TEST
S.No.No Load
Voltage (Vo) in volts
No Load Current
(Io) in amps
No Load Power (Wo) in watts
Actual = Observed x MF
BLOCKED ROTOR TEST
S.No.Short Circuit
Voltage (Vsc) in volts
Short Circuit
Current (Isc) in amps
Short Circuit Power (Wsc) in watts
Actual = Observed x MF
VIVA QUESTIONS:
1. What are losses in Single Phase induction motor?2. Name the types of single phase induction motor?3. What is the purpose of centrifugal switch?
4. State any four use of single-phase induction motor.
RESULT-
Exp. No: Date:
SPEED CONTROL OF THREE PHASE INDUCTION MOTOR BY V/F METHOD
AIM
To control the speed of a given Three-Phase Induction motor by V/f method and to
draw the characteristics curves.
APPARATUS REQUIRED
S. NO Name of the Apparatus Type Range Quantity
1 Voltmeter MI 0-600V 1
2 Three-Phase Autotransformer Variable 415V / (0-600)V 1
3 Tachometer Digital - 1
PROCEDURE
VOLTAGE CONTROL METHOD
1. Connections are given as per the circuit diagram.
2. Using the three-phase autotransformer motor is started to run.
3. The three-phase autotransformer is varied gradually and the corresponding voltage
and speed are noted up to 120% of the rated speed.
4. The motor is switched off using the TPST switch after bringing autotransformer is
their initial position.
TABULATION FOR VOLTAGE CONTROL METHOD
Speed (N) in r.p.m
S.NOAPPLIED VOLTAGE
in VoltsSPEED IN RPM
(N)
MODEL GRAPH:
Vin in volts
VOLTAGE CONTROL METHOD:
1. Circuit connections are given as per the circuit diagram.
2. Field rheostat of motor is kept at its minimum position at the time of starting.
3. DPST Switch is closed. The motor is started by means of starter.
4. The motor is set to run at rated speed of the alternator by varying the field rheostat of the motor.
5. Field rheostat of the alternator is gradually varied and set the rated voltage.
6. Then the field rheostat position of the motor is varied. i.e., the frequency of the induced emf also changed.
7. This induced voltage given to the induction motor.
8. For different frequency speed of the induction motor reading is noted.
TABULATION FOR VOLTAGE CONTROL METHOD
Speed
(N) in
r.p.m
S.NOFrequency in Hz
f=PN/120SPEED IN RPM
(N)
MODEL GRAPH:
Frequency in Hz
Viva Questions:
1.What are the speed control methods of induction motor?2.Write the speed equation for induction motor?3.What are the speed control methods for Slip-ring Induction motor.4.Define Synchronous speed.
RESULT: