Elevated Neutral to Earth Voltages Due to Harmonics – A T&D...
Transcript of Elevated Neutral to Earth Voltages Due to Harmonics – A T&D...
1
1
Elevated Neutral to Earth Voltages Due to Harmonics
– A T&D Update
E. R. (Randy) Collins, PhD, PE
Dept. of Electrical and Computer EngineeringClemson University
Clemson, South Carolina
Stray Voltage Panel Session2008 IEEE T&D Meeting - Chicago
April 24, 2008
2
Two Publications of Interest“Analysis of Elevated Neutral-to-Earth Voltage in Distribution Systems with Harmonic Distortion” to appear in 2008, IEEE Trans. on Power Delivery, Paper TPWRD-00652-2006 by Randy Collins and Jian Jiang.“Elevated Neutral-To-Earth Voltage In
Distribution Systems With Harmonic Distortion,” PhD Dissertation, Clemson University, by Jian Jiang, 2007.
2
3Three Phase Distribution Feeder with Single Phase Lateral
Earth
4
Equipotentials surround ground rods
3
5What do we mean by NEV and how does this relate to stray voltage?
Neutral-to-earth voltage is the neutral conductor voltage referred to remote earth.The NEV can be much higher than the “stray voltage” that can be contacted by humans or animals, so the results must be tempered with this understanding. Knowledge of NEV under different system conditions is extremely important in analyzing and mitigating stray voltage problems arising from NEV.
6
Common Sources and Conventional Resolutions for Elevated NEV and Stray Voltage
SourcesPower system groundingLoad unbalanceTransformer connectionsNeutral conductor impedance
Alleviation methodsBalance the loads Three-phase single phase lateralsIncrease the neutral conductor sizeImprove grounding connection Repair bad neutral connections and splices
4
7Trends of Consumer Electronics and Their Impact on NEV
Proliferation of single phase nonlinear power supplies in electronic appliancesNon-linear response of single-phase motors to voltage distortion
Increased triplen harmonic distortionElevated neutral conductor current
8
Our Research ObjectivesDevelop means for systematic analysis of NEV in distribution power systems including harmonic distortionDevelop procedures to predict NEV for planning and assessment, and to troubleshoot existing problemsAssess the effects of NEV mitigation techniques in an environment with harmonic distortion
5
9
Steps of This ProjectDevelop detailed power system models, including the nonlinear loads, for NEV analysis.Construct a multiphase harmonic load flow algorithm to calculate NEV.Test the algorithm accuracy by comparing with the actual field measurement.Examine the algorithm capabilities using a standard IEEE example system.Develop procedures for locating sources of elevated NEV and assess common methods in reducing NEV with nonlinear loads.
10
Single-Phase Distribution Feeder Modeling
Phase Conductor
Neutral
Parallel Ground Current
6
11Conventional Transmission Line Model (Carson’s Line)
( )41060935.1
/1065.8
..._2ln210386.0
...cos23
18
,,
4ln24
4ln24
−×=×=
++−=
+−=
=⎟⎟⎟
⎠
⎞
⎜⎜⎜
⎝
⎛+
⎟⎟⎟
⎠
⎞
⎜⎜⎜
⎝
⎛+=
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛+⎟
⎟⎠
⎞⎜⎜⎝
⎛++=
GfSk
ijkijQ
ijijkijPnaji
GijQijDijS
jGijPijZ
GiiQDii
iiSjGiiPiriiZ
ijij ρ
θπ
ωωω
ωωω
S Distance between conductors and the imagesD Distance between conductors⎥
⎦
⎤⎢⎣
⎡⎥⎦
⎤⎢⎣
⎡=⎥
⎦
⎤⎢⎣
⎡
−−
−−
n
a
gnngna
gangaa
nn
aa
II
ZZZZ
VV
'
'
12Practical Distribution Feeder with Non-zero Grounding Resistance
7
13
Equivalent PI ModelThe series impedance is the same as in Carson’s line
The shunt admittance matrix is obtained from the grounding resistance
[ ] ⎥⎦
⎤⎢⎣
⎡=
nnan
anaase ZZ
ZZZ
[ ]⎥⎥
⎦
⎤
⎢⎢
⎣
⎡=−
gRR 10
001
Zse
[R]-1 [R]-1 NEV2NEV1
14
Multiple Segments Assemblinga1
n1
g1
Za1
Zn1
Ia
In
Ig
Rg
a2
n2
g2
Za2
Zn2
a3
n3
g3
Ia
In
Ig
[ Y1 ] [ Y2 ]
Zan2 Zna2
Zng2
Zag2
Zan1 Zna1
Zng1
Zag1
Rg Rg
8
15
Equivalent PI ModelApply Kron reduction to Ybus to eliminate the nodes in the middle of the feederDerive the equivalent pi model from the resultant matrix
[ ] [ ][ ] [ ]⎥⎦
⎤⎢⎣
⎡=⎥⎦
⎤⎢⎣⎡
ABBAnew
busY
[ ] 1−−= BseZ
[ ]BAshY += [ ]BAshY +=
16
Step of This ProjectLinear modelingNonlinear modelingMultiphase harmonic load flowExamine algorithm capability using IEEE example systemTest algorithm accuracy by comparing with actual field measurementsAssess three-phasing method with harmonic distortion present
9
17Typical Non-Linear Loads in Distribution Systems
Three phase AC/DC converterSingle phase load with uncontrolled rectifier front endSingle phase induction motorFluorescent lighting
Amps4.2 8.3 12.5 16.6
-28.09
-14.04
0
14.04
28.09
18
Single Phase Rectifier
os
TsTth VddiLiRV ++=θ
ω
eq
oos R
VddVCi +=θ
ω
( ) ( ) thooo VV
ddV
dVd
323241412
2
ααααααθ
ααθ
=++++
( ) ( )θ
αααααααθ
ααθ d
dVViddi
did th
thsss
2423241412
2
+=++++
10
19Typical Waveforms of a Single Phase Rectifier
0 50 100 150 200 250 300 350 400- 600
- 400
- 200
0
200
400
600
Degr ee
Volt
s/Am
ps
Vo
V th
-Vth
Is
1θ 2θ
20
Step of This ProjectLinear modelingNonlinear modelingMultiphase harmonic load flowTest algorithm accuracy by comparing with actual field measurementExamine algorithm capability using IEEE example systemAssess three phasing method with harmonic distortion
11
21Multiphase Harmonic Load Flow for NEV Analysis
The nature of NEV problems demands a multiphase load flow solutionNEV problems are often more prevalent in radial distribution systemsSimple load flow program with robust convergence is desired
22
A Typical Radial Distribution TopologyRoot Node
Layer 11 2 3 4 5
6 7 8 9 10 11
12 13 14 15 16 17 18 19
20 21 22 23 24 25 2627 28
29 30 31 32 33 34 35
Layer 2
Layer 5
Layer 4
Layer 3
12
23Multiphase Load Flow Algorithm -Iterative Solution
Calculate the series impedance matrix for each branch and sum up the shunt admittance at every node except for the root nodeAssume the node voltages for initializationFind the nodal injection current using the node voltage in the previous iteration and determine the division between the neutral conductor and earth currentsBack sweep the system to find the branch current from the last layer by applying KCLForward sweep the system to find the voltage drop for each branch from the first layer and update the nodal voltageCheck convergence and start a new iteration if necessary
24
Steps of This ProjectLinear modelingNonlinear modelingMultiphase harmonic load flowTest algorithm accuracy by comparing with actual field measurementExamine algorithm capability using IEEE example systemAssess three phasing method with harmonic distortion
13
25Algorithm Verification Using Actual System Measurement
Three phase feeder with a single phase lateral (all conductor sizes are 336 kcmil)Transformer impedance: 7%Assume uniformly distributed loads after the measuring point and ignore any load before it
YG/Δ
26
Actual Measurement
Neutral
Phase
Meter ratios: Voltage (5000 V/div), Current (10 A/div)
14
27
Synchronized Measurement Waveforms
Phase voltage
Phase current
Neutral plus messenger current
0 50 100 150 200 250 300 350 400-15
-10
-5
0
5
10
15
Degree
Volta
ge (k
V) a
nd C
urre
nt (A
)
28
Synchronized Measurement Waveform
Phase voltage
Phase current
Neutral plus messenger current
0 50 100 150 200 250 300 350 400-15
-10
-5
0
5
10
15
Degree
Volta
ge (k
V) a
nd C
urre
nt (A
)
15
29
NEV Simulation
The measured current is injected half way from the measuring point due to the uniform load distributionThe calculated neutral current in the single phase lateral is compared with the measurement to check the modeling and algorithm accuracy
YG/Δ
30Waveform Comparison Using Simulation Results
Phase voltage
Phase current
Calculated neutral current
Measured neutral current
0 50 100 150 200 250 300 350 400-15
-10
-5
0
5
10
15
Degree
Volta
ge (k
V) a
nd C
urre
nt (A
)
Close match-up between measurement and calculation
16
31Comparison of Measurement and Simulation Results
Phase voltage
Phase current
Calculated neutral current
Measured neutral current
0 50 100 150 200 250 300 350 400-15
-10
-5
0
5
10
15
Degree
Volta
ge (k
V) a
nd C
urre
nt (A
)
Close match between measurement and calculation
32
Step of This ProjectLinear modelingNonlinear modelingMultiphase harmonic load flowTest algorithm accuracy by comparing with actual field measurementExamine algorithm capability using IEEE example systemAssess three phasing method with harmonic distortion
17
33Test on IEEE Example Distribution System
Black – Three phaseGreen – Two phaseRed – One phase
Load flow algorithms test system
Relative short feeder
High loading level
Various line configurations
Different load connections
34
Linear Loads on The System
8017000009Y
15117000003Δ
2203852203852203853Δ
00132230005Δ
00125170002Y
90120901201101608Y
kvarkWkvarkWkvarkW
Phase 3Phase 2Phase 1BusNo.
LoadType
18
35NEV Test with Linear Loads at Different Earth Resistivities
0
2
4
6
8
10
12
14
1 2 3 4 5 6 7 8 9
Bus Number
Neu
tral t
o Ea
rth V
olta
ge (r
ms
Volts
)
1000 Ω-m100 Ω-m10 Ω-m
36The Effect of Non-Linear Loads on NEV
Single-phase rectifier: 240V, 30kW with a 4200μF smoothing capacitor
Case 1: A single rectifier on a single-phase line at bus 3Case 2: Three balanced rectifiers on a three-phase line at bus 3 Case 3: Two identical rectifiers on two phases of a three-phase line at bus 3 to form an unbalanced load
Layer 1
Layer 2
Layer 3
Layer 4
Root
1
2 3 4
5 6 7 8
9
Nonlinear load bus
19
37NEV RMS Values with Different Nonlinear Load Combinations
0
5
10
15
20
25
30
35
1 2 3 4 5 6 7 8 9
Bus Number
Neu
tral t
o Ea
rth V
olta
ge (r
ms
volts
)
Linear load onlyCase 1Case 2Case 3
Case 2: Three identical single-phase rectifiers at bus 3
100 Ω-m ground resistance
38
Step of This ProjectLinear modelingNonlinear modelingMultiphase harmonic load flowTest algorithm accuracy by comparing with actual field measurementExamine algorithm capability using IEEE example systemAssess three phasing method with harmonic distortion
20
39
Three Phasing Single Phase Lateral
A common practice for distribution system upgradeSimulation setup
Three phasing the single phase lateralEvenly distribute the measured current among the three phasesInject the currents half way from the measuring point
YG/Δ
40Detailed Results of Harmonic Components
0.020.020.010.170.020.020.040.1715
1.0512.8TOT RMS
0.000.000.010.000.020.020.040.1913
0.000.000.010.000.020.020.030.1411
0.040.030.030.280.040.030.080.289
0.000.000.050.010.070.070.140.467
0.000.000.010.000.010.010.030.075
0.180.250.140.930.180.250.420.933
0.040.043.050.182.706.669.1512.741
IEInIphIEInIph
Current (A)NEV (V)
Current (A)NEV (V)
Three PhaseSingle PhaseHarmonic
Order
21
41Assessing The Effect of Three Phasing with Nonlinear Loads
Same system configurationThe linear loads are modeled in constant power mode with its value doubled: 120kW @ 0.9 pf laggingNonlinear load: single phase rectifier at 240V, 60kW with 6000 μF smoothing capacitors
YG/Δ
42Single Phase Lateral NEV Spectrum with nonlinear load
At each bus, the NEV spectrum include the following components:
Total RMSFund.3rd
5th
7th
9th
1 2 30
10
20
30
40
50
60
Bus number
Vol
tage
(V)
22
43NEV Spectrum with Nonlinear load After Three Phasing
At each bus, the NEV spectrum include the following component:
Total RMSFund.3rd
5th
7th
9th
1 2 30
5
10
15
20
25
30
35
40
Bus number
Vol
tage
(V)
44Detailed Results for Harmonic Components with Nonlinear Load
0.260.220.162.240.210.180.391.8315
3757.2RMSTOT
0.010.010.250.070.400.320.723.1813
0.010.010.310.050.390.320.712.9311
0.930.780.566.350.870.721.585.949
0.020.030.620.130.910.801.675.587
0.040.062.400.253.003.075.8416.685
7.199.865.4236.346.448.8614.5432.563
0.120.129.690.558.0920.0027.4438.211
IEInIphIEInIph
Current (A)NEV (V)
Current (A)NEV (V)
Three PhaseSingle PhaseHar-
monicOrder
23
45
ConclusionsCarson’s line model is adapted for NEV analysisA multiphase harmonic load flow algorithm is developed for NEV analysis in distribution systemsThe simple current injection method used in harmonic analysis achieves similar accuracy as the detailed nonlinear device modelIt is possible to approximately predict the NEV profile and help locate potential stray voltage problems Triplen harmonics elevates the NEV due to their additive nature in the neutralCommon methods for stray voltage mitigation, e.g. three phasing, may not be adequate when there is high harmonic distortion in the system
46
Future Research OpportunitiesMore field measurements to validate model.Improve models to incorporate more complex situationsImprove load flow program to handle large scale systemsBetter understand the human sensitivity to harmonic frequency voltages