ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all...

16
Brief Description / Applications • Suction Pressure Controller and/or High Pressure Controller, configurable for: - Standard Compressors - Compressors with CRII-System Control Stages - Condensation High Pressure Control • For up to 8 Suction Pressure Stages respective High Pressure Stages usable • For use as a single controller or in a network • Direct connection of up to 64 Cold Storage Controllers, Data Exchange for Energy Optimization • 4 Sensor-, 2 Pressure Transmitter- , 4 Digital Inputs, 5 Relay Outputs (2 Relays, 3 SSR-Relays), Analogue Output • Capable of handling up to 4 additional stages. (When used in conjunction with Expansion Module BMR 3002). • For Single- and Multi-Stage Loads Peak Load Limitation, Suction Pressure Shifting • Automatic Stage Sequencing Fixed or Autoadaptive Delay Times for Switching Frequency Optimization Capturing of Machine Feedback Signals and Plant Errors • Analogue Output for P/PI-Control In-/Outputs configurable Manual Operation of all Machines Night Operation via internal clock Please note Safety Instructions on page 10 ! Operating / Operating Elements ELEKTRONISCHE REGELUNGEN GMBH Actual Values Page Setpoint Page Suction Pressure increase values decrease values Attention The displayed setpoint is active Some functions may not be available on devices with older software versions. 1 2 3 4 ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate active control function(s). (Relay status is indicated separately on „Actual Page“). programming key LED blinking = Alarm The current states of the Digital Inputs, the Relay Outputs and the Data Transmission can be read on the Actual Values Page at L98 and L99. Programming The MSR eco parameters are simple to access, view and change. During normal operation, or if no key is pressed for at least 3 minutes, the MSR eco will display the following: 1st priority: current failure display (blinking) 2nd priority: operation status display (ex. „oFF“) 3rd priority: selected „permanent parameter“ display Selecting and Changing of Parameters Key Action P (> 2 sec.) ....Page name will be displayed .................Select desired page P ..................Enter the page .................Select parameter P ..................Prepare programming. Enter access code if necessary .................Change value. If you hold the key, the values change continuously P ..................Confirm programming P (> 2 sec.) ....Page name will be displayed again Access Protection All adjustable parameters/set-points are protected by an access code. They are divided into 3 groups or levels with 3 operator codes. An access code will be required to change an adjustable parameter, (see parameter listing).To change an adjustable parameter that requires an access code, begin by pressing the „P“ key.: The screen will display C00, prompting the user for access code entry. The Access Codes are divided into 3 access levels, (OEM, Technician, and Customer Codes). - OEM Code „oem“: Month + Hour + 20 The OEM Code grants access to all adjustable parameters on the device. - Technician Code „tec“ : 88 TheTechnician Code grants access only to „Technician“ and „Customer“ assigned adjustable parameters. - Customer Code „---“ : no access code required. The Customer Code grants access only to „Customer“ assigned adjustable parameters. If no key has been pressed for 3 minutes, the operator code must be re-entered. (00 Parameter Pages P (L) > 2 sec. P (r) (P) Mode Page (A) Address Page (h) Assign- ment Page L01 r01 P10 A01 h01 1st. Parameter on the P P P P (d) d01 P Setpoint Page High Pressure Technical Manual 5311437-03/02e/01 Stage Controller 2018-06-25, tkd/jr from Software Vers. 2.04 MSR eco 3140

Transcript of ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all...

Page 1: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

Brief Description / Applications• SuctionPressureControllerand/orHighPressureController, configurablefor: - StandardCompressors - CompressorswithCRII-SystemControlStages - CondensationHighPressureControl• Forupto8SuctionPressureStagesrespectiveHighPressureStagesusable• Foruseasasinglecontrollerorinanetwork• Directconnectionofupto64ColdStorageControllers, DataExchangeforEnergyOptimization• 4Sensor-,2PressureTransmitter-,4DigitalInputs, 5RelayOutputs(2Relays,3SSR-Relays),AnalogueOutput• Capableofhandlingupto4additionalstages. (WhenusedinconjunctionwithExpansionModuleBMR 3002).• ForSingle-andMulti-StageLoads• PeakLoadLimitation,SuctionPressureShifting• AutomaticStageSequencing• FixedorAutoadaptiveDelayTimesforSwitchingFrequencyOptimization• CapturingofMachineFeedbackSignalsandPlantErrors• AnalogueOutputforP/PI-Control• In-/Outputsconfigurable• ManualOperationofallMachines• NightOperationviainternalclock

Please note Safety Instructions on page 10 !

Operating / Operating Elements

ELEKTRONISCHE REGELUNGEN GMBH

ActualValuesPage

SetpointPageSuctionPressure

increasevalues

decreasevalues

Attention

Thedisplayedsetpointisactive

Somefunctionsmaynotbeavailableondeviceswitholdersoftwareversions.

1 2 3 4

EVP

ELREHA

P

Convenient3keycontrolforallfunctionsclearlyappearona7segmentLEDdisplay.4symbolstotherightindicateactivecontrolfunction(s).(Relaystatusisindicatedseparatelyon„ActualPage“).

programmingkey

LEDblinking=Alarm

ThecurrentstatesoftheDigitalInputs,theRelayOutputsandtheDataTransmissioncanbereadontheActualValuesPageatL98andL99.

ProgrammingTheMSR ecoparametersaresimpletoaccess,viewandchange.Duringnormaloperation,orifnokeyispressedforatleast3minutes,theMSR ecowilldisplaythefollowing:1stpriority: currentfailuredisplay(blinking)2ndpriority: operationstatusdisplay(ex.„oFF“)3rdpriority: selected„permanentparameter“display

Selecting and Changing of ParametersKey ActionP(>2sec.)....Pagenamewillbedisplayed.................SelectdesiredpageP ..................Enterthepage.................SelectparameterP ..................Prepareprogramming.Enteraccesscodeifnecessary.................Changevalue. Ifyouholdthekey,thevalueschangecontinuouslyP ..................ConfirmprogrammingP(>2sec.)....Pagenamewillbedisplayedagain

Access ProtectionAlladjustableparameters/set-pointsareprotectedbyanaccesscode.Theyaredividedinto3groupsorlevelswith3operatorcodes.Anaccesscodewillberequiredtochangeanadjustableparameter,(seeparameterlisting).Tochangeanadjustableparameterthatrequiresanaccesscode,beginbypressingthe„P“key.:

ThescreenwilldisplayC00,promptingtheuserforaccesscodeentry.

TheAccessCodesaredividedinto3accesslevels,(OEM,Technician,andCustomerCodes).- OEM Code „oem“:Month+Hour+20 TheOEMCodegrantsaccesstoalladjustableparametersonthe device.- Technician Code „tec“:88 TheTechnicianCodegrantsaccessonlyto„Technician“and„Customer“ assignedadjustableparameters.- Customer Code „---“:noaccesscoderequired. TheCustomerCodegrantsaccessonlyto„Customer“assigned adjustableparameters.Ifnokeyhasbeenpressedfor3minutes,theoperatorcodemustbere-entered.

(00

Parameter Pages

P

(L)

>2sec.

P

(r)

(P)ModePage

(A)AddressPage

(h)Assign-mentPage

L01

r01

P10

A01

h01

1st.Parameteronthe

P

P

P

P

(d)

d01PSetpointPageHighPressure

TechnicalManual 5311437-03/02e/01Stage Controller 2018-06-25,tkd/jr fromSoftwareVers.2.04

MSR eco 3140

Page 2: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140Page2

MSR ecoSystem Overview

Accessories

- TemperaturesensorTF501,quantitydependsonapplication- PressureTransmitterwith4...20mAOutput

Technical Data

SupplyVoltage.............................230V50-60Hz,max.9VA(controlleronly)AmbientTemperature.......................................................................0...+50°CMax.AirHumidity....................................................85%r.H.,notcondensingInputs.............................................. 4xTemperatureSensors,TF201(PTC) orTF501(Pt1000),orcustomerspecificprobes 2xPressureTransmitter4-20mADC(scalable),Ri=100OhmMeasuringranges TF501(Pt1000).................... -100°C...+100°Coftheprobeinputs TF201(PTC, 2 kΩ at 25°C)....... -50°C...+100°C So1......................................... -40°C...+25°C So2......................................... -50°C...+50°C

Temperature ranges of the sensor heads and cables must be observed !Accuracy ............................................................. ±0.5Kinrange-35..+25°C withintheambienttemperaturerange10..30°CDigitalInputs......................................................4xmainsvoltage,3mAmax. overvoltagecategoryII,pollutiondegree2RelayOutputs.....................................................1xSPDT,1xSPST,isolated 8Acosphi=1/250VAC overvoltagecategoryIII,pollutiondegree2

SSR-Output(e.g.forEEx-Valve)....................... 3xSolid-State-Relay(SSR) max.0,5A/230VAC overvoltagecategoryIII,pollutiondegree2TransmitterSupply.............................................22VDC±10%,40mAmax.AnalogueOutput..........................................0...10Vor4...20mA(selectable) 0...10VDC,max.currenttyp.1mA 4...20mA,max.shuntresistance500ohmsDisplay/ParameterRanges.......................................... seeparameterpagesDataInterfaces...............................................................................3xRS485DataStorage......................................................................................unlimitedRealTimeClock.........................................automaticsummer/winterswitch, 10daysclockbackupwithoutmainsvoltageHousing................plasticwithfoilkeypadforrailmounting(DINEN50022), screwterminals2,5mm²

compound(4stages)

MSReco3140

RS-

485

RS-485(Line)

ColdStorageController

Controller

SMZ5140

2xPressure Transmitters4xTemperatureSensors

DataManagementwith'CV-Scheduler'locally

Controller Controller

Upto64ColdStorages,connectedviaRS-485line

AnyReceiver:e.g.ServiceTechnician

ErrorMessagesasEmail

Browser/BrowserInternetExplorer,Firefox,etc.

Inte

rnet

AlternativeWeb-Gateway

phon

e

PC

PCPCwithBrowser

(+4stages)

BMR3002

NetworkingExamples

Analog-Modem

ErrorMessagesasEmail

TheMSRecoisdesignedtoprovidecompletecontrolforrefrigerationsystemswithupto4respective8stages,whileservingasacentralunitforupto64coldstoragecontrollers.WhenusedinconjunctionwithfrontenddevicessuchastheSMZ-5140orWeb-Gateway,theMSRecobecomesfullycapableofcontrolfromaremotelocation,aswellasmessagecommunication,(seeexamplebelow):

ColdStorageController

ColdStorageController

ColdStorageController

ColdStorageController

ColdStorageController

Page 3: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140 Page3

Error Messages / Error Memory / Error Codes

Ifafailureoccurs,parameterL20willdisplayaflashingerrorcode,(seebelowErrorCodeDefinitionListforreference).Ifmultipleerrorsoccur,theUP/DOWNarrowkeyscanbeusedtoscrollthroughtheerrorcodesonthedevicedisplay.Thedeviceisdesignedtoalwaysstorethelast15errormessages,(includingdateandtimeofeachoccurrence),andcanbeaccessedviadatainterface.----........noerrorhrd......hardwarefailureAdr......networkaddressassignedmorethanonceA00.......communicationerrorwithcontrollerataddress0 up toA63.......communicationerrorwithcontrollerataddress63Fb1......feedbacksignalformotor1notavailable up toFb4.......feedbacksignalformotor4notavailabletxb........sensorXbroken(pressuretransmitterinputs:nocurrentavailable)txc.......sensorXhot-wired(pressuretransmitterinput:20mAexceeded)PPA.......prewarningofsuctionpressurePXA.......prewarningofhighpressurePA.........suctionpressurefailureXA.........highpressurefailureEPA......externalsuctionpressurealarmEXA......externalhighpressurealarmsuP......superheatwarningsua......superheatalarms0f......coldstoragepositionssoftwareversionbnr......communicationfailurewithBMR3002cpd.......compoundassignmentofthecoldstoragepositiontyp.......wrongcoldstoragecontrollertypesel......errorinassignmentpage(Overviewlistingofthepossiblefailuresseepage10)Int......internalfailureAdditionally,intheActualValueListingcurrentfailurescanberead-likeMotorfailure(L22),SuctionPressurefailure(L23),Suctionpressurepre-alarm(L24).Highpressurefailure(L61)andHighpressurepre-alarm(L62).

Display of actual values and states

Allactualvaluesareshownonthe"Actual Values Page"((l)).

Display of Temperatures and Pressures"L01"-"L04":„ActualValuesPage“Displaysactualcurrenttemperatureforsensors1-4(-99.9...+100C)."L05":DisplaysactualcurrenttemperatureconvertedfromPressureTransmitter1input."L06":DisplaysactualcurrenttemperatureconvertedfromPressureTransmitter2andtheselectedrefrigerant"h99"."L15"&"L16":Displaystheactualcurrentpressurevalue."L10":Displaystheactualvalue"SP/HPCurrent".With"P31"-"P36"(ModePage)thedisplays'L01'-'L06'canbecalibrated."L93":DisplayscurrentDayorNightModestatus.SetpointsForallsetpoints,whichareshiftedbyspecificfunc-tions,thecurrentvalueswillbedisplayedatL30...L32 andL63...L65.Current state of stage control (L21)

Controllerinforerunmode.Thecenterbarmovesup

Neutral

Controllerinbackrunmode.Thecenterbarmovesdown

Time informationTheActualValuespagecontainsall theruntime/remainingtimeinformation.Thiscanbeviewedatanytime,uptothestartofafunction.State of Stages / Running Motors "L14"-"L48":DisplayshowmanySPstagesarecurrentlyswitchedon."L51"-"L58":DisplaysthecurrentSPstagestatus."L71"-"L78":DisplayshowmanyHPstagesarecurrentlyswitchedon."L81"-"L88":DisplaystheHPstagestatus."L36"-"L37":DisplaysactiveLoadLimitationorForcedBackrunstatus.State of inputs/outputsDigital-(DI)-Inputs(L97) Stateoftherelays(L99)

Display of the running SP and HP stages (L94andL95)

StateoftherelaysatthemoduleBMR(L98)AnalogueOutput:ParameterL96,valuein%

Temperature SensorsThesetypesoftemperaturesensorscanbeused:-TF 201,PTCsensor(2000ohms@25°C)-TF 501,PT1000sensor(1000ohms@0°C)-customerspecificsensorSo1(-40...+25°C)-customerspecificsensorSo2(-50...+50°C)Thetypeofsensorcanbesetby'h20'(AssignmentPage).

Pressure Transmitter Pressure Transmitters with 4...20mA output canbeused.Theymustbeselectedwiththeparameters"h25-h26"(AssignmentPage).

'Default Display Parameter' - Function

Whenthedeviceispoweredup,the"DefaultDisplayParameter"willappearonthedisplayafterafewseconds.(Thiswillalsobedisplayedduringnormaloperationofthesystemorifnokeyispressedforatleast3minutes)"L10":ActualValue is factorypresetandcanbechangedatanytime.Note:Intheeventofafailure,1stPrioritywillbetodisplaythecurrentfailure.

Configuration Concept

Theinputs/outputsoftheMSRecoStageControllerhavenofixedfunctions.TheMSRecoworkswithan"open configuration"concept.Thismeansthatallavailableinputsandoutputs(relays, sensors, digital inputs, analogue output)canbeconfiguredtoworkwithanyavailablecontrolfunctionorcontrolcircuit.Temperature SensorsSensorscanbeusedtocontrol,orsimplytodisplay.Digital inputs (DI, Optocoupler inputs)Each digital input can be assigned to one of thepossiblefunctions.Relay OutputsEachrelaycanbeusedtocontroloneofthepossiblefunctionsandcanalsobeswitchedonmanually.

The relay outputs #2, #3 and #5 are Solid State Relays (SSR) with a lower contact rating than the standard relay outputs. They can be used for any function within the specified current range.

ParameterOnlyassignedparameterswillappearontheparameterpageforscrollingefficiency.

AssignmentThefunctionofeachinputandoutputcanbepresetonthe'assignmentpage'.Theassignmentcanbedonebykeysorviainterface.

Notice

Changepermanentparameter

- Selecttheparameteryouwanttohaveas "defaultdisplayparameter"- Press""and""simultaneously. Thedisplayshows"888"foramoment,after thattheselectedparameterwillbeshownas the'defaultdisplayparameter'.

Relays

ON

OFF

DI 43

230V

0V

21 1 2 3 4 5

2468

1357

Configuration parameter setsTheMSReco includes twopredefinedconfigura-tions,whichcanbeloaded.Overmoretheusercansaveandrecallanotherindividualsetofconfigurati-onparameters,the‚userdefinedconfiguration‘.It isonlyavailable if itwassavedbeforeby ‚h90‘(AssignmentPage),whichsavesallcurrentsettingstothe‚userdefinedconfiguration‘.Todothis,theOEM-Codeisnecessary.Sequence: - Select'h90'- PresstheP-key- '---'appears- PresstheUP-keyandentertheOEM-code- Select'do'withtheUP-key- SavetheparameterbyclickingtheP-key- 'don'foractionexecutedrespective'Err'foraction notexecutedwillbedisplayedforabout2seconds.Ifanoverwriteoftheexistingconfigurationisnotdesired,thentheoperationcanbeabortedbeforepressingthe„P“key.Whenthedisplayshows„do“,pressthe„Down“keyagainand„---“willbeshownonthedisplay.Nowpressthe„P“key.„h90“willappearonthedisplay.Inordertorestoreasaveduserconfiguration,thiscanbeachievedbyselecting„h91“andenteringcode„70“.„h91“canalsobeusedtoloadthevaluesfromthe„permanentpresetconfiguration“.Ifnoconfigurationwaspreviouslysaved,then„h91“cannotbeselected.Behaviour of the User Configurations at Program Updates:Afterupdates,ifanOEMconfigurationisavailable,itispossibletoloadallparameterswhicharestoredintherespectiveprogramversion.Newparameterswillbesettodefaultvalues. Withprogramdowngrades/updatesin incombinationwithOEMconfigurations saving/loading,parametersintheuser configurationmaybelost.

Page 4: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140Page4

Parameter Pages

Relay

ON

OFF

1 2 3 4 5

Relay

ON

OFF

1 2 3 4 5DI 43

230V

0V

21

Actual Values Page (L)

Param nA Eb Note rangeL01.........X.....3,2...Actualtemperaturevalueofsensor1................................................................................................-99,9...+100,0°Cupto.........................(canbecorrected±10K,thefunctionisdefinedintheAssignmentPage)L04.........X.....3,2...Actualtemperaturevalueofsensor4....................................................................................... -99,9...+100,0°CL05.........X.....3,2...Actualtemperaturevalueofinput5(calculatedfromL15,pressuretransmitter1)................ -99,9...+100,0°CL06.........X.....3,2...Actualtemperaturevalueofinput6(calculatedfromL16,pressuretransmitter2)................ -99,9...+100,0°CL10.........X... 3,2,1..ActualvalueSP/HP,poss.alternatingdisplay,coolingsymbolSP,fansymbolHP.............. -99,9...+100,0°CL15.........X... 3,2,1..ActualvalueofPressureTransmitter1(4/20mA).TemperatureL05iscalculatedfromthis..... -1,0...+160,0barL16.........X... 3,2,1..ActualvalueofPressureTransmitter2(4/20mA).TemperatureL06iscalculatedfromthis..... -1,0...+160,0barL20.........X... 3,2,1..CurrentFailure.......................................................................................................................... Suction Pressure Actual ValuesL21.........X... 3,2,1..Currentstateofthestagecontrol(SP)..................................................................................... Forw.,Backrun,Neutral(descr.page3)L22.........X... 3,2,1..MotorFailure............................................................................................................................. 0:o.k.,1:unitfaulty, 2:>50%faulty,3:allfaultyL23.........X... 3,2,1..Suctionpressurefailure............................................................................................................ 0:o.k.,1:failureL24.........X... 3,2,1..Suctionpressurepre-alarm...................................................................................................... 0:o.k.,1:pre-alarmL25.........X.....3,2...RemainingTimeSuperheatCompoundLock.......................................................................... secondsL26.........X.....3,2...RemainingTimeSuperheatWarning....................................................................................... secondsL27.........X.....3,2...SuctionPressureActualSuperheatValue............................................................................... inKL30.........X... 3,2,1..CurrentSetpoint........................................................................................................................ in°CL31.........X......3,2..Currentcumulatedoffset........................................................................................................... inKL32.........X......3,2..Currentsuctionpressureshiftoffset......................................................................................... inKL33.........X....3,2,1.Remainingforerun/backrundelaytime.................................................................................... secondsL34.........X....3,2,1.Remainingforerun/backruntimecalculated(VBR)................................................................. secondsL35.........X....3,2,1.Remainingsteadystatetime.................................................................................................... minutesL36.........X.....3,2...Currentloadlimitation(motors)................................................................................................ 0...8motorsL37.........X....3,2,1.Currentforcedbackrunstate.................................................................................................... 0=no,1=forcedbackrunL38.........X.....3,2...Remainingsteadystatetimeofmotor1(CRII)........................................................................ 0...900sec.L39.........X.....3,2...Remainingtimeouttimeofmotor1(CRII)................................................................................ 0...900sec.L41.........X... 3,2,1..Numberofrunningstagesofmotor1(SP).............................................................................. 0....8stagesL42.........X... 3,2,1..Numberofrunningstagesofmotor2(SP).............................................................................. 0....8stagesL43.........X... 3,2,1..Numberofrunningstagesofmotor3(SP).............................................................................. 0....8stagesL44.........X... 3,2,1..Numberofrunningstagesofmotor4(SP).............................................................................. 0....8stagesL45.........X... 3,2,1..Numberofrunningstagesofmotor5(SP).............................................................................. 0....8stagesL46.........X... 3,2,1..Numberofrunningstagesofmotor6(SP).............................................................................. 0....8stagesL47.........X... 3,2,1..Numberofrunningstagesofmotor7(SP).............................................................................. 0....8stagesL48.........X... 3,2,1..Numberofrunningstagesofmotor8(SP).............................................................................. 0....8stagesL51.........X.....3,2...Stateofstage1(SP)................................................................................................................. 0=notavailable 1=autom.off,2=manuallyoff 3=autom.onwithoutfeedbacksignal 4=autom.onwithfeedbacksignal 5=manuallyon,6=failurestatesetL52.........X.....3,2...Stateofstage2(SP)................................................................................................................. ditto.bisL58.........X.....3,2...Stateofstage8(SP)................................................................................................................. ditto. High Pressure Actual ValuesL60.........X... 3,2,1..Currentstateofthestagecontrol(HP)..................................................................................... Forw.,Backrun,Neutral(descr.page3)L61.........X... 3,2,1..Highpressurefailure(HP)....................................................................................................... 0:o.k.,1:failureL62.........X.....3,2...Highpressurepre-alarm(HP)................................................................................................... 0:o.k.,1:pre-alarmL63.........X... 3,2,1..CurrentSwitch-offpoint(HP).................................................................................................... in°CL64.........X... 3,2,1..CurrentSwitch-onpoint(HP).................................................................................................... in°CL65.........X... 3,2,1..CurrentOffset(HP)................................................................................................................... inKL66.........X.....3,2...Remainingforerun/backrundelaytime(HP)............................................................................ secondsL71.........X.....3,2...Numberofrunningstagesofmotor1(HP).............................................................................. 0....8stagesL72.........X.....3,2...Numberofrunningstagesofmotor2(HP).............................................................................. 0....8stagesL73.........X.....3,2...Numberofrunningstagesofmotor3(HP).............................................................................. 0....8stagesL74.........X.....3,2...Numberofrunningstagesofmotor4(HP).............................................................................. 0....8stagesL75.........X.....3,2...Numberofrunningstagesofmotor5(HP).............................................................................. 0....8stagesL76.........X.....3,2...Numberofrunningstagesofmotor6(HP).............................................................................. 0....8stagesL77.........X.....3,2...Numberofrunningstagesofmotor7(HP).............................................................................. 0....8stagesL78.........X.....3,2...Numberofrunningstagesofmotor8(HP).............................................................................. 0....8stagesL81.........X.....3,2...Stateofstage1(HP)................................................................................................................. 0=notavailable 1=autom.off,2=manuallyoff 4=autom.on 5=manuallyon,6=failurestatesetL82.........X.....3,2...Stateofstage2(HP)................................................................................................................. ditto.bisL88.........X.... 3,2....Stateofstage8(HP)................................................................................................................. ditto.

L93.........X... 3,2,1..Stateoftheday/nightswitching................................................................................................nit(night),dA4(day)L94.........X... 3,2,1..DisplayoftherunningSPstages.............................................................................................

L95.........X... 3,2,1..DisplayoftherunningHPstages.............................................................................................

L96.........X... 3,2,1..Currentvalueoftheanalogueoutput....................................................................................... 0-100%L97.........X... 3,2,1..CurrentstatusofthedigitalinputsDI1uptoDI4...................................................................

L98.........X... 3,2,1..CurrentstatusoftherelaysoftheauxiliaryBMRmodule.......................................................

L99.........X... 3,2,1..Currentstatusoftherelays1-5................................................................................................

DI 43

230V

0V

21

2468

1357

2468

1357

Hinweis

Parametersmarkedwith"nA"areforinformationonlyandcannotbechanged.

Page 5: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140 Page5

Hinweis

Parametersmarkedby"nA"areforinformationonlyandcannotbechanged."Co"isthepassword/codeforthisparameter.The3codenumbersare:- OEM-Code(oem):Month+Hour+20- TechnicianCode(tec):88- CustomerCode(---):withoutcode

Address Page (A)Param SubPar. Co Level Note Range Cf1 Cf2 Cf3 Cf4A00 .................tec.....3,2........Addressofthe1st.connectedcontroller d01..........tec.....3,2.........Typeoftheconnectedcontroller.......................---=nocontroller..... ---.......... ---.......... ---............... --- connected E30=EVP1130 E40=EVP1140 E50=EVP3150 E60=EVP3160 E67=EVP3167 E68=EVP3168 E70=EVP3170 t30=TKP3130 t40=TKP3140 t50=TKP3150 d02..........tec.....3,2..........Theconnectedcontrolleractsonthe.............. 0=noeffect...............0................ 0................. 0...................0 suctionpressureshiftingwith: 1=limit.temperature 2=limit.temperature +openingpercentage d03..........tec.....3,2.........SuctionPressureShift-TemperatureOffset..... 0...20K......................1.0K......... 1.0K.......... 1.0K............1.0K

A01..........................tec.....3,2..........Addressofthe2ndconnectedcontroller d01..........tec.....3,2..........Typeoftheconnectedcontroller....................... seeabove d02..........tec.....3,2..........Theconnectedcontrolleractsonthe suctionpressureshifting................................... seeabove d03..........tec.....3,2..........SuctionPressureShift-TemperatureOffset.... seeaboveupto

A63..........................tec.....3,2.........Addressofthe64thconnectedcontroller d01..........tec.....3,2.........Typeoftheconnectedcontroller....................... seeabove d02..........tec.....3,2.........Theconnectedcontrolleractsonthe suctionpressureshifting................................... seeabove d03..........tec.....3,2.........SuctionPressureShift-TemperatureOffset.... seeabove

Mode Page (P)Param Co Level Note Range Cf1 Cf2 Cf3 Cf4P10.......oem...3,2........ Warnthresholdminimalsuperheat.......................................1,0...25,0K................5,0K.........5,0K........... 5,0K...........5,0KP11.......oem...3,2........ Warnhysteresissuperheat....................................................1,0...25,0K................1,0K.........1,0K........... 1,0K...........1,0KP12.......oem...3,2........ Warndelaysuperheat............................................................0...900sec.................5Sek........5Sek........... 5Sek..........5SekP13.......oem...3,2........ Superheatwarninglockscoldstoragecontrollers................0=no,1=yes...........1...............1.................. 1..................1P14.......oem...3,2........ Compoundlockthresholdminimalsuperheat.....................0,0...25,0K................0,0K.........0,0K........... 0,0K...........0,0K (0,0K=switchedoff)P15.......oem...3,2........ Compoundlockdelayminimalsuperheat.............................5...900sec.................5sec.........5sec........... 5sec...........5secP20.......oem...3,2........ Sendingdateandtimetoconnectedcoldstorage.............on,oFF......................oFF...........oFF............. oFF.............oFF controllersP21.......tec......3,2,1.... NightOperationModeONat.................................................0...23.5(0),oFF..........oFF...........oFF............. oFF.............oFFP22.......tec......3,2,1.... NightOperationModeOFFat...............................................0...23.5(0),oFF..........oFF...........oFF............. oFF.............oFF

P31.......oem...3,2........ Calibrationofsensorinput1..................................................±10.0Kadjustable.....0.0K.........0.0K........... 0.0K...........0.0KP32.......oem...3,2........ Calibrationofsensorinput2..................................................±10.0Kadjustable....0.0K.........0.0K........... 0.0K...........0.0KP33.......oem...3,2........ Calibrationofsensorinput3..................................................±10.0Kadjustable....0.0K.........0.0K........... 0.0K...........0.0KP34.......oem...3,2........ Calibrationofsensorinput4..................................................±10.0Kadjustable....0.0K.........0.0K........... 0.0K...........0.0KP35.......oem...3,2........ Calibrationofsensorinput5..................................................±10.0Kadjustable....0.0K.........0.0K........... 0.0K...........0.0KP36.......oem...3,2........ Calibrationofsensorinput6..................................................±10.0Kadjustable....0.0K.........0.0K........... 0.0K...........0.0KP69.......X........3,2........ SummertimeState.................................................................0=winter,.................--............... --.................. --.................-- 1=summerP70.......tec......3,2........ Modeofsummer/winterswitch..............................................oFF =off,..................EU.............oFF.............. oFF..............oFF EU =on, tVn =variabelP71........tec......3,2........ TimeZoneOffset.................................................................. -720...720min............60min......60min......... 60min.........60min.P72........tec......3,2........ SummerONMonth........................... (onlyfortVn)............ 1...12...........................3...............3.................. 3..................3P73........tec......3,2........ SummerONDay............................... (onlyfortVn)............ 0(Sunday)...6.............0...............0.................. 0..................0P74........tec......3,2........ SummerONx-Day............................ (onlyfortVn)............ 0...5(last),0=off..........5...............5.................. 5..................5P75........tec......3,2........ SummerONHour.............................. (onlyfortVn)............ 0...23...........................2...............2.................. 2..................2P76........tec......3,2........ SummerOFFMonth.......................... (onlyfortVn)............ 1...12...........................10.............10................ 10..............10P77........tec......3,2........ SummerOFFDay............................. (onlyfortVn)............ 0(Sunday)...6..............0...............0.................. 0..................0P78........tec......3,2........ SummerOFFx-Day.......................... (onlyfortVn)............ 0...5(last),0=off..........5...............5.................. 5..................5P79........tec......3,2........ SummerOFFHour............................ (onlyfortVn)............ 0...23...........................3...............3.................. 3..................3P80, P81...........3,2,1.... Year,Month........................................................................... adjustableP82, P83...........3,2,1.... Day,Hour............................................................................. adjustableP84, P85...........3,2,1.... Minute,Secund..................................................................... adjustableP86...................3,2,1.... SoftwareversionBMRP87...................3,2,1.... SoftwareversionP89........oem...3,2........ Datatransmissionspeed(baudrate).................................... 12(00)...115(00)..........96(00).......96(00)......... 96(00).........96(00)P90........oem...3,2........ AddressoftheMSRecounitinanetwork.............................0-78.........................78.............78................ 78................78P99...................3,2,1.... OperatingLevel/Accessauthorization..................................88:Level2...............0...............0.................. 0..................0 70:Level3

Page 6: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140Page6

Param Co Level Note Range Cf1 Cf2 Cf3 Cf4r01...... ---.......3,2,1...... Setpoint1(day)....................................................................-99,9...+100,0°C.......-10,0°C.....-10,0°C....... -10,0°C........-10,0°Cr02...... ---.......3,2,1...... Setpoint2(night)..................................................................-99,9...+100,0°C.......-10,0°C......-10,0°C....... -10,0°C........-10,0°Cr03...... ---.......3,2,1...... Setpointmaximum................................................................-99,9...+100,0°C.......0,0°C.........10,0°C........ 10,0°C.........10,0°Cr04...... ---.......3,2,1...... Hysteresis..............................................................................0,1...20,0K.................2.0K..........2.0K........... 2.0K............2.0Kr05......oem....3,2.......... HysteresisPosition...............................................................H--=symmetrical.....H--.............H--.............. H--................H-- H--=belowthe setpoint H--=abovethe setpointr06......oem....3,2.......... Alarmlimit..............................................................................-99,9...+100,0°C.......-20,0°C...... -99,9°C.......-99,9°C........-99,9°Cr07......oem....3,2.......... Pre-alarmlimit......................................................................-99,9...+100,0°C.......-18,0°C...... -99,9°C.......-99,9°C........-99,9°Cr08......oem....3,2.......... Pre-alarmdelay.....................................................................1...600sec................10sec........600sec.......600sec.......600secr11......oem....3,2.......... LoadLimitation1(max.runningmotors).............................0...8motors...............8................8..................8..................8r12......oem....3,2.......... LoadLimitation2(max.runningmotors).............................0...8motors...............8................8..................8..................8r13......oem....3,2.......... PIanalogueoutputproportionalband/range.......................0.1...30.0K................5.0K..........5.0K...........5.0K............5.0Kr14......oem....3,2.......... PIanalogueoutputintegraltime...........................................0...600sec...............60sec........60sec.........60sec.........60secr15......oem....3,2.......... PIanalogueoutputoutputdelay...........................................0...100sec................20sec........20sec.........20sec.........20secr16......oem....3,2.......... PIanalogueoutputstepsize................................................1...100%....................10%...........10%.............10%.............10%r17......oem....3,2.......... SuctionpressureshiftingEEx-Valvepercentage ofopeninglowerlimit(ofconnectedcontrollers)....................0...100%....................20%...........20%.............20%.............20%r18......oem....3,2.......... SuctionpressureshiftingEEx-Valvepercentage ofopeningupperlimit(ofconnectedcontrollers)....................0...100%....................80%...........80%.............80%.............80%r19......oem....3,2.......... Suctionpressureshiftingstepwidth..................................... 0...20,0K....................1,0K...........1,0K............1,0K.............1,0K (ofconnectedcontrollers)r20......oem....3,2.......... Stagecontroller-Steadystatetime.....................................10...540min...............540min......540min....... 540min.......540min.r21......oem....3,2.......... Stagecontroller-Operational-FeedbackTime....................5...600sec.................30sec........30sec......... 30sec.........30sec.r22......oem....3,2.......... Stagecontroller-BaseLoadChange(StageSequencing)..000=off/off/off.........hr1.............hr1...............hr1...............hr1 ....a..../....b..../....c.... Atpositiona,thesebaseloadfunctionscanbeset: rr0=runt./runt./off 0=off,r=forerundep.onruntime,h=for.dep.onstoptime hr0=stopt./runt./off Atpositionb,thesebaseloadfunctioncanbeset: rr1=runt./runt./on 0=off,r=backrundep.onruntime, hr1=stopt./runt./on Atpositionc,thesebaseloadfunctionscanbeset: Switchoptimization:0=off,1=onr23......oem....3,2.......... IdleTimeofthestagewith0%load.....................................0...900sec................5sec.......... 5sec........... 5sec...........5sec.r24......oem....3,2.......... Timeoutof0%control.Ifnopowerstageisactivated, themotorswitchesoffafter:..................................................0...900sec...............120sec. 120sec....... 120sec.......120sec.r25......oem....3,2.......... Variableforerun-/backrundelays.........................................on,oFF......................oFF............ oFF............. oFF.............oFF (VBR,SwitchingFrequencyOptimization)r26......oem....3,2.......... VBRForerunRange.............................................................0,5...20,0K................0,5K.......... 0,5K........... 0,5K...........0,5Kr27......oem....3,2.......... VBRBackrunRange............................................................0,5...20,0K................0,5K.......... 0,5K........... 0,5K...........0,5Kr28......oem....3,2.......... VBRForerun/BackrunRangeTimemin..............................1...900sec................1sec.......... 1sec........... 1sec...........1sec.r29......oem....3,2.......... VBRForerun/BackrunRangeTimemax.............................1...900sec................20sec........ 20sec......... 20sec.........20sec.

r41...... ---.......3,2,1...... ForerunDelayTimestage1(thefirstturnonstage)...........0...900sec.................10sec........ 10sec..........10sec.........10sec.r42...... ---.......3,2,1...... ForerunDelayTimestage2.................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r43...... ---.......3,2,1...... ForerunDelayTimestage3.................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r44...... ---.......3,2,1...... ForerunDelayTimestage4.................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r45...... ---.......3,2,1...... ForerunDelayTimestage5.................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r46...... ---.......3,2,1...... ForerunDelayTimestage6.................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r47...... ---.......3,2,1...... ForerunDelayTimestage7.................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r48...... ---.......3,2,1...... ForerunDelayTimestage8.................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.

r51...... ---.......3,2,1...... BackrunDelayTimestage1(thelastoffstage)..................0...900sec.................10sec........ 10sec..........10sec.........10sec.r52...... ---.......3,2,1...... BackrunDelayTimestage2................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r53...... ---.......3,2,1...... BackrunDelayTimestage3................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r54...... ---.......3,2,1...... BackrunDelayTimestage4................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r55...... ---.......3,2,1...... BackrunDelayTimestage5................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r56...... ---.......3,2,1...... BackrunDelayTimestage6................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r57...... ---.......3,2,1...... BackrunDelayTimestage7................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.r58...... ---.......3,2,1...... BackrunDelayTimestage8................................................0...900sec.................10sec........ 10sec..........10sec.........10sec.

r61.......oem...3,2...........Motor1automatic/manually...............................................oFF,Aut(autom.)......Aut...............Aut.................Aut.............Aut on(permanenton)r62.......oem...3,2...........Motor2automatic/manually...............................................ditto.............................Aut...............Aut.................Aut.............Autr63.......oem...3,2...........Motor3automatic/manually...............................................ditto.............................Aut...............Aut.................Aut.............Autr64.......oem...3,2...........Motor4automatic/manually...............................................ditto.............................Aut...............Aut.................Aut.............Autr65.......oem...3,2...........Motor5automatic/manually...............................................ditto.............................Aut...............Aut.................Aut.............Autr66.......oem...3,2...........Motor6automatic/manually...............................................ditto.............................Aut...............Aut.................Aut.............Autr67.......oem...3,2...........Motor7automatic/manually...............................................ditto.............................Aut...............Aut.................Aut.............Autr68.......oem...3,2...........Motor8automatic/manually...............................................ditto.............................Aut...............Aut.................Aut.............Aut

r71.......---.......3,2,1.......MinimumIdleTimeMotor1..................................................0...20min..................0min..........0min............0min.........0min.r72.......---.......3,2,1.......MinimumIdleTimeMotor2..................................................0...20min..................0min..........0min............0min.........0min.r73.......---.......3,2,1.......MinimumIdleTimeMotor3..................................................0...20min..................0min..........0min............0min.........0min.r74.......---.......3,2,1.......MinimumIdleTimeMotor4..................................................0...20min..................0min..........0min............0min.........0min.r75.......---.......3,2,1.......MinimumIdleTimeMotor5..................................................0...20min..................0min..........0min............0min.........0min.r76.......---.......3,2,1.......MinimumIdleTimeMotor6..................................................0...20min..................0min..........0min............0min.........0min.r77.......---.......3,2,1.......MinimumIdleTimeMotor7..................................................0...20min..................0min..........0min............0min.........0min.r78.......---.......3,2,1.......MinimumIdleTimeMotor8..................................................0...20min..................0min..........0min............0min.........0min.

Setpoint Page Suction Pressure (r)

Notice

IfthispointisONwhiledisplayingaparameternumber,thisparameterisactiveatpresent.

Hinweis

Parametersmarkedby"nA"areforinformationonlyandcannotbechanged."Co"isthepassword/codeforthisparameter.The3codenumbersare:- OEM-Code(oem):Month+Hour+20- TechnicianCode(tec):88- CustomerCode(---):withoutcode

Page 7: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140 Page7

Param Co Level Note Range Cf1 Cf2 Cf3 Cf4d01...... ---.......3,2,1..... Setpointofthefirststagetoswitchonrespective............... -99,9...+100,0°C....... 35,0°C.......35,0°C.........35,0°C..........35,0°C thelaststagetoswitchoffd02...... ---.......3,2,1..... Setpoint2............................................................................ -99,9...+100,0°C....... 35,0°C.......35,0°C.........35,0°C..........35,0°Cd03...... ---.......3,2,1..... Setpoint3............................................................................ -99,9...+100,0°C....... 35,0°C.......35,0°C.........35,0°C..........35,0°Cd04...... ---.......3,2,1..... Setpoint4............................................................................ -99,9...+100,0°C....... 35,0°C.......35,0°C.........35,0°C..........35,0°Cd05...... ---.......3,2,1..... Setpoint5............................................................................ -99,9...+100,0°C....... 35,0°C.......35,0°C.........35,0°C..........35,0°Cd06...... ---.......3,2,1..... Setpoint6............................................................................ -99,9...+100,0°C....... 35,0°C.......35,0°C.........35,0°C..........35,0°Cd07...... ---.......3,2,1..... Setpoint7............................................................................ -99,9...+100,0°C....... 35,0°C.......35,0°C.........35,0°C..........35,0°Cd08...... ---.......3,2,1..... Setpoint8............................................................................ -99,9...+100,0°C....... 35,0°C.......35,0°C.........35,0°C..........35,0°Cd10...... ---.......3,2,1..... NightOffset......................................................................... -20,0...+20,0K......... 0,0K.........0,0K...........0,0K.............0,0Kd11......oem....3,2......... NightLimitation................................................................... 0...100%................... 100%........100%.........100%............100%d12...... ---.......3,2,1..... Hysteresis............................................................................. 0,1...20,0K............... 2.0K.........2.0K...........2.0K.............2.0Kd13......oem....3,2......... HysteresisPosition.............................................................. H--=symmetrical.....H--.............H--...............H--................H-- H--=belowthe setpoint H--=abovethe setpointd14......oem....3,2......... Setpointshiftingviaoutdoortemperature,...........................0,0...+60,0°C............ 0,0°C.........0,0°C...........0,0°C............0,0°C lowertemperaturethresholdd15......oem....3,2......... Setpointshiftingviaoutdoortemperature,.......................... 0,0...20,0K............... 0,0K.........0,0K...........0,0K.............0,0K temperatureranged16......oem....3,2......... Setpointshiftingviaoutdoortemperature,factor................ -5,0...+5,0K/K.......... 0,0K/K......0,0K/K........0,0K/K.........0,0K/Kd17......oem....3,2......... Highpressurealarmlimit..................................................... -99,0...+100,0........... 42,0°C.......100,0°C.......100,0°C........100,0°Cd18......oem....3,2......... Highpressureprealarmlimit............................................... -99,0...+100,0........... 40,0°C.......100,0°C.......100,0°C........100,0°Cd19......oem....3,2......... Alarmdelay.......................................................................... 1...600sec................ 10sec.......600sec.......600sec........600secd20......oem....3,2......... PAnalogueOutput-OutputDelay...................................... 0...100sec................ 0sec.........0sec...........0sec............0sec.d21......oem....3,2......... PAnalogueOutput-StepSize............................................ 1...100%................... 100%........100%..........100%............100%d22......oem....3,2......... StageController-BaseLoadChange(StageSequenc.).... 000=off/off/off........ hr0.............hr0...............hr0................hr0 ....a..../....b..../....c.... Atpositiona,thesebaseloadfunctionscanbeset: rr0=runt/runt/off 0=off,r=forerundep.onruntime,h=fore.dep.onstoptime hr0=stopt/runt/off Atpositionb,thesebaseloadfunktioncanbeset: rr1=runt/runt/on 0=off,r=backrundep.onruntime, hr1=stopt/runt/on Atpositionc,thesebaseloadfunctionscanbeset: Switchoptimization:0=off,1=ond41...... tec......3,2......... ForerunDelayTimeStage1(thefirstturnonstage)......... 0...900sec.................10sec........0sec........... 0sec..............0secd42...... tec......3,2......... ForerunDelayTimeStage2............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd43...... tec......3,2......... ForerunDelayTimeStage3............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd44...... tec......3,2......... ForerunDelayTimeStage4............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd45...... tec......3,2......... ForerunDelayTimeStage5............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd46...... tec......3,2......... ForerunDelayTimeStage6............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd47...... tec......3,2......... ForerunDelayTimeStage7............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd48...... tec......3,2......... ForerunDelayTimeStage8............................................... 0...900sec.................10sec........0sec........... 0sec..............0sec

d51...... tec......3,2......... BackrunDelayTimeStage1(thelastoffstage)................ 0...900sec.................10sec........0sec........... 0sec..............0secd52...... tec......3,2......... BackrunDelayTimeStage2............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd53...... tec......3,2......... BackrunDelayTimeStage3............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd54...... tec......3,2......... BackrunDelayTimeStage4............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd55...... tec......3,2......... BackrunDelayTimeStage5............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd56...... tec......3,2......... BackrunDelayTimeStage6............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd57...... tec......3,2......... BackrunDelayTimeStage7............................................... 0...900sec.................10sec........0sec........... 0sec..............0secd58...... tec......3,2......... BackrunDelayTimeStage8............................................... 0...900sec.................10sec........0sec........... 0sec..............0sec

d61......oem....3,2..........Motor1automatic/manually.............................................. oFF,Aut(autom.).....Aut.............Aut............... Aut.................Aut on(permanentlyon)d62......oem....3,2..........Motor2automatic/manually.............................................. ditto............................Aut.............Aut............... Aut.................Autd63......oem....3,2..........Motor3automatic/manually.............................................. ditto............................Aut.............Aut............... Aut.................Autd64......oem....3,2..........Motor4automatic/manually.............................................. ditto............................Aut.............Aut............... Aut.................Autd65......oem....3,2..........Motor5automatic/manually.............................................. ditto............................Aut.............Aut............... Aut.................Autd66......oem....3,2..........Motor6automatic/manually.............................................. ditto............................Aut.............Aut............... Aut.................Autd67......oem....3,2..........Motor7automatic/manually.............................................. ditto............................Aut.............Aut............... Aut.................Autd68......oem....3,2..........Motor8automatic/manually.............................................. ditto............................Aut.............Aut............... Aut.................Aut

d71......oem....3,2..........MinimiumIdleTimeMotor1................................................ 0...20min.................. 0min.........0min...........0min............ 0min.d72......oem....3,2..........MinimiumIdleTimeMotor2................................................ 0...20min.................. 0min.........0min...........0min............ 0min.d73......oem....3,2..........MinimiumIdleTimeMotor3................................................ 0...20min.................. 0min.........0min...........0min............ 0min.d74......oem....3,2..........MinimiumIdleTimeMotor4................................................ 0...20min.................. 0min.........0min...........0min............ 0min.d75......oem....3,2..........MinimiumIdleTimeMotor5................................................ 0...20min.................. 0min.........0min...........0min............ 0min.d76......oem....3,2..........MinimiumIdleTimeMotor6................................................ 0...20min.................. 0min.........0min...........0min............ 0min.d77......oem....3,2..........MinimiumIdleTimeMotor7................................................ 0...20min.................. 0min.........0min...........0min............ 0min.d78......oem....3,2..........MinimiumIdleTimeMotor8................................................ 0...20min.................. 0min.........0min...........0min............ 0min.

Setpoint Page High Pressure (d)

Access Levels

Notallparametersarevisibleontheuserinterface.Dependingontheoperator‘sauthorization,parametersareswitchedonoroff.ThreeAccessLevelsareavailable:Level1-onlyselectedparameters-forthecustomer(defaultdisplay)Level2-parameterforthetechnician(P99=88)Level3-allparameters(P99=70)

Toentertheaccessauthorization,thereisparameterP99inthemodelist.If thevalue88 isenteredforthisparameter,allparametersof level2aredisplayed.Whenthevalue70isentered,allparametersoflevel3aredisplayed.

Ifthecontrollerisnotoperatedfor3minutes,thedisplayreturnstothebasicdisplayandonlytheparametersoflevel1areaccessible.Onlyrequiredparametersareaccessableonthedisplay,dependingonthecurrentconfiguration.

Withparameterh91,code70canbeusedtoloadoneoffourfixedconfigu-rationsorastoredconfiguration.Forspecialprotection,thecodenumber70mustbeenteredeachtimeforthisparameter.

Selectionoptions:„cF1“,„cF2“,„cF3“,„cF4“,„cFU“and„---“fortermination.Thevaluesof the four fixedconfigurationscanbeseen in theparameterlist.

Page 8: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140Page8

Assignment Page (h)Param Co Ebene Bedeutung Bereich Cf1 Cf2 Cf3 Cf4h01........ tec... 3,2........ FunctionofRelay1.............................. ---=switchedoff, on=continuously,..........................alA.......... l1...........l1............l1 alA =Warning/Alarm,alA =Warnung/Alarm, SuA =WarningSuctionSuperheat L1 =SP-Stage1,l2 =SP-Stage2,L3=SP-Stage3, L4 =SP-Stage4,L5 =SP-Stage5,l6=SP-Stage6, L7 =SP-Stage7,L8 =SP-Stage8,K1=HP-Stage1, K2 =HP-Stage2,K3 =HP-Stage3,K4=HP-Stage4 K5 =HP-Stage5,K6 =HP-Stage6,K7=HP-Stage7, K8 =HP-Stage8h02.......tec..... 3,2........ FunctionofRelay2(SSR)...................ditto.................................................................................L1...........--- .......L2............L2h03.......tec..... 3,2........ FunctionofRelay3(SSR)...................ditto.................................................................................---.........---.........---..........L3h04.......tec..... 3,2........ FunctionofRelay4..............................ditto.................................................................................---.........l2...........L3............L4h05.......tec..... 3,2........ FunctionofRelay5(SSR)...................ditto.................................................................................---.........L3...........L4............L5h06.......tec..... 3,2........ Fct.ofadd.moduleBMRRel.1(SSR)...ditto.................................................................................---.........---.........---..........---h07.......tec..... 3,2........ Fct.ofadd.moduleBMRRel.2(SSR)...ditto.................................................................................---.........---.........---..........---h08.......tec..... 3,2........ Fct.ofadd.moduleBMRRel.3(SSR)...ditto.................................................................................---.........---.........---..........---h09.......tec..... 3,2........ Fct.ofadd.moduleBMRRel.4(SSR)...ditto.................................................................................---.........---.........---..........---h20.......oem.. 3,2........ Sensor/ProbeType..............................201 =TF201,501 =TF501,5o1, 5o2 =cust.spec....501.........501.........501..........501h21.......oem.. 3,2........ FunctionofSensorInput1..................--- =switchedoff,dis =DisplaySensor,.................---.........---.........---..........--- Lco =ControlSensorSP,Hco =Contr.SensorHP, . out =OutdoorTemp.,Sut =SuctionTubeTemp.h22.......oem.. 3,2........ FunctionofSensorInput2..................ditto.................................................................................---.........---.........---..........---h23.......oem.. 3,2........ FunctionofSensorInput3..................ditto.................................................................................---.........---.........---..........---h24.......oem.. 3,2........ FunctionofSensorInput4..................ditto.................................................................................---.........---.........---..........---h25.......oem.. 3,2........ Funct.ofPress.Transm.1,4/20mA.....ditto.................................................................................Lco.........Lco .......Lco..........Lcoh26.......oem.. 3,2........ Funct.ofPress.Transm.2,4/20mA.....ditto.................................................................................---.........Hco .......hco..........hcoh31.......oem.. 3,2........ FunctionofDigitalInput(DI)1.............--- =switchedoff,.......................................................---.........FbK.........fbK..........fbK L(1 =LoadLimitation1,L(2 =LoadLimitation2, FbL =ForcedBackrun(passive), fbK =ForcedBackrun(active), dnL =NightOperation(passive), dnK =NightOperation(active), LFL =externalSuctionPressurefault(passive), LFK =externalSuctionPressurefault(active), KFL =externalHighPressurefault(passive), KFK =externalHighPressurefault(active), r1 =FeedbackSP-Motor1, r2 =FeedbackSP-Motor2, r3 =FeedbackSP-Motor3, r4 =FeedbackSP-Motor4h32.......oem.. 3,2........ FunctionofDigitalInput(DI)2.............ditto. ........................................................................---..........r1..........r1............r1h33.......oem.. 3,2........ FunctionofDigitalInput(DI)3.............ditto. ........................................................................---..........r2..........r2............r2h34.......oem.. 3,2........ FunctionofDigitalInput(DI)4.............ditto. ........................................................................---..........r3..........r3............r3h40.......oem.. 3,2........ AnalogueOutputdelivers....................420 =Current4-20mA,010=Voltage0-10V...............010..........010........010..........010h41.......oem.. 3,2........ AnalogueOutputworksas/delivers....--- =0V/4mA.............................................................---..........KP..........KP............KP 100 =100%(10Vrespective.20mA), LPi =PIControllerSP,KP =PControllerHPh49.......tec..... 3,2........ CRIIPowerContr.used(max.1motor). 0=no,1=yes.............................................................0..............0...............0.............1h50.......tec..... 3,2........ Numberoftheprioritizedmotor(SP). 0=allthesame,1=Motor1,2=Motor2,3..8=ditto....0..............0...............0.............1h51.......tec..... 3,2........ NumberofstagesSPmotor1............ 0...8...............................................................................1..............1...............2.............3h52.......tec..... 3,2........ NumberofstagesSPmotor2............ 0...8...............................................................................0..............1...............1.............1 h53.......tec..... 3,2........ NumberofstagesSPmotor3............ 0...8...............................................................................0..............1...............1.............1h54.......tec..... 3,2........ NumberofstagesSPmotor4............ 0...8...............................................................................0..............0...............0.............0h55.......tec..... 3,2........ NumberofstagesSPmotor5............ 0...8...............................................................................0..............0...............0.............0h56.......tec..... 3,2........ NumberofstagesSPmotor6............ 0...8...............................................................................0..............0...............0.............0h57.......tec..... 3,2........ NumberofstagesSPmotor7............ 0...8...............................................................................0..............0...............0.............0h58.......tec..... 3,2........ NumberofstagesSPmotor8............ 0...8...............................................................................0..............0...............0.............0h61.......tec..... 3,2........ Switchingstage1(SP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h62.......tec..... 3,2........ Switchingstage2(SP)inverted......... 0=no,1=yes.............................................................0..............0...............1.............1h63.......tec..... 3,2........ Switchingstage3(SP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h64.......tec..... 3,2........ Switchingstage4(SP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h65.......tec..... 3,2........ Switchingstage5(SP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h66.......tec..... 3,2........ Switchingstage6(SP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h67.......tec..... 3,2........ Switchingstage7(SP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h68.......tec..... 3,2........ Switchingstage8(SP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h71.......tec..... 3,2........ NumberofstagesHPmotor1............ 0...8...............................................................................0..............0...............0.............0h72.......tec..... 3,2........ NumberofstagesHPmotor2............ 0...8...............................................................................0..............0...............0.............0 h73.......tec..... 3,2........ NumberofstagesHPmotor3............ 0...8...............................................................................0..............0...............0.............0h74.......tec..... 3,2........ NumberofstagesHPmotor4............ 0...8...............................................................................0..............0...............0.............0h75.......tec..... 3,2........ NumberofstagesHPmotor5............ 0...8...............................................................................0..............0...............0.............0h76.......tec..... 3,2........ NumberofstagesHPmotor6............ 0...8...............................................................................0..............0...............0.............0h77.......tec..... 3,2........ NumberofstagesHPmotor7............ 0...8...............................................................................0..............0...............0.............0h78.......tec..... 3,2........ NumberofstagesHPmotor8............ 0...8...............................................................................0..............0...............0.............0h81.......tec..... 3,2........ Switchingstage1(HP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h82.......tec..... 3,2........ Switchingstage2(HP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h83.......tec..... 3,2........ Switchingstage3(HP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h84.......tec..... 3,2........ Switchingstage4(HP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h85.......tec..... 3,2........ Switchingstage5(HP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h86.......tec..... 3,2........ Switchingstage6(HP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h87.......tec..... 3,2........ Switchingstage7(HP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h88.......tec..... 3,2........ Switchingstage8(HP)inverted......... 0=no,1=yes.............................................................0..............0...............0.............0h90........oem.. 3.............SaveConfiguration............................. ---=quitwithoutsaving(withRETkey)....................---..........---........---..........--- (withOEM-Code) do=save(withRETkey)h91........70..... 3.............LoadConfiguration(with Code 70)... ---=no,cF1=Conf.1,cF2=Conf.2,......................---..........---........---..........--- cF3=Conf.3,cF4=Conf.4,cFU=Config.userh92........tec..... 3,2.........Add.-ModuleBMR3002available..... 0=no,1=yes.............................................................0..............0............0..............0h93.......---...... 3,2,1.....LowerlimitPress.Transm.Input1.... -1,0...160,0bar............................................................. -1,0bar...-0,5bar.. -0,5bar...-0,5barh94.......---...... 3,2,1.....UpperlimitPress.Transm.Input1.... -1,0...160,0bar.............................................................+9,0bar..+7,0bar.+7,0bar..+7,0barh95.......---...... 3,2,1.....LowerlimitPress.Transm.Input2.... -1,0...160,0bar............................................................. -1,0bar...0bar......0bar........0barh96.......---...... 3,2,1.....UpperlimitPress.Transm.Input2.... -1,0...160,0bar.............................................................+9,0bar..25,0bar.25,0bar..25,0barh99.......---...... 3,2,1.....UsedRefrigerant................................ ---=none,controlbytemperaturesensoronly.........2..............2............2..............2 1=NH3,2=R134a,3=R22,4=R23,5=R404a, 6=R507,7=R402A,8=R402B,9=R407C, 10=R123,11=R290,12=CO2,13=R502, 14=R723,15=R410A,16=R407F,17=R448A, 18=R449A,19=R1270

Hinweis

Parametersmarkedby"nA"areforinformationonlyandcannotbechanged."Co"isthepassword/codeforthisparameter.The3codenumbersare:- OEM-Code(oem):Month+Hour+20- TechnicianCode(tec):88- CustomerCode(---):withoutcode

Page 9: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140 Page9

Dimensions & Connection

Dimensionsinmm,(inbrackets=inches)

Note

35(1

.38)

26 (1 .02)

59 (2 .32)39 (1 .54) ProtectiveEarth

1 2 3 4

1 2 83 4 5 76 12119 1310

22

EVP

20 21 2723 24 25 26 28 3229 3130

105 (4.13)

46 (1

.81)

63 (2

.48)

91 (3

.58)

115 (

4.53)

1915 1814 16 17

ELREHA

P

38373433 35 36

MSReco

When connecting the switch outputs, the overvoltage category must be respected !

*Whenconnectingan inductiveload,suchasrelay, totheSolidStateRelay output,itmaybenecessary

toconnectasnubbercircuitin parallel to the

load to protecttheoutputfromengagingunexpectedly.Thesnubbercircuit must beproperlyadapted

totheloadinordertopreventtheoutputfromengagingpermanently.

SSR-Relay RC-Glied

RC-circuit

*** *

5

14

1 42 3

1110 12 13

Netzmains

876 9

17

PE

15 16 18

relay(SSR1)

relay(SSR2)

relay(SSR3)

relay(SSR4)

N L

RS485

NDO

DO

12-2

4V A

C, 1

8-33

V DC

50-6

0Hz,

max.

5,5V

A

Fühle

reing

ang

S1

R S4 8 5

Fühle

reing

ang

S2

R e la is K 2

1 2 43 5

R e la is K 1

Digit

al-ein

gang

DI 1

6 1 07 98

R e la is K 3

R e la is K 4

Digit

al-ein

gang

DI 2

2 02 32 4 2 12 2

! !

1 9 1 61 71 8

DONDO

GND

Netz-

werk

1 31 412

31

relay K1

N1 2 3

L4 5

relayK4

6 7 8 9 10 11

242120 2322 2825 26 27 29 30

19

relay(SSR)

K5 DI 2 DI 4

1613 14 15 17 18L N

DI 1 DI 3

383532 33 34 36 37

LL L

RS485

NDO

DO

RS485

NDO

DO

RS485

NDO

DO

PT

PT

relay(SSR)

K2

relay(SSR)

K3

MSR eco 3140

BMR 3002

Connection of the Expansion Module BMR 3002

Earth

12

31

N1 2 3

L4 5 6 7 8 9 10 11

242120 2322 2825 26 27 29 30

19

DI 2 DI 4

1613 14 15 17 18L N

DI 1 DI 3

383532 33 34 36 37

LL L

RS485

NDO

DO

RS485

NDO

DO

RS485

NDO

DO

PT

PT

Signalout4-20mA+SupplyVoltage

anal

ogo

ut

22V

supp

ly

Sens

or4

Sens

or2

Sens

or1

mains

Anal

og

IN

4-20

mA

Sens

or3

{{ Network(line)

Signalout4-20mA+SupplyVoltage

Anal

og

IN

4-20

mA

PressureTransmitter1

PressureTransmitter2

relayK1

relay(SSR)

K2

relay(SSR)

K3

relay(SSR)

K5

relayK4

{ BMR3

002

Add.

Mod

ul

PE

MSR eco 3140

12

31

relay K1

N1 2 3

L4 5

EVP 3168

relayK2

relayK3

relayK4

6 7 8 9 10 11

242120 2322 2825 26 27 29 30

19

relay(SSR)

K5 DI 2 DI 4

1613 14 15 17 18L N

DI 1 DI 3

383532 33 34 36 37

LL L

RS485

NDO

DO

RS485

NDO

DO

RS485

NDO

DO

PT

PT

Col

dSt

orag

eC

ontro

llers

Page 10: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140Page10

CONNECTION INFORMATION & SAFETY INSTRUCTIONS

Productwarrantydoesnotcoverdamagecausedbyfailuretocomplywiththeseoperatinginstructions!NorwillELREHAbeheldliableforanypersonalinjuryordamagetopropertycausedbyimproperhandlingorfailuretoobservethesavetyinstructionsandrecommendationscontainedinthisoranyotherELREHAsupplieddocumentrelatedtothisproduct!Thismanualcontainsadditionalsafetyinstructionsthroughoutthefunctionaldescription.Pleasepaycloseattentiontotheseinstruction!

TO AVOID RISK TO HEALTH OR POSSIBLE LOSS OF LIFE, DO NOT OPERATE IF: •Thedevicehasvisibledamageordoesn'twork•Afteralongstorageperiodunderunfavourableconditions•Thedeviceisheavilysoiledorwet•Whenshippedunderinadequateconditions•Neverusethisproductinequipmentorsystemsthatare intendedtobeusedinapplicationsorundercircumstances thatmayaffecthumanlife.Forapplicationsrequiring extremelyhighreliability,pleasecontactthemanufacturer beforeuse.•This product may only be used in the applications described on page 1.• Electrical installation and placement into service must be performed by qualified personnel only. • To avoid the risk of Electrical Shock, all ‘PE’ terminals must be connected to ground. Without adequately grounding the unit, the internal noise filter will not work, which can cause faulty readings, or inaccurate displayed values to occur. • To prevent electrical shock, the device may only be operated in a closed control cabinet or control box.• Be sure to observe all local, state, or federal safety regulations in the location that the unit is installed.

•Beforeinstallation,verifythatthecontrolspecifications suittheapplicationdetails.Damagemayoccurtothe devicewhenoperatediftheaforementionedconditions arenotwithinthedevicespecifications. Examples: -Supplyvoltage(printedonthetypelabel). -Environmentallimitsfortemperature/humidity. -Maximumcurrentratingfortherelays.•Sensor/probecablesmustbeshielded.Don’tinstallthem inparalleltohigh-currentcables.Shieldingmustbe connectedtoPEattheendclosetothecontroller. Ifnot,inductiveinterferencesmayoccur.•Noterelatedtowirelenghtsconnectedtothedevice: Wireshouldbe0,5mm²ataminimum.•Mountingthedeviceincloseproximitytopowerrelays isNOTrecommended.Strongelectro-magnetic interferencemaycausethedevicetomalfunction!•Alllineinterfacewiringmustmeetthespecified requirements.•Alltemperaturesensorsconnectedtothedevicemustbe ofthesametype.Theuseofinconsistentsensortypes willcausetheunitnotfunctionproperly.•TypeTFsensorsarenotdesignedforlongtermimmersion inliquids.Anysensorsofthistypethatareintendedtobe immersedinanyliquidenvironmentshoulduseadipfitting orsuitablecoatingtoprotectthesensoragainstcorrosion ormalfunction. Environmentswithextremetemperaturevariationsmay causedamagetothesensor(s).

CleaningTheuseofadry,lint-freeclothissufficienttocleantheproduct.Neveruseliquidsoracidicfluids!Riskofdamage!

Danger

Notice

Caution

Notice

The following conditions will result in an „Assignment Error“:

- Exceeding8HPstagesor8SPstagesassigned.- IftheSPcontrolsensor,HPcontrolsensor,outdoortemperature sensor,orthesuctiontubetemperaturesensorareselectedmore thanonce.- IfnoHPorSPcontrolsensorhasbeenselected.-Ifrelayfunctions6-9areassignedwithouttheBMRbeingselected.- IftheSPcontrolsensorisselectedwithoutdefiningtheSPstages orSPanalogueoutput.- IftheHPcontrolsensorisselectedwithoutdefiningtheHPstages orHPanalogueoutput.- IftheanalogueoutputSPisselectedwithoutSPstagesortheVVR beingswitchedon.-IfnoSPcontrolsensorisselectedbut *SPstages *asuctiontubesensor *SPanalogueoutput *DigitalInputfor -feedback,loadlimitation,forcedbackrun, externalsuctionpressureerror- IfnoHPcontrolsensorisselectedbut *HPstages *outdoortemperaturesensor *HPanalogueoutput *DigitalInputforhighpressureerror- Ifamotorwith0stagesisfollowedbyamotorwith1ormorestages.-Ifanythingotherthan1relayisselectedforeachSPandHPstage.- IfarelayisselectedforSP/HPstageswhicharenotrequired.- Iftherearemorefeedbackinputsselectedthanthenumber ofmotors.-Ifthesameinputisselectedmorethanonce.- Priorizedmotorismorethanzero,butnoSPstagesareselected- IftheCRIImodeisactivatedbut *SPmotor1haslessthan2stages *SPanalogueoutputisselected- IfnoSSRisassignedforCRIIpowerstage.- Ifatleast1currentinputisselectedbutwithnorefrigerantdefined.

Notice

Page 11: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140 Page11

Functional Description

Input Signals of the ControllerThe input signals come from a 2-wire pressuretransmitterwitha4-20mAsignaloroneofthefour(4)temperatureprobes.Thesourcecanbeselectedath21...h26(Assignmentpage).If a pressure transmitter is selected, additionallya refrigerant must be defined (at h99), which isnecessarytocalculateatemperaturein°C.Calibration of Transmitter, Display CorrectionForeachtransmitterinputmustbedefined,whichpressure corresponds to the delivered 4-20 mAsignals. 4-20mA Input Forthisinputs,thematchingpressurelimitscan besetbyh93,h94(pressuretransmitterinput1) andh95,h96(pressuretransmitterinput2).

Probe-/Transmitter FailuresIfaprobeortransmitterfailureisidentified,allstageswillswitchONwiththeselecteddelay.Afterthealarmdelayr08, thealarmrelay(ALA)switchesoffifitisdefinedandavailable.Control of Compressors (Load)TheMSRecoisabletocontrolupto8(withextensionmoduleBMR3002)singleormulti-stageloadswithuptofourstages.The kind and number of stages of the selectedloadsmustbedefinedwiththeparametersh51uptoh58.Example:

Standard Stage ControllerApplicationsinclude:- Standardcompressors-Compressorswith CRIIControlStages/PowerControl-CondensationHighPressureControl

Standard Compressors (SP)Thecontrolsetpointispresetbyr01(day)orr02(night).Withr03amaximumvalueforthissetpointcanbedetermined.Therangeofthehysteresiscanbesetusingparameterr04,whiler05determinesthepositionabovethesetpoint,(above,below,orbalanced).Forerun(StagesON)If the actual value exceeds the switching point,thentheforerundelaystarts(r41...r48,individualforeachstage).Afterthistimerisrundown,astagewillbeswitchedONandtheindividualdelaytimestartsagain.NeutralZoneIftheactualvalueislocatedwithinthehysteresisranger04/r05,nostagewillbeactivatedorde-activated.Backrun(StageswillswitchOFF)If the actual value falls below the tripping point,the backrun delay (r51...r58, individual for eachstage)willbestarted.Afterthistimerisrundown,onestagewillswitchOFFandtheindividualdelaytimestartsagain.

L21showsthecurrentstateofthecontroller.

LimitsIftheactualmeasuredvaluefallstoacriticallevel,thecontrollerwillreactintwoways:IftheactualvaluefallsbelowtheEarlyWarningAlarmsetpoint,parameter‚r07‘,thenatleast50%ofthemotorswillswitchoff,oncethesettimeofparameter‚r08‘isreached.Iftheactualvaluefallsbelowparameter‚r06‘,thenaforcedBackrunwillalsobeinitiated,shuttingdownallmotors.

Compressor Programming Relay selection free at h51 h52 h53 h54 h01 ... h05

4x single mach. 1 1 1 1 2x dual stage 2 2 0 0

1x 3-stage 3 0 0 0

1x 3-stage and

1x single mach. 3 1 0 0

Base Load Change / Switching Frequency Opt.Ifaplantislaidoutcorrectly,thennotallfansandcompressorsshouldruncontinuously.Whenusingnormalstagecontrollers,somemotorsbearaheavyloadwhileotherhardlyanyloadatall.Topreventthis,the„BaseLoadChange“functioncanbeutilized.(ThisfunctionisalsoknownasStageSequencing).The„r22“parametermonitorstherelativeruntimesofthemotorsandwillestablishaconsistentbalanceofapproximatelythesameruntimeforeachmotor.Differentapplicationscenarioscanbeselected.Ifamultistageunitisbeingused,onlytheruntimeoftheleadingstage,(=motoron)willbecalculated.Thecontrolsystemrecordsandstorestheruntimeanddowntimeofeachmotortodeterminewhichmotorcanbeswitchedonoroff.During„Backrun“operation,themotorwiththelongestruntimewillbeswitchedofffirst.Forthe„Forerun“operation,theoptionexiststoselectthemotorbasedon(a)shortestruntime,or(b)longestdowntime.If thepressureratio in theplantdoesnotchangeoveralongperiodoftime,no'Forerun/Backrun'isactiveandasequencingisimpossible.The'DelayTime(r20)startsashortbackrunafterthesettimetoenableanewmotorselection.Itisalsopossibletoselectanoptimizationfunction,(c),fortheswitchingfrequency.Iftheoptimizationfunctionisactivated,duringbackrun,thecontrollerswitchesoffanadditionalstageonacompressorbeforeamotorisswitchedoff.

Thus,amoreuniformutilizationcanbeachievedwithoutanyparticularmotorcar-ryinganunnecessaryhigherload.

With r21 an Operational-FeedbackTime can beset, which determines when a feedback signalmustberecognized.Minimum Idle TimeIfamotorisswitchedoff,itcanberestartedafteraMinimumIdleTime(r71...r78).

Control of Compressors withCRII-System Power ControlThiscontrolmethodcanbeactivatedby thepa-rameter"h49".Withthismethod,onlyoneofthecompressorscanbecontrolled.Characteristicforthiscompressortypeisthefactthatthefirststagegeneratesnorefrigerationcapacity.Thecontroloftherefrigerationcapacityisachievedbyafaston/offswitchingofthepowerstages.

ControlThecontroloftheCRII-Valvesisalwaysinverted,thatmeansifvoltageappearsatthecorrespondingoutput,therespectivepowerstageisdeactivated.Theswitchingbehaviourmustbeset separatelyfor each power stage (inverted for CRII-powerstages,h61...h68).

Whileastandstill,theCRII-Valvesofthemotorwillbede-energized.With thestartof themotor theswitchingoutputsofthepowerstageswillbeutlizedatthesametime.Ifthemotorrunswithoutpowerstages,anadjustable„switch-off“countdown"r24"willbeinitiated.Oncethesetamountoftimeisdepleted,themotorwillbeswitchedoff.ThecontrollerperformsregularsequenceexchangestoensuretheCRIIValvesswitchanequalnumberoftimes.Theforerun/backrunbehaviouristhesameasatthestandardapplication.

Toggling of Power StagesIfthepowerrequirementdevelopsinthewaythata power stage switches repeatedly, the forerun/backrundelaytimesarenotused,buttherespectivestagecanbeswitchedon/offimmediatelyafter"r23“(Idle Time of the stage with 0% load).

Base Load Change with Switching Frequency Optimization at BackrunDuetothespecialrequirementsofthecontrolde-pendingonthebasicstage,theSwitchingFrequencyOptimizationdoesnotworkandmustbede-activated.Soonlythevalues"000,rr0,hr0“areallowedfortheparameter"r22“."rr1"and"hr1"aretreatedas"rr0"and"hr0"respectively.

Condensation High Pressure Control (HP)The Condensation High Pressure Control canbeusedwiththeanalogueoutputasP-controllerand/orwithupto8relaystages.Therelaystagescanbeassigned toup to8machines.Foreachstageaforerundelaytime(d41...d48),abackrundelaytime(d51...d58)andasetpoint(d01...d08)isavailable.Eachmotorcanbesettomanually/off/automatic(d61...d68)aswellasaminimumidletime(d71...d78).TheHPfunctionhasthesamebase-loadchangefunctionandswitchingoptimizationastheSPfunction.HPoperateswithanunifiedcontrolhysteresis(d12)andhysteresisposition(d13),relativetotheactivesetpoint.Dependinginthenumberofstagesthatareon,theOn/OffSwitchpositionwillbedependedontherespective setpoint - hysteresis respectively thenextsetpoint+hysteresis.Withit,thepositionofthehysteresisistakenintoaccount.WhenusingtheanalogueoutputPController,theproportionalrangeisdeterminedbytheswitch-on/offpositionsoftherespectivestage,dependingonthenumberofrunningstages.Iftheconfigurationhasonlyoneorzerostages,theswitch-on/offpositionsarerepresentedbythefirstsetpointandthehysteresisofthestagecontrolleronly.Two (2) limit values 'High pressure alarm limit'(d17)and'Highpressureprealarmlimit'(d18)generateerrormessageswhenexceeded.Ifd18isexceeded,aloadlimitationoftheSPmachines will be activated to max 75% of theselectedmachines.Ifd17isexceeded,allSPmotorswillbeswitchedoffbyfastbackrun.

Minimum Overheat Monitoring (SP)Inordertoavoidinsufficientoverheat,andthepo-tentialforliquidrefrigeranttoflowintothesuctiontube,insystemswheretheremaynotbeenoughcompressorpowertocreatesufficientoverheat,the„MinimumSuperheatThreshold“,parameter‚P10‘shouldbeused.Whentheestablishedmini-mumlimitisnotreached,analarmwillbetriggeredandtheexpansionvalvesofthecoolingpositionswillbelockedwithspecialsettings.

Anadditionaltemperatureprobe(Sut)wouldneedtobeinstalledatthesuctiontube.Thesuctiongasoverheatwillbecalculatedusingthemeasuredtemperaturevalueatthesuctiontubeandthesuctionpressuretransmitter.

If‚P10‘isnotreached,and‚P12‘,(„SuperheatWarningDelayTimer“)timesout,thenan„SSGWarning“alarmwillbeactivated,andifneeded,thecoolingpositionswillbelocked.Thebackrunofthelastrunningcompressorstageswillnotbegeneratedatthestandardswitchpoint,butthecompoundsucksuptothedefinedsuctionpressurepre-warningsetpoint,andswitchesoffwithoutdelay.Iftheoverheathasreachedthedefinedlimitvalue+hysteresis,thewarningsandcoolingpositionlockswillbecanceled.If the overheat falls below a second limit value(Compound lock threshold minimal superheat,P14),whichissmallerthanthefirstlimitvalue,afterthesettabledelaytime(P15)afastbackrunofthecompoundwillbestartedandanalarm'SSGfault'appears.The delay for the switch-off starts earliest, afterthealarmdelay(P12,warndelaysuperheat)hasbeenrundown.Thecompoundwillbereleasedifthesecondlimitvaluehasbeenreachedagainorexceeded.

Page 12: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140Page12

SDS - Suction Pressure Optimization by Setpoint Shifting with Cold Storage Controllers

Cold Storage Controllers with EEx-Valves:When there isa reduced-power requirement, thesetpointofthecompoundshouldbehigherthanthesetvalue.Ifthereisademandforpoweratacoldstoragelocation,thenitmustensuredthatthesetpointshiftsdownenoughtoallowthecoldstoragetoreachitslowsetpoints.

WithinafixedtimeintervalitwillbecheckediftheopeningrateoftheEEx-Valvesoftheconnectedcontrollershaveexceededaspecificlimit(r18).Ifthelimithasbeenexceededatleastatonecoolingposition,thenthesetpointofthecompoundisreducedbyacertainvalue(r19).

Iftheactualvalueofthealarmprobeexceedsthelimitatevenoneofthecoldstoragelocations,thesetpointmustbelowered.Thelimitvalueisbasedontheswitch-ONpoint+d3.

Ifthefollowingconditionsoccur,thenthesetpointofthecompoundcanberaisedbyasetvalue,‚r19‘,uptotothemaximumsetpointdefinedby‚r03‘:1.AtleastoneEEx-Valveofacoldstoragelocation isbelowthelimit‚r17‘.2.Nounitsarerunningabovetheupperlimit.3.Nocoldstoragelocationhasexceededthe safetylimit.

Cold Storage Controllers without EEx-Valves:Inthesecases,iftheactualvalueofthealarmprobehas exceeded the limit value, (switching point +d03),areductionof thesuctionpressuresetpointwillbeneeded.Iftheactualvalueisequaltoorlessthan the limitvalue, thesuctionpressuresetpointcanberaised.

Thesetpointutilizedby thecompressorcontrol isbasedontheadjustedsetpoint,‚r01orr02‘,andtheoffsetvalues,whicharegeneratedby theoptimi-zationprocess.Theenteredsetpointisthelowestpossiblesetpoint.

For each connected cold storage controller withEEx-Valvestwoparametersareavailableatwhichthisinfluencecanbesetup:d02..... 0=off/noeffect,1=LimitationTemperature, 2=LimitationTemperature +OpeningDegreed03.....SuctionPressureShift-Temp.Offset

Thecurrentincrease/decreasevalues,whichhavebeen produced by this function, can be read atL31/L32.

SP-Optimized switching by variable Forerun/Backrun Runtimes (VBR)Ifthedifferencebetweensetpointandactualvalueissmall, thenumberofswitchingeventsshouldbe reduced.Rapidchanges insuctionpressurerequireaquickdeliveryofpower,whichrequiresaquickreductioninthepowerreserve.Thiscanbeachievedbyvariableswitchingdelaysdependingontheactualoffsetfromthesetpoint.This function, ‚r40‘, is located on the SetpointPage.Theforerun/backruntimeswillbeactivatedifthesuctionpressuregoesbeyondthehysteresisrange.Aboveandbelowthehysteresisrangearedefinableareas(VBR Forerun Range r41

respective VBR Backrun Range r42).Ifthesuctionpressureactual valuemoveswithin thisareas,theforerun/backruntimeswillbevariedwithintherangessetbyr43(VBR Forerun/Backrun Time min)andr44 (VBR Forerun/Backrun Time max).Thebigger thedifferencebetweenactual valueand setpoint, the shorter the time delay. If theactual value leaves the set range, always thesmallestsetdelayvaluewillbeused.Iftheelapsedtimeincreasesthecurrentcalcula-tedtime,thefunctionbeginstoswitch.ForinformationL34(Remaining time of Forerun/Backrun) shows the current calculated delaytime.

Forerun/BackrunTimemax.

Forerun/BackrunTimemin.

Cur

rent

set

poin

t(e

.g.3

.0b

ar)

Backrun(switchoff)Delay

Forerun(switchoff)Delay

BackrunArea ForerunAreaHysteresisRange

SuctionPressure

Machines with Feedback (SP, Motor 1-4)Todetecttherealstateofamachine,thesafetychaincanbecheckedusingadigitalinput,whichhasafeedbackfunction,(h31...h34).Thecontrollerswitchesamachineonandwaitsforafeedbacksignalwhilepowerisbeingappliedtothedigitalinput.Ifnofeedbackisdetected,themachinewillbeswitchedoffandadifferentmachinewillbeselected.‚r21‘canbeusedtosetthewaitingtime.Iftheswit-chingofamachineisunsuccessful,anewstartingattemptcanbeinitiatedafteranautomaticallycalculatedtimedelay.

Switching Behaviour of the Stage RelaysTheswitchingbehaviourcanbesettoactive(relayswitcheson)orpassive(relayswitchesoff)withtheparameters(h61...h68, SP) and(h81...h88, HP).Withthesetting'1'thestagewillbeinverted,with'0'thestageswitchesnormally.Load Limitation (SP)Aloadlimitationcanbeestablishedforeachofthe4digitalinputs.Thiscanbeusedduringpeakopera-tionperiods.Twoinputscanbeassignedtheirownmaximumnumber(r11...r12)ofrunningmachinestoprovidemoreopportunityforenergysavings.

Operating Mode of the Motors (Manual/Auto)Eachmotorcanbesettomanual„ON/OFF“operationvia‚r61-r68‘forSP,and‚d61-d68‘forHP.Default„ON/OFF“operationissetto„Auto“.

Second Setpoint (Ex. Night Operation)Alternatesetpointscanbeestablished forenergysavings.‚r01‘canbeestablishedasadaysetpoint,and‚r02‘fornighttime.Thesecanbealternatedviainternaltimersettings‚P21‘/‘P22‘,oranydigitalinput‚h31...h34‘,settingdnlordnh.IfoneoftheDIinputsisconfiguredforday/nightswitching and it has been activated,, the 2ndsetpointisactivealltimeandcannotbechangedbytheinternaltimer.Ifyouwanttouseexternalswitchingonly,pleaseset'P21'and'P22'to„oFF“.Fornightoperation,thehighpressurecontrollerhasanightoffset(d10)andadditionallyanightlimitation(d11)fortheanalogueoutput.

Page 13: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140 Page13

Digital Inputs

WiththeDigitalInputsDI1...DI4(formainsvoltage)anumberoftaskscanbetriggeredwhichcanbesetontheAssignmentPage(h).Iftheinputisnotrequired,itshouldbeswitchedoff.Whetherthedigitalinputreactsonvoltage,(Active),oronnovoltage,(Passive),isdependentupontheselectedtask:

--- = ThedigitalinputisswitchedoffL(1 = LoadLimitation1(r11)willbereleased(act)L(2 = LoadLimitat.2(r12)willbereleased(pass.)FbL = ForcedBackrunofthestages(passive)fbK = ForcedBackrunofthestages(active)dnL = NightOperation,i.e.NightSetpoint(passive)dnK = NightOperation,i.e.NightSetpoint(active)LFL = externalsuctionpressurefault(passive)LFK = externalsuctionpressurefault(active)KFL = externalhighpressurefault(passive)KFK = externalhighpressurefault(active)r1 = Feedbacksignal1(frommotor,active)r2 =Feedbacksignal2(frommotor,active)r3 =Feedbacksignal3(frommotor,active)r4 =Feedbacksignal4(frommotor,active)

Real Time Clock / Time Synchronization / Night Mode

Thebuilt-inrealtimeclockhasabufferformax.10dayswithoutmainsvoltage.Dateandtimecanbesetby"P80"..."P85"(ModePage).Bydefault,aGMT+01:00isset(P71=60min.),which isstandard for theCentralEuropeanArea.Iftheproductisusedinothercountries,thisvaluecanbechanged.Summer/Winter Switch - Time ZonesAnautomatic summer/winter switch "P70 =EU"(ModePage)considersthecurrentEU-rulesfrom1996(EU96),butcanalsobeswitchedofforsetasneeded.Thecurrentsetting,(Summer/Winter),canbeviewedat‚P69‘.Variable Time ZonesThe function for Variable Time Zones can beactivatedby"P70 =tun"andisadaptablebytheparameters"P72"..."P79".P72(SummerON Month) (Fact.SettingMarch,3rd) ThemonthofthebeginningofthesummertimeP73(SummerON Day)...(Fact.Setting.0,sunday) Theweekdayofthebeginningofthesummert.P74(SummerON x-Day)...(Fact.S.5,lastsunday) Thex-thwith"SummerON Day"presetdayof themonthP75(SummerON Hour)..... (Fact.Set.2,2o'clock) ThehourofthebeginningofthesummertimeP76(SummerOFF Month)(Fact.Set.October,10th.) ThemonthoftheendofthesummertimeP77(SummerOFF Day)...(Fact.Setting0,sunday) TheweekdayoftheendofthesummertimeP78(SummerOFF x-Day) ..(Fact.S.5,lastsunday) Thex-thwith"SommerOFF Day"presetdayof themonthP79(SummerOFF Hour).. (Fact.Set.3,3o'clock) ThehouroftheendofthesummertimeTheshifttothesummertime(=daylightsavingtime)respectivewintertimeissetbythetimesettingwhichisactiveatthistime.

Time SynchronisationIntheModePagetheparameterP20determinesifdateandtimewillbetransmittedtotheconnectedColdStorageControllers.

Second Setpoint Mode Seepage12.

Relay Outputs

Aspecific functioncanbeassignedtoeachrelayoutput,includingtheSSRrelayoutputs,via‚h01...h09‘.Anyoftheserelayscanalsobeswitchedonmanually.

--- = TherelayoutputisswitchedOFFon = TherelayoutputisswitchedONmanually/ permanent

alA = Warning/Alarm,SuA = WarningSuctionOverheatL1 =TherelayoutputswitchesSP-Stage1l2 =TherelayoutputswitchesSP-Stage2L3 =TherelayoutputswitchesSP-Stage3L4 =TherelayoutputswitchesSP-Stage4L5 =TherelayoutputswitchesSP-Stage5l6 =TherelayoutputswitchesSP-Stage6L7 =TherelayoutputswitchesSP-Stage7L8 =TherelayoutputswitchesSP-Stage8K1 =TherelayoutputswitchesHD-Stage1K2 =TherelayoutputswitchesHD-Stage2K3 =TherelayoutputswitchesHD-Stage3K4 =TherelayoutputswitchesHD-Stage4K5 =TherelayoutputswitchesHD-Stage5K6 =TherelayoutputswitchesHD-Stage6K7 =TherelayoutputswitchesHD-Stage7K8 =TherelayoutputswitchesHD-Stage8

Control with the Analogue Output (P-Controller, HP)Toadapttotheprocess,thefollowingparameterscanbesetontheSetpointPage.

d20= PAnalogueOutput-OutputDelayd21= PAnalogueOutput-StepSize

Thisfunctioncanbeusedfortriggeringofafrequencyconverter.TheP-rangeresultsfromtheswitchingpointofforerunandbackrun.WithanactiveP-controlleronlyaforerunsignalwillbegeneratediftheanalogueoutputhasreacheditsmaximumvalue.Inverselyabackrunsignalwillbegeneratedonly,iftheanalogueoutputhasfallento0%.Bythe'NightLimitation'setpoint(d11)themaximiumvalueoftheanalogueoutputwhilenightoperationcanbelimited.

Function ControlL96(ActualValuesPage)showsthecurrentoutputsignalas%-valueoftheselectedrange.

Analogue Output

Theanalogueoutput canbeused for regulationpurposesorforwardingoftheactualvalue.ThesignalisavailableasaDC-Voltage(010)oraDC-Current-Signal(420),setby"h40"(AssignmentPage).Parameter"L96"(ActualValuesPage)showsthecurrentoutputsignalasa%-partoftheselectedrange.Parameter"h41"(AssignmentPage)determinesthebehaviouroftheoutput:

Functionsh41 = "- - - "=Outputsignalfixedto0Vrespective.4mAh41 = "100" =Outputsignalfixedto 10Vrespective20mAh41 = "LPI" =OutputforPIcontrolSPh41 = "HP" =OutputforPcontrolHP

Control with the Analogue Output (PI controller, SP)Toadapttotheprocess,thefollowingparameterscanbesetontheSetpointPage.Forworkingwithextremedeadtimes,thecontrollerallowsanadditionaloutputdelay:

r13 = PIproportionalband/range,located symmetricallyaroundthesetpointr14 = PIintegraltimer15= PIoutputdelayr16= PIstepsize

Ifademandcomesfromthecontrollerwhichcausestheanalogueoutputtoriseorfall,thenanOutputDelay(r15,SetpointPage)willbestarted.Withinthistimeperiod,theoutputsignalchangesonlybyasetpercentagerate(StepSize,r16).If"r16"issetto"100%"and"r15"to"0",thenthefunctionisde-activated.TheseparametersapplytoallPIfunctionswhichcanberealizedbytheanalogueoutput.

Control Characteristic (SP)

t

t

r14:PIintegraltime

I-part

P-part

5Vresp.12mA

max.

min.

r15:

pro

porti

onal

ban

d

outp

utse

tpoi

ntde

viat

ion

Page 14: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140Page14

Theschemebesideshowsbriefly,howthedatalinewiringofseveralcontrollersviathe'network/line'interfaceismade.Ateachcontroller,theshieldhastobeconnectedto thenearestgroundterminal(PE).Alsothegroundconnectorofthecontroller(term.1)andterminal#24mustbeconnectedtothenearestgroundterminal.Thiswill assuregood interferencesuppression,evenforlongdatalinesbetweenthecontrollers.

TheMSRecocanbeusedasaCentralUnitforupto64ColdStorageControllersoftheseriesEVPandTKP.Thesecanbeconnectedviaaseparatenetworkinterface.Shieldingmustbeconnectedtothenearestgroundterminal.Alsothegroundconnectorofthecontroller(term.1)andterminal#24mustbeconnectedtothenearestgroundterminal.

Each connected controller gets an individualaddress,whichmustbesetatthecontrollerandontheAddressPage(A)underA00...A63.Thus,datacanbecentralizedandforwardedforoptimizationofthecontrolfunctions.On the ‚Address Page‘, the controller ‚type‘mustbeselectedvia‚d01‘foreachaddress,aswell as the influence on the suction pressureshiftingof theMSRecovia ‚d02andd03‘ foreachaddress.

Connection of Cold Storage Controllers as Slaves

Wiring of data lines (Network Line)

Networking of controllers via E-LINK

The MSR eco can be networked together withotherELREHAcontroldevicesviaanRS-485-2-wiredatabus,whichenablesupto78controllerstocommunicate.Forcommunication,theE-LINKtransmissionprotocolisused.Each controller in a network has its individualaddress('P90',ModePage).

!! Never use address 64 !!

Thedatatransmissionrateisfactorysetto"96"(9600Baud)andcanalsobesetmanually("P89",ModePage).IftheMSRecoisnotconnectedtoanetwork,theseparametersareofnoimportance. Remote control at Frontend SystemsTheMSRecocontrollercanbeoperatedremotelyvia interface when it is connected to FrontendSystemssuchasanSMZ.Inthiscase,theFrontendSystemshowsthedisplaycontentsandthekeysofthefrontendworkasiftheywherethekeysoftheMSReco.

Configuration / Service via PCThecontrollercanbelinkedtoaPCviaitsRS-485interface.ByusingthePC-software„Coolvision-MES“,parameterscanbechanged,theycanbesavedtotheharddisk(download)andcanbesenttothecontrollers(upload).Todothis,thePCmustbeequippedwithanRS-485interface(internalcardoraconverteroftheSSC-series).

Note

ProtectiveEarth

Earth

Note

ProtectiveEarth

Earth

RS-485(networkline)uptoany64modules

relay K1

N1 2 3

L4 5 6 7

242120 2322 25 26

RS485

NDO

DO

RS485

NDO

DO

RS485

NDO

DO

relay K1

N1 2 3

L4 5 6 7

242120 2322 25 26

RS485

NDO

DO

RS485

NDO

DO

RS485

NDO

DO

MSReco3140 MSReco3140

RS-485(Slave-Module)upto64ColdStorageControllers

relay K1

N1 2 3

L4 5 6 7

242120 2322 25 26

RS485

NDO

DO

RS485

NDO

DO

RS485

NDO

DO

N1 2 3

L4 5

242120 2322

RS485

NDO

DO

25 26

6N

1 2 3L

4 5

242120 2322

RS485

NDO

DO

25 26

6

MSReco3140

EVP3167/3168 EVP3167/3168

Page 15: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140 Page15

Rel

ayK

1(S

PDT)

Rel

ayK

2(S

SR)

Rel

ayK

3(S

SR)

Rel

ayK

4(S

PST)

Rel

ayK

5(S

SR)

Use

CR

IISy

stem

Pow

erC

ontro

l

Switc

hing

Out

putS

tage

1in

verte

d

Switc

hing

Out

putS

tage

2in

verte

d

Switc

hing

Out

putS

tage

3in

verte

d

Switc

hing

Out

putS

tage

4in

verte

d

Switc

hing

Out

putS

tage

5in

verte

d

Num

bero

fsta

ges

com

pres

sor1

Num

bero

fsta

ges

com

pres

sor2

Num

bero

fsta

ges

com

pres

sor3

Num

bero

fsta

ges

com

pres

sor4

No.

prio

r.co

mpr

esso

r

ApplicationNo.

CRII Compressor

OtherCompressor

h01 h02 h03 h04 h05

h49

h61

h62

h63

h64

h65

h51

h52

h53

h54

h50

CR II Compressor1 2-cyl. -- Alarm -- -- Motor1

CR(St.1)CRIIvalve1.1(St.2)

1 0 1 0 0 2 0 0 0 1

2 2-cyl. 1x1stages Alarm -- Motor2(Stage3)

Motor1CR(St.1)

CRIIvalve1.1(St.2)

1 0 1 0 0 2 1 0 0 1

3 2-cyl. 2x1stages Alarm Motor3(Stage4)

Motor2(Stage3)

Motor1CR(St.1)

CRIIvalve1.1(St.2)

1 0 1 0 0 2 1 1 0 1

4 2-cyl. 1x2stages Alarm Motor2(Stage4)

MV2.1(Stage3)

Motor1CR(St.1)

CRIIvalve1.1(St.2)

1 0 1 0 0 2 2 0 0 1

5 4-cyl. -- Alarm -- CRIIvalve1.2(St.3)

Motor1CR(St.1)

CRIIvalve1.1(St.2)

1 0 1 1 0 3 0 0 0 1

6 4-cyl. 1x1stages Alarm Motor2(Stage4)

CRIIvalve1.2(St.3)

Motor1CR(St.1)

CRIIvalve1.1(St.2)

1 0 1 1 0 3 1 0 0 1

7 6-cyl. -- Alarm CRIIvalve1.3(St.4)

CRIIvalve1.2(St.3)

Motor1CR(St.1)

CRIIvalve1.1(St.2)

1 0 1 1 1 4 0 0 0 1

Conv. Compressor20 -- 2x1stages Alarm Motor1

(Stage1)Motor2

(Stage2)-- -- 0 0 0 0 0 1 1 0 0 0

21 -- 3x1stages Alarm Motor1(Stage1)

Motor2(Stage2)

Motor3(Stage3)

-- 0 0 0 0 0 1 1 1 0 0

22 -- 4x1stages Alarm Motor1(Stage1)

Motor2(Stage2)

Motor3(Stage3)

Motor4(Stage4)

0 0 0 0 0 1 1 1 1 0

23 -- 1x2stages Alarm Motor1(Stage1)

MV1.1(Stage2)

-- -- 0 0 1 0 0 2 0 0 0 0

24 -- 1x2stages+1x1stage

Alarm Motor1(Stage1)

MV1.1(Stage2)

Motor2(Stage3)

-- 0 0 1 0 0 2 1 0 0 0

25 -- 1x2stages+2x1stages

Alarm Motor1(Stage1)

MV1.1(Stage2)

Motor2(Stage3)

Motor3(Stage4)

0 0 1 0 0 2 1 1 0 0

26 -- 1x1stages+1x2stages

Alarm Motor1(Stage1)

Motor2(Stage2)

MV2.1(Stage3)

-- 0 0 0 1 0 1 2 0 0 0

27 -- 1x1stages+1x3stages

Alarm Motor1(Stage1)

Motor2(Stage2)

MV2.1(Stage3)

MV2.2(Stage4)

0 0 0 1 1 1 3 0 0 0

28 -- 2x2stages Alarm Motor1(Stage1)

MV1.1(Stage2)

Motor2(Stage3)

MV2.2(Stage4)

0 0 1 0 1 2 2 0 0 0

29 -- 1x3stages Alarm Motor1(Stage1)

MV1.1(Stage2)

MV1.2(Stage3)

-- 0 0 1 1 0 0 3 0 0 0

30 -- 1x3stages+1x1stages

Alarm Motor1(Stage1)

MV1.1(Stage2)

MV1.2(Stage3)

Motor2(Stage4)

0 0 1 1 0 3 1 0 0 0

31 -- 1x4stages Alarm Motor1(Stage1)

MV1.1(Stage2)

MV1.2(Stage3)

MV1.3(Stage4)

0 0 1 1 1 4 0 0 0 0

Configuration examples for up to 4 suction pressure stages

Thistablegivesyouanoverviewoftheparameterswhichmustbesetforspecificplantstructures.

Page 16: ELEKTRONISCHE REGELUNGEN GMBH Technical Manual · EVP ELREHA P Convenient 3 key control for all functions clearly appear on a 7 segment LED display. 4 symbols to the right indicate

TechnicalManualStageControllerMSReco3140Page16

For the device MSReco 3140 we state the following: When operated in accordance with the technical manual, the criteria have been met that are outlined in the EMC Directive 2014/30/EC and the Low Voltage Directive 2014/35/EC. This declaration is valid for those products covered by the technical manual which itself is part of the declaration.Following standards were consulted for the conformity testing to meet the requirements of EMC and Low Voltage Guidelines: EN 55011:2016+A1:2017, EN 61010-1:2010, EN 61326-1:2013 CE marking of year: 2018

This statement is made for the manufacturer / importer by:

ELREHA Elektronische Regelungen GmbH Werner Roemer, Technical Director D-68766 Hockenheim www.elreha.de Hockenheim ......2018-06-26.......................................................................(Name / Address) City Date Signature

EC Declaration of Conformity

Thismanual,whichispartoftheproduct,hasbeensetupwithcareandourbestknowledge,butmistakesarestillpossible.Technicaldetailscanbechangedwithoutnotice,especiallythesoftware.Pleasenotethatthedescribedfunctionsareonlyvalidforunitscontainingthesoftwarewiththeversion-numbershownonpage1ofthismanual.Unitswithanotherversionnumbermayworkalittlebitdifferent.