Electromagnetic Compatibilit1

download Electromagnetic Compatibilit1

of 2

Transcript of Electromagnetic Compatibilit1

  • 7/28/2019 Electromagnetic Compatibilit1

    1/2

    Electromagnetic Compatibility (EMC) and Variable Speed Drives

    Editors Note: Much of the information which follows is taken from engineering information

    provided by Siemens AG in their Sinamics DCM Converter Units catalog D 23.1 2010. The

    Sinamics DCM is the line of industrial DC drives in the Sinamics family, which forms a part of

    Siemens Totally Integrated Automation concept; learn more atwww.siemens.com. However,

    the concepts discussed herein can generally be applied to any drive application.

    Because of the high switching frequencies of their electronic components, variable speed drives are

    by their nature radiating devices. This radiated energy is termed electromagnetic interference

    (EMI); measures to reduce EMI during design and installation are intended to ensure

    electromagnetic compatibility (EMC), which is essentially the ability of a device to function

    satisfactorily in an electromagnetic environment without itself causing interference unacceptable to

    other devices in the environment.

    In the typical industrial environment, EMI occurs in the range of 150kHz 30 MHz and can have

    adverse consequences on the operation of nearby sensitive equipment. When consideringmeasures to ensure EMC, the drive must be looked at as forming part of a system, the other

    components being minimally the cables and motor. Mitigation involves several design and

    installation practices involving all of these components. In the US, measures are usually focused

    on reducing interference to ensure the proper operation of sensitive devices such as PLCs,

    sensors, and transducers. In Europe, and in more susceptible US applications, documented

    compliance with IEC/EN product standard 61800-3 is often required. This standard describes the

    requirements for EMC compliance for Power Drive Systems (PDS) and is structured to consider the

    location and sensitivity of equipment likely to be present in a given environment. In any case, the

    following practical rules will go a long way toward ensuring that the PDS operates without causing

    undue interference within the industrial environment:

    Rule 1: All metal parts of the control cabinet are connected with one another through a largesurface area with a good electrical connection (not paint on paint!). If required, contact or serrated

    washers should be used. The cabinet door must be connected to the cabinet using the shortest

    possible grounding straps (at the top, center, and bottom).

    Do not rely on the cabinet hinge(s) for this purpose.

    Rule 2: Contactors, relays, solenoid valves, electromechanical counters, etc., in the cabinet and

    where applicable, in neighboring cabinets must be provided with surge protection, e.g. RC

    elements, varistors, and diodes. The protective circuit must be directly connected to the particular

    coil.

    Rule 3: Signal cables should only be routed at just one level in the cabinet, if at all possible.

    Rule 4: Unshielded cables in the same circuit (outgoing/incoming conductors) must be twisted

    wherever possible, or the area between them minimized, to prevent the unnecessary formation of

    frame antennae.

    This also can reduce the effects of capacitive coupling at higher frequencies. Cables designed

    specifically for drive applications, whether shielded or not, are symmetrically fabricated to take this

    into account.

    Rule 5: Connect spare wires to the cabinet ground at both ends . This achieves an additional

    shielding effect.

    This also reduces their ability to radiate if not low-impedance grounded.

    Rule 6: Avoid unnecessary cable lengths. This keeps coupling capacitances and inductances low.

  • 7/28/2019 Electromagnetic Compatibilit1

    2/2

    Rule 7: Crosstalk is generally reduced if cables are routed close to the control cabinet ground.

    Therefore, do not route cables freely around the cabinet, but route them as close as possible to

    the cabinet enclosure or to the mounting plates. This also applies to spare cables.

    Rule 8: Signal and power cables must be physically separated to prevent coupling paths. A

    minimum distance of 20 cm must be observed.

    If it is not physically possible to separate the conductors by distance, encase them in separate

    metallic conduits, with each conduit being solidly bonded throughout its length. (Note that other

    manufacturers have differing recommendations for conductor spacing, but the same general rule

    applies route the line, load, and signal conductors at a distance from one another.) Also, if

    routed at or near the recommended separation distances, avoid routing them in parallel for any

    distance; if they must cross, they are to do so at 90-degree angles.

    Rule 9: Ground the shields ofdigital signal cables at both ends (source and destination), ensuring

    maximum contact area and good conductivity. In the event of poor equipotential bonding between

    the shield connections, run an additional equipotential bonding conductor with a cross-section of at

    least 10 sq. mm parallel to the shield for the purpose of reducing the shield current. Generally

    speaking, the shields may also be connected to the cabinet enclosure (ground) at several points.The shields can be connected several times even outside the control cabinet.

    In each case, however, 360-degree shield bonding is required for good conductivity. Also bear in

    mind that the best way to ensure shield integrity is not to break the shield so minimize cable

    terminations wherever possible. Foil-type shields should be avoided, as they are at least 5 times

    less effective than braided shields.

    Rule 10: Connect shields for analog signal cables at one end to prevent low-frequency, capacitive

    interference from being coupled in (e.g. 50/60 Hz hum). In this case, the shield should be

    connected in the control cabinet(i.e. at the source end).

    Also keep in mind that the power conductors, particularly the motor leads, are typically the most

    severe source of EMI and should always be considered first when assessing EMC. Shielded cablesare usually recommended, especially for smaller motors and/or in sensitive applications. Unlike

    signal cable shields, power cable shields should be connected at bothends.

    If youd like additional information or assistance, please contact us [email protected], drop by

    our web site (www.joliettech.com), or visit the Comments section to drop off some

    thoughts/questions. And check back next week for another installment.

    (Posted on behalf of one of our readers):

    In the past I sent a problem on a RTD over load from a VFD drive.

    We have found a solution.

    First the problem:The person who wired up the VFD at the factory, feed the ground to the RTD cards and Relay

    panel.

    On the same wire. Feeding through one RTD board to the next and then to the relay panel.

    This caused a different ground load on the RTD cards causing them to fail.

    Solution:

    We removed the ground wire from the ground lug at the RTD cards and the relay panel.

    This will allow the board ground to keep the same as rest of the VFD.

    RTD boards are grounded on the back side to the VFD back board. The ground lug is connected to

    this connection after it is runs through the board (picking up the shields from the RTD wires from

    the motor) and is a bleed off for the RTD wires and the board the Back plate ground connection is

    for the board then the RTD wires at the opposite end of the board from the ground lug.

    Figured some one might have the same problem.

    mailto:[email protected]:[email protected]:[email protected]:[email protected]