ELECTRICAL SYMBOLS LIST 15...AF AMPERE FRAME AFF ABOVE FINISHED FLOOR AIC AMPERE INTERRUPTING...

4
LIGHTING FIXTURES. REFER TO "LIGHTING FIXTURE SCHEDULE". EMERGENCY LIGHTING FIXTURES. REFER TO "LIGHTING FIXTURE SCHEDULE". ABBREVIATIONS (NOT ALL ABBREVIATIONS ARE NECESSARILY USED ON THIS PROJECT) + MOUNTING HEIGHT ABOVE FINISHED FLOOR COORDINATE WITH ARCHITECTURAL PLANS (E) EXISTING TO REMAIN (ER) EXISTING TO BE REMOVED (ERR) REMOVED & RELOCATED (ERRO) REMOVED & RETURNED TO OWNER (N) NEW (RE) RELOCATED EXISTING 1P SINGLE POLE 2P TWO POLE 3P THREE POLE A AMPERE AF AMPERE FRAME AFF ABOVE FINISHED FLOOR AIC AMPERE INTERRUPTING CAPACITY AT AMPERE TRIP ATS AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GAUGE BLDG BUILDING C CONDUIT & DEGREE CELSIUS CB CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CD CANDELA CL CEILING MOUNT CKT CIRCUIT CONT CONTINUATION CU COPPER DEG DEGREE DIA DIAMETER DISC DISCONNECT DIV DIVISION EA EACH EC ELECTRICAL CONTRACTOR ELEC ELECTRICAL EM EMERGENCY EMT ELECTRICAL METALLIC TUBING ) DEGREE FAHRENHEIT FA FIRE ALARM FACP FIRE ALARM CONTROL PANEL FAAP FIRE ALARM ANNUNCIATOR PANEL FATC FIRE ALARM TERMINATION CABINET FC FOOT CANDLE FDR FEEDER FL FLOOR FLA FULL LOAD AMPERES FLEX FLEXIBLE FMC FLEXIBLE METAL CONDUIT G GROUND GFI GROUND FAULT INTERRUPTER GRC GALVANIZED RIGID CONDUIT HP HORSE POWER HZ HERTZ IG ISOLATED GROUND IMC INTERMEDIATE METAL CONDUIT JB JUNCTION BOX KCMIL THOUSAND CIRCULAR MILS KV KILOVOLT KVA KILOVOLT AMPERE KW KILOWATT KWH KILOWATT HOUR LTG LIGHTING MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MCM THOUSAND CIRCULAR MILS MI MINERAL INSULATED CABLE MTD MOUNTED N NEUTRAL NC NORMALLY CLOSED NO NORMALLY OPEN P POLE PB PULL BOX PHASE PNL PANEL PVC POLYVINYL CHLORIDE CONDUIT PWR POWER REC RECEPTACLE RMC RIGID METAL CONDUIT SPD SURGE PROTECTION DEVICE SPEC SPECIFICATION SW SWITCH SWBD SWITCHBOARD SYS SYSTEMS TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION TYP TYPICAL UON UNLESS OTHERWISE NOTED UPS UNINTERRUPTED POWER SUPPLY V VOLTS VIF VERIFY IN FIELD VFD VARIABLE FREQUENCY DRIVE WP WEATHERPROOF XFMR TRANSFORMER Y WYE ǻ DELTA VOICE / DATA SYMBOLS RISER / SINGLE LINE SYMBOLS POWER SYMBOLS 100/90/3 ATS 100A 480V,4P 208/120V 460V 500KVA 60/30/3 MOTOR RATED TOGGLE SWITCH, 20A SINGLE POLE, UON HORSEPOWER RATED WITH OVERLOAD PROTECTION. SINGLE POLE SWITCH FLUSH WALL MOUNTED @ 48" AFF, UON 3 = THREE-WAY 4 = FOUR-WAY D = INTEGRAL DIMMER OS = INTEGRATED OCCUPANCY SENSOR HOMERUN-NUMERAL WHERE USED INDICATES DESIGNATED PANEL AND CIRCUIT NUMBER FOR REFERENCE ONLY. WHERE CONDUIT IS NOT SPECIFIED USE AC OR MC CABLE FOR APPLICATION. 2#12, #12G, 3/4"C HOMERUN, UON 3#12, #12G, 3/4"C HOMERUN, UON 4#12, #12G, 3/4"C HOMERUN, UON AT 120V AND OVER 100' CIRCUIT LENGTH PROVIDE #10 MINIMUM. AT 277V AND OVER 200' CIRCUIT LENGTH PROVIDE #10 MINIMUM. 15 or 20A, 125V QUADRUPLEX RECEPTACLE, W/ ISOLATED GROUND FLUSH WALL MOUNTED @ 18" AFF, UON NUMBER INDICATES QUANTITIES OF IG TYPE RECEPTACLES. 1 = ONE DUPLEX IG TYPE & ONE DUPLEX STANDARD G. RECEPTACLE 2 = QUADRUPLEX IG TYPE RECEPTACLES JUNCTION BOX MOUNTED ABOVE SUSPENDED CEILING / FLUSH WALL INSTALLED WITHIN 2' OF EQUIPMENT AND CONNECTED VAV = DEDICATED TO VARIABLE AIR VOLUME BOX CONTROL SD = DEDICATED TO SMOKE DAMPER MD = DEDICATED TO MOTORIZED VOLUME DAMPER UH = UNIT HEATER EWC = ELECTRIC WATER COOLER DMO = DOOR MOTOR OPERATOR VOICE/DATA OUTLET FLUSH WALL MOUNTED @ 18" AFF UON, WITH 3/4" CONDUIT IN DEMISING WALL, 7(50,1$7(' ,1 $ %(1' ,172 $&&(66,%/( &(,/,1* SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED FLUSH CEILING MOUNTED 20A, 125V QUADRUPLEX RECEPTACLE FLUSH CEILING MOUNTED 20A, 125V DUPLEX RECEPTACLE FLUSH CEILING MOUNTED 3 PHASE SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED FLUSH WALL MOUNTED @ 18" AFF, UON SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED FLUSH WALL MOUNTED @ 18" AFF, UON DROP CORD RECEPTACLE CEILING MOUNTED 15 or 20A, 125V SURGE SUPPRESSION DUPLEX RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON 15 or 20A, 125V DUPLEX RECEPTACLE CONTROLLED BY WALL SWITCH FLUSH WALL MOUNTED @ 48" AFF, UON 20A, 125V, 2P W/G. SINGLE RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON EWC = ELECTRIC WATER COOLER 15 or 20A, 125V EMERGENCY QUADRUPLEX RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON 15 or 20A, 125V EMERGENCY DUPLEX RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON 15 or 20A, 125V DUPLEX RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON C = GRAY COLORED RECEPTACLE FOR COMPUTERS T = TAMPER PROOF XP = EXPLOSION PROOF 15 or 20A, 125V QUADRUPLEX RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON 15 or 20A, 125V DUPLEX RECEPTACLE, GFI TYPE FLUSH WALL MOUNTED @ 18" AFF, UON WP = WEATHER PROOF 15 or 20A, 125V SINGLE RECEPTACLE, W/ ISOLATED GROUND FLUSH WALL MOUNTED @ 18" AFF, UON 15 or 20A, 125V DUPLEX RECEPTACLE, W/ ISOLATED GROUND FLUSH WALL MOUNTED @ 18" AFF, UON TAPBOX, SPLICE BOX CONDUIT OR RACEWAY TURNING UP CONDUIT OR RACEWAY TURNING DOWN CAPPED CONDUIT CONDUIT WITH BUSHING NEW UNDERGROUND/UNDER SLAB CONDUIT SPLICE (JUNCTION) OF PATHS OF CONDUCTORS OR CABLES. TRANSFORMER COMBINATION MOTOR CONTROLLER / DISCONNECT SWITCH <SWITCH AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED VFD = VARIABLE FREQUENCY DRIVE UNFUSED DISCONNECT SWITCH <SWITCH AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED FUSED DISCONNECT SWITCH <SWITCH AMPS>/<FUSE AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED ENCLOSED CIRCUIT BREAKER <FRAME AMPS>/<TRIP AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED ST = SHUNT TRIP 208/120V PANELBOARD SURFACE MOUNTED 208/120V PANELBOARD FLUSH MOUNTED 208/120V DISTRIBUTION PANELBOARD SURFACE MOUNTED 480/277V PANELBOARD SURFACE MOUNTED 480/277V PANELBOARD FLUSH MOUNTED 480/277V DISTRIBUTION PANELBOARD SURFACE MOUNTED MOTOR GENERATOR GROUND CONNECTION TRANSFER SWITCH ATS = AUTOMATIC TRANSFER MTS = MANUAL TRANSFER POLES AND RATING AS NOTED POWER TRANSFORMER VOLTAGES, WINDINGS AND SIZE AS INDICATED CIRCUIT BREAKER - MOLDED CASE TYPE <FRAME AMPS>/<TRIP AMPS>/<POLES> CURRENT TRANSFORMER FLOOR MOUNTED METAL SUPPORT FRAME FOR ELECTRICAL ENCLOSURES NEW LOW VOLTAGE/CONTROL WIRING VFD ANNOTATION SYMBOLS KEY NOTE EQUIPMENT PROVIDED BY OTHERS ST NEW GROUND CABLE 100/3 30/3 100/60/3 NEW CONDUIT/CIRCUIT/EQUIPMENT ELECTRICAL SYMBOLS LIST (NOT ALL SYMBOLS ARE NECESSARILY USED ON THIS PROJECT) 20/1 GENERAL NOTES 1. THE SUBMISSION OF A BID BY THE ELECTRICAL CONTRACTOR IS NOTIFICATION THAT THE ELECTRICAL CONTRACTOR HAS TOTALLY FAMILIARIZED HIMSELF WITH THE CONTRACT DOCUMENTS AND EXISTING SITE CONDITIONS AND HAS AGREED TO PROVIDE THE NECESSARY LABOR AND MATERIAL FOR THE COMPLETE INSTALLATION OF EACH SYSTEM IN A NEAT AND WORKMANLIKE MANNER IN ACCORDANCE WITH THE BEST PRACTICES OF THE INDUSTRY AND IN COMPLIANCE WITH ALL AUTHORITIES HAVING JURISDICTION. 2. THESE DRAWINGS ARE PRESENTED TO THE ELECTRICAL CONTRACTOR WITH THE UNDERSTANDING THAT THE ELECTRICAL CONTRACTOR IS AN EXPERT AND COMPETENT IN THE PREPARATION OF CONTRACT BID PRICES ON THE BASIS OF INFORMATION SUCH AS IS CONTAINED IN THESE DOCUMENTS. IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED AND READY FOR OPERATION AND IN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULES, AND REGULATIONS. MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTLY NECESSARY FOR THE PROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE INCLUDED IN THE WORK AND IN THE PROPOSAL THE SAME AS IF SPECIFIED OR SHOWN ON THE DRAWINGS. IF ANY DEPARTURES FROM THE DRAWINGS ARE DEEMED NECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF SEPTA. 3. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND SHALL ADVISE THE PROJECT MANAGER AND THE OWNER OF ANY DISCREPANCIES BEFORE PERFORMING THE WORK. 4. THE DRAWINGS INDICATE ARRANGEMENTS AND APPROXIMATE SIZES AND RELATIVE LOCATIONS OF PRINCIPAL APPARATUS, EQUIPMENT, DEVICES, AND SERVICES TO BE PROVIDED. DRAWINGS ARE DIAGRAMMATIC AND ARE A GRAPHIC REPRESENTATION OF CONTRACT REQUIREMENTS TO THE BEST AVAILABLE STANDARDS AT THE SCALE INDICATED. 5. LAYOUT OF EQUIPMENT INDICATED ON THE DRAWINGS SHALL BE CHECKED AND COMPARED AGAINST ALL DRAWINGS AND SPECIFICATIONS OF ALL TRADES AND EXACT LOCATIONS DETERMINED USING APPROVED SHOP DRAWINGS OF SUCH EQUIPMENT. WHERE PHYSICAL INTERFERENCES OCCUR, CONSULT WITH THE PROJECT MANAGER AND PREPARE DATED, DIMENSIONED DRAWINGS COORDINATED WITH ALL OTHER TRADES WORKING IN THIS AREA AND CORRECTING SUCH INTERFERENCE. 6. ELECTRICAL CONTRACTOR SHALL SCHEDULE HIS WORK IN ACCORDANCE WITH THE CONSTRUCTION SCHEDULE SO THAT ALL OF HIS WORK CAN BE INSTALLED WITHOUT DELAYING THE PROJECT. ALL WORK RELATED TO SHUTDOWN OF EXISTING SERVICES SHALL BE PERFORMED AT THE HOURS DESIGNATED BY SEPTA WITH ALL ASSOCIATED COSTS BORNE BY THE ELECTRICAL CONTRACTOR AT NO COST TO SEPTA. PROVIDE ANY TEMPORARY FACILITIES REQUIRED TO PERMIT SEPTA'S USE OF EXISTING FACILITIES AND SYSTEMS TO REMAIN UNDISTURBED. COORDINATE ALL WORK, INCLUDING ALL SHUTDOWNS THAT AFFECT SYSTEMS AND/OR PORTIONS OF THE BUILDING THAT MUST REMAIN IN OPERATION, WITH SEPTA. 7. ELECTRICAL CONTRACTOR SHALL SECURE AND PAY ALL FEES, LICENSES, INSPECTIONS, AND PERMITS PERTAINING TO THE CONTRACT. SUBMIT TO SEPTA DUPLICATE CERTIFICATES OF INSPECTION FROM APPROVED INSPECTION AGENCY. 8. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS. 9. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WORKMEN'S IDENTIFICATION AND BADGING, SAFETY AND FIRE PROTECTION, BARRICADES, WARNING SIGNS, TRASH REMOVAL, CUTTING AND PATCHING. 10. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING, AND PROTECTION OF MATERIALS. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WITHOUT BLEMISH OR DEFECT. ALL EQUIPMENT INSTALLED SHALL BEAR THE LABEL OF AN APPROVED AGENCY. 11. ELECTRICAL CONTRACTOR SHALL PROVIDE LABOR TO RECEIVE, UNLOAD, STORE, PROTECT, AND TRANSFER TO POINT OF INSTALLATION FOR ALL FURNISHED ITEMS. 12. WHERE CONDUIT, CABLES, DUCTWORK, OR PIPING PASSES THROUGH FIRE RATED FLOORS OR WALLS, THE PENETRATION SHALL BE COMPLETELY SEALED WITH A FIRE STOP MATERIAL THAT IS UL LISTED, FM GLOBAL APPROVED (WWW.FMGLOBAL.COM/PAGE.ASPX?ID=50030000) AND ACCEPTED BY THE BUILDING DEPARTMENT AND FIRE DEPARTMENT AS BEING SUITABLE FOR THIS SERVICE. THIS MATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER TO MAINTAIN THE UL LISTED FIRE RATING OF THE PENETRATED WALL OR FLOOR. 13. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SLAB OPENINGS, WALL OPENINGS, BEAM PENETRATIONS, AND CORING AS IT RELATES TO HIS WORK. ELECTRICAL CONTRACTOR SHALL SUBMIT SIZE AND LOCATION FOR REVIEW AND APPROVAL. 14. ALL EXTERIOR WALL OPENINGS SHALL BE SLEEVED, PROPERLY CAULKED, AND SEALED WITH A HIGH QUALITY SEALANT TO PREVENT INFILTRATION OF MOISTURE AND OUTSIDE AIR. 15. CONTRACTOR SHALL SUBMIT SCHEDULE OF SUBMITTALS PRIOR TO SUBMITTING ANY SHOP DRAWINGS, ETC. TO BE SUBMITTED FOR THIS PROJECT, INCLUDING THE ANTICIPATED DATE OF EACH SUBMISSION. CONTRACTORS SHALL SUBMIT (6) SETS OF COMPLETE SHOP DRAWINGS AND CATALOG CUTS, WIRING DIAGRAMS AND ASSOCIATED DATA TO THE PROJECT MANAGER FOR APPROVAL PRIOR TO PURCHASING EQUIPMENT OR STARTING ANY WORK. ANY WORK INSTALLED OR EQUIPMENT PURCHASED PRIOR TO RECEIPT OF PROJECT MANAGER APPROVED SHOP DRAWINGS THAT REQUIRES CHANGES SHALL BE REPLACED AT CONTRACTOR'S EXPENSE. 16. SUBMIT CATALOG INFORMATION, FACTORY ASSEMBLY DRAWINGS AND FIELD INSTALLATION DRAWINGS AS REQUIRED FOR A COMPLETE EXPLANATION AND DESCRIPTION OF ALL ITEMS TO BE PROVIDED. THE ELECTRICAL CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOP DRAWINGS. NO SUBMISSION WILL BE ACCEPTED WITHOUT THE SIGNED APPROVAL OF THE ELECTRICAL CONTRACTOR. THE ELECTRICAL CONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS. 17. UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL SUPPLY THE PROJECT MANAGER WITH (1) COMPLETE SET OF CAD AS-BUILT DRAWINGS IN AUTOCAD 2000 AT CONTRACTOR'S EXPENSE AND (3) &203/(7( %281' &23,(6 2) 23(5$7,21 $1' 0$,17(1$1&( 0$18$/6 7+(6( 6+$// %( 3529,'(' 72 SEPTA AT CONTRACTOR'S EXPENSE. CONTRACTOR SHALL INSTRUCT SEPTA'S PERSONNEL WITH REGARD TO THE PROPER OPERATION OF ALL SYSTEMS TO THE SATISFACTION OF SEPTA. 18. ALL WORK FURNISHED UNDER THE CONTRACT SHALL BE GUARANTEED AGAINST ANY AND ALL DEFECTS IN WORKMANSHIP AND/OR MATERIALS FOR A PERIOD OF NOT LESS THAN (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THE INSTALLATION. ANY DEFECTS OF WORKMANSHIP DEVELOPING DURING THIS PERIOD SHALL BE REMEDIED AND ANY DEFECTIVE MATERIAL REPLACED WITHOUT ADDITIONAL COST TO SEPTA. 19. INSTALLED SYSTEMS SHALL OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT SOUND OR VIBRATION THAT IS OBJECTABLE TO THE PROJECT MANAGER, OR SEPTA. OBJECTABLE SOUND OR VIBRATION CONDITIONS DUE TO WORKMANSHIP SHALL BE CORRECTED IN APPROVED MANNER BY THE ELECTRICAL CONTRACTOR AT HIS EXPENSE. 20. ELECTRICAL CONTRACTOR SHALL SIMILARLY NOTIFY ENGINEER OF COMPLETION OF ALL WORK, INDICATING THE ELECTRICAL CONTRACTOR IS READY FOR THE ENGINEER TO PERFORM THE FINAL PUNCHLIST INSPECTION. 21. UPON COMPLETION OF ALL UNFINISHED OR FAULTY WORK NOTED IN ENGINEER FINAL PUNCH LIST, THE ELECTRICAL CONTRACTOR SHALL SUBMIT TO THE ENGINEER IN WRITING A LETTER OF COMPLETION CERTIFYING THAT ALL PUNCH LIST ITEMS HAVE BEEN COMPLETED AND ALL AS-BUILTS, MANUALS, ETC. HAVE BEEN SUBMITTED. 22. SHOULD A CONTRACTOR REQUIRE REMOVAL, RELOCATION, OR REROUTING OF ANOTHER TRADE'S WORK THAT IS NOT INDICATED ON DRAWINGS, THE CONTRACTOR REQUIRING SUCH WORK SHALL BE RESPONSIBLE FOR THAT WORK, AND PAY ALL REQUIRED COSTS. 23. ALL WORK INVOLVING ALTERATIONS TO EXISTING SYSTEMS, EQUIPMENT, AND MATERIALS SHALL BE REVIEWED WITH THE PROJECT MANAGER AND SEPTA BEFORE BEGINNING WORK. 24. DEFINITION: UNLESS OTHERWISE NOTED, ALL WORK SPECIFIED HEREIN OR NOTED ON DRAWINGS, SHALL BE BY THE ELECTRICAL CONTRACTOR. ALL REFERENCES TO "CONTRACTOR" OR "THIS CONTRACTOR" ON DRAWINGS OR SPECIFICATIONS ARE ADDRESSED TO THE ELECTRICAL CONTRACTOR. THE TERM "PROVIDE" WHENEVER ENCOUNTERED ON DRAWINGS OR IN THESE SPECIFICATIONS, SHALL MEAN "FURNISH AND INSTALL." 25. CODES AND STANDARDS: ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE, ALL APPLICABLE CODES, SPECIFICATIONS, LOCAL ORDINANCES, INDUSTRY STANDARDS, UTILITY COMPANY REGULATIONS AND FIRE INSURANCE CARRIER'S REQUIREMENTS. 26. MATERIALS: ALL MATERIALS FURNISHED BY THIS CONTRACTOR, SHALL BE NEW AND BEAR THE LABEL OR LISTING OF A NATIONALLY RECOGNIZED INDEPENDENT TESTING LABORATORY. 27. OUTLET AND SWITCH BOXES: PROVIDE AND INSTALL OUTLET BOXES OF PROPER TYPE AND SIZE AS REQUIRED AT ALL OUTLETS WHERE SHOWN. SECURED FIRMLY IN PLACE AND SET TRUE AND SQUARE AND FLUSH WITH THE FINISHED SURFACE. 28. INSTALLATION OF RACEWAYS: ALL RACEWAYS SHALL BE INSTALLED CONCEALED. NO SURFACE RACEWAY WILL BE ACCEPTED IN FINISHED AREAS. 29. WIRING: WIRING OF BRANCH CIRCUITS SHALL BE TYPE THHN/THWN IN RIGID GALVANIZED STEEL CONDUIT :+(5( (;326(' 2876,'( :,5(6 6+$// %( &233(5 $1' 6+$// %( 0,1 $:* 9 & $// RACEWAYS ARE SHOWN DIAGRAMMATICALLY, EXACT LOCATION TO BE DETERMINED ON THE JOB. EXACT LOCATION OF OUTLETS TO BE DETERMINED BY SEPTA. CONTRACTOR SHALL ARRANGE ALL NEW CIRCUITS IN PANELS SO AS TO BALANCE THE LOAD ON ALL PHASES. EXPOSED CONDUIT IN UNFINISHED AREAS SHALL BE EMT. CONDUIT DIRECTLY BURIED UNDERGROUND SHALL BE SCHEDULE 40 PVC WITH RGS ELBOWS AND STUB UPS. 30. A TYPED DIRECTORY CARD SHALL BE PROVIDED IN EACH PANEL WITH ADDED CIRCUITS TO INDICATE THE LOADS ACTUALLY SERVED. 31. PROVIDE NEW FIXTURES AS SPECIFIED ON LIGHTING FIXTURE SCHEDULE. ALL NEW LED LAMPS SHALL BE 3500K. 32. GROUNDING: SHALL BE IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 250. PROVIDE GROUND WIRES AS REQUIRED AND RESIZE CONDUIT IF NECESSARY. 33. DEMONSTRATION OF COMPLETE ELECTRICAL SYSTEMS: UPON COMPLETION OF THE WORK THIS CONTRACTOR SHALL OBTAIN A CERTIFICATE OF APPROVAL FROM ALL RECOGNIZED AGENCIES CONCERNED WITH THE WORK. CONTRACTOR SHALL NOTIFY AND MAKE ALL THE NECESSARY ARRANGEMENTS WITH THE INSPECTING AGENCY AND LOCAL AUTHORITIES SO THAT INSPECTION MAY BE CARRIED OUT AT THE PROPER TIME. 34. PROJECT MUST MEET FM GLOBAL STANDARDS (WWW.FMGLOBAL.COM/) METER LIGHTING SYMBOLS JUNCTION BOX OR POKE-THRU WITH COMBINATION POWER/DATA FLUSH FLOOR MOUNTED REFER TO DETAIL ON DRAWING E002 NEW EMERGENCY CIRCUIT UNDERGROUND SECONDARY CABLE SHOWN HERE FOR REFERENCE ONLY. SEE CIVIL PLANS UNDERGROUND TELEPHONE CABLE SHOWN HERE FOR REFERENCE ONLY. SEE CIVIL PLANS 2&&83$1&< 6(1625 5$1*( CEILING MOUNTED PHOTOCELL CONTROL SWITCH CEILING MOUNTED PHOTOCELL CONTROL SWITCH WALL MOUNTED @ 10" BELOW FINISHED CEILING ELECTRICALLY HELD UL LISTED RELAY FOR EMERGENCY LIGHTING. LIGHTING SHALL BE CONTROLLED BY SWITCH UNDER NORMAL POWER CONDITION FROM NORMAL SOURCE. IN EMERGENCY MODE THE RELAY SHALL ENABLE THE DEDICATED LIGHTING TO BE SWITCHED TO THE EMERGENCY SOURCE FOR FULL OPERATION. PROVIDE BODINE BALLAST #GTD OR SIMILIAR. TIME CLOCK MANHOLE ELECTRICALLY HELD UL LISTED RELAY FOR EMERGENCY LIGHTING. LIGHTING SHALL BE CONTROLLED BY SWITCH UNDER NORMAL POWER CONDITION FROM NORMAL SOURCE. IN EMERGENCY MODE THE RELAY SHALL ENABLE THE DEDICATED LIGHTING TO BE SWITCHED TO THE EMERGENCY SOURCE FOR FULL OPERATION. PROVIDE BODINE BALLAST #GTD OR SIMILIAR. ELECTRIC DOOR STRIKE CARD READER, PROVIDE 2"x4" JUNCTION BOX WALL MOUNTED @ 42" AFF UON ON NON-SECURED SIDE OF DOOR ADA ACCESS BUTTON, MAKE ALL FINAL CONNECTIONS TO DOOR CONTROLLER DOOR CONTROLLER SHEET NUMBER DWG. NO.: OF OF SHT. NO.: REV. NO.: SCALE: DRAWN BY: DATE: WORK ORDER NO.: SCALE FACTOR: CHECKED BY: ARCHIVE NO.: COMPUTER FILE NO.: ADDENDUM 1 4/17/15 1 MAN CWT CWT

Transcript of ELECTRICAL SYMBOLS LIST 15...AF AMPERE FRAME AFF ABOVE FINISHED FLOOR AIC AMPERE INTERRUPTING...

Page 1: ELECTRICAL SYMBOLS LIST 15...AF AMPERE FRAME AFF ABOVE FINISHED FLOOR AIC AMPERE INTERRUPTING CAPACITY AT AMPERE TRIP ATS AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GAUGE BLDG BUILDING

LIGHTING FIXTURES. REFER TO "LIGHTING FIXTURE SCHEDULE".

EMERGENCY LIGHTING FIXTURES. REFER TO "LIGHTING FIXTURE SCHEDULE".

ABBREVIATIONS

(NOT ALL ABBREVIATIONS ARE NECESSARILY

USED ON THIS PROJECT)

+ MOUNTING HEIGHT ABOVE FINISHED FLOOR

COORDINATE WITH ARCHITECTURAL PLANS

(E) EXISTING TO REMAIN

(ER) EXISTING TO BE REMOVED

(ERR) REMOVED & RELOCATED

(ERRO) REMOVED & RETURNED TO OWNER

(N) NEW

(RE) RELOCATED EXISTING

1P SINGLE POLE

2P TWO POLE

3P THREE POLE

A AMPERE

AF AMPERE FRAME

AFF ABOVE FINISHED FLOOR

AIC AMPERE INTERRUPTING CAPACITY

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BLDG BUILDING

C CONDUIT

°C DEGREE CELSIUS

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CD CANDELA

CL CEILING MOUNT

CKT CIRCUIT

CONT CONTINUATION

CU COPPER

DEG DEGREE

DIA DIAMETER

DISC DISCONNECT

DIV DIVISION

EA EACH

EC ELECTRICAL CONTRACTOR

ELEC ELECTRICAL

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

°F DEGREE FAHRENHEIT

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FAAP FIRE ALARM ANNUNCIATOR PANEL

FATC FIRE ALARM TERMINATION CABINET

FC FOOT CANDLE

FDR FEEDER

FL FLOOR

FLA FULL LOAD AMPERES

FLEX FLEXIBLE

FMC FLEXIBLE METAL CONDUIT

G GROUND

GFI GROUND FAULT INTERRUPTER

GRC GALVANIZED RIGID CONDUIT

HP HORSE POWER

HZ HERTZ

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

JB JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILS

KV KILOVOLT

KVA KILOVOLT AMPERE

KW KILOWATT

KWH KILOWATT HOUR

LTG LIGHTING

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCM THOUSAND CIRCULAR MILS

MI MINERAL INSULATED CABLE

MTD MOUNTED

N NEUTRAL

NC NORMALLY CLOSED

NO NORMALLY OPEN

P POLE

PB PULL BOX

Ø PHASE

PNL PANEL

PVC POLYVINYL CHLORIDE CONDUIT

PWR POWER

REC RECEPTACLE

RMC RIGID METAL CONDUIT

SPD SURGE PROTECTION DEVICE

SPEC SPECIFICATION

SW SWITCH

SWBD SWITCHBOARD

SYS SYSTEMS

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTED POWER SUPPLY

V VOLTS

VIF VERIFY IN FIELD

VFD VARIABLE FREQUENCY DRIVE

WP WEATHERPROOF

XFMR TRANSFORMER

Y WYE

Δ DELTA

VOICE / DATA SYMBOLS

RISER / SINGLE LINE SYMBOLS

POWER SYMBOLS

100/90/3

ATS

100A

480V,4P

208/120V

460V

500KVA

60/30/3

MOTOR RATED TOGGLE SWITCH, 20A SINGLE POLE, UON

HORSEPOWER RATED WITH OVERLOAD PROTECTION.

SINGLE POLE SWITCH

FLUSH WALL MOUNTED @ 48" AFF, UON

3 = THREE-WAY

4 = FOUR-WAY

D = INTEGRAL DIMMER

OS = INTEGRATED OCCUPANCY SENSOR

HOMERUN-NUMERAL WHERE USED INDICATES DESIGNATED PANEL AND CIRCUIT

NUMBER FOR REFERENCE ONLY. WHERE CONDUIT IS NOT SPECIFIED USE AC

OR MC CABLE FOR APPLICATION.

2#12, #12G, 3/4"C HOMERUN, UON

3#12, #12G, 3/4"C HOMERUN, UON

4#12, #12G, 3/4"C HOMERUN, UON

AT 120V AND OVER 100' CIRCUIT LENGTH PROVIDE #10 MINIMUM.

AT 277V AND OVER 200' CIRCUIT LENGTH PROVIDE #10 MINIMUM.

15 or 20A, 125V QUADRUPLEX RECEPTACLE, W/ ISOLATED GROUND

FLUSH WALL MOUNTED @ 18" AFF, UON

NUMBER INDICATES QUANTITIES OF IG TYPE RECEPTACLES.

1 = ONE DUPLEX IG TYPE & ONE DUPLEX STANDARD G. RECEPTACLE

2 = QUADRUPLEX IG TYPE RECEPTACLES

JUNCTION BOX

MOUNTED ABOVE SUSPENDED CEILING / FLUSH WALL

INSTALLED WITHIN 2' OF EQUIPMENT AND CONNECTED

VAV = DEDICATED TO VARIABLE AIR VOLUME BOX CONTROL

SD = DEDICATED TO SMOKE DAMPER

MD = DEDICATED TO MOTORIZED VOLUME DAMPER

UH = UNIT HEATER

EWC = ELECTRIC WATER COOLER

DMO = DOOR MOTOR OPERATOR

VOICE/DATA OUTLET

FLUSH WALL MOUNTED @ 18" AFF UON, WITH 3/4" CONDUIT IN DEMISING WALL,

TERMINATED IN A 90° BEND 6" INTO ACCESSIBLE CEILING

SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED

FLUSH CEILING MOUNTED

20A, 125V QUADRUPLEX RECEPTACLE

FLUSH CEILING MOUNTED

20A, 125V DUPLEX RECEPTACLE

FLUSH CEILING MOUNTED

3 PHASE SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED

FLUSH WALL MOUNTED @ 18" AFF, UON

SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED

FLUSH WALL MOUNTED @ 18" AFF, UON

DROP CORD RECEPTACLE

CEILING MOUNTED

15 or 20A, 125V SURGE SUPPRESSION DUPLEX RECEPTACLE

FLUSH WALL MOUNTED @ 18" AFF, UON

15 or 20A, 125V DUPLEX RECEPTACLE CONTROLLED BY WALL SWITCH

FLUSH WALL MOUNTED @ 48" AFF, UON

20A, 125V, 2P W/G. SINGLE RECEPTACLE

FLUSH WALL MOUNTED @ 18" AFF, UON

EWC = ELECTRIC WATER COOLER

15 or 20A, 125V EMERGENCY QUADRUPLEX RECEPTACLE

FLUSH WALL MOUNTED @ 18" AFF, UON

15 or 20A, 125V EMERGENCY DUPLEX RECEPTACLE

FLUSH WALL MOUNTED @ 18" AFF, UON

15 or 20A, 125V DUPLEX RECEPTACLE

FLUSH WALL MOUNTED @ 18" AFF, UON

C = GRAY COLORED RECEPTACLE FOR COMPUTERS

T = TAMPER PROOF

XP = EXPLOSION PROOF

15 or 20A, 125V QUADRUPLEX RECEPTACLE

FLUSH WALL MOUNTED @ 18" AFF, UON

15 or 20A, 125V DUPLEX RECEPTACLE, GFI TYPE

FLUSH WALL MOUNTED @ 18" AFF, UON

WP = WEATHER PROOF

15 or 20A, 125V SINGLE RECEPTACLE, W/ ISOLATED GROUND

FLUSH WALL MOUNTED @ 18" AFF, UON

15 or 20A, 125V DUPLEX RECEPTACLE, W/ ISOLATED GROUND

FLUSH WALL MOUNTED @ 18" AFF, UON

TAPBOX, SPLICE BOX

CONDUIT OR RACEWAY TURNING UP

CONDUIT OR RACEWAY TURNING DOWN

CAPPED CONDUIT

CONDUIT WITH BUSHING

NEW UNDERGROUND/UNDER SLAB CONDUIT

SPLICE (JUNCTION) OF PATHS OF CONDUCTORS OR CABLES.

TRANSFORMER

COMBINATION MOTOR CONTROLLER / DISCONNECT SWITCH

<SWITCH AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED

VFD = VARIABLE FREQUENCY DRIVE

UNFUSED DISCONNECT SWITCH

<SWITCH AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED

FUSED DISCONNECT SWITCH

<SWITCH AMPS>/<FUSE AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED

ENCLOSED CIRCUIT BREAKER

<FRAME AMPS>/<TRIP AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED

ST = SHUNT TRIP

208/120V PANELBOARD

SURFACE MOUNTED

208/120V PANELBOARD

FLUSH MOUNTED

208/120V DISTRIBUTION PANELBOARD

SURFACE MOUNTED

480/277V PANELBOARD

SURFACE MOUNTED

480/277V PANELBOARD

FLUSH MOUNTED

480/277V DISTRIBUTION PANELBOARD

SURFACE MOUNTED

MOTOR

GENERATOR

GROUND CONNECTION

TRANSFER SWITCH

ATS = AUTOMATIC TRANSFER

MTS = MANUAL TRANSFER

POLES AND RATING AS NOTED

POWER TRANSFORMER

VOLTAGES, WINDINGS AND SIZE AS INDICATED

CIRCUIT BREAKER - MOLDED CASE TYPE

<FRAME AMPS>/<TRIP AMPS>/<POLES>

CURRENT TRANSFORMER

FLOOR MOUNTED METAL SUPPORT FRAME FOR ELECTRICAL ENCLOSURES

NEW LOW VOLTAGE/CONTROL WIRING

VFD

ANNOTATION SYMBOLS

KEY NOTE

EQUIPMENT PROVIDED BY OTHERS

ST

NEW GROUND CABLE

100/3

30/3

100/60/3

NEW CONDUIT/CIRCUIT/EQUIPMENT

ELECTRICAL SYMBOLS LIST

(NOT ALL SYMBOLS ARE NECESSARILY USED ON THIS PROJECT)

20/1

GENERAL NOTES

1. THE SUBMISSION OF A BID BY THE ELECTRICAL CONTRACTOR IS NOTIFICATION THAT THE ELECTRICAL

CONTRACTOR HAS TOTALLY FAMILIARIZED HIMSELF WITH THE CONTRACT DOCUMENTS AND EXISTING SITE

CONDITIONS AND HAS AGREED TO PROVIDE THE NECESSARY LABOR AND MATERIAL FOR THE COMPLETE

INSTALLATION OF EACH SYSTEM IN A NEAT AND WORKMANLIKE MANNER IN ACCORDANCE WITH THE BEST

PRACTICES OF THE INDUSTRY AND IN COMPLIANCE WITH ALL AUTHORITIES HAVING JURISDICTION.

2. THESE DRAWINGS ARE PRESENTED TO THE ELECTRICAL CONTRACTOR WITH THE UNDERSTANDING THAT

THE ELECTRICAL CONTRACTOR IS AN EXPERT AND COMPETENT IN THE PREPARATION OF CONTRACT BID

PRICES ON THE BASIS OF INFORMATION SUCH AS IS CONTAINED IN THESE DOCUMENTS. IT IS THE INTENT

OF THE DRAWINGS AND SPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED AND READY FOR

OPERATION AND IN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULES, AND REGULATIONS.

MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTLY NECESSARY FOR THE PROPER

INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE INCLUDED IN THE WORK AND IN THE

PROPOSAL THE SAME AS IF SPECIFIED OR SHOWN ON THE DRAWINGS. IF ANY DEPARTURES FROM THE

DRAWINGS ARE DEEMED NECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASONS THEREFORE

SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT

PRIOR APPROVAL OF SEPTA.

3. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND SHALL

ADVISE THE PROJECT MANAGER AND THE OWNER OF ANY DISCREPANCIES BEFORE PERFORMING THE

WORK.

4. THE DRAWINGS INDICATE ARRANGEMENTS AND APPROXIMATE SIZES AND RELATIVE LOCATIONS OF

PRINCIPAL APPARATUS, EQUIPMENT, DEVICES, AND SERVICES TO BE PROVIDED. DRAWINGS ARE

DIAGRAMMATIC AND ARE A GRAPHIC REPRESENTATION OF CONTRACT REQUIREMENTS TO THE BEST

AVAILABLE STANDARDS AT THE SCALE INDICATED.

5. LAYOUT OF EQUIPMENT INDICATED ON THE DRAWINGS SHALL BE CHECKED AND COMPARED AGAINST ALL

DRAWINGS AND SPECIFICATIONS OF ALL TRADES AND EXACT LOCATIONS DETERMINED USING APPROVED

SHOP DRAWINGS OF SUCH EQUIPMENT. WHERE PHYSICAL INTERFERENCES OCCUR, CONSULT WITH THE

PROJECT MANAGER AND PREPARE DATED, DIMENSIONED DRAWINGS COORDINATED WITH ALL OTHER

TRADES WORKING IN THIS AREA AND CORRECTING SUCH INTERFERENCE.

6. ELECTRICAL CONTRACTOR SHALL SCHEDULE HIS WORK IN ACCORDANCE WITH THE CONSTRUCTION

SCHEDULE SO THAT ALL OF HIS WORK CAN BE INSTALLED WITHOUT DELAYING THE PROJECT. ALL WORK

RELATED TO SHUTDOWN OF EXISTING SERVICES SHALL BE PERFORMED AT THE HOURS DESIGNATED BY

SEPTA WITH ALL ASSOCIATED COSTS BORNE BY THE ELECTRICAL CONTRACTOR AT NO COST TO SEPTA.

PROVIDE ANY TEMPORARY FACILITIES REQUIRED TO PERMIT SEPTA'S USE OF EXISTING FACILITIES AND

SYSTEMS TO REMAIN UNDISTURBED. COORDINATE ALL WORK, INCLUDING ALL SHUTDOWNS THAT AFFECT

SYSTEMS AND/OR PORTIONS OF THE BUILDING THAT MUST REMAIN IN OPERATION, WITH SEPTA.

7. ELECTRICAL CONTRACTOR SHALL SECURE AND PAY ALL FEES, LICENSES, INSPECTIONS, AND PERMITS

PERTAINING TO THE CONTRACT. SUBMIT TO SEPTA DUPLICATE CERTIFICATES OF INSPECTION FROM

APPROVED INSPECTION AGENCY.

8. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S WRITTEN

INSTRUCTIONS.

9. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WORKMEN'S IDENTIFICATION AND BADGING,

SAFETY AND FIRE PROTECTION, BARRICADES, WARNING SIGNS, TRASH REMOVAL, CUTTING AND

PATCHING.

10. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING, AND PROTECTION OF

MATERIALS. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WITHOUT BLEMISH OR DEFECT. ALL

EQUIPMENT INSTALLED SHALL BEAR THE LABEL OF AN APPROVED AGENCY.

11. ELECTRICAL CONTRACTOR SHALL PROVIDE LABOR TO RECEIVE, UNLOAD, STORE, PROTECT, AND

TRANSFER TO POINT OF INSTALLATION FOR ALL FURNISHED ITEMS.

12. WHERE CONDUIT, CABLES, DUCTWORK, OR PIPING PASSES THROUGH FIRE RATED FLOORS OR WALLS, THE

PENETRATION SHALL BE COMPLETELY SEALED WITH A FIRE STOP MATERIAL THAT IS UL LISTED, FM

GLOBAL APPROVED (WWW.FMGLOBAL.COM/PAGE.ASPX?ID=50030000) AND ACCEPTED BY THE BUILDING

DEPARTMENT AND FIRE DEPARTMENT AS BEING SUITABLE FOR THIS SERVICE. THIS MATERIAL SHALL BE

INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER TO MAINTAIN THE UL

LISTED FIRE RATING OF THE PENETRATED WALL OR FLOOR.

13. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SLAB OPENINGS, WALL OPENINGS, BEAM

PENETRATIONS, AND CORING AS IT RELATES TO HIS WORK. ELECTRICAL CONTRACTOR SHALL SUBMIT SIZE

AND LOCATION FOR REVIEW AND APPROVAL.

14. ALL EXTERIOR WALL OPENINGS SHALL BE SLEEVED, PROPERLY CAULKED, AND SEALED WITH A HIGH

QUALITY SEALANT TO PREVENT INFILTRATION OF MOISTURE AND OUTSIDE AIR.

15. CONTRACTOR SHALL SUBMIT SCHEDULE OF SUBMITTALS PRIOR TO SUBMITTING ANY SHOP DRAWINGS,

ETC. TO BE SUBMITTED FOR THIS PROJECT, INCLUDING THE ANTICIPATED DATE OF EACH SUBMISSION.

CONTRACTORS SHALL SUBMIT (6) SETS OF COMPLETE SHOP DRAWINGS AND CATALOG CUTS, WIRING

DIAGRAMS AND ASSOCIATED DATA TO THE PROJECT MANAGER FOR APPROVAL PRIOR TO PURCHASING

EQUIPMENT OR STARTING ANY WORK. ANY WORK INSTALLED OR EQUIPMENT PURCHASED PRIOR TO

RECEIPT OF PROJECT MANAGER APPROVED SHOP DRAWINGS THAT REQUIRES CHANGES SHALL BE

REPLACED AT CONTRACTOR'S EXPENSE.

16. SUBMIT CATALOG INFORMATION, FACTORY ASSEMBLY DRAWINGS AND FIELD INSTALLATION DRAWINGS AS

REQUIRED FOR A COMPLETE EXPLANATION AND DESCRIPTION OF ALL ITEMS TO BE PROVIDED. THE

ELECTRICAL CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOP DRAWINGS. NO SUBMISSION WILL BE

ACCEPTED WITHOUT THE SIGNED APPROVAL OF THE ELECTRICAL CONTRACTOR. THE ELECTRICAL

CONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS.

17. UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL SUPPLY THE PROJECT MANAGER WITH (1)

COMPLETE SET OF CAD AS-BUILT DRAWINGS IN AUTOCAD 2000 AT CONTRACTOR'S EXPENSE AND (3)

COMPLETE BOUND COPIES OF OPERATION AND MAINTENANCE MANUALS. THESE SHALL BE PROVIDED TO

SEPTA AT CONTRACTOR'S EXPENSE. CONTRACTOR SHALL INSTRUCT SEPTA'S PERSONNEL WITH REGARD

TO THE PROPER OPERATION OF ALL SYSTEMS TO THE SATISFACTION OF SEPTA.

18. ALL WORK FURNISHED UNDER THE CONTRACT SHALL BE GUARANTEED AGAINST ANY AND ALL DEFECTS IN

WORKMANSHIP AND/OR MATERIALS FOR A PERIOD OF NOT LESS THAN (1) YEAR FROM THE DATE OF FINAL

ACCEPTANCE OF THE INSTALLATION. ANY DEFECTS OF WORKMANSHIP DEVELOPING DURING THIS PERIOD

SHALL BE REMEDIED AND ANY DEFECTIVE MATERIAL REPLACED WITHOUT ADDITIONAL COST TO SEPTA.

19. INSTALLED SYSTEMS SHALL OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT SOUND OR VIBRATION

THAT IS OBJECTABLE TO THE PROJECT MANAGER, OR SEPTA. OBJECTABLE SOUND OR VIBRATION

CONDITIONS DUE TO WORKMANSHIP SHALL BE CORRECTED IN APPROVED MANNER BY THE ELECTRICAL

CONTRACTOR AT HIS EXPENSE.

20. ELECTRICAL CONTRACTOR SHALL SIMILARLY NOTIFY ENGINEER OF COMPLETION OF ALL WORK,

INDICATING THE ELECTRICAL CONTRACTOR IS READY FOR THE ENGINEER TO PERFORM THE FINAL

PUNCHLIST INSPECTION.

21. UPON COMPLETION OF ALL UNFINISHED OR FAULTY WORK NOTED IN ENGINEER FINAL PUNCH LIST, THE

ELECTRICAL CONTRACTOR SHALL SUBMIT TO THE ENGINEER IN WRITING A LETTER OF COMPLETION

CERTIFYING THAT ALL PUNCH LIST ITEMS HAVE BEEN COMPLETED AND ALL AS-BUILTS, MANUALS, ETC.

HAVE BEEN SUBMITTED.

22. SHOULD A CONTRACTOR REQUIRE REMOVAL, RELOCATION, OR REROUTING OF ANOTHER TRADE'S WORK

THAT IS NOT INDICATED ON DRAWINGS, THE CONTRACTOR REQUIRING SUCH WORK SHALL BE

RESPONSIBLE FOR THAT WORK, AND PAY ALL REQUIRED COSTS.

23. ALL WORK INVOLVING ALTERATIONS TO EXISTING SYSTEMS, EQUIPMENT, AND MATERIALS SHALL BE

REVIEWED WITH THE PROJECT MANAGER AND SEPTA BEFORE BEGINNING WORK.

24. DEFINITION: UNLESS OTHERWISE NOTED, ALL WORK SPECIFIED HEREIN OR NOTED ON DRAWINGS, SHALL

BE BY THE ELECTRICAL CONTRACTOR. ALL REFERENCES TO "CONTRACTOR" OR "THIS CONTRACTOR" ON

DRAWINGS OR SPECIFICATIONS ARE ADDRESSED TO THE ELECTRICAL CONTRACTOR. THE TERM

"PROVIDE" WHENEVER ENCOUNTERED ON DRAWINGS OR IN THESE SPECIFICATIONS, SHALL MEAN

"FURNISH AND INSTALL."

25. CODES AND STANDARDS: ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE NATIONAL

ELECTRIC CODE, ALL APPLICABLE CODES, SPECIFICATIONS, LOCAL ORDINANCES, INDUSTRY STANDARDS,

UTILITY COMPANY REGULATIONS AND FIRE INSURANCE CARRIER'S REQUIREMENTS.

26. MATERIALS: ALL MATERIALS FURNISHED BY THIS CONTRACTOR, SHALL BE NEW AND BEAR THE LABEL OR

LISTING OF A NATIONALLY RECOGNIZED INDEPENDENT TESTING LABORATORY.

27. OUTLET AND SWITCH BOXES: PROVIDE AND INSTALL OUTLET BOXES OF PROPER TYPE AND SIZE AS

REQUIRED AT ALL OUTLETS WHERE SHOWN. SECURED FIRMLY IN PLACE AND SET TRUE AND SQUARE AND

FLUSH WITH THE FINISHED SURFACE.

28. INSTALLATION OF RACEWAYS: ALL RACEWAYS SHALL BE INSTALLED CONCEALED. NO SURFACE RACEWAY

WILL BE ACCEPTED IN FINISHED AREAS.

29. WIRING: WIRING OF BRANCH CIRCUITS SHALL BE TYPE THHN/THWN IN RIGID GALVANIZED STEEL CONDUIT

WHERE EXPOSED OUTSIDE. WIRES SHALL BE COPPER AND SHALL BE MIN. #12AWG, 600V, 75°C. ALL

RACEWAYS ARE SHOWN DIAGRAMMATICALLY, EXACT LOCATION TO BE DETERMINED ON THE JOB. EXACT

LOCATION OF OUTLETS TO BE DETERMINED BY SEPTA. CONTRACTOR SHALL ARRANGE ALL NEW CIRCUITS

IN PANELS SO AS TO BALANCE THE LOAD ON ALL PHASES. EXPOSED CONDUIT IN UNFINISHED AREAS

SHALL BE EMT. CONDUIT DIRECTLY BURIED UNDERGROUND SHALL BE SCHEDULE 40 PVC WITH RGS

ELBOWS AND STUB UPS.

30. A TYPED DIRECTORY CARD SHALL BE PROVIDED IN EACH PANEL WITH ADDED CIRCUITS TO INDICATE THE

LOADS ACTUALLY SERVED.

31. PROVIDE NEW FIXTURES AS SPECIFIED ON LIGHTING FIXTURE SCHEDULE. ALL NEW LED LAMPS SHALL BE

3500K.

32. GROUNDING: SHALL BE IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 250.

PROVIDE GROUND WIRES AS REQUIRED AND RESIZE CONDUIT IF NECESSARY.

33. DEMONSTRATION OF COMPLETE ELECTRICAL SYSTEMS: UPON COMPLETION OF THE WORK THIS

CONTRACTOR SHALL OBTAIN A CERTIFICATE OF APPROVAL FROM ALL RECOGNIZED AGENCIES

CONCERNED WITH THE WORK. CONTRACTOR SHALL NOTIFY AND MAKE ALL THE NECESSARY

ARRANGEMENTS WITH THE INSPECTING AGENCY AND LOCAL AUTHORITIES SO THAT INSPECTION MAY BE

CARRIED OUT AT THE PROPER TIME.

34. PROJECT MUST MEET FM GLOBAL STANDARDS (WWW.FMGLOBAL.COM/)

METER

LIGHTING SYMBOLS

JUNCTION BOX OR POKE-THRU WITH COMBINATION POWER/DATA

FLUSH FLOOR MOUNTED REFER TO DETAIL ON DRAWING E002

NEW EMERGENCY CIRCUIT

UNDERGROUND SECONDARY CABLE

SHOWN HERE FOR REFERENCE ONLY. SEE CIVIL PLANS

UNDERGROUND TELEPHONE CABLE

SHOWN HERE FOR REFERENCE ONLY. SEE CIVIL PLANS

OCCUPANCY SENSOR. 360° RANGE

CEILING MOUNTED

PHOTOCELL CONTROL SWITCH

CEILING MOUNTED

PHOTOCELL CONTROL SWITCH

WALL MOUNTED @ 10" BELOW FINISHED CEILING

ELECTRICALLY HELD UL LISTED RELAY FOR EMERGENCY LIGHTING.

LIGHTING SHALL BE CONTROLLED BY SWITCH UNDER NORMAL POWER

CONDITION FROM NORMAL SOURCE. IN EMERGENCY MODE THE RELAY

SHALL ENABLE THE DEDICATED LIGHTING TO BE SWITCHED TO THE

EMERGENCY SOURCE FOR FULL OPERATION. PROVIDE BODINE BALLAST

#GTD OR SIMILIAR.

TIME CLOCK

MANHOLE

ELECTRICALLY HELD UL LISTED RELAY FOR EMERGENCY LIGHTING.

LIGHTING SHALL BE CONTROLLED BY SWITCH UNDER NORMAL POWER

CONDITION FROM NORMAL SOURCE. IN EMERGENCY MODE THE RELAY

SHALL ENABLE THE DEDICATED LIGHTING TO BE SWITCHED TO THE

EMERGENCY SOURCE FOR FULL OPERATION. PROVIDE BODINE BALLAST

#GTD OR SIMILIAR.

ELECTRIC DOOR STRIKE

CARD READER, PROVIDE 2"x4" JUNCTION BOX

WALL MOUNTED @ 42" AFF UON ON NON-SECURED SIDE OF DOOR

ADA ACCESS BUTTON, MAKE ALL FINAL CONNECTIONS TO DOOR CONTROLLER

DOOR CONTROLLER

SHEET NUMBER

DWG. NO.:

OF

OF

SHT. NO.:

REV. NO.:

SCALE:

DRAWN BY:DATE:

WORK ORDER NO.:

SCALE FACTOR:

CHECKED BY:

ARCHIVE NO.:

COMPUTER FILE NO.:

AD

DE

ND

UM

1

4/1

7/1

51

MA

NC

WT

CW

T

Page 2: ELECTRICAL SYMBOLS LIST 15...AF AMPERE FRAME AFF ABOVE FINISHED FLOOR AIC AMPERE INTERRUPTING CAPACITY AT AMPERE TRIP ATS AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GAUGE BLDG BUILDING

MDP

REF.

REF.REF.REF.

+ +

+

+

+

+

+

+

ELECTRIC WH-2

1.5KVA, 120V

ELECTRIC WH-2

1.5KVA, 120V

ELECTRIC WH-2

1.5KVA, 120V

TRAP PRIMER TP-1

120V

T75K

LP2

TELEPHONE

4'x4' PLYWOOD

WP

WP

WP

WP

GAS WATER HEATER

RE-CIRC PUMP 120V

SD

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

VAV

+

+

CEILING FAN

CEILING FAN

CEILING FAN

BMS PANEL

120V

PUMP P-1

1.5HP,480V,3Φ

PUMP P-2

1.5HP,480V,3Φ

REFRIGERATOR

120V

C

C

C

C

C

C

1"C FOR DATA

1"C FOR POWER

LP1

LP1

6

4

HP1

HP1

1

2

1

LP1

LP1

3

7

LP1

LP2

LP1

LP2

2

LP2

LP2

LP1

LP2

LP2

LP2

LP2

LP2

LP2

LP2

LP2

LP2

LP2

LP2

LP1

LP2

LP2

LP2

2

11

LP2

6

8

19

12 13

15

14

16

18

20

LP2

LP1LP2

LP2LP2 LP2

LP2

LP1

23

10

1

3

5

7

15

17

21

23

19

LP2

25

LP2

32

22 24 2628 30

17

4

MD

MD

UH-1

UH-2

LP2

27

REC

ON

ROOF

EF-4

1/25HP,120V

EF-3

1/30HP,120V

5

LP1

BOILER CONTROLS

120V

21

LP2

1"C FOR DATA

3/4"C FOR POWER

TOILET (TYP 11)

50VA, 120V

TOILET (TYP 3)

50VA, 120V

SINK

35VA,120V

SINKS

100VA, 120V

SINKS

100VA, 120V

12

LP1

LP1

10

LP1

14

+

EWC

LP1

16

EWC

LP1

18

UP TO

CU-1

AC-1

208V,1Φ

LP2

LP1

LP1

25

CEILING FAN (TYP 4)

5.7A,120V

BURIED CONDUIT FOR TELE/DATA

REFER TO DRAWING E102 FOR CONTINUATION

CB-1

HP1

CT

TROUGH

ABOVE

LP1

MD

MD

MD

MD

LP1

VIDEO MONITORS, +48" (TYP 9)

120V & DATA

LP2

34

KIOSK & PRINTER

CONDESATE PUMP

120V

LP1

26

PRINTER/COPIER

LP2

29

27

LP1

LP1

29

HAND DRYER

1500VA, 120V

31

LP1

LP1

33

HAND DRYER

1500VA, 120V

CR

CR

CR

SECURITY

PANEL

CR

CR

DMO

DMO

DMO

LP1

28

TYP

TYP

LP1

30

LP1

32

TYP

TYP

SHEET NUMBER

DWG. NO.:

OF

OF

SHT. NO.:

REV. NO.:

SCALE:

DRAWN BY:DATE:

WORK ORDER NO.:

SCALE FACTOR:

CHECKED BY:

ARCHIVE NO.:

COMPUTER FILE NO.:

KEY NOTES

DATA ROOM'S AIR CONDITIONER & CONDENSING UNIT

POWERED THROUGH SINGLE POINT AT CONDENSING UNIT.

EXTEND CONDUIT/WIRE TO AIR CONDITIONER.

HANDS-FREE TOILET REQUIRES 120V. MOUNT IN LOCATION

RECOMMENDED BY MANUFACTURER. TOILET PROVIDED BY

OTHERS WITH LOW-VOLTAGE TRANSFORMER.

HANDS-FREE SINK REQUIRES 120V RECEPTACLE. SINK

PROVIDED BY OTHERS WITH LOW-VOLTAGE PLUG-IN

TRANSFORMER.

HANDS-FREE SINKS REQUIRES 120V. MOUNT JUNCTION BOX

BELOW SINK. SINK PROVIDED BY OTHERS WITH

LOW-VOLTAGE 100VA TRANSFORMER.

OUTLET IDENTIFICATION NUMBERING SHALL BE AS DIRECTED

BY OWNER'S M.I.S. DEPARTMENT INSTALLATION SHALL

COMPLY WITH SPECIFICATIONS. EACH CABLING SHALL BE

TAGGED AT ALL TERMINATIONS POINTS.

STANDARD OUTLET MOUNTING HEIGHT SHALL BE THE SAME

AS ELECTRICAL HEIGHT, U.O.N. EXACT LOCATION OF

OUTLETS SHALL BE AS INDICATED ON THE ARCHITECTURAL

DRAWINGS.

EQUIPMENT AND/OR CABLE LOCATED AT THIS STAGE OF THE

TELECOMMUNICATIONS CABLING CONFIGURATION IS EITHER

EXISTING OR NOT COVERED UNDER THIS CONTRACT AND

WILL BE FURNISHED BY OTHERS.

LABEL ALL RACKS, FRAMES, CABINETS, BLOCKS, CABLES,

CABLE SUPPORTS, ETC. IN ACCORDANCE WITH EIA/TIA 606.

TELECOMMUNICATIONS INSTALLATION SHALL COMPLY WITH

ALL CURRENT APPLICABLE CODES, INCLUDING

PHILADELPHIA ELECTRICAL CODES, THE NATIONAL ELECTRIC

CODE, AND ALL APPLICABLE LOCAL CODES HAVING

JURISDICTION.

PROVIDE FIRESTOPPING FOR ALL SLEEVE AND CONDUIT

PENETRATIONS THROUGH RATED PARTITIONS OR FLOORS IN

ACCORDANCE WITH THE SPECIFICATIONS.

TELECOMMUNICATION NOTES

DEDICATED RECEPTACLE FOR ELECTRIC WATER HEATER TO

BE MOUNTED UNDER SINK. LABEL FACEPLATE "FOR WATER

HEATER".

PROVIDE 120V:24V TRANSFORMER FOR LOW VOLTAGE

DAMPER.

PROVIDE 120V:24V TRANSFORMER FOR LOW VOLTAGE

DAMPER.

PROVIDE SECURITY PANEL, TYCO INTEGRATED SECURITY

ACE8/SWH-1 OR SEPTA APPROVED EQUAL

PROVIDE TWO CAT 6 CABLES IN A 1" EMT CONDUIT HOMERUN

BACK TO THE SECURITY PANEL IN THE COMM ROOM AND

SAFE OFF BOTH ENDS.

WIRE ALL ADA ACCESS BUTTONS TO CIRCUIT LP1#34

AD

DE

ND

UM

1

4/1

7/1

51

MA

NC

WT

CW

T

Page 3: ELECTRICAL SYMBOLS LIST 15...AF AMPERE FRAME AFF ABOVE FINISHED FLOOR AIC AMPERE INTERRUPTING CAPACITY AT AMPERE TRIP ATS AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GAUGE BLDG BUILDING

MECHANICAL EQUIPMENT PAD

SKYLIGHT

SKYLIGHT

SKYLIGHT

SKYLIGHT

WALKING PAD, TYP.

WALKING PAD, TYP.

SKYLIGHT

SKYLIGHT

EXHAUST FAN EF-1

1/4HP, 120V

ROOFTOP UNIT RTU-1

85MCA, 480V,3Φ

15HP SUPPLY FAN

(3)11.2A COMPRESSORS

(3)2A CONDENSORS

CU-1

208V,1Φ

100/100/3

WP

WP

MDP

3

LP1

9

REC CIRCUIT

LP2#2 BELOW

DOWN TO AC

SHEET NUMBER

DWG. NO.:

OF

OF

SHT. NO.:

REV. NO.:

SCALE:

DRAWN BY:DATE:

WORK ORDER NO.:

SCALE FACTOR:

CHECKED BY:

ARCHIVE NO.:

COMPUTER FILE NO.:

EXHAUST FAN PROVIDED WITH DISCONNECT AND OVERLOAD

PROTECTION BY OTHERS.

DATA ROOM'S AIR CONDITIONER & CONDENSING UNIT

POWERED THROUGH SINGLE POINT AT CONDENSING UNIT.

EXTEND CONDUIT/WIRE TO AIR CONDITIONER.

KEY NOTES

Page 4: ELECTRICAL SYMBOLS LIST 15...AF AMPERE FRAME AFF ABOVE FINISHED FLOOR AIC AMPERE INTERRUPTING CAPACITY AT AMPERE TRIP ATS AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GAUGE BLDG BUILDING

480/277

PANEL LP1 VIA TRANSFORMER 2125

DESCRIPTION OF LOAD

PER PHASE

A B C

LOADLOAD

4

FCU-2 620

FCU-4 820

SPACE 10-

SPACE 12-

SPACE 14-

AMPS

TRIP

NO.

CKT.

1 150

3 100

5 20

7 20

9 -

11 -

13 -

AMPS

TRIP

NO.

CKT.

PANEL HP1

ROOFTOP UNIT RTU-1

FCU-1

FCU-3

SPACE

SPACE

SPACE

PANEL:

FEEDER SIZE:

FED FROM:

BUILDING:

LOCATION:MOUNTING:

MDP

NEUTRAL:

VOLTS, PHASE, WIRE4

32,000AIC:

400MAIN BUS: AMPS

AMPSMAIN BRK: P3

BUS: COPPER ALUMINUM

SURFACE FLUSH

MANUFACTURER/MODEL:

AMPS100%

ELECTRICAL ROOM 130

FRANKFORD ADMINISTRATION BUILDING

REFER TO SINGLE LINE ON DRAWING E002

REFER TO SINGLE LINE ON DRAWING E002

REFER TO SPECIFICATIONS

3

400

(KVA)

(KVA)(KVA)

DESCRIPTION OF LOAD

ISOLATED GROUND

GROUND

LUGS:

FEED THRU MLO

FEED: TOP BOTTOM

SHUNT TRIP

ARC FLASH HAZARD CATEGORY:

NEMA ENCLOSURE TYPE:

2

1

REC MECH RM, EXTERIOR220

(KVA)

PER PHASE

A B (KVA)C

LOAD

(KVA)

LOAD

REC 112A, ELEC RM, C102420

REC 108, 110620

COMPUTER REC 102, 104, 106, 108, 110820

REC 102, 104, 1061020

REC RESTROOMS 111, 1131220

REC KITCHEN1420

REC KITCHEN1620

REC KITCHEN1820

REFRIGERATOR 1092020

22

HEATERS 130,131, DAMPERS 2420

CONDESATE PUMP 2620

DOOR CONTROLLER 2820

DOOR CONTROLLER 3020

DOOR CONTROLLER 3220

ADA DOOR ASSIST BUTTONS 3420

SPARE 3620

SPARE 3820

SPARE 4020

SPARE 4220

AMPS

TRIP

NO.

CKT.

1 20

3 20

5 20

7 20

9 20

11 20

13 20

15 20

17 20

19 20

21 20

23 20

25 20

27 20

29 20

31 20

33 20

35 20

37 20

39 20

41 20

AMPS

TRIP

NO.

CKT.

BMS PANEL

BOILER CONTROLS

TRAP PRIMER TP-2

RE-CIRC PUMP

EXHAUST FAN EF-1 (1/4HP)

EXHAUST FAN EF-2 (1/6HP)

WATER HEATER WH-2

WATER HEATER WH-2

WATER HEATER WH-2

VAV CONTROLLERS

VAV CONTROLLERS

CEILING FANS 120

CEILING FANS 120

HAND DRYER WOMENS RESTROOM

HAND DRYER WOMENS RESTROOM

HAND DRYER MENS RESTROOM

HAND DRYER MENS RESTROOM

SPARE

SPARE

SPARE

SPARE

PANEL:

FEEDER SIZE:

FED FROM:

BUILDING:

LOCATION:

MOUNTING:

LP1

VOLTS, PHASE, WIRE208/120 4

BUS: COPPER ALUMINUM

SURFACE FLUSH

MANUFACTURER/MODEL:

ELECTRICAL ROOM 130

REFER TO SPECIFICATIONS

3

DESCRIPTION OF LOAD DESCRIPTION OF LOAD

NEUTRAL:10,000

AIC:

250MAIN BUS: AMPS

AMPSMAIN BRK: P3

AMPS200%

250

ISOLATED GROUND

GROUND

LUGS:

FEED THRU MLO

FEED: TOP BOTTOM

SHUNT TRIP

ARC FLASH HAZARD CATEGORY:

NEMA ENCLOSURE TYPE:

1

1

480/277

PUMP P-2 (1.5HP) 215

DESCRIPTION OF LOAD

PER PHASE

A B C

LOADLOAD

4

6

8

10

12

SPARE 1420

SPARE 1620

SPARE 1820

SPACE 20-

SPACE 22-

SPACE 24-

SPACE 26-

SPACE 28-

SPACE 30-

SPACE 32-

SPACE 34-

SPACE 36-

SPACE 38-

SPACE 40-

SPACE 42-

AMPS

TRIP

NO.

CKT.

1 15

3

5

7 20

9 20

11 20

13 20

15 20

17 20

19 20

21 20

23 20

25 -

27 -

29 -

31 -

33 -

35 -

37 -

39 -

41 -

AMPS

TRIP

NO.

CKT.

PUMP P-1 (1.5HP)

LIGHTING

LIGHTING

LIGHTING

LIGHTING

LIGHTING

SPARE

SPARE

SPARE

SPARE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

PANEL:

FEEDER SIZE:

FED FROM:

BUILDING:

LOCATION:MOUNTING:

HP1

NEUTRAL:

VOLTS, PHASE, WIRE4

14,000AIC:

150MAIN BUS: AMPS

AMPSMAIN BRK: P3

BUS: COPPER ALUMINUM

SURFACE FLUSH

MANUFACTURER/MODEL:

AMPS100%

ELECTRICAL ROOM 130

REFER TO SPECIFICATIONS

3

MLO

(KVA)

(KVA)(KVA)

DESCRIPTION OF LOAD

ISOLATED GROUND

GROUND

LUGS:

FEED THRU MLO

FEED: TOP BOTTOM

SHUNT TRIP

ARC FLASH HAZARD CATEGORY:

NEMA ENCLOSURE TYPE:

2

1

220

(KVA)

PER PHASE

A B (KVA)C

LOAD

(KVA)

LOAD

420

620

820

1020

1220

1420

1620

1820

2020

REFRIGERATOR 120 2220

REFRIGERATOR 120 2420

REFRIGERATOR 120 2620

REC 120 2820

REC 120 3020

VIDEO MONITORS 120 3220

VIDEO MONITORS 120 3420

SPARE 3620

SPARE 3820

SPARE 4020

SPARE 4220

AMPS

TRIP

NO.

CKT.

1 20

3 20

5 20

7 20

9 20

11 20

13 20

15 20

17 20

19 20

21 20

23 20

25 20

27 20

29 20

31 20

33 20

35 20

37 20

39 20

41 20

AMPS

TRIP

NO.

CKT.

REC 120

REC 120, 125, 126, C103

REC 101A, 101B, 107, EXTERIOR

PRINTER/COPIER

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

PANEL:

FEEDER SIZE:

FED FROM:

BUILDING:

LOCATION:

MOUNTING:

LP2

VOLTS, PHASE, WIRE208/120 4

BUS: COPPER ALUMINUM

SURFACE FLUSH

MANUFACTURER/MODEL:

ELECTRICAL ROOM 130

REFER TO SPECIFICATIONS

3

DESCRIPTION OF LOAD DESCRIPTION OF LOAD

NEUTRAL:10,000

AIC:

250MAIN BUS: AMPS

AMPSMAIN BRK: P3

AMPS200%

MLO

ISOLATED GROUND

GROUND

LUGS:

FEED THRU MLO

FEED: TOP BOTTOM

SHUNT TRIP

ARC FLASH HAZARD CATEGORY:

NEMA ENCLOSURE TYPE:

1

1

FRANKFORD ADMINISTRATION BUILDING

REFER TO SINGLE LINE ON DRAWING E002

REFER TO SINGLE LINE ON DRAWING E002

FRANKFORD ADMINISTRATION BUILDING

REFER TO SINGLE LINE ON DRAWING E002

REFER TO SINGLE LINE ON DRAWING E002

FRANKFORD ADMINISTRATION BUILDING

REFER TO SINGLE LINE ON DRAWING E002

REFER TO SINGLE LINE ON DRAWING E002

TELEPHONE BOARD REC

SMOKE DAMPERS

DAMPERS, EF-5, EF-6

HANDS-FREE MENS RESTROOM

HANDS-FREE WOMENS RESTROOM

HANDS-FREE RESTROOMS 111 & 113

ELECTRIC WATER COOLER KITCHEN

ELECTRIC WATER COOLER LOUNGE

REC SERVER ROOM

REC SERVER ROOM

REC SERVER ROOM

REC SERVER ROOM

SPARE

REC RESTROOMS 122, 124

SPARE

REC C101, 100, EXTERIOR

REC 101

REC 101

REC 101

FIRE ALARM CONTROL PANEL

SPARE 20

SPARE 20

SPARE 20

SPACE -

AIR CONDITIONER & CONDENSING UNIT

DATA ROOM

KEY NOTES

PROVIDE 3#12, #12G, 3/4"C

REFER TO SINGLE LINE DIAGRAM ON DRAWING E002 FOR

FEEDER SIZE.

SHEET NUMBER

DWG. NO.:

OF

OF

SHT. NO.:

REV. NO.:

SCALE:

DRAWN BY:DATE:

WORK ORDER NO.:

SCALE FACTOR:

CHECKED BY:

ARCHIVE NO.:

COMPUTER FILE NO.:

AD