ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv...

14
48" SINGLE RECEPTACLE DUPLEX RECEPTACLE 2 SINGLE POLE (HORSE POWER RATED WHEN USED AS MOTOR DISCONNECT) PC DESCRIPTION CEILING SURFACE MOUNTED LIGHT FIXTURE, CAPITAL LETTER IDICATES FIXTURE TYPE, SMALL LETTER INDICATES SWITCHING RECESSED CEILING MOUNTED LIGHT FIXTURE SUSPENDED LIGHT FIXTURE TRACK AND TRACK LIGHT SURFACE FLUORESCENT FIXTURE EMERGENCY BATTERY LIGHT PENDANT LIGHT FIXTURE SYMBOL A 7' - 6" MOUNTING HEIGHT ELECTRICAL SYMBOL LEGEND a WALL MOUNTED LIGHT FIXTURE CEILING EXIT SIGN, SHADED SIDE INDICATES LIGHTED FACE, ARROWS INSTALLED AS SHOWN WALL EXIT SIGN RECESSED FLUORESCENT 6" ABOVE DOOR FRAME TO BOTTOM WALL MOUNT OCCUPANCY SENSOR SWITCH EMERGENCY REMOTE LAMP 7' - 6" DOUBLE POLE 48" 3 3 - WAY 48" 4 4 - WAY 48" LV LOW VOLTAGE 48" M DIMMER SWITCH 48" D KEY OPERATED SWITCH 48" K PILOT LIGHT (MAY BE USED WITH OTHER SWITCH TYPES) 48" P MOMENTARY CONTACT 48" MC PHOTOCELL 9' - 0" POLE MOUNTED FIXTURE CEILING MOUNT OCCUPANCY SENSOR OS TIME CONTROL SWITCH 48" T M MOTION SENSOR SWITCH POWER PACK PP C CONTACTOR (NUMBER INDICATES NUMBER OF POLES) 2 DESCRIPTION SYMBOL 18" 18" DOUBLE DUPLEX RECEPTACLE 18" TYPE L14-30 RECEPTACLE 18" A TYPE L14-50 RECEPTACLE 6" B SR CIRCUIT BREAKER PANEL WALL HEATER HATCHED SYMBOL INDICATES REMOVED DASHED SYMBOL INDICATES EXISTING T T1 BASEBOARD HEATER LINE VOLTAGE THERMOSTAT COMB. MOTOR STARTER VARIABLE FREQUENCY DRIVE DISCONNECT SWITCH. CEILING MOUNTED VERTICAL MULTIPLE OUTLET ASSEMBLY POWER OR DISTRIBUTION PANEL MOTOR (SEE SCHEDULE) TRANSFORMER SPECIAL CABINET CONDUIT TRANSITION DOWN CONDUIT TRANSITION UP BRANCH CIRCUIT HOME RUN CONDUIT EXPOSED SURFACE RACEWAY CONDUIT STUBBED OUT CONDUIT CONCEALED BELOW FLOOR CONDUIT CONCEALED IN WALL OR OVERHEAD SMOKE DETECTOR ('E' INDICATES DEVICE WITH ELEVATOR RECALL) DUCT SMOKE DETECTOR FLOORBOX COMMUNICATIONS OUTLET 1 KEYED NOTE MULTIOUTLET ASSEMBLY , PROVIDE DEVICES AS SHOWN ON PLANS GFCI RECEPTACLE 18" G SPECIAL RECEPTACLE FOURPLEX RECEPTACLE SWITCHED DUPLEX RECEPTACLE ISOLATED GROUND RECEPT (DUPLEX SHOWN) FLOOR RECEPTACLE (DUPLEX SHOWN) FOURPLEX RECEPTACLE WITH (1) DUPLEX SWITCHED AND (1) UNSWITCHED. 18" 18" 18" 18" DUPLEX RECEPTACLE - HALF SWITCHED 18" MOUNTING HEIGHT J J CEILING MOUNTED JUNCTION BOX WALL MOUNTED JUNCTION BOX PUSH BUTTON, SEE DWG FOR TYPE 48" 48" SF-1 DESCRIPTION SYMBOL MOUNTING HEIGHT 72"* 72"* 72"* 72"* 72"* 72"* AUDIO/VISUAL INPUT JACK - 'V' INDICATES VIDEO/HDMI WALLPLATE CEILING MOUNTED RECESSED SPEAKER SURFACE MT SPEAKER S MICROPHONE OUTLET CEILING MOUNTED HORN SPEAKER VOLUME CONTROL S S S S WALL MOUNTED SPEAKER WALL MOUNTED HORN SPEAKER WIRELESS CLOCK (120V POWERED) 90" 90" * DISTANCE TO THE TOP OF THE EQUIPMENT OR DEVICE ** DISTANCE TO THE BOTTOM OF THE EQUIPMENT OR DEVICE 84" V M 48" 18" A 18" COMPUTER OUTLET (NUMBER INDICATES QUANTITY OF CABLES, NO NUMBER INDICATES ONE) WALL TELEPHONE OUTLET TELEPHONE OUTLET W TELEVISION/ FLAT PANEL MONITOR LOCATION TV 2 WIRELESS ACCESS POINT OUTLET - QTY OF (2) CABLES AND JACKS AT EACH 18" 48" 18" 76" CARD READER KEYPAD CR 48" 48" BALANCED DOOR POSITION SWITCH ELECTRIC STRIKE ES P MAGNETIC LOCK ML 12'AFF IP CCTV CAMERA DESCRIPTION SYMBOL MOUNTING HEIGHT F MANUAL FIRE ALARM PULL STATION H FIXED TEMPERATURE DETECTOR 48" S FIRE ALARM HORN WITH STROBE FIRE ALARM SPEAKER WITH STROBE S 80"** 80"** H COMBINATION FIRE/SMOKE DAMPER OR SMOKE DAMPER BY DIVISION 23 DS FIRE ALARM STROBE LIGHT 80"** FIRE ALARM CHIME WITH STROBE C 80"** FR FIRE ALARM MODULE/RELAY MAGNETIC DOOR HOLD OPEN SPRINKLER VALVE TAMPER SWITCH, NUMBER INDICATES QUANTITY SPRINKLER FLOW SWITCH, NUMBER INDICATES QUANTITY SPRINKLER PRESSURE SWITCH FIRE ALARM REMOTE ANNUNCIATOR FA ANNUN 72"* FIRE ALARM CONTROL PANEL FACP 72"* CABLE TRAY CONDUIT SLEEVE (SIZE DENOTED) UE UNDERGROUND ELECTRICAL ABBREVATIONS A AMPERE AC ABOVE COUNTER AFF ABOVE FINISHED FLOOR AHU AIR HANDLING UNIT AL ALUMINUM AMP AMPERE ATS AUTOMATIC TRANSFER SWITCH AV AUDIO VISUAL BC BELOW COUNTER C CONDUIT CU COPPER CUH CABINET UNIT HEATER EF EXHAUST FAN EWC ELECTRIC WATER COOLER ANN ANNUNCIATOR FA FIRE ALARM FACP FIRE ALARM CONTROL PANEL GFCI GROUND FAULT CIRCUIT INTERRUPTER GR GROUND HP HORSEPOWER JBOX JUNCTION BOX KV KILOVOLT KW KILOWATT PH PHASE TV TELEVISION W WIRE WP WEATHERPROOF WH WATERHEATER V VOLT VFD VARIABLE FREQUENCY DRIVE UE UNDERGROUND ELECTRICAL RTU ROOF TOP UNIT SWBD SWITCHBOARD LIGHT FIXTURE WITH EMERGENCY BALLAST 1. NOT ALL SYMBOLS OR ABBREVATIONS ARE APPLICABLE TO THESE DRAWIANGS. 2. MOUNTING HEIGHT IS TO THE CENTER OF DEVICE UNLESS NOTED OTHERWISE. 3. FOR DEVICES SHOWN AS 48 INCHES MOUNTING HEIGHT, WHEN INSTALLED IN MASONRY BLOCK WALLS, MOUNTING AT 48 INCHES TO THE TOP OF THE OUTLET BOX IS ACCEPTABLE. AREA OF RESCUE STATION AR L P PUSH BUTTON PB 48" C ELECTRIFIED LOCK EL AP DH FS TS KP ALARM SIREN A 12'AFF TELEPHONE RINGER - EMERGENCY FIRE PHONE TR LUMINAIRE SCHEDULE TYPE MANUFACTURERS CATALOG INFORMATION FIXTURE DESCRIPTION LAMP DATA DRIVER DATA INPUT WATTS VOLTAGE MOUNTING REMARKS NO. TYPE NO. TYPE A1 METALUX 2GR SERIES 2' X 4' RECESSED LED TROFFER, REGRESSED ALUMINUM DOOR FRAME HINGED AND LATCHED WITH 0.125 INCH THICK PATTERN #12 DIFFUSER. 4900 LUMENS LED 0-10V DIMMING DRIVER 38 277 RECESSED OR EQUAL A2 METALUX 2GR SERIES SAME AS TYPE 'A1', 2'X2' VERSION, 4300 LUMENS. LED 0-10V DIMMING DRIVER 33 277 RECESSED OR EQUAL C1 HALO H4 LED 4 INCH LED RECESSED DOWNLIGHT. ALUMINUM CONSTRUCTION, 4000 DEGREE COLOR TEMPERATURE,80 CRI, INITIAL LUMEN OUTPUT OF 600. WET LISTED. WHITE REFLECTOR WITH WHITE TRIM RING. LED LED DRIVER 30 277 RECESSED OR EQUAL SERIES E1 LITHONIA LV SERIES SINGLE FACE LED EXIT LUMINAIRE, DIE CAST ALUMINUM HOUSING, WHITE BODY AND CANOPY, POLYCARBONATE COVER, STENCIL FACE, RED LETTERS, AC ONLY. LED LED DRIVER 1.5 277 UNIVERSAL OR EQUAL EM LITHONIA INDX SERIES INDUSTRIAL BATTERY PACK LIGHT, 90 MIN ILLUMINATION, HIGH TEMPERATURE BATTERY, POLYCARBONATE HOUSING AND LENS, GASKETED. LED LED DRIVER 1.5 277 UNIVERSAL OR EQUAL F1 METALUX SN LED SERIES 4 FOOT LED STRIP LIGHT, WIDE COVERAGE SEMI FROST LENS, HIGH GLOSS BAKED ENAMEL FINISH, 4000K, 5400 LUMENS, 80 CRI. LED LED DRIVER 43 277 SURFACE OR EQUAL F2 LITHONIA LBLED SERIES 4 FOOT LED CURVED BASKET WRAPAROUND LIGHT, #12 PRISMATIC DIFFUSER, NARROW HOUSING, 4000K, 4800 LUMENS. LED LED DRIVER 32 277 SURFACE OR EQUAL F3 METALUX SN LED SERIES 4 FOOT LED STRIP LIGHT, WIDE COVERAGE SEMI FROST LENS, HIGH GLOSS BAKED ENAMEL FINISH, 4000K, 7400 LUMENS, 80 CRI. LED LED DRIVER 64 277 SUSPENDED PROVIDE WITH STEM MOUNT KIT OR EQUAL H1 HOLOPHANE PHUZION PHS LED, HIGH BAY LUMINAIRE, CAST ALUMINUM HOUSING, PRISMATIC GLASS LENS, PENDANT MOUNTING, UPLIGHT, 4000K, 80 CRI, WIDE OPTIC, WHITE FINISH, 18000 LUMENS, HOOK MOUNT WITH SAFETY CHAIN LED LED DRIVER 166 277 SUSPENDED SUSPEND 24'AFF TYPICAL. OR EQUAL SERIES U1 FAIL SAFE UCL SERIES 2 FOOT LED UNDERCABINET FIXTURE, SOLID FACE, ACRYLIC LENS, WHITE FINISH, 3500K, 750 LUMENS/FT, INTEGRAL TOGGLE SWITCH. LED LED DRIVER 9 120 SURFACE OR EQUAL V1 TERON VICEROY SERIES 2 FOOT LED VANITY FIXTURE WITH (2) 6W LED STRIPS, SOLID FACE, ACRYLIC LENS, UP/DOWNLIGHT HOUSING, STEEL TEXTURED WHITE HOUSING, 4000K LED LED DRIVER 20 277 SURFACE OR EQUAL W1 LITHONIA D SERIES SIZE 0 EXTERIOR WALL MOUNTED AREA FIXTURE, P1 VERSION, FORWARD THROW DISTRIBUTION.SINGLE PIECE DIE-CAST ALUMINUM HOUSING,DARK BRONZE FINISH, 4000K, BI-LEVEL 50% MOTION SENSOR, GLARE SHIELD. LED LED-DRIVER 50 277 WALL SEE DRAWINGS FOR MOUNTING HEIGHT OR EQUAL W2 LITHONIA DSXW SERIES SIZE 1 EXTERIOR WALL PACK, 10 LED, TYPE II DISTRIBUTION SINGLE PIECE DIE-CAST ALUMINUM HOUSING, SINGLE PIECE DIE CAST ALUMINUM HOUSING, DARK BRONZE FINISH, 4000K. LED LED-DRIVER 14 277 WALL SEE DRAWINGS FOR MOUNTING HEIGHT OR EQUAL KEY PLAN Fargo, ND 58102 2101 Elm Street Medical Center Dept. of Veterans Affairs Building No. VA Project No. Drawing Title Contract No. Veterans Affairs Location Drawn By Checked By Designed By Project Title Drawing No. Date Scale: Department of Dwg. of 69 10 - BOILER PLANT FARGO VA HEALTH CARE SYSTEM FARGO, NORTH DAKOTA VA263-P-1218 CH MB CH VA263 Project Phase www.jlgarchitects.com copyright © 2017 Fargo 214 Broadway Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8 Elec. dwg name: Submittal Date S.D. 1 SUBMITTAL 12/30/2015 D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016 D.D. 1 (35%) SUBMITTAL 09/30/2016 D.D. 2 (50%) SUBMITTAL 03/03/2017 D.D. 3 (99%) SUBMITTAL 10/20/2017 C.D. 4 (100%) SUBMITTAL 06/01/2018 10/29/2018 1:38:24 PM E1 437-14-112 REPLACE BOILER PLANT 10.26.18 ELECTRICAL SYMBOLS AND ABBREVIATIONS 100% CONSTRUCTION DOCUMENT 56 15-193 E1.DWG AS NOTED

Transcript of ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv...

Page 1: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

48"

SINGLE RECEPTACLE

DUPLEX RECEPTACLE

2

SINGLE POLE (HORSE POWER RATED WHEN USED AS MOTOR DISCONNECT)

PC

DESCRIPTION

CEILING SURFACE MOUNTED LIGHT FIXTURE, CAPITAL LETTER IDICATESFIXTURE TYPE, SMALL LETTER INDICATES SWITCHING

RECESSED CEILING MOUNTED LIGHT FIXTURE

SUSPENDED LIGHT FIXTURE

TRACK AND TRACK LIGHT

SURFACE FLUORESCENT FIXTURE

EMERGENCY BATTERY LIGHT

PENDANT LIGHT FIXTURE

SYMBOL

A

7' - 6"

MOUNTINGHEIGHT

ELECTRICAL SYMBOL LEGEND

a

WALL MOUNTED LIGHT FIXTURE

CEILING EXIT SIGN, SHADED SIDE INDICATES LIGHTED FACE, ARROWSINSTALLED AS SHOWN

WALL EXIT SIGN

RECESSED FLUORESCENT

6" ABOVEDOORFRAME TOBOTTOM

WALL MOUNT OCCUPANCY SENSOR SWITCH

EMERGENCY REMOTE LAMP 7' - 6"

DOUBLE POLE 48"

33 - WAY 48"

44 - WAY 48"

LVLOW VOLTAGE 48"

M

DIMMER SWITCH 48"D

KEY OPERATED SWITCH 48"K

PILOT LIGHT (MAY BE USED WITH OTHER SWITCH TYPES) 48"P

MOMENTARY CONTACT 48"MC

PHOTOCELL 9' - 0"

POLE MOUNTED FIXTURE

CEILING MOUNT OCCUPANCY SENSOROS

TIME CONTROL SWITCH 48"T

M MOTION SENSOR SWITCH POWER PACKPP

C CONTACTOR (NUMBER INDICATES NUMBER OF POLES)2

DESCRIPTIONSYMBOL

18"

18"

DOUBLE DUPLEX RECEPTACLE 18"

TYPE L14-30 RECEPTACLE 18"A

TYPE L14-50 RECEPTACLE 6"B

SR

CIRCUIT BREAKER PANEL

WALL HEATER

HATCHED SYMBOL INDICATES REMOVED

DASHED SYMBOL INDICATES EXISTING

T

T1

BASEBOARD HEATER

LINE VOLTAGE THERMOSTAT

COMB. MOTOR STARTER

VARIABLE FREQUENCY DRIVE

DISCONNECT SWITCH.

CEILING MOUNTED VERTICAL MULTIPLE OUTLET ASSEMBLY

POWER OR DISTRIBUTION PANEL

MOTOR (SEE SCHEDULE)

TRANSFORMER

SPECIAL CABINET

CONDUIT TRANSITION DOWN

CONDUIT TRANSITION UP

BRANCH CIRCUIT HOME RUN

CONDUIT EXPOSED

SURFACE RACEWAY

CONDUIT STUBBED OUT

CONDUIT CONCEALED BELOW FLOOR

CONDUIT CONCEALED IN WALL OR OVERHEAD

SMOKE DETECTOR ('E' INDICATES DEVICE WITH ELEVATOR RECALL)

DUCT SMOKE DETECTOR

FLOORBOX COMMUNICATIONS OUTLET

1 KEYED NOTE

MULTIOUTLET ASSEMBLY , PROVIDE DEVICES AS SHOWN ON PLANS

GFCI RECEPTACLE 18"G

SPECIAL RECEPTACLE

FOURPLEX RECEPTACLE

SWITCHED DUPLEX RECEPTACLE

ISOLATED GROUND RECEPT (DUPLEX SHOWN)

FLOOR RECEPTACLE (DUPLEX SHOWN)

FOURPLEX RECEPTACLE WITH (1) DUPLEX SWITCHED AND (1)UNSWITCHED.

18"

18"

18"

18"

DUPLEX RECEPTACLE - HALF SWITCHED 18"

MOUNTINGHEIGHT

J

J CEILING MOUNTED JUNCTION BOX

WALL MOUNTED JUNCTION BOX

PUSH BUTTON, SEE DWG FOR TYPE 48"

48"

SF-1

DESCRIPTIONSYMBOLMOUNTING

HEIGHT

72"*

72"*

72"*

72"*

72"*

72"*

AUDIO/VISUAL INPUT JACK - 'V' INDICATES VIDEO/HDMI WALLPLATE

CEILING MOUNTED RECESSED SPEAKER

SURFACE MT SPEAKER

S

MICROPHONE OUTLET

CEILING MOUNTED HORN SPEAKER

VOLUME CONTROL

S

S

S

S

WALL MOUNTED SPEAKER

WALL MOUNTED HORN SPEAKER

WIRELESS CLOCK (120V POWERED)

90"

90"

* DISTANCE TO THE TOP OF THE EQUIPMENT OR DEVICE ** DISTANCE TO THE BOTTOM OF THE EQUIPMENT OR DEVICE

84"

V

M

48"

18"

A 18"

COMPUTER OUTLET (NUMBER INDICATES QUANTITY OF CABLES, NO NUMBERINDICATES ONE)

WALL TELEPHONE OUTLET

TELEPHONE OUTLET

W

TELEVISION/ FLAT PANEL MONITOR LOCATIONTV

2

WIRELESS ACCESS POINT OUTLET - QTY OF (2) CABLES AND JACKS AT EACH

18"

48"

18"

76"

CARD READER

KEYPAD

CR 48"

48"

BALANCED DOOR POSITION SWITCH

ELECTRIC STRIKEES

P

MAGNETIC LOCKML

12'AFF

IP CCTV CAMERA

DESCRIPTIONSYMBOLMOUNTING

HEIGHT

F MANUAL FIRE ALARM PULL STATION

H

FIXED TEMPERATURE DETECTOR

48"

S

FIRE ALARM HORN WITH STROBE

FIRE ALARM SPEAKER WITH STROBES 80"**

80"**

H

COMBINATION FIRE/SMOKE DAMPER OR SMOKE DAMPER BY DIVISION 23

DS

FIRE ALARM STROBE LIGHT 80"**

FIRE ALARM CHIME WITH STROBEC 80"**

FR FIRE ALARM MODULE/RELAY

MAGNETIC DOOR HOLD OPEN

SPRINKLER VALVE TAMPER SWITCH, NUMBER INDICATES QUANTITY

SPRINKLER FLOW SWITCH, NUMBER INDICATES QUANTITY

SPRINKLER PRESSURE SWITCH

FIRE ALARM REMOTE ANNUNCIATORFA ANNUN

72"*

FIRE ALARM CONTROL PANELFACP

72"*

CABLE TRAY

CONDUIT SLEEVE (SIZE DENOTED)

UE UNDERGROUND ELECTRICAL

ABBREVATIONS

A AMPERE

AC ABOVE COUNTER

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AL ALUMINUM

AMP AMPERE

ATS AUTOMATIC TRANSFER SWITCH

AV AUDIO VISUAL

BC BELOW COUNTER

C CONDUIT

CU COPPER

CUH CABINET UNIT HEATER

EF EXHAUST FAN

EWC ELECTRIC WATER COOLER

ANN ANNUNCIATOR

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GR GROUND

HP HORSEPOWER

JBOX JUNCTION BOX

KV KILOVOLT

KW KILOWATT

PH PHASE

TV TELEVISION

W WIRE

WP WEATHERPROOF

WH WATERHEATER

V VOLT

VFD VARIABLE FREQUENCY DRIVE

UE UNDERGROUND ELECTRICAL

RTU ROOF TOP UNIT

SWBD SWITCHBOARD

LIGHT FIXTURE WITH EMERGENCY BALLAST

1. NOT ALL SYMBOLS OR ABBREVATIONS ARE APPLICABLE TO THESE DRAWIANGS. 2. MOUNTING HEIGHT IS TO THE CENTER OF DEVICE UNLESS NOTED OTHERWISE. 3. FOR DEVICES SHOWN AS 48 INCHES MOUNTING HEIGHT, WHEN INSTALLED IN MASONRY BLOCK WALLS, MOUNTING AT 48 INCHES TO THE TOP OF THE OUTLET BOX IS ACCEPTABLE.

AREA OF RESCUE STATIONAR

L

P

PUSH BUTTONPB 48"

C

ELECTRIFIED LOCKEL

AP

DH

FS

TS

KP

ALARM SIRENA 12'AFF

TELEPHONE RINGER - EMERGENCY FIRE PHONETR

LUMINAIRE SCHEDULE

TYPE MANUFACTURERSCATALOG

INFORMATIONFIXTURE DESCRIPTION

LAMP DATA DRIVER DATA INPUT

WATTSVOLTAGE MOUNTING REMARKS

NO. TYPE NO. TYPE

A1

METALUX 2GR SERIES 2' X 4' RECESSED LED TROFFER, REGRESSED ALUMINUM DOOR FRAME HINGED AND LATCHED

WITH 0.125 INCH THICK PATTERN #12 DIFFUSER. 4900 LUMENS

LED 0-10V DIMMING DRIVER 38 277 RECESSEDOR EQUAL

A2

METALUX 2GR SERIES SAME AS TYPE 'A1', 2'X2' VERSION, 4300 LUMENS.

LED 0-10V DIMMING DRIVER 33 277 RECESSEDOR EQUAL

C1

HALO H4 LED 4 INCH LED RECESSED DOWNLIGHT. ALUMINUM CONSTRUCTION, 4000 DEGREE COLOR

TEMPERATURE,80 CRI, INITIAL LUMEN OUTPUT OF 600. WET LISTED. WHITE REFLECTOR WITH

WHITE TRIM RING. LED LED DRIVER 30 277 RECESSEDOR EQUAL SERIES

E1

LITHONIA LV SERIES SINGLE FACE LED EXIT LUMINAIRE, DIE CAST ALUMINUM HOUSING, WHITE BODY AND CANOPY,

POLYCARBONATE COVER, STENCIL FACE, RED LETTERS, AC ONLY.

LED LED DRIVER 1.5 277 UNIVERSALOR EQUAL

EM

LITHONIA INDX SERIES INDUSTRIAL BATTERY PACK LIGHT, 90 MIN ILLUMINATION, HIGH TEMPERATURE BATTERY,

POLYCARBONATE HOUSING AND LENS, GASKETED.

LED LED DRIVER 1.5 277 UNIVERSALOR EQUAL

F1

METALUX SN LED SERIES 4 FOOT LED STRIP LIGHT, WIDE COVERAGE SEMI FROST LENS, HIGH GLOSS BAKED ENAMEL

FINISH, 4000K, 5400 LUMENS, 80 CRI.

LED LED DRIVER 43 277 SURFACEOR EQUAL

F2

LITHONIA LBLED SERIES 4 FOOT LED CURVED BASKET WRAPAROUND LIGHT, #12 PRISMATIC DIFFUSER, NARROW HOUSING,

4000K, 4800 LUMENS.

LED LED DRIVER 32 277 SURFACEOR EQUAL

F3

METALUX SN LED SERIES 4 FOOT LED STRIP LIGHT, WIDE COVERAGE SEMI FROST LENS, HIGH GLOSS BAKED ENAMEL

FINISH, 4000K, 7400 LUMENS, 80 CRI.

LED LED DRIVER 64 277 SUSPENDED

PROVIDE WITH STEM MOUNT KIT

OR EQUAL

H1

HOLOPHANE PHUZION PHS LED, HIGH BAY LUMINAIRE, CAST ALUMINUM HOUSING, PRISMATIC GLASS LENS, PENDANT

MOUNTING, UPLIGHT, 4000K, 80 CRI, WIDE OPTIC, WHITE FINISH, 18000 LUMENS, HOOK

MOUNT WITH SAFETY CHAIN LED LED DRIVER 166 277 SUSPENDED

SUSPEND 24'AFF TYPICAL.

OR EQUAL SERIES

U1

FAIL SAFE UCL SERIES 2 FOOT LED UNDERCABINET FIXTURE, SOLID FACE, ACRYLIC LENS, WHITE FINISH, 3500K,

750 LUMENS/FT, INTEGRAL TOGGLE SWITCH.

LED LED DRIVER 9 120 SURFACEOR EQUAL

V1

TERON VICEROY SERIES 2 FOOT LED VANITY FIXTURE WITH (2) 6W LED STRIPS, SOLID FACE, ACRYLIC LENS,

UP/DOWNLIGHT HOUSING, STEEL TEXTURED WHITE HOUSING, 4000K

LED LED DRIVER 20 277 SURFACEOR EQUAL

W1

LITHONIA D SERIES SIZE 0 EXTERIOR WALL MOUNTED AREA FIXTURE, P1 VERSION, FORWARD THROW

DISTRIBUTION.SINGLE PIECE DIE-CAST ALUMINUM HOUSING,DARK BRONZE FINISH, 4000K,

BI-LEVEL 50% MOTION SENSOR, GLARE SHIELD. LED LED-DRIVER 50 277 WALL

SEE DRAWINGS FOR MOUNTING HEIGHT

OR EQUAL

W2

LITHONIA DSXW SERIES SIZE 1 EXTERIOR WALL PACK, 10 LED, TYPE II DISTRIBUTION SINGLE PIECE DIE-CAST

ALUMINUM HOUSING, SINGLE PIECE DIE CAST ALUMINUM HOUSING, DARK BRONZE FINISH,

4000K. LED LED-DRIVER 14 277 WALL

SEE DRAWINGS FOR MOUNTING HEIGHT

OR EQUAL

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:2

4 P

M

E1437-14-112

REPLACE BOILER PLANT 10.26.18ELECTRICAL SYMBOLS AND

ABBREVIATIONS

100% CONSTRUCTION DOCUMENT

5615-193 E1.DWG

AS NOTED

Page 2: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

SEE DRAWINGS AND ONE-LINE

FOR EXACT QUANTITY AND

SIZE OF WIRING AND

CONDUITS

15-193 E2.DWG

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Ve

tera

ns A

ffa

irs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

10 - BOILER PLANT

CH MB CH

Project Phase

www.jlgarchitects.com

copyright © 2015

214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

KEY PLAN

437-14-112

REPLACE BOILER PLANT 10.26.18

100% CONSTRUCTION DOCUMENT

Dwg. of 69

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

DATE 10-26-18

ELECTRICAL SITE PLAN AND DETAILS

AS NOTED

0' 30'15' 60'

0' 30'15' 60'

57

E2

Page 3: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

0' 4'2' 8'

0' 4'2' 8'

15-193 E3.DWG

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Ve

tera

ns A

ffa

irs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

10 - BOILER PLANT

CH MB CH

Project Phase

www.jlgarchitects.com

copyright © 2015

214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

KEY PLAN

437-14-112

REPLACE BOILER PLANT 10.26.18

100% CONSTRUCTION DOCUMENT

Dwg. of 69

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

DATE 10-26-18

ELECTRICAL DEMOLITION PLANS

AS NOTED

58

E3

Page 4: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

3

4 3

4

3

3

3

3

43

3 3

4

BOILER ROOM

101

ELECTRICAL

102

VESTIBULE

100

SHOP

105

GENERATOR

ROOM

107

STORAGE

CLOSET

106

HOUSEKEEPING

CLOSET

104

OFFICE/CONTROL

103

LOCKER ROOM

108

LOWER LEVEL

001

SHOP ALCOVE

105A

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1

F1

F1 F1 F1 F1

F1F1F1F1

F1

F1

F1

F1

F1 F1

F1

F1

E1

A1

B1

A1

A2

EB101N1 EB101N2 EB101N3

TO MEZZANINELEVEL LIGHTS,SEE SHEET E5

E1

F1

E1

TO TUNNELLIGHTS

E1

E

M

M

V1

U1

C1B1

1

W1 W2

W2

W1

W1

W1

W1

E1

U1

U1

1

D

EB101N3-5

EB101N3-3

EB101N3-9

EB101N3-7

B1

B1B1

D

TO UPPER LEVEL LIGHTINGSEE SHEET E5

TO UPPER LEVEL LIGHTINGSEE SHEET E5

W1

W1

W1 W1 W2

W1

W15

4

4

44

5

6

W1

54444

4

4

4

EB101N1-28

F1 F1 F1 F1 F1 F1 F1 F1

EM

EM

EM EM

EM

F1 F1 F1 F1

F1 F1 F1 F1 F1 F1

7

2

EM

EM

EM

EM

EM

EB101N3-11

EB101N3-13

EB101N3-15

VIA PHOTOCELL

VIA PHOTOCELL

PC 9

3

EM

EM

EM

nl

F1

F1

10

TO UPPER LEVEL LIGHTINGSEE SHEET E5

7 7 7 77

8 8 8

2 HOUR RATED WALL

1 HOUR RATED WALL

C

EXTERIOR LIGHTING CONTACTOR

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:2

6 P

M

E4437-14-112

REPLACE BOILER PLANT 10.26.18MAIN LEVEL REMODELING

PLAN - LIGHTING

100% CONSTRUCTION DOCUMENT

59

1/4" = 1'-0"1MAIN LEVEL REMODELING PLAN - LIGHTING

1

PLAN NOTES:

TO NEAREST AVAILABLE 120V RECEPTACLECIRCUIT.

WALL MOUNT AT 7' AFF.

CONNECT VESTIBULE LIGHT TO OUTDOOR LIGHTINGFOR CONTROL VIA PHOTOCELL.

MOUNT CENTER OF FIXTURE AT 16'-4".

MOUNT CENTER OF FIXTURE AT 9'-0".

MOUNT CENTER OF FIXTURE AT 12'-0".

MOUNT FIXTURE BELOW PIPE RACKING, COORDINATEWITH MECHANICAL CONTRACTOR.

MOUNT FIXTURE TO BOTTOM OF CATWALK SYSTEM.

PROVIDE PHOTOCELL TO CONTROL OUTDOOR LIGHTINGAND OTHER FIXTURES AS NOTED.

COORDINATE EXACT PLACEMENT OF LIGHT FIXTURES WITHMECHANICAL SYSTEMS IN THIS ROOM.

2

3

15-193 E4.DWG

N

4

5

6

7

8

9

AS NOTED

10

Page 5: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

OS

4

F2 V1

F3 F3

A1

A1

BOILER ROOM

101

BATHROOM

203

OFFICE

202

BOILER ROOM

101

H1 H1 H1 H1 H1

H1

H1 H1H1H1H1H1

H1 H1 H1H1 H1

H1

D

1

TO SWITCH BELOW,SEE SHEET E4

EB101N3-2

EB101N3-4

3

3

3

EM

EM

EM EM

EM

EM4

4 4

4

EM

3

F3 F3

UPPER LEVEL

201

F3 F3

F3 F3

16'AFF (TYP)

2 HOUR RATED WALLUPPER

MEZZANINE

301

F1F1

2

3

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:2

7 P

M

E5437-14-112

REPLACE BOILER PLANT 10.26.18UPPER LEVEL REMODELING

PLAN - LIGHTING

100% CONSTRUCTION DOCUMENT

60

1/4" = 1'-0"1UPPER LEVEL REMODELING PLAN - LIGHTING

1/4" = 1'-0"2UPPER MEZZANINE REMODELING PLAN - LIGHTING

1

PLAN NOTES:

TO UPPER MEZZANINE LIGHTING, SEE 2/E5 FOR CONTINUATION.

TO LIGHTING ON MEZZANINE BELOW, SEE 1/E5 FOR CONTINUATION.

TO SWITCH BELOW, SEE 1/E5 FOR CONTINUATION.

MOUNT TO CEILING STRUCTURE ABOVE CATWALK.

2

15-193 E5.DWG

N

3

4

AS NOTED

Page 6: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

48"

J

J

GWP

48"

48"

32 33

31

30

EX

28

29

48"

1 2 3

EX

G

G G

48" 48"

GWP

ACG

J

ACG

G

6

GWP

GWP

GWP

GWP

GWP

GWP

GWP

GWP

EWCG

GWP

25

26

48" 48"

GWP

GWP

GWP

34

13

8

4

9

10

5

J

J

J

EX

20

22 23 24

GWP

GWP

27

48"

21

J

BOILER ROOM

101

ELECTRICAL

102

VESTIBULE

100

SHOP

105

GENERATOR

ROOM

107

STORAGE

CLOSET

106

HOUSEKEEPING

CLOSET

104

OFFICE/CONTROL

103

LOCKER ROOM

108

LOWER LEVEL

001

SHOP ALCOVE

105A

EB101N1EB101N2EB101N3

FACP

T10-LV1

EXISTING EMERGENCYDOMESTIC WATER PUMPS

EXISTINGFAN

CHEMICALPUMPS

EXISTINGTRANSFERPUMPS

BOILER B-1 BOILER B-2 BOILER B-3

ANN

EXISTING GENSETANNUNCIATORS

AC

MOA

AC

MOA

REF

MICRO

NEW DAYTANK ANDPUMPS

1

9

7

6

4

5

10-SWBD

ANN

NEW GENSETANNUNCIATOR

EB101N1-13,15

EB101N1-20,22

EB101N1-33

EB101N1-16,18

EB101N1-4

EB101N1-10,12,14

10

12

EB101N1-8

EB101N1-27

EB101N1-21,23,25

21 2123 2325 25 21

EB101N1-2

EB101N1-45

EB101N1-47

EB101N1-1,3

EB101N1-6

EB101N1-35,37

EB101N1-19

48" 48" 48"

48"48"

48" 48"

SALVAGEDFEEDWATERPUMPSP-1 AND P-2

EB101N1-49,51

48"

48"

48"

TK-01

8

SP-1

HTP-01

WH-2UNDER COUNTER

ST-1

IN PIT BELOW

WH-3

WH-4

DA-1

BATTERYCHARGER

EB101N2-11EB101N2-13,15,17

EB101N3-19,21,23 (3)#10,#10G IN 3/4"C.

ANNANNANN

EB101N1-7,9,11

7

9

EB101N1-43

11 2

20

20

20

20

20

22

22

22

22

20

10

4949 51

51

11

37 35

14

EXHAUST FAN VFDS

AC

AC

EB101N2-35

12

13

14

EXISTINGVFD

EXISTINGVFD

EF-1 EF-2 EF-3

EB101N1-5

3 1

1

3

1616 1818

EF-5

BOILER COMPRESSR BC-1 BOILER COMPRESSR BC-2 BOILER COMPRESSR BC-3

P1 P2

P1

P2

23

EB101N2-39

EB10N1-34

EB101N1-36

15

15

DP-01

16 16

16

P-3

P-4

P-6 P-7

17

EB101N1-38

3

GENERATORREMOTEE-STOP BUTTON

P-8

P-9

EF-6

BELOW LANDING

AC

18

18

SEE SHEET E2 FOR CONTINUATION

19

19

SEE SHEET E2 FOR CONTINUATION

20

400KW GENERATOR

2122

EXHAUST FAN EF-5ECM CONTROLLER

EB101N1-38

23

EB101N1-4024

25

EB101N1-48

26

26

27

1 HOUR RATED WALL

2 HOUR RATED WALL

28

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:2

8 P

M

E6437-14-112

REPLACE BOILER PLANT 10.26.18MAIN LEVEL REMODELING PLAN

- POWER

100% CONSTRUCTION DOCUMENT

61

1/4" = 1'-0"1MAIN LEVEL REMODELING PLAN - POWER

PROVIDE NEW MOA, SEE SECTION 26 27 26 WIRINGDEVICES.

PROVIDE 3/4" PLYWOOD BACKBOARD FROM FLOORTO 8'AFF, PAINT WITH TWO COATS FIRE RETARDANTPAINT. DO NOT PAINT OVER UL LABEL.

PROVIDE SEPARATE 120V CIRCUIT FOR AIRCOMPRESSOR CONTROL RELAYS AND ADJACENT AIRDRYER.

NEW UNDERGROUND FEEDER CONDUITS, SEE SHEETE2 AND DETAIL 2/E10 FOR REQUIREMENTS.

CUT AND PATCH EXISTING CONCRETE FLOOR ASREQUIRED FOR INSTALLATION OF NEW CONDUITS,ROUTE SHOWN IS APPROXIMATE, COORDINATE WITHHOLDOUTS ON ELECTRICAL EQUIPMENT.

NEW 400 KW GENERATOR, SEE ONE LINE DIAGRAMON E13 FOR WIRING REQUIREMENTS. MAXIMUMDIMENSIONS ON GENERATOR ARE 138 INCHES LONGBY 65 INCHES WIDE. BASIS OF DESIGN ISCATERPILLAR E13 SERIES.

CIRCUIT BREAKERS REQUIRED TO BE MOUNTED ONNORTH SIDE OF GENSET.

WATER JACKET HEATER, FIELD COORDINATE EXACTLOCATION ON GENSET.

PROVIDE 120V CONNECTION TO MASTER CONTROLPANEL, COORDINATE WITH MECHANICAL.

RECONNECT EXISTING COMPRESSOR THROUGH NEWDISCONNECT TO CIRCUIT INDICATED.

RECONNECT EXISTING AIR DRYER THROUGH NEWDISCONNECT TO CIRCUIT INDICATED.

PROVIDE 120V CONNECTION FOR REINSTALLATIONOF EXISTING UNDERGROUND TANK MONITORINGSYSTEM CONTROL PANEL, RECONNECT EXISTINGALARMS AND MONITORING DEVICES AND REINSTALLALL EQUIPMENT.

ALL ELECTRICAL CONDUIT TO BE CONCEALED IN THISROOM, CUT AND PATCH EXISTING WALLS ASREQUIRED FOR INSTALLATION OF NEW DEVICES.

PROVIDE EQUAL TO ASCO MTS SERIES MANUALTRANSFER SWITCH WITH TEMPORARY GENERATORCONNECTIONS, SWITCHED NEUTRAL, NEMA 3RENCLOSURE,INTEGRAL QUICK CONNECT CAMLOCKCONNECTIONS. SEE 2/E10 FOR WIRINGREQUIREMENTS.

13

14

15

15-193 E6.DWG

N

16

17

AS NOTED

18

19

20

21

22

PLAN NOTES:

1 PROVIDE 120V CONNECTION ON DEDICATED20A CIRCUIT TO ELECTRIC DOOR LOCKINGHARDWARE POWER SUPPLIES, COORDINATEWITH HARDWARE SUPPLIER FOR EXACTQUANTITY OF POWER SUPPLIES TO BE USED.

PROVIDE 120V CONNECTION ON DEDICATED20A CIRCUIT TO INTRUSION DETECTIONSYSTEM EQUIPMENT.

PROVIDE NEW STARTER/DISCONNECTS AND RECONNECTSALVAGED PUMPS, SEE MOTOR AND EQUIPMENT SCHEDULEFOR ADDITIONAL INFORMATION.

PROVIDE 120V CONNECTION WITHDISCONNECT TO ELECTRIC COOKTOP.

PROVIDE RECEPTACLE AT SHELF LOCATIONFOR MICROWAVE, COORDINATE EXACTMOUNTING HEIGHT WITH CASEWORKELEVATIONS.

PROVIDE 120V CONNECTION TO MEDGASALARM PANEL, COORDINATE WITH MECHANICALCONTRACTOR.

PROVIDE DEDICATED 20 CIRCUIT FOR FIRE ALARMCONTROL PANEL.

CONNECT EXISTING RELOCATED FUEL OIL PUMPS, PROVIDEWITH NEW STARTERS, SEE MOTOR AND EQUIPMENTSCHEDULE FOR ADDITIONAL INFORMATION.

PROVIDE 120V CONNECTION OF DEDICATED CIRCUITFOR CARD ACCESS SYSTEM CONTROL PANELS.

(3)#6,#10G IN 1" CONDUIT.

PROVIDE 120V CONNECTION TO DANGEROUSGAS DETECTION SYSTEM CONTROL PANEL, COORDINATEWITH MECHANICAL CONTRACTOR.

RECIRCUIT EXISTING PUMPS THROUGH EXISTING WALLMOUNTED DISCONNECTS TO NEW PANEL SHOWN.

PROVIDE SINGLE POINT 208V/1 PHASE CONNECTION TOSUMP CONTROL PANEL PER MOTOR AND EQUIPMENTSCHEDULE. PROVIDE SEPARATE 120V CIRCUUIT FORAUDIBLE ALARM AS NOTED ON THE PLANS.

RECIRCUIT EXISTING PUMPS THROUGH EXISTING FLOORMOUNTED VFDS TO NEW PANEL, SEE MOTOR ANDEQUIPMENT SCHEDULE FOR PANEL AND CIRCUIT NUMBER.

2

3

4

5

6

7

8

9

10

11

12

23

24

25

26

27

28

Page 7: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

ACG

1617

18

11

19

12

J

15

14

7

BOILER ROOM

101

UPPER LEVEL

201

BATHROOM

203

OFFICE

202

EXISTINGDATARACK

EXISTINGVISNMETERS

EB101N1-27,29,31

PAGINGRACK

EB101N1-39,41

EB101N1-53

EB101N1-37

EF-1EF-2

EF-3

AH-1

EF-4

AH-2

48"

48"29

31

EB101N1-26

2

SS-21

2 HOUR RATED WALL

TO PLATFORM ABOVE

48"27

VIDEO SURVELLANCERACK

UPPER

MEZZANINE

301

SS-1

1

WH-1

TO OFFICE BELOW

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:2

9 P

M

E7437-14-112

REPLACE BOILER PLANT 10.26.18UPPER LEVEL PLAN - POWER

100% CONSTRUCTION DOCUMENT

62

1/4" = 1'-0"1UPPER LEVEL REMODELING PLAN - POWER

1/4" = 1'-0"2UPPPER MEZZANINE LEVEL REMODELING PLAN - POWER

PLAN NOTES:

1 WIRING BETWEEN CONDENSING UNIT AND EVAPORATORUNITS BY MECHANICAL CONTRACTOR.

PROVIDE (2) 20A/120V CIRCUITS FOR EXISTING VISN METERS,RECONNECT (7) EXISTING METER DISCONNECTS, ALTERNATE CIRCUITBETWEEN EACH DISCONNECT.

2

15-193 E7.DWG

N

AS NOTED

Page 8: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

S

S

SF

S

CR

FS

CR

CRS

F

S

S

FA ANNUNS

S

SF

S

CR

H

A

A

A

A

F

S

GENERATOR

ROOM

107

SHOP

105

LOCKER ROOM

108

OFFICE/CONTROL

103

BOILER ROOM

101

LOWER LEVEL

001

ELECTRICAL

102

16' AFF

16' AFF

CARD ACCESS PANEL

INTRUSION DETECTION PANEL

8' AFF(LOWERLEVEL)

9' AFF

9' AFF

9' AFF

P P9' AFF

9' AFF

P

P

A

9' AFF

9' AFF

A

A

IC

M3

16' AFF

AC3

AC3

MS

W

A

A

A

A

IC

P

EXISTING TELEPHONEBLOCKS

A

6

6

A

9' AFF

3

1

66

66

P

3

7

7

6

5

2

7

7

36

3

7

16' AFFA

FIRE SPRINKLER TAMPERAND FLOW SWITCHES

MS

MS

MS

MS

MS

5

5

5

5

A

A

P

5

5

A

5

A

A6

EXISTING FIBER PULLBOX

AP

AP

AP

AP

5

6

TO MEZZANINE LEVEL

4

9' AFF

FS TS 5

8

8

8

8

8

10

WP

11

8

12' AFF

CLG

12

13

13

14

TS

6

6

W

16

15

16

S

16

S

16

S

S

16

S

16

17

FACP

13

12' AFF

12' AFF

12' AFF

12' AFF

12' AFF

12' AFF

12' AFF

12' AFF

12'

12'

W

W

K18

K

18

K

18

K

18

K

18

S

S

12' AFF 13

12' AFF

TR

TR

TR

TR16

TR

8'AFF

8'AFF

TR

TR

19

KP

19KP

19KP

19KP

9

WALLS IN GENERATOR ROOMHAVE A 1 HOUR RATING

1 HOUR RATED WALL

2 HOUR RATED WALL

9'AFF

A

6

CLG

A

6

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:3

0 P

M

E8437-14-112

REPLACE BOILER PLANT 10.26.18MAIN LEVEL REMODELING PLAN

- SYSTEMS

100% CONSTRUCTION DOCUMENT

63

1/4" = 1'-0"1MAIN LEVEL REMODELING PLAN - SYSTEMS

REINSTALL EXISTING ACCESS POINT IN NEW CEILING GRID.

PROVIDE NEW PAGING HORN, CONNECT TO EXISTING BOILERPAGING ZONE.

PROVIDE ADDRESSABLE FIRE ALARM MODULE ANDASSOCIATED CONNECTIONS TO EXTERIOR POST INDICATORVALVE TO MONITOR VALVE POSITION, PROGRAM TOGENERATE TROUBLE CONDITION ON FACP WHEN VALVE ISCLOSED.

INSTALL SALVAGED FIRE PHONE, AND CONNECT TO NEW FIREPHONE ALERT SPEAKER.

PROVIDE TELEPHONE AUDIOV/VISUAL SOUNDER EQUAL TOWHEELOCK UTA SERIES REMOTE RINGER, CONNECT TO FIREPHONE FOR REMOTE ANNUCIATION OF RINGER, PROVIDEREMOTE POWER SUPPLY AS REQUIRED.

PROVIDE NEW SIMPLEX FIRE ALARM PANEL PER SECTION 283100, CONNECT TO EXISTING VA CAMPUS SIMPLEX MAPNETNETWORK CONNECTION IN THIS BUILDING.

PROVIDE KEYED SWITCH WITH CYLINDER TO MATCH VAMASTER KEYING SYSTEM, CONNECT TO CARD ACCESSSYSTEM TO SHUNT DOOR POSITION SWITCH TO ALLOEXTENDED HOLD OPEN.

PROVIDE INTRUSION DETECTION SYSTEM KEYPAD, SEEDETAIL 10/E12 FOR ADDITIONAL INFORMATION.

15-193 E8.DWG

N

AS NOTED

12

13

14

15

16

17

GENERAL NOTES:

1. ALL PAGING SYSTEM WIRING, SECURITY SYSTEM WIRING, ANDCAMERA WIRING TO BE IN MINIMUM 3/4" CONDUIT, ORANGE INCOLOR.

2. ALL FIRE ALARM SYSTEM WIRING SHALL BE IN MINIMUM 3/4"CONDUIT, RED IN COLOR.

3. ALL DATA/TELEPHONE WIRING SHALL BE IN MINIMUM 3/4"CONDUIT, ORANGE IN COLOR, WHERE EXPOSED TO VIEW ORROUTED ACROSS OPEN SPACES.

18

19

PLAN NOTES:

1 PROVIDE EQUAL TO AIPHONE JP-DV SERIES SURFACEMOUNTED. VANDAL PROOF VIDEOINTERCOM SYSTEM.PROVIDE WITH EXTERNALSIGNALING RELAY TO ACTIVATEINTERNALDOORBELL SOUNDERS.

PROVIDE EQUAL TO AIPHONE JPS SERIES 7 INCH VIDEOINTERCOM MASTER STATION, DESKTOP MOUNTING, CONNECTTO EXTERIORDOOR INTERCOM STATION, SEE PLAN NOTE #1.PROVIDE CONNECTION FROM MASTERSTATION TO RELEASEELECTRIC DOORHARDWARE ON EXTERIOR DOOR ADJACENTTO THE EXTERIOR INTERCOM.

PROVIDE CARD ACCESS AND DOOR MONITORING EQUIPMENT,SEE DETAIL 9/E12 FOR TYPICAL ROUGH IN AND WIRINGREQUIREMENTS.

PROVIDE DOOR POSITION MONITORING AT THIS DOOR,CONNECT TO ALARM ANNUNCIATOR PANEL IN CONTROLROOM 103.

INTRUSION DETECTION ALARM .DOOR ALARM TO SOUND UPONDOOR FORCE OR DOOR PROP ALARM, VALID CARD SWIPE ORKEYPAD CODE ENTRY SHALL DEACTIVATE ALARM.

PROVIDE 3/4” CONDUIT FROM CAMERA TO VIDEOSURVEILLANCE SYSTEM RACK ON MEZZANINE LEVEL FORVIDEO SURVEILLANCE CAMERA. MOUNT CAMERA AT HEIGHTINDICATED OR TO CEILING STRUCTURE BOTTOM WHERENOTED.

REINSTALL AND RECONNECT SALVAGED SPEAKER TOEXISTING SPEAKER WIRING.

PROVIDE CEILING MOUNTED MOTION SENSOR,CONNECT TO INTRUSION DETECTION SYSTEM PANEL IN 3/4"CONDUIT.

PROVIDE DATA JACK AT BOILER PLANT MASTER CONTROLPANEL, COORDINATE WITH MECHANICAL CONTRACTOR.PROVIDE CABLING IN 3/4" CONDUIT TO MEZZANINE DATARACK.

INSTALL DEVICE IN LOWER LEVEL UNDERNEATH STAIRSTRUCTURE NEAR STEAM TUNNEL ENTRANCE.

PROVIDE WEATHERPROOF FIRE ALARM HORN/STROBE ABOVEFIRE DEPARTMENT CONNECTION. PROGRAM TO ACTIVATEUPON SPRINKLER SYSTEM FLOW.

2

3

4

5

6

7

8

9

10

11

Page 9: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

S S S

S

F

BATHROOM

203

OFFICE

202

UPPER LEVEL

201

IC

M

9' AFF

EXISTINGDATA RACK

2 2

1

AP

A

3

4

5

TO LOWER LEVEL

J

A

CLG CLG

CLG

6

CLG

CLG

DS

DS

DS

DS

S

S S S

S

7

7J

J

S

8

9

9

2 HOUR RATED WALL

9

9

PAGING RACK

VIDEO SURV. RACK

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:3

1 P

M

E9437-14-112

REPLACE BOILER PLANT 10.26.18UPPER LEVEL REMODELING

PLAN - SYSTEMS

100% CONSTRUCTION DOCUMENT

64

1/4" = 1'-0"1UPPER LEVEL REMODELING PLAN - SYSTEMS

PLAN NOTES:

1 PROVIDE EQUAL TO AIPHONE JPS SERIES 7 INCH VIDEO INTERCOMSTATION, DESKTOP MOUNTING, CONNECT TO EXTERIOR DOORSTATION. PROVIDE CONNECTION TO RELEASE ELECTRIC DOORLOCK FROM MASTER STATION.

REINSTALL SALVAGED PUBLIC ADDRESS SYSTEM SPEAKER.

INSTRUSION DETECTION SYSTEM AUDIBLE ALARM. DOOR ALARM TOSOUND UPON DOOR FORCE OR DOOR PROP ALARM, VALID CARDSWIPE OR KEYPAD CODE SHALL DEACTIVATE ALARM.

PROVIDE (2) 2" CONDUITS FOR NEW COMMUNICATIONS CABLING,ROUTE ADJACENT TO MECHANICAL PIPING.

ROUTE COMMUNICATIONS CONDUITS DOWN WALL INTO EXISTINGDATA CABINET.

ROUTE COMMUNICATIONS CONDUIT DOWN WALL AND STUB INTOACCESSIBLE CEILING SPACE IN CONTROL OFFICE BELOW.

MOUNT REMOTE TEST SWITCH FOR DUCT DETECTORS INACCESSIBLE SPACE ABOVE CATWALK, FIELD COORDINATE EXACTLOCATION.

PROVIDE TELEPHONE AUDIOV/VISUAL SOUNDER EQUAL TOWHEELOCK UTA SERIES REMOTE RINGER, CONNECT TO FIREPHONE FOR REMOTE ANNUCIATION OF RINGER, PROVIDE REMOTEPOWER SUPPLY AS REQUIRED.

PROVIDE DUCT SMOKE DETECTOR IN SUPPLY AND RETURN WITHCONNECTION TO FAN SHUTDOWN RELAY.

2

3

4

5

6

15-193 E9.DWG

N

AS NOTED

7

8

GENERAL NOTES:

1. ALL PAGING SYSTEM WIRING, SECURITY SYSTEM WIRING,AND CAMERA WIRING TO BE IN MINIMUM 3/4" CONDUIT,ORANGE IN COLOR.

2. ALL FIRE ALARM SYSTEM WIRING SHALL BE IN MINIMUM 3/4"CONDUIT, RED IN COLOR.

3. ALL DATA/TELEPHONE WIRING SHALL BE IN MINIMUM 3/4"CONDUIT, ORANGE IN COLOR, WHERE EXPOSED TO VIEW ORROUTED ACROSS OPEN SPACES.

9

Page 10: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

J

800

A-3

P

EXISTING BUILDING 10SWITCHGEAR MAIN SWITCH480V

BUILDING 10GENERATOR300 kVA

BUILDING 10SWITCHBOARD480V, 800A

BUILDING

10 ATS

XFMR101C2,45.0 kVA

PANEL

101C2

WELDINGXFMR,15.0 kVA

WELDINGPANEL240V

PANEL

101W2

G

500A-3P

100

A-3

P

60

A-3

P

PANEL101W1480V

MCC10480V

600

A-3

P

XFMR

T-101C1

30 kVA

100

A-3

P

100

A-3

P

60

A-3

P

BLDG

50

PANEL

AIR COOLED CHILLER ACCH-4

SWITCH

SECTIONALIZINGSECTIONALIZING

SWITCH

EXISTING

SAC-2SAC-1

23.9KV

XCEL SOURCE #3

800

150E 150E

23.9KV

XCEL SOURCE #4

M

- EPDM STRESSCONE TERMINATIONS

- ELBOW TERMINATIONS

- FUSE

- SWITCH

- TRANSFORMER

- METER

- CURRENT TRANSFORMER

- POTENTIAL TRANSFORMER

EXISTING

25KV SERVICEDISCONNECTSWITCHGEARWITH METERINGSS-SOUTH

25E

SWITCH

SECTIONALIZING

S56-1

50E50E

PULL BOX

CHILLER PLANT FEED#1 CHILLER PLANT FEED#2

ADD FUSE

EXISTING VAULT

EXISTING

50E

T10-1

BOILER PLANT FEED #1 -SEE 2/E10

T10-2

BOILER PLANT FEED #2 -SEE 2/E10

50E

SWITCH

SECTIONALIZING

S10-1

NEW

TO SPARE OUTPUT

800A-3P

KIRK KEYINTERLOCK

SEE

1/E12

K K KDRAW OUT800A-3PLSIG

DRAW OUT800A-3PLSIG

T10-LV1150 KVA-480VKV-PRI 120/208-SEC

50A

-3P

PANEL

EB101N3

(4)3

/0+

#6G

ND

IN

2"C

.

SPD

50A

-3P

KIRK KEYINTERLOCK

LSIG 200

A-3

P

50A

-3P

100

A-3

P

90A

-3P

15A

-3P

225

A-3

P

PANELEB101N1

PANEL

EB101N2

SPD

BOILER

90A

-3P

BOILER

INTEGRAL ATS -OPEN TRANSITION

(4) 3/0+#6 GNDIN 2"C.

BLDG

50

PANEL

(4)#

3+

#8

GN

D IN

2"

C.

800

A-3

P

800

A-3

P

INTEGRAL ATS -OPEN TRANSITION

G

DETAIL NOTES:

(4) 3/0+#6 GNDIN EACH OF (2)2"C.

DETAIL NOTES:

(4) 300MCM IN EACH OF (3) 3 "C.

(4) 300MCM +1/0G

IN EACHOF(3) 2 1/2"C.

(4)#

8+

#1

0 G

ND

IN

1"

C.

T10-LV2

30 KVA-480V

KV-PRI120/208-SEC

BOILER

90A

-3P

ST-1

70A

-3P

15A

-3P

100

A-3

P

40A

-3P

30A

-3P

30A

-3P

AH-1

30A

-3P

AH-2

15A

-3P

15A

-3P

200

A-3

P

EF-1EF-2

15A

-3P

EF-3

30A

-3P

- DASHED INDICATES EXISTING EQUIPMENT OR WIRING

- SOLID LINE INDICATES NEW EQUIPMENT OR WIRING

#1 #3 #2WH-3

225

A-3

P

WH-4DA-1

HPT-01

SP

AR

E

BOILER PLANTFEED #1SEE 3/E10 FORCONTINUATION

SP

AR

E

SEE1/E12

SWBD-10

KIRK KEYINTERLOCK

800 AMPERES, 480/277V, 3 PH, 4 WIRE, 65,000 AIC

SP

AR

E

BOILER PLANTFEED #2SEE 3/E10 FORCONTINUATION

SP

AR

E

SWITCH

SECTIONALIZING

S56-2

EXISTING

60A

-3P

SP

AR

E

60A

-3P

SP

AR

E

40A

-3P

SP

AR

E

30A

-3P

SP

AR

E

PROVIDE TEMPORARY POWER TO BUILDING 50 PANEL

VIA EXISTING BURIED CONDUIT DURING CONSTRUCTION

OF NEW BUILDING 10 SERVICE. RETAIN EXISTING

TRANSFORMER T-101C1 AND PANEL 101C1 DURING

CONSTRUCTION FOR TEMPORARY CONNECTION OFF OF

EXISTING BUILDING #10 SWITCHGEAR. REMOVE WHEN

NEW SYSTEM IS OPERATIONAL.

DISCONNECT THE EXISTING 25KV FEEDER THAT IS

CURRENTLY CONNECTED TO S56-2, PULL BACK INTO

THE ADJACENT VAULT, AND RECONNECT INTO NEW

SWITCH S10-1.

PROVIDE NEW 25KV FEED INTO S56-2 FROM NEW

SWITCHGEAR S10-1, QUANTITY (3) 4/0 CU 25KV ,

4/0 CU 600V NEUTRAL IN 4" CONDUIT.

QTY (3) 4/0 CU 25 KV, 4/0 CU 600V NEUTRAL IN

EXISTING 4" CONDUIT

480V/277

3-PHASE

T10-1

750 KVA

23.9 KV-PRI

277/480-SEC

(3)#

8+

#10

GN

D

IN 3

/4"

C.

SEE MOTOR AND EQUIPMENT SCHEDULE FOR WIRING AND

CONDUIT REQUIREMENTS.

DETAIL NOTES:

T10-2

750 KVA

23.9 KV-PRI

277/480-SEC

(4) 300MCM IN EACH

OF (3) 3 " C.

(3)#

8+

#10

GN

D

IN 3

/4"

C.

(4)#

3+

#8 G

ND

IN2

" C

.

(4)

3/0

+#

6

GN

D IN

2"C

.

EXISTING 25KV SERVICE

DISCONNECT SWITCHGEAR

WITH METERING

SS-NORTH

1. PROVIDE CONTINUOUS RUNS OF 25 KV WIRING,

SPLICING IN VAULTS IS NOT ALLOWED.

DETAIL GENERAL NOTES:

(4) 300MCM IN EACH

OF (3) 3 " C.

(4) 300MCM IN EACH

OF (3) 3 " C.

EXISTING

PULLBOX

TO 5 KV

SERVICE

T10

BOILER

PLANT

500 KVA

PANEL

101C1

400KW GENERATOR

EXISTING BUILDING #10 TRANSFORMER TO REMAIN

OPERATIONAL DURING CONSTRUCTION TO PROVIDE

POWER TO TEMPORARY BOILERS, PUMPS, BUILDING

#50, AND OTHER TEMPORARY CONSTRUCTION

POWER REQUIREMENTS. REMOVE TRANSFORMER AND

PAD AFTER INSTALLATION AND TESTING OF

PERMANENT SYSTEMS. SEE DETAIL 4/E2.

(4) 300MCM +1/0G

IN EACH OF (3) 2 1/2"C.

TEMPGENSETINLET

TEMPGENSETMANUALSWITCH

SP

AR

E

(4) 300MCM +1/0G

IN EACHOF(3) 2 1/2"C.

PROVIDE EQUAL TO ASCO MTS SERIES MANUAL TRANSFER

SWITCH FOR TEMPORARY GENERATOR CONNECTIONS,

SWITCHED NEUTRAL, NEMA 3R ENCLOSURE,INTEGRAL QUICK

CONNECT CAMLOCK CONNECTIONS. MOUNT ON EXTERIOR

WALL PER FLOORPLANS.

LS

I

LS

I

THE EXISTING GENERATOR AND ATS MAY STAY IN PLACE

TO PROVIDE EMERGENCY POWER TO THE TEMPORARY

BOILER DURING CONSTRUCTION. CONTRACTOR SHALL

PROVIDE A TEMPORARY OUTDOOR GENERATOR WHEN THE

EXISTING GENSET IS REMOVED UNTIL THE NEW BOILER

SYSTEM IS OPERATIONAL.

1

1

1 3 2

BUILDING 10 ELECTRICAL ONE-LINE DIAGRAM- DEMOLITIONNO SCALE

1E1025 KV ONE LINE DIAGRAM - REVISED

NO SCALE

3E10

BUILDING 10 ELECTRICAL ONE-LINE DIAGRAMNO SCALE

2E10

1

1

2

2

2

2

411 1226179 18

3

33

105 13

1

11111 1 1 1 1 1 1 1 1

3

3

2

2

T56-1

M

25E 25E 25E

M

25E

T56-2 T56-3

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:3

1 P

M

E10437-14-112

REPLACE BOILER PLANT 10.26.18ELECTRICAL ONE-LINE

DIAGRAMS

100% CONSTRUCTION DOCUMENT

6515-193 E10.DWG

AS NOTED

Page 11: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

EB101N1 MCB 400A NEMA 1 107

208Y/120, 3 PH., 4W.

400 AMP 10,000 SURFACE SWBD

CKT

#

TRIP

AMPSPOLE

LOAD IN VOLT-AMPERES LOAD

DESCRIPTIONPH LOAD DESCRIPTION

LOAD IN VOLT-AMPERES TRIP

AMPSPOLE

CKT

#LIGHTING RECPT MTRS&EQUIP KITCHEN HEAT/AC HEAT/AC KITCHEN MTRS&EQUIP RECPT LIGHTING

1 20 1 1000 EXT.REC A LOCKER ROOM 400 20 1 2

3 20 1 600 EXT.REC B 103 1000 20 1 4

5 20 1 800 102 REC C 103 1200 20 1 6

7 20 1 1600 CARD ACCESS A MICROWAVE 1600 *20 1 8

9 20 1 1600 PWR SUPPLY B REF 1200 *20 1 10

11 20 1 1600 IDS SYSTEM C COOKTOP 1600 20 1 12

13 20 1 400 SHOP REC A 103 200 20 1 14

15 20 1 400 SHOP REC B WEST EXT.REC 400 20 1 16

17 20 1 400 SHOP REC C WEST EXT.REC 400 20 1 18

19 20 1 400 SHOP REC A 001 REC 600 20 1 20

21 20 1 400 SHOP REC B 101 REC 800 20 1 22

23 20 1 400 SHOP REC C DAY TANK PUMPS 1600 20 1 24

25 20 1 400 SHOP REC A CATWALK REC 800 20 1 26

27 20 1 800 OFFICE 202 B TUNNEL LIGHTS 1400 20 1 28

29 20 1 1200 IT RACK C SUMP PUMP 1664 15 30

31 20 1 1200 PAGING RACK A 2 32

33 20 1 1000 101 REC B SUMP ALARM 600 20 1 34

35 20 1 1000 MEDGAS C EXT. RECEPT 600 20 1 36

37 20 1 1000 GAS DET. A MASTER CONTROL 1200 20 1 38

39 20 1 400 VISN METERS B TANK MONITORING 1200 20 1 40

41 20 1 400 VISN METERS A SPARE 15 42

43 20 1 1600 FACP B 44

45 20 1 1200 106,107 C 3 46

47 20 1 1200 001 REC A AIR DRYER 20 1 48

49 20 1 400 CHEM.PUMPS B PANEL 101N2 16525 200 50

51 30 SPARE C 19885 52

53 2 A 18505 3 54

55 20 1 SPARE B SPARE 20 50

57 20 1 SPARE C 52

59 20 1 SPARE A 3 54

61 20 1 SPARE B SPARE 20 1 50

63 20 1 SPARE C SPARE 20 1 52

65 20 1 SPARE A SPARE 20 1 54

LOAD TYPEVA / PHASE TOTAL

VA

DEMAND

FACTOR

DIVERSIFIED

LOAD

NOTES:

A B C 1. BREAKERS NOTED WITH * TO BE GFCI

LIGHTING 0 1400 0 1400 1.00 1400

RECEPTACLES 10200 9400 8200 27800 0.50 13900

MOTORS & EQUIP 19125 22085 24369 65579 0.90 59021

KITCHEN EQUIP. 0 0 0 0 0.65 0

HEAT / AC 0 0 0 0 0.90 0

LARGEST MOTOR 0.25 0

TOTAL AMPS: 206 TOTAL VA: 74,321

PANELBOARD LOAD SCHEDULE

PANEL: MAIN: ENCLOSURE: LOCATION:

VOLTS:

RATING: AIC RATING: MOUNTING: FED FROM:

LOAD CALCULATIONS

EB101N2 MLO NEMA 1 107

208Y/120, 3 PH., 4W.

225 AMP 10,000 SURFACE 101N1

CKT

#

TRIP

AMPSPOLE

LOAD IN VOLT-AMPERES LOAD

DESCRIPTIONPH LOAD DESCRIPTION

LOAD IN VOLT-AMPERES TRIP

AMPSPOLE

CKT

#LIGHTING RECPT MTRS&EQUIP KITCHEN HEAT/AC HEAT/AC KITCHEN MTRS&EQUIP RECPT LIGHTING

1 20 1 400 EF-4 A SS-1 2080 30 2

3 40 3000 WH-1 B 2080 2 4

5 2 3000 C SS-2 2080 30 6

7 40 3000 WH-2 A 2080 2 8

9 2 3000 B SUMP PUMP 1300 30 10

11 20 1 1500 BATT.CHARGER C 1300 2 12

13 60 4800 JACKET HTR A HTP-01 2105 15 14

15 4800 B 2105 16

17 3 4800 C 2105 3 18

19 15 830 EX.PUMP P-1 A SPARE 40 20

21 830 B 22

23 3 830 C 3 24

25 15 830 EX.PUMP P-2 A SPARE 15 26

27 830 B 28

29 3 830 C 3 30

31 20 1 720 EF-5 A SPARE 15 32

33 20 1 600 DP-01 B 34

35 20 1 1600 EX. AIR DRYER C 3 36

37 20 1 REC -101 A SPARE 15 38

39 20 1 1600 EX. EXHAUST B 40

41 20 1 720 EF-6 A 3 42

43 20 1 SPARE B SPARE 20 44

45 20 1 SPARE C 2 46

47 20 1 SPARE A SPARE 20 48

49 20 1 SPARE B 2 50

51 20 1 SPARE C SPARE *20 1 52

53 20 1 SPARE C SPARE *20 1 54

LOAD TYPEVA / PHASE TOTAL

VA

DEMAND

FACTOR

DIVERSIFIED

LOAD

NOTES:

A B C 1. BREAKERS NOTED WITH * TO BE GFCI

LIGHTING 0 0 0 0 1.00 0

RECEPTACLES 0 0 0 0 0.50 0

MOTORS & EQUIP 16845 20145 18765 55755 0.90 50180

KITCHEN EQUIP. 0 0 0 0 0.65 0

HEAT / AC 0 0 0 0 0.90 0

LARGEST MOTOR 0.25 0

TOTAL AMPS: 139 TOTAL VA: 50,180

PANELBOARD LOAD SCHEDULE

PANEL: MAIN: ENCLOSURE: LOCATION:

VOLTS:

RATING: AIC RATING: MOUNTING: FED FROM:

LOAD CALCULATIONS

EB101N3 MLO NEMA 1 107

480Y/277, 3 PH., 4W.

225 AMP 25,000 SURFACE SWBD-10

CKT

#

TRIP

AMPSPOLE

LOAD IN VOLT-AMPERESLOAD DESCRIPTION PH LOAD DESCRIPTION

LOAD IN VOLT-AMPERES TRIP

AMPSPOLE

CKT

#LIGHTING RECPT MTRS&EQUIP KITCHEN HEAT/AC HEAT/AC KITCHEN MTRS&EQUIP RECPT LIGHTING

1 20 1 1992 MAIN LVL LTG A 101 LTG -HIGH BAY 2988 20 1 2

3 20 1 539 001 LTG B MEZZ LEVEL LTG 1240 20 1 4

5 20 1 294 102 LTG C SPARE 20 1 6

7 20 1 735 LTG -S. INT A EXISTING WTR.PUMP 3047 15 8

9 20 1 392 EXT. LTG B 3047 10

11 20 1 882 101 LTG C 3047 3 12

13 20 1 343 EXT. LTG A SPARE 20 1 14

15 20 1 LTG - OFFICE/LOCK. B SPARE 20 1 16

17 20 1 SPARE C SPARE 20 1 18

19 30 3878 EX.AIR COMP A EXISTING TRAN.PUMP 2100 15 20

21 3878 B 2100 22

23 3 3878 C 2100 3 24

25 15 830 EX.FUEL PUMP P-6 A EXISTING TRAN.PUMP 15 26

27 830 B 28

29 3 830 C 3 30

31 15 EX.FUEL PUMP P-7 A EX.DOMES.WTR PUMP 2100 15 32

33 B 2100 34

35 3 C 2100 3 36

37 15 1216 BOILER COMPRESSOR A EX.DOMES.WTR PUMP 15 38

39 1216 B 40

41 3 1216 C 3 42

43 15 1216 BOILER COMPRESSOR A SPARE 30 44

45 1216 B 46

47 3 1216 C 3 48

49 15 1216 BOILER COMPRESSOR A SPARE 25 50

51 1216 B 52

53 3 1216 C 3 54

LOAD TYPEVA / PHASE TOTAL

VADEMAND FACTORDIVERSIFIED LOAD

NOTES:

A B C 1. BREAKERS NOTED WITH * TO BE GFCI

LIGHTING 6058 2171 1176 9405 1.00 9405

RECEPTACLES 0 0 0 0 0.50 0

MOTORS & EQUIP 15603 15603 15603 46809 0.90 42128

KITCHEN EQUIP. 0 0 0 0 0.65 0

HEAT / AC 0 0 0 0 0.90 0

LARGEST MOTOR 0.25 0

TOTAL AMPS: 62 TOTAL VA: 51,533

PANELBOARD LOAD SCHEDULE

PANEL: MAIN: ENCLOSURE: LOCATION:

VOLTS:

RATING: AIC RATING: MOUNTING: FED FROM:

LOAD CALCULATIONS

MOTOR NO

LOCATION (ROOM NO)

LOAD IN HORSEPOWER (HP) OR FULL

LOAD AMPS (FLA)

VOLTAGE, PHASE

PANEL AND CIRCUIT NUMBER OR MCC

NUMBER

CONDUCTOR SIZE AND QUANTITY

GROUND CONDUCTOR SIZE

CONDUIT SIZE

CONTROLLER DISCONNECT CONTROL OR AUXILIARY DEVICE (SEE

NOTES)

MAGNETIC STARTER/DISCONNECT

STARTER SIZE

VARIABLE FREQUENCY DRIVE

MANUAL MOTOR CONTROLLER

LOW VOLTAGE SWITCH

OCC SENSOR

CONTROLLER BY (DIV. NO.)

CONTROLLER LOCATION (ROOM

NO.OR AS NOTED)

DISCONNECT SIZE

FUSIBLE / NON FUSIBLE

NEMA RATING

DISCONNECT BY (DIV. NO.)

VFD

DEFINITE PURPOSE RELAY

TIME SWITCH

THERMOSTAT

LOW VOLTAGE SWITCH

OCC SENSOR

FIRE ALARM CONTROL RELAY

FIRE ALARM DUCT DETECTORS

(SUPPLY AND RETURN)

INTERLOCK WITH

1 BOILER B-1 101 40 HP 480, 3 SWBD-10 3 #4 #8 1-1/4" 23 BAS 100A NF 1 26

2 BOILER B-2 101 40 HP 480, 3 SWBD-10 3 #4 #8 1-1/4" 23 BAS 100A NF 1 26

3 BOILER B-3 101 40 HP 480, 3 SWBD-10 3 #4 #8 1-1/4" 23 BAS 100A NF 1 26

4 ST-1 101 3 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 ON UNIT ON UNIT

5 DA-1 101 10 HP 480, 3 SWBD-10 3 #10 #10 3/4" 23 ON UNIT ON UNIT

6 DAY TANK KIT TK-01 107 .5 HP 120, 1 EB101N1-24 2 #12 #12 3/4" 20A NF 1 26

7 WH-1 MEZZ 301 6 KW 208, 1 EB101N2-3,5 2 #8 #10 3/4" 23 BAS 60A NF 1 26

8 WH-2 105 6 KW 208, 1 EB101N2-7,9 2 #8 #10 3/4" 23 BAS 60A NF 1 26

9 WH-3 101 144 KW 480, 3 SWBD-10 3 #3/0 #6 2" 23 BAS ON UNIT

10 WH-4 105 144 KW 480, 3 SWBD-10 3 #3/0 #6 2" 23 BAS ON UNIT

11 AH-1 101 15 MCA 480, 3 SWBD-10 3 #10 #10 3/4" 23 BAS 30A F 30 1 26 3 1

12 AH-2 101 15 MCA 480, 3 SWBD-10 3 #10 #10 3/4" 23 BAS 30A F 30 1 26 3 1

13 HPT-01 101 5 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 BAS 30A NF 1 26

14 SPLIT SYSTEM SS-1 (CONDENSING UNIT) MEZZ 301 20 MCA 208, 1 EB101N2-2,4 2 #10 #10 3/4" ON UNIT

15 SPLIT SYSTEM SS-2 (CONDENSING UNIT) 101-UPPER LVL 20 MCA 208, 1 EB101N2-6,8 2 #10 #10 3/4" ON UNIT

16 M-EF-1 101-ROOF 2 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 102 30A NF 1 26 3

17 M-EF-2 101-ROOF 2 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 102 30A NF 1 26 3

18 M-EF-3 101-ROOF 2 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 102 ON UNIT 3

19 M-EF-4 108- ROOF FRAC 120, 1 EB101N2-1 3 #12 #12 3/4" 23 BAS 20A NF 1 26

20 M-EF-5 102 -ROOF 1/2 HP 120, 1 EB101N2-31 3 #12 #12 3/4" 23 BAS ON UNIT

21 M-EF-6 107 1/4 HP 120, 1 EB10N2-41 2 #12 #12 3/4" 23 BAS 20A NF 1 26

22 BOILER COMPRESSOR BC-1 101 5 HP 480, 3 EB101N3-37,39,41 3 #12 #12 3/4" 23 ON UNIT ON UNIT

23 BOILER COMPRESSOR BC-2 101 5 HP 480, 3 EB101N3-43,45,47 3 #12 #12 3/4" 23 ON UNIT ON UNIT

24 BOILER COMPRESSOR BC-3 101 5 HP 480, 3 EB101N3-49,51,53 3 #12 #12 3/4" 23 ON UNIT ON UNIT

25 EXISTING FEEDWATER PUMP P-1 101 1.5 HP 208, 3 EB101N2-19,21,23 3 #12 #12 3/4" 1 26 101 ON STRT

26 EXISTING FEEDWATER PUMP P-2 101 1.5 HP 208, 3 EB101N2-25,27,29 3 #12 #12 3/4" 1 26 101 ON STRT

27 DIESEL PUMP DP-1 EXTERIOR. 4.9 AMP 120, 1 EB101N2-33 2 #12 #12 3/4" 26 101 20A NF 3R 26

28 EXISTING TRANSFER PUMP P-3 RM 001 3 HP 480, 3 EB101N3-20,22.24 3 #12 #12 3/4" EXISTING

29 EXISTING TRANSFER PUMP P-4 RM 001 3 HP 480, 3 EB101N3-26,28,30 3 #12 #12 3/4" EXISTING

30 EXISTING DOMESTIC WATER PUMP P-8 RM 001 7.5 HP 480, 3 EB101N3-32,34,36 3 #12 #12 3/4" EXISTING

31 EXISTING DOMESTIC WATER PUMP P-9 RM 001 7.5 HP 480, 3 EB101N3-38,40,42 3 #12 #12 3/4" EXISTING

32 EXISTING FUEL PUMP P-6 101 1.5 HP 480, 3 EB101N3-25,27,29 3 #12 #12 3/4" 1 26 101 ON STRT

33 EXISTING FUEL PUMP P-7 101 1.5 HP 480, 3 EB101N3-31,33,35 3 #12 #12 3/4" 1 26 101 ON STRT

34 SUMP PUMP SP-1 001-PIT 2 HP 208, 1 EB101N2-10,12 2 #10 #10 3/4" 23 ON UNIT 30A F 30 1 26

1. ELECTRICAL CONTRACTOR TO FURNISH, SET, AND WIRE AUXILIARY CONTROL DEVICE

2. ELECTRICAL CONTRACTOR TO SET, AND WIRE AUXILIARY CONTROL DEVICE FURNISHED BY OTHERS

3. ELECTRICAL CONTRACTOR TO WIRE AUXILIARY CONTROL DEVICE FURNISHED AND SET BY OTHERS

4. PROVIDE DUCT DETECTOR IN SUPPLY AND RETURN DUCTS AND CONNECT TO FA SYSTEM

MOTOR AND EQUIPMENT SCHEDULE

X

X

X

X

X

X

X

X

X

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:3

2 P

M

E11437-14-112

REPLACE BOILER PLANT 10.26.18ELECTRICAL SCHEDULES

100% CONSTRUCTION DOCUMENT

6615-193 E11.DWG

AS NOTED

Page 12: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

SPD

NOTE:

#6

48"

91.5"

36" 42" 36"42" 42"

1

2

1

2

2

1

DATA PHONE

DATA DATA

DATA-CLOSET#-ROOM#-PLATE#

NOTES:

PHONE-CLOSET#-PLATE#

1 2

3 4

3/4" CONDUIT

48"

CARDREADER

48"

NOTES:

TYPICAL SINGLEDOOR

TYPICAL DOUBLEDOOR

3/4" CONDUIT

SEE NOTE#3

LAN

200W/CH-70V

DATAPORT

200W/CH-70V

DATAPORT

SPEAKER

SPEAKER

DATAPORT

SPEAKER #18/2

GPIODOOR INTERCOM CONTACT

SPEAKER

SEE NOTE #2

SEE NOTE#1

1. ALL EQUIPMENT SHOWN AS DASHED IS EXISTING.

1.

2.

3.

4.

"DATA CLOSET#-ROOM#-PLATE#-JACK#"

4-POLE

TRANSFER

SWITCH

480V/277, 3 PH, 4 WIRE

LOAD

EGC

N G

SERVICE

EQUIPMENT

BONDING

JUMPER

CONDUCTOR

ELECTRODE NEARBY,

PREFERABLY THE

STRUCTURAL STEEL

N

GROUNDING

GROUNDING ELECTRODE

SEPARATELY

DERIVED SYSTEMGEN.

NOTE:

KP

MS

A

NOTES:

120V

PROVIDE OTHER GROUND CONNECTIONS AS

SPECIFIED IN N.E.C. ARTICLE 250-64

TO MOUNTING

STEEL

NEUTRAL BUS IN

DISCONNECT

GROUND BUS

TO DISCONNECT

FRAME GROUNDING ROD

(LOCATED NEAR

DISCONNECT

MOUNTING BASE)

PROVIDE A GROUNDING CONDUCTOR

IN ALL BRANCH CIRCUIT AND

FEEDER CONDUITS, SEE

SPECIFICATION SECTION 26 05 26

GANG

OPERATED

SWITCH

GANG

OPERATED

SWITCH

BUSSING

(TYPICAL)

FUSIBLE

SWITCH

FUSIBLE

SWITCH

GANG

OPERATED

SWITCH

COMPARTMENT

GANG

OPERATED

SWITCH

COMPARTMENT

FUSIBLE

INDIVIDUALLY

OPERATED

SWITCH

COMPARTMENT

FUSIBLE

INDIVIDUALLY

OPERATED

SWITCH

COMPARTMENT

GANG

OPERATED

SWITCH

OPERATING

HANDLE

BEHIND

PADLOCKED

COVER

GANG

OPERATED

SWITCH

OPERATING

HANDLE

BEHIND

PADLOCKED

COVERDOOR

HANDLE

W/PADLOCK

DATA JACK#

ROOM#-PLATE#

D2

101-1

2. SEE SECTION 27 10 05 FOR PLATE AND JACK REQUIREMENTS.

5. LABEL ALL VOICE AND DATA CABLES AT BOTH ENDS WITH

7. DATA JACKS ARE NUMBERED LEFT TO RIGHT, TOP TO BOTTOM.

6. ALL (4) JACKS TO BE CATEGORY 6e CABLES.

4. PLATES ARE LABELED AS SHOWN, NUMBER PLATES ARE CLOCKWISE FROM THE DOOR.

3. DATA JACKS TO BE ORANGE COLOR, PHONE JACKS TO BE IVORY.

1. = (3) DATA, (1) PHONE JACK.

GENERAL NOTES

DETAIL NOTES:

1. CONFIGURE DOOR INTERCOM TO TRIGGER DRY CONTACT

INPUTS ON EXISTING QSC Q-SYS DSP GPIO INPUT. PROGRAM

TO INITIATE DOOR CHIME OVER PA SPEAKERS IN BOILER

PLANT ZONE

2. BOILER PLANT SPEAKERS CURRENTLY CONNECTED TO ZONE

#13, DISCONNECT SPEAKER LINES AND RECONNECT TO SPARE

OUTPUT ON EXISTING QSC DAB-801 SPEAKER MODULE.

REPROGRAM BOILER PLANT AS A SEPARATE PUBLIC ADDRESS

ZONE

SOUND EQUIPMENT

CABINET 10

BOILER PLANT

MEZZANINE

DATAPORT

EXISTING REDUNDANT

AMPLIFIER

EXISTING AUDIO

NETWORK SIGNAL

EXISTING QSC CORE 110F

SERIES DSP/ IO FRAME EXISTING

AMPLIFIERQSC DAB-801

ZONE #13 BLDG 11/12/13

ZONE #14 BLDG 51

ZONE #15 BLDG 10 (BOILER PLANT)

CONFIGURE CARD ACCESS SYSTEM TO DISABLE AUDIBLE

ALARM SIGNAL UPON VALID CARD SWIPE OR FROM IDS

KEYPAD NUMERIC CODE ENTRY.

CONFIGURE CARD ACCESS SYSTEM TO ACTIVATE IDS

SYSTEM AUDIBLE ALARMS UPON DOOR PROP SIGNAL,

PROVIDE 30 SECOND TIMER FUNCTION.

EACH DEVICE SHALL BE GIVEN AN INDEPENDENT ADDRESS

ON THE IDS SYSTEM, AND ASSIGNED TO PARTITION NOTED.

IDS

POWER

SUPPLY

IDS

CONTROL

PANEL

ELECTRIC LATCH

RETRACTION OR

VERTICAL ROD DEVICE

BY DIVISION 08

ELECTRIC HINGE

OR POWER TRANSFER

BY DIVISION 08

BALANCED

DOOR

POSITION

SWITCH

BALANCED

DOOR

POSITION

SWITCH

REQUEST TO

EXIT SENSOR

3/4"

CONDUIT

3/4"

CONDUIT

TO ACCESS CONTROL

SYSTEM PANELS IN

ELECTRICAL ROOM 102

3/4" CONDUIT

TYPICAL

JUNCTION BOX

ELECTRIC STRIKE

BY DIVISION 08

CARD

READER

ELECTRIC HINGE

OR POWER TRANSFER

BY DIVISION 08

DOOR

POSITION

SWITCH

REQUEST TO

EXIT SENSOR

3/4"

CONDUIT

TO ACCESS CONTROL SYSTEM

PANELS IN ELECTRICAL ROOM 102

3/4" CONDUIT

PROVIDE MINIMUM 4" CONCRETE HOUSEKEEPING PAD

REINFORCE WITH #3 BARS AT 12 INCHES ON CENTER

PROVIDE WITH 3/4" CHAMFER EDGE

03

04

02

01

I1

I202

01

I2

I1

I3

I4

01

02

03

04

I2

I1

01

02

03

SEE NOTE #1

SEE NOTE #2 DOOR PROP SIGNAL

I/0 MODULE

THIS DETAIL IS A TYPICAL INSTALLATION, COORDINATE EXACT WIRING AND DOOR

HARDWARE REQUIREMENTS WITH DIVISION 08 AND ACCESS CONTROL SYSTEM SUPPLIER.

DOOR HARDWARE POWER SUPPLIES SHALL BE CENTRALLY LOCATED IN THE MAIN

ELECTRICAL ROOM, SEE POWER DRAWINGS FOR CIRCUIT REQUIREMENTS.

SURFACE MOUNTED CONDUIT IS ALLOWED WITHIN BOILER PLANT, ROUTE CONDUIT DOWN

SECURED SIDE OF DOOR AND STUB CONDUIT THROUGH TO EXTERIOR CARD READER.

DISARM SIGNAL

MS

MS

MS

KP

ALL WIRING IN EMT CONDUIT, 3/4" MINIMUM.

KP

KEYED

BYPASS

SWITCH

KP

4.

SEE NOTE #5 SEE NOTE #5

SEE NOTE #5

IDS MASTER KEYPADOFFICE 103

SEE DWG

IDS MOTION SENSORS

PARTITION #1

BOILER PLANT

PARTITION #2

GENERATOR ROOM 107

PARTITION #3

ELECTRICAL ROOM 102

PARTITION #4

STEAM TUNNEL ENTRY

IDS AUDIBLE ALARM

SEE DWG FOR LOCATION

SEE NOTE#6

SEE NOTE #3

1.

2.

3.

4.

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPD

TRANSFER SWITCH TRANSFER SWITCH

- KEY INTERLOCK

K

AP

PR

OX

IMA

TE

LY

45

IN

CH

ES

APPROXIMATELY 60 INCHES

OPERATOR

K

K

K

OPERATOR

K

K

K

3

SYSTEM GROUNDING DETAILNO SCALE

1E12

DISCONNECT GROUNDING DETAILSNO SCALE

2E12

SWITCHBOARD SWBD-10 ELEVATIONNO SCALE

3E12

S10-1 CIRCUIT DIAGRAMNO SCALE

4E12

S10-1 ENCLOSURE TOP VIEWNO SCALE

5E12

S10-1 SIDE VIEWNO SCALE

6E12

PATCH PANEL SAMPLE LABELSNO SCALE

7E12

TYPICAL COMMUNICATIONS PLATE DETAILNO SCALE

8E12

TYPICAL CARD ACCESS WIRING DETAILNO SCALE

9E12

PAGING AND DOORBELL SYSTEM ONE-LINE DIAGRAMNO SCALE

11E12

TYPICAL INTRUSION DETECTION SYSTEM WIRING DETAILNO SCALE

10E12

AUDIBLE ALARM SHALL SOUND IF DOOR HAS BEEN PROPPED

FOR MORE THAN 30 SECONDS UNLESS BYPASSED WITH

KEYED SWITCH ADJACENT TO DOOR.

AUDIBLE ALARM SHALL SOUND IF DOOR HAS BEEN PROPPED

FOR MORE THAN 30 SECONDS UNLESS BYPASSED WITH

KEYED SWITCH ADJACENT TO DOOR.

5. BALANCED MAGNETIC SWITCH FURNISHED

UNDER SECTION 28 16 00.

6. KEYED SWITCH PROVIDED IN SECTION 28 13 16.

PROVIDE WITH RED/GREEN LIGHTS TO INDICATED

DOOR BYPASS STATUS, MATCH VA KEY TYPE.

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:3

2 P

M

E12437-14-112

REPLACE BOILER PLANT 10.26.18ELECTRICAL DETAILS

100% CONSTRUCTION DOCUMENT

6715-193 E12.DWG

AS NOTED

Page 13: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

(10

") M

IN(1

0")

MIN

CONDUIT ROOF PENETRATION DETAILNO SCALE

1E13

ROOF

EMERGENCY GENERATOR EXHAUSTNO SCALE

2E13

4"

4"

PROVIDE EXOTHERMICWELDING FOR ALLCONNECTIONS (TYPICAL)GROUND

ROD(TYPICAL)

2"

TRANSFORMER PAD AND GROUNDING DETAILNO SCALE

3E13

EMERGENCY GENERATOR WITH INTEGRAL RADIATORNO SCALE

4E13

VIBRATION ISOLATORSTO STRUCTURE ( TYP)

CONDUIT, TYP.

BATT INSULATION

PREFABRICATED FORMED 0.06"

THICK ALUMINUM FLASHING ROUND COLLAR

WITH MIN. 3" WIDE FLANGE. ATTACH TO ROOF

PER MANUFACTURER'S INSTRUCTIONS

MULTIPLE MEMBRANE STRIPPING PLIES FEATHERED

AT FIELD OF ROOF BY ROOFING CONTRACTOR.

PRIME FLANGE BEFORE STRIPPING.

SEAL-OFF FITTING, TYP.

STAINLESS CLAMP, TYP.

PREFABRICATED RUBBER BOOT CAP

WITH GRADUATED STEPS &

WEATHER-PROOF PRESSURE SEAL

TO COLLAR

SEALANT AT PENETRATION

TO MEMBRANE JUNCTURE

BY ROOFING CONTRACTOR

ROOF MEMBRANE

METAL ROOF

WATER CUT-OFF MASTIC

COMPATIBLE WITH ROOF

MEMBRANE

CONDUIT CLAMP,

SIZE AS REQUIRED

INTEGRAL GALVANIZED

LIPPED STEEL MOUNTING

CHANNEL, ATTACH TO

STRUCTURE BELOW

DECK

GENERAL NOTES:

1. MAINTAIN A MINIMUM CLEARANCE OF 12 INCHES ON ALL SIDES OF ROOF PENETRATION FROM WALLS,

CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.

2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.

3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.

4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE PROPER METHODS

& MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.

ENGINE EXHAUST PIPE SIZE

AS RECOMMENDED BY

MANUFACTURER

MUFFLER, SIZE AS

RECOMMENDED BY

MANUFACTURER,

PROVIDE VIBRATION ISOLATORS

12" LONG DRIP LEG WITH DRAIN VALVE

EXHAUST PIPE, SIZE AS RECOMMENDED BY

MANUFACTURER.

THIMBLE OUTER SLEEVE

CLEARANCE AS REQUIRED BY THIMBLE

MANUFACTURER

FLASHING & ROOF OPENING BY GENERAL

CONTRACTOR

THIMBLE INNER SLEEVE

RAIN SHIELD

RAIN CAP

CONDUIT OPENING,

VERIFY SIZE AND

LOCATION WITH

TRANSFORMER

MANUFACTURER

PRIMARY SERVICE

CONDUITS

TO TRANSFORMER

NEUTRAL, #4/0.

SECONDARY

SERVICE CONDUITS

#4 REBAR WITH TIES

12 INCHES ON CENTER

EACH WAY

TRANSFORMER PAD,

VERIFY SIZE WITH

MANUFACTURER. PAD

SHALL EXTEND A MINIMUM

OF 8 INCHES BEYOND

TRANSFORMER

CONCRETE, SEE

SECTION 03 30 00.

FINISHED

GRADE

COMPACTED

GRAVEL BASE

SECONDARY

CONDUIT

PRIMARY

CONDUIT

GROUND

ROD

GROUND

ROD

HOT AIR

EXHAUST PIPING, ROOF THIMBLE AND

INSTALLATION PROVIDED BY DIVISION 26

INSTALL MUFFLER AND

FLEXIBLE CONNECTION.

INSULATE MUFFLER

INTEGRAL

RADIATOR

THERMOSTATIC AIR

RECIRCULATING

DAMPER PROVIDED BY

DIVISION 23

FLEXIBLE DUCT CONNECTOR

AND DUCTWORK PROVIDED BY

DIVISION 23

PROVIDE

VIBRATION

ISOLATORSPROVIDE FLEXIBLE FUEL

LINES FOR INSTALLATION

BY DIVISION 23

BLOCK

HEATER

EXTEND EXISTING

CONCRETE PAD

NOTE:

1.

CONDUIT

FLOOR

FIRESTOP MATERIAL

FLOOR OR DECK PENETRATION

PARTITION OR CHASE PENETRATION

[150mm] [150mm]

MASONRYPARTITION

PARTITION SUPPORT

FIRESTOP MATERIAL

[150mm] [150mm]

DRYWALL PARTITION

6" 6"

6" 6"

FLOOR PENETRATION

CONDUIT

[15

0m

m]

[15

0m

m]

6"

6"

CONDUIT PENETRATION OF SMOKE/FIRE BARRIERSNO SCALE

5E13

3/4" APPROVED

FIRESTOP INSULATION

WITH VAPOR BARRIER

APPLICABLE TO PENETRATIONS OF ALL FIRE

RATED MEMBRANES, IN ACCORDANCE WITH

NFPA 101. REFER TO SPECIFICATIONS SECTION

07 84 00, FIRE STOPPING SYSTEMS.

3/4" [19mm] APPROVED

FIRESTOP INSULATION WITH

VAPOR BARRIER

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:3

3 P

M

E13437-14-112

REPLACE BOILER PLANT 10.26.18ELECTRICAL DETAILS

100% CONSTRUCTION DOCUMENT

6815-193 E13.DWG

AS NOTED

Page 14: ELECTRICAL SYMBOLS AND ABBREVIATIONS REPLACE …...double pole 48" 3 3 - way 48" 4 4 - way 48" lv low voltage 48" m dimmer switch 48" d ... 12'aff ip cctv camera symbol description

GENERAL NOTES:

NO. 29 X 29 X 17 GAUGECOPPER CONDUCTOR

NO. 231 GROUND ROD CLAMPFOR 5/8 INCH ROD

NO. TL5810 5/8 INCH X 10 FOOTCOPPER CLAD GROUND ROD

NO. 55 1/2 INCH x 12 INCHSOLID COPPER POINT

NO. 29 X 29 X 17 GAUGECOPPER CONDUCTOR

NO. 685 CONCEALED BASE ASSEMBLY

NO. 166 LOOP CABLE HOLDERAT 3'-0" ON CENTER

LIGHTING PROTECTION GROUNDING DETAILNO SCALE

4E14

LIGHTING PROTECTION CONNECTION DETAILNO SCALE

5E14

8" RADIUS

NPL CAT. #10A ALUMINUMLIGHTNING PROTECTIONCONDUCTOR

NLP CAT. #1007AEALUMINUMPARALLEL CABLESPLICER

NPL CAT. #1308A ADHESIVE ALUMINUMCABLE HOLDER (FASTEN CABLE EVERY 36"WITH PROPER COMPATIBLE ADHESIVE,SEE GENERAL NOTE 21)

NLP CAT. #202A 1/2"X12" SOLIDALUMINUM AIR TERMINAL

NLP CAT. #804AE ALUMINUM FLATMOUNT AIR TERMINAL BASE (FASTENWITH NLP CAT. #TEKSS3 3/4" LONGSTAINLESS STEEL SELF TAPPING SCREWS)

NLP CAT. #1308A ADHESIVEALUMINUM CABLE HOLDER (FASTENCABLE EVERY 36" WITH PROPERCOMPATIBLE ADHESIVE, SEE GENERAL NOTE 21)

NLP CAT. #1007AEALUMINUM PARALLEL CABLESPLICER

NLP CAT. #10A ALUMINUMLIGHTNING PROTECTIONCONDUCTOR

NLP CAT. #1019AE ALUMINUM 3SQUARE INCH BONDING PLATE(FASTEN WITH NLP CAT. #TEKSS33/4" LONG STAINLESS STEEL SELFTAPPING SCREWS)

NLP CAT. #202A 1/2"X12" SOLIDALUMINUM AIR TERMINAL

NLP CAT. #801AE ALUMINUM SIDE MOUNT AIRTERMINAL BASE (FASTEN WITH NLP CAT.#TEKSS3 3/4" LONG STAINLESS STEEL SELFTAPPING SCREWS

NLP CAT. #10A ALUMINUM LIGHTNINGPROTECTION CONDUCTOR

NLP CAT. #1302A ALUMINUM CABLE LOOP(FASTEN CABLE EVERY 36 INCHES USINGNLP CAT. #TEKSS3 3/4" LONG STAINLESSSTEEL SELF TAPPING SCREWS)

EQUIPMENT AIR TERMINAL DETAILNO SCALE

2E14

PARAPET AIR TERMINAL DETAILNO SCALE

6E14

CABLE SPLICE DETAILNO SCALE

8E14DOWNLEAD TO GROUND DETAIL

NO SCALE

7E14

TYPICAL BONDING DETAILNO SCALE

3E14

NLP CAT. #27 COPPER LIGHTNINGPROTECTION CONDUCTOR TO GROUND ROD

1" SCH 40 PVC CONDUIT(SEE GENERAL NOTE 19)

SEE GENERAL NOTE 20

NLP CAT. #1150BE BIMETALLIC CABLECONNECTOR CAP FOR 1" SCH 40 PVC CONDUIT

NLP CAT. #10A ALUMINUM LIGHTNINGPROTECTION CONDUCTOR

10" MIN.

90°2'-0"

MAX.

24"

1. THE FINAL INSTALLATION SHALL MEET THE UL96A

REQUIREMENTS FOR LIGHTNING PROTECTION

SYSTEMS.

2. IT IS THE INSTALLING CONTRACTOR'S

RESPONSIBILITY TO PROVIDE A FULLY COMPLIANT

SYSTEM.

3. FIELD VERIFY PROTECTION REQUIREMENTS AND

COMMUNICATE ANY DISCREPANCIES AND/OR

DEFICIENCIES WITH THE SYSTEM DESIGNER PRIOR

TO INSTALLATION.

4. ACTUAL JOB SITE CONDITIONS MAY NECESSITATE

SLIGHT ALTERNATIONS OF AIR TERMINAL AND

GROUND LOCATIONS. ANY ALTERATIONS SHALL BE

APPROVED BY THE SYSTEM DESIGNER PRIOR TO

THEIR EXECUTION AND SHALL BE AT NO

ADDITIONAL COST TO THE GOVERNMENT.

5. AIR TERMINALS SHALL BE PLACED AROUND THE

ROOF PERIMETER OR RIDGE AT 20'-0" MAXIMUM

INTERVALS FOR 10" TO 23" AIR TERMINALS AND

AT 25'-0" MAXIMUM INTERVALS FOR 24" AIR

TERMINALS.

6. AIR TERMINALS SHALL BE PLACED WITHIN 24"

FROM THE OUTSIDE EDGES OF THE OBJECT TO BE

PROTECTED.

7. MID-ROOF AIR TERMINALS ON FLAT OR GENTLY

SLOPING ROOFS SHALL BE INSTALLED AT MAXIMUM

50'-0" INTERVALS.

8. ALL ROOF PROJECTIONS AND/OR OBJECTS THAT

ARE SUBJECT TO A DIRECT LIGHTNING STRIKE

SHALL BE PROVIDED WITH AIR TERMINALS UNLESS

THEY ARE LOCATED WITHIN A ZONE OF

PROTECTION.

9. FIELD VERIFY ALL ZONES OF PROTECTION.

10. METAL BODIES SITUATED WITHIN 6'-0" OF A

LIGHTNING PROTECTION CONDUCTOR SHALL BE

BONDED TO THE LIGHTNING PROTECTION SYSTEM.

11. NO BEND OF CONDUCTOR SHALL FORM A FINAL

INCLUDED ANGLE OF LESS THAN 90 DEGREES NOR

SHALL HAVE A RADIUS OF BEND LESS THAN 8".

CONDUIT SHALL ROUTE THE LIGHTNING

PROTECTION CONDUCTOR IN A MANNER CONSISTENT

WITH THESE BEND REQUIREMENTS.

12. CONDUCTORS SHALL INTERCONNECT ALL AIR

TERMINALS TO FORM A TWO WAY HORIZONTAL OR

DOWNWARD PATH TO THE GROUND SYSTEM.

13. ALL LIGHTNING PROTECTION CONDUCTORS SHALL

BE FASTENED AT MAXIMUM INTERVALS OF 3'-0"

ON CENTER.

14. CONNECTIONS TO GROUND RODS OR GROUND LOOP

CABLE SHALL BE MADE AT A POINT NOT LESS

THAN 12" BELOW GRADE AND 24" AWAY FROM

FOUNDATION WALL.

15. ALL POTENTIAL GROUND SOURCES THAT ENTER A

STRUCTURE FROM BELOW GRADE (EARTH) MUST BE

INTERCONNECTED TO THE LIGHTNING PROTECTION

SYSTEM.

16. ALL ADHESIVE TYPE FITTINGS SHALL BE SET IN

PLACE WITH COMPATIBLE ROOF CEMENT.

17. BARE COPPER LIGHTNING PROTECTION MATERIAL

SHALL NOT BE INSTALLED ON ALUMINUM AND

ALUMINUM LIGHTNING PROTECTION MATERIALS

SHALL NOT BE INSTALLED ON COPPER.

18. ALL INCOMING ELECTRICAL, TELEPHONE, DATA,

RADIO, AND TELEVISION SERVICES SHALL BE

EQUIPPED WITH SURGE SUPPRESSION DEVICE.

UNLESS SPECIFIED OTHERWISE THE REQUIRED

SURGE SUPPRESSION DEVICES SHALL BE

FURNISHED AND INSTALLED BY THE ELECTRICAL

CONTRACTOR.

19. ALL REQUIRED 1" SCHEDULE 40 PVC CONDUIT

SHALL FURNISHED AND INSTALLED BY THE

ELECTRICAL CONTRACTOR AT LOCATIONS

DESIGNATED BY THE DESIGNER. CONDUIT SHALL

MAINTAIN A CONTINUOUS AND DIRECT ROUTE TO

GROUND WITH NO MORE THAN 360 DEGREES OF

CUMULATIVE BEND IN ANY SINGLE RUN.

20. ALL REQUIRED SEALING AND/OR FLASHING OR

ROOF PENETRATION SHALL BE FURNISHED AND

INSTALLED BY THE CONTRACTOR.

21. ANY ROOF PADS, PAVERS, SLIP SHEETS, BATTEN

STRIPS, OR SPECIAL REQUIREMENTS OF THE ROOF

SYSTEMS MANUFACTURER FOR ROOF MOUNTED

LIGHTNING PROTECTION EQUIPMENT SHALL BE

FURNISHED AND INSTALLED BY THE CONTRACTOR.

22. THE LAYOUT SHOWN ON THIS DRAWING IS

DIAGRAMMATIC, CONTRACTOR TO FIELD

COORDINATE ALL ROOF PENETRATIONS AND EXACT

MOUNTING LOCATIONS OF ALL AIR TERMINALS.

23. CONTRACTOR TO PROVIDE SHOP DRAWINGS ON THIS

SYSTEM SHOWING MOUNTING DETAILS, AIR

TERMINAL LAYOUTS, ETC.

VENT

EXHAUST FAN

EXHAUST FANEXHAUST FAN

BOILER STACK BOILER STACK BOILER STACK

ROOF HATCH

EXHAUST FAN

ACCU UNIT

TYPICAL PARAPET MOUNTED AIR TERMINAL

CONCEAL DOWN

PROVIDE AIR TERMINAL AND BOND TO EACH

GENSETEXHAUST

EACH METALLIC ROOF PENETRATION

INTAKE HOOD

EXHAUST FAN

TYPICAL PARAPET MOUNTED AIR TERMINALMUFFLER VENT

RELIEF VENT

RELIEF VENT

VENT

INTAKE LOUVER

INTAKE LOUVER

GROUND ROD

STEAM VENT

PLUMBING VENT

BOILER VENTS BOILER VENTS BOILER VENTS

VENT

SCUPPERSCUPPER

SCUPPERSCUPPER

SCUPPER

SCUPPER

GAS VENTS

PLUMBING VENT

INTERIOR WALLSEE 7/E14

CONCEAL DOWNINTERIOR WALLSEE 7/E14

GROUND ROD

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

Vete

rans A

ffairs

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

Depart

ment of

Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218CH MB CHVA263

Project Phase

www.jlgarchitects.com

copyright © 2017

Fargo214 Broadway

Fargo, ND 58102

phone 7 0 1.3 6 4.0 2 3 7

facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

10/2

9/2

018 1

:38:3

3 P

M

E14437-14-112

REPLACE BOILER PLANT 10.26.18LIGHTNING DETAIL SHEET

100% CONSTRUCTION DOCUMENT

6915-193 E14.DWG

N 1/8" = 1'-0"1LIGHTING PROTECTION PLAN

AS NOTED