Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop...

53
Electrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003

Transcript of Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop...

Page 1: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

Electrical Maintenance Workshop

Transformer Maintenance & Testing

Thursday, November 6, 2003

Page 2: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

2

Transformer Maintenance & TestingPurpose

This presentation provides an overview of the major considerations associated with Transformer Maintenance and Testing.

Barker Edwards will provide the information for Transformer Maintenance & Testing.

Kate Brady will provide the information for Transformer Oil Testing.

Page 3: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

3

Transformer MaintenanceThings to know!

Things you should know about keeping your transformer healthy!

Page 4: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

4

Transformer MaintenanceAgenda

Types of transformersYearly checksTesting of transformersVacuum pressure devicePressure relief deviceSudden pressure relayGasketsPaints

Page 5: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

5

Transformer MaintenanceTypes of transformers

Dry type transformers

Varnished coils

Page 6: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

6

Transformer MaintenanceTypes of transformers

Dry type transformers

Cast coils

Page 7: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

7

Transformer MaintenanceType of transformers

Oil filled transformers

Sealed tank

Page 8: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

8

Transformer MaintenanceType of transformers

Oil filled transformers

Conservator system

Page 9: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

9

Transformer MaintenanceType of transformers

Oil filled transformers

Nitrogen blanket

Pressure regulator for Nitrogen Blanket transformer

Page 10: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

10

Transformer MaintenanceYearly transformer checks

Check vacuum pressure gauge for pressure reading.Check oil level.Check temperature maximum and minimum.Check for leaks.Check paint condition.Check transformer top and radiators for foreign material.Check radiator condition.Check fans and cooling systems.

Page 11: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

11

Transformer MaintenanceTesting of transformers

Megger test

600 megohms or better to ground is a good bench mark.

Page 12: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

12

Transformer MaintenanceTesting of transformers

Power factor test or “Doble” test

Readings should be .5% or less on newer equipment.

Readings should be 1% or less on older equipment that has been in service for a number of years.

Padmount transformers will usually run .7% to 1%.

Page 13: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

13

Transformer MaintenanceTesting of transformers

Infrared test

This equipment checks for hot connections and hot spots.

Can be used to check how the cooling is working on transformers.

Page 14: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

14

Transformer MaintenanceTesting of transformers

TTR test - Transformer Turns Ratio test

3 phase TTR set Single phase TTR set

- Readings should not deviate more than ½ of 1% from the calculated value.

Page 15: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

15

Transformer MaintenanceVacuum pressure devices

Vacuum pressure devices

Used to control the amount of positive and negative pressure a transformer tank has on it.

Page 16: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

16

Transformer MaintenancePressure relief devices

Pressure relief devices

Used to relieve pressure build up in the transformer.

Page 17: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

17

Transformer MaintenanceSudden pressure relay

Sudden pressure relay

This device detects a sudden rise in pressure in the transformer.

Page 18: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

18

Transformer MaintenanceGaskets

Gaskets shall be 1.33 times the height of groove and .75 times the width of the groove.

Types of gasket material:

Cork / CorkpreneNitrile / Buna N RubberViton Rubber

Page 19: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

19

Transformer MaintenancePaint

Types

Acrylic enamelEpoxy base

Page 20: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

20

Break

Page 21: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

21

Transformer Oil TestingAgenda

Transformer oilOil samplingOil qualityDissolved gas analysisCellulose insulationOil processing

Page 22: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

22

Transformer Oil TestingTransformer oil

Silicon based oil

Mineral oil

Synthetic oils

Ester / vegetable oils

Page 23: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

23

Transformer Oil TestingOil sampling

A Test is Only as Good as the Sample!Start with good, clean syringes!

Page 24: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

24

Transformer Oil TestingProper oil sampling

Do Not use small sampling port on side of drain valve.

Page 25: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

25

Transformer Oil TestingProper oil sampling

Flush drain valve, tubing, and syringe.

Page 26: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

26

Transformer Oil TestingProper oil sampling – (continued)

Do not pull back on the syringe barrel – apply slight resistance and allow fluid pressure to fill syringe.

Page 27: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

27

Transformer Oil TestingProper oil sampling – (continued)

Filled syringe should have no bubbles, but some may form later – do not release these!

Page 28: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

28

Transformer Oil TestingProper oil sampling – (continued)

Excellent Sampling Guidelines available on Doble Engineering website

www.Doble.comClick on “Laboratory Services”Sampling Guides:

Dielectric LiquidsDissolved Gas Analysis ©2002 Doble Engineering Company All Rights Reserved

Page 29: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

29

Transformer Oil TestingOil quality

Interfacial tension

Acidity

Moisture

Dielectric

Power factor

Color

Page 30: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

30

Transformer Oil TestingInterfacial Tension - IFT

Measure of contamination

Decreasing IFT = Increasing Contamination

Can be corrected

Page 31: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

31

Transformer Oil TestingAcidity

Measure of oxidation

Creates acidic compounds

Build-up of compounds forms sludge

Affects dielectric and cooling

Can be corrected

Page 32: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

32

Transformer Oil TestingMoisture

Decreases dielectric

Decreases IFT

Degrades cellulose

Failure risk

Can be corrected

Page 33: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

33

Transformer Oil TestingDielectric breakdown

Voltage at which the oil begins to conduct

Is reduced by moisture and contaminants

Two ASTM test methods:

D-877

D-1816

Can be corrected

Page 34: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

34

Transformer Oil TestingPower factor

Indication of contamination and/or deterioration

moisturecarbonvarnishsoapsother conducting matter

Page 35: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

35

Transformer Oil TestingColor

Higher Number Darker OilDarker Oil More Contamination, DeteriorationOil with Number of 5 is almost black

Page 36: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

36

Transformer Oil TestingDissolved gas analysis

DGA is the “blood test” for a transformer

Page 37: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

37

Transformer Oil TestingDissolved gas analysis

Partial discharge (Corona - “electrical rust”)Hydrogen H2

High temperature heatingMethane CH4, Ethane C2H4, Ethylene C2H6

ArcingAcetylene C2H2

Cellulose involvedCarbon monoxide C0, and Carbon Dioxide CO2

Page 38: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

38

Transformer Oil TestingCellulose insulation

The Life of the Transformer is directly related to the condition of the cellulose

Paper – windings, leads, shields

Pressboard – spacers, blocks, oil flows, tubes

Particle boards – supports

Laminates – structures, supports

Wood - structure

Page 39: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

39

Transformer Oil TestingPaper

Many layers of paper on this flux shield

Page 40: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

40

Transformer Oil TestingPressboard

Pressboard Sheets for directing oil flow

Page 41: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

41

Transformer Oil TestingPaper and pressboard

Paper wrapped windings

Pressboard spacers

Page 42: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

42

Transformer Oil TestingParticle board

Particle Board Lead Support that flashed over

Page 43: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

43

Transformer Oil TestingLaminates

Laminate Nuts

Laminate lead support structure members

Page 44: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

44

Transformer Oil TestingWood

Birch Structure Support Members

Page 45: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

45

Transformer Oil TestingThe Cellulose Polymer Chain

The life of a transformer is directly related to the condition of this polymer chain.

Page 46: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

46

Transformer Oil TestingDegree of polymerization

Measure of mechanical strength

New paper = 1000 – 1400

Age increases DP decreases

Industry accepted “End of Life” of cellulose

insulation is about 200

Estimated DP from Furan test

Page 47: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

47

Transformer Oil TestingWhat degrades the cellulose?

Primary sources

HeatMoistureOxygen

Secondary sources

Acids from oil oxidation

Page 48: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

48

Transformer Oil TestingWhy is this important?

Reduced dielectric strength

Unable to withstand voltage stress from system transients

Reduced mechanical strength

Unable to withstand mechanical stress from system faults

Page 49: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

49

Transformer Oil TestingWhat can we do about it?

Keep the Transformer Healthy!Do not overheatKeep moisture and oxygen out

If the Transformer is Sick, Get Help!Investigate abnormal DGA resultsProcess or replace the oilDe-hydrateHot oil flush

Page 50: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

50

Transformer Oil TestingTransformer oil processing

Page 51: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

51

Transformer Oil TestingWhat processes?

De-gas

Dehydrate

Hot oil flush

Reclaim oil

Page 52: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

52

Transformer Oil TestingOther maintenance options

Upgrades to oil preservation systemBladdersDe-hydrating breathersN2 blanket

On-line monitoring systemsGas and moistureBushing monitors

Page 53: Electrical Maintenance Workshop - Progress Energy · PDF fileElectrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003. 2 Transformer Maintenance

53

Avoid Premature Failure!