Electrical Failures Not related To Weather · • 1.he failure of the reactor was caused by...
Transcript of Electrical Failures Not related To Weather · • 1.he failure of the reactor was caused by...
Electrical FailuresNot related To Weather
IMIA 51st Conference
1st – 5th September 2018
Singapore
Working Group
Name Company ExperienceMamoon Alyah (Chair) CEERISK Consulting Forensic EngineeringOliver Thoma Advanta Global Loss AdjustingJeff Ashman Advanta Global Loss AdjustingBrendan Reed Codan UnderwritingTom Kristiansen Codan UnderwritingMilind Bhatawadekar Bhatawadekar Loss Surveys Loss AdjustingMichael Shehan Qatar General Claims Mike Robertson Liberty Specialty UnderwritingPaul Lowrie Clyde & Co SolicitorSimon Dejung Scor Global UnderwritingBen Adams Charles Taylor Risk Engineering
What is an electrical failure?
• Collins dictionary: “Electrical failure is an instance when an electricity supply stops working”
• IEC: “failure: the termination of the ability of an item to perform a required function”
Why should insurers car?
• Defining electrical failure as loss of power provides the general perspective of utilities and IPP’s that view reliability of the power system in terms of availability of supply, rather than specific incidents that are caused to or can lead to physical damage to property. • For instance, operator error that
results in interruption of power supply, through it does not involve any physical damage, is considered an electrical failure.
• This broad definition may prove to be irrelevant to insurers who are mainly concerned about events that involve physical damage to property.
Electrical failure v.
Electrical fault
• Electrical System fault as:“a condition in the electrical system that causes failure of the electrical equipment in the circuit such as: Generators, Transformers, Busbars, Cables and all other equipment in the system that operate at given voltage level”
• OEM’s define faults as:A fault in electrical equipment or apparatus is as an imperfection in the electrical circuit due to which current is deflected from the intended path. In other words, the fault is the abnormal condition of the electrical system which damages the electrical equipment and disturbs the normal flow of the electric current.
How should insurers define
“Electrical Failure”?
• When considering the definition from an insurance perspective, we relied on definition of two elements: “accident” and “object” when considering electrical failures/faults• “Accident”: means an unforeseen
breakdown of an “object” resulting in physical damage to the object, that requires that the “object” be either repaired or replaced before normal operations can be resumed. It is becoming more common for policies to no longer require the accident to be SUDDEN, as long as it is fortuitous and unforeseen
• “Electrical Objects”: Electrical equipment or apparatus used for the generation, transmission, Distribution or utilization of electrical power.
Our definition of Electrical
Failures (or is it faults?)
• We limit the scope of our paper to electrical faults and not electrical failures.
• We define electrical faults, as:any unforeseen abnormal condition (imperfection) in the electrical circuit which causes deflection of current flow from intended path that leads to physical damage to equipment.
Our Scope
• The scope of this paper is limited to:• Unforeseen abnormal conditions• Causes electric current to flow outside its
intended path, which can be caused by a breach of containment system (insulation breakdown) used to manage the flow of electrical current
• As a result, the fault causes physical damage to equipment which necessitates repair or replacement before it can be returned to normal operations
• Electrical faults are caused by • equipment failures (transformers, rotating
machines, cables, bus bars, switchgear assemblies …etc),
• human errors (manufacturing, commissioning and testing, operation …etc.) and
Examples of Electrical Faults
Electrical Failures in Transformers
Electrical Failures in Switchgear
Electrical Failures in Transformers
Electrical Failures in Substations
Devastating impact of a fault
www.ceerisk.com
Paper Structure
• Electrical System Components
• Types of electrical faults
• Common failure modes, causes and impact
• Insurance consideration• Risk assessment
• Loss prevention• Inspection and
condition monitoring• Maintenance and
inspection programmes• Underwriting• Claims
• Investigation of cause• Application of
exclusions and warranties
• Loss examples• EHV Bushing failure• Transformer fire• Switchgear fault• Fault in MCC• Cable Fault
Paper Focus
Accident Object
Electric Fault in MCC Cabinets
www.ceerisk.com
Loss Circumstances
• The loss occurred in the electric room in the concrete plant and involved a MCC (Motor Control Centre) used to operate several pieces of equipment in the plant.
• Fire broke out in the electric room
• PD was limited to contents of the electric room $230,000
• BI resulting from shut down as a result of the loss was in the $millions
www.ceerisk.com
Cause of Loss
• Electric fault occurred at the back of one of the switches (buckets) in the MCC
• The fault led to significant heat damage to the metal enclosure and everything around it
• A fire ensued when wire insulation was burned
www.ceerisk.com
Electric switches
• Each switch plugged into the busbar inside the cabinet
www.ceerisk.com
Connection Clasps
• Each control bucket was plugged into the cabinet where the busbars locked into location using pressure clasps
www.ceerisk.com
Busbars
Bus bars ran up and down the cabinet and switches plugged into them
www.ceerisk.com
Cause
• After sometime, the mechanical clasps start losing tension
• This creates a high resistance contact
• Heat starts building up around the contact point
• Heat causes oxidation of the contact surface which generates further heat
• Eventually, insulating barriers breakdown and an electrical fault occurs
www.ceerisk.com
Transformer Failure
• It was claimed that two power transformers located in the basement of a building, were damaged due to 10 week dormancy imposed during power outage related to a covered flooding loss
• There was no flooding from the loss to the basement where the transformers were located. • The humidity levels were reported to
be high due to weather conditions. • Weather condition changed to colder
temperatures over the period when the transformer was de-energized.
www.ceerisk.com
Background information of the transformers
• The two transformers were approximately 25 years old.
• Both transformers were periodically maintained.
• The transformers were tested and cleaned approximately four (4) years prior to the loss.
• The windings were inspected
www.ceerisk.com
Windings
www.ceerisk.com
Insulation Breakdown
www.ceerisk.com
Cause
• Damaged as a result of electrical fault consistent with insulation breakdown.
• Insulation breakdown was caused by condensation and moisture penetration due to prolonged shut down and improper re-energizing procedure.
www.ceerisk.com
Reactor
• ABB 90 kV 3-ph reactor, failed.• The reactor was in service at the time
and had been installed as a replacement for another reactor, which experienced similar failure at an earlier date.
• Both failures occurred during a thunderstorm
• It was claimed that lightning is the cause
www.ceerisk.com
Inspection & Testing
• Testing indicated there was an electrical sort in one of the three windings
• Inspection of leads and connection showed them to be free of any damage
www.ceerisk.com
Windings
• Excessive discolouration on the windings• Discolouration was wide spread
throughout the reactor
• Small particles from the electric short were found in other windings suggesting particles floated in the oil
www.ceerisk.com
Electric Fault
• Electric short occurred internally between windings
• Energy from the fault caused parts of the winding to disintegrate
• Beads floated in eth oil
www.ceerisk.com
Cause
• 1. The failure of the reactor was caused by electrical short between inner windings on phase A.
• 2. The electric short was caused by failure of the winding insulation. The root cause of the failure is consistent with normal wear and tear conditions.
• 3. The reactor exhibits signs of age related deterioration of the insulation on all different parts of the windings.
• 4. No signs of external causes of failure were observed on any of the winding leads or connections.
• 5. Review of inspection and cause analysis reports issued by the manufacturer and independent engineering investigator indicate that the failure in Reactor#1 was also due to age related deterioration and no signs of external causes were identified.
Case Study 500MW H2/Water cooled Generator.
Station Commissioned in Late 60sPlant Life Extension program mid-2000s• FGD• Steam Turbine Retrofit• Generator Stator Replacement• Generator rotor rewinds.
Case Study 500MW H2/Water cooled Generator.
18th May 2009 17:22 – Stator Water Pumps stopped.18:00 – Unit Tripped on Stator
Earth Fault• Stator Scrapped• Rotor required a full forging re-validation and rewind• 4 month outage.
Burn Damage to Generator Casing
Damaged Windings
Fault on NDE Slot Exit
Fault at DE End windings
Stator water Pump
ChangeoverStator heating
Alarm
GCMx
Stator Water Pump Stops
Dead
GeneratorStator Water
Flow Fail Protection
GCM activity vs Average Slot Temperature
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
17:16:48 17:24:00 17:31:12 17:38:24 17:45:36 17:52:48 18:00:00 18:07:12 18:14:24 18:21:36
Time
GC
M o
utpu
t %ag
e
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
90.0
100.0
110.0
120.0
130.0
140.0
150.0
160.0
Stat
or B
ar T
emp
Stator Earth Fault 18:00Stator water pump off (17:22)- Flow Failure Alarm
38minutes
GCM Verified
14
Stator Temp High Alarm (17:30)
30minutes
Between Top and Btm
Learning Points
• Protection Testing (ideally directly from plant)
• Flow switches – Replace old technology (pressure switches across an orifice)
• Control room alarm rate• Saunders Valve (correct grades and
lifetimes)• Remove the risk (Engineer out the risk
of water systems)
www.ceerisk.com
High Voltage Transformer Explosion
www.ceerisk.com
The Loss
• Transmission substation in California, USA
• 374 MVA Single Phase Transformer
• Explosion occurs at 18:30 on July 7, 2003
Damage to the Transformer
Damage to The Substation
www.ceerisk.com
HV Bushing
• Traces of PD and HV fault
Tear Down
Internal Inspection of the Tank
LV Leads Intact
Coil Disassembly
Observations: Static Discharge
Observation: Arc Tracking
Analysis
Signs of electrostatic discharge
Signs of arc tracking
Signs of gradual damage to insulation
Conclusion
Electrostatic Discharge caused by circulation of the oil during cool temperatures
Static electricity starts arcing in the oil with HV leads and conductors
Arc tracking causes stress to the insulation around the HV lead
Conclusions
Process goes undetected for sometime
The HV lead insulation fails and causes massive electric fault
Electric fault causes explosion of the oil, which in turn pushes the bushing and start the fire
Root Cause Cool Temperature
01Oil Circulation
02Electrostatic Discharge
03
Renewable Energy
The Equipment
www.ceerisk.com
Inside the Container
• Two rooms:• Power room: used to
house the power modules and high frequency filters
• Control room: used to house the PLC control cabinets as well as the air conditioning controls.
The Loss
• Two weeks after commissioning, a fire broke out in a container that houses control equipment and power filters designed to supply VARS to the grid
Burn patterns
Point of origin
Electric Fault
Analysis
There were no signs of burning outside of the container
Extensive burn damage in the power control room
The burn patterns in the power room of the container show heavier burning on the side of the room closest to the control section.
Closer examination of the cable connections indicated that there was significant electrical arcing in that area which resulted in significant damage to the cable connections, the brackets and the container walls.
www.ceerisk.com
Root Cause
• Cause of the fire incident is an improper cable connection causing a high resistance contact at the cable connection plate behind the charging transformer located in the corner of the power room
www.ceerisk.com
Lessons Learned
• Electric failures typically have devastating results
• Damage is rarely contained and limited to the part that fails
• Financial consequences can be severe:• Physical damage – PD• Business Interruption – BI• ICOW (Increased Cost of Working)• Liability • Punitive Damages
• Good (thorough and comprehensive) analysis is imperative to assess the risk
• Loss Prevention requires:• Early detection • Quick release and shut down of
electrical equipment, • Fast extinguishing of a short circuit/fire
• Claims handling should cover:• RCA: Root Cause Analysis• Subrogation/Recovery
Is electricity dangerous?