Electrical-Engineering-portal.com-Identifying the Primary and Secondary Phasor Polarities of...

2
electrical-engineering-portal.com http://electrical-engineering-portal.com/identifying-the-primary-and-secondary-phasor-polarities-of-transformer-polarity-test? utm_source=Technical+Articles&utm_campaign=3efb6ea18e- RSS_EMAIL_CAMPAIGN&utm_medium=email&utm_term=0_ae069f0d91-3efb6ea18e-315493569 CPC 100 - Universal testing device for electrical diagnostics on transformers, current transformers, voltage transformers, grounding systems, lines and cables, and circuit breakers (photo by www.omicron.at) Edvard Identifying The Primary And Secondary Phasor Polarities Of Transformer – Polarity Test Polarity Detection This is needed f or identif ying the primary and secondary phasor polarities . It is a must f or poly phase connections. Both a.c. and d.c methods can be used f or detecting the polarities of the induced emfs. The dot method is used to indicate the polarities. The transf ormer is connected to a low voltage a.c. source with the connections made as shown in the Figure 1 (a). A supply voltage Vs is applied to the primary and the readings of the voltmeters V 1 , V 2 and V 3 are noted. V 1 : V 2 gives the turns ratio. If V 3 reads V 1 −V 2 then assumed dot locations are correct (for the connection shown).

Transcript of Electrical-Engineering-portal.com-Identifying the Primary and Secondary Phasor Polarities of...

Page 1: Electrical-Engineering-portal.com-Identifying the Primary and Secondary Phasor Polarities of Transformer Polarity Test

elect rical-engineering-po rt al.co mhttp://electrical-engineering-portal.com/identifying-the-primary-and-secondary-phasor-po larities-o f-transformer-po larity-test?utm_source=Technical+Articles&utm_campaign=3efb6ea18e-RSS_EMAIL_CAMPAIGN&utm_medium=email&utm_term=0_ae069f0d91-3efb6ea18e-315493569

CPC 100 - Unive rsal te sting d e vice fo r e le ctrical d iag no stics o n transfo rme rs, curre nt transfo rme rs, vo ltag e transfo rme rs,g ro und ing syste ms, l ine s and cab le s, and c ircuit b re ake rs (p ho to b y www.o micro n.at)

Edvard

Identifying The Primary And Secondary Phasor Polarities OfTransformer – Polarity Test

Polarity Detection

This is needed f or identif ying the primary and secondary phasor polarit ies. It is a must f or poly phaseconnections. Both a.c. and d.c methods can be used f or detecting the polarit ies of the induced emfs.

The dot method is used to indicate the polarit ies.

The transf ormer is connected to a low voltage a.c. source with the connections made as shown in the Figure 1(a). A supply voltage Vs is applied to the primary and the readings of the voltmeters V1, V2 and V3 are noted.V1 : V2 gives the turns ratio.

If V3 reads V1−V2 then assumed dot locations are correct (for the connection shown).

Page 2: Electrical-Engineering-portal.com-Identifying the Primary and Secondary Phasor Polarities of Transformer Polarity Test

Fig ure 1 - Transfo rme r p o larity te st sche me

The

beginning and end of the primary and secondary may then be marked by A1 − A2 and a1 − a2 respectively. If thevoltage rises f rom A1 to A2 in the primary, at any instant it does so f rom a1 to a2 in the secondary.

If more secondary terminals are present due to taps taken f rom the windings they can be labeled as a3, a4, a5,a6. It is the voltage rising f rom smaller number towards larger ones in each winding. The same thing holds goodif more secondaries are present.

Figure 1 (b) shows the d.c. method of testing the polarity. When the switch S is closed if the secondaryvoltage shows a posit ive reading, with a moving coil meter, the assumed polarity is correct. If the meter kicksback the assumed polarity is wrong.

Reference: Electrical Machines I – Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao