electrical-engineering-portal.com Gas insulated switchgear (GIS) - Siemens http://electrical-engineering-portal.com/bus-design-in-aboveground- substations? utm_source=Technical+Articles&utm_campaign=a4dc4ac458-RSS_EMAIL_CAMPAIGN&utm_medium=email Bus Design In Aboveground Substations Substations can be constructed partly or entirely within aboveground or belowground enclosures. However, cost is high and complexity is increased by fire-protection and heat-removal needs. The following discussion deals with exposed aboveground substations. Air insulated substations (AIS) The bus and associated substation equipment are exposed and directly visible. An outdoor bus may be multitiered or spread out at one level. Metal or wood structures and insulators support such bus and power line terminations. Space permitting, a low-profile bus layout is generally best for aesthetics and is the easiest to conceal with landscaping, walls, and enclosures. Overhead transmission line terminating structures are taller and more difficult to conceal in such a

Transcript of electrical-engineering-portal.com-Bus_Design_In_Aboveground_Substations.pdf

Page 1: electrical-engineering-portal.com-Bus_Design_In_Aboveground_Substations.pdf

electrical-engineering-portal.com

Gas insulated switchgear (GIS) - Siemens

http://electrical-engineering-portal.com/bus-design-in-aboveground-substations?

utm_source=Technical+Articles&utm_campaign=a4dc4ac458-RSS_EMAIL_CAMPAIGN&utm_medium=email

Bus Design In Aboveground Substations

Substations can be constructed partly or entirely within aboveground or belowground enclosures.

However, cost is high and complexity is increased by fire-protection and heat-removal needs. Thefollowing discussion deals with exposed aboveground substations.

Air insulated substations (AIS)The bus and associated substation equipment are exposed and directly visible. An outdoor bus maybe multitiered or spread out at one level. Metal or wood structures and insulators support such bus andpower line terminations.

Space permitting, a low-profile bus layout is generally best for aesthetics and is the easiest to concealwith landscaping, walls, and enclosures.

Overhead transmission line terminating structures are taller and more difficult to conceal in such a

Page 2: electrical-engineering-portal.com-Bus_Design_In_Aboveground_Substations.pdf

layout.

In dry climates, a low-profile bus can be achieved by excavating the earth area, within which outdoorbus facilities are then located for an even lower profile.

SwitchgearMetal-enclosed or metal-clad switchgear designs that house the bus and associated equipment in ametal enclosure are an alternative design for distribution voltages. These designs provide a compactlow-profile installation that may be aesthetically acceptable.

Gas insulated substation (GIS)Bus and associated equipment can be housed within pipe-type enclosures using sulfur hexafluoride oranother similar gas for insulation. Not only can this achieve considerable compactness and reducedsite preparation for higher voltages, but it can also be installed lower to the ground.

A GIS can be an economically attractive design where space is at a premium, especially if a building-type enclosure will be used to house substation equipment (see IEEE Std. C37.123-1996).

Cable busShort sections of overhead or underground cables can be used at substations, although this use isnormally limited to distribution voltages (e.g., for feeder getaways or transformer-to-switchgearconnections).

At higher voltages, underground cable can be used for line-entries or to resolve a specific connectionproblem.

NoiseAudible noise, particularly continuously radiated discrete tones (e.g., from power transformers), is thetype of noise that the community may find unacceptable.

Community guidelines to ensure that acceptable noise levels are maintained can take the form ofgovernmental regulations or individual = community reaction (permit denial, threat of complaint to utilityregulators, etc.).

Where noise is a potential concern, field measurements of the area background noise levels andcomputer simulations predicting the impact of the substation may be required. The cost ofimplementing noise reduction solutions (low-noise equipment, barriers or walls, noise cancellationtechniques, etc.) may become a significant factor when a site is selected.

Page 3: electrical-engineering-portal.com-Bus_Design_In_Aboveground_Substations.pdf

Noise can be transmitted as a pressure wave either through the air or through solids. The majority ofcases involving the observation and measurement of noise have dealt with noise being propagatedthrough the air. However, there are reported, rare cases of audible transformer noise appearing atdistant observation points by propagating through the transformer foundation and underground solidrock formations.

It is best to avoid the situation by isolating the foundation from bedrock where the conditions arethought to favor transmission of vibrations.

Resource: Electric power substation engineering by J. McDonald