Electrical Basis of Design - OXY
-
Upload
abhijit-mandal -
Category
Documents
-
view
220 -
download
0
Transcript of Electrical Basis of Design - OXY
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 1/88
OCCIDENTAL PETROLEUM
OF QATAR LTD
PARNO.
DISC LOCATION I.D. DOC TYPE SEQUENTIAL No. SHEET No.
DOCUMENTNUMBER
000000-4-XPS1-BD-0001-001
DOCUMENTTYPE ELECTRICAL BASIS OF DESIGN
TITLE OCCIDENTAL MANAGED FACILITIES IN QATAR
00 Issued for General Use
A1 28th May 09 Issued for Review J Pilkington K Rose R Haddad
REV DATE DESCRIPTION WRITTEN BY CHECKED BY APPROVED BY
REVISION SIGNATURES
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 2/88
Occidental Petroleum of Qatar Ltd Page 2 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
CONTENTS
1. INTRODUCTION ........................................................................................................................... 4
1.0.
Scope and Purpose ..................................................................................................................... 5
1.1. Custodian .....................................................................................................................................5
2. ELECTRICAL SYSTEM DESIGN PHILOSOPHY ........................................................................6
2.0. General.......................................................................................................................................... 6
2.1. Protection against Explosion and Fire Hazards .......................................................................8
2.2. Environmental Conditions .......................................................................................................... 9
2.3. Power Supply Arrangements ................................................................................................... 10
2.4.
Protection, Power Management, Controls and Indications................................................... 13
2.5. ESD, DCS and General Control Interfaces .............................................................................. 16
2.6. Electrical Load Schedules and Load Forecasting .................................................................17
2.7. System Voltage, Frequency and Power Factor ......................................................................18
2.8. Voltages and Frequencies for Existing OPQL Installations ..................................................20
2.9. Electrical System Studies and Reviews .................................................................................. 22
2.10. Electrical Detailed Designs ....................................................................................................... 23
3.
EQUIPMENT SPECIFICATION AND SELECTION PHILOSOPHY ...........................................24
3.0. General........................................................................................................................................ 24
3.1. Generators..................................................................................................................................25
3.2. Neutral Earthing Resistors ....................................................................................................... 27
3.3. Switchgear ..................................................................................................................................28
3.4. Busbar Ducting .......................................................................................................................... 30
3.5. Power transformers ................................................................................................................... 30
3.6.
UPS Systems ..............................................................................................................................32
3.7. Electric Motors ...........................................................................................................................33
3.8. Cables, Wires and Supports ..................................................................................................... 34
3.9. Metering, Protection and Control equipment .........................................................................35
3.10. Power Management Systems ................................................................................................... 35
3.11. Packaged Equipment ................................................................................................................ 35
3.12. Variable Speed Drives and ESP’s ............................................................................................ 36
3.13.
HVAC Systems ...........................................................................................................................37
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 3/88
Occidental Petroleum of Qatar Ltd Page 3 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
3.14. Navigational Aids....................................................................................................................... 37
3.15. Cathodic Protection Systems................................................................................................... 39
3.16.
Electric Process Heaters........................................................................................................... 39
3.17. Electric Motor Operated Valve Actuators ................................................................................ 39
3.18. Electrical Heat Tracing .............................................................................................................. 39
3.19. Lighting, Small Power, Bulks and Minor Equipment .............................................................39
3.20. Distribution Boards ................................................................................................................... 40
3.21. Subsea Cables and Umbil icals ................................................................................................. 40
4. EQUIPMENT INSTALLATION DESIGN REQUIREMENTS .......................................................41
4.0.
General........................................................................................................................................ 41
4.1. Cables, Routing Considerations and Accessories ................................................................41
4.2. Lighting and Small Power Installations................................................................................... 45
4.3. Earthing and Bonding ............................................................................................................... 48
4.4. Major and Packaged equipment items .................................................................................... 48
4.5. ESP’s and Variable Speed Drives ............................................................................................ 49
4.6. Switchrooms, Equipment Rooms, Battery and Plant Rooms ...............................................51
4.7.
HVAC Requirements.................................................................................................................. 53
4.8. Temporary installations ............................................................................................................ 55
5. DOCUMENTS AND DRAWINGS................................................................................................ 56
APPENDICES ............................................................................................................................................. 57
APPENDIX A – DEFINITION OF TERMS AND ABBREVIATIONS ..........................................................58
APPENDIX B – APPROVED CODES, STANDARDS AND SPECIFICATIONS ....................................... 62
APPENDIX C – ELECTRICAL BULK MATERIALS AND MINOR EQUIPMENT...................................... 65
APPENDIX D – EARTHING AND BONDING ............................................................................................ 70
APPENDIX E – RECOMMENDED ILLUMINATION LEVELS ...................................................................74
APPENDIX F – EXAMPLE FORMAT – PLANNED MAINTENANCE ROUTINE ...................................... 75
APPENDIX G - FACILITIES KEY RECORDS LIBRARY ..........................................................................78
APPENDIX H – ELECTRICAL CONSTRUCTION AND COMMISSIONING CHECKLISTS ..................... 79
APPENDIX J – IEC 60092-352 CURRENT CAPACITIES AND DEFINED INSTALLATIONS .................83
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 4/88
Occidental Petroleum of Qatar Ltd Page 4 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
1. INTRODUCTION
Occidental Petroleum of Qatar Ltd (OPQL) operates the Idd El Shargi offshore Production Station PS1which is located 85 kilometres east of Doha. The station consists of a number of oil process, gas
process, utilities, water injection and accommodation jackets interconnected by bridges. Supplying the
production station with oil and gas from the North Dome (ISND) and South Dome (ISSD) fields are a
series of remote, unmanned wellhead platforms, interconnected to PS1 facilities by subsea pipelines.
Some (but not all) of these platforms have subsea power umbilicals. Oil and produced water is
transported to Halul Island via pipeline where the water and residual gas is separated from the oil prior to
fiscal metering then exported via oil tanker. The water depth at ISND and ISSD typically ranges between
28m and 33m.
Occidental also operate the Al-Morjan Permanent Production Facility and CALM loading buoy which
produce from the Al Rayyan oil field. This is a marginal field producing sour crude with a very low Gas Oil
ratio and very high water cut. The field is located approximately 84 km north/north east of Qatar
Peninsula in the Arabian Gulf. The water depth is typically 28m.
The location of the facilities are shown below.
DOHA
PS-1
PS-2
PS-3
Halul
Bunduq
Das Island
NAUTICAL MILES
50403020100
RAS LAFFAN
MESAIEED
DUKHAN
26' 00' N
25' 00' N
5 1 ' 0 0 ' E
5 3 ' 0 0 ' E
5 2 ' 0 0 ' E
N
ISND Field
ISSD Field
AL-MORJANField
OPQL MANAGED FACILITIES IN QATAR
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 5/88
Occidental Petroleum of Qatar Ltd Page 5 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
1.0. Scope and Purpo se
This Basis of Design provides the framework for electrical design, engineering and selection of equipment
for Brownfield modifications to existing offshore facilities managed by Occidental Petroleum (Qatar) atISND, ISSD, Al Morjan and the existing onshore produced water handling facilities at Halul Island. This
document shall also be used to determine engineering philosophy and equipment specification/selection
for new offshore and onshore installations.
Installation design requirements differ significantly between onshore and offshore facilities. Where major
new onshore installations are being considered, reference shall be made to section 10 of QP Electrical
Engineering Philosophy ES.2.03.0001. This document details requirements for indoor and outdoor
onshore substations, transmission lines, underground cabling and segregation requirements, etc.
Engineering Contractors working on behalf of OPQL shall exercise due diligence and comply with the
requirements of this Basis of Design. This remains a live document and users should refer to the OPQL
Technical Authority (TA) concerning recent updates and amendments.
A uniform and consistent approach to electrical design and engineering of OPQL managed facilities shall
be adopted, noting that the installations all have different characteristics. Engineering shall be in
accordance with latest international standards and industrial installation practices, whether or not listed
within this Basis of Design. The most suitable electrical equipment shall be selected as fit for its intended
use considering both technical and economical issues. All safety requirements shall be complied with.
OPQL have a Process Risk Management (PRM) programme which identifies project specific reviews
(either discipline specific or multi-discipline as appropriate) for all changes to facilities. These reviews and
all other safety requirements shall be adhered to and incorporated into designs where appropriate.
This document should be read in conjunction with the relevant project “Statement of Requirement” or“Functional Design Specification” where these are available.
1.1. Custodian
The custodian of this document is the Electrical Technical Authority (TA) within OPQL Facilities
Engineering Department. Occidental Documents and Standards section maintain controlled copies of this
document and other Field Technical Information (FTI).
Requests for deviations from the application of technical standards requires authorisation from the OPQL
Technical Authority. Refer to OPQL Technical Authorities Manual, document 000000-8-XPS1-TD-0001-
001 for further details. All deviation requests, comments or recommendations should in the first instance
be directed to the Occidental Document controller.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 6/88
Occidental Petroleum of Qatar Ltd Page 6 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
2. ELECTRICAL SYSTEM DESIGN PHILOSOPHY
2.0. General
Compatibility with existing systems
Due regard shall be taken during engineering design and selection of equipment to ensure compatibility
between new and existing systems. Because of obsolescence issues and changing codes and
standards, it is recognised that full equipment compatibility is not always achievable (or indeed desirable).
Where any doubt exists, please refer to OPQL TA for guidance.
Standards, Codes and Regulations
The design and engineering of the electrical installation shall meet all the Statutory Requirements of the
National and Local Regulations currently in force in the State of Qatar. Legal requirements aredocumented in detail within QP Environmental Management Standard for Legal Requirements STD-ENV-
005. The requirements laid down by Qatar General Organisation for Standards and Metrology (QGOSM)
and *Ministry of Environment shall also be met.
*Formerly Supreme Council for the Environment and Natural Reserves (SCENR).
OPQL have entered into a Development and Production Sharing Agreement (DPSA) with QP to manage
a number of assets on their behalf within Qatar. OPQL are obliged to adopt good industrial practice when
managing these assets but application of QP codes and standards is not mandatory.
Occidental Oil and Gas Corporation (OOGC) have published a number of engineering guides which are
applicable to all subsidiaries operated and controlled by OOGC (this includes OPQL). The general
introductory guide (EG-300) defines these as intended for onshore oil and gas processing facilities only
and makes provision for the use of International, host country or locally mandated regulations where
these meet (or exceed) the OOGC guides. Hence, these guides will not be applied to OPQL (mainly
offshore) managed facilities.
The OPQL managed facilities have to a large extent been engineered based upon British Standards
Institute publications (BSI) and those published by the International Electro technical Commission (IEC).
These publications, together with OPQL and QP codes and standards shall form the basis of OPQL
adoption of good industrial practice.
OPQL and QP have published a large number of specifications, standards, codes and regulations, some
of which are generic and others prepared for specific project purposes. Not all of these are maintaineddocuments and conflicts do exist. Where significant conflicts are identified, these should be referred to
OPQL TA for advice. An abbreviated list of the most relevant documents prepared by OPQL and QP is
given in Appendix B and referenced throughout this Basis of Design. This document and the standards
referred to shall be used for the specification and selection of equipment and materials for use on facilities
managed by OPQL on behalf of QP. The substitution of other standards requires prior approval from
OPQL TA.
Engineering design activities and equipment offered should be of a good quality, be fit for its intended use
and designed/manufactured to recognised industry standards without “gold plating”. If engineering
contractors or equipment suppliers considers that any specification requirements result in avoidable
additional cost then this shall be brought to the attention of OPQL.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 7/88
Occidental Petroleum of Qatar Ltd Page 7 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
In the event of any conflict between this Basis of Design and other Specifications and Data Sheets or with
any of the applicable Codes and Regulations and as a general principle, the most stringent shall apply. In
case of conflict, OPQL shall be notified in writing before proceeding with any work. OPQL’s decision shall
be final and binding. The general order of precedence shall be as follows:
1) Statutory Requirements
2) This Basis of Design
3) OPQL Data Sheets, Standards and Specifications
4) Qatar Petroleum Data Sheets, Standards and Specifications
6) International Codes and Standards
The SI system of units shall be used. All documentation shall use the English language. Electrical
symbols shall conform to QP Engineering Standard for Draughting, document number ES.D.10. Where
symbols are not given in ES.D.10, those given in IEC 60617 shall be used.
Operational Safety, Security of Supply and Reliability
The design of the electrical installation shall be based on the provision of a safe and reliable supply of
electricity at all times. Safe conditions shall be ensured under all operating conditions, including those
associated with start-up and shutdown of plant and equipment, and throughout the intervening shutdown
periods.
The design of electrical systems and equipment shall ensure that all operating and maintenance activities
can be performed safely and conveniently. Essential equipment and supplies shall be backed up to allow
maintenance without disturbance to process operations. Distribution system design and protection
systems shall be engineered so that the minimum amount of equipment is disconnected following an
electrical fault.
The design of the electrical installation shall ensure that access is provided for all operational and
maintenance purposes. Adequate isolation facilities shall be provided, compatible with OPQL Permit to
Work systems. More details concerning this is provided within OPQL Procedure PRD 500, Electrical
Safety Guidelines.
The requirements of OPQL Process Risk Management Programme shall be complied with. Actions
arising from these risk reviews shall be incorporated into engineering designs in an auditable manner.
Quality Assurance and Control
The contractors, consultants and manufacturers of equipment shall have a quality management system
which conforms to the requirements of IS0 9000, IS0 9001 and IS0 9004.
Certificates, Declarations and Test Reports
For all major electrical equipment like generators, motors, VSD’s, switchgear, transformers and UPS
systems, Type Test Reports of the equipment shall be provided by manufacturers at the tendering stage
of an enquiry.
In addition to other Type Tests, short-circuit test reports especially for switchgear, transformers,
generators, bus-bar ducting and motors shall essentially be submitted.
Certificates or declarations in relation to the application of equipment in hazardous areas shall be
provided by manufacturers. All equipment and devices sourced from European manufacturers and
installed in hazardous areas shall be manufactured as per ATEX directives. Alternative certification
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 8/88
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 9/88
Occidental Petroleum of Qatar Ltd Page 9 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
For installations having presence of flammable dust, area classification and selection of electrical
equipment shall be as per IEC 61241. For the construction and installation of electrical equipment in
hazardous area, all relevant parts of IEC 60079 shall be complied with. Following shall be considered for
proper selection of electrical equipment for use in hazardous area:
Electrical distribution equipment shall normally be installed in non hazardous areas. Where it is
impractical to comply with this requirement, hazardous area equipment may be considered subject to
approval of OPQL TA.
Electrical sub-stations should normally always be located in non-hazardous areas.
2.2 . Env i ronm enta l Cond i t io ns
Engineering designs and equipment shall be in general comply with the requirements of the latest edition
of QP Standard Offshore Environmental Conditions; document number EFS.00.08.03.
The climatic conditions associated with the Occidental managed facilities are those of a corrosive marine
environment with high humidity and a highly saliferous atmosphere. High levels of abrasive dust may be
present periodically. The design wind speed shall be taken as 45m/s and the average barometric
pressure ranges between 995 and 1020 mbar. The annual rainfall ranges between 13mm and 175mm.
Lightning and thunderstorms occur but are relatively infrequent. Refer to EFS.00.08.03 for more detailed
information concerning wind and weather conditions.
Ultra-violet radiation levels are high. All plastics, including glass reinforced plastics exposed to direct
sunlight shall be ultra-violet resistant.
TEMPERATURES AND HUMIDITY
PARAMETER SUMMER WINTER
Recorded maximum shade temperature 48oC 38
oC
Recorded minimum shade temperature 21oC 4
oC
Design maximum air temperature *50oC
Average daily maximum relative humidity 90% 95%
Average daily minimum relative humidity 50% 50%
Maximum temperature of surfaces exposed to sun
(Black bulb temperature)84
oC
Sea surface temperature 35oC 15
oC
Sea bed temperature 25oC 15
oC
*Temperature excursions above 45oC are relatively infrequent and short duration and in most instances,
an ambient temperature limit of 45oC will be acceptable for equipment specification and cable sizing
purposes. If in doubt, please refer to OPQL TA for guidance.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 10/88
Occidental Petroleum of Qatar Ltd Page 10 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
The ambient air temperatures for enclosed modules, equipment rooms, switchgear rooms and control
rooms shall generally be within defined conditions as dictated by the HVAC system, typically 25oC. To
satisfy conditions that may occur when HVAC is inoperative, the internal air temperature shall be
considered as a maximum of 45o
C (under extreme, infrequent conditions). Engineering contractors andmanufacturers shall take this into account when calculating and quoting de-rating factors for main power
components of equipment.
Allowance shall be made for the entry of dust, salt and sulphur contaminated air. When the HVAC is out
of service, humidity levels of 95% can be experienced and due allowance shall be made for this.
Equipment installed on platforms shall be designed for the following accelerations due to earthquakes:
• Horizontal acceleration 0.2g
• Vertical acceleration 0.15g up or down
Equipment installed on platforms shall be designed for the following forces due to barge motion during thesea voyage from fabrication yard to offshore site. These forces shall be considered to act coincidentally
with the equipment weight.
• Horizontal force 0.7W (Pitch or Roll) + 0.2g Vertical
2.3 . Power Supp ly Ar rangements
Existing installations
Power supply arrangements for existing installations are largely determined by the existing platform
facilities. Refer to section 2.8 for details of available voltages and frequencies on OPQL managed
facilities. The following alternatives for the electrical supply shall be considered when designing theelectrical supply and distribution systems for additions to existing installations:
• Utilization of existing power generation and distribution systems
• Captive power generation (i.e. own generation)
• Power provided from an adjacent OPQL facility via subsea cable.
• *Power provided by third party facilities
• Alternative energy sources (for example battery systems charged by Photo-voltaic (PV) solar
arrays, wind turbines, intermittent running gensets etc.) can be considered for low power
(instrumentation and radiotelemetry) applications on remote unmanned platforms.
*There are security of supply, economic and contractual issues that require to be considered and finalized
before power from third parties can be accepted. Please refer to OPQL TA for guidance on these
matters.
New installations
Subject to compatibility with existing installations, voltage levels shall be selected from IEC 60038. The
nominal voltage supply recommended in IEC 60038 is 400/230V 3 phase and neutral on 50Hz systems.
For new plants, the capacity of the electrical distribution system shall be capable of supplying
continuously 125% of the peak load. While sizing equipment like generators and transformers, direct on
line starting and auto-reacceleration of motors shall be duly considered. Future plant load, if any, shall be
duly considered in the peak load calculations. This 25% spare capacity is kept to cater for the possibility
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 11/88
Occidental Petroleum of Qatar Ltd Page 11 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
of future de-bottlenecking of the plant and to accommodate changes taking place during project design
that may involve minor adjustments in electrical loads. This factor of 25% may get reduced to 10% when
the plant is ready to start.
The number of power supply generator or power transformer units to be installed and their individual
ratings depend on many factors, e.g. maintenance requirements, economic size, future load development
pattern, unit reliability etc. Sufficient stand-by capacity shall be incorporated to fulfil the requirement of
the peak load continuously, even if the largest supply unit trips or is out of service for maintenance
purposes. The provision of stand-by capacity shall be considered in relation to safety, reliability and the
continuity of plant operation.
For plants having only captive generating units, the number of units n+2 or n+1 (where n is the number of
generating sets required to supply the peak load) shall be decided by the nature of process and
acceptance of load shedding scheme for non-essential loads. Sufficient spare capacity shall be available
to avoid load shedding following loss of the largest generator or supply source.
The availability of further stand-by supply capacity to cater for unit failures during maintenance or repair
periods shall be provided where the aggregate maintenance or repair time warrants this. Where no such
capacity is provided, nor it is practically possible to provide (especially for an existing plant), then
automatic load shedding schemes shall be implemented.
The maximum rating of power transformers shall be decided such that the rated current of their low
voltage winding does not exceed 2000 A when feeding HV switchboard and 2500A when feeding LV
switchboard. Higher ratings shall only be considered in case of significant cost saving. Please refer to
OPQL TA for guidance and approval as required.
Distribution Philosophy
The main sources and feeders of power shall be duplicated in such a manner that if one of them is tripped
or is out of service, the remaining units can take care of the total power. New plants should be designed
with sufficient spare capacity in the captive generation (n-1) to render load shedding unnecessary under
normal operation of the plant.
Consideration shall be given to providing a secondary selective interlocking system to automatically
reinstate power following loss of a single feeder. Details are provided within QP Engineering Standard for
Secondary Selective System ES.2.14.0060.
Each distribution system should have reliability at least comparable with its primary supply system and
shall incorporate sufficient standby capacity to enable maintenance work, tests and inspection checks to
be carried out without operational disturbance.
Single Line Diagrams
The conceptual design and philosophy of the electrical distribution system shall be represented by means
of a Single Line Diagram. This diagram may be a new document or a modification of an existing
document. The following information shall be shown on the Single Line Diagram:
• All sources of electric power
• The main supply voltage and distribution system interconnections at each voltage level
• System capacities, autonomies, frequencies, equipment ratings (including fault ratings), and
impedances, winding configuration and earthing arrangements
• Vector diagrams for all voltage levels
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 12/88
Occidental Petroleum of Qatar Ltd Page 12 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
• Relevant information that basically describes the design and operating philosophy to be adopted
for the system, e.g. arrangement of main and stand-by circuits, normal switch positions, switch
interlocking and circuit changeover facilities, synchronising facilities, power factor correction
facilities, anticipated future loads or circuit extensions, etc.
• Location of earth switches, CTs, VTs and measuring instruments
• Interfaces with remote SCADA, DCS, PMS, substation controls etc.
• Details of all protective devices
• Cable type, size and tag numbers
• HV motor kW ratings
For large installations, the Single Line Diagram can be sub-divided into several Single Line Diagrams so
that all aspects are shown more clearly and easily. Nominal system voltage(s), frequency and the
positive phase sequence shall be indicated on the Single Line Diagram. The phase sequence shall be
specified in alphabetical order L1, L2, L3 or U, V, W, each phase reaching its maximum in time sequence
in that order.
Load Shedding
Load shedding shall be based upon the high speed tripping of the lowest priority loads. Various loads or
groups of loads shall be selected for load shedding, ranked and placed in the tripping sequence. The
load shedding system shall pre-calculate the minimum number of loads to bring the system back into
balance in the event of supply loss. On receipt of a load shed signal these predetermined loads will be
tripped. The priority sequence and choice of loads for shedding shall be determined based upon
ensuring system stability with minimum operational disturbance.
Short Circuit Capacities
All equipment shall be capable of withstanding the effects of short circuit currents (initial symmetrical short
circuit current and peak short circuit current) and consequential voltage arising in the event of equipment
failure or equipment faults. Each short circuit interrupting device shall be designed to have rated breaking
capacity equal to or higher than the maximum value of short circuit current calculated at its location.
For calculation of maximum value of short circuit ratings including the short circuit making and breaking
capacity of circuit breakers, parallel operation of all power supplies and contributions from motors shall be
duly considered.
For power intake switchboards, close co-ordination will be required with the third party power providerand due consideration shall be given to the expected future planned increase in short circuit level.
The short circuit rating of generator switchgear shall be calculated taking into consideration the maximum
number of generators simultaneously in operation including future expansions. All switchgear and bus-
bar ducting shall withstand the maximum fault current for a minimum period of one second. Sizing of high
voltage cables shall be based on the short circuit withstand capacity for a duration dictated by the
protection system.
Neutral Earthing
For HV systems with voltage not exceeding 33 kV, the neutrals of following shall be earthed through a
current limiting Neutral Earthing Resistor (NER) or other approved fault limiting device:
• Generators directly connected to HV switchboards
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 13/88
Occidental Petroleum of Qatar Ltd Page 13 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
• Generator transformers
• Incoming transformer feeders from third party power providers
The rating of each NER shall be such as to limit the earth fault current supplied by the equipment to whichit is connected to a value as low as practical and which can be reliably detected by earth fault relays in
the circuit. Generally the earth fault current shall not exceed 50% of transformer or generator full load
current.
Where generators are connected in parallel to the same switchboard and each is earthed through its own
NER, then each NER shall be rated to allow the circulation of zero sequence harmonic currents to flow
continuously. If the circulating current is such as to exceed the thermal rating of the NER, then the
generators shall be earthed via one NER only. Each generator shall then be provided with a suitable
switching device to facilitate connection of any generator to the single NER.
LV electrical system neutrals at each source of supply shall be solidly earthed by means of dedicated
earth electrodes, which have a direct, low impedance connection to the installation main earth grid. The
system of earthing shall be designated as 'TN-S', as defined in IEC 60364, unless otherwise specified.
For fixed LV equipment, the earth loop impedance shall be low enough to cause circuit disconnection in
less than one second (as determined by equipment fault limits), when a bolted fault of negligible
impedance is applied. Refer also to Appendix D.
AC UPS systems shall have their neutrals solidly earthed. DC UPS systems for electrical loads and
critical lighting shall normally be unearthed. Earthing of DC UPS systems (for electrical, telecom, fire
alarm and plant communication systems) shall take into account recommendations of the respective
equipment manufacturer.
2.4 . Pro tec t ion , Power Management , Cont ro l s and Ind ica t ions
Electrical Protection System
The electrical system shall be equipped with reliable automatic protection. QP Engineering Standards for
HV Switchgear and Control gear for indoors ES.2.14.0010 and LV Switchgear and Control gear
ES.2.14.0015 give details of the selection and specification of switching and protective devices, control
circuits and associated auxiliary equipment.
The type and characteristics of protective devices shall be selected according to the application and shall
be compatible with those of existing system. However, for new installations microprocessor based
numerical protection system in combination with a Power Management System shall be considered.Protective relays shall be solid state multi-function. Protection should use 'industry standard'
communications protocols compatible with relevant systems (for direct interface with DCS, power
management systems etc.)
The automatic protective systems shall be designed to achieve selective isolation of faulted equipment
within a time corresponding to the short-circuit current withstand capability of equipment, system stable
operating limits and the maximum fault clearance times.
Adequate and selective phase short-circuit and earth fault protection shall be provided. Due regard shall
be given to the magnitude of short-circuit currents and method of system earthing. Limited duration over-
currents arising from single or group motor starting and reacceleration shall be permitted. Automatic
control systems such as load transfer, motor restarting arrangements and protective systems to initiate
load shedding, may be required for a particular plant.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 14/88
Occidental Petroleum of Qatar Ltd Page 14 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
A protection diagram in the form of a Single Line Diagram shall be prepared for the complete electricity
supply and distribution system. The drawing shall indicate the type and location of all protective devices
and associated CTs and VTs that are to be provided. Based on this drawing, an electrical protection
report shall be prepared which shall demonstrate the adequacy of all protective systems in fulfilling theabove requirements. The protection report shall include at least a description of the system and of the
system operating modes on which the settings have been based, together with relevant short circuit
current calculations or computations for specified minimum and maximum generation or supply
conditions, single line diagrams for each part of the system, tabulated settings of the individual devices
and co-ordinated characteristics of the protection devices and fuses, etc., plotted in graphical form.
Protective relay settings shall be based on a study of the fault conditions for which the protective system
has been designed and incorporated. Protective relay systems shall be selective and the settings shall
be co-ordinated so that back-up protection is provided in the event of protective system or switching
device failure. The minimum generation or supply capacity conditions shall be at least representative of
those that arise during normal operation of the process units, production facilities and their utilities.
Where required, the dynamic performance of the electrical system shall be analysed to verify the
adequacy of the protection system provided, by ensuring successful recovery of the electrical system to a
stable operating state following the clearance of a short circuit. The study shall be repeated for the
application of a short circuit at various critical locations in the power system. In particular, systems
incorporating on-site generation as the main means of power supply, shall be studied to establish the
extent to which re-energisation of essential service loads may be applied. The protection of the
interconnections with third party power providers require to be mutually agreed.
The protection relay settings shall be self-contained within the relay so that they can only be changed at
the relay, and not by remote means. For intelligent relays, access to the settings shall be via the software
and password protected or by a similar secure method.
Power Management System
A dedicated Power Management System (PMS) for the electrical generation and distribution system shall
be considered where centralised supervision, control and metering is required. This system shall comply
with the requirements of QP Engineering Standard for Power Management System ES.2.14.0065. The
requirements of OPQL Specification for Power Management Systems, document No. 403086-4-PS1E-
SP-0002-001 shall also be taken into consideration.
For new projects involving power generation, consideration shall be given to installation of a Power
Management System (PMS). For upgrade projects, the requirement of PMS shall be based on the
operational requirements, operator task analysis and an economic evaluation.
PMS Basic Requirements and DCS Interfacing
The PMS shall be a continuously on-line computer-based system using high integrity self monitoring
PLC’s. For new installations, it shall not be an integral part of the overall DCS network system and the
operation of the power system shall be kept independent of other DCS type of operations. An important
function of the PMS will be to ensure system stability in event of disturbances. This will include a high
speed load shedding needed when one or more generators or system feeder’s trip. This essential feature
will require the PMS to be constantly monitoring the power generation and distribution network status, to
be making complex real time calculations based upon dynamic power information, and to be in a state of
readiness to load shed within a few milli-seconds of receiving a “load shed” initiating event.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 15/88
Occidental Petroleum of Qatar Ltd Page 15 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
The PMS should be connected to the overall DCS system simply for the purpose of 'delivering'
information to the DCS network for the purposes of event recording, trending, reporting and the like. The
systems architecture and functional design specification shall be established at an early stage of a new
project in conjunction with instrumentation group. This will enable the PMS to function as required, withthe maximum availability, when the connection to the DCS is out of service.
PMS Management Funct ions
The main PMS functions that should be considered are:
• VDU display of main equipment in single-line format, at a suitably located control point
• Display of load flows, voltage profiles, frequencies
• Alerting operators when n+1 power margin is not satisfied
• Operational status of equipment
• Load shedding
• Inhibiting the start of large motors on load mismatch
• Protecting the ability of fire pumps etc., to start even on load mismatch
• Load sharing between generators and third party feeders
• Synchronising of generators
• Monitoring and alarming performance
• Fault level surveillance in special cases
• Intelligent interlocking for special cases
Other details like configuration, inputs, outputs, displays, indications and alarms shall be as
detailed out in QP Engineering Standard for Power Management System ES.2.14.0065.
Control, Metering, Alarms and Indications
Adequate controls, metering, alarms and indications for checking and monitoring of the power system, as
required for proper control and operation of the electrical installation shall be provided. Metering shall be
provided to keep a record of power consumption and measurement of current, voltage, power, frequency,
power factor etc. Where third party supplies are provided to (or from) OPQL, consumption metering shall
be revenue class. Maximum demand indicators shall be provided for third party supplies with contractualtariff restrictions.
QP Engineering Standards for HV Switchgear and Control-gear for indoors ES.2.14.0010 and LV
Switchgear and Control-gear ES.2.14.0015 give full details of requirements for each type of incomer and
outgoing feeder. Equipment specific requirements are also covered in QP Engineering Standards for HV
Gas Turbine Driven Synchronous Generators ES.2.14.0001, Diesel Engine Driven Generators
ES.2.14.0002, HV Induction and Synchronous Motors ES.2.14.0030, Electric Motor Operated Valve
Actuators ES.2.14.0036, AC UPS Systems ES.2.14.0040 and DC UPS Systems ES.2.14.0044.
Grid intake circuits which are required to operate in parallel with captive generators shall be provided with
synchronising facilities, check synchronising relay and dead-bus override. These controls shall be
located where control of the frequency and voltage of the generators can be exercised. Each motor
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 16/88
Occidental Petroleum of Qatar Ltd Page 16 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
circuit shall be provided with a remote ammeter and provision of power supply for motor anti-
condensation heater (for all motors above 30kW).
Switching counters shall be provided on all HV motor and transformer feeders. Running hour meters shall
be provided for generators and HV motors.
Classifi cation of Electrical Loads
Electrical loads shall be classified as performing a service, which is of the following types:
• Vital (i.e. critical)
• Essential (i.e. emergency)
• Non-essential (i.e. normal)
Refer also to QP-PHL-S-001 Corporate Philosophy for Fire and safety, section 14; Emergency Power
Supply System.
Vital Service
Vital service is a service which, when failing in operation or when failing if called upon, can cause an
unsafe condition of the installation, jeopardise life or cause major damage to the installation. This applies
to life support systems on offshore platforms, emergency and escape lighting, DCS, ESD etc. Depending
on the service conditions, the electrical supply to the vital service may have to be non-interruptible. Since
the faultless functioning of equipment cannot be guaranteed, duplication of sources of power supply and
redundancy of equipment shall be provided. Vital services are normally provided by dual redundant
battery backed power supply systems, or by self contained battery/inverter packs for plant emergency
lighting.
Essential Service
Essential service is a service which, when failing in operation or when failing if called upon, can affect the
continuity of operation, the quality or the quantity of product. Therefore the economics of partial or
complete duplication of the energy source, of the lines of supply or of the equipment or the introduction of
automatic restarting facilities or of changeover facilities or provision of standby energy source shall be
evaluated in relation to the consequences of service interruptions mentioned above. One example is a
power supply to process equipment by means of a duplicate supply system with a changeover facility.
Non-essential Service
Non-essential service is a service that is neither vital nor essential and therefore does not require any
special measures for safeguarding it. An example of this is normal lighting or non critical domestic
installations, etc.
2.5. ESD, DCS and Genera l Contr o l In ter f aces
In general, interfaces between electrical and instrument systems should not introduce voltage levels into
equipment not already present. Unless otherwise advised, interface signals to DCS and ESD panels
shall be at 24V DC. Where required, interposing relay panels shall be installed to segregate equipment
voltage levels.
Interfaces between electrical and control systems (i.e. DCS) should be selected to ensure
communications protocol compatibility with minimal (ideally no) intermediate converters. A serial link
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 17/88
Occidental Petroleum of Qatar Ltd Page 17 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
interface is preferred when large numbers of signals are involved. Lesser signal requirements (grouped
common alarms etc.) shall be hard wired. All safety critical signals (ESD etc.) shall be hard wired.
Interconnected PLC based control systems with fast response requirements (for example load shedding),
functional logic and initiating devices require special consideration and may require event prioritization
and/or fiber optic/direct wired connections. Refer to OPQL Electrical and Instrument TA’s for additional
guidance if required.
2.6 . E lec t r i ca l Load Schedu les and Load Forecas t in g
Summations and Diversity Factors
A schedule of electrical loads shall be prepared as early in a project as possible in an approved format
(examples can be made available by the OPQL TA). The Electrical Load Schedule will form the basis for
confirming the necessary electrical distribution system capacity and what upgrades (if any) are required.
The following shall be included in the Electrical Load Schedule:
• The installed electrical loads
• Category of load i.e. continuous (all loads required continuously for normal operation and running
all the time), intermittent (all loads required for intermittent operation and running occasionally) or
standby (all loads required in emergencies only).
• Rated active power in kW (shaft output), rated power factor, rated current, rated efficiency and
load factor.
• Absorbed active power in kW
• Reactive power in kvar
The continuous (Sum C), intermittent (Sum I) and standby (Sum S) loads shall be summated separately
in a manner that does not introduce kW/KVAr summation errors. A diversity factor shall be applied to
each of these summations so that the Total Plant Running Load (TPRL) and the Total Plant Peak Load
(TPPL) can be calculated.
The recommended diversity factors are 1.0 for (Sum C), 0.3 for (Sum I) and 0.1 for (Sum S). Adequate
care needs to be given to the requirement that 0.3 x (Sum I) shall not be less than the largest single
intermittent load. For non-process loads like offices, workshops lighting etc., a typical diversity factor of
0.9 shall be applied to (Sum C) of such loads.
The TPRL, shall be the sum of 1.0 x (Sum C) and 0.3 x (Sum I). The TPPL shall be the sum of 1.0 x (SumC), 0.3 x (Sum I) and 0.1 x (Sum S).
The diversity factor may vary and there will be instances where engineering judgement has to be applied.
Where necessary, the OPQL TA shall be consulted for guidance. The load schedule is critical to allow
accurate estimating of equipment and shall be finalised as an early stage of the project. For extension of
existing plants, the TPRL, and TPPL shall be checked against the actual measured values of the facility.
All loads to be automatically restarted after a voltage dip shall be clearly identified. Also, all loads to be
shed as part of load shedding scheme shall be clearly identified. The Electrical Load Schedule shall be
updated regularly throughout the design stage of the project.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 18/88
Occidental Petroleum of Qatar Ltd Page 18 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Sub-division of Electrical Load Schedule
A separate schedule shall be prepared for each HV and LV switchboard. Each separate schedule will
therefore be a sub-division of the complete Electrical Load Schedule. Each subdivision shall clearly show
the following information:
• Summations of the load fed from the particular switchboard, excluding feeds to and received from
other switchboards
• Active and reactive power fed individually to other switchboards, including losses in feeder
transformer if used
• Total active and reactive power received from the source, e.g. up-stream switchboard, generator,
transformer intake.
Load forecasting and power profiling
Power profile load forecasts are used for scenario planning and to estimate load growth over the
operating life of an asset. Where required, these shall be provided in an approved format (examples can
be made available by the OPQL TA).
2.7. System Vol tage, Frequency and Power Facto r
Selection of vo ltage and frequency
The various voltages to be adopted shall be decided based on the following factors:
• Compatibility with voltage levels of existing installations
• Size and location of loads
• Future margin and expansions
• Short circuit levels
• Availability of switchgear for continuous and short circuit ratings
• Keeping the number of different voltage levels to a minimum
• Economic considerations
The frequency for all installations shall be 50 Hz unless limited by source of supply constraints (as at Al-
Morjan).
Deviations in Supply Voltage and Frequency
The following parameters are to be applied to new installations and can be used (in the absence of site
specific information) as a guide to system disturbances that can be expected on power installations of
existing installations.
During normal system operation, the voltage at consumer terminals shall not deviate from the rated
equipment voltage by more than +/-6% and the frequency shall not deviate from the rated frequency by
more than +/-2% under steady-state conditions. The combined voltage and frequency deviations shall lie
within Zone-A as described in IEC 60034. All loads shall be balanced such that the negative phase
sequence components of voltage and current, at any point in the system, shall not exceed the values
quoted in IEC 60034.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 19/88
Occidental Petroleum of Qatar Ltd Page 19 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
During starting or re-acceleration of a motor, either individually or in a reacceleration group, the transient
voltage dip at the motor terminals shall under no circumstances exceed 20% from rated voltage when
started direct on line under the worst operating scenario (i.e. the largest motor started against the
minimum fault level) - this is an absolute operating limit. When sizing cables for new and existinginstallations, locked rotor voltage drops shall be kept within a 15% limit. Transient voltage variations
occurring at switchgear bus bars during starting or re-acceleration of a motor or group of motors shall be
such as to maintain a minimum of 90% voltage on switchgear bus-bars for HV motors and 92.5% for LV
motors. Voltage depressions resulting in consumer terminal voltages down to 80% of rated voltage shall
not affect plant operations.
In the absence of any other consideration, under normal service conditions the voltage at the terminals of
equipment shall be greater than the lower limit corresponding to the said equipment.
When sizing cables and calculating voltage drops, a maximum steady state aggregate voltage drop for
feeder and motor and final sub circuits of 6% shall be considered (this being based upon a 2% limit for
feeders and a further 4% for final sub circuit). Refer to section 4.1 for cable sizing design basis.
The maximum voltage drop in UPS powered systems requires special consideration and shall take into
account voltage decline during battery discharge conditions together with voltage tolerances of connected
instrumentation. These shall be assessed on a case by case basis. In the absence of more detailed
information, the following tolerances are recommended:
• DC UPS outgoing feeders (for electrical controls): 5%
• DC UPS instrumentation outgoing feeders: 2%
• AC UPS instrumentation outgoing feeders: 5%
In the absence of approved project specific cable sizing documents and software, engineering contractors
shall use document number YPS1-4-CA-6921-001 Phase 3 Water Injection LV cable sizing tables. This
document is available from OPQL DCC on request.
Deviations and Variations in Supply Waveform
All equipment shall be suitable to operate satisfactorily with a total harmonic voltage distortion of 5% in
the supply voltage. Electrical loads having non-linear characteristics, such as to produce voltage and
current waveform distortion of a magnitude detrimental to the lifetime or performance of electrical
equipment shall not be utilised unless appropriate measures are taken to render harmless the effect of
such distortions e.g. by filtering or phase displacement, etc.
For installations having submarine cables used to transmit power to or from offshore platforms, studiesmay be required to determine the possibility of resonances occurring especially at low order harmonics
leading to over voltages and over currents. Means shall be provided to mitigate the problem of
resonance and to avoid the voltage distortion at the load or the supply. This can take the form of either
active or passive harmonic suppression. Based on the study, necessary protective measures shall be
adopted. However, these will be project specific. Equipment having special requirements with respect to
variation in voltage level and waveform shall be provided with a power supply that is adequately stabilised
or filtered.
System Power Factor
The overall system power factor, inclusive of reactive power losses in transformers and other distribution
system equipment, for new installations should ideally be no less than 0.9 lagging at rated load. The
requirements for power factor correction shall be decided at an early stage of the project. Static
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 20/88
Occidental Petroleum of Qatar Ltd Page 20 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Capacitor Banks (HV and or LV) shall be provided to improve the power factor. Automatic control of
Capacitor Banks shall be provided where these are provided for a group of motors/ loads.
The measured power factor for OPQL managed facilities is typically in the range of 0.8 - 0.85 lagging
(PS1 facilities are 0.85).
2.8 . Vo l tages and Frequenc ies fo r Ex is t ing OPQL Ins ta l la t ions
General
The primary system characteristics are summarised below, facility by facility. It has not been possible to
list all of the voltage levels for all of the remote facilities but this information is available on key drawings
available from OPQL Documents and Standards section.
Idd El Shargi - PS1 Product ion Station - (ISND)
There are two main power plants on PS1. The PS1E power plant comprises four x *2.36MW RGT
Gensets generating and supplying power at 3300v, 3ph, 50Hz to a main dual section HV switchboard
SB4141. The generators neutrals are individually earthed through NER’s. The HV voltage is transformed
to 415v, 3ph, 50Hz via two x 1600kVA transformers which supply a low voltage switchboard SB4102.
There is one diesel genset on PS1G which provides 415v, 3ph, 50Hz to the emergency switchboard
SB4103 and two further 415v, 3ph, 50Hz diesel gensets which provide power for platform black-starting.
There are also 415v, 3ph sub-distribution switchboards on PS1R, PS1W, PS1G and PS1Q. Lighting and
small power distribution is at 415v 3ph and 240v, 1ph.
The PS1K power plant comprises 3 x *12.82MW Solar Titan GT gensets generating and supplying powerat 6600v, 3 ph, 50Hz to a main dual section HV switchboard SB3102. Neutral earthing is provided by 2 x
earthing transformers connected to sections A and B of SB3102. The HV voltage is transformed to 415v,
3ph, 50Hz via 2 x 1600kVA transformers which supply the PS1K low voltage switchboard SB3103. There
are 2 x 5/7MVA interconnectors which provide 2 way power exchange between SB3102 and SB4141.
PS1K has no emergency switchboard and is also dependent upon PS1E power plant for black starting.
Lighting and small power distribution is at 415v 3ph and 240v 1ph. Further information is available within
PS1K Electrical Basis of Design, document 402160-4-PS1K-BD-6015-001.
There are a number of battery backed UPS systems which provide vital and emergency power at 240v
ac, 50Hz, 110v DC and 24v DC (typically 60 minutes autonomy for PS1E and 90 minutes for selected K
loads). There are also other battery systems providing battery backed power to navigational aids, turbine
control systems and engine starting batteries.
There are also a large number of remote, unmanned wellhead platforms. Some (but not all) of these
wellheads have subsea power umbilicals from PS1,variously powered at 6600v, 3300v and 415v. The
remainder are powered at 24v DC via a mixture of photovoltaic solar arrays and wind turbines with back-
up batteries.
*Note: - The available output power from the gensets is less than nameplate ratings, for example PS1ERGT’s cannot reliably deliver more than 2MW and PS1K Solars are normally limited to 9.6MW or less.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 21/88
Occidental Petroleum of Qatar Ltd Page 21 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
This is based upon site ratings and operator experience over several years. Refer to OPQL TA for further
information if required.
Idd El Shargi – IS04 and IS34 Remote Facilities - (ISSD)
The two ISSD platforms do not have their own independent power plant. On PS1 voltage is transformed
from 3300v to 6600v via a 3MVA transformer located on PS1R. PS1 and IS04 are linked via a 22km 3c
300mm subsea cable. The incoming 6600v 3ph, 50Hz supply on IS04 powers switchboard 71-SB12731.
IS34 is powered from IS04 via a 2.2kM 3c 95mm subsea cable from switchboard 71-SB12731. The
6600v supply on each of the two platforms is transformed to 480v via a 2.4MVA transformer on each
platform. This is a dual secondary transformer used to supply two 480V switchboards (one star, one
delta) which in turn supply a number of ESP’s. HVAC is powered from the star switchboard at 480v, 3ph,
50Hz. Lighting and small power is provided at 480v, 3ph, 50Hz and 277v, 1ph, 50Hz. There is a 15kVA
480/240v ac transformer which provides a limited amount of power at 240v for equipment unsuitable for
277v supply.
Halul Island – Produced Water Handling Facili ties (PWHF)
The OPQL PWHF at Halul does not have its own independent power plant. It is supplied with power via
two x 33kV feeders from an adjacent substation. The incoming 33kV voltage is transformed to 11kV by
two x 15MVA transformers which supply an 11kV switchboard SB5170. The transformer neutrals are
individually earthed. This is transformed to 400v, 3ph, 50Hz via two x 1600kVA transformers which
supply a low voltage switchboard SB5171. This switchboard has an auto transfer system which closes
the bus section on loss of one of the incoming feeders. There is one 400v, 3ph, 50Hz diesel genset
which provides limited backup power to SB5171. Loads are selectively shed from SB5171 following an
interruption of the primary power supply. Lighting and small power distribution is at 400v, 3ph and 230v,
1ph.
The PWHF substation was installed and is operated by OPQL, however the 11kV switchgear also
supplies power to a number of QP operated assets on HALUL island.
There are a number of battery backed UPS systems which provide vital and emergency power at 110v
ac, 50Hz, 110v DC and 24v DC (typically 60 minutes autonomy). There is also a 24v DC UPS providingpower to remote telemetry units (RTU’s). This is supplied from QP combined industrial building 415V,
3ph switchboard.
Further information is available within The PWHF Electrical Philosophy, document 400060-4-HALU-6593.
Al Rayyan - Al-Morjan Permanent Product ion Facil ity and CALM loading Buoy
The OPQL Al-Morjan facility does not have its own independent power plant. On NFA, voltage is
transformed from 6600v to 33kV via a 15MVA transformer fitted with automatic tap changers to provide
voltage regulation. NFA and Al-Morjan are linked via a 41km 3c 185mm subsea cable. The incoming
33kV, 3ph, 60Hz supply to Al-Morjan powers a main 33kV switchboard SB945B.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 22/88
Occidental Petroleum of Qatar Ltd Page 22 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
The 33kV voltage is individually transformed and distributed to four x 480v, 3ph, Electrical Submersible
Pump (ESP) switchboards. Voltage is transformed to 440v, 3ph, 60Hz, supplying process and utilities
switchboards. There are a number of standby and emergency diesel gensets which provide limited
backup power at 440v, 3ph, 60Hz when the primary supply from NFA is unavailable.
HVAC distribution is supplied at 440v, 3ph, 60Hz. Lighting and small power distribution is supplied at
380v, 3ph, 60Hz and 220v 1ph.
There are a number of battery backed UPS systems which provide vital and emergency power at 220v,
60Hz ac (instruments), 48v DC (telecoms), 24v DC (navaids). The autonomy period is 60 minutes.
Further information is available within the Electrical Design Basis included within section 8 of the Al-
Morjan Basis of Design.
2.9. E lectr i ca l System Studi es and Reviews
Where major modifications or additions to platform facilities are contemplated, then concept studies,
usually single discipline (but often part of a larger multi-discipline concept development) shall be
competed. These are typically initiated with a project Statement of Requirement (SoR), project objective
statement, etc. and scope of study agreed with OPQL TA. QP Engineering Standard for Power System
Studies ES.2.14.0095 can be used as a guide when developing the study scope of work. These will
typically evaluate several study options and investigate/eliminate those which are non viable.
The Power System Studies and Protection studies shall be performed in support of the design and
procurement of equipment with correct specifications. These studies may comprise of the following
depending on the type, size and complexity of the electrical generation and distribution system:
• Load flow studies
• Fault level studies
• Motor start-up and voltage depression studies
• Transient stability studies
• Power factor studies
• Harmonics penetration studies
• Power system reliability and availability studies
• Relay settings/protection studies
Modelling software used for system studies shall be agreed in advance. OPQL shall review and approve
software tools to be adopted (or propose alternatives). These shall accredited industry recognised
software. EDSA, ETAP or CYME suite of software programs created by CYME International Inc. Power
Engineering Software are all acceptable.
Safety and Operabilit y (SAFOP) Reviews
The requirement for SAFOP reviews shall be determined as part of OPQL Process Risk Management
programme and (where required) will be finalised in consultation with OPQL TA. These shall ideally be
facilitated by an independent agency not involved in the design of the electrical system. Attendance
should include a senior representative with significant knowledge of the design of the system, operations,
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 23/88
Occidental Petroleum of Qatar Ltd Page 23 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
maintenance representatives and OPQL electrical TA. Refer to document YPS1-4-SP-6928-001 Safety
and Operability Review (SAFOP) Terms of Reference for further guidance.
In order to ensure full range of safety, operability and operator task analysis, the SAFOP review shall be
performed in the early stages and validated in the final stages of electrical system design. The
engineering design and operability of the system is systematically questioned with key words to identify
any possible limitations and lack of flexibility and to assess the consequences on the operability and
safety of the system as well as safety of the operator. Smaller projects do not require these reviews.
Where required, they shall consist of the following:
SYSOP (System Operability) Review
The method for this is comparable to that of a HAZOP. Nodes and boundaries are defined using key
SLD’s etc. followed by a review of the overall electrical system design examining control systems, main
equipment of plant and their auxiliaries and consider any limitations found and their effect on the system
operability.
SAFAN (Safety Analysis) Review
The SAFAN is very similar to “What-if” reviews performed as part of the OPQL PRM programme. This
will examine hazards present in construction, commissioning and operation of electrical installation and
consider them in relation to the safety of personnel who are to operate, work or be in the vicinity of the
equipment.
OPTAN (Operator Task Analysis) Review
This will look at the probable tasks to be undertaken by both the control room and the field operator
during normal and abnormal conditions. It will also review the instructions and measures built-in to
prevent human error. The OPTAN review is best performed towards the end of engineering design when
operability aspects are reasonably well defined and the relevant vendor documentation is available.
2.10. Electr ica l Deta i l ed Desig ns
Engineering detailed design shall be executed against a defined scope of work (usually multi-discipline)
and managed by an OPQL appointed project engineer or discipline specialist. The engineering contractor
shall not deviate from this scope without approval from the OPQL representative. Typically OPQL require
project reviews at 10% (confirmation of base scope), 50% (mid-design review) and 90% (after first formal
issue, constructability reviews etc).
The requirements of OPQL Engineering and Procurement Procedure FAC 223 shall be complied with.
The focus is on compliance with the defined project electrical engineering requirements while managing
schedules and man-hours within agreed limits. Detail designs shall be incorporated into a construction
work package in an approved OPQL format.
OPQL Management of Change PRM requirements shall be complied with. PRM deliverables include Pre-
Start Safety Reviews (PSSR), revisions to operations manuals, identification of training requirements and
preparation of planned maintenance routines (PMR’s). Where instructed, these shall be prepared by
engineering contractor in an approved format. Refer to Appendix F for sample PMR format.
Commissioning requirements shall be taken into account during the design and included within the project
deliverables.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 24/88
Occidental Petroleum of Qatar Ltd Page 24 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
3. EQUIPMENT SPECIFICATION AND SELECTION PHILOSOPHY
3.0. General
All electrical equipment should be specified as being of a good quality, be fit for its intended use and
designed/manufactured to recognised industry standards without “gold plating”. Equipment should be
selected from manufacturers standard product ranges wherever possible. If engineering contractors or
equipment suppliers consider that any of the listed or referenced specification requirements result in
avoidable additional cost then this shall be brought to the attention of OPQL.
Refer to Appendix C for guidance concerning selection of bulk items and minor equipment. OPQL carry
stocks of commonly used cables, cable racking, trays etc. Engineering contractors are required to verify
and use items from OPQL stock lists wherever it is feasible to do so.
In general, OPQL shall adopt (and accept the use of) QP codes and standards and are obliged to follow
good industrial practice but it is noted however that application of QP codes and standards is not
mandatory within the DPSA. Refer to Appendix B for the list of codes and standards that are
recommended for use when selecting and specifying equipment for OPQL managed facilities.
Engineering contractors working on behalf of OPQL shall comply with these requirements. Where QP
codes and standards are used for major equipment procurement, it is required that a project specific
addendum specification and data sheets (listing accepted deviations) be prepared, suitable for open
tendering in lieu of a dedicated project specific specification. This shall be approved by the OPQL TA
prior to issue. The substitution of other standards requires prior approval from OPQL TA.
For tendering purposes, the approved project specifications, datasheets drawings and OPQL/QP codes
and standards are compiled into a requisition package. Where instructed, engineering contractors shall
prepare this requisition. The OPQL buyer issues the requisition as an “Invitation to Tender” to all
companies on the pre-approved bid list. Please refer to document 410924-8-PS1E-MR-0001-001 for an
example requisition in an approved format. Management of all bidder correspondence up until order
placement is an OPQL responsibility.
The requirements of OPQL Engineering and Procurement Procedure FAC 223 shall be complied with.
OPQL will make available their Approved Suppliers Lists for use during equipment specification. Where
requested, engineering contractors shall supply suggested bid lists for potential suppliers. Inclusion of
suggested suppliers within the OPQL approved suppliers bid list will be determined by OPQL at time of
tendering.
Unless otherwise agreed in writing, all electrical equipment shall be new and unused. Equipment shall be
manufactured with proven state of the art technology. The equipment shall not be prototype or from a
new product line that is not proven earlier in the oil and gas and petrochemical industry. The equipment
shall be designed for a service life of at least 20 years.
All electrical equipment shall be suitable for the site and environmental conditions as specified in section
2.2 Environmental Conditions and the respective equipment Data Sheets and Project Specifications.
Auxiliary supply voltages shall be selected compatible with the intended installation location. Refer to
section 2.8 for specific details.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 25/88
Occidental Petroleum of Qatar Ltd Page 25 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
All electrical equipment shall be designed and sized to operate at the specified design ambient
temperature. For batteries, the maximum design ambient temperature shall be considered while for
electrical heat tracing, minimum ambient temperature shall be considered.
Where appropriate, outdoor equipment shall be protected with suitable sun-shading. The ingress
protection for equipment enclosures shall be minimum IP55 as per IEC 60529. Weather shelters with
open sides shall be considered as outdoor installations. Indoor equipment shall normally be installed in
rooms having HVAC systems. The ingress protection for the equipment enclosure shall be minimum IP42
as per IEC 60529.
The atmosphere throughout all OPQL managed installations shall be considered to be corrosive, as
normally associated with oil and gas processing plants, refineries, chemical plants, LNG plants, offshore
platforms, industrial sites and the like. In addition, for offshore and coastal locations, the atmosphere
shall be considered as salt laden with presence of H2S. High humidity is experienced in all areas and
condensation will occur on all equipment during some period of their lifetime and therefore all
components, nuts, bolts and washers etc. shall be of corrosion resistant material and shall be
tropicalised. Anti-condensation heaters shall be provided where specified in their respective Engineering
Standards.
Equipment like main generators, emergency generators, distribution transformers, VSD’s, AC UPS
system, DC UPS system, batteries and switchboards shall be installed in non-hazardous areas. Only in
exceptional (and unavoidable) cases, shall these be installed in hazardous areas in specially designed
rooms.
3.1. Generators
HV GT Synchronous Generators
The generator, generator control panel and auxiliaries shall comply with QP Engineering Standard for HV
Gas Turbine Driven Synchronous Generators ES.2.14.0001. Engineering contractor shall prepare project
specific data sheets prior to tendering this equipment. The generators shall be procured as a complete
package along with the gas turbines. The kVA rating of the generator shall be such that it does not limit
the output of prime mover over the specified operating temperature range. The generator shall be sized
to have at least 10% spare capacity for future.
The generator rated power factor shall be 0.8 lagging, unless otherwise specified in the Generator Data
Sheet.
Generators shall normally be air-cooled. Use of water-cooled generators shall be subject to approval byOPQL TA.
The rating, type, characteristic and other technical parameters of the generators shall be based on the
mode of operation i.e. island mode or parallel operation with other generators or parallel operation with
third party feeders or any combination of these.
Where generators are being added to existing electrical systems, studies are required confirming
increased short circuit ratings are within the limits of existing equipment ratings.
Based on the application, the overload capacity, impact loading capacity, active and reactive power
sharing, speed variations, response time, reactance and inertia etc. shall be decided and indicated in the
project addendum specification and data sheets..
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 26/88
Occidental Petroleum of Qatar Ltd Page 26 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
The generators shall be provided with the following controls:
• Manual and automatic synchronising with a check synchronising relay and a dead bus-bar
override
• Manual and automatic voltage control
• Reactive power sharing among various generators
• Power factor control to keep the generator power factor constant when operating in parallel with
third party supplies
• Speed control with droop characteristic when operating in parallel with other sets
• Isochronous control in island operation
Details of controls, metering, alarms and indications shall comply with requirements of QP Engineering
Standard for HV Gas Turbine Driven Synchronous Generators ES.2.14.0001 unless otherwise stated ondata sheets.
Each generator set shall normally be provided with its own LV auxiliary switchboard for supply and control
of all its motor driven auxiliaries. For new installations this switchboard shall be treated as an emergency
switchboard and shall be provided with an essential supplies feeder (derived from the emergency
switchboard). Generator LV auxiliary switchboard supply arrangements for existing installations shall be
determined case by case and approved by OPQL TA.
For installations having captive power generation only, appropriate black-starting requirements shall be
provided for the facility (this can be either HV or LV). Requirements for dual fuelling of GT’s shall be
considered in conjunction with other platform constraints. It is noted that reliability of dual fuelled
equipment is often inadequate. This shall be duly considered when specifying and selecting equipment.
Diesel Engine Driven Generators
Offshore diesel fuelling costs are a significant operating expense and diesel fuelled gensets should only
considered for temporary platform power plant, standby systems or for base load plant where a reliable
gas supply is unavailable.
These Generators shall comply with the requirements of QP Engineering Standard for Diesel Engine
Driven Generators ES.2.14.0002 and associated data sheets (ES.2.13.0002). Engineering contractor
shall prepare project specific data sheets prior to tendering this equipment. The Diesel Engine Driven
Generators shall be procured as a self-contained complete package along with Diesel Engine and shall
be subject to any of the following applications:
• Standby or Essential/Emergency Operation
• Black Start Facility
• Base Load Power Generation
The package shall be complete with AVR, Generator Control Panel and Generator Breaker. The
Generator Control Panel shall contain AVR controls, metering, indications, annunciations and protective
relays for the generator. The generating set shall be hooked-up to the switchboard through the incomer
circuit breaker in the switchboard. Additional local breaker near to the generator shall be provided in
those cases where the generating set is located away from the switchboard to which it is hooked-up and
local isolation is essential.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 27/88
Occidental Petroleum of Qatar Ltd Page 27 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Necessary hardware for automatic mains failure detection shall also be provided for Standby/Emergency
Generators.
Generators supplied for emergency power should have their own self contained (preferably gravity feed)
diesel fuel storage suitable for 8hrs continuous running on emergency power. There should be sufficient
diesel storage capacity on the platform to provide a total of 24hrs operation of the emergency power
system. The diesel fuel transfer system (to the emergency generator fuel storage tank) should be
functional when platform is operating on emergency power. Refer also to QP-PHL-S-001 Corporate
Philosophy for Fire and safety, section 14; Emergency Power Supply System.
Generators used to provide electrical power to firewater pumps shall comply with the requirements of
NFPA 20. Engine staring systems in particular require special consideration. Protection systems are
normally inoperative when running under duty conditions and NFPA 20 compliant sets are configured as
“run to destruction” thereby protecting the primary asset.
Generators of sizes up to 1250 kVA shall be supplied at LV. Above 1250kVA, generators shall normallybe HV.
Generators shall normally be air-cooled. Use of water-cooled generators shall be subject to approval by
OPQL.
The emergency generators shall feed the following loads:
• Electrical loads essential for safe shutdown of the plant and personnel safety
• Emergency lighting
• Plant instruments, as applicable
• Communication equipment
• Fire and gas detection system
• Vital UPS system battery chargers ( AC and DC)
• Fire fighting equipment
• Helicopter landing area perimeter and obstacle lighting
Motor starting requirements and black-start load sequencing shall be duly considered when sizing of
generators. The generators shall be sized to have at least 10% spare capacity for future load growth at
the maximum operating temperature, net of auxiliaries after considering all other factors.
The facility shall be provided for synchronisation with normal supplies to enable full load testing of the
emergency generators without operational disturbance.
3.2. Neutr a l Eart h in g Resis to rs
The neutral earthing resistor shall comply with the requirements of QP Engineering Standard
ES.2.14.0085. The NER shall be housed in a sheet metal enclosure and shall be naturally ventilated.
The resistance elements shall be made of stainless steel alloy in a grid formation unless otherwise stated
on the data sheets. NER’s shall be rated to withstand the specified fault current for minimum 10 seconds.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 28/88
Occidental Petroleum of Qatar Ltd Page 28 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
3.3. Swi tchgear
General
Switchgear shall be of the compartmentalised metal clad type design to minimise any risk of developing ashort-circuit or the non-contained propagation of a short-circuit. It shall ensure personnel and operational
safety during all operating conditions, inspections and maintenance. The connection of main, control and
auxiliary cables and the equipping and commissioning of spare panels whilst the switchgear is live and in
operation shall be possible.
All switchboard components e.g. circuit breakers, main horizontal and vertical bus bars, bus bar joints,
bus bar supports etc. shall be designed to withstand the maximum expected short circuit level for a
minimum time of 1 sec.
All switchgear and associated equipment fed from generators and transformers shall be rated at least
125% of the rating of maximum number of generators and/or transformers (ONAF) simultaneously
feeding it including future expansions. The bus-section circuit breaker shall have rating equal to that of
the rating of the largest incomer circuit breaker.
Local operation of high energy potential equipment is discouraged. All HV switchboards shall have
facilities for remote operation. LV switchgear incoming, bus section and large outgoing feeders shall also
have remote operation facilities.
The application of intelligent switchgear and multifunction microprocessor based numerical protection
systems, in combination with electrical network control shall be considered the norm for all new
installations. Automatic protective systems shall be designed to achieve selective isolation of faulted
equipment with minimum delay. In any event this shall be within a time corresponding to the short circuit
current withstand capability of equipment, system stability limits and the maximum fault clearance times.
Adequate and selective phase short circuit and earth fault protection shall be provided, due regard being
given to the magnitude of short circuit currents and method of system earthing. The type and
characteristics of protective devices shall be selected according to application and shall be compatible
with existing platform facilities wherever possible.
Unless otherwise specified, unrestricted overcurrent protective devices shall have IDMT characteristics in
accordance with IEC 60255.
All signal interface requirements shall be as identified within section 2.5. Interposing relays shall be
provided as noted.
HV Switchgear
HV switchgear shall be in accordance with the requirements of QP Engineering Standard ES.2.14.0010.
The use of SF6 (Sulphur Hexafluoride) circuit breakers within switchgear is discouraged for environmental
reasons except where clear overriding technical advantages can be demonstrated.
Contactors used in motor starters shall have AC3 utilisation category as per IEC 60947.
HV switchgear and controlgear shall be of withdrawable type.
LV Switchgear
LV switchgear shall be in accordance with the requirements of QP Engineering Standard ES.2.14.0015.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 29/88
Occidental Petroleum of Qatar Ltd Page 29 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Components of LV switchgear shall be standardised as much as possible and selected in accordance
with the current ratings.
Back-to-back design or double front design of LV switchgear shall not be considered unless floor space is
restricted, preventing the installation of single fronted equipment.
All LV switchgear incomers shall be provided with breakers/isolators. The choice of incoming isolation
shall be as per Data Sheet.
LV switchgear and controlgear shall be of withdrawable type. Equipment to be typically Form 4, type 5,
however Form 4, type 4 may be acceptable. To be agreed with OPQL TA on a case by case basis.
Configuration of Switchboards
For all main switchboards, the number of sections shall be two, with each bus-section having a 100%
rated incoming circuit.
For interruptible, maintained supplies to essential and emergency services, a separate switchboard
should be provided. The normal feeder to this switchboard shall be derived from the mains power system
and the standby circuit from an emergency diesel generating set. An automatic changeover system shall
be provided to changeover to the standby circuit in case of mains failure.
Duplicate (double) bus-bar arrangements are occasionally required for the principal high voltage
switchboards in a plant, e.g. main generation switchboards or intake stations. Their use shall be justified
on the basis of requirements of very high availability. Duplicate (double) bus-bar systems are not
normally be considered for offshore applications.
For non essential loads, and remote installations supplied by subsea cables, switchgear with a single
100% rated incoming section can be considered.
Operating Philosophy of HV and LV Switchboards
The requirements for controls and interlocks will influence the physical size of some circuit breaker and
contactor cubicles. This shall be taken into account in the sizing and layout of switchgear as a whole unit
and in the interchangeability of individual units, trays and trucks. Details to be included on project data
sheets.
In the majority of plants, the normal operating position of switchboard incoming and bus section circuit
breakers shall be as follows:
• For the upstream HV switchboards the bus-section circuit breakers shall be operated normally
closed on switchboards at intake stations, generation stations and distribution stations.
• For downstream HV and LV switchboards the bus-section circuit breakers shall be operated
normally open. When a section of bus bars or a feeder transformer is being taken out of service,
the normal operation of the bus-section circuit breakers shall be a manual function, carried out for
the purposes of maintenance or restoration of supplies following fault on an incoming feeder.
The configuration of intake, power plant and distribution switchboards shall permit one section of the
switchboard to be taken out of service while still maintaining the normal plant operations. Operational
loads shall be distributed on opposite sides of the board.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 30/88
Occidental Petroleum of Qatar Ltd Page 30 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Spare Cubicles
HV switchboards shall have at least two spare outgoing cubicles on each busbar section. The type and
rating of the spare cubicles shall be decided based on the type and rating of feeders provided in the HV
Switchgear. All spare cubicles shall be fully equipped.
LV switchboards shall have spare cubicles, for future installation of additional outgoing circuits equivalent
to approximately 30% of the number of circuits initially utilised. Unless otherwise shown on the data
sheets, there shall be a minimum of two circuits of each size and type of consumer (e.g. outgoing static
feeder, outgoing motor feeder). Spare cubicles shall be fully equipped. Cubicles in excess of 30% can
be semi-equipped.
Choice of 3-pole and 4-pole LV Circuit Breaker
The neutral circuit of each transformer and generator incomer shall be connected to the earth bus-bar by
bolted links so that the connection is physically located on the busbar side of the neutral earthing facility.
This isolating facility shall be either a bolted link or one of the poles of a 4-pole circuit breaker. All earth
links shall be labelled 'neutral earth link'. Provision shall be made for the installation of CT’s on each
incoming neutral connection, both before and after the point where it is earthed, and on the connections
to the earth busbar.
Ring-main Units (RMU’s)
The use of RMU’s can be considered for simple radial feeder distribution switchgear typically supplying
remote unmanned facilities powered from host platform (PS1). Refer to YPS1-4-SP-6928 RMU
Specification and also to Technical Note YPS1-4-TN-6920-001 Comparison of HV Switchgear and Ring
Main Units for further guidance.
The use of RMU’s in their original application (i.e. as ring feeders distributing power to load centres) has
limited application offshore compared to conventional HV switchgear. OPQL TA should be consulted
before seriously considering this application to OPQL managed facilities.
3.4 . Busbar Duc t ing
Bus-bar ducting shall comply with the requirements of QP Engineering Standard ES.2.14.0019.
For LV systems where the current rating exceeds 1600 Amp, interconnection of equipment the use of
bus-ducting should be evaluated compared to the use of cables. Where used, the continuous and short-
circuit rating of bus-bar ducting shall be same as that of the switchgear, transformers and generators to
which these are connected.
In HV systems, decision of using bus-bar ducting shall be based on the number of cables used for
interconnection of equipment. Where the number of cables required is more than three per phase, the
use of bus-ducting should be evaluated compared to the use of cables.
3.5 . Power t rans fo r mers
The transformers shall comply with the requirements specified in QP Engineering Standards for Liquid
Filled Power Transformers ES.2.14.0020 and Dry-Type Power Transformers ES.2.14.0022.
The transformers for outdoor use shall be oil filled type. Sealed type transformers shall be specified for
ratings less than 5 MVA. Transformers 5 MVA and above shall be provided with membrane type splitconservator.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 31/88
Occidental Petroleum of Qatar Ltd Page 31 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Transformers are no longer manufactured with Poly-Chlorinated Biphenyls (PCB’s), however this remains
an industry wide concern and it is prudent to request a certificate from the manufacturer stating that the
transformers are free of PCB’s.
Insulation liquid for offshore transformers shall be an environmentally friendly less-flammable liquid. The
Vendor shall preferably use a biodegradable fluid as the insulating liquid. Examples of biodegradable
fluids, manufactured from vegetable oil, classified as less-flammable available are:
• BIOTEMP®
• ENVIROTEMP® FR3™
• MIDEL 7131
Where biodegradable insulation oils are used, then bunding (for environmental containment purposes) is
not required.
For increased fire risk locations and indoor installations and where transformers are an integral part of a
switchboard, a VSD’s line-up of cubicles or a large UPS, dry-type transformer shall be used. Their
maximum rating should be up to 2.5 MVA.
The transformer rated duty shall be selected as at least 100% of the nominal continuous running kVA as
calculated in the Electrical Load Schedule for the short-term situation. Short term in this context relates to
the time duration of the project engineering and a few years after the plant is commissioned. In the case
of doubly fed switchboards each transformer shall be sized on the assumption that it is taking the entire
load on the switchboard, i.e. one feeder is out of service and the bus-bar section circuit breaker is closed.
Voltage regulation considerations shall also be taken into account when sizing transformers as there may
be a requirement to oversize the transformer to maintain satisfactory voltage tolerances.
It is also necessary to cater for long-term plant extension requirements. At least a 25% margin shall be
added to the rated duty to obtain the highest rated duty for continuous running. This margin shall be
obtained from forced air-cooling by attaching fans at a later stage. The fan fixings shall be incorporated in
the initial purchasing of the transformers. The cables, bus-bar ducting and switchgear in the primary and
secondary circuits of the transformer shall be sized initially for the currents corresponding to the highest
rated duty. The overload settings of the protection relays in these circuits shall be initially set to match the
rated duty, and only increased when the fans are added.
In accordance with IEC 60076, the transformer kVA rating refers to maximum secondary current and to
no-load voltage, not system voltage.
Consideration shall be given to provision of on load tap changers on intake transformers fed from thirdparty power sources.
Transformers equipped with a manual or automatic on-load tap changer shall have a separate switching
compartment so that the oil can be independently sampled and filtered during operation. All tappings
shall be on the highest voltage winding.
The automatic on-load tap changers of transformers working in parallel shall each have selective facilities
for independent, master and slave operation.
The percentage impedance of the transformers shall be as per IEC 60076, unless otherwise a different
value is specified from the considerations of short circuit and voltage drop during motor start up.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 32/88
Occidental Petroleum of Qatar Ltd Page 32 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
3.6. UPS Syst ems
System Autonomy
System autonomy shall normally be a minimum of 60 minutes in accordance with QP-PHL-S-001 QPCorporate Philosophy for Fire and Safety. Operational considerations may require a greater autonomy
period; however by their very nature such UPS systems will require very large battery banks. Autonomy
should be kept within reasonable limits consistent with maintaining vital supplies for safe operation and
shutdown of process plant following interruption of normal power.
AC UPS System
An AC UPS system shall be provided for vital supplies, continuous process loads and instrumentation
system requiring an uninterruptible maintained AC supply. The preferred voltage is 110v ac, single
phase. Other voltages (and 3 phase systems) may be required. Please refer to OPQL TA for guidance in
these matters. AC UPS systems shall comply with the requirements of QP Engineering Standard
ES.2.14.0040. The following loads are typically connected to the AC UPS system:
• DCS system
• ESD system
• Fire and gas system
• Local panels for critical packages
• Analyser room instruments
• Metering station instruments
• Annunciation panel
• PA/GA system
The configuration of UPS System, e.g. redundant, stand-by redundant, parallel redundant, will depend
upon the function of its consumers. For all configurations of the UPS System, 2 x 100% rated rectified
charger/inverter units with 2 x 50% rated back-up battery banks shall be provided. The UPS system shall
also be provided with stabilised static and maintenance bypass.
AC UPS systems shall be sized to take care of the crest factor of the load current. It is recommended
that a 10% margin in capacity be kept for future requirements. The UPS Distribution Board shall have at
least 20% spare outgoing feeders for future use. The largest outgoing feeder load shall not exceed 25%
of the AC UPS System rating.
DC UPS System
A DC UPS system shall be provided for vital supplies, continuous process loads and instrumentation
system requiring an uninterruptible maintained DC supply. The preferred voltages are 24v and 110v DC.
Other voltages may be required as determined by characteristics of the supplied equipment. Please refer
to OPQL TA for guidance in these matters. DC UPS systems shall comply with the requirements of QP
Engineering Standard ES.2.14.0044. The DC UPS system shall be provided to feed the following:
• Switchgear control
• Critical lighting and navigational aids
• DC motors, (as in GT emergency lube oil systems and diesel engine starting systems)
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 33/88
Occidental Petroleum of Qatar Ltd Page 33 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
• Telephone system
• Fire alarm system
• Communication equipment
• Solenoid valves
• Telecom
• SCADA
The DC UPS system shall comply with the requirements of QP Engineering Standard ES.2.14.0044. The
DC UPS system shall typically comprise 2 x 100% rated rectified charger units and 2 x 50% rated back-up
battery banks.
It is recommended that a 10% margin in the capacity shall be provided for future requirements. DC
Distribution Board shall have at least 20% spare outgoing feeders for future use.
Batteries
Batteries shall be of adequate capacity to meet the back-up requirements for the required duty cycle and
to take care of future load margin of 10%. While sizing the batteries, temperature correction factor and
ageing factor shall be duly considered.
For both AC UPS and DC UPS systems, Ni-Cd batteries shall be specified. These should be past gel,
sealed for life type. Lead acid batteries are acceptable for engine starting applications.
In exceptional conditions (where space is a constraint), valve regulated lead-acid (VRLA) batteries with
absorbed electrolyte in a micro porous structure may be accepted. In such installations, close control of
working temperature is essential. Please refer to OPQL TA for guidance before specifying VRLA
batteries.
3.7 . E lec t r ic Motors
Asynchronous (Squirrel cage) induction motors shall be specified on account of their robust construction
and lower capital cost. Synchronous motors of the same rating as squirrel cage induction motors are
more efficient but have higher capital cost. For applications where power factor compensation is
beneficial and cost permits, synchronous motors may be used. This section is not applicable to motors
for downhole pumping applications (ESP’s). These are considered elsewhere within this BoD.
LV induction motors shall comply with the requirements of QP Engineering Standard ES.2.14.0035. HVinduction and synchronous motors shall comply with the requirements of QP Engineering Standard
ES.2.14.0030. The purpose of the driven equipment shall be considered when sizing motors and the
appropriate de-rating factors applied (typically a 10% margin is required). All motors shall be rated for
continuous duty except for cranes/hoists/engine starting which may be rated for the envisaged duty cycle.
All motors shall be designed for Direct On Line starting unless otherwise other methods of reduced
voltage starting are specifically mentioned.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 34/88
Occidental Petroleum of Qatar Ltd Page 34 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
The recommended power ratings of electric motors in relation to system voltages are:
Motor Rating System Voltage
Up to 132kW 415v
132kW to 185kW 415v or 3300v (HV preferred)
185kW to 1000kW 3300v or 6600v
1000kW to 4000kW 6600v or 11000v
Above 4000kW 11000v
The above limits are a guide and there may be instances where larger machines may be justifiable.Conversely, care should be exercised when specifying motors at the upper limits of their voltage range as
starting currents may cause excessive voltage depression on starting. Switchgear circuit breaker
limitations may also be an issue and shall be finalized prior to selecting voltage rating and supply source.
It is recommended that all motors above 30kW be provided with anti-condensation heaters. Integrated
Motor Control Systems (IMCS) which are micro-processor controlled motor starters and with additional
drive monitoring, protection features and self-diagnostic and communication facilities shall be considered
for new installations.
The use of DC motors shall be limited to special applications; for example emergency lube oil pump
motors on large rotating equipment, engine starting systems etc.
3.8. Cabl es, Wires and Suppo rt s
All cables used on OPQL managed facilities shall be specified and selected in accordance with the
requirements of OPQL General Cable Specification, Document 000000-4-XPS1-SP-0001-001.
Cable types H1 and H2 are suitable for 1900/3300V but specification of these is discouraged for reasons
of standardisation and HV cables should normally be specified and selected from H3 and H4 ranges
(6350/11000V).
Cable support systems shall be specified and selected from manufacturers GRP product ranges.
Galvanised systems are not acceptable. Cable trays shall be perforated and ventilated with the holesoccupying 30% or more of the tray area. This is required to satisfy “freely ventilated” criteria as detailed
within IEC 60092, Annex A, Installation methods E or F. Refer to Appendix C for more detailed guidance
concerning selection and specification of these items.
Switchroom and equipment plant room ceiling grid support systems shall be selected from Oglaend,
Norway product range (or approved equivalents).
OPQL carry stocks of commonly used cables, cable racking, trays etc. Engineering contractors are
required to verify and use items from OPQL stock lists wherever it is feasible to do so.
Refer also to section 4.1 for cable design and application details.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 35/88
Occidental Petroleum of Qatar Ltd Page 35 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
3.9 . Meter ing , Pro tec t ion and Cont ro l equ ipment
The electrical system shall be specified as equipped with adequate controls, metering, alarms and
indications for checking, monitoring and control of the power system. Metering shall be provided to keep
a record of power consumption and measurement of current, voltage, power, frequency, power factor etc.
The electrical system shall be equipped with automatic protection which shall provide safeguards in the
event of electrical equipment failures or system mal-operation. The selection and specification of
switching and protective devices, control circuits and associated auxiliary equipment shall be in
accordance with the respective GT gensets, HV and LV switchgear specifications. This shall normally be
included within the packaged equipment scope of supply.
3.10. Power Management Systems
A dedicated Power Management System (PMS) for the electrical generation and distribution system shall
be specified for all larger networks and where centralised supervision, control and metering is required.This system shall comply with the requirements of QP Engineering Standard for Power Management
System ES.2.14.0065. The requirements of OPQL Specification for Power Management Systems,
document No. 403086-4-PS1E-SP-0002-001 shall also be taken into consideration. Refer to section 2.4
for further details.
3.11. Packaged Equip ment
The engineering contractor shall prepare a project specific specification and data sheets outlining specific
requirements for the packaged equipment. The equipment shall be in general compliance with the
following documents with exceptions as noted:
EFS.00.08.05 – QP General Specification for Packaged Equipment
The above document outlines the general requirements for design, manufacture, testing and
commissioning of packaged equipment.
EFS.00.08.05 – QP Electrical Requirements for Packaged Equipment
The above document outlines the electrical requirements for design, manufacture, testing and
commissioning of packaged equipment. The voltage levels specified within this document are not
relevant to most of OPQL managed facilities. Please refer to section 2.8 of this BoD for further details.
000000-4-XPS1-BD-0001-001 – Electrical Basis of Design
All electrical bulk materials and minor equipment shall be selected in accordance with Appendix C of the
above document. It should be noted that all cable racking and supports shall be GRP. The package
system voltages, frequency and power factor shall be compatible with platform systems defined within
section 2.8 of the above document.
000000-4-XPS1-SP-0001-001 - OPQL General Cable Specif ication
All package cabling requirements shall be in accordance with the above document.
HES-027 - Lifting Equipment Control and Operations Policy
All lifting devices and aids on all equipment shall comply with requirements defined within the above
document.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 36/88
Occidental Petroleum of Qatar Ltd Page 36 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
3.12. Var iab le Speed Dr i ves and ESP’s
Where instructed, the engineering contractor shall prepare project specific specifications and data sheets
for this equipment. The specification for a VSD shall include all responsibilities, design activities,
materials, requirements, tests, documentations, instructions, and be reviewed by electrical, instruments,
drilling, process and artificial lift specialists prior to issue for tender. ESP Package Specification YPS1-4-
SP-6922-001 and associated datasheets is indicative of what is required and shall be used for guidance.
The purchase order of a VSD shall make provision for include start up assistance but not the site
installation, installation materials and downhole cables. The manufacturer shall confirm capabilities (and
where support is based) within his quote.
OPQL have supply agreements with some ESP service providers and preparation of equipment
specifications for some equipment is not always necessary.
Where deemed necessary by one of the parties involved, a pre-ordering meeting shall be arranged to
define clearly the scope, individual responsibilities, test methods and documentation requirements.
Attendance of all disciplines, including downhole and artificial lift specialist is recommended.
To avoid incompatibility issues, the various components which comprise an electrical Variable Speed
Drive System shall normally be purchased as a complete package from a single supplier. The scope of
supply of such a package will typically include the following items:
• Specialist design services for ESP package to suit specified performance and interface
requirements
• Variable speed drive unit, direct-on-line or soft starter
•
Active or passive harmonic filter
• Transient voltage surge suppressor
• Surface termination and interface panel for downhole instrumentation (may be part of VSD)
• ESP HV step-down transformer (multi-tap or dual winding as required)
• ESP HV step-up transformer
• ESP Wellhead HV terminations junction box (EEx certified)
• Wellhead outlet and cable to surface junction box
• Downhole pump string (typically comprising, downhole pumps, seal systems, motors, instrument
monitoring for pressure, temp and pump/motor protection, terminations)
• Downhole cable and clamps
• Spare parts, consumables and specialist tools
It should be noted that OPQL require purchase of 50% back-up for all downhole equipment (including
downhole cable). This is to avoid rig downtime in event of equipment damage.
Engineering contractors should take care when specifying control interfaces to avoid protocol
mismatches. Historically, there have been several instances where this has occurred. All ESP
equipment shall have remote start and monitoring capability.
Well fluid properties (e.g. presence of H2S) shall be taken into account when specifying all downhole
equipment and components.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 37/88
Occidental Petroleum of Qatar Ltd Page 37 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
3.13. HVAC Syst ems
The HVAC equipment requirements shall be identified and specified by the engineering contractor within
a Functional Requirements Specification and associated data sheets. This specification shall include a
clause excluding the use of Ozone depleting refrigerants. Standard industrial HVAC equipment should be
used wherever it is feasible to do so. HVAC systems can be specified as supplied by manufacturers as
single components or integrated into packaged units and will typically include the following equipment as
appropriate:
• Air Handling Units (AHU’s)
• Chilled Water Units (Compressor type)
• Chilled Water Units (Direct expansion type)
• Humidifiers and Dehumidifiers
• Duct air heaters
• Mechanical ventilation systems and fans
• Sound attenuators
• Inlet air filters/coalescers
• Fire and gas air shut off dampers, and weather louvers
• Internal and external ductwork and air terminal boxes
• HVAC control systems
3.14. Nav igat io nal A id s
Marine Navigational Aids
Marine and air navigational aids are required for all OPQL mobile and fixed offshore installations. These
shall generally comply with the requirements of QP Engineering Standard for Navigational Aids
ES.2.14.0003 unless otherwise stated. Refer also to OPQL Phase 3 Marine Navigational Aids
Specification YPS1-4-SP-6927-001. These shall comprise the following:
• Main lights
• Secondary lights
• Subsidiary lights
• Fog signals
• Secondary fog signals
• Underdeck illumination of legs, risers and conductors
An alarm for the failure of main lights and fog signals shall be provided in the DCS system to give a
warning to the operator. These alarms shall also be provided for satellite platforms, structures and
unmanned installations.
Navigational Aids shall be capable of performing independently within the parameters specified in ProjectDatasheets and conform to International Association of Marine Aids to Navigation and Lighthouse
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 38/88
Occidental Petroleum of Qatar Ltd Page 38 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Authorities (IALA) O-114 standard requirements. All equipment and components shall preferably be of
the Vendor’s standard product line.
Marine Navigational Aids shall be equipped with batteries having ninety six (96) hours autonomy time.
Where 96 hours cannot be achieved the Vendor shall nominate the maximum capacity available. The
batteries shall be charged through on-board solar panels and/or battery chargers as detailed within the
data sheets.
Marine navigational aid lanterns shall preferably incorporate LED's and shall be of the omni-directional
type, emitting a white light as an aid to shipping. Marine navigational aid lanterns shall have an apparent
intensity of not less than 1400 candelas in any horizontal direction and shall be visible for a distance of
not less than 10 km from all points more than 5 metres above sea level, when the visibility is not less than
10 km. If this is not attainable with LED’s the Vendor shall recommend what intensity and range is
available.
Where LED’s are not available, the vendor may as an alternative, offer lamps. If lamps are offered, eachlantern shall be fitted with an automatic, six position lamp changing facility to achieve a minimum of 6000
burning hours. The lamp changer shall be automatically deactivated if no serviceable lamps are available
and, where specified on the data sheets shall activate contacts for a remote alarm. The lamp changer
shall have reverse polarity protection and shall include provision for lamp filament focusing.
Each lantern shall show the letter “U” in Morse code at intervals of not more than 15 seconds. Where
more than one lantern is installed on a platform, synchronization (GPS synch preferred) shall be provided
to ensure that all lanterns simultaneously flash the specified characteristic code. Failure or malfunction of
one or more lights shall not interfere with the operation of the remaining lights.
Each Navigational Aids lantern shall contain an integral photocell to control lantern operation. Photocell
failure shall result in the lantern operating.
Lanterns shall be free standing with provision for fixing directly to the platform steel work. The mounting
hardware shall include three bolt self leveling hardware, washers and self locking nuts, complete with ISO
metric threads.
The lanterns shall be equipped with 360° clear acrylic lenses fitted with bird spikes.
Helideck Perimeter and Obstruction Ligh ting
The helicopter landing area on all offshore platforms and structures shall be provided with perimeter
lighting, comprising alternate omni-directional yellow and blue lights. The lights shall not be below the
level of the deck and shall not exceed a height of 0.125 metres above the deck. The lights shall be
spaced at interval of 3m around the perimeter. Helideck lighting shall conform to the latest edition of CAA
CAP 437.
Tall structures, stacks, columns and tall vessels etc. shall be provided with obstacle lights and/or markers
as per the guidelines of International Civil Aviation Organisation. The obstacle lights shall be provided on
the top most level of the structure. Where it is not practical e.g. flare tower tips, these lights shall be
provided at a lower level with suitable heat shields based on radiation calculations.
For offshore installations, obstacle lights shall be installed at suitable locations to provide the helicopter
pilot with visual information on the proximity and height of objects which exceed the height of landing area
and are close to landing area.
Obstacle lights shall be connected to emergency power supply.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 39/88
Occidental Petroleum of Qatar Ltd Page 39 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
It is prudent to seek the guidance of the Chief Pilot, helicopter operations (Gulf Helicopters at time of
writing) concerning changes/additions to all helideck and obstruction lighting.
3.15. Cathod i c Pro tec t ion Sys tems
Cathodic protection is an electrochemical technique for preventing corrosion of buried or immersed
metalwork to an electrolytic media surrounding the metal. This can be achieved either by sacrificial
means or by applying DC current to the metal surface by external power supply source. The preferred
means of cathodic protection is to protect against corrosion by the use of sacrificial anodes.
The cathodic protection shall be provided for underground pipelines, tank internals, tank bottoms,
submerged pipelines, offshore steel structures etc. The cathodic protection system shall be designed and
installed as per the guidelines of QP Engineering Standard ES.2.14.0045.
3.16. Electr i c Process Heaters
Electric process heaters shall comply with the requirements of QP Engineering Standard for Electrical
Process Heaters ES.2.14.0005. General guidance is also provided within OPQL Specification No.
410924-8-PS1E-SP-0001-001; Glycol Re-boiler Electric Heater Skid.
The heaters shall be either contactor controlled having on/off facility or thyristor controlled as per process
requirements. For thyristor-controlled heaters, the power of each heater shall be controlled by firing of
thyristors according to zero-crossover mode i.e. where the voltage or current is zero.
Over-temperature protection for the heaters and the thyristor control panel, heater protection for low
flow/low level and earth leakage protection device in the power supply circuit shall be provided.
3.17. Electr i c Motor Operated Valve Act uator s
Electric Motor Operated Valve actuators (MOV’s) shall generally comply with the requirements of QP
Engineering Standard ES.2.14.0036. These shall be provided with integral starters. The necessary
local/remote selector switches, start/stop switches or push buttons, torque limit switches etc. shall be
provided on the actuator for local and remote control depending on the mode of selection. Failure of the
torque limit switches shall not cause any damage to the actuator motor.
The valves to be actuated with electric motor shall be identified by Process Department and shown on the
P&ID’s.
3.18. Electr i ca l Heat Trac ing
Electrical heat tracing systems shall comply with the requirements of QP Engineering Standard for
Electrical Heat Tracing ES.2.14.0004. The system shall be ordered as a packaged unit including design,
supply of tracers and cables, installation at site and all necessary control auxiliaries. In all cases where
electric heating is applied, each circuit shall be fitted with earth leakage protection devices in accordance
with hazardous area regulations.
3.19. L igh t ing , Smal l Power , Bu lks and Minor Equ ipment
For smaller projects, equipment should be selected compatible with existing platform equipment. Refer to
section 2.0 “Standardisation of Equipment and Materials” for further details. Please also refer to
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 40/88
Occidental Petroleum of Qatar Ltd Page 40 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Appendix C for guidance concerning specification of commonly used electrical bulk items and minor
equipment.
The use of incandescent lighting is no longer acceptable on OPQL managed facilities and should not be
specified.
3.20. D is t r ib u t io n Boards
Distribution board schedules shall be prepared in OPQL approved standard format by the engineering
contractor. Wherever feasible, these shall be installed indoor in non-hazardous air conditioned
equipment rooms. Equipment shall be specified and selected from manufacturer’s standard product
range where compliant with the following:
• Equipment to be fully fault rated
•
Ingress protection of IP42 minimum (if placed indoors), otherwise IP56 minimum• Ingress protection (doors open) to be IP23 minimum
• Equipment to be fitted with an ammeter
• Cables to be bottom entry via removable gland-plates
Specifications and data sheets should be kept to a minimum consistent with documenting the project
requirements. The following OPQL specification and data sheets can be used for general guidance:
• 410641-4-PS1R-SP-0001-001 – Distribution board specification
• 410641-4-PS1R-DS-0001-001 – Distribution board data sheets
3.21. Subsea Cables and Umbi l ica ls
Subsea cables and umbilicals shall generally comply with requirements of ISND Phase 3 Water Injection
Subsea Cable Specification and datasheets, documents YPS1-4-SP-6923-001 and YPS1-4-DS-6923-
001. Subsea cable J tube armour clamps shall have a ventilated spool piece (or equivalent) to avoid
reductions in current carrying capacity within J tubes.
Prior to tendering, subsea cable lengths shall be calculated precisely based upon subsea routing
drawings. There shall be due allowance made for route length variance, seabed undulations, J tube
risers and repair contingencies. A template for subsea route length determination is given in example
calculation YPS1-4-CA-6924-001. Subsea cable length shall be reconfirmed immediately prior to orderplacement.
OPQL policy is for subsea cables to be installed direct on seabed without trenching. There are a large
number of subsea obstructions in vicinity of ISND structures, giving rise to free span crossings typically of
the order of 3 to 5m. Subsea cables and umbilicals shall be specified suitably armoured to provide
seabed stability and withstand unprotected free span crossings as noted.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 41/88
Occidental Petroleum of Qatar Ltd Page 41 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
4. EQUIPMENT INSTAL LA TION DESIGN REQUIREMENTS
4.0. General
The electrical installation shall conform to good working practice and be of a high quality and safety in
general accordance with QP Engineering Standard for Electrical Installation Recommended Practices
ES.2.06.0001.
The electrical equipment shall be installed in accordance with the installation instructions and supporting
drawings provided by the manufacturer of the respective equipment. The design of the electrical
installation shall ensure that satisfactory access is provided for all operational and maintenance purposes.
Minor field equipment shall generally be EEx certified and suitable for installation in hazardous areas.
Refer to section 2.1 for further details.
Temporary installation work, required during erection of permanent installations, shall also comply with
the basic rules of design and engineering.
4.1 . Cab les , Rout ing Cons idera t ions and Accessor i es
General
OPQL carry stocks of commonly used cables, cable racking, trays etc. Engineering contractors are
required to verify and use items from OPQL stock lists wherever it is feasible to do so.
All cables used on OPQL managed facilities shall be specified and selected in accordance with the
requirements of OPQL General Cable Specification, Document 000000-4-XPS1-SP-0001-001. Multi-core
cables shall be given preference to single core cables. It is permissible to use single core cables for
practical and economic reasons (as in large LV feeders).
Cable types H1 and H2 are suitable for 1900/3300V but specification of these is discouraged for reasons
of standardisation and HV cables should normally be specified and selected from H3 and H4 ranges
(6350/11000V).
Cables for general use shall be multi-core armoured. Unarmoured cables shall only be used where
cables are routed entirely within accommodation areas and terminated into uncertified electrical
equipment which is not part of a safety critical or vital service.
Cable Sizing Design Basis
The sizing of LV cables shall generally be in accordance with OPQL LV Cable sizing document YPS1-4-
CA-6921-001 (noting that this document is currently being revised to align with cable sizing criteria
specified below). This is based upon tabulated data within IEC 60092-352 (Electrical Installations in
Ships – Choice and installation of electrical cables). Refer to Appendix J for details. Where cables are
individually sized, this shall be on the following basis unless specifically agreed otherwise with OPQL TA:
• Cables shall be selected from Cable Specification, Document 000000-4-XPS1-SP-0001-001.
• An ambient air temperature of 45oC shall be used.
• A steady state aggregate maximum voltage drop limit of 6% shall be applied (normally a 2% limit
for feeders and 4% for the final sub circuit).
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 42/88
Occidental Petroleum of Qatar Ltd Page 42 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
• The maximum permissible voltage drop on motor starting shall be 15% with a starting/running
ratio of 6.5x (unless specific motor starting data is available).
• Tabulated current carrying capacities shall be in accordance with IEC 60092-352, Table A4,
Installation methods E, F or G.
• For LV cables, a cable installation grouping factor of 0.73 shall be applied (based upon a
maximum of 6 fully loaded cables, touching in accordance with IEC 60092-352, Table A6). In
general it is noted that cable installation grouping factors are conservative, given that most
offshore electrical systems function with 100% duty/standby basis and control cables carry very
little current. Thus heat dissipation in most instances will be well below that determined as worst
case by cable rating factors.
• For HV cables a cable installation grouping factor of 0.79 shall be applied, or if cables are
individually cleated (multicore) or in trefoil formation (single core) in accordance with IEC 60092-
352, Table A6 a grouping factor of 1.0 shall be applied.
• Cable impedances at a conductor operating temperature of 90oC shall be assumed.
• The short circuit conductor operating temperatures shall not exceed 250oC.
• The circuit design current to be based upon cable protective devices (short circuit, overload).
The tabulated current ratings within IEC 60092-352 assume the use of class 2 stranded high conductivity
copper conductors for fixed installations in accordance with IEC 60228 and are suitable for both HV and
LV cables. A 5% de-rating factor shall be applied where they are used for sizing HV cables unless
manufacturers tabulated ratings confirm otherwise.
Where class 5 conductors are used (flexible cables feeding mobile equipment), then manufacturerstabulated ratings shall be used or a suitable de-rating factor applied.
Cables carrying very large LV currents and all HV cables shall be individually sized. Temperature
excursions above 45oC are relatively infrequent and short duration and cable insulation is designed to
withstand short temperature excursions so an ambient temperature limit of 45oC is acceptable for
equipment specification and cable sizing purposes.
The following guidance is provided for equipment power factor (Cosø) and can be used in the absence of
specific manufacturer’s information:
• 0.8 for non motor feeders
• 0.58 to 0.9 for motor loads (size dependent)
• 0.3 for motor starting and fault calculations
Where engineering contractor wishes to use other sources of reference information for cable sizing, this
shall be agreed in advance with OPQL TA.
Battery cables and supply cables from battery backed systems shall be sized to take into account the
minimum voltage tolerance at end of discharge (this is typically 22.7V on a 24V DC system). Similarly,
field cables to solenoid valves etc. powered from 24V DC systems shall be verified as having a voltage
drop within the lowest voltage tolerance of the supplied equipment.
The detailed offshore environmental conditions to be applied are detailed within section 2.2 and voltage
drop considerations are detailed within section 2.7.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 43/88
Occidental Petroleum of Qatar Ltd Page 43 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
All power and control cables shall be in continuous lengths and cable joints shall be avoided wherever
possible. These will only be accepted in exceptional circumstances. Cable joints in hazardous area shall
not be permitted.
Cable routing and segregation
Offshore cables shall generally be routed on freely ventilated perforated cable racks in groups of no more
than 6 cables, bunched in a maximum of 1 layer (in accordance with IEC 60092-352, Annex A). Single
core cables pertaining to one 3 phase circuit shall be laid in trefoil formation. All cables shall be
adequately clipped. Cables carrying large currents shall have cleats spaced taking into account potential
fault currents. Adequate restraint is normally provided by clamps at 1m spacing on straight runs and
0.5m spacing on the bends; however the spacing shall be as calculated by the Contractor for the
applicable cable type and fault level. The fault level used for calculation shall be as per the rating of the
associated switchgear busbars, restricted by the largest fuse size possible (where appropriate). All trefoil
clamps shall be of an approved type tested design.
Instrument and telecommunication cables shall be routed on racks and trays segregated from HV and LV
power and control cables. For new installations (and wherever feasible in existing installations), HV and
LV cables shall be routed on separate racks and trays. For long continuous runs, there shall be adequate
separation between instrument and power cables to avoid signal interference.
Cable rack and tray support systems shall be specified and selected from manufacturers GRP product
ranges. Galvanised systems are not acceptable. Refer to Appendix C for more detailed guidance
concerning selection and specification of these items.
The minimum size for new external cable racks should be 200mm minimum and a minimum size for cable
trays of 150mm. Generally, new cable routes should allow a generous margin for future cabling
requirements (typically 25%). Judgement shall be applied however, and this shall be determined case by
case.
Cables shall be routed such as to minimize mechanical damage. Supplementary protection (kick plates,
removable rack covers, etc. shall be provided where necessary. Sun shielding shall be provided to
reduce effects of direct solar radiation.
Changes of direction in cable routes shall cater for the following minimum cable bending radii:
• LV cables: 10 times the cable OD
• HV cables (multi-core): 15 times the cable OD
• HV cable (single core): 20 times the cable OD
In all cases, the cable manufacturer's recommendations shall be adhered to.
Fibre optic cables or fibre optic cores in composite cables can be used for the transmission of signals and
data. Such cables shall be routed on trays and racks with other instrumentation cables.
All cables shall carry identification numbers (in an approved format) at each end.
Multi-cable Transit Penetrations
All bulkhead and deck penetrations, and where cables enter a pressurised room or shelter shall be
carried out using agreed proprietary multi-cable transits. Transit locations shall be logically designed
compatible with cable routing requirements (but kept to a minimum). The use of transits through roofs isto be avoided to reduce possibility of moisture ingress.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 44/88
Occidental Petroleum of Qatar Ltd Page 44 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
It is recommended that there is at least 50% spare capacity provided within transit frames on completion
of design. Transits shall always be used where cables pass:
• From a safe area to a hazardous area, separated by a gas-tight wall or barrier
• Through blast walls or fire walls
• Through solid decks
• Through walls and floors of enclosures or rooms to open areas
Care shall be taken during design (and installation) to continue the trefoil formation of single core AC
cables when passing through transits. Non-magnetic brass stay-plates are required within the transits
and each trefoil group shall pass through the same transit window.
Cables passing through transits shall be perpendicular to the transit for a minimum distance of 300mm on
each side of the transit. Suitable cable supports and fixings shall be applied to maintain the perpendicular
approach.
Cables routed in conduits
Wiring in conduits shall not be used in hazardous areas and is generally excluded in most offshore
applications except in specific circumstances (such as final droppers within non-hazardous equipment
rooms). Such installations shall comply with the requirements of BS7671 – Requirements for Electrical
Installations. Wires laid in conduits shall have minimum cross section area of 2.5mm² except for wiring
between a switch and a lighting fixture, when a minimum cross-section of 1.5mm² may be used.
For control wiring within panels, a minimum cross section of 1mm² may be used.
Cable Accessories and terminations
Cable glands shall be selected to suit the type of cable and termination box/enclosure and shall be of
appropriate type of protection for the hazardous area. Effective earth continuity shall be ensured between
the cable armour and the gland plate or the internal earth terminal. All LV terminations shall utilize cable
lugs. HV terminations shall normally be through heat shrinkable type termination kits, however for HV
motors and generators, the terminations shall utilize Elastimold/Bi-mold plug and socket connectors (or
other approved equivalent).
The armouring of multi-core cables shall be solidly earthed at both ends.
The armour and screen of single-core cables shall be earthed on one side. For longer cable lengths, due
attention shall be paid to open end voltages and consideration shall be given to the use of insulated
glands. The open end voltage shall not exceed 60V under full load rated current conditions and 430V
under maximum short circuit current conditions. Where packaged equipment requiring large single core
supply cables is required, guidance from manufacturers shall be taken into consideration. Single core
cables should be terminated using non-ferrous gland-plates.
All cables shall be terminated using approved cable glands, certified to match the equipment they are
glanded into. To avoid the use of non certified glands in hazardous areas, consideration shall be given to
standardising on certified glands only. This is not a mandatory requirement and shall be considered on a
project by project basis.
All cables and equipment shall be identified and tagged in accordance with OPQL DCC requirements.
Typically, projects (on request from DCC) will be allocated a block of cable and equipment tag numbers.This also includes temporary installations.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 45/88
Occidental Petroleum of Qatar Ltd Page 45 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
4.2 . L igh t ing and Smal l Power Ins ta l la t ions
General
Fluorescent lighting shall in general be used for area illumination. High-pressure sodium discharge lampsmay be used for practical and economic reasons in certain applications (e.g. compressor sheds,
underdeck lighting etc.) or large areas where colour rendering is unimportant. Where HP sodium lamps
are used, consideration shall also be given to providing supplementary fluorescent lighting to cater for re-
strike delays caused by momentary power failures.
Flood lighting shall be used for the open areas around process and production plants. High pressure
discharge lamps shall be used for flood lighting. Care shall be taken to avoid shadows in the working
areas and glare factor will require to be considered during the design. Low-pressure sodium lamps shall
not be used, as they constitute a fire hazard in the event of breakage.
All outdoor lighting shall be controlled by means of photoelectric cell with manual over riding control.
Where special requirements regarding colour distinction exist (for example laboratories), these shall be
met.
The use of incandescent lighting is not acceptable for any new installations on OPQL managed facilities.
Plant Lighting
Plant lighting shall comprise of following:
• Normal lighting
• Emergency (critical task) lighting
• Escape/Critical lighting
Normal and emergency lighting shall be fed by AC supply while escape/critical lighting shall be fed from
self-contained batteries. For hazardous areas, the preferred form of illumination shall be fluorescent
lamps with type of protection Ex-e. For standardisation purposes, the same type Ex-d or Ex-e lighting
fixtures should be used whether classified Zone-1 or Zone-2. Refer to Appendix C for details of preferred
equipment types.
If high-pressure discharge lamp fittings are needed in hazardous areas then they shall be of the Ex-d type
only. An isolating switch shall be included inside the fitting to prevent the light fitting from being energised
when it is not fully assembled.
Interior Lighting
Lighting fittings in closed buildings, which are classified as non-hazardous areas, such as offices, control
rooms, sub-stations, shall be fluorescent bi-pin, switch-start type, industrial or domestic type with high
frequency ballasts and power factor correction.
Illumination levels
Refer to Appendix E for recommended plant area illumination levels. This covers most (but not all)
situations. Please refer to OPQL TA for guidance if required.
Note that emergency lighting levels available are dependent upon the autonomy period of luminaires.
Most battery backed emergency luminaires are selectable to provide either 3hr or 1.5hr autonomy. The
light output with 3hr autonomy is approximately half that when selected for 1.5hrs. Generally, escape
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 46/88
Occidental Petroleum of Qatar Ltd Page 46 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
lighting shall be set for 3hr autonomy and emergency (task) lighting shall normally be set for a 1.5hr
period.
A light loss (maintenance) factor of 0.8 is recommended for lighting illumination level calculations for all
indoor areas. For outdoor areas subject to dirt etc, a lower factor shall be used, determined by
circumstances.
Power supply considerations
Plant lighting shall be fed from dedicated lighting distribution boards installed within switchrooms. The
use of outdoor distribution panels is discouraged. Plant lighting distribution boards shall include 20%
spare outgoing circuits. Distribution board schedules shall be prepared in OPQL standard format.
Templates are available from OPQL DCC on request.
Lighting circuits shall be arranged to give a balanced load across the three phases at the distribution
board. All lighting circuits shall be with double pole isolation facility. Plant lighting circuits shall be single-
phase (phase and neutral) and protected with maximum 16 A fuses or MCBs. Lighting circuits shall not
be loaded higher than 12A.
Adjacent lighting fittings shall not be supplied from the same circuit. Lighting fittings shall be mounted on
the available structures and shall be so located that maintenance and lamp changing can be effected
without the use of ladders and scaffolding. In tall buildings, such as compressor and turbo-generator
houses, maintenance and lamp changing should be possible by using the overhead crane. When no
structure is available to support lighting fittings, lighting poles of adequate height shall be used to support
the fluorescent lighting fittings.
Plant lighting circuits that are adequately served by natural light shall be designed for automatic switching
via photoelectric relays. Manual over-ride facilities shall be provided.
External plant areas shall normally be switched from the distribution board. Where boards are lockable,
then external switching facilities shall be considered.
Internal lighting of non-process buildings and sub-station buildings shall be switched from inside the
building. The lighting installation in the control rooms shall be designed to enable groups of ceiling lights
to be switched off by the operator. The lighting fixtures shall be situated in such a way that reflection on
instrument windows and displays is avoided. Depending on type of instruments installed, dimmers may
be required.
Emergency and Escape Lighting
Fixed emergency lighting shall be installed at strategic points in the installations, including control rooms,switchrooms, fire-fighting stations, emergency response muster points, first-aid rooms, the main
entrances and in all other buildings and areas where required for safety reasons.
The location and electrical arrangement shall be such that danger to personnel in the case of a power
failure is prevented, and escape routes are illuminated. The emergency lighting system shall normally
consist of self-powered emergency lighting fittings with power derived from the emergency generator.
In the case of emergency diesel generator supply, a number of lighting fittings in the control room and the
basement of the control room, as well as field auxiliary rooms, shall have lighting fittings with self-
contained batteries to avoid complete darkness during start-up time of the diesel generator. All battery
backed lighting fixtures on offshore platforms shall be suitable for Zone-1 hazardous area.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 47/88
Occidental Petroleum of Qatar Ltd Page 47 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
The number of emergency lighting fittings to be installed as a percentage of the total number of fittings
shall be determined as follows:
• Control room 50%
• Switchrooms 30%
• Generator area 30%
• Utility areas 20%
• Muster points 20%
• Process areas 10%
• Administrative areas 5%
Critical task lighting shall be installed above equipment required for black-starting facilities (emergency
generator control panels etc.).
For escape lighting, the lighting fixtures shall have self contained batteries rated to maintain the lighting
for at least 60 minutes. Escape lighting shall be provided in all buildings to illuminate the way for
personnel leaving the building along defined escape routes to defined muster points.
Special Lighting
Special lighting, e.g. navigation aids, obstruction warning lights and aircraft navigation lights, shall be
installed in accordance with national and international standards. Long life lamps at reduced voltage shall
be used. The installation shall be backed up by an emergency supply system.
The illumination of any areas to be observed by TV cameras shall be designed in particular with regard touniformity of the level of illumination as well as to the location of the individual lamp fittings. The
illumination level to be maintained shall be compatible with the camera system utilised.
Helideck lighting shall conform to the latest edition of CAA CAP 437.
Power and Convenience Outlets
For maintenance purposes, an adequate number of 3-phase power outlets for movable equipment and
single-phase convenience outlets for the supply of portable tools and hand lamps shall be provided at
suitable locations.
Power outlets shall be rated for at least 100A and be suitable for outdoor installation. They shall normally
be located in non hazardous areas. The outlets installed in existing installations shall be compatible withexisting equipment. Refer to Appendix C for further details.
Convenience outlets shall have a single-phase supply voltage equal to the voltage selected for normal
lighting. The outlets installed in existing installations shall be compatible with existing equipment. For
industrial areas the outlets shall be rated for 16 A suitable for outdoor installation and shall conform to the
hazardous area classification. These shall have necessary mechanical interlocks and earthing facility.
An adequate number of convenience outlets for hand lamps and portable tools shall be provided at
suitable locations.
Plugs shall not be interchangeable with sockets of different voltages or current ratings nor shall it be
possible to insert an industrial type plug into an outlet suitable of Zone-1/Zone-2 hazardous areas.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 48/88
Occidental Petroleum of Qatar Ltd Page 48 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
All power and convenience outlets shall be protected by means of short circuit protective devices and
current operated earth leakage protective devices i.e. residual current circuit breakers (RCCB). The
RCCB operating current shall be 30mA for circuits less than 100A rating and 300mA for circuits above
100A rating. The operating time shall not exceed 30 msec.
4.3 . Ear th i ng and Bond i ng
The primary purpose of the earthing system is to reduce and control voltages on equipment to an
acceptable level under abnormal conditions and provide a conductive path to earth for fault currents. A
secondary purpose is to eliminate any risk of sparking in hazardous areas due to voltages under
abnormal conditions. Such conditions include equipment faults, static electricity build up or lightning
strikes. This document covers
Please refer to Appendix D for the primary and secondary earthing requirements to be adopted on all
OPQL managed facilities. Engineering contractor shall comply with these requirements. Please refer toOPQL TA for guidance if required.
4.4. Major and Packaged equip ment i tems
Packaged equipment encompasses a large variety of equipment from small pump-sets with simple
interfaces to major packaged equipment with many interconnected systems. The emphasis shall always
be for the engineering contractor to ensure a fully integrated system design without unnecessary
duplication of vendor documentation.
All interfaces shall be identified, validated and incorporated into the overall design, including the following
commonly encountered items:
• Supply source compatibility (voltages, frequencies, current ratings).
• Cable rack and tray requirements (within skid and external to skid)
• Cable entry sizes, compatibility, glandplate accessibility, MCT locations, etc.
• Cable size compatibility (with terminations etc.).
• Skid limit junction boxes, termination panels
• Lighting and small power requirements
• Serial link and comms protocol compatibility
• Earthing and bonding
• Sun shading of critical equipment
• Hazardous area compatibility
• Electrical protection and discrimination
• Specialist commissioning requirements
• Maintenance routines and operations procedures
Cables to motors, starters, switchgear, heaters are normally routed direct to skid equipment. All
termination and interface points shall be identified.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 49/88
Occidental Petroleum of Qatar Ltd Page 49 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Each motor shall be provided with a Remote Control Unit (RCU) in the field near the motor for emergency
stopping purposes. This shall be provided by engineering contractor where it is not part of packaged
equipment design. Based on the control requirements, there may also be a requirement for local
start/stop push button, ammeter, auto/manual and local/remote selector switches, etc. Motors installed atelevated platforms shall be provided with additional RCU at ground level for stopping the motor.
Adequate interface information shall be included within engineering designs consistent with the above
(including drawing references etc.). The wholesale repeat of vendor design data on engineering design
contractor drawings shall be avoided. The vendor drawings and documents shall be included within work
packages where necessary and available.
4.5. ESP’s and Var i ab le Speed Dr iv es
General
There is a growing (industry wide) use of electric submersible pumps (ESP’s) for oil and water artificial lift.This means there are an increasingly diverse choice of equipment and technologies available both for
surface and downhole facilities. Engineering considerations to take into account when designing these
systems include:
• Minimizing the equipment requirements (and hence footprint) of surface facilities
• Provision of maximum future flexibility (as reservoir conditions can vary)
• Measures to ensure a reliable run life of downhole equipment
• Keeping system harmonics to a minimum (important when large loads are considered)
This BoD makes reference to equipment available at the time of writing and shall be considered togetherwith technology developments. A typical ESP installation will include permutations of the following:
Step Down Transformer
HV systems are normally transformed to LV due to limitations within the power electronics. Usually, there
are two secondary windings which provide a phase shift for a 12 pulse converter, thereby reducing
harmonics. These secondary windings can supply several ESP's with multiple converters via star-delta
distribution switchboards or directly supply a larger converter controlling a single ESP.
An alternative transformer configuration has multi-tap phase shifted secondary windings which can supply
up to four smaller ESP’s. This has the added advantage of eliminating the requirement for star-delta
distribution switchboards. It can also permit the use of 6 pulse converters, with harmonic cancellationthrough phase shifted secondary windings.
Variable Speed Drive
Variable speed drive power converters offer design and operational flexibility when compared to soft start
units. The drive frequency (and consequently power output) is variable over a wide range & this is an
advantage as downhole conditions can vary. The frequency ramp up control facility of a VSD offers a
soft-start capability.
These units are available in a number of ratings and configurations for both indoor and outdoor
applications. Indoor units offer space saving advantages over outdoor units but air conditioning
requirements due to heat dissipation can be significant. Protection and monitoring systems for ESP’s are
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 50/88
Occidental Petroleum of Qatar Ltd Page 50 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
normally included within the VSD and typically includes motor protection, current monitoring, winding
temperature, fluid temperature, etc.
The equipment shall be specified and configured for remote start, interfacing with DCS system (refer to
section 2.5). Remote start is particularly relevant where equipment is located on remote unmanned
facilities accessible only by boat or helicopter.
The input voltage ratings are typically 380V or 480V AC. Input voltages of 415V are available but with a
corresponding reduction in power output.
Technology within this area is changing and some manufacturers now offer a VSD with HV power
electronics, thus eliminating the requirement for a step down transformer.
Soft-Start Unit
There can be space and cost saving advantages by using soft starters in place of VSD’s. However this
has to be balanced against operational inflexibility once installed. Voltage depression studies based uponmotor characteristics may be required in such applications.
Direct on Line Starter
In some applications, direct on line starting can be considered as an option (and would eliminate the VSD
or soft-start unit). The use of DOL starting imposes additional stresses on downhole ESP’s (particularly
cable insulation) and for this reason equipment run life considerations require to be formalized with
manufacturer before DOL starting can be considered. DOL starting also has the same operational
inflexibility of soft-start units. Voltage depression studies based upon motor characteristics may be
required in such applications.
Step-up Transformer
The output from the VSD or soft start unit is transformed to HV to suit the requirements of the ESP
through the step up transformer.
Harmonic Filters
Where large non linear loads are proposed, consideration shall be given to the effects of harmonics on
the electrical system. Where studies confirm the requirement, passive or active harmonic suppression
shall be installed. Harmonic filters shall be connected as close as possible to source of harmonics.
Electric Submersible Pumps (ESP)
The detailed specification of ESP’s is outside the scope of this BoD. Within OPQL, this is normally
completed by (or in conjunction with) the artificial lift specialist. Close coordination is required however to
ensure that electrical and control interfaces are adequately specified and designed. Project testing and
documentation requirements shall be clearly defined at the outset and identified on SDRL.
The Manufacturer shall be required to supply calculated rotor responses, lubrication requirements, ramp
times, and the transient air gap torques with their duration in case of 2 and 3 phase short circuits on the
motor terminals. Where specified, the Manufacturer shall be quote a torsional vibration analysis as a
separate item. The Principal may request this study to be performed in addition to that performed by the
driven equipment Manufacturer. In such event, the results shall be acceptable to all parties involved.
Coiled Tubing Deployed ESP’s
Coiled tubing deployed ESP’s have a different pump string configuration (the pump is at the bottom) and
production is through the annulus and not the tubing. With the exception of the wellhead outlet there is
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 51/88
Occidental Petroleum of Qatar Ltd Page 51 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
no significant difference however between surface equipment used for coiled tubing deployed or
conventional ESP’s.
Location of Equipment
Historically, OPQL have installed VSD’s as packaged equipment, normally on remote platforms in close
proximity to the wellhead. Industry experience has confirmed the acceptability of installing the VSD
remote from the wellhead (in extreme cases, several kilometres distant). Future ESP installation
campaigns shall consider the possibility of installing the VSD on central manned facilities (for example
PS1), with the ESP supplied via subsea power cable. Where such installations are proposed,
consideration shall be given to utilizing a suitably specified downhole cable instead of a conventional
subsea cable. Potentially, there are considerable maintainability, operability and economic advantages
with such an installation.
The inclusion of equivalent subsea/downhole cable impedance may be required together with a detailed
Factory Acceptance “String Test” when innovative installation techniques are considered (such as remoteinstallation of VSD’s).
4.6 . Swi tchro oms, Equ ipment Rooms, Bat te ry and P lan t Rooms
General
The design of equipment and plant rooms shall always pay due regard to their intended use and whether
these are manned or normally unmanned areas. This to include safe and satisfactory access
arrangements to equipment for operational and maintenance purposes. Manual handling requirements
shall be taken into account. Refer to section 4.7 for HVAC design requirements.
Satisfactory access and egress requirements shall be provided. In most cases this will require theprovision of two means of escape.
Switchrooms and Equipment Rooms
These shall be located in non-hazardous areas and preferably near the equipment they are provided for.
In exceptional cases, equipment rooms may be located in a hazardous area classified as Zone-2 subject
to approval by OPQL TA. The following requirements shall apply:
• The interior of the sub-station shall be pressurised in accordance with IEC 60079
• An over-pressure of at least 0.5 mbar shall be maintained using a duplicate fan system with a
suitable dry-type dust filtering system to ensure a supply of clean air, each fan system being
capable of supplying the required pressure. The air shall be taken from non hazardous area.
• The fan systems shall be suitable for a Zone-1 area and shall be supplied from two different and
independent sources of electricity supply
• Both fans shall be normally in operation with individual alarms to indicate failure in a manned
control centre
In all cases, for reasons of reliability and serviceability, the electrical switchgear installations including
batteries shall be located indoors in allocated buildings provided with HVAC system.
All rooms containing switchgear shall have two access doors to allow personnel and the largest
equipment to pass in to or out of the room. Safety and escape routes shall be provided all around
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 52/88
Occidental Petroleum of Qatar Ltd Page 52 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
switchgear where personnel may need to operate or maintain the equipment. Such routes shall have two
clear and unobstructed paths to a door. All doors shall be dust tight and weatherproof.
33 kV switchgear shall be located in a separate room. Access to this room shall be through a lockable
door.
Switchrooms and local equipment rooms shall be provided with portable wall mounted rechargeable
hand-lamps. These shall be plug-in type complete with fixed charging units and rechargeable batteries
and be suitable for hazardous area (Zone-1) use. These shall be located near the entrances.
New switchroom and equipment plant rooms shall be fitted with ceiling grid support systems. These shall
be selected from Oglaend, Norway product range (or approved equivalents).
Fire and smoke detection system shall be provided throughout the sub-station building. A weatherproof
fire alarm pushbutton shall be located on the external wall adjacent to the main personnel access door.
Portable fire extinguishers shall be provided inside the sub-station, in each separate room. They shallhave an extinguishing medium that is fully compatible with the electrical and electronic equipment in the
station. Instruction charts should be fitted on the wall adjacent to each extinguisher. Each sub-station
shall be provided with the following minimum items:
• Fire extinguishers
• Fire blankets
• First aid kit and instruction plate
• Escape lights and emergency exit signs
•
No smoking sign
• Vertical drawing rack
• White board
• Framed single line diagrams
• Telephone
• Tools and spares cabinet
• Key box
Rubber matting shall be provided in front of HV and LV switchboards. The matting shall be minimum
650V grade tested to 15000V and shall be of black colour and with non-slip finish.
The construction of sub-station building and the material used shall be such that propagation of fire
through the building is minimal. The fire rating of the sub-station building shall be as per QP Corporate
Philosophy for Fire and Safety QP-PHL-S-001.
Each sub-station shall be suitably identified with warning plates shall be provided at the outside of the
building. New sub-stations shall make provision for extension of switchboards by an additional 2 cubicles
at each end without compromise to equipment access or escape routes.
Equipment access ways shall be provided front and rear 1m minimum after considering wall mounted
distribution boards, interposing relay panels etc. There shall be sufficient space at front of switchgear
panels to manoeuvre circuit breaker handling trucks without blocking emergency access routes.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 53/88
Occidental Petroleum of Qatar Ltd Page 53 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Battery Rooms
Separate battery rooms shall normally be provided for housing UPS system batteries. It is acceptable to
locate switchgear tripping and closing batteries within the switchroom. In such event, the batteries shall
be fully enclosed within ventilated panels. The HVAC requirements shall ensure adequate air dilution
avoiding a build up of hazardous gases (proven buy calculation). A direct link to air extraction system is
preferred. Where dedicated fans are provided, they shall be fitted with fan failure detection. Refer to
section 4.7 for battery room HVAC design requirements.
Battery rooms shall normally be accessed from outside of the switchroom. Manual handling requirements
in particular require consideration, noting that the weight of some batteries will require simultaneous
access by two persons for removal/installation. It is recommended that the room size is adequate to
allow access to at least three sides of each battery bank for maintenance purposes.
A water tap, wash-basin, eye-wash facility, sink and drain shall be installed in the room. The floor and
walls (up to 2m height) shall be provided with acid resistant tiles. All electrical equipment in the batteryroom e.g. lighting fixtures, exhaust fans, convenience outlets, fire and gas detectors etc. shall be suitable
for hazardous area classification Zone-1, Apparatus Group IIC. Battery isolation devices shall be
provided.
Onshore Indoor Sub-stations
The land-based sub-stations shall normally be designed as elevated structures sitting on a minimum
number of reinforced concrete legs. These shall contain switchgear, UPS systems, batteries, annunciator
panels, fire detection and fire fighting equipment, HVAC system, power management system equipment,
etc. Transformers are normally located in an adjacent lockable fenced area in transformer bays. A
typical sub-station layout for raised sub-stations is provided on QP Engineering Standard Drawing
ES.2.68.0001. A more detailed specification of onshore outdoor substations is outside the scope of this
BoD. Refer to ES.2.03.0001 for guidance concerning this if required.
Package Sub-stations
Package sub-stations may be used for temporary installations but only in very special cases can these be
considered for permanent installations. Package sub-station shall be supplied as complete factory
assembled and tested transportable units. HVAC systems shall be provided for package sub-stations in
accordance with section 4.7 HVAC requirements.
The HV switchgear, oil-filled transformer and LV switchgear shall be located in separate compartments
each accessible from the outside by lockable doors. Dry-type transformer can be located in the same
compartment having the LV switchgear. Sufficient space shall be available in the compartments fortermination of cables and safe operation of the switchgear. The ingress protection of the compartments
housing the switchgear shall be minimum IP 55 as per IEC 60529. The compartment having the oil-filled
transformer shall be equipped with leak-proof oil containment area. Each compartment shall be provided
with lighting fixtures and convenience outlets of the weatherproof and industrial type.
4.7. HVAC Requi rements
The HVAC equipment requirements shall be identified and specified by engineering contractor within a
functional requirements specification and associated data sheets.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 54/88
Occidental Petroleum of Qatar Ltd Page 54 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Due regard shall be taken of the intended use of the area served as this will have a significant effect on
the cooling and ventilation requirements, i.e.:
• Manned (or unmanned)
• Installed equipment criticality
• Battery rooms
• General (normally unmanned) plant rooms
Equipment specifications shall include a clause excluding the use of Ozone depleting refrigerants.
Standard industrial HVAC equipment should be used wherever it is feasible to do so. HVAC systems can
be specified as supplied by manufacturers as single components or integrated into packaged units.
Measures shall be taken to avoid damage due to chilled water leakage. Under no circumstances shall
chilled water lines be routed through equipment rooms.
The temperature of rooms which are continuously occupied shall be maintained between 20 and 25°C,
(controlled within +/-1°C, set point typically 21°C) and a relative humidity between 20 and 70% (controlled
within +/-10%, set point typically 50%). The temperature of unmanned plant rooms should not exceed
25°C after taking equipment heat gains into account.
Ingress and distribution of dust particles in plant buildings shall be avoided by sealing of doors and
incorporation of filters into air handling units and all air intakes.
HVAC calculations should be based on heat gain from all sources such as personnel, electronic
equipment, lighting, fresh air intake, walls, roofs, dehumidification losses, windows etc. The heat gain
from electronic equipment requires special attention and shall be based on data provided by the
equipment suppliers. Where necessary, provisional; data can be used with adequate contingencies. The
design contractor shall calculate the necessary minimum number of air-changes per hour that are needed
to regulate the room temperature and to remove the dissipated heat.
Fresh air ventilation may be required in order to provide the specified minimum number of air-changes or
to maintain an over-pressure in order to prevent the ingress of hazardous atmospheres. Overpressure
relief dampers or other measures to equalize air pressure should be considered within the design.
A ventilation system with 100% redundancy (positive exhaust type) shall be provided in battery rooms for
diluting the concentration of hydrogen present in the room by exhausting it to the outside of the room.
The ventilation flow rate within battery rooms shall be adequate to maintain dilution of hydrogen from
batteries to within safe levels under boost charge conditions. Interlocking to inhibit boost/quick charging
on failure of ventilation system shall be provided. Air-conditioning ducts shall be located near the floor.
The fresh air ventilation fans shall be provided with adequate air filters. Redundancy (e.g. double fans)
should be provided. They shall be suitably located to provide adequate dilution of the total space. The
extraction system shall operate satisfactorily in wind conditions varying from still air to design wind
speeds.
Noise limits directly or indirectly caused by HVAC equipment shall be specified within the functional
design specification and measures taken to keep within these limits.
The HVAC system design shall cater for abnormal conditions. The required working conditions for the
equipment shall be ensured during abnormal conditions. All HVAC equipment shall be backed up (within
reasonable limits). Equipment rooms with critical heat sensitive equipment shall have 100% redundancy
of HVAC equipment.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 55/88
Occidental Petroleum of Qatar Ltd Page 55 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
HVAC electrical equipment shall be suitable for the applicable hazardous area. It should be noted that
installation of equipment rooms within hazardous areas shall be avoided wherever possible.
HVAC vendor control and alarm systems are normally acceptable and shall include temperature and
humidity control for each working area. Control systems shall normally operate in automatic mode but
manual operation shall be possible.
HVAC alarms shall be individually displayed on local HVAC panels. Common HVAC alarm signals
generated by the HVAC control system shall be routed to DCS system. Microprocessor-based control
systems such as Programmable Logic Controllers (PLC’s) should be used.
For buildings containing both the control room(s) and administration offices, the integration of HVAC
control systems and the Building Automation System shall be considered.
4.8 . Temporary ins t a l la t ions
Temporary installations are installations which are installed for a short duration (typically 3 months or
less), normally to satisfy an urgent operational requirement or to assist with construction of permanent
facilities. Many temporary facilities ultimately remain in service for much longer than the original intended
service life.
Unless otherwise agreed with OPQL TA, temporary facilities shall be engineered and installed in full
compliance with this BoD as per permanent facilities.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 56/88
Occidental Petroleum of Qatar Ltd Page 56 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
5. DOCUMENTS AND DRAWINGS
All necessary drawings required for the design of electrical system, installation of equipment and theinterconnection of equipment, cables, and wires shall form part of the design. Such information shall be
updated when alterations to the design are made and shall include additional information that is required
during erection or may be required for future maintenance, troubleshooting and operation.
Only certain categories of documentation are maintained by OPQL as key field technical information.
OPQL core drawings are defined in document FAC 226 (OPQL Key Drawing Change Procedure).
Refer also to Appendix G for a list of core drawings. Wherever possible, engineering contractor design
drawings shall be based upon these core documents, backed by additional drawings where required.
Drawings and technical documentation shall be prepared using OPQL standard formats and templates.
These are available from OPQL DCC on request. Please refer to OPQL TA for guidance if any doubt
exists. Standard formats exist for the following documents:
• Switchgear GA’s, SLD’s, interconnection and block diagrams
• Distribution board schedules
• Protection setting schedules
• Lighting & small power layouts
• Earthing details
Equipment vendors shall be responsible for providing all documentation in accordance with FAC-229
“Instructions to Sellers” and the Seller Document Requirement List (SDRL) supplied by the Purchaser. Alldocumentation shall be forwarded to Purchaser’s nominated address.
Review documentation should normally be issued in electronic (PDF) format via OPQL and contractor
DCC. Final documentation shall be issued in PDF and native file format.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 57/88
Occidental Petroleum of Qatar Ltd Page 57 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
APPENDICES
A Definition of Terms and abbreviations
B Approved Codes Standards and Specifications
C Electrical Bulk Materials and Minor Equipment
D Earthing and Bonding
E Recommended Illumination Levels
F Example Format – Planned Maintenance Routine
G Facilities Key Records Library
H Electrical Construction and Commissioning Checklists
J IEC 60092-352 Current Capacities and Defined Installations
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 58/88
Occidental Petroleum of Qatar Ltd Page 58 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
APPENDIX A – Def i n i t i on o f Terms and Abbrev i at i o ns
Definition of Terms
The technical definition of the electrical terms/words shall generally be as per IEC 60050 unless
otherwise defined within this document and below:
Pre-Commissioning
This shall be taken to mean functional tests of equipment (such as protection relay injection tests etc.)
and equipment energisation. All vendor and installation checks and tests are completed sufficient to
ensure equipment is ready to handover for operational trials.
Commissioning
This shall be taken to mean energisation and the final tests and checks at OPQL facilities site subsequentto the energisation necessary to ensure that each circuit satisfactorily performs its function. These tests
will include interface checks across inter-related systems and 4 hr run tests on motors etc. For smaller
projects, equipment can be handed over to operational use after commissioning. Larger projects will
require integrated performance trials.
Plant Start-up
Larger projects have more complex operational performance tests that are required subsequent to
commissioning of individual and inter-related systems.
Contractor
Is the party which carries out all aspects or part of the design, engineering, procurement, construction andcommissioning of the plant.
Inspection
This shall be taken to mean a visual inspection of the equipment/installation.
Manufacturer
Is the party that manufactures equipment and services to perform the duties specified.
Shall
The word 'shall' is to be understood as mandatory.
Should
The word 'should' is to be understood as being strongly recommended.
Supplier
Is the party that supplies equipment and services to perform the duties specified.
Testing
This shall be taken to mean the performance, routine and special tests normally carried out at the factory
of the manufacturer.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 59/88
Occidental Petroleum of Qatar Ltd Page 59 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Autonomy (of a battery)
The duration for which the battery can supply its rated load within its specified voltage limits, following a
prolonged period of battery float charge operation.
Certificate
Document issued by a recognised authority certifying that it has examined a certain type of apparatus
and, if necessary, has tested it and concluded that the apparatus complies with the relevant standards for
such apparatus.
Certificate of conformity
Document issued by a testing station and approved by a national or other appropriate authority, stating
that a prototype or test sample and its specification have a level of safety equivalent to that of an
electrical apparatus for potentially explosive atmospheres which complies with the requirements of one or
more types of protection as laid down in a national or international standard.
Certified electrical apparatus
Electrical apparatus for which a certificate of conformity or a certificate of inspection has been issued.
This is usually (but not exclusively) applied to hazardous area equipment.
Declaration of conformi ty
Document issued by the manufacturer stating that the electrical apparatus complies with the requirements
of one or more types of protection for use solely in locations where the danger is limited and the electrical
apparatus complies with the requirements of national or international standard.
Vital Service
This is a service which, when failing in operation or when failing if called upon, can cause an unsafe
condition of the installation, jeopardise life or cause major damage to the installation.
Electrical power system
All installations and plant provided for the purpose of generation, transmitting and distributing electricity.
Emergency light ing
Lighting provided for use when the supply to the normal lighting fails.
Escape lighting
That part of emergency lighting which is provided to ensure that an escape route is illuminated at all time.
Power management system
A computerised system that is dedicated to monitoring and controlling defined aspects of an electrical
system.
Remote Control Unit (RCU)
A field mounted control device in the vicinity of a motor/consumer for operation of the remotely installed
control gear of the consumer.
ATEX
An abbreviation from the French title of the 94/9/EC directive “Appareils destinés à être utilisés en ATmosphères Explosibles”.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 60/88
Occidental Petroleum of Qatar Ltd Page 60 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
As of July 2006, organizations in EU must follow the directives to protect employees from explosion risk inareas with an explosive atmosphere. There are two ATEX directives (one for the manufacturer and onefor the user of the equipment):
• ATEX 95 equipment directive 94/9/EC, Equipment and protective systems intended for use inpotentially explosive atmospheres;
• ATEX 137 workplace directive 99/92/EC, Minimum requirements for improving the safety andhealth protection of workers potentially at risk from explosive atmospheres.
Hazardous Area
Areas where hazardous explosive atmospheres may occur are classified into zones depending upon thelikelihood of an explosive atmosphere occurring and its persistence if it does.
TN-S
An electrical system with separate neutral and protective (earthing) conductors throughout the system.
Definition of Abbreviations
AFC Approved for Construction
DCC Document Control Centre
FAC Facilities Engineering and Construction
FTI Facilities Technical Information
HES Health, Environment and Safety
OPQL Occidental Petroleum Qatar Ltd
PHR Process Hazard Review
PRM Process Risk Management
QA Quality Assurance
QC Quality Control
STOMP Spares, Training, Operating and Maintenance Procedures
DCN Drawing Change Notice EQ Engineering Query FAC Facilities Engineering and Construction MOC Management of Change
PMR Planned Maintenance Routine
PSICR Programmable Systems/ Information Change Request
PTW Permit to Work
RfC Request for Change
DPSA Development and Production Sharing Agreement
SCENR Supreme Council for the Environment and Natural ReservesQGOSM Qatar General Organization for Standards and Metrology
OOGC Occidental Oil and Gas Corporation
IEC International Electro technical Commission
BSI British Standards Institution
CAA Civil Aviation Authority
VSD Variable Speed Drive
ESP Electrical Submersible Pump
UPS Uninterruptible Power System
TA Technical Authority
SAFOP Safety and Operability Studies
SoR Statement of Requirement
HAZOP Hazard and Operability StudiesHVAC Heating, Ventilating and Air Conditioning
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 61/88
Occidental Petroleum of Qatar Ltd Page 61 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
RCU Field mounted (motor/consumer) control device
PMS Power Management System
HV High Voltage - a voltage exceeding 1000V ac
LV Low Voltage - a voltage up to 1000V ac
RCCB Residual current circuit breaker
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 62/88
Occidental Petroleum of Qatar Ltd Page 62 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
APPENDIX B – App ro ved Codes , Standards and Sp ec i f i cat i ons
The following list are the recommended codes, standards and specifications to be used for electricalengineering design specification and procurement activities on OPQL managed facilities in Qatar. Where
more than one standard exists, only the most relevant document (either QP or OPQL originated) is listed.
Project specific documents are included where no suitable company specification exists. Please refer to
OPQL TA for guidance for any subject areas not adequately covered by these standards.
The user’s attention is drawn to section 2 of this document which gives guidance on application of these
codes and standards, and precedence clauses to be used for reconciling conflicts between documents.
Prior to use, the user shall ascertain the latest revisions of these documents. This information is readily
available from OPQL Documents and Standards section.
These documents have been categorised into 3 groups as follows:
Cat 1: Reference standard for subject area. The document shall be applied in its entirety.
Cat 2: Reference standard for subject area. The document is directly applicable to the subject area
but there are exceptions. Refer to clarification within this BoD or OPQL TA as necessary.
Cat 3: The document is to be used for general guidance but engineering judgement will be required
as there are many exceptions. The document is either project specific or included for reference because
there are no other relevant company standards. Refer to clarification within this BoD or OPQL TA as
necessary.
RECOMMENDED CODES and STANDARDS FOR USE ON OPQL MANAGED FACILITIES
DOCUMENT NUMBER DESCRIPTION CATEGORY
OPQL DOCUMENTS
000000-4-XPS1-BD-0001-001 Electrical Basis of Design 1
000000-5-XPS1-BD-0002-001 Instrumentation Basis of Design 1
000000-4-XPS1-SP-0001-001 General Cable Specification 1
000000-4-XPS1-29-682-001 Primary Earthing System 1
000000-4-XPS1-21-6820-001 Secondary Earthing System 1
E250 to E343 inclusive Electrical construction and commissioning checklists 2000000-8-YPS1-PR-00001-001 Project Document numbering format 1
000000-8-XPS1-TD-0001-001 OPQL Technical Authorities Manual 1
000000-8-XPS1-TN-0003-001Certification Matrix and Requirements Summary forMaterial Requisition
1
000000-8-XSP1-SD-0001-001 State of Qatar Environmental Protection Standards 1
YPS1-4-SP-6923-001 ISND Phase 3 Subsea Cable Specification 2
YPS1-4-CA-6924-001 Calculation example – Subsea cable length 2
YPS1-4-CA-6921-001 LV Cable Sizing 2
YPS1-4-TN-6921-001 Hazardous Area Classification Technical Note 2
YPS1-4-SP-6928-001 Safety and Operability Review (SAFOP) Terms ofReference
2
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 63/88
Occidental Petroleum of Qatar Ltd Page 63 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
RECOMMENDED CODES and STANDARDS FOR USE ON OPQL MANAGED FACILITIES
DOCUMENT NUMBER DESCRIPTION CATEGORYYPS1-4-SP-6922-001 ESP Package Specification 3
YPS1-4-DS-6921-001 ESP Transformer Data Sheet 3
YPS1-4-DS-6922-001 ESP Soft Starter Data Sheet 3
YPS1-4-DS-6923-001 ESP Motor Data Sheet 3
YPS1-4-DS-6925-001 ESP Junction Box Data Sheet 2
YPS1-4-SP-6927-001 Marine Navigational Aids Specification 3
YPS1-4-SP-6928-001 RMU Specification 2
YPS1-4-TN-6920-001 Comparison of HV Switchgear vs Ring Main Units 2
403086-4-PS1E-SP-0002-001
OPQL Specification for Power Management
Systems 3
410426-4-PS1E-SP-0001-001 Specification for Replacement HV Switchgear 3
410924-8-PS1E-MR-0001-001 Glycol Reboiler Requisition 3
410924-8-PS1E-SP-0001-001 Glycol Reboiler Electric Heater Skid 3
PRD 500 Electrical Safety Guidelines 1
DEV-201 Facilities Engineering and Construction Policy 1
FAC-219 Commissioning Procedure 1
FAC-223 Engineering and Procurement Procedures 1
FAC-225 Engineering Closeout Procedure 1
FAC-226 Key Drawing Change Procedure 1FAC-227 Document Control Procedure 1
FAC-228 Drawing Office Procedure 1
FAC-229 Instructions to Sellers 1
FAC-230 Instructions to Contractors 1
PRM-PY-001 Process Risk Management Policy 1
PRM-PR-001 Facilities Technical Information 1
PRM-PR-002 Process Hazard Review and Risk Assessment 1
PRM-PR-002-MATRIX OPQL Risk Matrix 1
PRM-PR-003 Management of Change 1PRM-PR-004 Operating, Maintenance Procedures 1
PRM-PR-005 Mechanical Integrity and Quality Assurance 1
PRM-PR-006 Pre-Start up Safety Review 1
HES-027 Lifting Equipment Control and Operations Policy 1
402160-4-PS1K-BD-6015-001 PS1K Electrical Design Basis 2
402160-4-PS1K-SP-6063-001 PS1K Electrical Package Specification 3
400060-4-HALU-6593 PWHF Electrical Philosophy Document 2
Al Morjan BoD Section 8 Electrical Design Basis 2
410641-4-PS1R-SP-0001-001 Distribution board specification 3
410641-4-PS1R-DS-0001-001 Distribution board data sheets 3
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 64/88
Occidental Petroleum of Qatar Ltd Page 64 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
RECOMMENDED CODES and STANDARDS FOR USE ON OPQL MANAGED FACILITIES
DOCUMENT NUMBER DESCRIPTION CATEGORYQP DOCUMENTS
EFS.00.08.03 Offshore Environmental Conditions 1
EFS.00.08.04Specification for Equipment Preservation, Protectionand Packaging
2
EFS.00.08.05 QP General Specification for Packaged Units 2
QP-SPC-L-002QP Technical Specification for Painting andWrapping of Metal Surfaces
2
QP-PHL-S-001 QP Corporate Philosophy for Fire and Safety 2
QP-STD-ENV-005 QP Environmental Standard for Legal Requirements 1
ES.D.10 Engineering Standards - Draughting 2
ES.2.06.0001 Electrical Installation Recommended Practices 2
ES.2.14.0001 HV GT Driven Synchronous Generators 2
ES.2.14.0002 Diesel Engine Driven Generators 2
ES.2.14.0010 HV Switchgear and Controlgear for Use Indoors 2
ES.2.14.0015 LV Switchgear and Controlgear for Use Indoors 2
ES.2.14.0019 Busbar Ducting 2
ES.2.14.0020 HV Liquid Filled Transformers 2
ES.2.14.0022 Dry Type Power Transformers 2
ES.2.14.0030 HV Cage Induction Motors and Synch Motors 2
ES.2.14.0035 LV Cage Induction Motors 2
ES.2.14.0036 Electric MOV Actuators 2
ES.2.14.0040 AC UPS Systems 2
ES.2.14.0044 DC UPS Systems 2
ES.2.14.0045 Cathodic Protection Facilities for Offshore Facilities 2
ES.2.14.0060 Secondary Selective System 2
ES.2.14.0065 Power Management System 3
ES.2.14.0085 Neutral Earthing Resistors 2
ES.2.14.0095 Power System Studies 3
ES.2.14.0098 Electrical Requirements for Package Equipment 3
ES.2.50.0001 DC UPS System Key Single Line Diagram 2
ES.2.53.0001 DOL Starter up to 3.7kW 2
ES.2.53.0002 DOL Starter above 3.7kW up to 55kW 2
ES.2.53.0011 Switch Fuse Feeder 2
ES.2.53.0012 Switch Fuse and Contactor Feeder 2
ES.2.53.0013 PEC Controlled Lighting Feeder 2
ES.2.53.0014 Contactor Feeder for Heaters 2
ES.2.13.0044 Data sheets - DC UPS Systems 3
ES.2.03.0001 QP Electrical Engineering Philosophy 3
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 65/88
Occidental Petroleum of Qatar Ltd Page 65 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
APPENDIX C – Elec t r i c al Bu l k Mater i al s and Mino r Equ i pm en t
General
Due regard shall be taken during engineering design and selection of equipment to ensure compatibility
between new and existing systems. The following outline specification of bulk items and minor equipment
is compatible with equipment installed on PS-1 facilities and typical of equipment on other OPQL
managed facilities. This is not an exhaustive listing. For minor projects equipment should be selected
from the attached listing. For larger projects, economic considerations will prevail, however compatibility
and standardisation should also be taken into account. Please refer to OPQL TA for guidance as
necessary.
Operating voltages shall be specified suitable for the electrical system of use.
Specifications for Electrical Bulk Materials and Minor Equipment
Fluorescent Fixtures
The fittings shall be suitable for Zone-1, IIB, T3 and the Make of the EX fluorescent fitting shall be
CEAG or approved equivalent as follows:
• 2ft normal light fitting CEAG type eLLK 92018/18
• 4ft normal light fitting CEAG type eLLK 92036/36
• 2ft emergency light fitting with back up battery of 3 hours: CEAG type eLLK 92018/18 NIB
• 4ft emergency light fitting with back up battery of 3 hours: CEAG type eLLK 92036/36 NIB
Battery room lighting shall be suitable for Zone-1, IIC or IIB+H2.
Floodlights – Ex 'D’
Floodlights shall be suitable for offshore marine use. They shall be IP 66/67 rated, 250W, EEXde IIC
T3 at 55C type. The make shall be Chalmit or a pre-approved equivalent.
Junction Boxes
All outdoor Junction Boxes (JB’s) including lighting JB’s shall be fully weatherproof and dust proof (IP-
66 minimum), corrosion resistant suitable for use in Zone-1 certified Ex ’e’, Gas group IIB,
Temperature Class T3. Enclosure material shall be GRP (UV and Hydrocarbon resistant) or 316L
stainless steel and provided with 6mm² size external 316L stainless steel earth screw and internal
metallic back plate with earthing point. Junction boxes shall have external fixing lugs. Operating
voltages shall be suitable for the electrical system of use.
Cable entries and terminals (SAK type polyamide) shall be sized based on cable sizes specified in the
requisition.
Cable entry shall be from bottom only, top side entry shall be avoided and all entries shall be ISO
metric threaded. The material shall be of high mechanical and thermal strength, UV resistant. The
material shall be anti-static and anti-magnetic.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 66/88
Occidental Petroleum of Qatar Ltd Page 66 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
All accessories such as bolts, nuts etc. shall be 316L stainless steel. Junction Boxes shall be provided
complete with terminals, mounting rails, end plates/partition plate, marking strips/tags, etc and clear
PVC protective covers with danger voltage labels.
Outside identification plates shall be corrosion proof by nature (stainless steel) and securely fixed to
enclosure (not glued or Aluminium riveted) by stainless steel screws / PVC rivets.
The make shall be Abtech, CEAG, Klippon, Hawke or pre-approved equivalent.
Cable Trays and Ladder Racks
ALL cable ladder rack, cable tray, covers, bends, tees and all ancillaries shall be manufactured from
an industry accepted pultruded glass reinforced plastic (GRP), complete with UV veil, from MITA or
pre-approved equivalent GRP products. Cable Tray shall be MITA Fibatray GF series (or equivalent).
Cable Ladder Racks shall be MITA Fibarack “GN” Heavy Duty Series (or equivalent). Accessories
and fittings such as bends, risers, tees, crosses, reducers, etc. shall be fabricated from the samematerial of cable trays/ladders as a single piece construction. The trays and bends etc. shall be
perforated and ventilated with the holes occupying 30% or more of the tray area. This is required to
satisfy “freely ventilated” criteria as detailed within IEC 60092, Annex A, Installation methods E or F.
The fixing accessories such as nuts, bolts and fasteners shall be supplied by the vendor.
Remote Control Units
All Remote Control Units (RCU’s) will be field installed near the respective motors. The RCU shall be
Ex-d / Ex-e ATEX certified type construction suitable for Zone-1 or Zone-2, Gas group IIB,
Temperature T3 environnemental conditions, IP 66. The make shall be CEAG or MEDC, or pre-
approved equivalent.
Convenience Socket/Welding Socket Outlets
Convenience socket outlets and welding socket outlets shall be EEx d, IIB, T3 certified for use in
Zone-1 areas. All socket outlets shall have ingress protection of IP 66.
Each convenience outlet/welding circuit shall be protected by phase short circuit protective devices
and by current-operated earth leakage protective devices/residual current device (RCD). The
sensitivity of RCD shall be 100mA for single phase convenience outlets and 300mA for welding
socket. The operating time shall be less than 30 msec. The rating and make of the sockets shall be as
follows:
• 110V AC socket outlet: STAHL, P/N 8575/11-304 (16 Amps, 2P+E , EEXde IIC T6)
• 240V AC: STAHL, P/N 8575/11-306 (16 Amps, 2P+E , EEXde IIC T6)
• Welding Sockets: ABB type GHG 534 1506 VO (63Amps, 3P+N+E, EEXde IIC T6)
Cable Glands
Cable glands shall be manufactured to BS 6121. Make shall be CMP/HAWKE/Cooper or pre-
approved equivalent. Cables glands shall be explosion proof suitable for use in Zone-1, Gas groups
IIB, temperature class T3 and shall be certified EEx “de” in accordance with CENELEC Standards EN
50018/50019. The certification shall be by an internationally recognised authority like BASEEFA.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 67/88
Occidental Petroleum of Qatar Ltd Page 67 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
However, certification from other recognised authorities such as FM, PTB, etc. shall be considered
subject to purchaser’s approval.
Cable glands shall meet the requirements of IP-66 (minimum) double sealing universal type forsuitable weather protection, in accordance with IEC-60529.
Cable glands shall be of double compression type and shall be Nickel plated brass. Cable glands
shall have ISO metric threads, deluge proof without PVC shrouds. Cable glands shall be
manufactured to provide cable sealing of inner and outer sheaths and mitigate cold flow potential of
outer sheath. Clamping of armour by special ring. Cable glands shall be provided with earth tag, lock
nut, serrated washer and nylon IP sealing washer (not the Red moisture absorbent fibre type). Cable
glands for single core cables shall be connected to non-magnetic non-ferrous gland plates. Cable
entry adaptor and reducer shall be Exde nickel platted brass
Cable Lugs
Crimping type cable lugs of appropriate size suitable for the core cross-section (Power and Control),
as required shall be provided from Bicon or approved make. Necessary sleeving shall be provided
over the lugs using either HELLIMAN RUBBER or HEAT SHRINK SLEEVE.
Cable Terminations
Conductors shall be fitted with approved pre-insulated crimped pins for connection into clamp type
terminals or fitted with crimp lugs for stud terminals. Lugs shall either be pre-insulated or heat shrink
shrouds shall be fitted to un-insulated lugs. Cable terminations shall be of solder less crimped design
to suit the particular equipment and shall be tin plated copper lugs.
HV Cable Termination Kits / Jointing Kits
HV cable joints should be avoided wherever possible. Where unavoidable, HV termination kits shall
be suitable for specified size, voltage rating, and type of the Cables and suitable for the hazardous
area classification (Zone-1, IIB, T3). Elastimold/Raychem Heat shrinkable, stress relieving type
termination kits shall be used for HV cable termination.
The termination kits shall contain all accessories that are required for completing the end termination
at switchgear, transformer, well head JB etc. Any items/components/accessories that are not
specifically mentioned but are required for making the Elastimold/Heat shrinkable type termination
complete, shall be considered and supplied along with the termination kits.
HV Terminations
HV cable end termination kits shall be of heat shrink type Raychem (or equivalent) make suitable for
the type of cables indicated on cable specification or datasheet. The end termination kits shall be
complete with all standard accessories including heat shrink stress relieving sleeves, trifurcating glove,
solder less earth spring coils, drain wire and installation instructions etc.
Lighting and Small Power Switches
Switching of lighting etc. is normally done from distribution boards. Exceptionally, where required,
on/off switches shall be double pole, suitably rated, 240V, 50Hz, and suitable for outdoor installation.
Typically CEAG or MEDC supply.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 68/88
Occidental Petroleum of Qatar Ltd Page 68 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Enclosures shall be certified for Ex-d/Ex-e type construction suitable for Zone-1, Gas group IIB,
Temperature T3 environmental conditions, IP 66/67. They shall typically be provided with a 6mm² size
external earth screw/stud. The switch/enclosure shall be moisture resistant and fungus proof resistant
to salty weather condition, UV resistant and hydrocarbon resistant, corrosion and ambient environmentas specified. Small Power Switches shall be as follows:
• 240V,1ph, 10A, 50Hz, switched socket outlet with interlocked switched suitable for Zone-1,
IIB, T3.
• 240 V,1ph, 10A, 50Hz, switched socket outlets suitable for Zone-1, IIB, T3.
• 415V, 3ph+N, 63A, 50Hz, welding outlet, suitable for Zone-1, IIB, T3.
Wellhead Junction Boxes
High Voltage (3.3kV or 6.6kV) outdoor well head junction boxes shall be fully weatherproof and dustproof (IP-66 minimum), corrosion resistant stainless steel 316L, suitable for use in Zone-1 certified Ex
’e’, Gas group IIB, Temperature Class T3 application. Make shall be ABTECH or pre-approved
equivalent.
Multicable Transits
Multi Cable Transit MCT frames shall be type suitably sized in every aspect, with a generous
allowance for future cables (typically 50% minimum). The make shall be Roxtec or HAWKE or Oxy
approved equivalent.
PA/GA Field equipment
PA/GA equipment inclusive of field switches, control stations, sounders, beacons/strobes, junction
boxes manual call points shall be specified from MEDC accredited product range (or pre-approved
equivalents) and be fully compatible with other equipment on the installation.
Ceiling Grid Support
The preferred make for switchroom and plant room ceiling support systems shall be Oglaend, Norway (or
pre-approved equivalents).
Cable Identification Systems
Cable identification systems shall be compatible with existing platform items, typically Critchley (or other
approved equivalents). Another acceptable alternative shall be Silver Fox, UK
Interposing Relay Panels
These shall be as detailed by the engineering contractor on specifications and data sheets in accordance
with project drawings. Incoming and outgoing cables shall be bottom entry unless otherwise specified on
the data sheets. The panels shall be mounted indoors and have ingress protection of IP42 minimum.
There shall be an external nameplate fitted with equipment tag number and description and a separate
label identifying voltage levels present within the panel.
Internally, incoming and outgoing cables/panel wiring shall be conspicuously identified. Cables shall be
separately routed in trunking within the panel in accordance with voltage levels. All relay connections
shall be wired down to separate incoming and outgoing terminals with different voltage levels segregated.Relays shall be of the multi-pole plug in type and be identified within the panel.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 69/88
Occidental Petroleum of Qatar Ltd Page 69 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Ai r Condit ioning Equipment
Air conditioning units shall be suitably sized and rated and be of a good industrial quality from a
recognized supplier (Mitsubishi, Carrier, Toshiba, etc). The use of hazardous area A/C equipment shall
be avoided wherever possible. Where no alternatives exist, the engineering contractor shall propose a
specification that will be pre-approved by OPQL TA.
Power and control Cables
All power and control cables shall be fully compliant with OPQL General Cable Specifications, document
reference 000000-4-XPS1-SP-0001-001.
Substation and Equipment Shelter wall Cladding
The internal wall cladding for substations and air conditioned equipment shelters shall be INEXA TNF
50mm x 3m or an equivalent product from a pre-approved supplier.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 70/88
Occidental Petroleum of Qatar Ltd Page 70 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
APPENDIX D – Ear t h i ng an d Bond ing
General
The primary purpose of the earthing system is to reduce and control voltages on equipment to an
acceptable level under abnormal conditions and provide a conductive path to earth for fault currents, thus
facilitating rapid disconnection of faulted equipment from the electrical system. A secondary purpose is to
eliminate any risk of sparking in hazardous areas due to voltages under abnormal conditions. Such
conditions include equipment faults, static electricity build up or lightning strikes.
This document covers the primary and secondary earthing philosophy to be adopted on OPQL managed
facilities. The earthing networks on most of OPQL managed facilities are TN-S systems.
Lightning and Static Electrici ty
Lightning protection is not required nor normally provided on steel offshore platforms as a good
conductive path to earth exists by virtue of the structure, jacket and piles. There may be a requirement
for surge arrestors to be fitted to protect sensitive offshore (mainly telecommunication) equipment.
Specification of these is however outside the scope of this BoD.
For protection against lightning of onshore structures and the accumulation of static charges, guidelines
given in BS 6651 (Code of Practice for Protection of Structures against Lightning) shall be used. Earth
electrodes shall be located near the base of elevated structures that require lightning protection. This is
to ensure a low impedance lightning discharge path to earth. The electrode(s) shall be connected to the
structure to be protected and to the main earth grid using conductors of 120mm² cross-sectional area.
The combined resistance to the general mass of the earth of the electrodes providing for lightning
protection shall not exceed 10 ohm when isolated from the structure to be protected and from the main
earth grid.
Onshore metal structures like tanks, vessels etc. do not require additional protection beyond the earthing
requirements provided all structural elements are bonded to form a single conductive structure, which is
to be connected to the plant earth grid. Care should be taken to ensure that all structural elements
forming part of lighting protection system are suitable both mechanically and electrically.
Instrument Clean Earth Systems
Separate instrument clean earthing networks (to reduce/eliminate signal interference levels etc.) and
protective earthing for intrinsically safe (IS) instrumentation systems shall be provided where required.
These networks shall be segregated from the electrical primary and secondary earthing systems and
comply with appropriate codes and standards. Instrument cable earth screens, etc, are part of the clean
earth system. These are normally bonded to the clean earth system within control/equipment rooms and
insulated at the field end.
Refer to Instrument Basis of Design, document number 000000-5-XPS1-BD-0002-001 for full details of
Instrument earthing philosophy.
For avoidance of doubt, conductive instrument casings are considered part of the secondary earthing
system and shall be locally bonded to earth.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 71/88
Occidental Petroleum of Qatar Ltd Page 71 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Primary and Secondary Earthing System – Offshore facilities
The platform jacket steelwork is in direct contact with sea and the seabed “earth” at all times.
Consequently the steelwork is the zero reference point regarding the dissipation of electrical fault
currents. Since the module sub-framing and all topsides main structures are welded in place, they have
reliable electrically conducting paths and interfaces. These have an adequate cross-sectional area to
safely conduct electrical currents to earth.
Platform generators, distribution transformers, switchboards, neutral earthing resistors etc. shall be
bonded with copper conductors, to ensure that high earth currents are directed to their correct return
location, preferably in an interconnected ring with copper earth bars appropriately located. These
conductors form the PRIMARY EARTHING SYSTEM.
Other items of equipment such as low voltage motors, distribution boards, UPS systems, battery and
charger units, junction boxes, cables, control panels and packaged equipment shall be bonded to the
local steelwork using copper cables. The particular methods used for these items of equipment will formpart of the SECONDARY EARTHING SYSTEM.
Earth Bonding Cable Sizes
The following cable sizes for earth bonding shall be adopted and are to be used as follows:
• HV and LV Switchboards and Main Substation primary earth loops 120mm²
• LV Equipment with a supply cable greater than 35mm² 70mm²
• LV Equipment with a supply cable between 6 and 35mm² 35mm²
• Equipment not in direct (i.e. welded) contact with platform steelwork 35mm²
• External (field) equipment with a supply cable of 6mm² or less 16mm²
• Equipotential bonding and conductive (non GRP) cable ladder racks and trays 16mm²
• Internal equipment with a supply cable of 6mm² or less 6mm²
The earth cable sizes indicated above are minimum and larger cables may be substituted as required.
Cables should be selected from Oxy General Cable Specification 000000-4-XPS1-SP-0001-001, type E1
shall be used unless otherwise specified.
Typical earthing installation details are shown on the following drawings:
• Primary Earthing System: 000000-4-XPS1-29-6821-001
• Secondary Earthing System: 000000-4-XPS1-21-6820-001
Switchboards
Each electrical switchboard shall be connected to earth at two points directly bonding the switchboard
earth bar to a Switch Room earth bar forming part of the primary earth loop.
Transformers and Generators
The earthing conductors linking the transformer or generator neutral point to the earth, via fault limiting
equipment (if fitted), shall be as short as possible and mechanically well protected.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 72/88
Occidental Petroleum of Qatar Ltd Page 72 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Field Equipment
The minimum recommended size of separate bonding conductors for field equipment is 16mm² to
maintain mechanical integrity. The size of protective conductors within small power cables shall not be
less than the size of phase conductor. The armour of cables shall not be used as the sole means of
providing earth continuity.
Motors, control stations and other field equipment shall be bonded using approved standard earth bosses
welded to the steelwork.
Equipotential Bonding Test
Offshore installations provide good inherent natural equipment grounding. A measurement (using a low
resistance ohmmeter) performed between any two metal frames or between one metal frame and one
point on the structure or any two points of the structure should not give a reading above 0.5Ω.
Circuit disconnection times
Earth loop impedances shall be sufficiently low to guarantee rapid disconnection of faulted equipment
within a minimum period of time, thus minimizing equipment damage. Disconnection times should always
be within the equipment specified fault limits (normally within 1 second for main HV & LV switchgear). For
all other fixed equipment, disconnection should occur within a maximum of 5 seconds.
Smaller final sub circuits require more rapid disconnection times, taking into account requirements for
personnel protection. The following times shall be applied for final circuits not exceeding 32A:
U0 Volts Disconnection Time
Up to 120V 0.8s
120V to 277V 0.4s
277V to 400V 0.2s
Above 4000kW 0.1s
The engineering contractor shall verify circuit disconnection times by calculation and specify the
maximum earth fault impedance level required to achieve this. For further guidance concerning this
matter, please refer to the following publications:
• IEC 60364-4-41 Electrical Installation of Buildings, Protection for Safety, Protection against
electric shock.
• BS 7671 Requirements for Electrical Installations, Chapter 41, Protection against electric shock.
Earth Loop Impedance
In every new installation, an earth loop impedance measurement (using an earth loop impedance tester)
should be made to confirm the calculated values of impedance required to achieve circuit disconnection
within the specified time period before equipment is put into service. A clause to this effect shall be
included within construction workpackages.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 73/88
Occidental Petroleum of Qatar Ltd Page 73 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Earthing systems – Onshore Installations
For on-shore installations electrical earthing systems, equipment and structures each installation shall
have one main earth grid connected to at least two groups of earth electrodes. These shall comply with
the requirements of IEEE 80 Guide for Safety in Substation Grounding. Potential step and touch voltage
levels shall be kept within acceptable limits.
The earth grid shall comprise copper earthing cables. Each item of equipment to be earthed shall be
connected to main earth grid by two branch earth connectors. The earth grid shall be installed throughout
the plant site in the form of a main earth ring with branch interconnections to the equipment and
structures to be earthed.
Each earthing electrode shall be sunk vertically to a depth of 2 metres below the summer water table.
The earth resistance of each electrode shall be as low as is practicable but shall in any event be such that
the electrical resistance between the main earth grid and the general mass of the earth shall not exceed 4
ohms when any one group of electrodes is disconnected. Earth electrodes shall be galvanised steel pipeor other suitable material, which guarantees low resistance and long life. Copper electrodes shall not be
used in areas with impressed-current cathodic protection. Aluminium shall not be used for any part of an
earthing system.
Use of buried un-insulated earthing cable, for achieving the desired earth resistance values, shall be
subject to approval of OPQL TA.
The connections between electrode heads and conductors shall be so executed that easy inspection and
testing of the earth resistance of individual electrodes is possible. All bare parts of underground earthing
conductors shall be suitably protected against direct contact with the surface soil so as to prevent
electrolytic corrosion of plant equipment. All earthing terminations shall be made with compression-type
cable lugs. Interconnections shall be directly clamped with compression-type branch connectors or 'Cad-
Welded'.
The metallic enclosures of electrical and nonelectrical equipment, vessels, tanks, structures, etc., shall be
bonded and earthed by connection to the common earth grid or to be provided with their own duplicate
electrodes. Pipelines shall not be used for earthing purposes.
The earth bonding cable sizes specified within this document equally applicable to onshore as well as
offshore installations unless system fault levels require larger cables to be specified and substituted.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 74/88
Occidental Petroleum of Qatar Ltd Page 74 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
APPENDIX E – Recom mended Il l um inat i on Level s
The lighting system shall be designed to provide the average illumination levels as given below:
Location Average Il lumination
level (lux)
Control rooms, laboratories and offices 500
Catering areas (Food preparation and Serveries) 300
Recreation areas, Dining areas 250
Switchrooms and Local Equipment Rooms 250
Indoor workshop areas 250
Plant Rooms and Indoor Stores areas 150
General plant areas with rotating equipment 150
General process areas(Static equipment and Piperacks) 100
Locker rooms and toilets 100
Outdoor stores and materials yards 50
Access ways and stairs 50
Escape lighting 5
Tank Farm areas 2 - 5
Note that emergency lighting levels available are dependent upon autonomy. Most battery backed
emergency luminaires are selectable to provide either 3hr or 1.5hr autonomy. The light output with a 3hr
autonomy is approximately half that when selected for 1.5hrs.
It is recommended that a lighting survey be conducted on completion of major installation activities. This
will consider lighting conditions under normal and emergency conditions. The lighting survey shall be
carried out with a colour and cosine corrected lightmeter. Any dark areas shall be recorded on the
lighting layout drawings and show recommended locations of additional luminaires.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 75/88
Occidental Petroleum of Qatar Ltd Page 75 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
APPENDIX F – Exam p le Fo rm at – Planned Main tenance Rou t in e
Sheet 1 of 3
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 76/88
Occidental Petroleum of Qatar Ltd Page 76 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Sheet 2 of 3
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 77/88
Occidental Petroleum of Qatar Ltd Page 77 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
Sheet 3 of 3
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 78/88
Occidental Petroleum of Qatar Ltd Page 78 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
APPENDIX G - Fac i l i t i es K ey Reco rds L i b rar y
Only certain categories of documentation are maintained by OPQL as key field technical information(FTI). Attached below is a reference list of the key records library documents, most of which are available
in native file format from OPQL DCC on request. Engineering contractor designs shall be based upon
key records documentation, backed by additional drawings where required.
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 79/88
Occidental Petroleum of Qatar Ltd Page 79 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
APPENDIX H – Elec t r i cal Cons t ruc t i on and Co mmiss io n i ng Check l i s t s
All the checklists referenced below are available from OPQL DCC on request:
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 80/88
Occidental Petroleum of Qatar Ltd Page 80 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 81/88
Occidental Petroleum of Qatar Ltd Page 81 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 82/88
Occidental Petroleum of Qatar Ltd Page 82 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 83/88
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 84/88
Occidental Petroleum of Qatar Ltd Page 84 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 85/88
Occidental Petroleum of Qatar Ltd Page 85 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 86/88
Occidental Petroleum of Qatar Ltd Page 86 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 87/88
Occidental Petroleum of Qatar Ltd Page 87 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001
C:\Documents and Settings\pilkingj\Local Settings\Temporary Internet Files\OLK47\Electrical BoD 28th May.doc
8/10/2019 Electrical Basis of Design - OXY
http://slidepdf.com/reader/full/electrical-basis-of-design-oxy 88/88
Occidental Petroleum of Qatar Ltd Page 88 of 88
ELECTRICAL BASIS OF DESIGN Document No: 000000-4-XPS1-BD-0001-001