Induron Coatings Inc.3333 Richard Arrington Jr. Blvd NBirmingham, Alabama 35234-2303
Phone: 205-324-9584 · 800-324-9584 · Fax: 205-320-5220induron.com · Email: [email protected]
COAT IT AND FORGET IT.
Induron has the solutions for all of your ElectricTransmission and Distribution maintenancecoatings needs. Whether it is recoatingweathered galvanized lattice type towers,previously painted transmission poles, substationstructures, below-grade tower footings, or largetransformers; Induron has the exact right coatingfor the job! All of the products listed below andseveral other innovative coatings have beenspecifically developed for T&D asset protection inthe form of corrosion protection.
At Induron, we invest ourselves in your success, your satisfaction,and your reputation. It’s why — for example — we won’t specify themost expensive option when a more economical solution will suffice.Its why we’ve been known to recommend customers postponeprojects that we honestly don’t believe need immediate re-coating.
So what can we do to help you succeed? If it takes climbing towersfor a closer inspection, we climb towers. If you need us to dropeverything for an impromptu face-to-face, we’re on our way. If youneed technical support with any coating-related issue, we’ve got theexpertise. Because at Induron, “getting it right” is who we are, notjust what we do.
PROTECTIVE COATINGS ELECTRIC UTILITY COATING SYSTEM SELECTION GUIDESubstation Equipment including Circuit Breakers, Switchgear Enclosures,Transformer and Regulator Bodies, Misc. Boxes.
SSUURRFFAACCEE CCOONNDDIITTIIOONNRRAANNKKIINNGG
EENNVVIIRROONNMMEENNTTAALLRRAANNKKIINNGG
SSUURRFFAACCEEPPRREEPPAARRAATTIIOONN PPRROODDUUCCTT NNAAMMEE ## OOFF CCOOAATTSS FFIILLMM TTHHIICCKKNNEESSSS
((MMIILLSS DDFFTT))
APreviouslypainted, Light rust
R-1, R-2 Mild to ModerateC-1 to C-3 SSPC-SP2
Spot Prime - P30 PrimerFull Intermediate – P30 PrimerFull Finish - Indurasil Enamel
111
2.5-4.02.5-4.01.5-2.5
BPreviouslyPainted
Moderate RustR-3 Moderate to Severe
C-3 to C-4SSPC-SP2, SSPC-SP3
Full Prime - P30 Primer Full Intermediate – P30 Primer Full Finish – Indurasil Enamel
111
2.5-4.02.5-4.01.5-2.5
C
Unpainted orpreviously
Painted HeavyRust
R-4, R-5 Moderate to SevereC-3 to C-5m
SSPC-SP3, SSPC-SP6
or SSPC-SP7
Full Prime – E-Bond Penetrating SealerFull Intermediate –
Induramastic AluminumFull Finish – Indurethane 6600
1
1
1
1.0-2.0
5.0-8.0
2.0-3.0
Transmission Towers and Poles
SSUUBBSSTTRRAATTEE CCOONNDDIITTIIOONNRRAANNKKIINNGG
EENNVVIIRROONNMMEENNTTAALLRRAANNKKIINNGG
SSUURRFFAACCEEPPRREEPPAARRAATTIIOONN PPRROODDUUCCTT NNAAMMEE ## OOFF CCOOAATTSS FFIILLMM TTHHIICCKKNNEESSSS
((MMIILLSS DDFFTT))
AWeatheredGalvanizedStructures
R-1, R-2 Mild to ModerateC-1 to C-3 SSPC-SP2 Induraguard 9200 1 8.0-10.0 mils DFT
BWeatheredGalvanizedStructures
R-3 Moderate to SevereC-3 to C-4
SSPC-SP2, SSPC-SP3
Spot PrimeP30 Primer (or)Armorlux Primer Induraguard 9200
Spot or 1 FullPrime
1
2.5-4.0 mils DFT
8.0-10.0 mils DFT
CWeatheredGalvanizedStructures
R-3, R-4 Moderate to SevereC-3 to C-5m
SSPC-SP2, SSPC-SP3
E-Bond Penetrating Sealer
Induraguard 9200
1 full prime
1
1.0-2.0 mils DFT
8.0-10.0 mils DFT
DWeatheredGalvanizedStructures
R-2 to R-5 C-5i SevereChemical Exposures
SSPC-SP-3SSPC-SP-11
E-BondInduramastic
Induramastic Aluminum
111
1.0-2.0 4.0-6.04.0-6.0
E Carbon Steel Structures R-1, R-2 Mild to
Moderate SSPC-SP2 E-Bond Indurasil Enamel
11
0.5-1.02.5-3.5
F Carbon Steel Structures R-3, R-4 Moderate to
SevereSSPC-SP-3 SSPC-SP-11
E-Bond orInduramastic Aluminum
11
1.0-2.0 4.0-6.04.0-6.0
Current Substrate Conditions
Environmental Conditions
EENNVVIIRROONNMMEENNTTAALLCCAATTEEGGOORRYY EEXXTTEERRIIOORR
C1 Non-Corrosive Environment
C2 Atmospheres with low level of pollution. Mostly rural areas.
C3 Urban and industrial atmospheres; moderate sulfur dioxide pollution. Coastal areas with low salinity.
C4 Industrial areas and coastal areas with moderate salinity.
C5-i Industrial areas with high humidity and aggressive atmospheres.
C5-m Coastal and offshore areas with high salinity.
CCOONNDDIITTIIOONN CCOOMMPPAANNYY RRAATTIINNGG GGUUIIDDEE RRAATTIINNGG DDEEFFIINNIITTIIOONN
Non-deteriorated R - 10 to 0.1% rust
Coating almost intact; red rust covers less than 0.1% of all surfaces, Re-evaluate in 6–12 years
Slightly to moderatelydeteriorated R - 2
0.1 to 1% rustCoating somewhat weathered; may show slight staining or blistering;
after stains are wiped off, less than 1% of surface area shows rust, blistering, loose mill scale, or loose paint film.
Re-evaluate in 3–6 years.
Deteriorated R - 3
1 to 10% rustCoating thoroughly weathered, blistered, or stained, up to 10% of
surface area is covered with rust, rust blisters, hard scale or loose paint film, very little pitting visible.
Needs attention in 1–3 years
Severely deteriorated R - 410 to 50% rust. Large portion of surface is covered with rust, pits,
nodules, and non-adherent paint. Pitting is visible. Needs attention within 1 year
Totally deteriorated R - 5 Over 50% rust.
Needs immediate attention
Substation Equipment - Transformer and Regulator Cooling Fins (flo-coat only)
SSUURRFFAACCEE CCOONNDDIITTIIOONNRRAANNKKIINNGG
EENNVVIIRROONNMMEENNTTAALLRRAANNKKIINNGG
SSUURRFFAACCEEPPRREEPPAARRAATTIIOONN PPRROODDUUCCTT NNAAMMEE ## OOFF CCOOAATTSS FFIILLMM TTHHIICCKKNNEESSSS
((MMIILLSS DDFFTT))
APreviouslypainted, no or light rust
R-1, R-2 Mild to ModerateC-1 to C-3 SSPC-SP2 Full Prime – P30 Primer
Full Finish - Indurasil Enamel11
2.5-4.01.5-2.5
BPreviouslyPainted
Moderate RustR-3 Moderate
C-3 to C-4SSPC-SP2, SSPC-SP3
Spot Prime - P30 Primer (spray or brush)
Full Intermediate – P30 Primer Full Finish – Indurasil Enamel
1
11
2.5-4.02.5-4.01.5-2.5
CPreviously
Painted HeavyRust
R-4, R-5 Moderate to SevereC-3 to C-5m
SSPC-SP3, SSPC-SP6
or SSPC-SP7
Full Prime - P30 PrimerFull Intermediate – P30 Primer Full Finish – Indurasil Enamel
111
2.5-4.02.5-4.01.5-2.5
90% of Transmission Towers and Poles willrequire Systems A or B, however somestructures will corrode past the ideal“window of opportunity” and require moresurface preparation, or more primer, orgreater film thickness. Other structures willbe located near corrosive industries, and/orsevere marine exposures; and may require amore chemical resistant coatings system.Always consult with your Induron T&Drepresentative before finalizing your coatingspecification. Use the 2 charts on this pageto determine your environmental exposureranking, as well as your degree ofdeterioration/corrosion.
AASSTTMM DD 33335599 MMeetthhoodd BB 55BBRRaattiinngg ((NNoo AAddhheessiioonn LLoossss))FFllooww CCooaatteedd IInndduurraassiill GGlloossss EEnnaammeell