Electric energy meter СЕ208 - sp.energomera.ru
Transcript of Electric energy meter СЕ208 - sp.energomera.ru
СЕ208САНТ.411152.068-05.1 РЭ Operation Manual
Manufacturer:Electrotechnical Factories Energomera JSC415 Lenina Str., Stavropol, Russia 355029Tel.: (8652) 35-75-27, Fax: 56-66-90, Hot line (free): 8-800-200-75-27 e-mail: [email protected] www.energomera.ruWarranty service:217 Gagarina street, Nevinnomyssk, Stavropol region, 357106
Electric energy meterSingle-phase multifunctional
Case type S7
OKP 42 2863 6Harmonized System Codes (TN VED) 9028301 100
2 3
CONTENTS 1 SAFETY REQUIREMENTS ....................................................................................................................................52.1 Purpose ............................................................................................................................................................... 62.2 Designation of meter modifications .................................................................................................................... 82.3 The meter is certified.......................................................................................................................................... 122.4 Normal operating conditions: ............................................................................................................................. 122.5 Operating usage conditions ............................................................................................................................... 122.6 Ambient conditions ........................................................................................................................................... 132.7 Technical specifications ..................................................................................................................................... 132.8 Meter design ..................................................................................................................................................... 183 PREPARING THE METER FOR OPERATION........................................................................................................ 193.1 Unpacking ......................................................................................................................................................... 193.2 Preparing for operation ...................................................................................................................................... 193.3 Installation procedure ........................................................................................................................................ 203.4 Wiring diagrams ................................................................................................................................................ 213.5 Lithium cell replacement .................................................................................................................................... 263.6 Meter configuration ........................................................................................................................................... 274 READING THE METER ..................................................................................................................................... 274.1 Displaying information on the LCD .................................................................................................................... 274.2 Viewing total accumulated values (on an accrual basis) ...................................................................................... 295 METER VERIFICATION ..................................................................................................................................... 356 MAINTENANCE AND SEALING........................................................................................................................ 36
4
7 ROUTINE MAINTENANCE ...............................................................................................................................368 STORAGE AND TRANSPORTATION CONDITIONS .............................................................................................379 CONTAINERS AND PACKING ...........................................................................................................................3810 LABELING .....................................................................................................................................................39ANNEX A ...........................................................................................................................................................40ANNEX B ...........................................................................................................................................................41ANNEX C ...........................................................................................................................................................42
4 5
This САНТ.411152.068-05.1 РЭ Operation Manual contains brief information about CE208 S7 multifunctional single-phase electric energy meter (hereinafter referred to as the «Meter»). Complete information on the above meter is contained in САНТ.411152.068-05.1 РП User Manual, which can be found at the manufacturer’s website: www.energomena.ru/ru/products/meters/ce208-all.
When learning about the meter and operating it, you must be additionally guided by САНТ.411152.068-03.1 ФО Data Sheet (supplied with the meter) and САНТ.411152.068-05.1 РП User Manual.
Only persons who have received special training for working with voltages up to 1000 V and who have studied the Operation Manual are allowed to work with the meter.
1 SAFETY REQUIREMENTS
1.1 By operational safety, the meter meets the safety requirements of GOST 22261-94 and IEC 61010-1:2001.1.2 Protection against electric shock is ensured through the use of double or reinforced insulation according
to IEC 61010-1:2001.1.3 The insulation between all current and voltage circuits connected together and with the «ground» can
withstand a voltage of 4 kV AC at 50 Hz for 1 minute. During the test, the leads of the electrical test output device, the interface circuits are connected to the «ground» (the «ground» is a conductive foil film enclosing the meter and attached to a flat conductive surface on which the meter base is mounted).
1.4 The insulation between all current and voltage circuits connected together and with the «ground» can withstand pulse voltage of 6 kV. During the test, the leads of the electrical test output device must be connected to the «ground».
1.5 Insulation resistance between the casing and electrical circuits, at least: 20 MΩ — under conditions of clause 2.5;7 MΩ – at an ambient air temperature (40±2) °С, relative air humidity of 93%.1.6 The meter must be installed and operated in accordance with the applicable rules for technical operation of
electrical installations.1.7 Do not put foreign objects on the meter, avoid bumps.
6
2 METER DESCRIPTION
2.1 PurposeThe meter is single-phase, multifunctional, direct connection, and is designed to measure active and reactive
electric energy in single-phase AC circuits.The meter has the following functions:• multi-tariff electricity metering (with three tariff levels - event-based, external and time-based tariffing);• maintenance of the retrospective (recording the current values of energy storage devices: at the end of the
billing period (month), at the end of the day, at the end of the year and upon occurrence of a specific event);• maintaining a load profile, with the ability to customize the type of the parameters stored and the averaging
time;• measuring network parameters: voltage frequency, current in the phase and neutral wires, voltage, angle
between current and voltage, active power factor, active, reactive and apparent power;• measuring Unified Power Quality Index (UPQI) in accordance with class «S» of the measurement process
specifications in IEC 61000-4-30:2008: stable voltage deviation, network frequency deviation, duration and depth of voltage dips, duration and maximum value of overvoltage, interruptions in power supply;
• power quality analysis for compliance with quality standards in accordance with EN50160:2010;• indicating the instance of violating an individual power quality indicator on the LCD (disabled by default);• recording the violation of an individual power quality indicator (event logs available for reading on the interface);• monitoring active power consumption;• monitoring «instantaneous power» consumption;• monitoring active energy consumption (control of energy limits, prepaid mode, low consumption control);• monitoring supply network voltage;• monitoring current;• monitoring network frequency;• monitoring the oncoming power flow (in the phase and neutral wires);
6 7
• telemetric output with the ability to use it as a «relay»;• alarm using the interface (the ability to act as an initiator of communication with the level of DCU or HES during:
terminal cover opening; exposure to a magnetic field; reparameterization; maximum power excess; deviation from the normalized value of voltage level, etc., in accordance with the full list, for details, see the user manual САНТ.411152.068-05.1 РП);
• time accounting;• self-diagnostics;• information protection;• protection against unauthorized opening (electronic seals);• magnetic field sensor;• event logs with recording of: terminal cover opening; case opening; dates of last re-programming; exposure
to a magnetic field causing unacceptable deviations of the metrological characteristics of the metering device; facts of communication with the metering device that led to data changes; voltage deviations from the device’s nominal values in the measuring circuits; results of self-diagnostics; changes in the current values of time and date during time synchronization (at least 3,500 records using the DMLS protocol), etc., for details, see the user manual САНТ.411152.068-05.1 РП;
• mechanism for flexible adjustment of the reaction to events occurring in the meter;• DLMS/COSEM exchange protocol support;• display of information on the LCD accompanied by OBIS codes;• management of consumer load according to a predefined schedule.The meter’s functions are described in detail in the full version of САНТ.411152.068-05.1 РП.The meter can be used in Automatic Informational and Measuring Systems for Commercial Electric Power
Metering (AMI systems) to transfer the parameters measured or calculated to the control room for controlling, accounting and distributing electric power.
The measurement results are obtained through processing and calculating current and voltage input signals performed by the microprocessor circuit on the meter board. The measured data and other information are displayed
8
on a liquid crystal display (LCD) and can be transmitted via an optical port or one of the interfaces.The meter has an electronic measuring mechanism performing active and reactive energy measurement in
kW•h and kVar•h, respectively, cumulatively and according to eight tariffs in one or two (for a bi-directional meter) directions of electric energy metering.
The meter has two additional electronic measuring mechanisms performing active and reactive energy metering in kW•h and kVar•h, respectively, in one or two (for a bi-directional meter) directions of electric energy metering by specified events (tariff 9, tariff 10).
Changing time of the measuring mechanism indications complies with the requirements of IEC 62052-11:2003, IEC 62053-21:2003 and IEC 62053-23:2003.
2.2 Designation of meter modifications 2.2.1 The structure of meter designation is shown in Figure 2.1.
8 9
СЕ 208 S7.Х4Х.Х.OХ.XXXX XXX
Designation of the integrated communication moduleAdditional functions:See Table 2.3.Integrated communication interfaces:See Table 2.2.Number of measuring elements:1 – meter with one current sensor (in the phase circuit);2 – meter with two current sensors (in the phase and neutral circuits);Nominal or base (max.) current:5 – 5(60) А;6 – 5(100) А.Nominal voltage (phase/line):4 – 3x230/400 V.Active/reactive energy accuracy class:8 – 1/2 for active/reactive energy;7 – 1/1 for active/reactive energy.Body type and number:S7 – for 3 screws mounting
Figure 2.1 – Designation structure
10
Table 2.1
Item No. Designation Interface
1 O Optical port
2 А RS485
3 P PLC interface
4 R1 Radio interface with a built-in antenna
5 R2 Radio interface with an external antenna socket
6 G GSM/GPRS modem
7 N Ethernet interface
Table 2.2
Item No. Designation Additional function
1 Q* Load control relay
2 Y* 2 directions of metering
3 U* Network parameters
4 V* Electronic seals
5 F* Magnetic field sensor
6 L* LCD backlight
7 Z* Extended set of parameters
* — by default, included in all meter versions
10 11
2.2.2 Meter modifications, nominal voltage, the meter constant and the position of the decimal point when displaying energy values on the LCD, depending on the nominal voltage (Unom), base (Ib) and maximum (Imax) current, are shown in Table 2.1.
Table 2.3
Meter designation Nominal voltage, V
Nominal, base (max.) current, A
Meter constantimp/(kW•h),imp/(kVar•h)
Positionof the decimal
point
CE208 S7.845.X...X; CE208 S7.745.X...X
230 5 (60) 2000 000000.00
CE208 S7.846.X...X; CE208 S7.746.X...X
230 5 (100) 2000 000000.00
2.2.3 Example of a meter inscriptionWhen ordering a meter, the required version is determined by the structure of the designation shown
in Figure 2.1.A meter inscription example: accuracy class 1 meter for active energy and 2 for reactive energy (8), with nominal
voltage of 230 V (4), with base current 5 A and maximum current 60 A (5), with two current sensors (in the phase and neutral channels) (2), with an optical port (O), with an RS485 interface (A), with a load control relay (Q), for two measuring directions (Y), measuring power quality parameters (U), with a cover opening control (V), with a magnetic field sensor (F), with an indicator backlight (L) and an extended set of parameters (Z):
Multifunctional single-phase electric meterCE208 S7.845.2.OA.QYUVFLZ ТУ 4228-090-63919543-2012.
12
2.3 The meter is certifiedThe information on meter certification is given in the САНТ.411152.068-03.1 ФО Data Sheet
2.4 Normal operating conditions:– ambient air temperature (23±2)°С;– ambient air relative humidity (30-80)%;– atmospheric pressure from 70 to 106.7 kPa (537-800 mm Hg).– network frequency (50±0.5) Hz;– the shape of the voltage curve of the measuring network is sinusoidal with a nonsinusoidal factor according to
EN50160:2010*.
2.5 Operating usage conditionsThe meter is connected to a single-phase AC network and installed in closed premises with operating usage
conditions:– temperature range from minus 45 to 70 °С– ambient air relative humidity (30-98) %;– atmospheric pressure from 70 to 106.7 kPa (537...800 mm Hg).– network frequency (50±2.5) Hz;– the shape of the voltage curve of the measuring network is sinusoidal with a nonsinusoidal factor according to
EN50160:2010*.* ATTENTION! WHEN OPERATING METERS IN CONJUNCTION WITH A POWERFUL NON-LINEAR LOAD
WHICH CAN DEGRADE THE POWER QUALITY (FOR EXAMPLE, AN ELECTRIC DRIVE WITH A FREQUENCY CONVERTER), YOU SHOULD USE SPECIAL FILTERING DEVICES.
OTHERWISE, THE METER MAY OVERHEAT AND FAIL. FAILURE OF THE METERS DUE TO POOR POWER QUALITY IS NOT A WARRANTY CASE. THE MANUFACTURER IS NOT RESPONSIBLE FOR DAMAGE TO THE CONSUMER’S PROPERTY RESULTING FROM VIOLATION OF THE OPERATING CONDITIONS OF THE METERS DESCRIBED IN THIS OPERATION MANUAL, INCLUDING DUE TO A POOR POWER QUALITY.
12 13
2.6 Ambient conditions2.6.1 In terms of resistance to climatic influences, the meter belongs to group 4 in accordance with GOST 22261-94, with an extended range of temperature and humidity, satisfying version T category 3 in
accordance with GOST 15150-69.In terms of resistance to mechanical impacts, the meter belongs to group 2 according to GOST 22261-94.2.6.2 The meter is protected from dust and water. The protection degree of the meter is IP51 according to
IEC 60529:2013.2.6.3 The meter is resistant against single impacts with a maximum acceleration of 300 m/s2.2.6.4 The meter is resistant to vibrations in the frequency range (10-150) Hz.2.6.5 The meter body withstands impact of spring hammer blows with kinetic energy (0.20±0.02) J applied to
the external surfaces of the body, including the windows, and to the terminal cover.2.6.6 Parts and components of the meter that are designed for operation in areas with a tropical climate, in terms
of resistance to the effects of mold fungi, comply with the requirements of GOST 9.048-89.The permissible growth of fungi amounts up to 3 points according to GOST 9.048-89.
2.7 Technical specifications 2.7.1 The meters meet the requirements of IEC 62052-11:2003, IEC 62053-21:2003 and IEC 62053-23:2003.2.7.2 The technical specifications given with tolerances or limit values are considered guaranteed. Values without
tolerances are for reference only.Main technical specifications are given in Table 2.4.Limits of the permissible errors of the measured values are given in Annex A.
14
Table 2.4
Specification name Specification value Note
Base (max.) currents 5(60); 5(100) А Direct connection
Nominal phase voltage 230 V
Operating phase voltage (0.55...1.21) Unom V
Nominal network frequency (50±2.5) Hz
Non-sinusoidal factor of the measuring network voltage, %, max
–In accordance with
EN50160:2010
Sensitivity threshold 0,002 Ib
Number of decimal places on the LCD from Table 2.1
Apparent power consumed by each current circuit, max
0.3 (V•A) for version Q 0.05(V•A) for others
With nominal (base) current
Apparent (active) power (consumed by voltage circuit at nominal voltage, max
9(V•A) (1.1 W) With nominal voltage
Active power consumed by the built-in communication modules at the nominal voltage value, max, W
3 WFor versions with
communication modules
Limit of the clock basic absolute error ± 0.5 s/day
Manual and system correction, clock rate ± 29 s Once a day
14 15
Specification name Specification value Note
Limit of the clock additionaltemperature error
± 0.15 s/°С per day From minus 10 to 45 °С
± 0.2 s/°C per dayFrom minus 40 to minus 10 °С
and from 45 to 70 °С
Duration of data storage whenpower is off
30 years
Built-in lithium cell service life 16 yearsIt is possible to install an
additional external lithium cell (see section 3.5)
Additional external lithium cell service life 5 years
Number of tariffs in the daily schedule up to 8
Number of tariff zones in a day up to 16
Number of seasonal schedules in a year up to 12
Number of exclusive days up to 80
Number of daily rate scales up to 32
Number of power control zones in a day 3
Number of power control zone schedules
up to 12
Power averaging time1; 2; 3; 4; 5; б; 10; 12; 15;
20, 30, 60 min
Table 2.4 (continued)
16
1The profile storage depth is directly proportional to the averaging time with reduction to the integer part.
Specification name Specification value Note
Number of accounted tariffs by events 2 Tariffs 9 and 10
Depth of monthly energy storageby tariffs
at least 40 months Current and 39 previous
Depth of daily energy storage, accumulated by tariffs
128 days Current and 127 previous
Depth of annual energy storage, accumulated by tariffs
10 years Current and 9 previous
Depth of event energy storage by tariffs 20 events
Depth of monthly maximum power storage in the three power control zones
13 months Current and 12 previous
Number of parameters in a profile up to 6
Profile storage depth, days1 128With an averaging time
of 60 minutes
Averaging time of load profiles1; 2; 3; 4; 5; 6; 10; 12; 15;
20, 30, 60 min
Event logsFor details, see
САНТ.411152.068-05.1 РП
Table 2.4 (continued)
16 17
Specification name Specification value Note
Nominal (permissible) voltage of electrical pulse outputs, max
10 (24) V DC voltage
Nominal (permissible) current value of electrical pulse outputs, max
10 (30) mA DC voltage
Duration of output pulses 35 ms In a TM mode
Interface communication speed From 300 to 19200 bdDepending on the characteristics of
communication modules
Optical port communication speed From 300 to 19200 bd
Meter update time 1 s
Reading time of any meter parameter via interfaces
from 0.1 to 1000 s (at 9600 bd)
Depends on the parameter type
Initial start, max 5 sFrom the moment the voltage
is supplied
Meter weight, max 1 kg
Overall dimensions (height; width; length), max
200; 122; 73;
Mean time to failure 220000 h
Table 2.4 (continued)
18
Specification name Specification value Note
Average service life 30 years
Meter cover and terminal block cover opening control
Meter cover and terminal cover opening logs
Protection against unauthorized accessMeter password,
hardware lock
Maximum relay current during the turn-off (turn-on) operation, does not exceed
1.1·Imax А
Switching wear resistance of relay contacts
5000 cycles
2.8 Meter designThe meter design complies with the requirements of IEC 62052-11:2003 and the manufacturer’s drawings.The meter is made in a plastic case.The appearance of the meter is given in Annex B.In general, the meter body consists of two parts, upper and lower, mating along the perimeter, a transparent window
and a removable transparent terminal cover.On the front panel of the meter, there are the following:• liquid crystal indicator;• one indicator of active energy metering and one indicator of reactive energy metering. The indicators operate at the
frequency of the main transmitter. The indicators can be used to calibrate the meter.• indicator of functioning;
Table 2.4 (continued)
18 19
• optical port elements;• «FRAME» and «VIEW» buttons;The clamps for connecting the meter to the network, to interface lines and to pulse outputs,«ACCESS» button are closable with a plastic cover.In order to access the «ACCESS» button (programming permission), you need to remove the sealing label of the energy
supplying company that installed the meter.The meter comprises:• measuring module;• supply module;• load control relay (Q) module;• one or two current sensors (shunts), depending on the version.
3 PREPARING THE METER FOR OPERATION
The meter is supplied with a set of everything necessary for installation at operating site. The САНТ.411152.068-05.1 РП has a comprehensive set of information for installing the meter at operating site.3.1 Unpacking3.1.1 After unpacking, inspect the meter visually, verify that there are no mechanical damages, and check
the presence and integrity of the seals.3.2 Preparing for operation3.2.1 The meters produced by the manufacturer have factory settings. Changes to factory settings are made in
accordance with the САНТ.411152.068-05.1 РП by companies authorized to configure the meter.ATTENTION! PRESENCE OF READINGS ON THE METERING DEVICE IS CAUSED BY CHECKING THE METER
AT THE MANUFACTURER’S, AND DOES NOT ATTEST TO ITS WEAR OR OPERATION.
20
3.3 Installation procedure3.3.1 Connect the electric meter to a single-phase AC network with a nominal voltage of 230 V. To do this, remove
the terminal cover and connect the wires by securing them in the terminals of the block according to the wiring diagram printed on the cover, or given in Annex C.
When installing a meter, the wire (cable) must be stripped of insulation to approximately the amount shown in Table 3.1. The stripped part of the wire should be smooth, without bends. Insert the wire into the terminal clamp without tilts. It is not allowed to get a wire with insulation into the terminal, as well as for the stripped area to protrude outside the block. First, tighten the top screw. Pull the wire lightly to make sure that it has been clamped. Then tighten the bottom screw. After several minutes, tighten the connection again.
The diameter of the wires connected to the meter is shown in Table 3.1.
Таблица 3.1
Meter with a current range The length of the stripped wire, mm Wire cross-section diameter2, mm
5(60) А 27 (1 ÷ 7)
5(100) А 20 (1 ÷ 8)
If it is necessary to connect the meter into an AMI system, connect the signal wires to the interface outputs in accordance with the wiring diagram.
Make sure that the time and date readings of the meter correspond to the actual values, otherwise set the date and time (for details see САНТ.411152.068-05.1 РП).
Seal the covers and the «ACCESS» button.Initialize the electronic seal of the clamp cover (see САНТ.411152.068-05.1 РП). 2The range of the wire diameter is specified based on the possibility of its connection to the meter block. The required cross-section
(and therefore the diameter) of the wire is selected depending on the value of the maximum current
20 21
3.4 Wiring diagramsThe designation of meter contacts is shown in Figure 3.1
Figure 3.1 – Designation of CE208 S7 meter pins
1 – Meter designation.2 – LCD indicator.3 – Power supply indicator.4 – Active energy indicator.5 – Reactive energy indicator.6 – Optical port.7 – «Frame» button.8 – «View» button.9 – Cover opening control button.10 – «Access» button.11 – Holder for an additional battery.
pin 7 – TM1 pulse output «+» contact;pin 8 – TM1 pulse output «-» contact;pin 9* – RS485 interface «A» contact;pin 10* – RS485 interface «B» contact;pin 11* – RS485 interface «-» power supply;pin 12* – RS485 interface «+» power supply.* – only for modifications with an RS485 interface
22
designation of pins of the meter with RS485 interface designation of pins of the meter with radio modules, with external antenna
designation of pins of the meter with Ethernet module designation of pins of the meter with GSM module
22 23
3.4.1 Pulse output connectionThe meter features TM1 pulse output. The output may be used (programmed) as the main transmitting output
device of active or reactive energy, with parameters according to IEC 62052-11:2003, IEC 62053-21:2003 and IEC 62053-23:2003. The output is implemented on transistors with an “open” collector and is intended for switching DC voltage. Nominal supply voltage (10±2) V, maximum allowable value is 24 V.
The value of the switched nominal current is (10±1) mA, the maximum allowable value is 30 mA. By default, TM1 generates pulses proportional to the imported and exported active energies (Ai + Ae). The output can be reconfigured to generate pulses proportional to the individual type of measured energy or as a relay (for details, see САНТ.411152.068-05.1 РП).
To ensure operation of the pulse output, it is necessary to supply DC voltage according to the diagram shown in Figure 3.2
(8÷24) В СЕ208 «7»
«8»
- R
+
Figure 3.2 – Connection diagram of the meter’s pulse outputs. The value of electrical resistance R in the load circuit of the pulse output is determined by the following formula:
where U – is the output supply voltage, V.
(3.1)
24
3.4.2 Connection of meter interfacesThe meter provides data exchange with external data processing devices through its optical port and one of the
interfaces, according to the meter modification, in accordance with GOST IEC 61107-2011 protocol and DLMS (for more details, see САНТ.411152.068-05.1 РП).
The optical port is designed in accordance with GOST IEC 61107-2011. The optical port is intended for local connection of the meter via an optical probe connected to the PC serial port.
3.4.2.1 RS485 interface connectionThe meter versions with an RS485 interface make it possible to combine up to 256 devices (meters) on one
common bus. When connecting two or more metering devices, it is necessary to assign an individual address for each one (for details, see САНТ.411152.068-05.1 РП).
The meter’s RS485 interface connection diagram is shown in Figure 3.3.If the ground potentials at the installation sites of meters and data concentrator units (DCU) are equal, then it is
enough to connect pin 11 to the zero potential point, otherwise take potential equalization measures.In the event that the length of the communication lines does not exceed several meters and there are no sources
of interference, then the connection diagram can be significantly simplified by connecting the meter to the DCU or PC using only two signal wires A and B.
The exact resistance value of the termination resistors3, as well as the need to use them, should be determined during the preliminary survey of the facility. In general, if the communication line is up to 1000 m and the exchange rate is up to 9600 bd, the use of termination resistors is not recommended4.
3.4.2.2 Connection of PLC, GSM, Ethernet, radio interfacesThe connection of the CE208 meter to the PC via communication modules is described in detail in
САНТ.411152.068-05.1 РП. 3 It also depends on the cable brand, its length, linear resistance, as well as the input impedance of all other receivers in the line.4 If the termination resistor is already installed inside the data concentrator unit, it can be disconnected using the appropriate
microswitches (jumpers) of the data concentrator unit.
24 25
R – termination resistor with a rating equal to the cable wave impedance
Figure 3.3 – CE208 S7 meter connection diagram with an RS485 interface using an external adapterRS485/RS232, RS485/USB to the PC
Note – Biasing resistors (+R) and (-R) (nominal 100 kΩ) are installed in the meter and are always connected to the A and B lines, respectively. When it is necessary to connect external biasing resistors (resistance of 560 Ω), you should: make contact between pin 9 and pin 12, in this case the +R resistor installed in the meter is activated; between pins 10 and 11 install an external (-R) resistor with a resistance of 560 Ω. In order to avoid line overload, activation of biasing resistors with a resistance of 560 Ω, as a rule, is only performed for the extreme meters.
3.4.2.3 To exchange data via the optical interface, an optical probe in accordance with GOST IEC 61107-2011 is used.
26
3.5 Lithium cell replacementIn the meter, an integrated CR14250BL-VY lithium cell or equivalent is used for the real-time clock.The lithium cell should only be replaced by a service company or in the workshop of the utility or organization that
is authorized to repair and check the meter.In the meter, it is necessary to remove the seals of the utility, the service department and state verification,
remove the meter cover, and remove the top meter board from the connector. Solder out the lithium cell from the board and replace it. To replace the lithium cell, it is necessary to comply with the polarity using the symbols on the board. CR14250BL-VY lithium cell by EEMB is recommended. The lithium cell should have the following technical specifications: supply voltage +3.0 V; capacity at least 900 (mA•h); working temperature range from minus 40 to 85 °C; self-discharge max 1% per year.
After replacing the lithium cell, set the date and time, initialize the electronic seal of the body (see САНТ.411152.068-05.1 РП). After replacing the lithium cell, install the board in its original place, close and seal the meter, and verify it. With each replacement, it is necessary to make a note in the Data Sheet – who replaced the lithium cell, when and the type of the replacement battery.
In the meter, it is possible to install an additional lithium cell (in case that the integrated battery is discharged) without opening the meter body. To connect (or replace) it, remove the cover of the clamps (Figure 3.1) and remove the lithium cell holder, install a new lithium cell in the holder, then reinstall the holder. CR2032 lithium cell or equivalent is recommended. The lithium cell should have the following technical specifications: supply voltage +3.0 V; capacity at least 250 (mA•h); working temperature range from minus 40 to 85 °C; self-discharge max 1% per year.
Note — When the meter is turned off, replacing the lithium cell will stop the clock (the LCD displays «Attention» ), so after the replacement of the lithium cell, you must program the current time («Attention» icon will disappear).
ATTENTION! YOU MAY REPLACE THE ADDITIONAL CR2032 LITHIUM CELL WHEN THE VOLTAGE IS ON, AT THE SAME TIME OBSERVE SAFETY PRECAUTIONS, AS THE LITHIUM CELL IS UNDER VOLTAGE OF 230 V.
26 27
3.6 Meter configurationConfiguration is carried out according to САНТ.411152.068-05.1 РП, which is available at the manufacturer’s
website:www.energomera.ru/ru/products/meters/ce208-all.
4 READING THE METER
The meter can be read both manually and in the automated mode.In the automated mode, full information on energy consumption can be obtained using a PC or AMI system via
the interface.In the manual mode, data is displayed on the LCD in a window eight decimal places wide (with a decimal point).
4.1 Displaying information on the LCD 4.1.1 A complete list of output formats of measured, calculated and accumulated parameters is given in Table 4.1.The measurement units of the displayed energy/power values are indicated respectively as «kW•h» «kVAr•h»,
«MW•h» «MVAr•h» or «MkW•h» «MkVAr•h», respectively, and characterize the type of indicated energy, respectively: active and reactive.
28
Table 4.1
Name of output parameters
To LCD By interfaces
Measure-mentunits
Number of dig-its left/right of
the point
Measure-mentunits
Number of digits left/right of the
point
Voltage V 4 digits V /3
Current А 4 digits А /4
Active power W-kW 4 digits kW /5
Reactive power Var-kVar 4 digits kVar /5
Apparent power VA-kVA 4 digits kVA /5
Power factor /3 /3
Angle between current and voltage ◦ /1 ◦ /1
Network frequency Hz /2 Hz /2
Active energy on an accrual basis (monthly, daily accumulation) kW•h 6/2 kW•h /5
Reactive energy on an accrual basis kVar•h 6/2 kVar•h /5
Averaged power values of the load profiles
kW /5
28 29
4.2 Viewing total accumulated values (on an accrual basis)The amount of active imported, active exported (only for bi-directional meters), reactive imported and exported
energy on an accrual basis, cumulatively and by tariffs is available for viewing on the meter’s LCD in the first group of parameters.
The meter keeps record metering to tariffs, according to the specified tariffing parameters and the time of the built-in clock. The current tariff and the type of energy measured is displayed on the meter’s LCD with the corresponding OBIS code (in the upper left corner of the LCD indicator (see Figure 4.1)), according to the scheme given in Table 4.2.
In the event of an overcurrent in the circuit of the neutral wire by 5 (or 10)% relative to the current in the circuit of the phase wire and the allowed metering by the neutral wire, the consumption metering is performed via the neutral wire. In this case, «N» symbol will be displayed on the LCD.
OBIS code
Figure 4.1 — Appearance of the CE208 S7 meter LCD indicator
30
Table 4.2 – OBIS code values for the first group of meter parameters
OBIS code value Type of accounted energy Tariff
1.8.0 Active imported
A+
Total by tariffs 1-8
1.8.1 Active imported Tariff 1
1.8.2 Active imported Tariff 2
•••
•••
•••
1.8.A Active imported Tariff 10
1.8.P Active imported Cumulatively by the phase wire
1.8.n Active imported Cumulatively by the neutral wire
2.8.0 Active exported
A-
Cumulatively by all tariffs
2.8.1 Active exported Tariff 1
2.8.2 Active exported Tariff 2
•••
•••
•••
30 31
OBIS code value Type of accounted energy Tariff
2.8.A Active exported Tariff 10
2.8.P Active exported Cumulatively by the phase wire
2.8.n Active exported Cumulatively by the neutral wire
3.8.0 Reactive imported
R+
Cumulatively by all tariffs
3.8.1 Reactive imported Tariff 1
3.8.2 Reactive imported Tariff 2
•••
•••
•••
3.8.A Reactive imported Tariff 10
3.8.P Reactive imported Cumulatively by the phase wire
3.8.n Reactive imported Cumulatively by the neutral wire
4.8.0 Reactive exported Cumulatively by all tariffs
4.8.1 Reactive exported Tariff 1
4.8.2 Reactive exported Tariff 2
Table 4.2 (continued)
32
OBIS code value Type of accounted energy Tariff
• • R- •
4.8.A Reactive exported Tariff 10
4.8.P Reactive exported Cumulatively by the phase wire
4.8.n Reactive exported Cumulatively by the neutral wire
4.2.1 Viewing total accumulations when the meter is powered from the networkGo to the first group of meter parameters. To do this, press6 and hold the «FRAME» button, then, after
«GROUP 1» appears on the indicator, release the button. On the LCD screen, the first frame of the viewed «GROUP 1» group parameters will be displayed, containing information on the amount of imported active energy, cumulatively by all tariffs.
By briefly pressing the «FRAME» button, select the type of accounted energy:
«A+» → «A-» → «R+» → «R-»By briefly pressing the «VIEW» button, select a tariff:
«Total » → « Tariff 1 » → « Tariff 2 » → « Tariff 10 » 6 In meter modifications with LCD backlight, when the backlight is off, the first short pressing of the «FRAME» button turns on the
backlight without changing the frame.
Table 4.2 (continued)
32 33
Figure 4.2 shows the value («00089.38 kW•h») of the active imported energy on an accrual basis for the fifth tariff (OBIS code value is «1.8.5»). At the present moment:
• the active tariff is 5 («Т5»);• the current time is «09h08m06s»;• the reactive power direction is «Q+», active power direction is «P-»;• phase «L1» is normal, energy is measured by the phase wire.
Figure 4.2 – Active imported energy on an accrual basis for the eights tariff
Figure 4.3 shows the value («00096.89 kVAr•h») of the reactive exported energy on an accrual basis for the third tariff (OBIS code value is «4.8.3»). At the present moment:
• the active tariff is 3 («Т3»);• the current time is «18h58m39s»;• the reactive power direction is «Q+», active power direction is «P+»;• phase «L1» is normal, energy is measured by the neutral wire.
34
Figure 4.3 – Reactive exported energy on an accrual basis for the third tariff
4.2.2 Viewing the total accumulations of a de-energized meter (when powered by the built-in lithium cell).Press the «FRAME» button briefly. On the LCD screen, the first frame of the viewed «GROUP 1» group parameters
will be displayed, containing information on the amount of consumed active energy, cumulatively, by all tariffs (OBIS code value is «1.8.0»). Subsequently pressing the «Frame» button briefly will send to the LCD information on the accounted energy type and tariff according to the scheme:
«А+, total» → «А+», «Tariff 1» → «А+», «Tariff 2» →...→ «А+ →», «Tariff 10» →→ «А-», «total» → «А-», «Tariff 1» → «А-», «Tariff 2» →...→ «А-», «Tariff 10» →→ «R+», «total» → «R+», «Tariff 1» → «R+», «Tariff 2» →...→ «R+», «Tariff 10» → → «R-», «total» → «R-», «Tariff 1» → «R-», «Tariff 2» →...→ «R-», «Tariff 10» →→ «current time and date»
Figure 4.4 shows the value («00055.03 kVAr•h») of the reactive exported energy on an accrual basis for the first tariff (OBIS code value is «4.8.1»). At the present moment:
34 35
• the meter is disconnected from the network (indicator of the presence of phase «L1» is off);• the current time is «10h50m33s»;
Figure 4.4 – Reactive exported energy on an accrual basis for the first tariff
ATTENTION! The meter is able to mask the readings on the LCD. In case of masking, only available information about the accrual result will be displayed on the meter’s LCD. For details on masking, see САНТ.411152.068-05.1 РП.
5 METER VERIFICATION
5.1 The verification is carried out according to «CE208 multifunctional single-phase electric meters. САНТ.411152.068 Д1 verification method», when released from production, after mid-term repair or periodically
once every 167 years.
7For meters supplied to the Republic of Kazakhstan, the interval between verifications is 8 years.
36
6 MAINTENANCE AND SEALING
6.1 Maintenance of the meter at the installation sites consists in systematic monitoring of its operation and eliminating meter errors and malfunctions.
ATTENTION! IN CASE OF LCD FAILURE, THE INFORMATION IS STORED FOR 30 YEARS. YOU CAN READ THE INFORMATION VIA THE METER INTERFACE BY CONNECTING THE METER TO THE POWER NETWORK.
6.2 The cover of the terminal clamps is sealed by the company commissioning the meter.The meter cover is sealed with two seals: by the verification officer and by the QC department.The cover of the terminal clamps of the meter is sealed with a single seal.The «ACCESS» button is sealed by attaching a self-destructive sealing label.
7 ROUTINE MAINTENANCE
7.1 Possible malfunctions and methods for their elimination by the consumer are given in Table 7.1.
Table 7.1
Name and signs of the malfunction Possible cause Elimination method
1 The LCD is off
1 No voltage at the meter voltage terminals2 Failure in the meter’s electronic circuit
1 Check for voltage at the meter’s voltage terminals2 Send the meter to repairs
36 37
Name and signs of the malfunction Possible cause Elimination method
2 The information displayed on the LCD is not changing, no reaction to the buttons
1 Failure in the meter's electronic circuit 1 Send the meter to repairs
3 When a load is connected to the meter, the measuring direction does not correspond to the true value
1 Incorrect connection of parallel and/or serial circuits of the meter
1 Check the correct connection of circuits
4 During periodic verification, the error went beyond the permissible limits
1 The parameters of the elements determining accuracy in the meter’s electronic circuit are gone2 Failure in the meter’s electronic circuit
1 Send the meter to repairs
5 Missing or poor power accounting via telemetry channels
1 Wrong connection of telemetry lines to the meter’s terminals2 The telemetry outputs are poorly configured
1 Connect the telemetry lines in accordance with the OM2 Configure the telemetry outputs correctly
8 STORAGE AND TRANSPORTATION CONDITIONS
8.1 Meters shall be stored in the manufacturer’s packaging at an ambient temperature of 5 to 40°C and a relative humidity of 80% at a temperature of 25 °C.
Table 7.1 (continued)
38
8.2 Meters are transported in closed vehicles of any kind.Limiting transportation conditions:– ambient air temperature from minus 40 to plus 70 °С.– relative humidity 98% at a temperature of 35 °С.– atmospheric pressure from 70 to 106.7 kPa (537...800 mm Hg).– transportation bounce for 1 hour with an acceleration of 30 m/s2 with a shocks rate of 80 to 120 per minute.
9 CONTAINERS AND PACKING
9.1 The meters, operational and shipping documentation are packed in accordance with the manufacturer’s drawings.
9.2 When prepared for packaging, the meter is placed in a plastic bag in accordance with GOST 12302-2013, in a consumer packaging made of T15EE cardboard, GOST R 52901-2007.9.3 Operational documentation is in consumer packaging on top of the product. The consumer packaging is
covered with packing tape.9.4 The meters, packed in consumer packaging, are placed in a shipping container, which is a cardboard box
made according to the manufacturer’s drawings.9.5 The shipping document is enclosed in the box, including a packing list containing the following information:– name and symbol of the meters, their quantity;– packing date;– signature of the person responsible for packing;– stamp of the QC department.The box is sealed.9.6 Overall dimensions of the package, net weight, gross weight meet the requirements of the manufacturer’s
design documentation.
38 39
10 LABELING
10.1 Information applied to the front panel of the meter by offset printing or in another way not degrading the quality:
– meter type designation — CE208;– accuracy class according to IEC 62052-11:2003, IEC 62053-21:2003 and IEC 62053-23:2003;– meter constant in accordance with Table 2.3;– a bar code8 including the year of manufacture, the number of the meter and other additional information;– nominal voltage;– base and max. current;– frequency 50 Hz;– the number of phases and the number of wires in the circuit for which the counter is intended, as a graphic
symbol in accordance with GOST 25372-95;– trademark of the manufacturing enterprise ENERGOMERA;– IEC 62052-11:2003, IEC 62053-21:2003 and IEC 62053-23:2003.– measuring instruments approval type sign image;– the image of the common EAC circulation mark when receiving the certificate;– a double square sign for meters of protection class II placed into an insulating housing;insulation testing voltage (C2 symbol as per GOST 23217-78);– inscription – RUSSIA;– interface type in accordance with the structure of meter designation given in clause 2.2;– labeling of controls «FRAME», «VIEW», «ACCESS».The meter activation diagrams are given on the cover of the clamping block or on the meter’s front panel. On the
cover of the clamping block there is an «Attention» sign ( ) – according to GOST 23217-78. 8 The barcode of split metering devices is applied by laser printing and is weatherproof during the service life of the device.
40
ANNEX A(required)
The permissible error limits of the measured valuesA.1 The limits of the permissible basic relative error when measuring the root-mean-square values of current δI,
in percent, do not exceed the values shown in Table A.1.
Table А.1
Current value for meters Limits of permissible basic error δI, %, for active/reactive energy accuracy class meters
with direct connection 1/1 1/2
0,05 Ib ≤ I ≤ Imax ± 1,0 ± 1,0
A.2 The limits of the permissible basic relative error when measuring the root-mean-square values of phase voltage δU, in percent, do not exceed the values shown in Table A.2.
Table А.2
Voltage value
Limits of the permissible basic error δU, %, for accuracy class meters
1/1 1/2
0,55 UNOM ≤ U ≤ 1,21 UNOM ± 0,5 ± 0,5