ELECTRIC ACTUATOR & VALVE - AUTOMA-INT
Transcript of ELECTRIC ACTUATOR & VALVE - AUTOMA-INT
ELECTRIC ACTUATOR & VALVE
www.automa-int.com
VER 0315.03
2
ROTARY ACTUATOR
Hard anodized Aluminum casting and external epoxy powder coated against severe industrialenvironment.
Sealed by O-ring in all interfaces, and double o-ring sealing for IP68(option)
EP type grease, maintenance free service for a long period time
Difference size depending on actuator torque, and knob on hand wheel for easy operation
Precisely machined double worm gear c/w minimum back-lash, low noise, high output torque
Provided by double worm gearing to keep position of valve unchanged against reverse torque fromvalve
● Housing
● Sealing
● Lubrication
● Hand wheel
● Gear
● Self locking
3
ROTARY TYPE ACTUATOR
External mechanical stopper- To prevent over run of travel angle when limit switch fails
Cable entries- Standard 2 X PF 3/4″(Max 1″) cable entry for various
cable gland
Manual override- Auto/Manual switch able lever hand wheel engagement for
emergency manual operating- Drive force automatically resorted by motor start unless
lever padlock to prevent it
Removable drive bushing andISO5211 mounting base- Easy machining for step adaption- Standard ISO5211 mounting base(F03 ~ F16)for easy mounting on valve
- Large size drive bushing accept large valve stem
Terminal block- Specially designed induction motor generate high starting
torque and high efficiency equip with thermal protector toprevent damage from over heating
Space Heater- Anti-condensation equip with thermal
4
ROTARY TYPE ACTUATOR
Captive cover bolt- Cover bolts are captive type designed to prevent loosing
during maintenance or installation
- All external bolts are stainless steel for rust prevention
Torque switches(Open/Close)- To protect actuator from damage caused by overload from
the driven valve over the whole travel
Potentiometer kit(PK)- High resolution potentiometer and precisely machined
gearing are directly engaged with drive shaft to feedbackcontinuous position of valve
Limit switches- Directly engaged with driving shaft to set accurate position
of valve- 1 ea for each travel end (open/close)- Optional Extra Limit Switches
(Max 4 ea for each end)
Indicator position with arrow supported Byspring- Large size position directly engaged with driving shaft for
better visibility from a distance- Spring loaded underneath keeps set position unchanged
unless used move it
5
ELECTRIC ROTARY TYPE ACTUATOR
● Technical Information
ModelRatedtorque
Nm %
Oper.time
50/60Hz90。
Dutycycle
Max boresizemm
Motor insula-
tion class
Rated current (A) 50/60Hz
1Phase 3Phase DC
110V 220V 380V 440V 24V Kg90。
No ofturns
Weight
▶Small ATM-Series
ATM0020
ATM0040
ATM0080
25
40
80
50
50
50
1
3
7
N/A
7.5
7
3.0
3.5
2.9
E
E
E
□9×9
□14×14
□17×17
11
14/12
16/14
0.28/0.40
0.30/0.42
0.17/0.16
0.03/0.31
0.32/0.33
0.18/0.17
0.26/0.25
0.29/0.28
0.48/0.46
0.45/0.44
0.49/0.48
0.92/0.88
▶Large ATM-Series
ATM6000
ATM9000
6000
9000
30
30
152
152
39
39
-
-
F
F
Ø120
Ø120
□100
□100
178/149
178/149
2.3/2.2
2.5/2.4
1.5/1.8
1.6/2.0
2.95/3.15
3.75/3.85
-
-
▶Regular-ATM-Series
ATM0100
ATM0160
ATM0240
ATM0350
ATM0500
ATM0800
ATM1100
ATM2000
ATM3000
100
160
240
350
500
800
1100
2000
3000
40
30
30
30
30
30
30
30
30
7
15
15
20
20
25
25
42
42
10
12
12
14
14
17
17
13
13
2.8
1.8
2.4
3.8
5.0
-
-
-
-
F
F
F
F
F
F
F
F
F
Ø22
Ø25
Ø25
Ø40
Ø40
Ø48
Ø48
Ø75
Ø75
□20
□23
□23
□34
□34
□40
□40
□64
□64
21/18
26/22
26/22
31/26
31/26
39/32
39/32
59/50
59/50
0.59/0.42
0.30/0.32
0.32/0.35
0.32/0.31
0.55/0.58
0.82/0.88
0.84/0.88
2.3/2.2
2.5/2.4
0.43/0.33
0.30/0.30
0.32/0.32
0.30/0.30
0.52/0.56
0.82/0.88
0.84/0.90
1.5/1.8
1.6/2.0
0.52/0.58
0.85/0.90
0.87/0.90
0.93/0.89
2.50/1.60
2.05/2.20
2.15/2.30
2.95/3.15
3.75/3.85
0.98/1.10
1.60/1.70
1.62/1.72
1.75/1.68
3.60/3.90
3.90/4.20
3.90/4.30
-
-
● Standard Specification
Enclosure
Main Power supply
Control power supply
Duty cycle (on-off)
Duty cycle (modulating)
Motor
Limit switches
Torque switches
Stall protection/set temp.
Travel angle
Position indicator
Manual override
Self locking
Mechanical stopper
Space heater
Cable entries
Lubrication
Terminal block
Ambient temperature
Ambient humidity
Anti vibration
External coating
Weatherproof IP67, NEMA 4X and 6, O-ring sealed (ATM0020&ATM0040:IP66)
24VDC, 110/220VAC/1Ph/50/60Hz, 380/440VAC/3Ph/50/60Hz ±10%, (ATM0020&ATM0040:1Phase)
110/220VAC/1Ph/50/60Hz ±10%
S2 : 10min ~ 30min
S4 : 30 ~ 50%, 300 ~ 1200 start/hour
Squirrel cage induction motor
2 each for open and close(SPDT 250VAC/10A rating)
2 each for open and close(SPDT 250VAC/10A rating except for ATM0020/0040/0080/0100)
Built in thermal protection, open 150℃±5℃, close 97℃±15℃
90。± 5。(0。~100。)
Continuous mechanical indicator with arrow
De-clutchable (except for ATM0020 : N/A, ATM0040 : by shaft, ATM0080 : by wrench)
Provided by double worm gearing (no brake) (except for ATM0020/0040/0080)
1 each for each travel end (open and close), external adjustable (except for ATM0020/0040)
5W(110/220VAC) for anti condensation
2-PF3/4” TAP except for ATM0020:1-PG11, ATM0040:2-PG13.5, ATM0080:2-M20X1.5
EP type grease
screw and lever push type(spring loaded)
Basic actuator : -20℃ ~ +70℃ except for ATM 0020: -10℃~ +65℃ c/w control option: -10℃~ +60℃
90%RH Max(Non-condensing)
XYZ 10g. 02 ~ 34 Hz, 30 minutes
Dry powder(Polyester), Blue Color, Munsell No. B-0188
6
ELECTRIC ROTARY TYPE ACTUATOR
Potentiometer Kit(output signal:0~1kohm)
High resolution potentiometer and precisely machined gearing
are directly engaged with drive shaft to feedback
continuous position of valve
Current Transmitter(output signal:4~20mA)
Zero/Span Adjustment
Convertible DIP switch(4 wire to 2 wire)
Remote Position Controller(by input and output signal)
Input:4~20mA, 0~10VDC, 2~10VDC, 1~5VDC, 0~5VDC
Output:4~20mA, 0~10VDC, 2~10VDC, 1~5VDC, 0~5VDC
Auto calibration
Reverse operating direction
● Options Available
Symbol
EX
WT
ALS
ATS
EXT
SV
Description
Explosion proof(Exd IIB T4)/Approved by KTL
Watertight(IP68), Temporary submersible/10M Head 1000hours
Auxiliary limit switches(Max 2 for each travel end)
Auxiliary torque switches(Max 2 for each travel end)
Extended travel angle(up to 120。, 135。, 180。, 270。)
Variation in torque and operating speed
Remark
Except for ATM0020/0040/0080
Except for ATM0020/0040/0080
Except for ATM0020/0040
Except for ATM0020/0040/0080/0100
Except for ATM with Large ATM-Series
Please consult before ordering
▶Mechanical
PK
CT
RPC
/Signal
configulation
▶Remote monitoring and control
LP4 / LM4 LP4 for 1 & 3Phase(ATM0160~9000)
Control power : Free Voltage(85~265VAC)50/60Hz, Option:24VDC
Magnetci slector switches, SMPS(Switching Module Power Supply)
:Open/Close & Local/Stop/Remote
Local lamp indication
:Power-White(on), Remote:Blue(on)
:In case of Close Torque Switch Trip-
Yellow(on)+Green(flickering:only at Local Position)
:In case of Open Torque Switch Trip-
Yellow(on)+Red(flickering:only at Local Position)
:Full Close-Green(on), Closing-Green(flickering:only at Local Position)
:Full Open-Red(on), Opening-Red(flickering:only at Local Position)
※ Options Available:PK, CT, RPC(Modulating), IP68, Explosion proof
LM4 for 3 Phase(ATM0160~9000)
Including the same function as LP4
Revesing electric contactors, Transformer
▶Local control
PK CT
RPC
LP4 / LM4
7
ELECTRIC ROTARY TYPE ACTUATOR
ICM1 for 1 & 3 Phase(Integral Control Module)(ATM0160~9000)
Main Power : 3Ph 220V/380/440 VAC
1Ph 110V/220 VAC
Control Power : 24 VDC, 5 VDC
Magnetic selector switches
:Open/Close & Local/Stop/Remote
Reversing electric contactors, Transformer, Phase Detector
Local lamp indication
:Power-White(on), Remote:Blue(on)
:In case of Close Torque Switch Trip-Yellow(on)+Green(flickering)
:In case of Open Torque Switch Trip-Yellow(on)+Red(flickering)
:Full Close-Green(on), Closing-Green(flickering:only at Local Position)
:Full Open-Red(on), Opening-Red(flickering:only at Local Position)
:Single & Revese Phasing:(Yellow+Green+Red)all flickering
※ Options Available:Explosion proof, IP68
ICM2 for 1 & 3 Phase(Integral with LCD Display)(ATM0160~9000)
Including the same function as ICM1
Reversing electric contactors, Transformer, Phase Detector
Auto-PhaseDiscriminator, LCD Display
※ Options Available:CT, RPC(Modulating), Explosion proof
※ Options Available:IP68, Bus Communication
ICM3 for 1 & 3 Phase(Integral with LCD Display/IP68 Enclosure)(ATM0160~9000)
Including the same function as ICM2
Reversing electric contactors, Transformer, Phase Detector
Auto-PhaseDiscriminator, LCD Display, IP68, Explosion proof
RPC(Modulating), Bus Communication
34pins separate compartment for terminal block
▶Fail Safety
BP for 1 Phase(ATM0160~9000)
Rechargeable Battery back up-Fail Safe function
When main power is alive, actuator works as normally
Once power fails, actuator will move to pre-set fail safe position
Input power-Free Voltage(85~265 VAC) 50/60Hz
Output contacts:Open/Close/Alarm relay
LED signal indication:4 LEDs(Full Open/Close, Over Torque and Power)
Rechargeable battery:2.0 AH 27.5 VDC(Ni-Cd)
▶Local control
ICM1
ICM2
8
ELECTRIC ROTARY TYPE ACTUATOR
● Dimensions
ATM0020 ATM0040 ATM0080
9
ELECTRIC ROTARY TYPE ACTUATOR
● Dimensions
ATM0100, ATM0160, ATM0240, ATM0350 ATM0500, ATM0800, ATM1100, ATM2000, ATM3000
ATM6000, ATM9000
10
ELECTRIC ROTARY TYPE ACTUATOR
ATM0100
ATM0160/0240
ATM0350/0500
ATM0800/1100
ATM2000/3000
ATM6000/9000
RPC
X Y Z
340 190 245
○
○
○
○
○
CT
X Y Z
316 172 245
○
○
○
○
○
BP
X Y Z
396 172 245
475 229 259
494 244 288
×
×
×
LP4/LM4/ICM1/ICM2
X Y Z
×
499 229 259
518 244 288
541 284 313
600 375 385
677 417 668
LD2
X Y Z
×
517 284 259
536 284 288
559 284 313
620 375 385
697 417 668
*O : Installed inside of actuator *X : Not available *Z : Height of basic actuator
ATM 0100 ATM 0160~9000
11
ELECTRIC ROTARY TYPE ACTUATOR
● Typical Wiring (ATM 0040~0080)
110/220VAC, 50/60Hz, 1Ph(On-off)
110/220VAC, 50/60Hz, 1Ph(On-Off) 110/220VAC, 50/60Hz, 1Ph(Modulating:RPC)
ATM0020 ATM0040
ATM0080 ATM0080(RPC)
110/220VAC, 50/60Hz, 1Ph(On-off)
12
ELECTRIC ROTARY TYPE ACTUATOR
110/220VAC, 50/60Hz, 1Ph(On-Off)
110/220VAC, 50/60Hz, 1Ph(Modulating:RPC)
ATM0100 ATM0100(3Ph)
ATM0100(RPC)
380/440VAC, 50/60Hz, 3Ph(On-Off)
● Typical Wiring (ATM 0100)
CLS : Close Limit Switch (250VAC 10A)
OLS : Open Limit Switch (250VAC 10A)
ACLS : Aux. Close Limit Switch (250VAC 10A)
AOLS : Aux. Open Limit Switch (250VAC 10A)
ACTS : Aux. Close Torque Switch (250VAC 10A)
AOTS : Aux. Open Torque Switch (250VAC 10A)
TP : THERMAL PROTECTOR (250VAC 15A OPTION)
* Each actuator should be powered through its own
individual switch or relay contacts to prevent cross feed
between two or more actuators.
13
ELECTRIC ROTARY TYPE ACTUATOR
● Typical Wiring (ATM 0160~9000)
110/220VAC, 50/60Hz, 1Ph(On-Off)
110/220VAC, 50/60Hz, 1Ph(Modulating:RPC)
ATM0160~9000 ATM0160~9000(3Ph)
ATM0160~9000(RPC)
380/440VAC, 50/60Hz, 3Ph(On-Off)
CLS : Close Limit Switch (250VAC 10A)OLS : Open Limit Switch (250VAC 10A)ACLS : Aux. Close Limit Switch (250VAC 10A)AOLS : Aux. Open Limit Switch (250VAC 10A)ACTS : Aux. Close Torque Switch (250VAC 10A)AOTS : Aux. Open Torque Switch (250VAC 10A) TP : THERMAL PROTECTOR (250VAC 15A OPTION)* Each actuator should be powered through its ownindividual switch or relay contacts to prevent cross feedbetween two or more actuators.
14
ELECTRIC ROTARY TYPE ACTUATOR
110/220VAC, 50/60Hz, 1Ph(CT)
380/440VAC, 50/60Hz, 3Ph(CT)
ATM0100(CT CARD)
ATM0160~9000(CT CARD, 3PH)
ATM0160~9000(CT CARD)
110/220VAC, 50/60Hz, 1Ph(CT)
● Typical Wiring (ATM 0100~9000)
CLS : Close Limit Switch (250VAC 10A)
OLS : Open Limit Switch (250VAC 10A)
ACLS : Aux. Close Limit Switch (250VAC 10A)
AOLS : Aux. Open Limit Switch (250VAC 10A)
ACTS : Aux. Close Torque Switch (250VAC 10A)
AOTS : Aux. Open Torque Switch (250VAC 10A)
TP : THERMAL PROTECTOR (250VAC 15A OPTION)
* Each actuator should be powered through its own
individual switch or relay contacts to prevent cross feed
between two or more actuators.
15
ELECTRIC LINEAR ACTUATOR
● AQL Electric Linear Actuator
LeverPadlockable, switchableauto/manual lever for easy operation
Stroke Scale
Indicator
Digital Display unit(Option)
Handwheel
Disc spring arrangementProviding accurate setting force andtight shut up for closing
Folding stackDrive shaft protection
Mounting Coupler
HousingHard anodized aluminum alloy housing external powdercoating against corrosive industrial environment
Pillar
Valve Stem
Automa designs, produces and provides high quality electric actuator and services
related to industrial valve automation and controls.
AQL series linear actuator has been developed for a wide range of linear applications and to service reliable
performance, long trouble free operation, more flexibility and maximized ability to integrate fully into sophisticated
control system.
16
ELECTRIC LINEAR ACTUATOR
● Robust construction, precise positioning, reliable performance
● Wide range of application
● Compact internal Arrangement
● Modulating control options can be instaled on site
● Local control options for easy commissioning and
emergency operation in the field
Electric Operation- On-off
Modulating control- 4-20mA / input / output- 0-10 V or other signal selection- Transmitter output 4-20 mA
Seals & O-rings- protection to water proof IP67
Terminal
Simple and easier handling and adjustment of Limit &Signal switches
Indicator
Coupler
Pillar
17
ELECTRIC LINEAR ACTUATOR
● Technical Information
● Standard Specification
AQL04 4 40 0.7/0.9 0.45/0.44 0.26/0.25 0.30/0.31 0.28/0.40 3.00 Max. M20 100 M16 7
AQL06 6 60 0.7/0.9 0.49/0.48 0.29/0.28 0.32/0.33 0.30/0.42 3.50 Max. M20 100 M16 8
AQL08 8 50 0.9/1.1 0.92/0.88 0.48/0.46 0.18/0.17 0.17/0.16 2.90 Max. M20 100 M16 15
AQL10 10 50 0.9/1.1 0.95/0.91 0.50/0.48 0.19/0.18 0.18/0.17 3.20 Max. M20 100 M16 16
AQL12 12 50 0.9/1.1 0.98/0.94 0.52/0.50 0.20/0.19 0.19/0.18 3.50 Max. M20 100 M16 16
AQL20 20 100 0.9/1.1 1.75/1.68 0.93/0.89 0.30/0.30 0.32/0.31 6.00 Max. M24 165 M20 20
AQL25 25 100 0.9/1.1 1.80/1.72 0.95/0.92 0.32/0.32 0.34/0.33 7.00 Max. M24 165 M20 21
Model
Max.Force
Max.Stroke
Speed50/60Hz
ValveStem
Threads
PCD on
FlangeWeight
Rated Current(A)
50/60Hz
KN mm mm/sec1 Phase
110V 220V 380V 440V 24V
DCmm mm kg
3 Phase
Manual Override Handwheel with switchable declutchable lever
Enclosure (EN60529) IP67
Cable Entry 2 × PF 3/4” TAP
Position Indication Scale on pillar pointed by indicator
Housing Aluminum alloy hard anodized for anti-corrosion
Painting Epoxy power coated
Ambient Temperature -20℃ ~ +70℃
Operating Mode (EC34-1, 8) S2-Max. 30 Min / S4-50% ED, 800 c/h / S4-50% ED, 1200 c/h
Motor Protection Thermal Switch, Class F Insulation
Space Heater 5W (110/220VAC) for anti condensation
Limit Switch 1 each for open/close (SPDT 10A 250VAC rating)
Mounting Direction Any direction except for heading downward
Pillar Material Stainless steel, carbon steel with special surface treatment
Available Optional Control
- Remote position control RPC 4~20mA input/output, Selectable other signal
- Potentiometer PK 0~1Kohm feedback
- Current transmitter CT 4~20mA output
Local control
- Local control (1 Phase) LP4 Local control unit
- Local control (3 Phase) LM4 LP4 with reversing contactor and transformer
- Integral unit ICM Local controller with phase detector / discriminator
- Battery back up unit BP Fail Safe (Fail position either open/close)
- Explosion proof EX Exd IIB T4
● Option Specification
- Auxiliary limit switch ALS1 each for open/close (SPDT 10A 250VAC rating) (Except for AQL04/AQL06)
Pillar
Threads
18
ELECTRIC LINEAR ACTUATOR AQL04/06
Dimensions(mm)
Setting closing(opening) force
Standard wiring
F : Closing(opening) force S : Amount of disc spring compression
1PH WIRING DIAGRAM 1PH+RPC WIRING DIAGRAM 3PH+RPC WIRING DIAGRAM
AQL04 AQL06
Disc spring arrangement
Correct mounting direction
19
ELECTRIC LINEAR ACTUATOR AQL08/10/12
Dimensions(mm)
Setting closing(opening) force
Standard wiring
F : Closing(opening) force S : Amount of disc spring compression
1PH WIRING DIAGRAM 1PH+RPC WIRING DIAGRAM 3PH+RPC WIRING DIAGRAM
AQL08 AQL10 AQL12
Disc spring arrangement
Correct mounting direction
20
ELECTRIC LINEAR ACTUATOR AQL20/25
Dimensions(mm)
Setting closing(opening) force
Standard wiring
F : Closing(opening) force S : Amount of disc spring compression
1PH WIRING DIAGRAM 1PH+RPC WIRING DIAGRAM 3PH+RPC WIRING DIAGRAM
AQL20 AQL25
Disc spring arrangement
Correct mounting direction
ELECTRIC 1 PIECE BALL VALVE
Application■ Water Distribution pipes.■ Industrial Cleaning Machines.■ Sterilizers, Boilers■ Air Conditioners , Water Filters■ Medical Equipments, Vacuum Packing
● Dimension (mm)
● Specification
Valve Size
Actuator Model
Actuator Type
Electrical
Output Torque
Operating time
Operating Type
Rotating Angle
Fluid Temp
Rating
Body Material
Electric
AC110V, 220V
ON-OFF
1000Psi
10A(3/8″) 15A(1/2″) 20A(3/4″) 25A(1″) 32A(1-1/4″) 40A(1-1/2″) 50A(2″)
ATM0020-10S1
ATM0020-15S1
ATM0020-20S1
ATM0020-25S1
ATM0040-32S1
ATM0040-40S1
ATM0040-50S1
10A
15A
20A
25A
32A
40A
50A
SizeModel
3/8″
1/2″
3/4″
1″
1-1/4″
1-1/2″
2″
89.4
89.4
89.4
89.4
113.5
113.5
113.5
A
109.7
109.7
109.7
109.7
121.8
121.8
121.8
A1
156.5
168.5
188.5
192.5
200
200
200
H(APPROX.)
45
56.5
59
71
78
83
100
L
7.7
9.2
12.5
15
20
25
32
Ød
END CONNECTION(PT SCREW) Motor
SUS316 / BODY SUS316 / BALL PTFE / SEAT
ATM0040 ATM0020
40Nm25Nm
11/50Hz, 60Hz
90。±5。
-10℃~ +65℃
90。±10。
-20℃~ +70℃
14/50Hz, 12/60Hz
21
22
ELECTRIC 3 PIECE BALL VALVE
Application■ Water Distribution pipes■ Industrial Cleaning Machines■ Sterilizers, Boilers■ Air Conditioners , Water Filters■ Medical Equipments, Vacuum Packing
● Specification
Valve Size
Actuator Model
Actuator Type
Electrical
Output Torque
Operating Type
Rotating Angle
Fluid Temp
Rating
Body Material
Operating time
Electric
AC110V, 220V
10A(3/8″)8A(1/4″) 15A(1/2″) 20A(3/4″) 25A(1″) 32A(1-1/4″) 40A(1-1/2″) 50A(2″)
SUS316 / BODY SUS316 / BALL PTFE / SEAT
ATM0080
80Nm
16/50Hz,
14/60Hz14/50Hz, 12/60Hz11/50, 60Hz
(mm)● Dimension
ATM0020-8S3
ATM0020-10S3
ATM0020-15S3
ATM0020-20S3
ATM0040-25S3
ATM0040-32S3
ATM0040-40S3
ATM0080-50S3
8A
10A
15A
20A
25A
32A
40A
50A
SizeMotor
Model
1/4″
3/8″
1/2″
3/4″
1″
1-1/4″
1-1/2″
2″
89.4
89.4
89.4
89.4
113.5
113.5
113.5
160
A109.7
109.7
109.7
109.7
121.8
121.8
121.8
121
A1173.5
173.5
173.5
173.5
216
227
231
218
H(APPROX.)
60
60
65
75
81
94.5
108
121.5
L
8
10
15
20
25
32
40
50
Ød
END CONNECTION(PT SCREW )
ATM0040ATM0020
20Nm 40Nm
-20℃ ~ +70℃
1000Psi
ON-OFF
90。±5。
-10℃ ~ +65℃
90。±10。
ON-OFF MODULTING SAME LEFT
23
ELECTRIC FLANGE BALL VALVE
Application■ Water distribution pipes■ Industrial cleaning machines■ Sterilizers, Boilers ■ Air conditioners, Water filters■ Medical equipments, Vacuum packing■ Food & Beverage lines■ Vacuum distribution pipes
● Dimension
Valve Size
Actuator Model
Actuator Type
Electrical
Rotating Angle
Operating Type
Fluid Temp
Rating
Body Material
Electric
AC110V 220V, AC380V 440V
90。±5。
ON/OFF, MODULATING(Except for ATM0040)
-20℃ ~ 70℃
JIS10K (20K) (40K) ANSI150# (300#) (600#)
SCS13 (SCS14)/Body SUS304 (SUS316)/Ball PTFE(RTFE PEEK, METAL)/Seat
※ ( ) Option
15A ~ 350A
ATM0040 ~ ATM3000
Model
(mm)
SizeA A1
● Specification
ATM0040-15FATM0040-20FATM0040-25FATM0040-32FATM0040-40FATM0080-50FATM0160-65FATM0160-80FATM0350-100FATM0500-125FATM0500-150FATM1100-200FATM2000-250FATM3000-300FATM3000-350F
15A20A25A32A40A50A65A80A100A125A150A200A250A300A350A
113.5113.5113.5113.5113.5160338338357357357380440440440
121.8121.8121.8121.8121.8121229229244244244287375375375
233236245248269256406482492547543645813875951
-----
40115115145145145170225225225
108117127140165178190203229356397457533610686
121414161616181818202222242426
1520253240506580
100125150200250300350
5258708085100120130155185215265325375415
707590
100105120140150175210240290355400445
95100125135140155175185210250280330400445490
4-154-154-194-194-194-194-198-198-198-238-2312-2312-2316-2516-25
1/2″3/4″1″
1-1/4″1-1/2″
2″2-1/2″
3″4″5″6″8″10″12″14″
Motor END CONNECTION(JIS 10K RF)H(Approx) H2
T Ød ØRF ØC ØD N-ØHL±1.6
24
ELECTRIC BUTTERFLY VALVE
Application■ Water distribution pipes■ Industrial cleaning machines■ Sterilizers, Boilers ■ Air ventilation■ Medical equipments, Vacuum packing■ Air ventilation systems
Valve Size
Actuator Model
Actuator Type
Electrical
Rotating Angle
Operating Type
Fluid Temp
Rating
Body Material
Electric
AC110V 220V, AC380V 440V
90。±5。
ON/OFF, MODULATING(Except for ATM0040)
-20℃~±70℃
JIS10K Wafer ANSI150# Wafer
FC (SCS13)/Body SCS13 (SCS14)/Disc EPDM (MTFE)/Seat
※ ( ) Option
40A ~ 1000A
ATM0040 ~ ATM3000
● Specification
● Dimension
Model Size A A1H1 H2 L
ØD ØC N-ØHEND CONNECTION(JIS 10K WAFER)H
(APPROX.)
(mm)
ATM0040-40BFATM0040-50BFATM0080-65BFATM0080-80BFATM0100-100BFATM0160-125BFATM0240-150BFATM0350-200BFATM0500-250BFATM0800-300BFATM0800-350BFATM1100-400BFATM2000-450BFATM2000-500BFATM3000-600BF
40A50A65A80A100A125A150A200A250A300A350A400A450A500A600A
1-1/2″2″
2-1/2″3″4″5″6″8″10″12″14″16″18″20″24″
113.5113.5160160258338338357357380380380440440440
121.8121.8121121172229229244244244287287375375375
263270268278418472489581608660669713836900985
58657183100110130163227252272343366421493
--
4040
100115115145145170170170225225225
4143464652565660687878
102114127154
86105114129155180207260331377416475535590695
105120140150175210240290355400445510565620730
4-194-194-198-198-198-238-2312-2312-2516-2516-2516-2720-2720-2724-33
Actuator
25
ELECTRIC LINEAR TYPE ACTUATOR (ON/OFF)
Very excellent to generate various thrust by accelerating gear and power supplyequipment which using the turning power of synchronous motor.It is usually used with 2-WAY and 3-WAY globe valves for Heating.Ventilating. Air Conditioning, plant.
A. Robust DesignB. EnclosureC. Reliable Operating
General
Model
Storke (mm)
Output Torgue (N)
Operating Time (Sec)
Power Supply
Rated Load (A)
Condenser (μF)
Rated Current (VA)
Control Signal
Control Output
Motor effic.
Ambient Temp.
Housing protection
Conduit Entries
Weight (Kg)
0.5 (0.075)
34 (0.474)
12 (16.5)
2.1 (0.25)
150, (5)
51, (55)
※ ( ) Option
20 40 70 80
● Specification
3, (0.35)
210, (5)
72,(77)
(1)
(6)
(220)
2.4 3.2 3.3 10.4 11.6 21.3
AGE-10 AGE-20 AGE-35 AGE-55 AGE-100 AGE-250
1000 2000 3500 5500 10000 25000
50 50
24V (220V) AC. ±10%
CW / CCW
- Option (2*Open/Close 3A) (2*Open/Close 10A)
S4 - 30% ED - 600c/hr
-15℃ ~ 60℃
220V (110V)
100 94 94 210
IP54 (EN60529)
PF 1/2 × 2EA
IP65 (EN60529)
Cap Screws
Cap
Terminal Box
Linkage Frame
Manual Handle
Coupling Piece
Quick MountClamp jaws
● Design Feature•Assembling actuator and valve requires neither special tools nor adjustments•Blocking proof geartrain with self-lubricating bearings•Manual operation with automatic resetting to control operation
(When motor operate, Manual handle returns to its own position for electric operation)
26
ELECTRIC LINEAR TYPE ACTUATOR
● Dimension
● Wiring Diagram
AGE-10
ΦB
AGE-20
AGE-35
AGE-55
AGE-100
AGE-250
Model
208
295
330
355
585
665
H
62
90
90
100
100
120
E
62
125
125
135
170
200
G
81
106
130
125
195
250
D
111
185
185
215
330
445
F
168
140
140
160
180
270
(mm)
TERMINAL BLOCK
OPEN(Down)
COM
CLOSE(Up)
Field Wiring
AC Power24V or 220V
Actuator Wiring
Close Torque Limit
Motor
Open Torque Limit
27
ELECTRIC LINEAR TYPE ACTUATOR (CONTROL)
Very excellent to generate various thrust by accelerating gear and power supplyequipment which using the turning power of synchronous motor.It is usually used with 2-PORT and 3-PORT globe valves for Heating.Ventilating. Air Conditioning, plant.
A. Manual Handle for Hand/Auto Switch System.B. Torque Switch for Protection from overloadC. Signal Output for Remote Control.D. Easy Transition for Normal Open/Normal Close.E. It is operated 24V AC voltage (0~10V DC / 4~20mA) or 220V AC (4~20mA or
0~10V DC)
General
Model
Storke (mm)
Output Torgue (N)
Operating Time (Sec)
Power Supply
Rated Torque (A)
Condenser (μF)
Rated Current (VA)
Control Signal
Output Signal
Motor effic.
Ambient Temp.
Housing protection
Conduit Entries
Weight (Kg)
0.5, (0.075)
34 (0.474)
12 (16.5)
2.1, (0.25)
150, (5)
51, (55)
20 40 70 80
● Specification
3, (0.35)
210, (5)
72, (77)
1
6
(220)
2.4 3.2 3.3 10.4 11.6 21.3
AGE-10P AGE-20P AGE-35P AGE-55P AGE-100P AGE-250P
1000 2000 3500 5500 10000 25000
50 50
24V (220V) AC. ±10%
(AC 24V : 0 ~ 10V / 4 ~ 20mA D.C) ( AC220V : 0 ~ 10V or 4 ~ 20mA D.C)
0 ~ 10V or 4 ~ 20mA D.C
S4 - 30% ED - 600c/hr
-15℃ ~ 60℃
IP 54 (EN60529)
220V AC ±10%
100 94 94 210
PF1/2 × 2EA
● Mounting and Installation Guide
(permitted) (Not permitted)
28
ELECTRIC LINEAR TYPE ACTUATOR
STANDARD (AGE-10P, 20P, 35P, 55P AC24V)
OPTION (AGE-20P, 35P, 55P AC24V)
(AGE-20P, 35P, 55P, 100P, 250P AC220V)
● Wiring Diagram
29
ELECTRIC LINEAR TYPE ACTUATOR
K0 : Volumetric flow 0%
K100 : Volumetric flow 100%
S : Signal (0~10V, 2~10V, 4~20mA d.c)
K100
K0
04
10V20mA
S
● Technical Features
AGE-10
ΦB
AGE-20
AGE-35
AGE-55
AGE-100
AGE-250
Model
208
295
330
355
585
665
H
62
90
90
100
100
120
E
62
125
125
135
170
200
G
81
106
130
125
195
250
D
111
185
185
215
330
445
F
168
140
140
160
180
270
(mm)● Dimension
30
ELECTRIC LINEAR TYPE VALVE (FLANGED)
The valve which controls two positions or proportion of cold/hot water,steam andair, The body and the seat are manufactured in castiron and the valvestem,seat,valve plug are in stainless steel.The stuffing box prevents leakage viaO-ring and teflon.
■ Technical DataOperating Pressure : JIS 10 Kgf/cm2
Operating Temp : -25 ~ 120℃Valve curve : Equal percentage or linearLeakage rate : ≤ 0.01% of Kvs value Class IV
■ ApplicationHot water : max 120℃Chilled water : -25℃ max. in closed circuit only water with following additives- Hydrazine, Phosphate, for frost protection. - Glycol, max 50%, for frost protection.- Saturated steam, superheated steam.
ΔPvmax in kgf/cm2=Max. permissible pressure difference across the valve at which the drive can stillsafely open and close the valve
ΔPsmax in kgf/cm2=Max. permissible pressure difference across the valve during malfunction at which thedrive can close the valve
(KV=Cv/1.167)
General
● Material
PartName
Material
NO
Body
FC20
1
Cover
FC20
2
PackingBox
VITON
Plug
SCS13
3
Stem
SUS304
4 5
AGE-15F
AGE-20F
AGE-25F
AGE-32F
AGE-40F
AGE-50F
AGE-65F
AGE-80F
AGE-100F
AGE-125F
AGE-150F
● Specification
DNModel
mm
15
20
25
32
40
50
65
80
100
125
150
inch
1/2″
3/4″
1″
1-1/4″
1-1/2″
2″
1-1/2″
3″
4″
5″
6″
Kv
3
5
10
16
25
39
65
91
130
188
283
Cv
3.5
5.8
11.7
18.7
29
45
75.8
106
152
219
330
FLOW Stroke
mm
20
20
20
20
20
20
20
20
40
40
40
50
50
50
50
50
50
50
50
50
50
50
∆Pv
PvmaxSv
AGE-35AGE-20
10
10
10
10
10
10
10
8
4
4
4
10
10
10
10
10
8
5
3
-
-
-
-
-
-
-
-
-
-
-
3.5
2
1.5
Actuator ∆Ps(Kgf/cm2)
31
ELECTRIC LINEAR TYPE VALVE (FLANGED)
AGE-15F
AGE-20F
AGE-25F
AGE-32F
AGE-40F
AGE-50F
AGE-65F
AGE-80F
AGE-100F
AGE-125F
AGE-150F
Model A C D E F B H2 H1
330
334
334
339
339
339
360
360
-
-
-
330
334
334
339
339
339
360
360
421
432
448
-
-
-
-
-
-
-
-
-
-
478
5.5
6
6.9
8.9
10
15
22
25
42
76
87
DNH
AGE-20 AGE-35 AGE-55
WeightValve(Kg)
● Valve sizing chart-size 15A ~ 50A
● Dimensions
15
20
25
32
40
50
65
80
100
125
150
130
150
160
200
200
230
290
310
350
400
480
95
100
125
135
140
155
175
185
210
250
280
16
18
18
20
20
20
22
22
24
24
26
70
75
90
100
105
120
140
150
175
210
240
15X4
15X4
19X4
19X4
19X4
19X4
19X4
19X8
19X8
23X8
23X8
69
75
75
97
97
147
180
186
205
238
279
67.5
67.5
67.5
67.5
67.5
67.5
67.5
67.5
92.5
92.5
92.5
75
80
77
74
74
70
83
73
129
118
140
▶FLOW DIAGRAM
V : WATER FLOW (㎥/h) ΔPv : VALVE PRESSURE DROP (Kgf/㎠)
(mm)
32
ACTUATORS INSTALLATION MANUAL-AC200V
■ It is recommended that the valves be mounted upright in an easily accessible location. The actuator
must be protected against dripping water, which could enter the housing and damage the
mechanism or motor.
■ How to connect the vallve and actuator
•Unfasten the coupling nut and insert in the valve shaft. <Figure 2- >
•Fit the coupling washer to the groove on the shaft. <Figure 2- >
•Fit the actuator to the groove on the valve body and then
fasten the actuator by using the hexagonal bolt.
Hexagonal wrench(6mm) needed. <Figure 2- >
•Tighten the coupling nut completely.
<Figure 1- >
■ Manual Operating
•The actuator is delivered with factory(auto) settings. Use when manual operating or power off.
<Figure 3>
•Turn right the Lever to clockwise(90°) and then turn the manual override slightly.
•When turning the manual override to clockwise, the shaft of the actuator come down and in case of
counterclockwise, the shaft go up. <Figure 3- >
After using it, turn the lever to clockwise(90°) and also turn the manual override slightly.
After that, use auto settings.
Manual Operation : Do not use when power on.
MODEL : AGE-SERIES
<Figure 1>
<Figure 3>
<Figure 4>
<Figure 2>
( 20P )
Coupling Washer
(35P,55P:Cutting required)
※ The product is subject to change for technical development and quality improvement without prior notice.
021502
(JB0247)
Automa Bldg. Ⅱ #35 , Bucheon-ro 168beon-gil,
Wonmi-Gu, Bucheon-City, Gyeonggi-Do, Korea
TEL : 82-(0)32-613-4800
FAX : 82-(0)32-613-4801
www.automa-int.com