AC ACUp To (8) 24V Emergency Lighting Circuits
CentralBattery
100-1000Watts
for 90 mins.
Central CentralBattery Battery
100-1000 100-1000Watts Watts
for 90 mins. for 90 mins.
Converts ANY type of LED fixture to low voltage emergency operation from central batteries
Factory or field installable in the Fire and Electrical Enclosure of UL listed fixtures
Compatible with all types of dimming and lighting controls
Fully automatic self-test and self-diagnostics is standard for all systems
Central batteries allow efficient & easy maintenance that ensures compliance with the Life Safety Code
Reduces number of batteries per building by more than 100:1 compared to unit equipment
Exit signs, exterior and other fixtures for emergency lighting are included in the system throughout any building
Installations with MARS (Monitoring And Reporting System) allow internet communication between all fixtures and battery systems and deliver automatic fault reports via email to any address
ELC Emergency Lighting Controller forLED General Lighting Fixtures
CBS
ELC ELCELC ELC
D E S I G N E D & M A D E I N
T H E U S A
ELC ELC ELC
ELC
ELC ELCELC
ELC
Warehouse
Low Voltage Emergency Circuits
ELC
ELC
ELC
ELC
Office
10-12 FT CEILING
30-40 FT CEILING
EMERGENCY LIGHTING CIRCUIT: LOW VOLTAGE 24 VDC
NORMAL LIGHTING BRANCH CIRCUIT 120/ 277 VAC
UC US
LISTED
L®
STEP
1STEP
2STEP
3STEP
4STEP
5STEP
6
SELECT FIXTURE DESIRED FOR EMERGENCY LIGHTING AND DOWNLOAD THE IES PHOTOMETRIC FILE.
Determine LIGHT LOSS FACTOR (LLF) for emergency lighting: (a)For normal power range to 120W, use LLF of 25%.(b)For luminaires with normal power range above 120W: LLF = 100 x 30/ (Luminaire Power) %
ELC Spec Procedurefor LED General Lighting Luminaires
run a photometric calculation for the fixture at specified mounting height and reflectivity criteria, and determine the spacing required to produce 1fc average over the path of egress.
EMERGENCY POWER = LLF (%) x NORMAL POWER
TOTAL POWER = EM POWER x TOTAL EM FIXTURES
Select ELC model PACKAGE TYPE (P1-P4) based on:EMERGENCY POWER (EPR)NORMAL DRIVER OUTPUT VOLTAGEQUANTITY OF NORMAL DRIVERSSPACE AVAILABLE IN DRIVER COMPARTMENT