Car park ventilation
ufiveufive
Car
park
ven
tilat
ion
Pollr
ich
DLK
Fan
Fac
torie
s
-
Type code
Designation Type Type of construction DriveH_Centrifugal fan (heavy-duty) A_axial O_Without guide vanes M_Motor (direct)C_Centrifugal fan (compact) R_centrifugal N_Outlet guide vanes K_CouplingA_Axial fan V_Inlet guide vanes R_Belt driveP_Plug fan R_ReversibleS_Smoke extraction fan E_Single inlet
Z_Double inletT_TunnelJ_JetfanD_RoofG_Car parkW_Wall
Type code of all products
S A J M 03 - 0315 - B
7. Basic series 6. Nominal impeller diameter DN [mm] 5. Product specific code: 01 = No temperature class 03 = Temperature class F300 04 = Temperature class F400 4. Drive M = Motor (direct)
3. Type of construction O = Without guide vanes = Toromax by Pollrich DLK
N = Outlet guide vanes = ToromaxPro by Pollrich DLK J = Jetfan = Alujet / AlujetPad by Pollrich DLK
G = Car park = ToromaxPro duplex by Pollrich DLK
2. Type A = Axial R = Centrifugal
1. Designation A = Axial fan C = Centrifugal fan S = Smoke extraction fan
SymbolsN SpeedDN Nominal impeller diameterLW(A) Sound power level A-weightedLP(A), 3m. Sound pressure level A-weighted, 3m distancepf Total pressure increaseqV Flow rateFt Thrust
for car park ventilation
-
Content
Page Trademark and products ................................................................... 2
System engineering and CFD analysis .............................................. 4
Supply air fansAAOM-product line Toromax by Pollrich DLK Product-specific information, Performance diagramDN 500 DN 1600, 40 C ................................................................................................. 6AANM-product line ToromaxPro by Pollrich DLK Product-specific information, Performance diagramDN 500 DN 1600, 40 C ................................................................................................. 8
Comparison of Jetfans .............. ........................................................ 10
Axial-Jetfans
AAJM-product line Alujet by Pollrich DLK Product-specific information, Performance diagramDN 315 DN 400,40 C, unidirectional / reversible SAJM-product line Alujet by Pollrich DLK (smoke extraction) Product-specific information, Performance diagramDN 315 DN 400,300/400 C /120 min, unidirectional / reversible .................................. 11
Centrifugal-Jetfans
CRJM-product line AlujetPad by Pollrich DLK
Product-specific information, Performance diagramDN 500 DN 560,40 C, unidirectionalSRJM-product line AlujetPad by Pollrich DLK (smoke extraction)Product-specific information, Performance diagramDN 500 DN 560,300 C/120 min, unidirectional ............................................................ 20
Exhaust air fans (smoke extraction)SAOM-product line Toromax by Pollrich DLK Product-specific information, Performance diagramDN 500 DN 1400, 300 C/120 min ................................................................................. 24 SANM-product line ToromaxPro by Pollrich DLK
Product-specific information, Performance diagramDN 500 DN 1600, 300/400 C/120 min ........................................................................... 26SAGM-product line ToromaxPro duplex by Pollrich DLK
Product-specific information, Performance diagramDN 500 DN 1600, 300/400 C/120 min ........................................................................... 28
Control system Installation, commissioning and maintenance ...................................... 30
Pollrich DLK Fan Factories 1
-
The Trademark Pollrich DLK Fan Factories
The common trademark Pollrich DLK Fan Factories pools more than 140 years of production know-how of industrial fans by the manufacturers Pollrich Ventilatoren GmbH and DLK Ventilatoren GmbH. A workforce of more than 220 employees at the two production sites Mnchengladbach and Schntal-Berlichingen manufacture axial and centrifugal fans for nearly any industrial requirement.
As the only manufacturer in the world offering all five product segments of industrial fans, we propose an unmatched range of products for the most different requirements of our customers. As our sales teams are organised in market segments they will better understand the specific project of their customer and supply knowledgeable solutions.
With a mix of standardisation, sophisticated variant management, tight internal organisation, and an intelligently controlled staff employment, we manufacture as well standard fans as pinpointed special units always precisely matching the
Trademark and products
2 Pollrich DLK Fan Factories
ufive products plus full-service
ufive
-
customers requirements, including highest efficiency, zero-defect and shortest delivery time.
Our R&D department combines expertise within all sectors of fan technology with highly efficient simulation tools such as CFD (Computational Fluid Dynamics) for flow visualisation and FEM (Finite-Element-Method) to calculate the structure-mechanical characteristics, as well as test ducts and -chambers according to international standard ISO 5801, equipped with the latest measuring technology in order to determine the aerodynamic and aeroacoustic characteristics.
Our companys commitment is centered to high quality and customers needs. Our understanding for quality is not limited to the product and to the production methods certified according to DIN ISO 9001. Our quality commitment includes the results of the individual work of every employee. This is the philosophy that every employee is realising towards inside and outside of the company. Products and management processes are consistently adjustedto the customers requirements by applying Kaizen/CIP. This means for our customers: Qualified advice and
support, innovative product solutions, reliable delivery times and unvarying high product quality.
We take care of you, wherever you are in the world, with our comprehensive power service package beginning at the moment of feasibility or project studies, passing by the commissioning on site, and ending in a first class after sales service. Our worldwide acting service team will be ready to help every day of the year for 24 hours.
Trademark and products
Pollrich DLK Fan Factories 3
-
CAR PARK VENTILATION: THE PLANNING
Natural ventilation in car parks is usually insufficient or even impossible because the building structure is mostly closed. Complex ventilation technology has therefore become industry standard, particularly due to the fact that local requirements have to be taken into account for almost every car park.
Most countries have developed a national standard for car park ventilation or have adopted legislation to cover the minimum requirements. Most countries distinguish two functions for the ventilation systems. A base function of air refreshment is to comply with the max. permissible limits with pollution. In this case, carbon monoxide concentra-tions are usually the basis for the normative regulations. A second function for the ventilation system is usually the extraction of smoke and heat in the case of fire. The requirements for smoke and heat extractors are given in national standards, often supplemented by the fire depart-ment, planning commission and fire safety bodies.
The traditional concept of a ventilation system with fans and ducts has been changed drastically with the intro-duction of jetfan systems. Space and labour consuming ductwork is almost fully replaced by controllable jetfans. These fans offer precise ventilation possibilities, combined with very flexible positioning possibilities, mostly making ductwork obsolete. These flexible application possibilities have had a large influence on regulations and offer large design freedom.
As a major jetfan manufacturer of jetfans, Pollrich DLK Fan Factories aims to supply all compo-nents required to compose a complete car park ventilation system from a single source.
Our qualified fire safety engi-neers can assist in designing a complete system, consisting of: Selection and positioning of the jetfans, warning signs, gas de-tectors, alarm horn, flashlights etc. They can also calculate the required airflows, pressure los-ses and other details of the air supply, general ventilation and smoke extraction points, as well the required CFD-simulations for approval by proper autho-rities.
CFD (Computational Fluid Dynamics) simulations can
illustrate different ventilation and fire scenarios of interest to the authorities involved in the safety approval of the par-king. CFD simulations are based on numerical calculation methods and algorithms to analyse (complex) problems of liquid and gas flows and make them visible.
It is a very useful tool that has proven itself over time. It enables the designers to visualise fires. Parameters like temperature, pressure, air velocity, smoke dispersi-on, smoke density, sight distance can be studied prior to building the system. These parameters can be decisive, especially when evaluating evacuation plans or fire fighting plans.
CFD- simulations are based on the exact three-dimensio-nal architectural design, including all relevant details such as stair cases, columns, structural beams and other important items. CFD-simulation will prove the effectiveness of all designs and can be used to
System engineering and CFD analysis
ufive
4 Pollrich DLK Fan Factories
-
determine if the supply or extract points, jetfans and other system components are positioned and dimensi-oned correctly and according to the requirements.
Taking all into account, CFD-calculation enables a foun-ded statement about important values like air velocity and temperatures that are expected to be achieved.CFD-simulations by Pollrich DLK Fan Factories are concluded with
a well-founded and comprehensive report.It shows all the positional information of the planned com-ponents for installation, in order to guarantee customers the best possible performance of the system.
>
TH
E C
OM
PLET
E SYSTEM FROM ONE SO
UR
CE
motor). Upstream motor (motor -> impeller) on request.
Installation:As standard suitable for horizontal instal-lation. Vertical installation on request.
Dimensions:All dimensions in mm, weights in kg.
Accessories: Various accessories are available, see catalogue: axial fans.
Specifications:Available in the download area of our website www.pollrichdlk.com
Subject to change.
All indicated values for 400V/50Hz/3~.
Total p
ressure increa
se p
f [Pa]
Flow rate qV [m3/h]
0
200
400
600
800
1000
1200
1400
1600
1800
2000
0 50000 100000 150000 200000 250000 300000
Flow rate qV [m3/h]
-
Product-specific information
8 Pollrich DLK Fan Factories
SUPPLY AIR 2: AXIAL FAN AANM WITH OUTLET GUIDE VANES, DN 500 - DN 1600
Range of application:The medium pressure axial fans of product line ToromaxPro by Pollrich DLK (AANM) are suitable for ventilation and for conveying clean and slightly dusty air for various applications.
The essential benefits are:- Aerodynamically optimised im-
peller with profiled single blades- Blade angle adjustable during
standstill for optimal adjust-ment to the operating point
- Impeller made of a highly corrosion-resistant aluminium alloy (up to DN 1120)
- Highest efficiencies and high pressures due to optimised outlet guide vanes
- Low sound levels- Energy efficient IE2-motors with
PTC resistor
Permissible conveying temperatures:-20 up to +40 C.
Casing:Made of steel, welded, with flanges on both sides and welded motor bracket.Optimal corrosion protection by powder-coating (RAL 7015).Optional: hot-dip galvanising or special coating.
ufive
-
Product-specific information
0
500
1000
1500
2000
2500
3000
0 50000 100000 150000 200000
Flow rate qV [m3/h]
Total p
ressure increa
se p
f [Pa]
Pollrich DLK Fan Factories 9
Impeller:Hub and impeller blades made of a highly corrosion-resistant aluminium alloy (saltwater-proof, DN 315-1120). DN 1250-1600 impeller made of steel, powder-coated (optionally stainless steel). Profiled blades adjustable during standstill.
Drive:IEC norm motor, protection class IP55, insulation class F. Ambient temperature for motor max. 40 C. Motor perfor-mance selected for cold start-up at 20 C. All motors are according to ener-gy efficiency class IE2.
Performance adjustment:Our motors are equipped with PTC resi-stors for operation with frequency con-verters with sinusoidal filters. As option, the motor PTC resistor can be extended to the fan terminal box. The max. speed of the impeller and the max. power output of the motor must be taken into consideration. As standard for operation at 50 Hz (60 Hz on request).
Direction of airflow:Downstream motor (impeller -> motor).
Installation:As standard suitable for horizontal instal-lation. Vertical installation on request.
Dimensions:All dimensions in mm, weights in kg.
Accessories: Various accessories are available, see catalogue: axial fans.
Specifications:Available in the download area of our website www.pollrichdlk.com
Subject to change.
ToromaxPro by Pollrich DLK
DN
[mm]
Max. speed [1/min]
Max. continuous temperature [C]
Max. motor power [kW]
Max.flow rate [m/h]
Max. total pressure increase [Pa]
Weight
[kg]
500 3600 40 7,5 21100 1285 51-109560 3600 40 7,5 23500 1315 58-119630 3600 40 18,5 35000 1720 74-121710 3000 40 22 41150 2230 122-232800 1800 40 18,5 54000 890 168-301900 1800 40 30 74500 1140 211-417
1000 1800 40 45 100000 1290 320-5311120 1800 40 45 125000 1270 373-5751250 1500 40 90 149500 2670 810-12001400 1500 40 90 156000 1530 810-12451600 1100 40 55 172500 1540 950-1250
All indicated values for 400V/50Hz/3~.
-
10 Pollrich DLK Fan Factories
JETFAN-TECHNOLOGY: THE HEART OF MODERN CAR PARK VENTILATION
- Jetfans: Axial- and centrifugal design- 2 centrifugal and 3 axial fan sizes- Centrifugal-Jetfans with minimum construction height- Short delivery times- Aluminium lightweight construction- Corrosion-resistant- Any coating colour on request- Unidirectional and reversible- Certified according to EN 12101-3, F300 and F400- CE-Certified- DIBt-approved- 50 Hz and 60 Hz (on request)- Single- and dual speed
Alujet by Pollrich DLK
Comparison of Jetfans
High performance polygone silencer, aluminium lightweight construction.
-
Pollrich DLK Fan Factories 11
AlujetPad by Pollrich DLK
ufive
Centrifugal Jetfan with casing as aluminium lightweight construction.
-
DN 315 DN 355 DN 400
DN 315 DN 355 DN 400
Thrust [N
]Th
rust [N
]Th
rust [N
]Th
rust [N
]
12 Pollrich DLK Fan Factories
DN 315 DN 355 DN 400
25
46
67
0
10
20
30
40
50
60
70
80
Comparison of Jetfans
AAJM01 Unidirectional 40 C50 Hz
Maximum values indicated. Values might vary, when using different motors.
23
38
62
0
10
20
30
40
50
60
70 AAJM01 Reversible 40 C50 Hz
25
44
65
0
10
20
30
40
50
60
70SAJM03 Unidirectional 300 C/120 min. 50 Hz
0
10
20
30
40
50
60
70
SAJM03 Reversible 300 C/120 min. 50 Hz
DN 315 DN 355 DN 400
38
23
60
-
Thrust [N
]Th
rust [N
]
SAJM04 Unidirectional 400 C/120 min. 50 Hz
0
10
20
30
40
50
60
70
DN 315 DN 355 DN 400
Thrust [N
]
SAJM04 Reversible400 C/120 min. 50 Hz 23
38
60
0
10
20
30
40
50
60
70
DN 315 DN 355 DN 400DN 315 DN 355 DN 400
65
24
45
SRJM03Unidirectional300 C/120 min.50 Hz
DN 500 DN 560
DN 500 DN 560
Pollrich DLK Fan Factories 13
Comparison of Jetfans
43
75
0
10
20
30
40
50
60
70
80 CRJM01, Unidirectional 40 C50 Hz
Maximum values indicated. Values might vary, when using different motors.
DN 315 DN 355 DN 400
Thrust [N
]
43
75
0
10
20
30
40
50
60
70
80
-
Product-specific information
14 Pollrich DLK Fan Factories
Range of application:The product line Alujet by Pollrich DLK combines functionality with the latest design and sets new standards for axial Jetfan-technology.
The essential benefits are:- Maximum thrust and maximum efficiency
through CFD-optimised design
- Easiest handling due to aluminium lightweight construction
- Weight savings up to 50% compared to common products
- Worldwide applica-ble, 50 Hz- and 60 Hz (on request)
- Whisper mode through high performance polygone silencer
- Optimum solutions through product diversity: 3 fan sizes, unidirectional or fully reversible, single speed or dual speed motors
- Temperature class F300 resp. F400- CE-certified according to EN 12101-3- DIBt-approved
All smoke extraction Jetfans are available for combined ventilati-on and smoke extraction or as version for ventilation/CO-management only.
Permissible conveying temperatures:-20 up to +40 C (ventilation). In case of fire 300 C/120 min. resp. 400 C/120 min.
AXIAL-JETFANS AAJM and SAJMDN 315 DN 400
ufive
-
Pollrich DLK Fan Factories 15
Product-specific information
Alujet by Pollrich DLK
Casing:Made of aluminium with
riveted motor bracket (in-cluding aluminium silencer).
Optional: special coating on request.
Impeller:Hub and impeller blades made of a highly corrosion-resistant aluminium alloy (saltwater-proof). Profiled blades adjustable during standstill. Optional: fully reversible
Drive:Three phase motor according to EN 12101-3 / IEC norm motor 400V/50Hz. Suitable for continuous operation S1. Ambient temperature for motor max. 40 C. Motor performance selected for cold start-up at 20 C.
Performance adjustment:Our motors are are optionally equipped with PTC resistors for operation with frequency converters with sinusoidal filters. As option, the motor PTC resistor can be extended to the fan terminal box. The max. speed of the impeller and the max. power output of the motor must be taken into consideration. As standard, the motors can be operated at 50 Hz (60 Hz on request). In case of fire, the PTC has to be bridged, in order to ope-rate the fan at main supply.
Direction of airflow:Upstream motor (motor -> impeller) for unidirectional fans, optionally reversible.
Sound:All sound values measured in the labora-tory on the basis of EN 45635.
Installation:As standard suitable for horizontal installation.
Dimensions:All dimensions in mm, weights in kg.
Specifications:Available in the download area of our website www.pollrichdlk.com
Subject to change.
Isolator switch on request.
-
315 mm Axial-Jetfan, unidirectional / reversible, AAJM and SAJM
16 Pollrich DLK Fan Factories
All specifications for 400V/50 Hz/3~
Type code
Thrust
[N]No. of
poles
Max. motor
power [kW]Order no.
Max. speed
[1/min]Voltage
[V] ConnectionNominal
current [A]Starting
current [A]Sound pressure level
Lp (3m) [dB(A)]Weight [kg]
40C AAJM01-0315-B 25 2 1.1 B215010 2875 400 Y 2.37 16.59 58 37
40C AAJM01-0315-B 24/6 2/4 0.95/0.25 B215148 2825/1380 400 YY/Y 2.33/0.87 17.17/4.62 58/39 42
F300 SAJM03-0315-B 24 2 1.1 B215174 2840 400 Y 2.45 17.15 58 41
F300 SAJM03-0315-B 25/7 2/4 0.95/0.25 B215176 2870/1410 400 YY/Y 2.32/0.89 17.4/4.9 58/39 40
F400 SAJM04-0315-B 24 2 1.1 B215183 2810 400 Y 4.03 13.9 58 42
F400 SAJM04-0315-B 24/6 2/4 1.1/0.25 B215185 2810/1390 400 YY/Y 2.41/0.75 14.4/2.9 58/37 43
unidirectional
Type code
Thrust
[N]No. of
poles
Max. motor
power [kW]Order no.
Max. speed
[1/min]Voltage
[V] ConnectionNominal
current [A]Starting
current [A]Sound pressure level
Lp (3m) [dB(A)]Weight [kg]
40C AAJM01-0315-B 23 2 1.1 B214334 2875 400 Y 2.37 16.59 59 37
40C AAJM01-0315-B 23/6 2/4 0.95/0.25 B215150 2825/1380 400 YY/Y 2.33/0.87 17.17/4.62 59/39 42
F300 SAJM03-0315-B 23 2 1.1 B215170 2840 400 Y 2.45 17.15 59 41
F300 SAJM03-0315-B 23/6 2/4 0.95/0.25 B215172 2870/1410 400 YY/Y 2.32/0.89 17.4/4.9 60/40 40
F400 SAJM04-0315-B 23 2 1.1 B215187 2810 400 Y 4.03 13.9 59 42
F400 SAJM04-0315-B 23/6 2/4 1.1/0.25 B215189 2810/1390 400 YY/Y 2.41/0.75 14.4/2.9 59/39 43
reversible
[unidirectional]
[reversible]
12.5AIR 270
440
345
420460
317750 75018201963
12,5AIR 270
440
345
420460
317750 75018202106
Alujet by Pollrich DLK
-
355 mm Axial-Jetfan, unidirectional / reversible, AAJM und SAJM
Pollrich DLK Fan Factories 17
All specifications for 400V/50 Hz/3~
Type code
Thrust
[N]No. of
poles
Max. motor
power [kW]Order no.
Max. speed
[1/min]Voltage
[V] ConnectionNominal
current [A]Starting
current [A]Sound pressure level
Lp (3m) [dB(A)]Weight [kg]
40C AAJM01-0355-B 46 2 1.5 B219652 2890 400 Y 3.16 22.12 63 48
40C AAJM01-0355-B 42/11 2/4 1.4/0.3 B219654 2840/1380 400 YY/Y 3.43/0.85 24.94/4.51 62/41 48
F300 SAJM03-0355-B 44 2 1.5 B219983 2840 400 Y 3.26 22.82 63 51
F300 SAJM03-0355-B 44/11 2/4 1.4/0.3 B219988 2880/1430 400 YY/Y 3.08/1.1 23.7/6.05 63/41 53
F400 SAJM04-0355-B 45 2 1.5 B220012 2900 400 Y 3.54 21.1 63 50
F400 SAJM04-0355-B 46/12 2/4 1.5/0.37 B220014 2900/1435 400 YY/Y 3.54/1.25 23/5.6 64/41 48
unidirectional
Type code
Thrust
[N]No. of
poles
Max. motor
power [kW]Order no.
Max. speed
[1/min]Voltage
[V] ConnectionNominal
current [A]Starting
current [A]Sound pressure level
Lp (3m) [dB(A)]Weight [kg]
40C AAJM01-0355-B 38 2 1.5 B219642 2890 400 Y 3.16 22.12 63 48
40C AAJM01-0355-B 37/10 2/4 1.4/0.3 B219644 2840/1380 400 YY/Y 3.43/0.85 24.94/4.51 62/38 48
F300 SAJM03-0355-B 38 2 1.5 B219997 2840 400 Y 3.14 22.82 62 51
F300 SAJM03-0355-B 38/10 2/4 1.4/0.3 B219999 2880/1430 400 YY/Y 3.08/1.1 23.7/6.05 62/41 53
F400 SAJM04-0355-B 38 2 1.5 B220006 2900 400 Y 3.54 21.1 62 50
F400 SAJM04-0355-B 38/10 2/4 1.5/0.37 B220010 2900/1435 400 YY/Y 3.54/1.25 23/5.6 62/41 49
reversible
[unidirectional]
[reversible]
12.5AIR 270
500
385
470510
357800 80019202073
AIR 12,5
22261920
800800 357
510470
385
500
270
Alujet by Pollrich DLK
-
18 Pollrich DLK Fan Factories
All specifications for 400V/50 Hz/3~
400 mm Axial-Jetfan, unidirectional / reversible, AAJM and SAJM
Type code
Thrust
[N]No. of
poles
Max. motor
power [kW]Order no.
Max. speed
[1/min]Voltage
[V] ConnectionNominal
current [A]Starting
current [A]Sound pressure level
Lp (3m) [dB(A)]Weight [kg]
40C AAJM01-0400-B 67 2 2.2 B216308 2890 400 Y 4.48 31.36 66 59
40C AAJM01-0400-B 65/17 2/4 2.5/0.65 B216306 2840/1400 400 YY/Y 5.25/1.85 39.37/10.17 65/44 73
F300 SAJM03-0400-B 65 2 2.2 B216323 2840 400 Y 4.61 32.27 65 62
F300 SAJM03-0400-B 63/16 2/4 1.9/0.4 B216321 2885/1380 400 YY/Y 4.18/1.47 31.35/8.1 66/44 62
F400 SAJM04-0400-B 65 2 2.2 B216347 2840 400 Y 4.47 33.5 65 63
F400 SAJM04-0400-B 65/17 2/4 2.2/0.5 B216345 2845/1420 400 YY/Y 4.63/1.54 27.8/5.38 65/42 63
[unidirectional]
Type code
Thrust
[N]No. of
poles
Max. motor
power [kW]Order no.
Max. speed
[1/min]Voltage
[V] ConnectionNominal
current [A]Starting
current [A]Sound pressure level
Lp (3m) [dB(A)]Weight [kg]
40C AAJM01-0400-B 62 2 2.2 B215842 2890 400 Y 4.48 31.36 67 59
40C AAJM01-0400-B 60/15 2/4 2.5/0.65 B215840 2840/1400 400 YY/Y 5.25/1.85 39.37/10.17 66/43 73
F300 SAJM03-0400-B 60 2 2.2 B216319 2840 400 Y 4.61 32.27 66 62
F300 SAJM03-0400-B 57/15 2/4 1.9/0.4 B216317 2885/1380 400 YY/Y 4.18/1.47 31.35/8.1 65/44 62
F400 SAJM04-0400-B 60 2 2.2 B216343 2840 400 Y 4.47 33.5 66 63
F400 SAJM04-0400-B 60/15 2/4 2.2/0.5 B216341 2845/1420 400 YY/Y 4.63/1.54 27.8/5.38 66/43 63
[reversible]
[unidirectional]
[reversible]
AIR 12.5
21832020
850850 402
560520
430
560
270
AIR 12,5
23462020
850850 402
560520
430
560
270
Alujet by Pollrich DLK
-
Pollrich DLK Fan Factories 19
-
Product-specific information
20 Pollrich DLK Fan Factories
Range of application:The product line AlujetPad by Pollrich DLK combines functionality with the latest design and sets new standards for centrifu-gal Jetfan-technology.
The essential benefits are:- Maximum thrust at
lowest height and maximum efficiency through CFD-optimised design
- Easiest handling due to aluminium lightweight construction
- Weight savings up to 60% compared to common products
- Optimum-solution through product diversity: 2 fan sizes, high perfor-mance centrifugal impeller, single speed or dual speed motors
- Temperature class F300.- CE-certified according to
EN 12101-3- DIBt approved
All smoke extraction Jetfans are available for combine ventilation and smoke extraction or as version for ventilation/ CO-management only.
Permissible conveying temperatures:-20 up to +40 C (CO-management). In case of fire 300 C/120 min.
CENTRIFUGAL-JETFANS CRJM and SRJM DN 500, 560
ufive
-
Pollrich DLK Fan Factories 21
Product-specific information
AlujetPad by Pollrich DLK
Casing:Made of aluminium with aerodynamically optimised inlet nozzle made of coated steel with integrated motor bracket.
Impeller:High performance impeller, aerodynami-cally optimised, single inlet with welded, backward curved blades.
Drive:Three phase motor according to EN 12101-3 / IEC norm motor 400V/ 50 Hz, protection class IP55, insulation class F/H. Suitable for continuous operation S1. Ambient temperature for motor max. 40 C. Motor performance selected for cold start-up at 20 C.
Performance adjustment:The motors have no PTC resistors. For operation with frequency converter the motor current has to be monitored. The max. speed of the impeller and the max. power output of the motor must be taken into consideration.
Sound:All sound values measured in the labora-tory on the basis of EN 45635.
Installation:As standard suitable for horizontal installation.
Dimensions:All dimensions in mm, weights in kg.
Specifications:Available in the download area of our website www.pollrichdlk.com
Subject to change.
Isolator switch on request.
-
500 mm Centrifugal-Jetfan CRJM and SRJM
22 Pollrich DLK Fan Factories
All specifications for 400V/50 Hz/3~
[unidirectional]
AlujetPad by Pollrich DLK
14
500
279
755
815
855
370267
1428
Type code
Thrust
[N]No. of
poles
Max. motor
power [kW]Order no.
Max. speed
[1/min]Voltage
[V] ConnectionNominal
current [A]Starting
current [A]Sound pressure level
Lp (3m) [dB(A)]Weight [kg]
40C CRJM01-0500-B 43 4 1.5 B222250 1440 400 Y 3.26 20.5 73 63
40C CRJM01-0500-B 42/11 4/8 1.6/0.4 B222247 1420/700 400 YY/Y 3.8/1.69 21.66/5.41 73/55 61
F300 SRJM03-0500-B 42 4 1.5 B222199 1420 400 Y 3.29 20.5 73 63
F300 SRJM03-0500-B 42/11 4/8 1.6/0.4 B222191 1420/700 400 YY/Y 3.8/1.69 21.66/5.41 73/55 61
unidirectional
-
560 mm Centrifugal-Jetfan CRJM and SRJM
Pollrich DLK Fan Factories 23
All specifications for 400V/50 Hz/3~
AlujetPad by Pollrich DLK
[unidirectional]
14307 370
996
956
896
294
X
560
1430
Type code
Thrust
[N]No. of
poles
Max. motor
power [kW]Order no.
Max. speed
[1/min]Voltage
[V] ConnectionNominal
current [A]Starting
current [A]Sound pressure level
Lp (3m) [dB(A)]Weight [kg]
40C CRJM01-0560-B 75 4 2.2 B222518 1420 400 Y 4.64 34 76 70
40C CRJM01-0560-B 61/16 4/8 1.6/0.4 B222513 1420/700 400 YY/Y 3.8/1.69 21.66/5.41 76/58 70
F300 SRJM03-0560-B 75 4 2.2 B222525 1410 400 Y 5.19 34 76 70
F300 SRJM03-0560-B 61/16 4/8 1.6/0.4 B222523 1420/700 400 YY/Y 3.8/1.69 21.66/5.41 76/58 70
X = 30 mm. (only for motor 2.2 kW)
unidirectional
-
Range of application:The low pressure axial fans of product line Toromax by Pollrich DLK (SAOM) are suitable for ventilation up to 40C and up to 300C/120 minutes in case of smoke extraction.
The essential benefits are:- Aerodynamically optimised
impeller with profiled single blades
- Blade angle adjustable during standstill for optimal adjust-ment to the operating point
- Impeller made of a highly corrosion-resistant aluminium alloy
- High efficiencies with low sound levels
- Wide range of accessories - Energy efficient IE2-motors with
PTC resistor
Permissible conveying temperatures:-20 up to +40 C (ventilation). In case of fire: 300 C/120 min.
Exhaust air 1: AXIAL FAN SAOMDN 500 - DN 1400
Product-specific information
24 Pollrich DLK Fan Factories
ufive
-
0200
400
600
800
1000
1200
1400
1600
1800
2000
0 50000 100000 150000 200000 250000
Casing:Made of steel, welded, with flanges on both sides and riveted resp. welded mo-tor bracket. Optimal corrosion protection by powder-coating (RAL 7015). Optional: hot-dip galvanising or special coating.
Impeller:Hub and impeller blades made of a highly corrosion-resistant aluminium alloy (saltwater-proof). Profiled blades adjustable during standstill.
Drive:Three phase motor according to EN12101-3/IEC-norm motor according to energy efficiency class IE2. PTC resistor optional. Protection class IP 55, insulation class H.
Electrical connection:Directly at fan terminal box in protection class IP65.
Direction of airflow:Downstream motor (impeller -> motor). On request upstream motor (motor -> impeller).
Toromax by Pollrich DLK
Product-specific information
Total p
ressure increa
se p
f [Pa]
Flow rate qV [m3/h]
Installation:As standard suitable for horizontal instal-lation. Vertical installation on request.
Dimensions:All dimensions in mm, weights in kg.
Accessories: Various accessories are available, see catalogue: smoke extraction fans.
Specifications:Available in the download area of our website www.pollrichdlk.com
Subject to change.
DN
[mm]
Max. speed [1/min]
Max. continuous temperature [C]
Max. motor power [kW]
Max.flow rate [m/h]
Max. total pressure increase [Pa]
Weight
[kg]
500 3600 40 7,5 23000 890 35-100560 3600 40 11 32000 1180 59-109630 3600 40 18,5 41000 1430 67-111710 3000 40 22 60000 1800 81-120800 1800 40 15 48000 580 108-156900 1800 40 18,5 55400 650 144-287
1000 1800 40 30 82500 800 171-3961120 1800 40 45 116000 930 328-4601250 1800 40 90 162000 1120 350-8721400 1500 40 90 215000 1380 458-950
All indicated values for 400V/50Hz/3~.
Pollrich DLK Fan Factories 25
-
Product-specific information
EXHAUST AIR 2: AXIAL FAN SANM WITH OUTLET GUIDE VANES, DN 500 - DN 1600Range of application:The medium pressure axial fans of product line ToromaxPro by Pollrich DLK (SANM) are suitable for ventilation up to to 40C and up to 300C/120 minutes in case of smoke extraction.
The essential benefits are:- Aerodynamically optimised
impeller with profiled single blades
- Blade angle adjustable during standstill for optimal adjustment to the operating point
- Impeller made of a highly corrosion-resistant alumini-um alloy (up to
DN 1120)- Highest efficiencies and
high pressure due to opti-mised outlet guide vanes
- Low sound levels- Wide range of accessories - Energy efficient with IE2-
motors (up to DN 1120). PTC resistor optional.
Permissible conveying tempera-tures:-20 up to +40 C (ventilation). In case of fire: 300 C/120 min resp. 400 C/ 120min.
Casing:Made of steel, welded, with flanges on both sides and welded motor bracket. Optimal corrosion protection by powder-coating (RAL 7015). Optional: hot-dip galvanising or special coating.
ufive
26 Pollrich DLK Fan Factories
-
Product-specific information
Impeller:Hub and impeller blades made of a highly corrosion-resistant aluminium alloy (saltwater-proof, DN 315 DN 1120). SANM03: DN 1250 DN 1400 im-peller made of steel, powder coated (optional: stainless steel) SANM04: DN 1250 DN 1600 hub made of steel powder coated. Profiled blades adjustable during standstill.
Drive:Three phase motor according to EN 12101-3 / IEC- norm motor according to energy efficiency class IE2 (up to DN 1120). PTC resistor optional. Protection class IP 55, insulation class H.
Electrical connection:Directly at terminal box in protection class IP65
Direction of airflow:Downstream motor (impeller -> motor).
Installation:As standard suitable for horizontal installation. Vertical installation on request.
Dimensions:All dimensions in mm, weights in kg.
Accessories: Various accessories are available, see catalogue: smoke extraction fans.
Specifications:Available in the download area of our website www.pollrichdlk.com
Subject to change.
ToromaxPro by Pollrich DLK
DN
[mm]
Max. speed
[1/min] SANM03 SANM04
Max. continuous temperature [C]
Temperature class
SANM03 SANM04
Max. motor power [kW]
Max.flow rate [m/h] SANM03 SANM04
Max. total pressure increase [Pa]SANM03 SANM04
Weight
[kg]
Flow rate qV [m3/h]
Total p
ressure increa
se p
f [Pa]
All indicated values for 400V/50Hz/3~.
500 3000 3000 40 F300 F400 7,5 21100 21100 1285 1285 51-109
560 3000 3000 40 F300 F400 7,5 23500 23500 1315 1315 58-119
630 3000 1500 40 F300 F400 18,5 35000 26000 1720 400 74-121
710 1500 1500 40 F300 F400 11 37000 37000 580 580 122-232
800 1500 1500 40 F300 F400 18,5 54000 54000 890 890 168-301
900 1500 1500 40 F300 F400 30 74500 74500 1140 1140 211-417
1000 1500 1500 40 F300 F400 45 100000 100000 1290 1290 320-531
1120 - 1500 40 - F400 45 - 125000 - 1270 373-575
1250 1500 1500 40 F300 F400 90 149500 160000 2670 1625 810-1200
1400 1000 1000 40 F300 F400 55 160000 148700 1540 875 810-1245
1600 - 1000 40 - F400 55 - 208000 - 1150 950-1250
Total p
ressure increa
se p
f [Pa]
Flow rate qV [m3/h]
Pollrich DLK Fan Factories 27
0
500
1000
1500
2000
2500
3000
0 50000 100000 150000 200000
0
200
400
600
800
1000
1200
1400
1600
1800
0 50000 100000 150000 200000 250000
-
Range of application:The medium pressure axial fans of product line ToromaxPro duplex by Pollrich DLK in two-stage design (SAGM) are suitable for ventilation up to 40 C and up to 300 C/120 minutes in case of smoke extraction, particu-larly for applications demanding high pressure increase.
The essential benefits are:- Aerodynamically optimised
impeller with profiled single blades
- Blade angle adjustable during standstill for optimal adjust-ment to the operating point
- Impeller made of a highly corrosion-resistant aluminium alloy (up to DN 1120)
- Highest efficiencies due to optimi-sed outlet guide vanes
- Highest pressures due to two-stage design
- Low sound levels- Wide range of accessories - Energy efficients IE2-motors (up to DN 1120). PTC resistor optional.
Permissible conveying temperatures:-20 up to +40 C (ventilation). In case of fire: 300 C/120 min resp. 400 C/120 min.
Casing:Made of steel, welded, with flanges on both sides and welded motor bracket. Optimal corrosion protec-tion due to powder-coating (RAL 7015). Optional: hot-dip galvanising or special coating.
EXHAUST AIR 3: AXIAL FAN SAGM WITH OUTLET GUIDE VANES DN 500 DN 1600
ufive
Product-specific information
28 Pollrich DLK Fan Factories
-
Impeller:Hub and impeller blades made of a highly corrosion-resistant aluminium alloy (saltwater-proof, DN 315 DN 1120).SAGM03: DN 1250 DN 1400 impeller made of steel, powder coated (optional: stainless steel) SAGM04: DN 1250 DN 1600 hub made of steel powder coated. Profiled blades adjustable during standstill.
Drive:Three phase motor according to EN 12101-3 / IEC- norm motor according to energy efficiency class IE2 (up to DN 1120). PTC resistor optional. Protection class IP 55,insulation class H.
Electrical connection:Directly at terminal box in protection class IP65.
Direction of airflow:Downstream motor (impeller -> motor).
Installation:As standard suitable for horizontal installation. Vertical installation on request.
Dimensions:All dimensions in mm, weights in kg.
Accessories: For various installation situations, see catalogue smoke extraction fans
Specifications:Available in the download area of our website www.pollrichdlk.com
Subject to change.
ToromaxPro duplex by Pollrich DLK
All indicated values for 400V/50 Hz/3~
0
1000
2000
3000
4000
5000
6000
0 50000 100000 150000 200000
0
500
1000
1500
2000
2500
3000
3500
0 50000 100000 150000 200000 250000
Total p
ressure increa
se p
f [Pa]
Flow rate qV [m3/h]
Total p
ressure increa
se p
f [Pa]
Flow rate qV [m3/h]
DN[mm]
Max. speed
[1/min] SANM03 SANM04
Max. continuous temperature [C]
Temperature class
SANM03 SANM04
Max. motor power [kW]
Max.flow rate [m/h] SANM03 SANM04
Max. total pressure increase [Pa]SANM03 SANM04
Weight
[kg]
500 3000 3000 40 F300 F400 7,5 21100 21100 42208 42208 107-229
560 3000 3000 40 F300 F400 7,5 23500 23500 47008 47008 121-250
630 3000 1500 40 F300 F400 18,5 35000 26000 70019 52019 155-254
710 1500 1500 40 F300 F400 11 37000 37000 74011 74011 256-487
800 1500 1500 40 F300 F400 18,5 54000 54000 108019 108019 353-632
900 1500 1500 40 F300 F400 30 74500 74500 149030 149030 443-632
1000 1500 1500 40 F300 F400 45 100000 100000 200045 200045 672-1150
1120 - 1500 40 - F400 45 - 125000 - 250045 783-1208
1250 1500 1500 40 F300 F400 90 149500 160000 299090 320090 1700-2615
1400 1000 1000 40 F300 F400 55 160000 148700 320055 297455 1700-2520
1600 - 1000 40 - F400 55 - 208000 - 416055 1995-2560
Product-specific information
Pollrich DLK Fan Factories 29
-
TAYLOR MADE CONTROL SYSTEMS FOR CONTROL AND MONITORING
Control system, Installation, commissioning and maintenance
A state of the art control system is es-sential for car park ventilation systems. Tayloring the system controls ensures a correct functioning as well as optimal performance. The individual tuning of the system ensures that requirements regarding performance, energy- and cost efficiency are precisely met.
The control functions are stored in a controller that constantly interprets the state and signals from all system com-ponents.
The controller is preset to determine what functions are required and controls the ventilation system accordingly.Preseting the controller enables optimum safety during situations where effective ventilation is required.
The system is tuned to ensure low pollution levels in fresh air ventilation mode, whilst obtaining the most energy effective running mode of the fans. This usually includes switching and speed control of individual fans.
CO-sensor
NO2-sensor
LPG-sensor
Repeater for cables > 900m
Controller (analogue / digital)
Control box (control panel)
Contactor Frequency- converter
Jetfans Exhaust fans
Warning horn
Combination flashlight/
warning horn
CO-warning sign with
text
+ warning horn/flash-
light
If smoke extraction functionality is re-quired, a smoke detection system must be incorporated. The system is switched to an optimal state of ventilation when the smoke detection system is activated. Several different states are possible, depending on the size and layout of the car park and ventilation system.The system is set to assist safe evacua-tion of persons during fire and to assist fire fighting by directing the flow of smoke to predetermined routes.
Uninterruptable Power Source
(UPS)
30 Pollrich DLK Fan Factories
-
Control system, Installation, commissioning and maintenance
Pollrich DLK Fan Factories 31
Warning signs
Order no.
B228179 24 V / DC
B228181 230 V / AC
Warning signs enable visual warning of dangerous carbon monoxide levels or a failure of the ventilation system in car parks,
tunnels, shelters, loading zones and other confined spaces where a visual warning of dangerous gas levels is required.
CO-sensor
Order no.
B228160 analogue
B228168 digital
For carbon monoxide detection in a wide range of commer-
cial applications such as car parks, tunnels, confined work
spaces, loading zones, engine test rigs, shelters, indoor
go-cart tracks, etc.
The CO-sensor/transmitter with 4-20 mA output signal is
suitable for connection to the gas controller.
LPG-sensor
Order no.
B228164 analogue
B228172 digital
LPG-sensor to monitor combustable fumes and gases in a
wide range of commercial applications.
The standard output signal is suitable for connection to the
gas controller.
Controller
Order no
B228174 - digital
Extension of analogue input and output connections,
such as the alarm relais of the gas controller.
Controller
Order no.
B228166 analogue
The GC-05 gas controller is used to monitor a wide variety
of toxic or combustable fumes and gases. It is applied
industry-wide for reliable monitoring.
A large amount of free configurable parameters and limits
allows the controller to be set to the individual needs for
many applications.
In underground car parks, tunnels and other confined
spaces it complies with monitoring functions according to
(inter)national regulations and standards.
Repeater
Order no.
B228177 digital
The Connector Module is used in the system as fieldbus
protection module. One BC-module per system is obligatory.
Repeaters are also used in systems as protection modules.
The repeater serves as a signal amplifier in systems with
excessive cable length. Up to 4 repeaters can be applied
in a system.
Flashlight/warning horn (slow-whoop)
Order no.
B228237 24 V / DC
B228239 230 V / AC
Universal warning horn with integrated Xenon-flashlight for
separately controllable acoustical and visual warning.
Warning horn
Order no.
B228187 24 V / DC
B228189 230 V / AC
Universal slow-whoop warning horn with 32 different
selectable tones.
NO2-sensor
Order no.
B228162 analogue
B228170 digital
For NO2-detection in a wide range of commercial applica-
tions like car parks, traffic tunnels, engine test rigs, shelters
and loading zones with diesel trucks.
The standard output signal is suitable for connection to the
gas controller.
Flashlight
Order no.
B228235 24 V / DC
-
5Axial fansThe basic series
ufive
7
Smoke extraction fansThe basic series
ufive
32 Pollrich DLK Fan Factories
Basic seriesAs catalogue or online:
www.pollrichdlk.com
-
Pollrich Ventilatoren GmbH
Neusser Strae 172
D-41065 Mnchengladbach
phone +49(0) 2161 - 968 - 0
fax +49(0) 2161 - 968 - 300
DLK Ventilatoren GmbH
Ziegeleistrae 18
D-74214 Schntal-Berlichingen
phone +49(0) 7943 - 9102 - 0
fax +49(0) 7943 - 9102 - 10
Northern Germany
DLK Ventilatoren GmbH
Ziegeleistrae 18
D-74214 Schntal-Berlichingen
phone +49(0) 2161 - 968 - 404
fax +49(0) 2161 - 968 - 33440
mobile +49(0) 175 - 5867 095
Southern Germany
DLK Ventilatoren GmbH
Ziegeleistrae 18
D-74214 Schntal-Berlichingen
phone +49(0) 2161 - 968 - 407
fax +49(0) 2161 - 968 - 408
mobile +49(0) 171 - 9778 192
United Fans Carpark & Tunnel
Dotterbloemstraat 9
3053 JV Rotterdam
The Netherlands
phone +31(0) 10 7600 205
fax +31(0) 10 7600 206
United Fans Middle East
In foundation
P.O. box 6237,
Abu Dhabi,
United Arab Emirates
phone +971 2 628 246 8
fax +971 2 628 246 9
Partners:
Belgium, China, Middle East,
France, Netherlands, Austria, Poland,
Switzerland, Turkey
> see www.pollrichdlk.com
Service-Hotline:
phone +49(0)2161 - 968 184
fax +49(0)2161 - 968 307
Our service-team is available for you
around-the-clock
- Technical advice
- Assembly
- Commissioning
- Performance tests
- Noise and vibration measurements
- Inspection
- Preventative maintenance
- Maintenance and repair
- Electronic balancing
- System optimisation
203.E.02
.13
ufive
Car
park
ven
tilat
ion
Pollr
ich
DLK
Fan
Fac
torie
s