Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
-
Upload
sheffy-abraham -
Category
Documents
-
view
216 -
download
0
Transcript of Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
1/46
Effect of Depth on Shear capacityof Transfer Beam in High rise
building
By- Kalpesh Patel
SD0308
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
2/46
Index
Introduction to transfer beam
Study on shear capacity of RC beam
Experimental Programme
Material properties Test Procedure
Test Result And Discussion
Conclusions
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
3/46
What is Transfer beam?
To provide for functional requirement of large columnfree space in high rise building ,the RC column are
placed at the periphery of the built-up plan area.
With a view to developing high flexural and torsionalstiffness ,these column are very closely spaced and
connected through very stiff beam ,called as Spandrel
beam.
These closely spaced columns at the periphery,however, pose hindrance to the movement of people and
the goods at the ground floor and basement levels.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
4/46
To fulfill this requirement , the columns at these floorlevels have to be placed at larger spacing.
As a result an interface has to be provided between the
closely spaced columns of the upper floor and the widelyspaced columns at the ground or basement level. This
interface has to be a horizontal RC element and , hence,
is referred as Beam.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
5/46
Conventionally , a beam is taken to be a flexural member
of the structural system. The above mentioned interfacebeam, dose not behave as a flexural member ,since itgets sandwiched between closely spaced upper columnsand a little widely spaced supporting columns below it.
Also to transfer the high magnitude of loads collectedfrom all the upper floor of a high-rise building , the depthof the interface beam has to kept much higher than theconventional beams , ranging from 1 m to 4.5 m.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
6/46
As the result of this , the load transfer mechanism
through this beam becomes altogether different from theconventional mechanism of flexure , and failure of such
beam is in brittle mode.
Such a beam is referred to as TRASFER BEAM
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
7/46
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
8/46
It is therefore , required to generate the shear capacityof transfer beams.
Figure shows a 25 storey building having Transfer beamof 1.7 m depth provided at ground floor level to create aspace for free movement of people and for parkingpurpose.
In spite of its wide structural application , only a fewnational codes include their design.
For example , the British standard BS 8110 for structuraluse of concrete explicitly state that, for the design ofdeep beams , reference to be made to specialistliterature
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
9/46
Similarly,Euro-2 for design of concrete structure statethat itis not apply to the deep beam.
Consequently, there is no specific , unified , and rational
design procedure available in the codes of thesecountries.
I describe the experimental studies conducted on beam
of different depth to investigate the effect of depth onshear capacity of transfer beam in high rise buildings.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
10/46
Study on shear capacity of RC beam
What is shear span?
it is the horizontal distance between load on top of
beam and support.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
11/46
The study on beam related to varying shear- span todepth ratio (a/d) has been carried out by varying the depth
(d) and not by varying the shear span (a).
This has been done to achieve flow of applied loadthrough the entire depth of body of concrete.
This allows the concrete to develop stress over the fulldepth of beam which varies non-linearly across the depth.
This aspect is very distinct, important and relevant from
view points of the structural response of the beams.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
12/46
It is to be particularly noted that the same value of a/dcan be attained by varying the shear span (a) which iseasy to implement since it simply demands shifting of thetop loading points toward the supports.
This way of varying the shear span-to-depth ratio dosenot result in the true structural response as in a deepbeam to be used as a transfer beam.
The failure patterns are significantly different in the twosets of beams , one obtained by varying the depth (d) ,and second by varying the shear-span (a) having thesame a/d ratio.
The primary objective of the research is to build-up shearresisting capacity in RC beams by increasing the depth.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
13/46
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
14/46
Experimental Programme
Shear strength of concrete is evaluated experimentally.
This is so primarily due to interlocking of the coarseaggregates among themselves.
As a result of particle interlocking , it is not feasible toapply a shearing action ( direct shearing force) in a plane ,as is customarily done in the case of metals.
Experiments have to be , therefore , devised to indirectlyasses the shear strength of concrete.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
15/46
In one of the popularly adopted devices, a beam of
appropriate length is subjected to shearing and
bending action under 4 points loading system (2-
active and 2-passive forces) as shown in fig.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
16/46
Beam subjected to be constant shear is refereed to asshear span , which offers itself to be studied forperformance under shear , bending being negligible forshort shear span.
In the present study, such a device has been adopted tostudy the performance of concrete under direct shearing
action.
Once steel bars are introduction generally along adirection perpendicular to shearing force , these bars startcoming in to action to resist shearing force.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
17/46
Thus , steel bars becomes essential linked to resisting
shearing force along with the inherent concrete resistance.
The shear resistance due to these longitudinal steel barsis commonly referred as dowel effect.
The primary design variable was depth in term of shearspan-to-depth ratio.
The study aims to investigation the effect of depth ofbeams in terms of shear span-to-depth ratio on shearstrength of concrete.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
18/46
Material properties
The test specimens were cast using cement , fine
aggregate, coarse aggregate , water and
susperplasticizer. The materials, in general, conformed to
the specification laid down in the relevant Indian Standard
Codes. For grading of fine and coarse aggregate , sieve
analysis was carried out.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
19/46
Cement:
ordinary portland cement of 43-grade conforming toIS:8112:1989 was used throughout the experimentalwork.
All test were carried out as per IS:4031-1988
The specific gravity and finess respective were 3.14 and275 m2/kg
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
20/46
Coarse aggregate:
Crushed granite obtained from a local source was usedas coarse aggregate and maximum size used was 20
mm along with 10 mm size.
Fine aggregate:
Locally available sand was used as fine aggregate. The
specific gravity was 2.6 and fineness modulus was 2.29.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
21/46
Superplasticizer:
A modified melamine based highly effective high range
water reducing concrete admixture was used throughout
the investigation. It was dark brown in colour having 1.22
specific gravity.
Reinforcing steel rebar:
Thermo mechanically treated (TMT) rebar of Fe 415grade was used.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
22/46
Concrete Mix Design
The concrete mix were designed in accordance with the
Indian standard recommended method of concrete mix
design (IS 102621982).
The concrete mix table was prepared for 400kg/m3
cement content.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
23/46
Table-1: Concrete Mix properties
Sr. No. Description Value
1 Cube compressive strenth (MPa) 43.00
2 Cement (kg) 24.50
3 Fine Aggregate (Send) (kg) 44.50
4 Coarse Aggregate (kg) 81.00
5 Water - Cement Ratio 0.32
6 Water (Litres) 7.80
7 Plasticizer as % of wt. of cement 0.85
8 Mix Proportion 1:1.82:3.31
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
24/46
Test specimen
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
25/46
Twelve specimens were designed and fabricated. The
span of beam kept constant at 1 m with 0.1 moverhanging on either side of the supports.
The spacing between the top two pointsloads has been
kept at 200 mm as shown in fig . The depth of the beamvaried at 150 , 200, 250, 300, 350, and 400 mm to
achieve desired six shear span to depth ratio (a/d ratios).
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
26/46
All beam were rectangular in cross section, 100 mm
wide .
Standard cubes (150 mm X 150 mm X 150 mm), cylinder
(150 mm X 300 mm), were cast with each mix to know
the various mechanical properties of concrete.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
27/46
Test Procedure
After 28 days curing period, the beam specimens were
removed from the curing tank and both sides of the beam
were white-washed to aid observation of crack
development during testing.
Load was applied gradually with the help of jack and
deflection of proving ring was recorded to find the failure
load.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
28/46
All the beams were tested to failure under four-point
loading test set-up (2-active, 2-passive) as shown in fig-
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
29/46
The cube specimens were tested for compressive
strength, the cylinder specimens for split tensile strength.
Crack in beam
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
30/46
Test Result And Discussion
The result obtained from the experimental investigation
are shown in table-2.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
31/46
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
32/46
All beam specimens failed in shear i.e. a sudden failure
without warning , loud noise at failure with the
appearance of single shear crack in the shear span andfine flexural cracks in the middle portion of the beam.
The shear crack crosses the compression zone of the
beam. Figure shows typical crack pattern for RC beamspecimens of different a/d ratio.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
33/46
1.for depth D=150 mm
2.for depth D=200 mm
3.for depth D=250 mm
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
34/46
4.for depth D=300 mm
5.for depth D=350 mm
6.for depth D=400 mm
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
35/46
From, the result obtained , the effect of depth of beam in
term of shear spantodepth ratio on shear strength of
concrete are analyzed and discussed as follows.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
36/46
Effect of depth of beams in terms of
shear span-to-depth (a/d) ratio
The shear strength of concrete beams for different
depths at 28 days curing age and the variation of shear
strength with different shear span-to-depth ratio is shownin table-2.
It is evident from the plots that high shear strength is
developed at lower value of span-to-depth ratio and theshear strength decreases at higher value of span-to-
depth ratio.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
37/46
0.75
1.25
1.75
2.25
2.75
0.25
1.1 1.23 1.45 1.78 2.29 3.2
Shear spantodepth ratio
Shearstress(MPa)
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
38/46
Figure shows the effect of shear span-to-depth ratio onnominal shear stress at diagonal cracking , which isobtained by dividing measured failure load to the nominalcross sectional area (bXd).
As the shear span-to-depth (a/d) ratio decreases, theshear strength increases .
The increase in shear strength is significant in RC beamspecimens with a/d ratio less than about 1.78 (AI-0.8/1.10, AII-0.8/1.23 , AIII-0.8/1.45) , because a
significant portion of the shear is transmitted directly tothe support by an inclined strut.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
39/46
This mechanism is frequently referred to as arch action
and the magnitude of direct load transfer increases with
decreasing a/d ratio.
The shear strength of RC beam with a/d ratio less than
1.78 is higher than those of RC beam with a/d ratio more
than 1.78.
This result is due to the beneficial effect of direct load
transfer to the support by arch action or so called strut-
and-tie load transfer mechanism.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
40/46
The transition point between the arch action and beam
action ( or transfer beam and normal beams) lies
between a/d ratio 1.45 to 1.78.
Either side of this a/d ratio , behaviors of RC beams in
term of load resisting mechanism , failure pattern and the
noise at failure , were entirely different.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
41/46
Conclusions
The primary objective of the research was to built-upshear resisting capacity in beam by increasing the depthof the experimental result and the nature of variation of
shear strength against independent parameters , thefollowing broad conclusions are arrived at:
1.shear resisting capacity of beam significantly dependsupon the shear span-to depth ratio (a/d)
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
42/46
Beam with higher value of a/d (a/d > 1.8) exhibitincreasing influence of moment and hence developflexuralshear crack in the tension zone.
Such beam may be categorized as normal beams(flexural beams) and have a/d ratio in excess of 1.8
2.shear resisting capacity of beam in the lower range of a/dratio (a/d
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
43/46
The beams fail in sudden splitting mode with increasingloud sound. Sudden splitting with loud sound is a
measure of brittleness.
This may be taken as a transition zone between a normalbeam and a deep beam.
3.beams with a/d
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
44/46
This is of particular interest since transfer beam fall inthis rang of a/d ratio.
While the beam shows very high shear resistance , theytend to fail in highly brittle mode.
This mode is characterized by sudden failure in shear
with very loud sound .
This mode of failure is considered undesirable and isbranded as treacherous.
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
45/46
References:
Building code requirement for structural concrete and commentary
(ACI-318)
Structure use of concrete-part 1:code of practice for design and
construction (BS-8110)
Civil engineering and construction review magazine.
IS : 456-2000
Reinforced concrete design : by H.J.Shah
-
8/12/2019 Effect of Depth on Shear Capacity of Transfer Beam in High Rise Building Ppt
46/46
THANKYOU