EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE
REPORT SUMMARY
Developed by: Southern California Edison Design & Engineering Services 6042 N. Irwindale Avenue, Suite B Irwindale, California 91702 September 7, 2004
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 2 DESIGN & ENGINEERING SERVICES 9/07/2004
THE ORIGINAL MOTIVATION FOR THE STUDY
BACKGROUND: KEY ASSUMPTIONS IN THE SEER RATING METHODOLOGY
ANALYSIS METHODOLOGY: UNDERSTANDING WHAT IMPACTS SEER
ANALYSIS METHODOLOGY: SIMULATION ANALYSIS PROCESS
FINDINGS REGARDING KEY ASSUMPTIONS OF THE SEER RATING PROCEDURE
FINDINGS THAT ADDRESS THE QUESTIONS THAT GUIDED THE RESEARCH
SUMMARY OF FINDINGS
NEXT STEPS
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 3 DESIGN & ENGINEERING SERVICES 9/07/2004
The Original Motivation for the Study
It was expected that the EER and SEER alternative ratings would correlate with one another. The data in Figure 1 (approximately 13,000 HVAC systems) show this not to be true.
Figure 1: Performance Characteristics of SEER-rated Cooling Systems Rated SEER (at 82°F) versus Rated EER (at 95°F)
8
9
10
11
12
13
14
15
10 11 12 13 14 15 16 17 18
SEER
EER
Air Conditioners Heat Pumps
Number of Units in Sample = 12898
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 4 DESIGN & ENGINEERING SERVICES 9/07/2004
The questions That Guided This Study
QUESTION 1: How effective is SEER as a predictor of expected annual cooling energy use? QUESTION 2: How effective is SEER in estimating cooling energy savings? QUESTION 3: How effective is SEER in estimating the relative seasonal cooling efficiency of different units, i.e., rank
ordering seasonal performance? QUESTION 4: How effective is SEER as a predictor of cooling peak demand and demand savings?
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 5 DESIGN & ENGINEERING SERVICES 9/07/2004
Background: Key Assumptions in the SEER Rating Methodology 1) Distribution of outdoor temperatures illustrated in Figure 2a (median value of approximately 76°F). 2) Building thermal characteristics yield a 65°F balance point for the building (Figure 2b). 3) All cooling coil load is a linear function of outdoor temperature only (Figure 2b). 4) Assumptions (1) through (3) results in load distribution illustrated in Figure 2c and a mid-load temperature of 82°F.
Figure 2: Key Assumptions Implicit in the SEER Rating Procedure Derivation of the 82°F “Mid-Load” Temperature a: Percent of Cooling Season at Each Temperature Range
21%23%
22%
16%
10%
5%
0.4%2%0%
5%
10%
15%
20%
25%
67 72 77 82 87 92 97 102Mid-Bin Temperature (F)
% o
f Tot
al C
oolin
g Se
ason
65 - 69 70 - 74 75 - 79 80 - 84 85 - 89 90 - 94 95 - 100 100 - 104
a: Percent of Cooling Season at Each Temperature Range Percent of Design Cooling at Each Temperature Range
21.2%
36.4%
51.5%
66.7%
81.8%
96.8%
6.0%
97.0%
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
67 72 77 82 87 92 97 102Mid-Bin Temperature (F)
% o
f Des
ign
Coo
ling
Load
b: Percent of Design Cooling at Each Temperature Range
65 - 69 70 - 74 75 - 79 80 - 84 85 - 89 90 - 94 95 - 100 100 - 104
Percent of Seasonal Cooling Load by Temperature Range
13.7%
22.0%23.3%
19.4%
11.9%
1.1%4.9%
3.6%
0%
5%
10%
15%
20%
25%
67 72 77 82 87 92 97 102Mid-Bin Temperature (F)
% o
f Ann
ual C
oolin
g Lo
ad
82
50% Load < 82°F 50% Load > 82°F
c: Percent of Annual Cooling Load by Temperature Range
65 - 69 70 - 74 75 - 79 80 - 84 85 - 89 90 - 94 95 - 100 100 - 104
Mid-Load Temperature = 82°F
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON DESIGN & ENGINEERING SERVICES
Background: Key Assumptions in the SEER Rating Methodology 5) The sensitivity of capacity and efficiency to outdoor temperature for individual HVAC units assumed to be linear with
outdoor temperature.
• Units with equal SEER but differing EER at other temperatures have equal annual cooling energy consumption.
• Hour-by-hour performance for DX units will vary with outdoor temperature: less efficient in warmer outdoor temperatures; more efficient in cooler temperatures.
Example: two units with equal SEER but differing sensitivity to outdoor temperature
• Unit with higher temperature sensitivity will be less efficient at hotter outdoor temperatures than the other unit.
• Temperature sensitivity is linear (Figure 3)
• This will balance out over an entire cooling season,
6) The assumption (5) involves two added ass ons: • Energy from both fans is a small and co portion of the total energy requirement. • Indoor and condenser fans are assumed le with the compressor
Figure 3 Unit Performance-Related Assumptions Implicit in the SEER Rating Procedure
Efficiency (EER) Sensitivity to Temperature
7
8
9
10
11
12
13
14
65 75 85 95 105Outdoor Temperature (F)
EER
High Tem peratureSens itivity
Ave Tem peratureSens itivity
Low Tem peratureSens itivity
82
umptinstantto cycPAGE 6 9/07/2004
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 7 DESIGN & ENGINEERING SERVICES 9/07/2004
Analysis Methodology: Understanding What Impacts SEER
Climate characteristics California climate cooling season median temperature is not 82°F.
• Initial analysis was run using five climate zones: Oakland, Long Beach, San Diego, Sacramento, and Palm Springs, to capture the typical range of California cooling climates.
• Final analysis was run using all sixteen climate zones.
Building characteristics Building thermal characteristics will help determine the mid-load temperature
• Zone balance point • Zone operating schedule • Linearity of the relationship between cooling coil load and outdoor temperature
Building types (characteristics determined from state-wide surveys) • Single-family Residential • Small office • Small Retail • Conventional School Classrooms • Portable School Classrooms
HVAC system characteristics Approximately 90 HVAC systems to reflect the range of currently available systems varying sensitivity to:
• Outdoor temperature • Cycling effects (i.e., CD) • Coil entering conditions
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 8 DESIGN & ENGINEERING SERVICES 9/07/2004
Analysis Methodology: Simulation Analysis Process Analysis Tool
• DOE-2.2 was used • Prior experience gives industry confidence DOE-2 is capable of predicating actual system performance.
All systems were simulated using manufacturers’ extended ratings data. Simulation Steps
• Average effect of climate on SEER o Median building and median HVAC characteristics in CTZ’s
• Effect of building characteristics on SEER o Min/median/max buildings with median HVAC system characteristics in CTZ’s. o Identify those combinations of building characteristics that yield min and max SEER. o Use these cases to characterize the impact of building on SEER.
• Effect of HVAC system characteristics on SEER o Median buildings with min/median/max HVAC system characteristics in all climate zones.
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 9 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings Regarding Key Assumptions of the SEER Rating Procedure 1) How similar are California climates to the U.S. average SEER climate? They are not.
Figure 4: Distribution of Cooling Season Outdoor Temperature California Climate Zones vs. SEER rating assumption
a: California climate zone 6 (mild) b: California climate zone 15 (hot arid)
0
10
20
30
40
50
60
67 72 77 82 87 92 97 102 107
Climate Zone 6
median = 70°F
0
10
20
30
40
50
60
67 72 77 82 87 92 97 102 107
Climate Zone 15
median = 82°F
c: Average for all California Climate zones d: Average for major California cities only
0
10
20
30
40
50
60
67 72 77 82 87 92 97 102 107
All California CZ's
median = 74°F
0
10
20
30
40
50
60
67 72 77 82 87 92 97 102 107
Major CA Cities Only
median = 71°F
San Diego area, Los Angeles area, bay area, Sacramento area
California Climate Zone SEER assumed
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 10 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings Regarding Key Assumptions of the SEER Rating Procedure 2) How valid is the SEER-assumed distribution of annual cooling coil loads for typical single-family homes in California climates? It is not valid.
Figure 5: Distribution of Cooling Coil Load by California Climate Zones DOE-2 cooling loads, Median Single Family Residence
a: California climate zone 6 (mild) b: California climate zone 15 (hot arid)
0%
5%
10%
15%
20%
25%
30%
35%
40%
45%
67 72 77 82 87 92 97 102 107
Climate Zone 696% < 82F< 4%72.7°F Mid-Load T
0%
5%
10%
15%
20%
25%
30%
35%
40%
45%
67 72 77 82 87 92 97 102 107
Climate Zone 1519% < 82F< 81%93.5°F Mid-Load T
c: Average for all California Climate zones d: Average for major California cities only
0%
5%
10%
15%
20%
25%
30%
35%
40%
45%
67 72 77 82 87 92 97 102 107
55% < 82F< 45%All California CZ's
80°F Mid-Load T
0%
5%
10%
15%
20%
25%
30%
35%
40%
45%
67 72 77 82 87 92 97 102 107
71% < 82F< 29%
Major CA Cities Only
75.8°F Mid-Load T
San Diego area, LA area, bay area, Sacramento area
California Climate Zone SEER assumed
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 11 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings Regarding Key Assumptions of the SEER Rating Procedure 3) Is the linear relationship between cooling load and outdoor temperature assumed by SEER rating process valid for typical (median) California single-family houses? It is not.
Figure 6: Cooling Coil Load as a Function of Outdoor Temperature (median single family residence, DOE-2 cooling loads, CZ09)
0
5
10
15
20
25
30
35
40
55 65 75 85 95 105
Coo
ling
Coi
l Loa
d (k
Btu
h) a: Simplified steady-state model cooling t-stat=78F + no effects due to: internal loads, wind, radiant losses from ext surfaces, slab losses, infiltration, envelope mass, surface solar absorbtance, interior mass, window solar gain, or natural ventilation
0
5
10
15
20
25
30
35
40
55 65 75 85 95 105
Outdoor Drybulb Temperature (F)
Coo
ling
Coi
l Loa
d (k
Btu
h)
b: all other effects omitted from (a) added
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 12 DESIGN & ENGINEERING SERVICES 9/07/2004
6
7
8
9
10
11
12
13
14
15
16
17
8 9 10 11 12 13 14 15 16Rated SEER
DOE-
2 Si
mul
ated
SEE
R
+15%
─30%
Findings That Address the Questions That Guided the Study QUESTION 1: How effective is SEER as a predictor of expected annual cooling energy use?
Not very effective, results in +15% to -30% accuracy.
Figure 7: Rated SEER as a Predictor of Annual Cooling Efficiency Single Family Residential Prototype, Representative California Climate Zones Min/Median/Max Building Characteristics, Min/Median/Max System Characteristics
What causes this variation?
Three areas of shortcomings were found:
• Climate effects • Building effects • System effects
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 13 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings That Address the Questions That Guided the Study How much of the total variation due to climate zone effects? Half to two thirds (from +10% to -20%)
Figure 8: Effect of Climate on Simulation-Estimated SEER Median Building Characteristics, Median System Characteristics
6
7
8
9
10
11
12
13
14
15
16
8 9 10 11 12 13 14 15 16Rated SEER
DO
E-2
Sim
ulat
ed S
EER
CZ03 CZ06 CZ07 CZ12 CZ15
+10%
─20%
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 14 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings That Address the Questions That Guided the Study Can this much variation be reduced using a simple correction factor for each climate zone?
Yes, from +10% and -20% to ±5%.
Figure 9: Climate Zone-Adjusted SEER as a Predictor of Annual Cooling Efficiency Median Building Characteristics, Median System Characteristics
8
9
10
11
12
13
14
15
16
8 9 10 11 12 13 14 15 16CZ-Adjusted SEER
DO
E-2
Sim
ulat
ed S
EER
CZ03 CZ06 CZ07
CZ12 CZ15
+5%
─5%
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 15 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings That Address the Questions That Guided the Study How much of the total variation is due to variation in building characteristics? About ±7%.
Figure 10: Effect of Building Characteristics on Simulation-Estimated SEER Single Family Residential Prototype, Climate Zones 6 (mild) and 15 (hot arid)
Min/Median/Max Building Characteristics, Median System Characteristics
6
7
8
9
10
11
12
13
14
15
16
8 9 10 11 12 13 14 15 16Rated SEER
DOE
-2 S
imul
ated
SE
ER
Min Bldg Med Bldg Max Bldg
CZ15
CZ06±7%
±7%
For a discussion of corrections for building effects, see the full report.
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 16 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings That Address the Questions That Guided the Study How much of the total variation is due to variation in HVAC system characteristics? Approximately ±5%
Figure 11: Effect of HVAC System Characteristics on Simulation-Estimated SEER Single Family Residential Prototype, Climate Zones 6 (mild) and 15 (hot arid)
Median Building Characteristics, All System Characteristics
6
7
8
9
10
11
12
13
14
15
16
17
8 9 10 11 12 13 14 15 16Rated SEER
DOE-
2 Si
mul
ated
SEE
R
CZ06
CZ15
±5%
±5%
For a discussion of corrections for system effects, see the full report.
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 17 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings That Address the Questions That Guided the Study QUESTION 2: How effective is SEER in estimating cooling energy savings? Not very effective.
Figure 12: Percentage Savings Achieved by SEER Upgrade (Upgrading from a Lower SEER System to a Higher SEER System) Single Family Residential Prototype, All California Climate Zones Min/Median/Max Buildings, Min/Median/Max Systems
29%
16%8%
26%
10%
20%
0%
5%
10%
15%
20%
25%
30%
35%
40%
2 pts 4 pts 5 pts 2 pts 3 pts 1 pt
% A
nnua
l Coo
ling
Ener
gy S
avin
gs
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
% H
VAC
Units
Ach
ievi
ng E
xpec
ted
Savi
ngs Expected Savings Median Savings % Units ≥ Expected
10 to 12 10 to 14 10 to 15 12 to 14 12 to 15 14 to 15
SEER Upgrade
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 18 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings That Address the Questions That Guided the Study QUESTION 3: How effective is SEER in estimating the relative seasonal cooling efficiency of different units, i.e., rank ordering seasonal performance? Not very effective unless at least a 2 to 3 point SEER rating increase is adopted, but then demand can be unfavorably effected.
Figure 13: Reliability of SEER* in Ranking the Relative Savings of HVAC Systems Single Family Residential Prototype, Climate Zones 6 (mild) and 15 (hot arid) Min/Median/Max Building Characteristics, Min/Median/Max System Characteristics
6
7
8
9
10
11
12
13
14
15
16
17
8 9 10 11 12 13 14 15 16Rated SEER*
DOE-
2 Si
mul
ated
SEE
R
Min Bldg Features
Med Bldg Features
Max Bldg Features
CZ06
CZ15
* rated SEER values in Figure 13 have been slightly juxtaposed to improve legibility. Actual rated SEER values are integer values.
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 19 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings That Address the Questions That Guided the Study QUESTION 4: How effective is SEER as a predictor of cooling peak demand and demand savings? Poor.
Figure 14: SEER and EER as Predictors of EER at HVAC Peak Demand Single Family Residential Prototype, All California Climate Zones Median Building Characteristics, Median System Characteristics
a: Rated SEER
7
8
9
10
11
12
13
14
15
16
8 9 10 11 12 13 14 15 16Rated SEER
EER
@ D
OE-
2 H
VAC
Pea
k D
eman
d
All CZ's CZ06 CZ15
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 20 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings That Address the Questions That Guided the Study Figure 14 (cont’d): SEER and EER as Predictors of EER at HVAC Peak Demand Single Family Residential Prototype, All
California Climate Zones Median Building Characteristics, Median System Characteristics
b: Rated EER (by climate zone) c: Rated EER (by SEER)
7
8
9
10
11
12
13
14
15
16
8 9 10 11 12 13 14 15 16Rated EER
EER
@ D
OE-
2 H
VAC
Pea
k D
eman
d
All CZ's CZ06 CZ15
7
8
9
10
11
12
13
14
15
16
8 9 10 11 12 13 14 15 16Rated EER
EER
@ D
OE-
2 H
VAC
Pea
k D
eman
d
SEER 10 SEER 12 SEER 14 SEER 15
d: Climate Zone Corrected SEER e: Climate Zone Corrected EER
7
8
9
10
11
12
13
14
15
16
8 9 10 11 12 13 14 15 16
Climate Zone Corrected SEER
EER
@ D
OE-
2 H
VAC
Pea
k D
eman
d
All CZ's CZ06 CZ06
7
8
9
10
11
12
13
14
15
16
8 9 10 11 12 13 14 15 16
Climate Zone Corrected EER
EER
@ D
OE-
2 H
VAC
Pea
k D
eman
d
All CZ's CZ06 CZ15
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 21 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings That Address the Questions That Guided the Study Figure 15: SEER and EER as Predictors of HVAC Peak Demand Single Family Residential Prototype, All California Climate
Zones Median Building Characteristics, Median System Characteristics
a: Rated SEER
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
8 9 10 11 12 13 14 15 16Rated SEER
DO
E-2
HVA
C P
eak
Dem
and
(kW
/ton)
All CZ's CZ06 CZ15
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 22 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings That Address the Questions That Guided the Study Figure 15 (cont’d): SEER and EER as Predictors of HVAC Peak Demand Single Family Residential Prototype, All California
Climate Zones Median Building Characteristics, Median System Characteristics
b: Rated EER (by climate zone) c: Rated EER (by SEER)
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
8 9 10 11 12 13 14 15 16Rated EER
DO
E-2
HVA
C P
eak
Dem
and
(kW
/ton)
All CZ's CZ06 CZ15
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
8 9 10 11 12 13 14 15 16Rated EER
DO
E-2
HVA
C P
eak
Dem
and
(kW
/ton)
SEER 10 SEER 12 SEER 14 SEER 15
d: Climate Zone Corrected SEER e: Climate Zone Corrected EER
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
8 9 10 11 12 13 14 15 16
Climate Zone Corrected SEER
DO
E-2
HVA
C P
eak
Dem
and
(kW
/ton)
All CZ's CZ06 CZ06
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
8 9 10 11 12 13 14 15 16
Climate Zone Corrected EER
DO
E-2
HVA
C P
eak
Dem
and
(kW
/ton)
All CZ's CZ06 CZ15
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 23 DESIGN & ENGINEERING SERVICES 9/07/2004
Findings That Address the Questions That Guided the Study QUESTION 1-4: What about non-residential applications?
QUESTION 1: How effective is SEER as a predictor of expected annual cooling energy consumption in non-residential applications? Not very Effective.
The analysis revealed VERY different findings for non-residential applications.
The most significant violation of SEER rating process assumptions in non-residential applications was related to the operation of the indoor fan:
• In non-residential applications, the indoor fan operated continuously during occupied hours, to provide code-mandated ventilation air.
Once indoor fan energy was excluded, the non-residential results more nearly resembled residential results, however, significant remaining differences included:
• Influence of ventilation air,
• The greater range in non-residential building balance point due to the potential for much greater solar gain and internal load, and
• Use of core versus perimeter zoning.
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 24 DESIGN & ENGINEERING SERVICES 9/07/2004
3
5
7
9
11
13
15
17
9 10 11 12 13 14
Condensing Unit SEER (Excludes Indoor Fan)Si
mul
ated
Con
dens
ing
Uni
t SEE
R CZ06 CZ15
3
5
7
9
11
13
15
17
9 10 11 12 13 14
Rated SEER (Includes Indoor Fan)
DO
E-2
Sim
ulat
ed S
EER
CZ06 CZ15
Findings That Address the Questions That Guided the Study Figure 16: Rated SEER as a Predictor of Annual Cooling Efficiency Small Office Prototype, Climate Zones 6 (mild) and 15 (hot
arid) Median Building Characteristics, All Zones, Min/Median/Max System Characteristics
a: Indoor Fan Energy Included b: Indoor Fan Energy Excluded
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 25 DESIGN & ENGINEERING SERVICES 9/07/2004
Summary of Findings • Neither SEER nor EER is a sufficiently reliable indicator of cooling energy performance (consumption or demand) for
California. In residential applications – savings fall short 75% to 90% of the time. Non-residential applications are more complex and require substantial additional Study, but indications are that a similar fraction will fall short.
• Three of the basic assumptions implicit in the SEER rating process were found not to hold true for California. Use of these rating methodologies in the California market will require correction factors for each of those assumptions. o Climate effects: the assumed climate variation is a poor match for California CTZ’s. o Building effects: the assumed load distribution is a poor match for California buildings. o System effects: the assumed equipment off-temperature and load performance is a poor match for actual
equipment on the market in California.
• For residential applications in California, climate effects account for the greatest inaccuracy of the SEER and EER ratings o Climate effects: correction factors were developed that were effective in reducing error in both SEER and EER.
• Significant sources of error in using SEER or EER in non-residential applications require additional investigation:
o Building effects: non-residential buildings tend to have much greater variation in internal load and solar load, greatly compromising the implicit relation SEER assumes between cooling load and outdoor temperature
o System effects: in non-residential buildings, code requires indoor fans to run continuously to provide needed ventilation during occupancy periods; thus, indoor fan energy becomes a significant portion of the total HVAC system energy but the SEER rating assumes the fan cycles with the condensing unit compressor and fan.
• In 2002, ARI decided to no longer include EER in its equipment performance listings of SEER-rated equipment. Having at least two ratings points, i.e., SEER and EER, is critical to the energy efficiency industry in California.
EER & SEER AS PREDICTORS OF SEASONAL ENERGY PERFORMANCE REPORT SUMMARY
SOUTHERN CALIFORNIA EDISON PAGE 26 DESIGN & ENGINEERING SERVICES 9/07/2004
Next Steps • Extend this work to include:
o Systems rated as SEER 13 (the minimum efficiency for the 2005 standards); o Include additional high efficiency two-speed systems (SEER 15 and 18 ratings); o Add HVAC equipment penetration rates and apply statistical methods to more accurately characterize the California
state-wide impacts of performance variability on expected savings and demand.
• Explore how the inherent performance variability of SEER-rated HVAC systems, as characterized by this Study, can be applied to: o Future development of the California energy efficiency standards to better ensure resultant savings; o Utility incentive programs to improve efficiency realization rates.
• In residential applications, additional Study is required to more effectively correct for: o Building effects, e.g., varying mid-load temperatures; o System effects, e.g., including off-rated coil entering conditions.
• In non-residential applications, additional Study is required to better understand and characterize: o Building effects due to
increased internal loads core/perimeter HVAC zoning occupancy ventilation
o System effects due to indoor fan energy and operation off-rated coil entering conditions