EE369 POWER SYSTEM ANALYSIS Lecture 2 Complex Power, Reactive Compensation, Three Phase Tom Overbye...
-
Upload
walter-dormer -
Category
Documents
-
view
249 -
download
9
Transcript of EE369 POWER SYSTEM ANALYSIS Lecture 2 Complex Power, Reactive Compensation, Three Phase Tom Overbye...
EE369POWER SYSTEM ANALYSIS
Lecture 2Complex Power, Reactive Compensation, Three Phase
Tom Overbye and Ross Baldick
1
Reading and Homework
Read Chapters 1 and 2 of the text.HW 1 is Problems 2.2, 2.3, 2.4, 2.5, 2.6, 2.8,
2.12, 2.14, 2.17, 2.19, 2.24, 2.25 and Case Study Questions A., B., C., D. from the text; due Thursday 9/5.
2
Review of PhasorsGoal of phasor analysis is to simplify the analysis of constant frequency ac systems:
v(t) = Vmax cos(t + v),i(t) = Imax cos(t + I),
where:•v(t) and i(t) are the instantaneous voltage and current as a function of time t,• is the angular frequency (2πf, with f the frequency in Hertz), • Vmax and Imax are the magnitudes of voltage and current sinusoids,•v and I are angular offsets of the peaks of sinusoids from a reference waveform.
Root Mean Square (RMS) voltage of sinusoid:
2 maxmax
0
1( ) , so 2 .
2
T VV v t dt V V
T
3
Phasor Representationj
( )
Euler's Identity: e cos sin ,
Phasor notation is developed by rewriting
using Euler's identity:
( ) 2 cos( ),
( ) 2 Re .
(Note: is the RMS voltage).
V
V
j t
j
v t V t
v t V e
V
4
Phasor Representation, cont’d
The RMS, cosine-referenced voltage phasor is:
,
( ) Re 2 ,
cos sin ,
cos sin .
V
V
jV
jj t
V V
I I
V V e V
v t V e e
V V j V
I I j I
(Note: Some texts use “boldface” type for complex numbers, or “bars on the top”.)
Also note that the convention in power engineering is that the magnitude of the phasor is the RMS voltage of the waveform:
contrasts with circuit analysis. 5
Advantages of Phasor Analysis
0
2 2
Resistor ( ) ( )
( )Inductor ( )
1 1Capacitor ( ) ( ) (0)
C
= Impedance ,
= Resistance,
= Reactance,
Z = , =arctan .
t
v t Ri t V RI
di tv t L V j LI
dt
v t i t dt v V Ij C
Z R jX Z
R
X
XR X
R
Device Time Analysis Phasor
(Note: Z is a complex number but
not a phasor).
6
RL Circuit Example
2 2 1
( ) 2 100cos( 30 ), so 100 30 ,
60Hz,
4 , 2 3 ,
4 3 5, tan (3/ 4) 36.9 ,
100 30,
5 36.920 6.9 Amps,
( ) 20 2 cos( 6.9 ).
v t t V
f
R X L fL
Z
VI
Z
i t t
7
Complex Power
max
max
max max
( ) ( ) ( ),
( ) = cos( ),
(t) = cos( ),
1cos cos [cos( ) cos( )],
21
( ) [cos( )2cos(2 )].
V
I
V I
V I
p t v t i t
v t V t
i I t
p t V I
t
Instantaneous Power :
8
Complex Power, cont’d
max max
0
max max
1( ) [cos( ) cos(2 )],
2
1( ) ,
1cos( ),
2cos( ),
= = .
V I V I
T
avg
V I
V I
V I
p t V I t
P p t dtT
V I
V I
Instantaneous Power is
Power F
sum
acto
of average
r Angl
and varying te
e
rms :
9
Complex Power, cont’d
max max
max max
max max
max max
1( ) [cos( ) cos(2 )],
21
[cos( ) cos(2 2 ( ))],21
[cos( ) cos(2 2 )cos( )]2
1sin(2 2 )
2
V I V I
V I V V I
V I V V I
V
p t V I t
V I t
V I t
V I t
Re - interpretation of instantaneous Power :
sin( ),
Second term is power into electric and magnetic fields.
V I
10
Complex Power
*
cos( ) sin( ) ,
,
= Real Power (W, kW, MW),
= Reactive Power (VAr, kVAr, MVAr),
= magnitude of power into electric and magnetic fields,
= Complex power (VA, kVA, MVA),
Power Factor
,
(pf
V I V IS V I j
P jQ
V
P
Q
I
S
) = cos ,
If current leads voltage then pf is leading,
If current lags voltage then pf is lagging.
(Note: S is a complex number but not a phasor.)
11
Complex Power, cont’d
2
1
Relationships between real, reactive, and complex power:
cos ,
sin 1 pf ,
Example: A load draws 100 kW with a leading pf of 0.85.What are (power factor angle), and ?
cos 0.85 31.8 ,
10
P S
Q S S
Q S
S
0kW117.6 kVA,
0.85117.6sin( 31.8 ) 62.0 kVAr.Q
12
Conservation of Power
At every node (bus) in the system:– Sum of real power into node must equal zero,– Sum of reactive power into node must equal zero.
This is a direct consequence of Kirchhoff’s current law, which states that the total current into each node must equal zero.– Conservation of real power and conservation of
reactive power follows since S = VI*.
13
Conservation of Power ExampleEarlier we foundI = 20-6.9 amps
*
* *
2
* *
2
100 30 20 6.9 2000 36.9 VA,
36.9 pf = 0.8 lagging,
( ) 4 20 6.9 20 6.9 ,
1600W ( 0),
( ) 3 20 6.9 20 6.9 ,
1200VA r , ( 0).
R R
R R
L L
L L
S V I
S V I RI I
P I R Q
S V I jXI I j
Q I X P
= 1600W + j1200VAr
Power flowing from source to load at bus
14
Power Consumption in Devices
2Resistor Resistor
2Inductor Inductor L
2Capacitor Capacitor C
Capaci
Resistors only consume real power:
,
Inductors only "consume" reactive power:
,
Capacitors only "generate" reactive power:
1.C
P I R
Q I X
Q I X XC
Q
2Capacitor
torC
(Note-some define negative.). CXV
X
15
Example
*
40000 0400 0 Amps
100 0
40000 0 (5 40) 400 0
42000 16000 44.9 20.8 kV
44.9k 20.8 400 0
17.98 20.8 MVA 16.8 6.4 MVA
VI
V j
j
S V I
j
First solvebasic circuitI
16
Example, cont’dNow add additionalreactive power loadand re-solve, assumingthat load voltage is maintained at 40 kV.
70.7 0.7 lagging
564 45 Amps
59.7 13.6 kV
33.7 58.6 MVA 17.6 28.8 MVA
LoadZ pf
I
V
S j
17
Need higher source voltage to maintain load voltage magnitude when reactive power load is added to circuit. Current is higher.
59.7 kV
17.6 MW
28.8 MVR
40.0 kV
16.0 MW
16.0 MVR
17.6 MW 16.0 MW-16.0 MVR 28.8 MVR
Power System NotationPower system components are usually shown as“one-line diagrams.” Previous circuit redrawn.
Arrows areused to show loads
Generators are shown as circles
Transmission lines are shown as a single line
18
Reactive Compensation
44.94 kV
16.8 MW
6.4 MVR
40.0 kV
16.0 MW
16.0 MVR
16.8 MW 16.0 MW 0.0 MVR 6.4 MVR
16.0 MVR
Key idea of reactive compensation is to supply reactivepower locally. In the previous example this canbe done by adding a 16 MVAr capacitor at the load.
Compensated circuit is identical to first example with just real power load. Supply voltage magnitude and line current is lower with compensation.
19
Reactive Compensation, cont’d Reactive compensation decreased the line flow
from 564 Amps to 400 Amps. This has advantages: – Lines losses, which are equal to I2 R, decrease,– Lower current allows use of smaller wires, or
alternatively, supply more load over the same wires,– Voltage drop on the line is less.
Reactive compensation is used extensively throughout transmission and distribution systems.
Capacitors can be used to “correct” a load’s power factor to an arbitrary value.
20
Power Factor Correction Example
1
1desired
new cap
cap
Assume we have 100 kVA load with pf=0.8 lagging,
and would like to correct the pf to 0.95 lagging
80 60 kVA cos 0.8 36.9
PF of 0.95 requires cos 0.95 18.2
80 (60 )
60 -ta
80
S j
S j Q
Q
cap
cap
n18.2 60 26.3 kVAr
33.7 kVAr
Q
Q
21
Distribution System Capacitors
22
Balanced 3 Phase () SystemsA balanced 3 phase () system has:
– three voltage sources with equal magnitude, but with an angle shift of 120,
– equal loads on each phase,– equal impedance on the lines connecting the
generators to the loads. Bulk power systems are almost exclusively 3.Single phase is used primarily only in low
voltage, low power settings, such as residential and some commercial.
Single phase transmission used for electric trains in Europe.
23
Balanced 3 -- Zero Neutral Current
* * * *
(1 0 1 1
3
Note: means voltage at point with respect to point .
n a b c
n
an a bn b cn c an a
xy
I I I I
VI
Z
S V I V I V I V I
V x y
24
Advantages of 3 Power
Can transmit more power for same amount of wire (twice as much as single phase).
Total torque produced by 3 machines is constant, so less vibration.
Three phase machines use less material for same power rating.
Three phase machines start more easily than single phase machines.
25
Three Phase - Wye ConnectionThere are two ways to connect 3 systems:
– Wye (Y), and– Delta ().
an
bn
cn
Wye Connection Voltages
V V
V V
V V
26
Wye Connection Line Voltages
Van
Vcn
Vbn
VabVca
Vbc
-Vbn
(1 1 120
3 30
3 90
3 150
ab an bn
bc
ca
V V V V
V
V V
V V
Line to linevoltages arealso balanced.
(α = 0 in this case)
27
Wye Connection, cont’dWe call the voltage across each element of a
wye connected device the “phase” voltage.We call the current through each element of a
wye connected device the “phase” current.Call the voltage across lines the “line-to-line” or
just the “line” voltage.Call the current through lines the “line” current.
6
*3
3 1 30 3
3
j
Line Phase Phase
Line Phase
Phase Phase
V V V e
I I
S V I
28
Delta Connection
IcaIc
IabIbc
Ia
Ib
*3
For Delta connection,
voltages across elements
equals line voltages
For currents
3
3
a ab ca
ab
b bc ab
c ca bc
Phase Phase
I I I
I
I I I
I I I
S V I
29
Three Phase Example
Assume a -connected load, with each leg Z = 10020 is supplied from a 3 13.8 kV (L-L) source
13.8 0 kV
13.8 0 kV
13.8 0 kV
ab
bc
ca
V
V
V
13.8 0 kV138 20 amps
138 140 amps 138 0 amps
ab
bc ca
I
I I
30
Three Phase Example, cont’d
*
138 20 138 0
239 50 amps
239 170 amps 239 0 amps
3 3 13.8 0 kV 138 amps
5.7 MVA
5.37 1.95 MVA
pf cos 20 lagging
a ab ca
b c
ab ab
I I I
I I
S V I
j
31
Delta-Wye Transformation
Y
Linephase
To simplify analysis of balanced 3 systems:
1) Δ-connected loads can be replaced by 1
Y-connected loads with 3
2) Δ-connected sources can be replaced by
Y-connected sources with 3 30
Z Z
VV
32
Delta-Wye Transformation Proof
For the
Suppose
side
the two sides have identical te
we get
rminal behavior
Hence
.
ab ca ab caa
ab ca
a
V V V VI
Z Z Z
V VZ
I
33
+
-
Delta-Wye Transformation, cont’dFor the side we get
( ) ( )
(2 )
Since 0
Hence 3
3
1Therefore
3
ab Y a b ca Y c a
ab ca Y a b c
a b c a b c
ab ca Y a
ab caY
a
Y
Y
V Z I I V Z I I
V V Z I I I
I I I I I I
V V Z I
V VZ Z
I
Z Z
34
Three Phase Transmission Line
35