EE2351POWER SYSTEM ANALYSIS
EE2351 A.Ahamed RiazudeenAP/EEE
1
A.Ahamed RiazudeenEEE DEPARTMENT
UNIT I
INTRODUCTION
EE2351 A.Ahamed RiazudeenAP/EEE
2
Power system network
EE2351 A.Ahamed RiazudeenAP/EEE
3
SINGLE LINE DIAGRAM
It is a diagrammatic representation of a power system inwhich the components are represented by their symbols.
EE2351 A.Ahamed RiazudeenAP/EEE
4
It is a diagrammatic representation of a power system inwhich the components are represented by their symbols.
COMPONENTS OF A POWER SYSTEM
1.Alternator2.Power transformer
3.Transmission lines
4.Substation transformer
5.Distribution transformer
6.Loads
EE2351 A.Ahamed RiazudeenAP/EEE
5
1.Alternator2.Power transformer
3.Transmission lines
4.Substation transformer
5.Distribution transformer
6.Loads
MODELLING OF GENERATOR ANDSYNCHRONOUS MOTOR
EE2351 A.Ahamed RiazudeenAP/EEE
6
1Φ equivalent circuit of generator 1Φ equivalent circuit of synchronous motor
MODELLING OF TRANSFORMER
EE2351 A.Ahamed RiazudeenAP/EEE
7
2 2 1
1 1 2
' 201 1 2 1 2
' 201 1 2 1 2
E N IK
E N I
RR R R R
KX
X X X XK
=Equivalent resistance referred to 1o
=Equivalent reactance referred to 1o
MODELLING OF TRANSMISSION LINE
EE2351 A.Ahamed RiazudeenAP/EEE
8
Π type T type
MODELLING OF INDUCTION MOTOR
EE2351 A.Ahamed RiazudeenAP/EEE
9
'
'
'
1( 1 )r
S r
S r
Rs
R R R
X X X
=Resistance representing load
=Equivalent resistance referred to stator
=Equivalent reactance referred to stator
per unit=actual value/base value
Let KVAb=Base KVA
kVb=Base voltage
Zb=Base impedance in Ω
EE2351 A.Ahamed RiazudeenAP/EEE
10
2 2
1000
b bb
bb
kV kVZ
KVAMVA
Changing the base of per unit quantities
Let z = actual impedance(Ω)= base impedance (Ω)bZ
. 2 2
* bp u
b b b
b
Z MVAZ ZZ
Z kV kV
MVA
EE2351 A.Ahamed RiazudeenAP/EEE
11
. 2 2
* bp u
b b b
b
Z MVAZ ZZ
Z kV kV
MVA
Let , ,
, ,
&
&b old b old
b new b new
kV MVB
kV MVB
represent old base values
represent new base values
,. , 2
,
. , ,
2
,
,. , 2
,
2
, ,. , . , 2
,,
*(1)
*(2)
*(3)
* *
b oldp u old
b old
p u old b old
b old
b newp u new
b new
b old b newp u new p u old
b oldb new
Z MVAZ
kV
Z MVAZ
kV
Z MVAZ
kV
kV MVAZ Z
MVAkV
EE2351 A.Ahamed RiazudeenAP/EEE
12
,. , 2
,
. , ,
2
,
,. , 2
,
2
, ,. , . , 2
,,
*(1)
*(2)
*(3)
* *
b oldp u old
b old
p u old b old
b old
b newp u new
b new
b old b newp u new p u old
b oldb new
Z MVAZ
kV
Z MVAZ
kV
Z MVAZ
kV
kV MVAZ Z
MVAkV
ADVANTAGES OF PER UNIT CALCULATIONS
The p.u impedance referred to either side of a 1Φtransformer is same
The manufacturers provide the impedance value in p.u The p.u impedance referred to either side of a 3Φ
transformer is same regardless of the 3Φ connections Y-Y,Δ-Y
p.u value always less than unity.
EE2351 A.Ahamed RiazudeenAP/EEE
13
The p.u impedance referred to either side of a 1Φtransformer is same
The manufacturers provide the impedance value in p.u The p.u impedance referred to either side of a 3Φ
transformer is same regardless of the 3Φ connections Y-Y,Δ-Y
p.u value always less than unity.
IMPEDANCE DIAGRAM
• This diagram obtained by replacing each component bytheir 1Φ equivalent circuit.
Following approximations are made to draw impedancediagram
1. The impedance b/w neutral and ground omitted.2. Shunt branches of the transformer equivalent circuit
neglected.
EE2351 A.Ahamed RiazudeenAP/EEE
14
• This diagram obtained by replacing each component bytheir 1Φ equivalent circuit.
Following approximations are made to draw impedancediagram
1. The impedance b/w neutral and ground omitted.2. Shunt branches of the transformer equivalent circuit
neglected.
REACTANCE DIAGRAM
It is the equivalent circuit of the power system in whichthe various components are represented by theirrespective equivalent circuit.
Reactance diagram can be obtained after omitting allresistances & capacitances of the transmission line fromimpedance diagram
EE2351 A.Ahamed RiazudeenAP/EEE
15
It is the equivalent circuit of the power system in whichthe various components are represented by theirrespective equivalent circuit.
Reactance diagram can be obtained after omitting allresistances & capacitances of the transmission line fromimpedance diagram
REACTANCE DIAGRAM FOR THE GIVEN POWER SYSTEMNETWORK
EE2351 A.Ahamed RiazudeenAP/EEE
16
PROCEDURE TO FORM REACTANCEDIAGRAM FROM SINGLE DIAGRAM
1.Select a base power kVAb or MVAb
2.Select a base voltage kVb
3. The voltage conversion is achieved by means of transformer kVb on LTsection= kVb on HT section x LT voltage rating/HT voltage rating
4. When specified reactance of a component is in ohmsp.u reactance=actual reactance/base reactancespecified reactance of a component is in p.u
EE2351 A.Ahamed RiazudeenAP/EEE
17
1.Select a base power kVAb or MVAb
2.Select a base voltage kVb
3. The voltage conversion is achieved by means of transformer kVb on LTsection= kVb on HT section x LT voltage rating/HT voltage rating
4. When specified reactance of a component is in ohmsp.u reactance=actual reactance/base reactancespecified reactance of a component is in p.u
2
, ,. , . , 2
,,
* *b old b newp u new p u old
b oldb new
kV MVAX X
MVAkV
p.u. calculation of 3 winding transformer
EE2351 A.Ahamed RiazudeenAP/EEE
18
Zp=Impedance of primary windingZs’=Impedance of secondary windingZt’=Impedance of tertiary windingShort circuit test conducted to find out the above 3impedances
'
' '
' '
1
21
21
2
p ps pt st
s ps st pt
t ps pt st
Z Z Z Z
Z Z Z Z
Z Z Z Z
EE2351 A.Ahamed RiazudeenAP/EEE
19
psZ
ptZ
= Leakage impedance measured in 1o with 2o short circuitedand tertiary open.
= Leakage impedance measured in 1o with tertiary shortcircuited and 2o open.
'stZ = Leakage impedance measured in 2o with tertiary short
circuited and 1o open and referred to primary
PRIMITIVE NETWORKIt is a set of unconnected elements which provides informationregarding the characteristics of individual elements. it can berepresented both in impedance & admittance form
EE2351 A.Ahamed RiazudeenAP/EEE
20
BUS ADMITTANCE(Y BUS) MATRIX
Y BUS can be formed by 2 methods
1.Inspection method
2.Singular transformation
11 12 1
21 22 2
1 2
n
n
n n nn
Y Y Y
Y Y Y
Y Y Y
EE2351 A.Ahamed RiazudeenAP/EEE
21
Y BUS =11 12 1
21 22 2
1 2
n
n
n n nn
Y Y Y
Y Y Y
Y Y Y
INSPECTION METHOD
For n bus systemDiagonal element of Y BUS
Off Diagonal element of Y BUS1
n
ii ijj
Y y
EE2351 A.Ahamed RiazudeenAP/EEE
22
For n bus systemDiagonal element of Y BUS
Off Diagonal element of Y BUS
ij ijY y
1
n
ii ijj
Y y
SINGULAR TRANSFORMATION METHOD
Y BUS =
Where [y]=primitive admittance
A=bus incidence matrix
TA y A
EE2351 A.Ahamed RiazudeenAP/EEE
23
ALGORITHM FOR FORMATION OF THEBUS IMPEDANCE MATRIX
• Modification of Zbus matrix involves any one of the following 4 cases
Case 1:adding a branch impedance zb from a new bus p tothe reference bus
Addition of new bus will increase the order the Zbus matrix by 1
(n+1)th column and row elements are zero except the diagonaldiagonal element is zb
EE2351 A.Ahamed RiazudeenAP/EEE
24
• Modification of Zbus matrix involves any one of the following 4 cases
Case 1:adding a branch impedance zb from a new bus p tothe reference bus
Addition of new bus will increase the order the Zbus matrix by 1
(n+1)th column and row elements are zero except the diagonaldiagonal element is zb
,
0
0original
bus newb
zZ
z
Case 2: adding a branch impedance zb from a new bus pto the existing bus qAddition of new bus will increase the order the Zbus matrix by 1The elements of (n+1)th column and row are the elements ofqth column and row and the diagonal element is Zqq+Zb
Case 3:adding a branch impedance zb from an existing bus p tothe reference bus
The elements of (n+1)th column and row are the elements ofqth column and row and the diagonal element is Zqq+Zb and(n+1)th row and column should be eliminated using the followingformula
EE2351 A.Ahamed RiazudeenAP/EEE
25
Case 2: adding a branch impedance zb from a new bus pto the existing bus qAddition of new bus will increase the order the Zbus matrix by 1The elements of (n+1)th column and row are the elements ofqth column and row and the diagonal element is Zqq+Zb
Case 3:adding a branch impedance zb from an existing bus p tothe reference bus
The elements of (n+1)th column and row are the elements ofqth column and row and the diagonal element is Zqq+Zb and(n+1)th row and column should be eliminated using the followingformula
( 1) ( 1),
( 1)( 1)
1,2... ; 1,2..j n n kjk act jk
n n
Z ZZ Z j n k n
Z
Case 4:adding a branch impedance zb between existing buses h and qelements of (n+1)th column are elements of bus h column –bus q column and elements of (n+1)th row are elements ofbus h row – bus q row the diagonal element=and (n+1)th row and column should be eliminated using the followingformula
2b hh qq hqZ Z Z Z
EE2351 A.Ahamed RiazudeenAP/EEE
26
Case 4:adding a branch impedance zb between existing buses h and qelements of (n+1)th column are elements of bus h column –bus q column and elements of (n+1)th row are elements ofbus h row – bus q row the diagonal element=and (n+1)th row and column should be eliminated using the followingformula
( 1) ( 1),
( 1)( 1)
1,2... ; 1,2..j n n kjk act jk
n n
Z ZZ Z j n k n
Z
UNIT II
POWER FLOW ANALYSIS
EE2351 A.Ahamed RiazudeenAP/EEE
27
BUS CLASSIFICATION
1.Slack bus or Reference bus or Swing bus:|V| and δ are specified. P and Q are un specified, and to becalculated.
2.Generator bus or PV bus or Voltage controlled bus:P and |V| are specified. Q and δ are un specified, and to becalculated
3.Load bus or PQ bus:P and Q are specified. |V| and δ are un specified, and to becalculated
EE2351 A.Ahamed RiazudeenAP/EEE
28
1.Slack bus or Reference bus or Swing bus:|V| and δ are specified. P and Q are un specified, and to becalculated.
2.Generator bus or PV bus or Voltage controlled bus:P and |V| are specified. Q and δ are un specified, and to becalculated
3.Load bus or PQ bus:P and Q are specified. |V| and δ are un specified, and to becalculated
ITERATIVE METHOD
The above Load flow equations are non linear andcan be solved by following iterative methods.
1.Gauss seidal method2.Newton Raphson method3.Fast Decoupled method
1
*
*1
n
p pq qq
p p p P p
np p
pq qqP
I Y V
S P jQ V I
P jQY V
V
EE2351 A.Ahamed RiazudeenAP/EEE
29
The above Load flow equations are non linear andcan be solved by following iterative methods.
1.Gauss seidal method2.Newton Raphson method3.Fast Decoupled method
1
*
*1
n
p pq qq
p p p P p
np p
pq qqP
I Y V
S P jQ V I
P jQY V
V
GAUSS SEIDAL METHOD
For load bus calculate |V| and δ from Vpk+1 equation
11 1
*1 1
1
( )
p np pk k k
p pq q pq qkq q ppp P
P jQV Y V Y V
Y V
EE2351 A.Ahamed RiazudeenAP/EEE
30
For generator bus calculate Q from QPK+1 equation
11 * 1
1
1*Im ( )p n
k k k kp P pq q pq q
q q p
Q V Y V Y V
11 1
*1 1
1
( )
p np pk k k
p pq q pq qkq q ppp P
P jQV Y V Y V
Y V
• Check Qp,calk+1 with the limits of Qp
• If Qp,calk+1 lies within the limits bus p remains as PV bus
otherwise it will change to load bus• Calculate δ for PV bus from Vp
k+1 equation• Acceleration factor α can be used for faster convergence
• Calculate change in bus-p voltage
• If |ΔVmax |< ε, find slack bus power otherwise increasethe iteration count (k)
• Slack bus power=
EE2351 A.Ahamed RiazudeenAP/EEE
31
• Check Qp,calk+1 with the limits of Qp
• If Qp,calk+1 lies within the limits bus p remains as PV bus
otherwise it will change to load bus• Calculate δ for PV bus from Vp
k+1 equation• Acceleration factor α can be used for faster convergence
• Calculate change in bus-p voltage
• If |ΔVmax |< ε, find slack bus power otherwise increasethe iteration count (k)
• Slack bus power=
1 1k k kp p pV V V
G LS S
NEWTON RAPHSON METHOD
1
1
1
1 2
3 4
co s( )
s in ( )
n
i i i j ij ij i jj
n
i i j ij ij i jj
n
i i j ij ij i jj
k sch ki i i
k sch ki i i
P Q V V Y
P V V Y
Q V V Y
J JP
J J VQ
P P P
Q Q Q
EE2351 A.Ahamed RiazudeenAP/EEE
32
1
1
1
1 2
3 4
co s( )
s in ( )
n
i i i j ij ij i jj
n
i i j ij ij i jj
n
i i j ij ij i jj
k sch ki i i
k sch ki i i
P Q V V Y
P V V Y
Q V V Y
J JP
J J VQ
P P P
Q Q Q
• Calculate |V| and δ from the following equation
• If
• stop the iteration otherwise increase the iteration count (k)
1
1
k k ki i
k k ki i iV V V
ki
ki
P
Q
EE2351 A.Ahamed RiazudeenAP/EEE
33
• Calculate |V| and δ from the following equation
• If
• stop the iteration otherwise increase the iteration count (k)
ki
ki
P
Q
FAST DECOUPLED METHOD J2 & J3 of Jacobian matrix are zero
1
4
1
4
'
''
1'
1''
0
0
i
i
JP
VJQ
PP J
QQ J V V
V
PB
V
QB V
V
PB
V
QV B
V
EE2351 A.Ahamed RiazudeenAP/EEE
34
1
4
1
4
'
''
1'
1''
0
0
i
i
JP
VJQ
PP J
QQ J V V
V
PB
V
QB V
V
PB
V
QV B
V
1
1
k k ki i
k k ki i iV V V
This method requires more iterations than NR
method but less time per iteration
It is useful for in contingency analysis
EE2351 A.Ahamed RiazudeenAP/EEE
35
This method requires more iterations than NR
method but less time per iteration
It is useful for in contingency analysis
COMPARISION BETWEEN ITERATIVEMETHODS
Gauss – Seidal Method1. Computer memory requirement is less.2. Computation time per iteration is less.3. It requires less number of arithmetic operations to
complete an iteration and ease in programming.4. No. of iterations are more for convergence and rate of
convergence is slow (linear convergencecharacteristic.
5. No. of iterations increases with the increase of no. ofbuses.
EE2351 A.Ahamed RiazudeenAP/EEE
36
Gauss – Seidal Method1. Computer memory requirement is less.2. Computation time per iteration is less.3. It requires less number of arithmetic operations to
complete an iteration and ease in programming.4. No. of iterations are more for convergence and rate of
convergence is slow (linear convergencecharacteristic.
5. No. of iterations increases with the increase of no. ofbuses.
NEWTON – RAPHSON METHOD
Superior convergence because of quadratic convergence. It has an 1:8 iteration ratio compared to GS method. More accurate. Smaller no. of iterations and used for large size systems. It is faster and no. of iterations is independent of the no. of buses. Technique is difficult and calculations involved in each iteration are
more and thus computation time per iteration is large. Computer memory requirement is large, as the elements of jacobian
matrix are to be computed in each iteration. Programming logic is more complex.
EE2351 A.Ahamed RiazudeenAP/EEE
37
Superior convergence because of quadratic convergence. It has an 1:8 iteration ratio compared to GS method. More accurate. Smaller no. of iterations and used for large size systems. It is faster and no. of iterations is independent of the no. of buses. Technique is difficult and calculations involved in each iteration are
more and thus computation time per iteration is large. Computer memory requirement is large, as the elements of jacobian
matrix are to be computed in each iteration. Programming logic is more complex.
FAST DECOUPLED METHOD
It is simple and computationally efficient. Storage of jacobian matrix elements are60% of NR
method computation time per iteration is less. Convergence is geometric,2 to 5 iterations required for
accurate solutions Speed for iterations is 5 times that of NR method and 2-3
times of GS method
EE2351 A.Ahamed RiazudeenAP/EEE
38
It is simple and computationally efficient. Storage of jacobian matrix elements are60% of NR
method computation time per iteration is less. Convergence is geometric,2 to 5 iterations required for
accurate solutions Speed for iterations is 5 times that of NR method and 2-3
times of GS method
UNIT III
FAULT ANALYSIS-BALANCED FAULT
EE2351 A.Ahamed RiazudeenAP/EEE
39
Need for fault analysis To determine the magnitude of fault current throughout
the power system after fault occurs. To select the ratings for fuses, breakers and switchgear. To check the MVA ratings of the existing circuit breakers
when new generators are added into a system.
EE2351 A.Ahamed RiazudeenAP/EEE
40
Need for fault analysis To determine the magnitude of fault current throughout
the power system after fault occurs. To select the ratings for fuses, breakers and switchgear. To check the MVA ratings of the existing circuit breakers
when new generators are added into a system.
BALANCED THREE PHASE FAULT
All the three phases are short circuited to each other and to earth. Voltages and currents of the system balanced after the symmetrical fault
occurred. It is enough to consider any one phase for analysis.
SHORT CIRCUIT CAPACITY
It is the product of magnitudes of the prefault voltageand the post fault current.
It is used to determine the dimension of a bus bar and theinterrupting capacity of a circuit breaker.
EE2351 A.Ahamed RiazudeenAP/EEE
41
BALANCED THREE PHASE FAULT
All the three phases are short circuited to each other and to earth. Voltages and currents of the system balanced after the symmetrical fault
occurred. It is enough to consider any one phase for analysis.
SHORT CIRCUIT CAPACITY
It is the product of magnitudes of the prefault voltageand the post fault current.
It is used to determine the dimension of a bus bar and theinterrupting capacity of a circuit breaker.
Short Circuit Capacity (SCC)0
2
,1
1.
,3
3.
6
3
6,
/
*10
3 * *10
F
TF
T
bT
T T p u
b
T p u
f
L b
SCC V I
VI
Z
SVSCC MVA
Z Z
SSCC MVA
Z
SCCI
V
EE2351 A.Ahamed RiazudeenAP/EEE
42
0
2
,1
1.
,3
3.
6
3
6,
/
*10
3 * *10
F
TF
T
bT
T T p u
b
T p u
f
L b
SCC V I
VI
Z
SVSCC MVA
Z Z
SSCC MVA
Z
SCCI
V
Procedure for calculating short circuit capacityand fault current
Draw a single line diagram and select common base SbMVA and kV
Draw the reactance diagram and calculate the total p.uimpedance from the fault point to source (Theveninimpedance ZT)
Determine SCC and If
EE2351 A.Ahamed RiazudeenAP/EEE
43
Draw a single line diagram and select common base SbMVA and kV
Draw the reactance diagram and calculate the total p.uimpedance from the fault point to source (Theveninimpedance ZT)
Determine SCC and If
ALGORITHM FOR SHORT CIRCUIT ANALYSISUSING BUS IMPEDANCE MATRIX
• Consider a n bus network. Assume that three phase faultis applied at bus k through a fault impedance zf
• Prefault voltages at all the buses are
• Draw the Thevenin equivalent circuit i.e Zeroing all voltage sourcesand add voltage source at faulted bus k and draw the reactancediagram
1
2
(0)
(0)
.(0)
(0)
.
(0)
busk
n
V
V
VV
V
EE2351 A.Ahamed RiazudeenAP/EEE
44
• Consider a n bus network. Assume that three phase faultis applied at bus k through a fault impedance zf
• Prefault voltages at all the buses are
• Draw the Thevenin equivalent circuit i.e Zeroing all voltage sourcesand add voltage source at faulted bus k and draw the reactancediagram
1
2
(0)
(0)
.(0)
(0)
.
(0)
busk
n
V
V
VV
V
(0)kV
• The change in bus voltage due to fault is
• The bus voltages during the fault is
• The current entering into all the buses is zero.the current enteringinto faulted bus k is –ve of the current leaving the bus k
1
.
.
.
busk
n
V
VV
V
( ) (0)bus bus busV F V V
EE2351 A.Ahamed RiazudeenAP/EEE
45
• The change in bus voltage due to fault is
• The bus voltages during the fault is
• The current entering into all the buses is zero.the current enteringinto faulted bus k is –ve of the current leaving the bus k
( ) (0)bus bus busV F V V
11 1 1
1
1
. . 0
. . . . . .
. . ( )
. . . . . .
. . 0
( ) (0) ( )
( ) ( )
(0)( )
( ) (0) ( )
bus bus bus
k n
bus k kk kn k
n nk nn
k k kk k
k f k
kk
kk f
i i ik k
V Z I
Z Z Z
V Z Z Z I F
Z Z Z
V F V Z I F
V F Z I F
VI F
Z Z
V F V Z I F
EE2351 A.Ahamed RiazudeenAP/EEE
46
11 1 1
1
1
. . 0
. . . . . .
. . ( )
. . . . . .
. . 0
( ) (0) ( )
( ) ( )
(0)( )
( ) (0) ( )
bus bus bus
k n
bus k kk kn k
n nk nn
k k kk k
k f k
kk
kk f
i i ik k
V Z I
Z Z Z
V Z Z Z I F
Z Z Z
V F V Z I F
V F Z I F
VI F
Z Z
V F V Z I F
UNIT IV
FAULT ANALYSIS – UNBALANCEDFAULTS
EE2351 A.Ahamed RiazudeenAP/EEE
47
FAULT ANALYSIS – UNBALANCEDFAULTS
INTRODUCTION
UNSYMMETRICAL FAULTSo One or two phases are involvedo Voltages and currents become unbalanced and each phase is to be
treated individuallyo The various types of faults are
Shunt type faults1.Line to Ground fault (LG)2. Line to Line fault (LL)3. Line to Line to Ground fault (LLG)
Series type faultsOpen conductor fault (one or two conductor open fault)
EE2351 A.Ahamed RiazudeenAP/EEE
48
UNSYMMETRICAL FAULTSo One or two phases are involvedo Voltages and currents become unbalanced and each phase is to be
treated individuallyo The various types of faults are
Shunt type faults1.Line to Ground fault (LG)2. Line to Line fault (LL)3. Line to Line to Ground fault (LLG)
Series type faultsOpen conductor fault (one or two conductor open fault)
FUNDAMENTALS OF SYMMETRICALCOMPONENTS
Symmetrical components can be used to transformthree phase unbalanced voltages and currents tobalanced voltages and currents
Three phase unbalanced phasors can be resolved intofollowing three sequences1.Positive sequence components2. Negative sequence components3. Zero sequence components
EE2351 A.Ahamed RiazudeenAP/EEE
49
Symmetrical components can be used to transformthree phase unbalanced voltages and currents tobalanced voltages and currents
Three phase unbalanced phasors can be resolved intofollowing three sequences1.Positive sequence components2. Negative sequence components3. Zero sequence components
Positive sequence componentsThree phasors with equal magnitudes, equally displaced from oneanother by 120o and phase sequence is same as that of originalphasors.
Negative sequence componentsThree phasors with equal magnitudes, equally displaced from oneanother by 120o and phase sequence is opposite to that of originalphasors.
Zero sequence componentsThree phasors with equal magnitudes and displaced from one anotherby 0o
1 1 1, ,a b cV V V
2 2 2, ,a b cV V V
EE2351 A.Ahamed RiazudeenAP/EEE
50
Positive sequence componentsThree phasors with equal magnitudes, equally displaced from oneanother by 120o and phase sequence is same as that of originalphasors.
Negative sequence componentsThree phasors with equal magnitudes, equally displaced from oneanother by 120o and phase sequence is opposite to that of originalphasors.
Zero sequence componentsThree phasors with equal magnitudes and displaced from one anotherby 0o
2 2 2, ,a b cV V V
0 0 0, ,a b cV V V
RELATIONSHIP BETWEEN UNBALANCED VECTORSAND SYMMETRICAL COMPONENTS
0 1 2
0 1 2
0 1 2
0
21
22
2
2
1 1 1
1
1
1 1 1
1
1
a a a a
b b b b
c c c c
a a
b a
c a
V V V V
V V V V
V V V V
V V
V a a V
a aV V
A a a
a a
EE2351 A.Ahamed RiazudeenAP/EEE
51
0 1 2
0 1 2
0 1 2
0
21
22
2
2
1 1 1
1
1
1 1 1
1
1
a a a a
b b b b
c c c c
a a
b a
c a
V V V V
V V V V
V V V V
V V
V a a V
a aV V
A a a
a a
Similarly we can obtain for currents also
SEQUENCE IMPEDANCE
Impedances offered by power system components to positive,negative and zero sequence currents.
Positive sequence impedanceThe impedance of a component when positive sequencecurrents alone are flowing.
Negative sequence impedanceThe impedance of a component when negative sequencecurrents alone are flowing.
Zero sequence impedanceThe impedance of a component when zero sequence currentsalone are flowing.
EE2351 A.Ahamed RiazudeenAP/EEE
52
Impedances offered by power system components to positive,negative and zero sequence currents.
Positive sequence impedanceThe impedance of a component when positive sequencecurrents alone are flowing.
Negative sequence impedanceThe impedance of a component when negative sequencecurrents alone are flowing.
Zero sequence impedanceThe impedance of a component when zero sequence currentsalone are flowing.
SEQUENCE NETWORK
SEQUENCE NETWORK FOR GENERATOR
EE2351 A.Ahamed RiazudeenAP/EEE
53
positive sequence network negative sequence network Zero sequence network
SEQUENCE NETWORK FORTRANSMISSION LINE
EE2351 A.Ahamed RiazudeenAP/EEE
54
positive sequence network negative sequence network Zero sequence network
SEQUENCE NETWORK FORTRANSFORMER
EE2351 A.Ahamed RiazudeenAP/EEE
55
positive sequence network negative sequence network Zero sequence network
SEQUENCE NETWORK FOR LOAD
EE2351 A.Ahamed RiazudeenAP/EEE
56
positive sequence network negative sequence network Zero sequence network
SINGLE LINE TO GROUND FAULT
b
c
fa a
a1 a2 a0 a
a11 2 0
I 0
I 0
V Z I
I I I I /3
I3
af
E
Z Z Z Z
EE2351 A.Ahamed RiazudeenAP/EEE
57
b
c
fa a
a1 a2 a0 a
a11 2 0
I 0
I 0
V Z I
I I I I /3
I3
af
E
Z Z Z Z
Consider a fault between phase a and
ground through an impedance zf
LINE TO LINE (LL) FAULT
a2 a1
a0
fa1 a2 a1
a11 2
1 2
I 0
I I
V V I
I I
I 0
V V Z I
I3
I I3
a
c b
fb c b
af
ab c f
Z
E
Z Z Z
jE
Z Z Z
EE2351 A.Ahamed RiazudeenAP/EEE
58
a2 a1
a0
fa1 a2 a1
a11 2
1 2
I 0
I I
V V I
I I
I 0
V V Z I
I3
I I3
a
c b
fb c b
af
ab c f
Z
E
Z Z Z
jE
Z Z Z
Consider a fault between phase b and cthrough an impedance zf
DOUBLE LINE TO GROUND (LLG) FAULT
a0
a1 a2 a0
fa0
fa0 a1 a0
a11 2 0 2 0
I 0
I I I 0
V=V (I I ) 3Z I
V V V 3Z I
I( 3 )/( 3 )
fb c b c
b
af f
Z
E
Z Z Z Z Z Z Z
EE2351 A.Ahamed RiazudeenAP/EEE
59
a0
a1 a2 a0
fa0
fa0 a1 a0
a11 2 0 2 0
I 0
I I I 0
V=V (I I ) 3Z I
V V V 3Z I
I( 3 )/( 3 )
fb c b c
b
af f
Z
E
Z Z Z Z Z Z Z
Consider a fault between phase b and cthrough an impedance zf to ground
UNBALANCED FAULT ANALYSIS USINGBUS IMPEDANCE MATRIX
SINGLE LINE TO GROUND FAULT USING Zbus
Consider a fault between phase a and ground throughan impedance zf at bus k
For a fault at bus k the symmetricalcomponents of fault current
EE2351 A.Ahamed RiazudeenAP/EEE
60
For a fault at bus k the symmetricalcomponents of fault current
0 1 21 2 0
V (0)I I I
3k
k k k fkk kk kkZ Z Z Z
LINE TO LINE (LL) FAULT
Consider a fault between phase b and c through an impedance zf
0
1 21 2
I 0
V (0)I I
k
kk k f
kk kkZ Z Z
EE2351 A.Ahamed RiazudeenAP/EEE
61
0
1 21 2
I 0
V (0)I I
k
kk k f
kk kkZ Z Z
DOUBLE LINE TO GROUND (LLG) FAULT
Consider a fault between phase b and c through an impedance zf to ground
12 0
12 0
1 12
2
1 10
0
V (0)I
( 3 )3
V (0) II
V (0) II
3
I ( ) I I
kk f
kk kkkk f
kk kk
k kk kk
kk
k kk kk f
kk
b ck k k
Z Z ZZ
Z Z Z
Z
Z
Z
Z Z
F
EE2351 A.Ahamed RiazudeenAP/EEE
62
12 0
12 0
1 12
2
1 10
0
V (0)I
( 3 )3
V (0) II
V (0) II
3
I ( ) I I
kk f
kk kkkk f
kk kk
k kk kk
kk
k kk kk f
kk
b ck k k
Z Z ZZ
Z Z Z
Z
Z
Z
Z Z
F
BUS VOLTAGES AND LINE CURRENTSDURING FAULT
0 0 0
1 0 1 1
2 2 2
0 00
0
1 11
1
2 22
2
( ) 0 I
( ) (0) I
( ) 0 I
( ) ( )I
( ) ( )I
( ) ( )I
i ik k
i i ik k
i ik k
i jij
ij
i jij
ij
i jij
ij
V F Z
V F V Z
V F Z
V F V F
Z
V F V F
Z
V F V F
Z
EE2351 A.Ahamed RiazudeenAP/EEE
63
0 0 0
1 0 1 1
2 2 2
0 00
0
1 11
1
2 22
2
( ) 0 I
( ) (0) I
( ) 0 I
( ) ( )I
( ) ( )I
( ) ( )I
i ik k
i i ik k
i ik k
i jij
ij
i jij
ij
i jij
ij
V F Z
V F V Z
V F Z
V F V F
Z
V F V F
Z
V F V F
Z
UNIT V
STABILITY ANALYSIS
EE2351 A.Ahamed RiazudeenAP/EEE
64
UNIT V
STABILITY ANALYSIS
STABILITY The tendency of a power system to develop restoring
forces equal to or greater than the disturbing forces tomaintain the state of equilibrium.
Ability to keep the machines in synchronism with anothermachine
EE2351 A.Ahamed RiazudeenAP/EEE
65
STABILITY The tendency of a power system to develop restoring
forces equal to or greater than the disturbing forces tomaintain the state of equilibrium.
Ability to keep the machines in synchronism with anothermachine
CLASSIFICATION OF STABILITY
Steady state stabilityAbility of the power system to regain synchronism after small and
slow disturbances (like gradual power changes)
Dynamic stabilityAbility of the power system to regain synchronism after smalldisturbances occurring for a long time (like changes in turbinespeed, change in load)
Transient stabilityThis concern with sudden and large changes in the networkconditions i.e. . sudden changes in application or removal of loads,line switching operating operations, line faults, or loss of excitation.
EE2351 A.Ahamed RiazudeenAP/EEE
66
Steady state stabilityAbility of the power system to regain synchronism after small and
slow disturbances (like gradual power changes)
Dynamic stabilityAbility of the power system to regain synchronism after smalldisturbances occurring for a long time (like changes in turbinespeed, change in load)
Transient stabilityThis concern with sudden and large changes in the networkconditions i.e. . sudden changes in application or removal of loads,line switching operating operations, line faults, or loss of excitation.
Steady state limit is the maximum power that can betransferred without the system become unstable whenthe load in increased gradually under steady stateconditions.
Transient limit is the maximum power that can betransferred without the system becoming unstable whena sudden or large disturbance occurs.
EE2351 A.Ahamed RiazudeenAP/EEE
67
Steady state limit is the maximum power that can betransferred without the system become unstable whenthe load in increased gradually under steady stateconditions.
Transient limit is the maximum power that can betransferred without the system becoming unstable whena sudden or large disturbance occurs.
Swing Equation for Single Machine InfiniteBus System
• The equation governing the motion of the rotor of asynchronous machine
whereJ=The total moment of inertia of the rotor(kg-m2)
=Singular displacement of the rotorTm=Mechanical torque (N-m)Te=Net electrical torque (N-m)Ta=Net accelerating torque (N-m)
2
2m
a m e
dJ T T T
dt
EE2351 A.Ahamed RiazudeenAP/EEE
68
• The equation governing the motion of the rotor of asynchronous machine
whereJ=The total moment of inertia of the rotor(kg-m2)
=Singular displacement of the rotorTm=Mechanical torque (N-m)Te=Net electrical torque (N-m)Ta=Net accelerating torque (N-m)
m
• Where pm is the shaft power input to the machinepe is the electrical powerpa is the accelerating power
2 2
2 2
2
2
m sm m
m msm
m m
mm a m e
t
d d
dt dt
d d
dt dt
dJ p p p
dt
EE2351 A.Ahamed RiazudeenAP/EEE
69
• Where pm is the shaft power input to the machinepe is the electrical powerpa is the accelerating power
2 2
2 2
2
2
m sm m
m msm
m m
mm a m e
t
d d
dt dt
d d
dt dt
dJ p p p
dt
2
2
2
2
2
2
2
20
20 0
2 max2
20
2
2
2
2
2
sin
m
ma m e
machinesm
m a m e
sm machine machine
a m es
s
a m e
m a
a
J M
dM p p p
dtH
M S
d p p pH
dt S S
H dp p p
dt
f
H dp p p
f dt
f fdp p p
dt H Hd
dt
fd dp
dt H dt
H=machine inertia constant
EE2351 A.Ahamed RiazudeenAP/EEE
70
2
2
2
2
2
2
2
20
20 0
2 max2
20
2
2
2
2
2
sin
m
ma m e
machinesm
m a m e
sm machine machine
a m es
s
a m e
m a
a
J M
dM p p p
dtH
M S
d p p pH
dt S S
H dp p p
dt
f
H dp p p
f dt
f fdp p p
dt H Hd
dt
fd dp
dt H dt
δ and ωs are in electricalradian
p.u
p.u
Swing Equation for Multimachine System
2
2
systema m e
machinesystem machine
system
H dp p p
f dt
SH H
S
p.u
m a ch in eS =machine rating(base)
systemS =system base
EE2351 A.Ahamed RiazudeenAP/EEE
71
2
2
systema m e
machinesystem machine
system
H dp p p
f dt
SH H
S
p.u
Rotor Angle Stability
• It is the ability of interconnected synchronous machinesof a power system to maintain in synchronism. Thestability problem involves the study of the electromechanical oscillations inherent in power system.
• Types of Rotor Angle Stability1. Small Signal Stability (or) Steady State Stability2. Transient stability
EE2351 A.Ahamed RiazudeenAP/EEE
72
• It is the ability of interconnected synchronous machinesof a power system to maintain in synchronism. Thestability problem involves the study of the electromechanical oscillations inherent in power system.
• Types of Rotor Angle Stability1. Small Signal Stability (or) Steady State Stability2. Transient stability
Voltage Stability
It is the ability of a power system to maintain steadyacceptable voltages at all buses in the system undernormal operating conditions and after being subjected toa disturbance.
The major factor for instability is the inability of thepower system to meet the demand for reactive power.
EE2351 A.Ahamed RiazudeenAP/EEE
73
It is the ability of a power system to maintain steadyacceptable voltages at all buses in the system undernormal operating conditions and after being subjected toa disturbance.
The major factor for instability is the inability of thepower system to meet the demand for reactive power.
• Mid Term StabilityIt represents transition between short term and longterm responses.Typical ranges of time periods.1. Short term : 0 to 10s2. Mid Term : 10 to few minutes
3. Long Term : a few minutes to 10’s of minutes• Long Term Stability
Usually these problem be associated with1. Inadequacies in equipment responses.2. Poor co-ordination of control and protection equipment.3. Insufficient active/reactive power reserves.
EE2351 A.Ahamed RiazudeenAP/EEE
74
• Mid Term StabilityIt represents transition between short term and longterm responses.Typical ranges of time periods.1. Short term : 0 to 10s2. Mid Term : 10 to few minutes
3. Long Term : a few minutes to 10’s of minutes• Long Term Stability
Usually these problem be associated with1. Inadequacies in equipment responses.2. Poor co-ordination of control and protection equipment.3. Insufficient active/reactive power reserves.
Equal Area Criterion
• This is a simple graphical method to predict the transientstability of two machine system or a single machineagainst infinite bus. This criterion does not require swingequation or solution of swing equation to determine thestability condition.
• The stability conditions are determined by equating theareas of segments on power angle diagram.
EE2351 A.Ahamed RiazudeenAP/EEE
75
• This is a simple graphical method to predict the transientstability of two machine system or a single machineagainst infinite bus. This criterion does not require swingequation or solution of swing equation to determine thestability condition.
• The stability conditions are determined by equating theareas of segments on power angle diagram.
Power-angle curve for equal area criterion
EE2351 A.Ahamed RiazudeenAP/EEE
76
Power-angle curve for equal area criterion
multiplying swing equation by on both sides
Multiplying both sides of the above equation by dt and then integrating between two arbitrary angles δ0 and δc
Once a fault occurs, the machine starts accelerating. Once the fault is cleared, themachine keeps on accelerating before it reaches its peak at δc ,
The area of accelerating A1
EE2351 A.Ahamed RiazudeenAP/EEE
77
The area of deceleration is given by A2
If the two areas are equal, i.e., A1 = A2, then the power system will be stable
Critical Clearing Angle (δcr) maximum allowable value of the clearing time and angle forthe system to remain stable are known as critical clearing time and angle.
δcr expression can be obtained by substituting δc = δcr in the equation A1 = A2
Substituting Pe = 0 in swing equation
EE2351 A.Ahamed RiazudeenAP/EEE
78
Substituting Pe = 0 in swing equation
Integrating the above equation
Replacing δ by δcr and t by tcr in the above equation, we getthe critical clearing time as
EE2351 A.Ahamed RiazudeenAP/EEE
79
Factors Affecting Transient Stability
• Strength of the transmission network within the systemand of the tie lines to adjacent systems.
• The characteristics of generating units including inertia ofrotating parts and electrical properties such as transientreactance and magnetic saturation characteristics of thestator and rotor.
• Speed with which the faulted lines or equipments can bedisconnected.
EE2351 A.Ahamed RiazudeenAP/EEE
80
• Strength of the transmission network within the systemand of the tie lines to adjacent systems.
• The characteristics of generating units including inertia ofrotating parts and electrical properties such as transientreactance and magnetic saturation characteristics of thestator and rotor.
• Speed with which the faulted lines or equipments can bedisconnected.
Numerical Integration methods
Modified Euler’s method
Runge-Kutta method
EE2351 A.Ahamed RiazudeenAP/EEE
81
MODIFIED EULER’S METHOD
• Using first derivative of the initial point next point is obtained• the step
• Using this x1p dx/dt at x1
p=f(t1, x1p)
• Corrected value is
1 0p dX
X X tdt
1 0t t t
EE2351 A.Ahamed RiazudeenAP/EEE
82
0 1
1
1 0
1
2
2
p
pi i
X XP
X Xci i
d x d x
d t d tX X t
d x d x
d t d tX X t
Numerical Solution of the swing equation
• Input power pm=constant• At steady state pe=pm,
• At synchronous speed
10
1 m ax
'
1 m ax1
s in mp
p
E Vp
X
EE2351 A.Ahamed RiazudeenAP/EEE
83
• Input power pm=constant• At steady state pe=pm,
• At synchronous speed
10
1 m ax
'
1 m ax1
s in mp
p
E Vp
X
0
'
2 max2
0
E Vp
X
2
20
20 0
2max2
20
2
sin
a m e
m a
a
H dp p p
f dt
f fdp p p
dt H Hd
dt
fd dp
dt H dt
The swing equation
EE2351 A.Ahamed RiazudeenAP/EEE
84
2
20
20 0
2max2
20
2
sin
a m e
m a
a
H dp p p
f dt
f fdp p p
dt H Hd
dt
fd dp
dt H dt
Applying Modified Eulers method to above equation
1 0t t t
1
1
i
i
pi i
pi i
dt
dt
dt
dt
• The derivatives at the end of interval
1
11
1
0
pi
ppi
i
pi
a
d
dt
fdp
dt H
The corrected value
EE2351 A.Ahamed RiazudeenAP/EEE
85
1
1
1
1
2
2
pi i
pi i
ci i
ci i
d d
dt dtt
d d
dt dtt
Runge-Kutta Method• Obtain a load flow solution for pretransient conditions• Calculate the generator internal voltages behind transient reactance.• Assume the occurrence of a fault and calculate the reduced admittance matrix• Initialize time count K=0,J=0• Determine the eight constants
1 1
1 2
1 12 1
1 12 2
2 23 1
2 23 2
3 34 1
3 34 2
1 2 3 4
( , )
( , )
( , )2 2
( , )2 2
( , )2 2
( , )2 2
( , )2 2
( , )2 2
2 2
k k k
k k k
k kk k k
k kk k k
k kk k k
k kk k k
k kk k k
k kk k k
k k k
k
K f t
l f t
K lK f t
K ll f t
K lK f t
K ll f t
K lK f t
K ll f t
K K K K
1 2 3 4
6
2 2
6
k
k k k k
kl l l l
EE2351 A.Ahamed RiazudeenAP/EEE
86
1 1
1 2
1 12 1
1 12 2
2 23 1
2 23 2
3 34 1
3 34 2
1 2 3 4
( , )
( , )
( , )2 2
( , )2 2
( , )2 2
( , )2 2
( , )2 2
( , )2 2
2 2
k k k
k k k
k kk k k
k kk k k
k kk k k
k kk k k
k kk k k
k kk k k
k k k
k
K f t
l f t
K lK f t
K ll f t
K lK f t
K ll f t
K lK f t
K ll f t
K K K K
1 2 3 4
6
2 2
6
k
k k k k
kl l l l
• Compute the change in state vector
• Evaluate the new state vector
• Evaluate the internal voltage behind transient reactance using the relation
• Check if t<tc yes K=K+1• Check if j=0,yes modify the network data and obtain the new reduced
admittance matrix and set j=j+1• set K=K+1• Check if K<Kmax, yes start from finding 8 constants
1
1
k k k
k k k
1 2 3 4
1 2 3 4
2 2
6
2 2
6
k k k k
k
k k k k
k
K K K K
l l l l
1 1 1cos sink k k k kp p p p pE E j E
EE2351 A.Ahamed RiazudeenAP/EEE
87
• Compute the change in state vector
• Evaluate the new state vector
• Evaluate the internal voltage behind transient reactance using the relation
• Check if t<tc yes K=K+1• Check if j=0,yes modify the network data and obtain the new reduced
admittance matrix and set j=j+1• set K=K+1• Check if K<Kmax, yes start from finding 8 constants