ECP UPSM-B

1
GB 2 Schneider Electric Micrologic 2.3 (NSX) Sensor = 630 Plug = 630 Amps Ir = Fine Adj. 0.9 (567 Amps) LT Band = Fixed Isd = 10 x Ir (5670 Amps) tsd = Fixed Ii = Fixed (6930 Amps) IT-Q6 Merlin Gerin MICROLOGIC 2.0 Sensor = 1000 LT Pickup = 0.8 (800 Amps) LT Band = 0.5 ST Pickup = 5 (4000 Amps) ST Band = Fixed SB Schneider Electric Micrologic 2.2 (NSX) Sensor = 40 Plug = 40 Amps Ir = Fine Adj. 1 (40 Amps) LT Band = Fixed Isd = 1.5 x Ir (60 Amps) tsd = Fixed Ii = Fixed (600 Amps) IT-Q7 Merlin Gerin MICROLOGIC 2.0 Sensor = 1000 LT Pickup = 0.5 (500 Amps) LT Band = 0.5 ST Pickup = 10 (5000 Amps) ST Band = Fixed TTA TSA2 Schneider Electric Micrologic 2.2 (NSX) Sensor = 40 Plug = 40 Amps Ir = Fine Adj. 1 (40 Amps) LT Band = Fixed Isd = 1.5 x Ir (60 Amps) tsd = Fixed Ii = Fixed (600 Amps) GB 1 Schneider Electric Micrologic 2.3 (NSX) Sensor = 630 Plug = 630 Amps Ir = Fine Adj. 0.9 (567 Amps) LT Band = Fixed Isd = 10 x Ir (5670 Amps) tsd = Fixed Ii = Fixed (6930 Amps) STS-B3 Merlin Gerin MICROLOGIC 2.0 Sensor = 1000 LT Pickup = 0.4 (400 Amps) LT Band = 0.5 ST Pickup = 5 (2000 Amps) ST Band = Fixed STS-B2. Merlin Gerin MICROLOGIC 2.0 Sensor = 1000 LT Pickup = 0.7 (700 Amps) LT Band = 0.5 ST Pickup = 5 (3500 Amps) ST Band = Fixed 10K .5 1 10 100 1K 3 5 30 50 300 500 3K 5K Amps X 10 UPSM-B2 (Nom. kV=0.4, Plot Ref. kV=0.4) 10K .5 1 10 100 1K 3 5 30 50 300 500 3K 5K Amps X 10 UPSM-B2 (Nom. kV=0.4, Plot Ref. kV=0.4) 1K .01 .1 1 10 100 .03 .05 .3 .5 3 5 30 50 300 500 Seconds 1K .01 .1 1 10 100 .03 .05 .3 .5 3 5 30 50 300 500 Seconds ETAP Star 12.6.0H ECP UPSM-B Project: Coordinacion Proteccion IBM Location: LA MOLINA 02 Date: 16-05-2015 Rev: Base Fault: Phase UDP-B UDP-B. DDPB TS-B TTA-TSA GB 1 TTA TSA2 STS-B2. STS-B3 IT-Q6 GB 2 IT-Q7 Open SB TTA-TSA TS-B DDPB UDP-B. UDP-B IT-Q7 Open GB 2 IT-Q6 STS-B2. STS-B3 SB TTA TSA2 GB 1

description

gráficos proteccion

Transcript of ECP UPSM-B

  • GB 2Schneider Electric Micrologic 2.3 (NSX)Sensor = 630 Plug = 630 AmpsIr = Fine Adj. 0.9 (567 Amps)LT Band = FixedIsd = 10 x Ir (5670 Amps)tsd = FixedIi = Fixed (6930 Amps)

    IT-Q6Merlin Gerin MICROLOGIC 2.0Sensor = 1000LT Pickup = 0.8 (800 Amps)LT Band = 0.5ST Pickup = 5 (4000 Amps)ST Band = Fixed

    SBSchneider Electric Micrologic 2.2 (NSX)Sensor = 40 Plug = 40 AmpsIr = Fine Adj. 1 (40 Amps)LT Band = FixedIsd = 1.5 x Ir (60 Amps)tsd = FixedIi = Fixed (600 Amps)

    IT-Q7Merlin Gerin MICROLOGIC 2.0Sensor = 1000LT Pickup = 0.5 (500 Amps)LT Band = 0.5ST Pickup = 10 (5000 Amps)ST Band = Fixed

    TTA TSA2Schneider Electric Micrologic 2.2 (NSX)Sensor = 40 Plug = 40 AmpsIr = Fine Adj. 1 (40 Amps)LT Band = FixedIsd = 1.5 x Ir (60 Amps)tsd = FixedIi = Fixed (600 Amps)

    GB 1Schneider Electric Micrologic 2.3 (NSX)Sensor = 630 Plug = 630 AmpsIr = Fine Adj. 0.9 (567 Amps)LT Band = FixedIsd = 10 x Ir (5670 Amps)tsd = FixedIi = Fixed (6930 Amps)

    STS-B3Merlin Gerin MICROLOGIC 2.0Sensor = 1000LT Pickup = 0.4 (400 Amps)LT Band = 0.5ST Pickup = 5 (2000 Amps)ST Band = Fixed

    STS-B2.Merlin Gerin MICROLOGIC 2.0Sensor = 1000LT Pickup = 0.7 (700 Amps)LT Band = 0.5ST Pickup = 5 (3500 Amps)ST Band = Fixed

    10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

    Amps X 10 UPSM-B2 (Nom. kV=0.4, Plot Ref. kV=0.4)

    10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K

    Amps X 10 UPSM-B2 (Nom. kV=0.4, Plot Ref. kV=0.4)

    1K

    .01

    .1

    1

    10

    100

    .03

    .05

    .3

    .5

    3

    5

    30

    50

    300

    500

    Seco

    nds

    1K

    .01

    .1

    1

    10

    100

    .03

    .05

    .3

    .5

    3

    5

    30

    50

    300

    500

    Seconds

    ETAP Star 12.6.0H

    ECP UPSM-B

    Project: Coordinacion Proteccion IBMLocation: LA MOLINA 02

    Date: 16-05-2015 Rev: BaseFault: Phase

    UDP-B

    UDP-B.

    DDPB

    TS-BTTA-TSA

    GB 1

    TTA TSA2 STS-B2. STS-B3

    IT-Q6

    GB 2

    IT-Q7Open

    SB

    TTA-TSA TS-B

    DDPB

    UDP-B.

    UDP-B

    IT-Q7Open

    GB 2

    IT-Q6

    STS-B2. STS-B3 SBTTA TSA2

    GB 1