Scientia Iranica B (2017) 24(2), 610{623

Sharif University of TechnologyScientia Iranica

Transactions B: Mechanical Engineeringwww.scientiairanica.com

Economic and environmental evaluation of di�erentoperation alternatives to aquifer thermal energystorage in Tehran, Iran

H. Ghaebia;�, M.N. Bahadorib and M.H. Saidib

a. Department of Mechanical Engineering, Faculty of Engineering, University of Mohaghegh Ardabili, Ardabil, P.O. Box 179, Iran.b. School of Mechanical Engineering, Sharif University of Technology, Tehran, P.O. Box 11155-9567, Iran.

Received 10 April 2015; received in revised form 14 January 2016; accepted 2 May 2016

KEYWORDSAquifer thermalenergy storage;Economic evaluation;Environmentalevaluation.

Abstract. Aquifers are underground porous formations containing water. Con�nedaquifers are surrounded by impermeable layers on top and bottom, called cap rocks and bedrocks. A con�ned aquifer with a very low groundwater ow velocity was considered to meetthe annual cooling and heating energy requirements of a residential building complex inTehran, Iran. Three di�erent alternatives of Aquifer Thermal Energy Storage (ATES) wereemployed to meet the heating/cooling demands of the buildings. These alternatives wereusing ATES for: cooling alone, heating alone by coupling with at-plate solar collectors,and cooling and heating by coupling with a heat pump. For the economic evaluation of thealternatives, a life cycle cost analysis was employed. For the environmental evaluation, RetScreen software was employed. For the considered 3 operational alternatives, using ATESfor cooling alone had the minimum payback period time of 2.41 years and the life cycle costof 16000 $. In the environmental perspective, among the 3 alternatives, coupling of ATESwith heat pump for cooling and heating had the minimum CO2 generation, correspondingto 359 tons/year.

© 2017 Sharif University of Technology. All rights reserved.

1. Introduction

Nowadays, 40% of energy consumption and greenhousegas (GHG) emissions of developed economies are re-lated to buildings and 55% of building energy usageis for heating and cooling. The reduction of building-related GHG emissions is a high international policypriority. Since there are many technical solutions, thesepolicies should involve signi�cant improvements in theuse of highly energy-e�cient systems [1].

To reduce the energy consumption and the emis-sion of GHG, the building sector needs energy e�cientsolutions operating at the lowest cost.

*. Corresponding author. Tel./Fax: +98 45 33512912E-mail address: [email protected] (H. Ghaebi)

In relation with energy and buildings, sustainableengineering requires:

1. Reduction of the heating and cooling energy needsof buildings to their minimum possible values;

2. Reduction of consumption of primary sources ofenergy to meet these minimum values throughinnovative designs of energy conversion systems andthe employment of innovative methods to meet theenergy demands.

Seasonal storage of thermal energy in aquifers andthe utilization of solar energy and heat pumps areexamples of innovative approaches to reduce primaryenergy demand for heating and cooling of buildings.Furthermore, ATES is technically and economicallyfeasible [2-4].

H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623 611

Recently, ATES has become more popular, con-sidering the problems caused by the depletion of fossilfuels and the increase of global warming [5,6]. AquiferThermal Energy Storage (ATES) systems are generallyconsidered to be economically viable for the seasonalstorage of thermal energy. In an ATES, contaminationand depletion of groundwater are minimal, since thewater withdrawn from aquifer is circulated through aheat exchanger and it is immediately injected back intothe aquifer though injection well(s) [7-9].

Sommer et al. [10] determined the thermal per-formance of large-scale application of ATES usinga simpli�ed hydrogeological model. They comparedthe di�erent zonation patterns and determined thein uence of well-to-well distances. The role of aquiferthickness, thermal radius, and heat loss through theupper and lower con�ning aquitards was discussed.Jeon et al. [11] conducted a sensitivity analysis ofrecovery e�ciency in two cases of high-temperatureATES system with a single well to select key param-eters. For a fractional factorial design used to chooseinput parameters with uniformity, they considered theoptimal Latin hypercube sampling with an enhancedstochastic evolutionary algorithm. Then, the recoverye�ciency was obtained using a computer model devel-oped by COMSOL multiphysics. They concluded thatkey parameters varied with the experimental domain ofhydraulic and thermal properties as well as the numberof input variables. Bloemendal et al. [12] describedwhat optimal and sustainable use of the subsurfacewould look like in relation to ATES systems. Withsimulations, they showed their impact on the subsur-face and described the current way of dealing withthese impacts in the Netherlands. They also consideredself-organization and self-governance to improve theadoption and operation of ATES. Zeghicia et al. [13]assessed the suitability of using heat and cold storage ina single deep geothermal aquifer for district heating andcooling. They used an integrated modelling approachfor evaluating the controls on the energy e�ciencyof High-Temperature Aquifer Thermal Energy Storage(HT-ATES). They also analyzed sensitivity of thesystem e�ciency with respect to the main physical(density, viscosity, and longitudinal dispersivity) andoperational (distance between warm and cold storagevolumes, ow rates) design parameters.

In 2007, Sethia and Sharma [14] conducted aneconomic evaluation of an aquifer and its combinationwith a heat exchanger for heating and cooling of agreenhouse. The payback period in this project was 3.5years. It was more economical than the conventionalheating/cooling system, which had a payback periodof 7 years. They also employed a thermo-economicanalysis for the economic evaluation of the system [15].Gaine and Du�y [16] employed a Life Cycle Cost (LCC)method in their economic analysis of a borehole ther-

mal energy storage system. They considered capitaland operational costs, and calculated the costs of therecovered energy for di�erent scenarios. Vanhoudtet al. [17] monitored the performance of an aquiferthermal energy storage system in combination with aheat pump for heating, cooling, and the ventilation ofair in a Belgian hospital for a period of three years.Furthermore, they conducted an economic analysis andshowed an annual cost reduction of 54000 ¿, whencompared with the basic case with the payback timeof 3.9 years.

Zhua et al. [18] conducted a probabilistic life cyclecost analysis for a Ground Source Heat Pump (GSHP)based on Monte Carlo method. They found that,from a life cycle perspective, the GSHP option wasmore favorable than the conventional system. Hanget al. [19] evaluated the solar water heating systemsfor typical US residential buildings from the energyconsumption, economic, and environmental points ofview. They considered at-plate and evacuated-tubesolar collectors. Their results showed that the at-plate solar water heating systems, using a natural gasauxiliary heating, had the best performance. Kegelet al. [20] conducted a life cycle cost analysis forseveral combinations of heat pumps with renewablesources under Canadian climatic conditions. Throughoptimization, and for a 20-year life cycle analysis,they found that a standard air source heat pumpsystem was the most economical option for an energy-e�cient house. However, to our knowledge, no previousinvestigation has proposed or assessed ATES from theeconomic and environmental points of view. Therefore,the sub-objectives of this research paper are multi-foldand include:

� Designing a suitable con�ned aquifer to meet thecooling and heating energy needs of a residentialbuilding complex located in Tehran, Iran;

� Providing a comprehensive numerical model of theaquifer thermal energy storage and thermodynamicevaluation;

� Considering three di�erent operational alternativesin combination with ATES;

� Noting economic and environmental considerationsof the di�erent operational alternatives;

� Using LCC method for economic considerations.

2. Heating and cooling energy needs of theresidential building complex

A residential complex, consisting of 10 four-storybuildings, located in Pounak region of Tehran wasconsidered. Each oor consisted of 4 small apartments.The total oor area of the residential complex was12800 m2.

612 H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623

Hourly cooling and heating energy needs of thebuildings were estimated using the software HAP 4.41(Carrier) [6]. The building needed heating in 4 monthsof the year, beginning on November 21, and cooling in4 months, beginning on May 21. The peak heatingand cooling loads were estimated to be 0.504 MWand 1.13 MW, respectively. The annual heating andcooling requirements of the complex were estimatedto be 1.9 TJ and 8.7 TJ, respectively. Since thecooling requirement was much larger than that of theheating, we designed the ATES considering coolingrequirement [6].

Presently, the heating and cooling needs of thebuildings are met through gas-�red boilers, with supplyand return hot water temperatures of 60 and 40�C,respectively. Vapor-compression system, employingan environmentally safe refrigerant, is employed forcooling, with supply and return chilled water temper-atures of 7 and 15�C, respectively. Also, fan coils areemployed in rooms for space heating and cooling.

3. Utilizations of ATES for cooling andheating of the buildings

We considered several alternatives to meet the heatingand cooling energy requirements of the building com-plex. These alternatives were: direct cooling throughATES, coupling ATES with at-plate solar collectorsfor heating, and �nally coupling ATES with heat pumpfor both heating and cooling. These alternatives arebrie y described below [6].

3.1. Direct cooling through ATESIn the ATES, water is withdrawn from the extractionwell(s) in order to supply the thermal energy require-ments of the building. In summer, cold water is with-drawn from the aquifer. It provides the cooling needsof the building by going through a heat exchanger. Itis then injected back into aquifer through the injectionwell(s) and stored there for winter operation. In winter,water is withdrawn from the aquifer and it is cooled bygoing through a cooling tower and then injected backinto the aquifer. Figure 1 shows the system operationin this alternative.

Figure 1. Direct Cooling through ATES.

Figure 2. Heating by coupling of the ATES with at-plate solar collectors.

3.2. Coupling ATES with at-plate solarcollectors for heating

Figure 2 shows an ATES, coupled with solar collectors.In this system, solar energy is utilized during thesummer months to heat the water withdrawn from theaquifer. The heated water is then injected back intothe aquifer. The stored warm water is withdrawn inwinter to meet the heating needs of the building.

3.3. Coupling of ATES with a heat pump forboth cooling and heating

Another alternative for ATES to meet the heatingneeds of buildings is its combination with a heatpump. Summer application of this alternative is sameas the summer operation mode for the direct coolingalternative.

Warm water from aquifer acts as a low-temperature heat source for the heat pump (see Fig-ure 3). Since, in this study (for the building locatedin Tehran), the heating energy needs are much smallerthan the cooling needs, only a portion of the withdrawnwater is needed to pass through the heat pump toprovide the low-temperature heat source for it. Theother part of the withdrawn water passes through thecooling tower. These two parts of withdrawn water arecombined and then injected back into the aquifer forsummer cooling.

Figure 3. Combination of ATES with a heat pump forheating of the building (winter operation).

H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623 613

4. Modeling

4.1. Governing equationsThermo-hydraulic analysis of the aquifer performancerequires calculation of the groundwater ow and thetemperature distribution in the aquifer and its sur-rounding layers. In this section, theoretical principlesof water ow and heat transfer phenomena for calculat-ing the temperature distribution inside the aquifer areexplained. The coupled groundwater and heat ow aregoverned by the partial di�erential equations describingthe mass and energy balances in the aquifer.

The aquifer is a porous medium. The continuityequation in a porous medium may be expressed by thefollowing equation [21]:�

@(��)@t

+ ~r: (�~q)�dV = Sf ; (1)

where Sf is related to source/sink term inside theporous medium and ~q is ow ux vector. It is obtainedfrom the Darcy's equation:

~q = �K ~rh; (2)

which is the governing equation for the ow in aporous medium. In this equation, K is the aquiferpermeability.

The governing equation for heat transfer, in-cluding conduction and convection, is derived by ap-plying the energy conservation principle in a porousmedium [22]:

ps@T@t

= r2(�T )� (�c)f~q:~rT + SH ; (3)

ps = (�c)f�+ (�c)S(1� �); (4)

where, ps, (�c)f , and (�c)s are heat capacities per unitvolume of aquifer, water, and the pebbles, respectively.Also, T , q, and SH are temperature, ow ux, and en-ergy source/sink terms inside the aquifer, respectively,while � is a combined ratio that is a function of thethermal conductivity of water, pebbles, and aquiferporosity:

� = �kf + (1� �)ks: (5)

The main heat transfer phenomenon within the upperand lower surrounding layers of the aquifer is conduc-tion. Therefore, we have:

@T@t

= �r2T: (6)

4.2. Numerical modelingIn this research, the �nite di�erence approach is em-ployed for modeling of ow and temperature distri-

bution in the con�ned aquifer under consideration,because of simple computational geometry and bound-aries. Implementation and simulation in the �nitedi�erence method is simple. But, the quality of a�nite di�erence approximation is often lower than thatof the other corresponding approaches, such as �niteelement.

The computational domain is three-dimensional.Using �nite di�erence approach is conventional inATES ow and thermal modeling [21]. The ow andtemperature equations are as follows:

@2h@x2 +

@2h@y2 +

@2h@z2 = �Sf (x; y; z)

K�dV; (7)

(�c)s@T@t

=��@2T@x2 +

@2T@y2 +

@2T@z2

�� (�c)f

��Kf

�@h@x~i+

@h@x~j +

@h@x~k��

:�@T@x~i+

@T@x~j +

@T@x

~k�

+ SH ; (8)

@T@t

= ��@2T@x2 +

@2T@y2 +

@2T@z2

�: (9)

The �rst step in the �nite di�erence method is dis-cretization. The numerical solution of the aboveequations is performed by using fractional steps inthree dimensions [23]. Initially, the equation is solvedusing Crank-Nicolson implicit method, and results ofthe solution in one direction (for example, x direc-tion) are used for solutions in other directions (yand z directions). In any direction, the solution isperformed by applying the Thomas's TDMA2 (ThreeDiagonal Matrix Algorithm) algorithm. Central dif-ference scheme is used to discretize Eqs. (7), (8),and (9).

It should be noted that this method has second-order truncation errors in each direction. The advan-tage of this procedure is its unconditional stability andhigher rate of convergence, because of using the TDMAmethod [23].

4.2.1. MeshingThe computational domain was cubic and three-dimensional. Since the boundary conditions in anaquifer are simple, using the uniform structured meshis more applicable. Meshing was performed in such away that injection/withdrawal wells were considered inall nodes of computational domain. Figure 4 shows themeshing arrangement.

For investigation of mesh size independency, sothat a unique solution would be obtained, three seriesof mesh sizes were examined: �x = 0:5 m, �y = 0:5 m,�z = 0:25 m with �t = 0:5 hours; �x = 1 m,

614 H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623

Figure 4. Three-dimensional computational domain.

�y = 1 m, �z = 0:5 m with �t = 1 hours;and �x = 5 m, �y = 5 m, �z = 2:5 m with�t = 10 hours. The parameter on which the errorwas estimated was recovery factor of the aquifer (seeSection 4.2.3). The time of simulation was 2 years forall of them. We found out that the recovery factordi�erences between the �rst and the second series andbetween the second and the third series were 1 and 5percent, respectively, since the stability condition wasful�lled. Therefore, the second series was selected asinterval steps.

4.2.2. Initial and boundary conditionsThe boundary condition at the upper layer of cap rockis constant temperature. It is assumed that in itsdepth, the temperature remains constant throughoutthe year and it is approximately equal to the yearlyaverage of the ambient air temperature of the location(Tehran). At the lower layer of the bed rock, theboundary condition is thermally insulated. The sidesare also assumed to be thermally isolated. The initialtemperature in the model domain linearly increasesfrom the top to the bottom to express the thermalequilibrium state prior to thermal injection.

According to the condition, a value is consideredfor ow rates of the injection/withdrawal wells. Thisvalue is considered as the source term in Eq. (1). Byconsidering groundwater velocity, a pressure gradientis added in the direction of x that is obtained from theDarcy equation. The initial head in the model domainis equal to the model elevation. Boundary conditionon the lateral and the upper and lower sides is no ow.

4.2.3. Energy recovery factor in the aquiferAfter determining the temperature �eld within theaquifer at di�erent time steps, the amount of recoveredenergy from the aquifer is determined. The mostimportant factor of ATES numerical modeling is theenergy recovery factor. It indicates the amount ofenergy which can be recovered from the stored energyin the aquifer. Thermal energy recovery factor of anaquifer, �A, is equal to the ratio of the extracted energy

to the amount of injected energy, or:

�A =Qwithdraw

Qinjection: (10)

4.2.4. Coe�cient of performance of the thermalenergy storage system

In air conditioning systems (heating or cooling), thecoe�cient of performance is de�ned as:

COPsystem =Qrequired

W; (11)

where QRequired is the annual amount of energy require-ment for cooling or heating of the building and W isthe total annual electrical energy consumed to run thecirculation pumps, cooling tower fans, chillers, and heatpumps.

5. Steps followed for the design of the ATES

To determine the parameters of an ATES, the followingdata must be available:

- Energy storage capacity;

- The maximum injection/withdraw rate and the tem-perature di�erence.

In the aquifer thermal energy storage system con-sidered in this study, �rst, the amount of energyrequired for cooling or heating of the building complexis estimated. The aquifer parameters, such as thick-ness, porosity, and permeability, are generally obtainedfrom the hydrological data available at the site. Ingeneral, the aquifer parameters vary in the domain. Tosimplify the investigation, constant values are assumedin this study [6]. Table 1 shows the aquifer propertiesemployed in the analysis.

After determining the aquifer characteristics andthe heating/cooling requirements of the building, thestorage system can be designed as follows [24]:

1. Determine the speci�c heat capacity (ps);

Table 1. Thermo-physical properties of the aquifer.

Property Value

Aquifer permeability 0.0017 m/s

Porosity 0.3

Density of water 1000 kg/m3

Density of pebbles 1800 kg/m3

Speci�c heat of water 4200 J/kg K

Speci�c heat of pebbles 1292 J/kg K

Thermal conductivity of water 0.63 W/m K

Thermal conductivity of pebbles 1.3 W/m K

H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623 615

2. Determine the recovery factor of the aquifer, �A.The recovery factor is calculated via numericalsimulations. The aquifer dimensions and propertiesare supplied as inputs. First, an approximate valuefor the recovery factor of the aquifer is assumed.Then, at the end of the simulation procedure andafter determining distance of the wells, the value ofthe recovery factor is calculated;

3. The required storage volume is calculated from thefollowing equation:

Vstorage =Erequired

pS�T�A: (12)

By dividing the storage volume to the injec-tion/withdraw period, the amount of injection/withdrawal ow rate is obtained;

4. The horizontal area of the aquifer with the depthof b is determined from:

A =Vstorage

b: (13)

5. The distance between the wells is obtained from thefollowing relation [24]:

R =pA=1:05: (14)

6. With the known distance between wells and theinjection/withdraw ow rate, the recovery factorof the aquifer is determined through the developedsimulation code;

7. Steps 3 to 6 are repeated until the di�erencebetween the assumed and estimated values of therecovery factor of the aquifer is less than a certainamount.

6. Economic model

Economic investigation of energy systems can be con-ducted in two ways. One is the �nancial assessmentthat is used by buyers and only takes account of thecapital and operational costs versus gained energy.Another method that has been used by governmentsand decision makers is called the economic assessment.In this method, all economic factors such as costs,taxes, and subsidies are generally considered. Inthe economic assessment, the following methods andfactors are considered:

1. Life Cycle Cost (LCC) is the sum of all costs duringapplication of the system based on the prices of theday;

2. Payback Period (PP) is the time required to recoverall spent costs via incoming or saving money.

Economic evaluation based on the life cycle cost anal-ysis is a perfect method for studying of commercialpurposes.

6.1. The actual value of costsIn this method, not only the capital costs, but also thecosts imposed during system operation are considered.The study period should be equal to the maximumlifetime of the elements of the considered system. Afterconsidering the capital investment and the operatingand maintenance costs, it can be easy to detect thecheaper system by comparison. For a meaningfulcomparison, expenditures and revenues or costs andbene�ts should be expressed in the day worth ofequivalent present value (PW ) in the future. For thispurpose, the discount or interest rate is used as follows:

PW = Pr � FW; (15)

where:

Pr =1

(1 + d)n; (16)

where PW , Pr, d, and n are present worth, presentworth factor, discount rate, and lifetime of the system,respectively. FW is the future worth of revenues orincomings. The annual interest or discount rate (d) isthe depreciation percent of the invested capital in oneyear.

The economic calculation of the present values ofthe life cycle cost of expenditures or incoming includestwo parts:

1. Single payment: The present worth of costs thatare paid once in lifetime of the system (purchase,piping, and installation costs). The present valueof a single payment can be obtained by replacingFW in Eq. (15):

PW = Pr � Cr: (17)

Cr and Pr are the single payment cost and presentworth factor, respectively. In this study, the pipingand installation cost is assumed to be 5% of thetotal purchase cost;

2. Annual payment: The present worth of theexpenditures that will be annually paid duringlifetime of the system (operational and maintenancecosts) and obtained as follows:

PW =Ca+ Ca�

11 + d

�+ Ca

�1

1 + d

�2

+ � � �

+ Ca�

11 + d

�n�1

: (18)

By allocation of x = 11+d , Eq. (18) can be rewritten

as:1Xi=0

xi = 1 + x+ x2 + � � � = 11� x; (19)

616 H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623

Pa = 1 + x+ x2 + � � �+ xn =1

1� x �1Xi=n

xi

=1

1� x � xn1Xi=0

xi =1� xn1� x : (20)

Eq. (18) can be brie y rewritten as follows:

PW = Pa� Ca; (21)

where:

Pa =(1 + d)n � 1d(1 + d)n�1 : (22)

Ca and Pa are the annual cost and the cumula-tive present worth factor, respectively. When thediscount rate is smaller, the present worth factoris larger and by reduction of the discount rate, thecosts that should be paid in the future gain higheractual worth [25]. The maintenance cost is usuallyconsidered as a portion of the purchase cost. In thisstudy, this cost is assumed to be 2% of the capitalinvestment at the �rst operational year.

6.2. Life Cycle Cost (LCC)By using the present worth factor of Pr and Pa forall types of costs, the present worth can be calculated.The summation of all of the present worth is equal tothe total cost that will be paid during lifetime of thesystem and is called LCC:

LCC =Xi

PWi: (23)

By having and comparing the LCCs of di�erent sys-tems, the suitable system can be selected economi-cally [25].

6.3. Annualized Life Cycle Cost (ALCC)This quantity is obtained by dividing LCC to thecumulative present worth factor and its unit is thecurrency per year:

ALCC =LCCPa

: (24)

6.4. Payback periodThis study is a comparative study; thus, the paybackperiod is important in it. First, the energy productioncost is calculated for the basic case based on the LCCmethod. This cost is our criterion for comparison. Fordetermination of payback period, the expenditures forenergy production in di�erent systems and alternativesshould be compared with each other. The relations forcalculation of payback period are as follows:

PWc = PWb; (25)

PWc is the present worth of the total cost (single andannual costs) and PWb is the present worth of theincomings (cost of energy production in basic case).Then, we have:

LCC = E � P ��

(1 + d)n � 1d(1 + d)n�1

�; (26)

where n, d, E, and P are payback period, discountrate, annual energy production (energy requirement),and cost of energy production unit (basic case), respec-tively.

7. Discussion of the results

7.1. Numerical model veri�cationThe important parameter in ATES system that hasa key role on the performance of the system is thewithdrawal temperature. A veri�cation was performedby using the FLUENT software and simulation ofcomputational domain. The computational domain isshown in Figure 5. In this meshing, an unstructured3D mesh of 259346 cells was built. The chosenelement was Tet/Hybrid and its type was TGrid. Forvalidation of the cold and warm wells, temperatureswere compared with the ones which had been obtainedvia the developed code (Table 2) during two years. Theresults show a good agreement between the developedcode and the ones that were obtained using FLUENT.

7.2. Design of the ATES system for coolingand heating of the building

The input parameters are listed in Table 3. Designsimulation is carried out as explained in Section 5. Theresults of the design simulation are listed in Table 4.

For cooling and heating of the building complex,we have coupled the ATES system with a heat pump.Since the annual cooling needs in TJ/year are muchhigher than the annual heating needs, we base ourdesign on the annual cooling requirements. For thisreason, when solar collectors are coupled with ATESfor thermal energy storage for heating of the buildingcomplex, a much smaller aquifer would be needed.

The estimated pressure losses in the system arelisted in Table 5. These values were determined

Figure 5. Model mesh in FLUENT.

H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623 617

Table 2. Model veri�cation with results of FLUENT simulation.

t (day)Warm well temperature Cold well temperatureTFLUENT

(�C)TCode

(�C)Error(%)

TFLUENT

(�C)TCode

(�C)Error(%)

90 12 12 0 3 3 0

180 12 12 0 3 3.13 4.15

270 14 14 0 8.64 8.94 3.35

360 13.31 13.86 3.96 10.2 10.66 4.31

450 12.35 12.8 3.51 3 3 0

540 11.89 12.34 3.64 3.48 3.58 2.79

630 14 14 0 8.59 8.82 2.6

720 14 13.86 1.01 10.34 10.53 1.8

Table 3. Input information for the design of the ATES system.

QuantityCooling and a heatpump coupled withATES for heating

Flat-plate solarcollectors coupled with

ATES for heating

Injection temperature in winter (�C) 3 43

Injection temperature in summer (�C) 14 65

Initial recovery factor of the aquifer (%) 70 70

Aquifer height (m) 16 16

Cap rock height (m) 25 25

Bed rock height (m) 50 50

Groundwater velocity (m/year) 5 5

Groundwater temperature (�C) 12 12

Aquifer initial temperature (�C) 12 12

The temperature of upper surface of

the cap rock layer (�C)18 18

The energy that should be stored (TJ/y) 8.7 (cooling requirements) 1.9 (heating requirements)

Table 4. Results of the di�erent operational alternative designing.

QuantityCooling and a heatpump coupled withATES for heating

Flat-plate solarcollectors coupled with

ATES for heating

The recovery factor of the aquifer (%) 73 63

Aquifer length (m) 182 80

Aquifer width (m) 116 32

Injection/withdraw rate L/s 32.5 7.5

Aquifer volume (m3) 337080 35387

The area of the horizontal surface of

the aquifer (m3)21067 2527

Distance of the wells (m) 142 50

Coordination of cold well in horizontal

surface of the aquiferx = 20 my = 58 m

x = 15 my = 16 m

Coordination of warm well in horizontal

surface of the aquiferx = 162 my = 58 m

x = 65 my = 16 m

618 H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623

Table 5. Pressure losses for di�erent sections of the ATES system.

Unit Directcooling

ATES coupledwith heat

pump

ATES coupledwith solarcollectors

�Pfriction loss (m) 51.12 51.12 26.68�Pdepth (m) 45 45 40�Pwell pairs (m) 1.19 1.19 0.1�P�tting (m) 5 5 0.5�Pheat exchanger (m) 2.25 2.25 1.2�Pheat pump (m) | 1.5 |�Pcooling towers (m) 16 16 |�Psolar collectors (m) | | 8�Ptotal (m) 120.56 122.06 78.48

supposing 250 m of straight pipes, 10 elbows, a pipediameter of 10 cm for the alternatives of direct coolingand the coupled ATES with heat pump and 5 cmof pipe for the coupled ATES with solar collectors,2.5 cm of diameter for tube in the shell and tube heatexchanger with 5 m of length, and �nally 45 m of depthfor the wells. The head needed for the cooling towerpumps, and the pressure losses through the heat pumpand the solar collectors were obtained from the man-ufacturers' catalogues [26-28]. The pressure losses dueto friction were calculated from the Moody's diagramby considering the Reynolds number and roughness ofthe pipe that was supposed to be commercial steel.

7.3. Economical assessmentTable 6 shows the speci�cations and costs of theequipment that have been used in di�erent alternativesand in the basic case [26-32]. For economic analysisand comparison of energy systems, the annualizedcapital cost, fuel cost, and maintenance cost shouldbe calculated. The discount rate and lifetime of allof the systems have assumed to be 20% and 20 years,respectively. The electricity and natural prices are localprices in Iran that are considered to be 0.032 $/kWhand 0.04 $/m3, respectively.

The electricity and natural gas consumption ineach of the abovementioned alternatives are obtainedby using Ret Screen software. These values areobtained by this assumption such that all of thesealternatives can satisfy heating and cooling require-ments. In Figure 6, the electricity and natural gasconsumption of the di�erent alternatives and basic caseare compared. In the alternatives of coupled ATESwith heat pump and coupled ATES with solar collector,natural gas is not consumed and the heating of thebuilding is satis�ed through a new system. In thebasic case and the alternative of direct cooling, theheating requirement is supplied via gas �red boilerand, therefore, these systems have the same naturalgas consumption. The highest electricity consumption

Figure 6. Comparison of energy consumption of di�erentalternatives.

Figure 7. Comparison of LCCs and ALCCs of di�erentalternatives.

is of compression chiller and, then, the consumption ofthe basic case and coupled ATES with solar collectoris higher than that of other systems. In the directcooling alternative, electricity consumption is less thanother alternatives; this is also the case for the pumpconsumption.

In Figure 7, the values of LCC and ALCC areprovided for di�erent alternatives. The highest valuesare of the coupled ATES with solar collectors and thebasic case, respectively. As seen in Table 6, the highestcapital investment is of compression chiller that is used

H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623 619

Table 6. Speci�cations of the equipment for di�erent alternatives.

Equipment Speci�cations Number Manufacturer Cost ($)Basic case

Cooling

Compression chiller Capacity: 160 TRType: Screw

2 Sarma Afarin-Iran [29] 228000

Heating

Boiler Capacity: 600 kWType: Water tube

1 Tahvieh Damavand-Iran [30] 12000

ATES for direct coolingCooling

PumpHead:120 mFlow: 32.5 L/sPower: 36 kW

2 Pumpiran-Iran [31] 9200

Heat exchangerType: shell & tubeHeat rate: 1000000 kcal/hrFlow: 515 gpm

1 Tehran Mobaddel-Iran [32] 29400

Cooling tower Flow: 515 gpm 1 Damatajhiz-Iran [27] 3800Pipe Steel 300 m Iran 2400Wells drilling | 120 m Iran 4800Feasibility study | | Iran 8000Ground preparing | | Iran 4000Hydrology tests | | Iran 4000Justi�cations | | Iran 20000Heating

Boiler Capacity: 600 kWType: water tube

1 Tahvieh Damavand-Iran [30] 12000

Coupled ATES with heat pumpCooling

PumpHead: 120 mFlow: 32.5 L/sPower: 36kW

2 Pumpiran-Iran [31] 9200

Heat exchangerType: shell & tubeHeat rate: 1000000 kcal/hrFlow: 515 gpm

1 Tehran Mobaddel-Iran [30] 29400

Cooling tower Flow: 515 gpm 1 Damatajhiz-Iran [27] 3060Pipe steel 300 m Iran 2400Wells drilling | 120 m Iran 4800Feasibility study | | Iran 8000Ground preparing | | Iran 4000Hydrology tests | | Iran 4000Justi�cations | | Iran 20000Heating

Heat pump Capacity: 600 kWType: water to water

30 Miami Heat Pump-USA [28] 128000

620 H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623

Table 6. Speci�cations of the equipment for di�erent alternatives (countinued).

Equipment Speci�cations Number Manufacturer Cost ($)

Coupled ATES with solar collector

Cooling

Compression chillerCapacity: 160 TRType: Screw

2 Sarma Afarin-Iran [29] 228000

Heating

PumpHead: 75 mFlow: 7.5 L/sPower: 13 kW

2 Pumpiran-Iran [31] 4000

Heat exchangerType: shell & tubeHeat rate: 300000 kcal/hrFlow: 100 gpm

1 Tehran Mobaddel-Iran [32] 11400

Solar collector Type: Glazed 450 Watt-Poland [26] 40000Pipe Steel 300 m Iran 1800Wells drilling | 120 m Iran 4800Feasibility study | | Iran 8000Ground preparing | | Iran 4000Hydrology tests | | Iran 4000Justi�cations | | Iran 20000

Figure 8. Payback time of di�erent alternatives.

in these alternatives and has a greater portion in theirLCC and ALCC. Moreover, the electricity consumptionof these alternatives is too much that leads to highLCC and ALCC. The alternative of the direct coolinghas the minimum LCC and ALCC because of its lowcapital investment.

Figure 8 shows the payback period of three inves-tigated alternatives. Because of low capital investmentand low operational cost of the alternative of the directcooling, this alternative has the minimum paybackperiod.

7.4. Environmental assessmentThe main index of environmental sustainability of anenergy system is the amount of CO2 emission. CO2emission of di�erent alternatives is shown in Figure 9.

Figure 9. Comparison of CO2 emission of di�erentalternatives.

The alternative of the coupled ATES with heat pumphas low electricity consumption and zero natural gasconsumption. Therefore, its CO2 emission is lessthan other alternatives. Also, the basic case has themaximum CO2 generation because of much electricityand natural gas consumption.

8. Conclusion

In this study, 3 di�erent operational alternatives ofATES (using ATES for direct cooling, coupling ofATES with heat pump for both cooling and heating,

H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623 621

and coupling of ATES with at-plate solar collectorsfor heating) were economically and environmentallycompared with each other and with the basic case.These systems were employed to store the thermalenergy needs of a residential complex, located inTehran, Iran. The objective was the storage of 8.7 TJand 1.9 TJ of energy for summer cooling and winterheating, respectively. The LCC method and the RetScreen version 4.0 software were used for economic andenvironmental assessment. The important concludingremarks of this research are the following:

� The highest fuel (electricity and natural gas) costwas for the basic case that was used as boilerand compression chiller for heating and cooling,respectively;

� The alternative of coupled ATES with solar collectorand basic case had maximum and the alternative ofATES for cooling alone had minimum LCC;

� The payback periods of the alternatives of ATESfor cooling alone, coupled ATES with heat pumpfor cooling and heating, and coupled ATES with at-plate solar collectors were 2.41, 2.9, and 5.48,respectively;

� The alternative of coupled ATES with heat pump forheating and cooling had the minimum CO2 emission(359.32 tones/year).

Nomenclature

A Area, cross section (m2)ALCC Annualized Life Cycle Cost ($)b Aquifer thickness (m)c Speci�c heat (J/kgK)Ca Annual cost ($)Cr Single payment cost ($)COP Coe�cient Of Performanced Discount rate (%)E Energy (J)FW Future value ($)g Gravitational acceleration (m/s2)h Hydraulic head (m)K Permeability (m/s)k Speci�c permeability (m2)L Length (m)LCC Life Cycle Cost ($)n Life time, payback (year)p Speci�c heat capacity (J/m3K)P Price of energy production unit ($/J)Pa Cumulative present factor

Pr Present worth factorPW Present value ($)q Speci�c velocity (m/s)Q Heat (J)R Wells distance (m)S Flow source term (kg/s) and heat

source term (J/m3K)t Time (s)T Temperature (K)

V Volume (m3)_V Flow rate (m3/s)

Greek Symbols

� Di�usivity (m2/s)� E�ciency� Porosity� Aquifer thermal conductivity

(W/m/K)

� Density (kg/m3)

Subscripts

A Aquiferf Fluidgw Groundwaterimp Imposedinjection InjectionO OverallRock Rock or pebblesS Speci�c, solidV Voidwater Waterwithdraw Withdraw

References

1. Dincer, I. \Renewable energy and sustainable devel-opment: a crucial review", Renewable and SustainableEnergy Reviews, 4, pp. 157-175 (2000).

2. Bakema, G., Snijders, A.L. and Nordell, B., Un-derground Thermal Energy Storage-State of the ArtReport, Arnhem, Netherlands (1995).

3. Sanner, B., Karytsas, C., Menfrinos, D. and Rybach,L. \Current status of ground source heat pumps,and underground thermal energy storage, in Europe",Geothermics, 32, pp. 579-588 (2003).

4. Dincer, I. and Rosen, M.A., Thermal Energy Storage- Systems and Applications, Wiley Press, Chichester(2002).

622 H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623

5. Kim, J., Lee, Y., Yoon, W.S., Jeon, J.S., Koo,M.H. and Keehm, Y. \Numerical modeling of aquiferthermal energy storage system", Energy, 35, pp. 4955-4965 (2010).

6. Ghaebi, H., Bahadori, M.N. and Saidi, M.H. \Perfor-mance analysis and parametric study of thermal energystorage in an aquifer coupled with a heat pump andsolar collectors, for a residential complex in Tehran,Iran", Applied Thermal Engineering, 62, pp. 156-170(2014).

7. Dickinson, J.S., Buik, N., Matthews, M.C. and Sni-jders, A. \Aquifer thermal energy: theoretical andoperational analysis", Geotechnique, 59, pp. 249-260(2009).

8. Novo, V.A., Bayon, R.J., Castro-Fresno, D. andRodriguez-Hernandez, R. \Review of seasonal heatstorage in large basins: water tanks and gravel waterpits", Applied Energy, 87, pp. 390-397 (2010).

9. Preene, M. and Powrie, W. \Ground energy systems:delivering the potential", Energy, 84, pp. 77-84 (2009).

10. Sommer, W., Valstar, J., Leusbrock, I., Grotenhuis, T.and Rijnaarts, H. \Optimization and spatial patternof large-scale aquifer thermal energy storage", AppliedEnergy, 137, pp. 322-337 (2015).

11. Jeon, J.S., Lee, S.R., Pasquinelli, L. and Fabricius,I.L. \Sensitivity analysis of recovery e�ciency in high-temperature aquifer thermal energy storage with singlewell", Energy, 90, pp. 1349-1359 (2015).

12. Bloemendal, M., Olsthoorn, Th. and Boons, F. \Howto achieve optimal and sustainable use of the sub-surface for aquifer thermal energy storage", EnergyPolicy, 66, pp. 104-114 (2014).

13. Zeghicia, R.M., Essink, G.H.P.O., Hartogc, N.and Sommer, W. \Integrated assessment of variabledensity-viscosity groundwater ow for a high tempera-ture mono-well aquifer thermal energy storage (HT-ATES) system in a geothermal reservoir", Geother-mics, 55, pp. 58-68 (2015).

14. Sethia, V.P. and Sharma, S.K. \Greenhouse heatingand cooling using aquifer water", Energy, 32, pp. 1414-1421 (2007).

15. Sethia, V.P. and Sharma, S.K. \Experimental andeconomic study of a greenhouse thermal control systemusing aquifer water", Energy Conversion and Manage-ment, 48, pp. 306-319 (2007).

16. Gaine, K. and Du�y, A. \A life cycle cost analy-sis of large-scale thermal energy storage technologiesfor buildings using combined heat and power", ZeroEmission Buildings - Proceedings of Renewable EnergyConference, Trondheim, Norway (2010).

17. Vanhoudt, D., Desmedta, J., Van Baela, J., Robeynb,N. and Hoe, H. \An aquifer thermal storage system ina Belgian hospital: Long-term experimental evaluation

of energy and cost savings", Energy and Buildings, 43,pp. 3657-3665 (2011).

18. Zhua, Y., Tao, Y. and Rayegan, R. \A comparison ofdeterministic and probabilistic life cycle cost analysesof ground source heat pump (GSHP) applications inhot and humid climate", Energy and Buildings, 55,pp. 312-321 (2012).

19. Hang, Y., Qu, M. and Zhao, F. \Economical- andenvironmental life cycle analysis of solar hot watersystems in the United States", Energy and Buildings,45, pp. 181-188 (2012).

20. Kegel, M., Sunye, R. and Tamasauskas, J. \Life cyclecost comparison and optimization of di�erent heatpump systems in the Canadian climate", Proceedingsof e-Sim: The Canadian Conference on Building Sim-ulation, pp. 492-506 (2012).

21. Bear, J., Dynamics of Fluids in Porous Media, Else-vier, Dover Publication Inc., pp. 450-510 (1992).

22. Bejan, A., Convective Heat Transfer, McGraw HillPress, New York (1997).

23. Ho�mann, K.A. and Chiang, S.T., ComputationalFluid Dynamic, Publication of Engineering educationSystem, USA (2000).

24. Schaetzle, W.J., Thermal Energy Storage in Aquifers,Design and Applications, Pergamon Press, New York(1980).

25. Pehnt, M. \Dynamic life cycle assessment (LCA) ofrenewable energy technologies", Renewable Energy,31, pp. 55-71 (2005).

26. www.watt.pl/en (Accessed 30 March 2015).

27. www.damatazhiz.com (Accessed 30 March 2015).

28. www.heatpumpsuppliers.com (Accessed 30 March2015).

29. www.ssi.co.ir (Accessed 30 March 2015).

30. www.damavandac.com (Accessed 30 March 2015).

31. www.pumpiran.com (Accessed 30 March 2015).

32. www.tehranmobaddel.com (Accessed 30 March 2015).

Biographies

Hadi Ghaebi is Assistant Professor in the MechanicalEngineering Faculty of Mohaghegh Ardabili University,Ardabil, Iran. He received his PhD degree fromSharif University of Technology, Tehran, Iran, in 2014.His research areas include thermal system design andoptimization, renewable energy technologies, net zeroenergy buildings, and hydrogen and fuel cells.

Mehdi N. Bahadori received his PhD degree inMechanical Engineering from the University of Illinois,

H. Ghaebi et al./Scientia Iranica, Transactions B: Mechanical Engineering 24 (2017) 610{623 623

USA, in 1964, and is currently Professor of Mechan-ical Engineering at Sharif University of Technology,Tehran, Iran. His research interests include naturalcooling systems, solar energy utilization, environmen-tally compatible energy systems, development of in-digenous technology, application of scienti�c-spiritualthinking to social problems, entropy and awareness,and engineering ethics and engineering of ethics.

Mohammad Hassan Saidi is Professor in the Schoolof Mechanical Engineering at Sharif University of Tech-nology, Tehran, Iran. His current research interestsinclude MEMS, heat transfer enhancement in boilingand condensation, modeling of pulse tube refrigeration,vortex tube refrigerators, indoor air quality and cleanroom technology, energy e�ciency in home appliances,and desiccant cooling systems.