2; Contents
3; Nomeclature
4; Electrical Characteristics Scroll 1 Phase
5; Electrical Characteristics Scroll 3 Phase
6; Physical Characteristics Scroll Process
7; Drawings
8; Drawings Option Process
9; Wiring Diagram-single phase
10; Wiring Diagram-Three phase
11; Performance Scroll
12; Performance Scroll Process
13; Installation Requeriments
ECCLA/P036A25/46ER2/4/5
ECCL A/P 036 A 25/46/38/50 E R2/4/5
Product category
Eco ChillersRefrigerant
typeR2 = R22
Aplications R4 = R410A = Standard R5 = R507P = Process includes recirculating pump,tank,float level ctrl. CHILLER TYPE
E = ECOLOGIC
Nominal Cooling Capacity-MBH
012 = 1 Ton018 = 1.5 Ton024 = 2 Ton Voltage036 = 3 Ton 25 = 230-3-60060 = Ton 38 = 380-3-60
46 = 460-3-6050 = 575-3-60
Airflow OptionsA = Stándard
Motor
MODELECCLA012 ECCLA018 ECCLA024 ECCLA036 ECCLA060
1 Ton 1.5 ton 2 ton 3 ton 5 ton
Unit Supply Voltage 208-230v,1ø, 60Hz
Normal Voltage Range¹ 187 to 252
Minimum Circuit Ampacity 9.08 9.08 12.4 17.9 34.3
Max. Overcurrent Device Amps² 15 15 20 30 60
Min. Overcurrent Device Amps³ 15 15 15 20 35
Compressor Type Rotary Recip Recip Recip Recip
Compressor AmpsRated Load 7.4 7.4 9.3 13.1 26.2
Locked Rotor 40 40 43 74 150
Crankcase Heater No No No No No
Fan Motor Amps Rated Load 0.5 0.5 0.8 1.5 1.5
Fan Diameter Inches 17.5 17.5 17.5 22 24
Fan Motor
Rated HP 1/12 1/12 1/8 1/4 1/4
Nominal RPM 1100 1100 1075 850 850
Nominal CFM 1400 1400 1950 3200 3600
Coil
Face Area Sq. Ft. 9.6 9.6 9.6 13.07 18.68
Rows Deep 1 1 1 1 1
Fin / Inches 23 23 23 23 23
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8
Vapor Liner Set OD (Field Installed) 5/8 5/8 3/4 3/4 7/8
Unit Charger (Lbs.-Oz.)⁴ 3-3 3-3 3-13 4-9 5-6
Charger Pear Foot, Oz. 0.58 0.58 0.62 0.62 0.67
Operating Weight Lbs. 97 97 129 145 195
1 PHASE ELECTRICAL TABLE
MODELECCLA036 ECCLA060 ECCLA036 ECCLA060
3 ton 5 ton 3 ton 5 ton
Unit Supply Voltage 208-230v,1ø, 60Hz 460V,3ø,60 Hz
Normal Voltage Range¹ 187 to 252 432 to 532
Minimum Circuit Ampacity 12.3 23.9 7.1 13.5
Max. Overcurrent Device Amps² 20 40 15 20
Min. Overcurrent Device Amps³ 15 15 15 15
Compressor Type Recip Scroll Recip Scroll
Compressor AmpsRated Load 8.6 17.9 4.5 9.6
Locked Rotor 68 120 34 70
Crankcase Heater No No No No
Fan Motor Amps Rated Load 1.5 1.5 1.5 1.5
Fan Diameter Inches 22 22 22 22
Fan Motor
Rated HP 1/4 1/4 1/4 1/4
Nominal RPM 850 850 850 850
Nominal CFM 3200 3600 3200 3600
Coil
Face Area Sq. Ft. 13.07 18.68 13.07 18.68
Rows Deep 1 1 1 1
Fin / Inches 23 1 1 1
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8
Vapor Liner Set OD (Field Installed) 3/4 7/8 3/4 7/8
Unit Charger (Lbs.-Oz.)⁴ 4-9 5-6 4-9 5-6
Charger Pear Foot, Oz. 0.62 0.67 0.62 0.67
Operating Weight Lbs. 145 195 145 195
3 PHASE ELECTRICAL TABLE
MODEL ECCLP012 ECCLP018 ECCLP024 ECCLP036 ECCLP060
CAPACITY TONS 1 1.5 2 3 5
VOLTS 230/3/6 230/3/6 230/3/6 230/3/6 230/3/6
460/3/6 460/3/6 460/3/6 460/3/6 460/3/6
PUMP HP 2 / 1HP 2 / 1HP 2 / 1HP 2 / 1HP 2 / 1HP
GPM 2.4 3.6 4.8 7.2 12
IN / OUT WATER PIPE (Inches) 1'' 1'' 1'' 1'' 1''
TANK LTS 50 Lts 50 Lts 50 Lts 50 Lts 50 Lts
TANK DIMENTIONS (Mts)
HIGH 0.64 0.64 0.64 0.64 0.64
WIDE 0.65 0.65 0.65 0.65 0.65
LONG 0.91 0.91 0.91 0.91 0.91
WEIGHT (Lbs) 286.59 286.59 286.59 286.59 286.59
VOLUMEN M3 0.37 0.37 0.37 0.37 0.37CHILLER DIMENTIONS
(Inches)
HIGH 28'' 28'' 28'' 28'' 32
WIDE 23-1/2'' 23-1/2'' 23-1/2'' 29'' 33-5/8''
LONG 23-1/2'' 23-1/2'' 23-1/2'' 29'' 33-5/8''
OPERATING WEIGHT (Lbs) 97 97 129 145 195
VOLUMEN M3 .24 .24 .24 .37 .59
PHYSICAL PROCESS TABLE
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 1 of 2
Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
ECCLA036A06 1 ECCLA036A06 3 220/1/60 R410A Pin No: ECCLA036A06
Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) 0.6
Electrical Data Circuit 1 2 3 4
Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5
Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)
20
Min. Dual Element Fuse Size (Amps)
20
Max. Dual Element Fuse Size (Amps)
30
Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 8 Total Amps 15.6 Operating Condition Electrical
Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW 0.18 Total kW 2.64
Notes:
RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 2 of 2
Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0
75 86.3 50 80.6 13.2 / 3.9 25 66.9
SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLA036A06 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLA036A06 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision: 2.0 Performance Page 1 of 2
Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
ECCLA036A25 1 ECCLA036A25 3 220/3/60 R410A Pin No: ECCLA036A25
Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) 0.6
Electrical Data Circuit 1 2 3 4
Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5
Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)
20
Min. Dual Element Fuse Size (Amps)
20
Max. Dual Element Fuse Size (Amps)
30
Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 12 Total Amps 15.6 Operating Condition Electrical
Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW .18 Total kW 2.64
Notes:
RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision: 2.0 Performance Page 2 of 2
Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0
75 86.3 50 80.6 13.2 / 3.9 25 66.9
SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLA036A25 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLA036A25 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 1 of 2
Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
ECCLA036A46 1 ECCLA036A46 3 460/3/60 R410A Pin No: ECCLA036A46
Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) 0.6
Electrical Data Circuit 1 3 4
Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5
Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)
20
Min. Dual Element Fuse Size (Amps)
20
Max. Dual Element Fuse Size (Amps)
30
Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 14 Total Amps 15.6 Operating Condition Electrical
Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW .18 Total kW 2.64
Notes:
RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 2 of 2
Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0
75 86.3 50 80.6 13.2 / 3.9 25 66.9
SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLA036A46 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLA036A46 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 1 of 2
Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
ECCLP036A06 1 ECCLP036A06 3 220/1/60 R410A Pin No: ECCLP036A06
Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) 0.6
Electrical Data Circuit 1 2 3 4
Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5
Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)
20
Min. Dual Element Fuse Size (Amps)
20
Max. Dual Element Fuse Size (Amps)
30
Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 8 Total Amps 15.6 Operating Condition Electrical
Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW .18 Total kW 2.64
Notes:
RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 2 of 2
Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0
75 86.3 50 80.6 13.2 / 3.9 25 66.9
SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLP036A06 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLP036A06 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 1 of 2
Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
ECCLP036A25 1 ECCLP036A25 3 220/3/60 R410A Pin No: ECCLP036A25
Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) 0.6
Electrical Data Circuit 1 2 3 4
Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5
Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)
20
Min. Dual Element Fuse Size (Amps)
20
Max. Dual Element Fuse Size (Amps)
30
Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 12 Total Amps 15.6 Operating Condition Electrical
Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW .18 Total kW 2.64
Notes:
RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 2 of 2
Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0
75 86.3 50 80.6 13.2 / 3.9 25 66.9
SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLP036A25 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLP036A25 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 1 of 2
Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
ECCLP036A46 1 ECCLP036A46 3 460/3/60 R410A Pin No: ECCLP036A46
Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) .6
Electrical Data Circuit 1 2 3 4
Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5
Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)
20
Min. Dual Element Fuse Size (Amps)
20
Max. Dual Element Fuse Size (Amps)
30
Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 14 Total Amps 15.6 Operating Condition Electrical
Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW 0.18 Total kW 2.64
Notes:
RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]
AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B
Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 2 of 2
Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0
75 86.3 50 80.6 13.2 / 3.9 25 66.9
SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLP036A46 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0
SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLP036A46 ( Equipped with Low Sound Fans )
Load % Ambient (°F)
63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases
Dwg. Scale : NTSDwg. Lev.: 08/04
For: Contractor: Engineer:
TAG:
Date:JUNE2011 Rev.: 2.0 Form: 190.54-E1S
Sold To: Cust Purch Order#: Contract#: UNIT
INSTALLATION REQUERIMENTS
AIR-COOLED SCROLL CHILLER SYSTEM
PRODUCT DRAWING Location: Project Name:
MODEL ECCLA036A25E / A46E