ECCLA036A25 46E

23

Transcript of ECCLA036A25 46E

Page 1: ECCLA036A25 46E
Page 2: ECCLA036A25 46E

2; Contents

3; Nomeclature

4; Electrical Characteristics Scroll 1 Phase

5; Electrical Characteristics Scroll 3 Phase

6; Physical Characteristics Scroll Process

7; Drawings

8; Drawings Option Process

9; Wiring Diagram-single phase

10; Wiring Diagram-Three phase

11; Performance Scroll

12; Performance Scroll Process

13; Installation Requeriments

Page 3: ECCLA036A25 46E

ECCLA/P036A25/46ER2/4/5

ECCL A/P 036 A 25/46/38/50 E R2/4/5

Product category

Eco ChillersRefrigerant

typeR2 = R22

Aplications R4 = R410A = Standard R5 = R507P = Process includes recirculating pump,tank,float level ctrl. CHILLER TYPE

E = ECOLOGIC

Nominal Cooling Capacity-MBH

012 = 1 Ton018 = 1.5 Ton024 = 2 Ton Voltage036 = 3 Ton 25 = 230-3-60060 = Ton 38 = 380-3-60

46 = 460-3-6050 = 575-3-60

Airflow OptionsA = Stándard

Motor

Page 4: ECCLA036A25 46E

MODELECCLA012 ECCLA018 ECCLA024 ECCLA036 ECCLA060

1 Ton 1.5 ton 2 ton 3 ton 5 ton

Unit Supply Voltage 208-230v,1ø, 60Hz

Normal Voltage Range¹ 187 to 252

Minimum Circuit Ampacity 9.08 9.08 12.4 17.9 34.3

Max. Overcurrent Device Amps² 15 15 20 30 60

Min. Overcurrent Device Amps³ 15 15 15 20 35

Compressor Type Rotary Recip Recip Recip Recip

Compressor AmpsRated Load 7.4 7.4 9.3 13.1 26.2

Locked Rotor 40 40 43 74 150

Crankcase Heater No No No No No

Fan Motor Amps Rated Load 0.5 0.5 0.8 1.5 1.5

Fan Diameter Inches 17.5 17.5 17.5 22 24

Fan Motor

Rated HP 1/12 1/12 1/8 1/4 1/4

Nominal RPM 1100 1100 1075 850 850

Nominal CFM 1400 1400 1950 3200 3600

Coil

Face Area Sq. Ft. 9.6 9.6 9.6 13.07 18.68

Rows Deep 1 1 1 1 1

Fin / Inches 23 23 23 23 23

Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8

Vapor Liner Set OD (Field Installed) 5/8 5/8 3/4 3/4 7/8

Unit Charger (Lbs.-Oz.)⁴ 3-3 3-3 3-13 4-9 5-6

Charger Pear Foot, Oz. 0.58 0.58 0.62 0.62 0.67

Operating Weight Lbs. 97 97 129 145 195

1 PHASE ELECTRICAL TABLE

Page 5: ECCLA036A25 46E

MODELECCLA036 ECCLA060 ECCLA036 ECCLA060

3 ton 5 ton 3 ton 5 ton

Unit Supply Voltage 208-230v,1ø, 60Hz 460V,3ø,60 Hz

Normal Voltage Range¹ 187 to 252 432 to 532

Minimum Circuit Ampacity 12.3 23.9 7.1 13.5

Max. Overcurrent Device Amps² 20 40 15 20

Min. Overcurrent Device Amps³ 15 15 15 15

Compressor Type Recip Scroll Recip Scroll

Compressor AmpsRated Load 8.6 17.9 4.5 9.6

Locked Rotor 68 120 34 70

Crankcase Heater No No No No

Fan Motor Amps Rated Load 1.5 1.5 1.5 1.5

Fan Diameter Inches 22 22 22 22

Fan Motor

Rated HP 1/4 1/4 1/4 1/4

Nominal RPM 850 850 850 850

Nominal CFM 3200 3600 3200 3600

Coil

Face Area Sq. Ft. 13.07 18.68 13.07 18.68

Rows Deep 1 1 1 1

Fin / Inches 23 1 1 1

Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8

Vapor Liner Set OD (Field Installed) 3/4 7/8 3/4 7/8

Unit Charger (Lbs.-Oz.)⁴ 4-9 5-6 4-9 5-6

Charger Pear Foot, Oz. 0.62 0.67 0.62 0.67

Operating Weight Lbs. 145 195 145 195

3 PHASE ELECTRICAL TABLE

Page 6: ECCLA036A25 46E

MODEL ECCLP012 ECCLP018 ECCLP024 ECCLP036 ECCLP060

CAPACITY TONS 1 1.5 2 3 5

VOLTS 230/3/6 230/3/6 230/3/6 230/3/6 230/3/6

460/3/6 460/3/6 460/3/6 460/3/6 460/3/6

PUMP HP 2 / 1HP 2 / 1HP 2 / 1HP 2 / 1HP 2 / 1HP

GPM 2.4 3.6 4.8 7.2 12

IN / OUT WATER PIPE (Inches) 1'' 1'' 1'' 1'' 1''

TANK LTS 50 Lts 50 Lts 50 Lts 50 Lts 50 Lts

TANK DIMENTIONS (Mts)

HIGH 0.64 0.64 0.64 0.64 0.64

WIDE 0.65 0.65 0.65 0.65 0.65

LONG 0.91 0.91 0.91 0.91 0.91

WEIGHT (Lbs) 286.59 286.59 286.59 286.59 286.59

VOLUMEN M3 0.37 0.37 0.37 0.37 0.37CHILLER DIMENTIONS

(Inches)

HIGH 28'' 28'' 28'' 28'' 32

WIDE 23-1/2'' 23-1/2'' 23-1/2'' 29'' 33-5/8''

LONG 23-1/2'' 23-1/2'' 23-1/2'' 29'' 33-5/8''

OPERATING WEIGHT (Lbs) 97 97 129 145 195

VOLUMEN M3 .24 .24 .24 .37 .59

PHYSICAL PROCESS TABLE

Page 7: ECCLA036A25 46E
Page 8: ECCLA036A25 46E
Page 9: ECCLA036A25 46E
Page 10: ECCLA036A25 46E
Page 11: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 1 of 2

Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant

ECCLA036A06 1 ECCLA036A06 3 220/1/60 R410A Pin No: ECCLA036A06

Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) 0.6

Electrical Data Circuit 1 2 3 4

Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5

Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)

20

Min. Dual Element Fuse Size (Amps)

20

Max. Dual Element Fuse Size (Amps)

30

Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 8 Total Amps 15.6 Operating Condition Electrical

Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW 0.18 Total kW 2.64

Notes:

RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]

Page 12: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 2 of 2

Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0

75 86.3 50 80.6 13.2 / 3.9 25 66.9

SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLA036A06 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K LWA

100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLA036A06 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K dBA

100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0

** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases

Page 13: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision: 2.0 Performance Page 1 of 2

Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant

ECCLA036A25 1 ECCLA036A25 3 220/3/60 R410A Pin No: ECCLA036A25

Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) 0.6

Electrical Data Circuit 1 2 3 4

Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5

Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)

20

Min. Dual Element Fuse Size (Amps)

20

Max. Dual Element Fuse Size (Amps)

30

Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 12 Total Amps 15.6 Operating Condition Electrical

Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW .18 Total kW 2.64

Notes:

RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]

Page 14: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision: 2.0 Performance Page 2 of 2

Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0

75 86.3 50 80.6 13.2 / 3.9 25 66.9

SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLA036A25 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K LWA

100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLA036A25 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K dBA

100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0

** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases

Page 15: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 1 of 2

Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant

ECCLA036A46 1 ECCLA036A46 3 460/3/60 R410A Pin No: ECCLA036A46

Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) 0.6

Electrical Data Circuit 1 3 4

Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5

Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)

20

Min. Dual Element Fuse Size (Amps)

20

Max. Dual Element Fuse Size (Amps)

30

Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 14 Total Amps 15.6 Operating Condition Electrical

Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW .18 Total kW 2.64

Notes:

RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]

Page 16: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 2 of 2

Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0

75 86.3 50 80.6 13.2 / 3.9 25 66.9

SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLA036A46 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K LWA

100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLA036A46 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K dBA

100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0

** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases

Page 17: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 1 of 2

Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant

ECCLP036A06 1 ECCLP036A06 3 220/1/60 R410A Pin No: ECCLP036A06

Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) 0.6

Electrical Data Circuit 1 2 3 4

Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5

Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)

20

Min. Dual Element Fuse Size (Amps)

20

Max. Dual Element Fuse Size (Amps)

30

Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 8 Total Amps 15.6 Operating Condition Electrical

Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW .18 Total kW 2.64

Notes:

RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]

Page 18: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 2 of 2

Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0

75 86.3 50 80.6 13.2 / 3.9 25 66.9

SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLP036A06 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K LWA

100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLP036A06 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K dBA

100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0

** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases

Page 19: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 1 of 2

Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant

ECCLP036A25 1 ECCLP036A25 3 220/3/60 R410A Pin No: ECCLP036A25

Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) 0.6

Electrical Data Circuit 1 2 3 4

Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5

Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)

20

Min. Dual Element Fuse Size (Amps)

20

Max. Dual Element Fuse Size (Amps)

30

Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 12 Total Amps 15.6 Operating Condition Electrical

Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW .18 Total kW 2.64

Notes:

RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]

Page 20: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 2 of 2

Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0

75 86.3 50 80.6 13.2 / 3.9 25 66.9

SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLP036A25 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K LWA

100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLP036A25 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K dBA

100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0

** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases

Page 21: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 1 of 2

Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant

ECCLP036A46 1 ECCLP036A46 3 460/3/60 R410A Pin No: ECCLP036A46

Evaporator Data Condenser Data Performance Data EWT (°F) 55.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6 LWT (°F) 45.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8 Design Flow Rate (gpm) 7.2 Water 100% Physical Data Pressure Drop (ft.) 10 Rigging Wt. (lbs.) 225 Fluid Water Operating Wt. (lbs.) 335 Fouling Factor .00010 Water Volume. (gal) .6

Electrical Data Circuit 1 2 3 4

Compressor RLA 14.1 Compressor Start Current (LRA) 77 Fan QTY/FLA (each) 1/1.5

Single Point Min. Circuit Ampacity 19.1 Min. Non-Fused Disconnect (Amps)

20

Min. Dual Element Fuse Size (Amps)

20

Max. Dual Element Fuse Size (Amps)

30

Min. Circuit Breaker (Amps) 30 Max. Circuit Breaker (Amps) 30 Wire Lugs Per Phase* 1 Wire Range (Lug Size) 14 Total Amps 15.6 Operating Condition Electrical

Data Inrush (PW) Amps 10 Compressor kW 2.46 Starter Type Across the Line Total Fan kW 0.18 Total kW 2.64

Notes:

RATED IN ACCORDANCE WITH ARI STANDARD 550/590. * Use Copper Conductors only **CALCS do not include pump motors, all the information is subject to change whit out notice, If you need specific calcs, please call a representative or email to [email protected]

Page 22: ECCLA036A25 46E

AIR COOLED SCROLL CHILLER PERFOMANCE SERIES A, B

Project Name: Sold To: Location: Customer Purchase Order No.: Engineer: Contract No.: Contractor: Date: MAY 2011 Revision : 2.0 Performance Page 2 of 2

Part Load Rating Data Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency* 100.0 95.0 3 2.46 10.3 / 3.0

75 86.3 50 80.6 13.2 / 3.9 25 66.9

SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz ECCLP036A46 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K LWA

100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0 77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0 67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0 44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0 22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) ** ECCLP036A46 ( Equipped with Low Sound Fans )

Load % Ambient (°F)

63 125 250 500 1K 2K 4K 8K dBA

100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0 77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0 67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0 44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0 22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0

** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation) • *Chillers capacity and performance may vary according to specifications releases

Page 23: ECCLA036A25 46E

Dwg. Scale : NTSDwg. Lev.: 08/04

For: Contractor: Engineer:

TAG:

Date:JUNE2011 Rev.: 2.0 Form: 190.54-E1S

Sold To: Cust Purch Order#: Contract#: UNIT

INSTALLATION REQUERIMENTS

AIR-COOLED SCROLL CHILLER SYSTEM

PRODUCT DRAWING Location: Project Name:

MODEL ECCLA036A25E / A46E