EC2-711 Condenser Controller
-
Upload
maria-daza -
Category
Documents
-
view
220 -
download
0
Transcript of EC2-711 Condenser Controller
-
7/28/2019 EC2-711 Condenser Controller
1/4
EC2-711_65107_EN_R01.doc Rev.: 01Replacement for Rev.: 00 1 / 4 21.06.2007
EC2-711 Condenser ControllerOperating Instructions
GB
Contents:
Safety instructions: 1
Technical data: 1
Mounting 1Electrical Installation 1
Set-up and Parameter Modification
using the Keypad 1
Display Of Data: 2
Load Default Parameters: 2
Special Functions 2Alarm Codes and Messages 2
Parameter List 3
Visualising Data: LON Monitoring 4
Note: This document contains short form instructions for experienced users.Use last column in List of Parameters to document your individual settings.
More detailed information can be found in the User Manual.
The EC2-711 has been designed to control condensers with up to four fans. The
purpose of the controller is to keep condensing pressure to a minimum by
switching fans on or off.
The PT4 pressure transmitter (5) senses condensing pressure and feeds the signal
into a condensing pressure dead band control loop. Condensing pressure ismodulated by turning fan motors on and off.
No change occurs as long as the condensing pressure remains within the dead band
(P1) around the condensing pressure setpoint (P0). The controller will add/removefan capacity when the condensing pressure goes beyond the limits of the
condensing pressure dead band. For stable condenser operation, adjustable timedelays for fan motor on and off are available. To avoid premature wear of
individual fan motors, run time equalization is built into the controller.
remove capacity dead band add capacity
Condensing Pressure
A fast recovery procedure can be used to immediately switch off all fans when thecondensing pressure falls below a set limit. Similarly an emergency routine can be
activated automatically if the condensing pressure exceeds a definable limit.
! Safety instructions: Read installation instructions thoroughly. Failure to comply can result in
device failure, system damage or personal injury.
The product is intended for use by persons having the appropriateknowledge and skills.
Ensure electrical ratings per technical data are not exceeded. Disconnect all voltages from system before installation. Keep temperatures within nominal limits. Comply with local electrical regulations when wiring
Technical data:
Power supply 24VAC 10%; 50/60 Hz; Class II
Power consumption 4VA max.
Communication LonWorks Interface, FTT10, RJ45 connector
Terminals Removable screw terminals
wire size 0.14 1.5mm2
Temperaturestorage
operating
-20 +65C
0 +60C
Pressure sensor input 24VDC, 4 20mA
Fan output relays SPDT contacts, AgCdO
Inductive (AC15) 250V / 2A
Resistive (AC1) 250V / 6A; 12A total return current
Fan variable output signal 0 10V; (3mA max)
Digital inputs Volt free contacts 5V/0,1mA
Humidity 0 80% rh. non condensing
Protection class IP65 (front protection with gasket)
Mounting
The EC2-711 can be mounted in panels with a 71 x
29 mm cutout. See dimensional drawing below for
space requirements including rear connectors.Push controller into panel cutout.(1)Make sure that mounting clamps are flush with
outside of controller housing
Insert allen key into front panel holes and turnclockwise. Mounting clamp will turn and gradually
move towards panel (2)
Turn allen key until mounting clamp barely touches
panel. Then move other mounting clamp to the sameposition (3)
Tighten both sides very carefully until controller is
secured. Do not over tighten as mounting clampswill break easily.
Electrical Installation
Refer to the electrical wiring diagram(right) for electrical connections. A copy
of this diagram is labelled on the
controller.
Use connection wires/cables suitable for90C operation (EN 60730-1).
EC2 analog inputs are for dedicated
sensors only and should not be connectedto any other devices. Volt free digital
inputs should only be connected to serial
control loops or relays with gold
contacts. They should not be connected
to any other devices
Important: Keep controller and sensor wiring well separated from mains wiring.
Minimum recommended distance 30mm.Warning: Use a class II category transformer for 24VAC power supply
(EN 60742). Do not ground the 24VAC lines. We recommend to use one
transformer per EC2 controller and to use separate transformers for 3rd party
controllers, to avoid possible interference or grounding problems in the power
supply. Connecting any EC2 inputs to mains voltage will permanently damage theEC2.
Set-up and Parameter Modification Using The Keypad
For convenience, an infrared receiver for the optional IR remote control unit is
build-in, enabling quick and easy modification of the system parameters when a
computer interface is not available.Alternatively, the parameters can be accessed via the 4-button keypad. The
configuration parameters are protected by a numerical password. The default
password is 12. To select the parameter configuration:Press the PRG button for more than 5 seconds
A flashing 0 is displayed
Press or until 12 is displayed; (password)
Press SEL to confirm passwordThe first modifiable parameter code is displayed (/1).
To modify parameters see Parameters modification below..
-
7/28/2019 EC2-711 Condenser Controller
2/4
EC2-711_65107_EN_R01.doc Rev.: 01Replacement for Rev.: 00 2 / 4 21.06.2007
EC2-711 Condenser ControllerOperating Instructions
GB
Parameter Modification: Procedure
Press or to show the code of the parameter that has to be changed;
Press SEL to display the selected parameter value;
Press or to increase or decrease the value;
Press SEL to temporarily confirm the new value and display its code;
Repeat the procedure from the beginning "press or to show..."To exit and save the new settings:
Press PRG to confirm the new values and exit the parameters modificationprocedure.
To exit without modifying any parameter:
Do not press any button for at least 60 seconds (TIME OUT).Press ESC on IR remote control.
Load Default Parameters:
The default parameter settings can be reloaded into the controller memory by using
the special function described below
Special Functions:
The Special Functions can be activated by:
Press and together for more than 5 seconds.
A flashing 0 is displayed.
Press or until the password is displayed (default = 12). If password was
changed, select the new password.
Press SEL to confirm passwordA 0 is displayed and the Special Function mode is activated.
Press or to select the function. The number of special functions is dynamic
and controller dependent. See list below.
Press SEL to activate the function without leaving the special function mode.
Press PRG to activate the function and leave the special function mode.
Most of the Special Functions work in a toggle mode, the first call activates thefunction, and the second call deactivates the function.
The indication of the function can only be displayed after exiting the special
function mode.
0: Display test function 1: Resets all parameters to the factory default setting. The controller will
indicate oF during the reset and the valve will close.
Display of Data:
The data to be permanently shown on the display can be selected by the user (parameter/1). In case of an alarm, the alarm code is displayed alternately with the selected data.
The user can inhibit the alarm code.
It is possible to temporarily display these values. This is a useful feature when
initially setting-up the system without the aid of the WebPages. Press the SELbutton to scroll through all possible displayable data.. The display will show for one
second the numerical identifier of the data (see /1 parameter) and then the selected data.
After two minutes the display will return to the by parameter /1 selected data. Thisaction is only valid when parameter H2 = 3.
LON activity LED(only active when service pin is pressed)
Display indicates condenser controller
Display indicates pressure in bar
Alarm condition
Fan 3 on
IR LED Fan 4 on
Fan 2 on Fan 1 on
Indications On The Display:
Condenser fan controller
State Alarm in combination with alarm message and alarm LED Condensing pressure or saturation temperature from condensing pressure ParameterOther display Pressure: Pressure value in bar (g) Alarm: Alarm condition IR: IR communication enabledAlarm Codes
hP High pressure alarmCondensing pressure higher than the maximum limit
lP Low pressure alarmCondensing pressure lower than the minimum limit
EP Error pressureCondensing pressure sensor failure
Fr Fast recovery alarmFast recovery form low condensing pressure
hr High discharge pressure alarmHigh condensing pressure recovery
E1 Feedback alarm 1Digital input associated with fan 1 has changed into alarm state (safety chain)
E2 Feedback alarm 2
Digital input associated with fan 2 has changed into alarm state (safety chain)
E3 Feedback alarm 3Digital input associated with fan 3 has changed into alarm state (safety chain)
E4 Feedback alarm 4
Digital input associated with fan 4 has changed into alarm state (safety chain)
n1 Service alarm 1Fan 1 operating time higher than run limit
n2 Service alarm 2Fan 2 operating time higher than run limit
n3 Service alarm 3Fan 3 operating time higher than run limit
n4 Service alarm 4Fan 4 operating time higher than run limit
Er Data errorData send to the display is out of range
Messages
--- No data to displayThe display will show an --- at node start up and when no data is send to the
display.
In Reset to default values activatedThe display will show an In when the factory default configuration data set
is initialized.
Id Wink request receivedThe display will show a flashing Id when the wink request was received.
The flashing Id will be shown on the display until the service button will bepressed, or a 30 min delay timer will expire or a second wink request is
received.
OFNode is offlineThe node is offline and no application is running. This is the result of a
network management command and will happen for example during node
installation.
-
7/28/2019 EC2-711 Condenser Controller
3/4
EC2-711_65107_EN_R01.doc Rev.: 01Replacement for Rev.: 00 3 / 4 21.06.2007
EC2-711 Condenser ControllerOperating Instructions
GB
Fan controller
/ DISPLAY PARAMETERS Min Max Unit Def Individ.
/1 Value to be shown on display 0 2 - 0
0 = Fan states1 = condensing pressure (bar)
2 = condensing temperature (C)
r SENSOR PARAMETERS
r0 Condensing pressure sensor
minimum value
-1.0 50 bar 0.0
r1 Condensing pressure sensor
maximum value
-1.0 50 bar 30
r2 Pressure offset for condensingpressure
-1.0 1.0 bar 0.0
r3 Refrigerant type 0 5 - 40 = no temperature conversion;
1 = R22; 2 = R134a; 3 = R507; 4 = R404A; 5 = R407C
P SET-POINT PARAMETERS
P0 Pressure set-point (condensing) for
fan circuit
-1.0 50 bar 14.0
P1 Pressure band (dead band for deadband control mode)
0.0 50 bar 4.0
P3 Fast recovery from low pressure -9.9 50.0 bar 9
P4 Enable set-point compensation
0 = disabled; 1 = enabled
0 1 - 0
P5 Maximum pressure compensation -3.0 3.0 bar -3.0
P6 Temperature at minimal shift value
(0)
-50.0 50 C 30
P7 Temperature at maximal shift value
(Shift Max)
-50.0 50 C 15.0
P8 High discharge pressure recovery.Activates sprinkler valve
-9.9 50 bar 20
A ALARM PARAMETERS
A2 Minimum condensing pressurealarm limit -1.0 50 bar 10.0
A3 Maximum condensing pressure
alarm limit
-1.0 50 bar 27
A4(1) Delay time for minimum pressure
alarm limit
0 99 10sec 0
A5(1) Delay time for maximum pressure
alarm limit
0 99 10sec 0
A8(1) Fan serial alarm delay 0 99 10sec 0
A9(2) Fan run limit 0 99 10000hr 0
u STEP ENABLE PARAMETERS Min Max Unit Def Individ.
u0 Reset operating time
0 = do nothing1 = reset operating time fan 1
2 = reset operating time fan 2
3 = reset operating time fan 34 = reset operating time fan 4
5 = reset operating time all fans
0 5 - 0
u1 Enable/disable fan 1 0 1 flag 1
u2 Enable/disable fan 2 0 1 flag 1
u3 Enable/disable fan 3 0 1 flag 1
u4 Enable/disable fan 4 0 1 flag 1
C APPLICATION PARAMETERS
C1 Number of fans 1 4 - 4
C4 Fan 1 (0 = standard control loop
1 = fan 1 act as base load)
0 1 - 0
C5 Fan switch logic (Rotation) 0 1 flag 1
0 = FILO logic (First In, Last Out)Capacity demand: Adds first fan.
Capacity excess: Removes last fan.
1 = Rotation enabledCapacity demand: Adds fan with lowest runtime out of
available fans.Capacity excess: Removes fan with highest runtime out of
available fans.
C6 Number of fans to switch on in case
of sensor failure
0 4 - 0
H OTHER PARAMETERS
H2 Keyboard and IR remote control 0 3 - 3
0 = all disabled(Caution, access to controller only via LON network possible)
1 = Keyboard enabled
2 = IR remote control enabled
3 = Keyboard and IR remote control enabled
H3 IR remote control access code 0 199 - 0H5 Password 0 199 - 12
(1) These values have a resolution of 10 sec,on the local display. Ex. a value 1 means 10 sec.(2) These values have a resolution of 10.000 hours,on the local display. Ex. a value 1 means 10.000 hours.
Note: Concerning the indicated parameters, it is recommended to check, before installing, if the factory value is suitable for the required use
-