Eaton rack PDU guide to plugs and receptacles

2
Rack PDU plugs and receptacles This cheat sheet provides an overview of the different styles of plugs and receptacles for Eaton rackmount PDUs. R indicates receptacle P indicates plug L indicates locking plug or receptacle L6-30R L6-30P L14-30R L14-30P 5-15R 5-15P 5-20R 5-20P L5-20R L5-20P L5-30R L5-30P 6-15R 6-15P L6-20R L6-20P 16A 32A General PDU environment specifications Operating temperature is 0 to 60˚C (32 to 140˚F) Altitude maximum 10,000 ft. Relative humidity is 95% max non-condensing Learn more at Eaton.com/PDU Eaton.com/PDU

Transcript of Eaton rack PDU guide to plugs and receptacles

Rack PDU plugs and receptaclesThis cheat sheet provides an overview of the different styles of plugs and receptacles for Eaton rackmount PDUs.

R indicates receptacle P indicates plug L indicates locking plug or receptacle

L6-30R L6-30P L14-30R L14-30P

5-15R 5-15P 5-20R 5-20P

L5-20R L5-20P L5-30R L5-30P

6-15R 6-15P L6-20R L6-20P

16A 32A

General PDU environment specifications

• Operating temperature is 0 to 60˚C (32 to 140˚F)

• Altitude maximum 10,000 ft.

• Relative humidity is 95% max non-condensing

Learn more at Eaton.com/PDU

Eaton.com/PDU

Eaton1000 Eaton Boulevard Cleveland, OH 44122 United StatesEaton.com

©2021 EatonAll Rights ReservedPrinted in USAPDU37FXA / GGOctober 2021

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

IEC309

332P6250V

30A 60A

360P6250V

30A

532P63ØY230/400V

60A 60A 60A

460P93Ø250V

560P93ØY120/208V

563P63ØY230/400V

50A, 2P3W250V

Y

G

X

Y

X

ZG

HBLCS8265C HBLCS8365C

Y

G

X

Y

X

ZG

50A, 3P4W

3Ø250V

IEC320

C13 C14

North AmericanEurope

20 amp 250 volts16 amp 250 volts

C19 C20

15 amp 250 volts10 amp 250 volts

Standard NEMA plugs

L22-30277/480V30A3 phase wyetwist lock

5-20120V20A1 phasestraight blade

L5-20120V20A1 phasetwist lock

L5-30120V30A 1 phasetwist lock

5-15 120V15A1 phasestraight blade

6-20208V20A1 phasestraight blade

L6-20208V20A1 phase twist lock

L6-30 208V30A, 1 phasetwist lock

L14-30120/240V30A2 phase (split phase)

L21-20 120/208V20A, 3 phase wyetwist lock

L21-30120/208V30A3 phase wyetwist lock

L15-20208V20A3 phase deltatwist lock

L15-30208V30A3 phase deltatwist lock

L22-20277/480V20A3 phase wyetwist lock

Eaton C39 universal outlet:The C39 outlet allows both C14 and C20 plugs to connect into a single outlet. Like its NEMA counterpart the 5-20P, the C39 outlet allows for both 15- and 20-amp inlets. This flexibility allows you to swap out equipment without having the inconvenience of re-ordering a new rack PDU to meet specific outlet count requirements on a per rack basis.