Page 1: East Coast Electric...over all existing outlets feeding vending machines and microwave circuits to eliminate possible overload of circuit. e13. all electrical work to be performed
Page 2: East Coast Electric...over all existing outlets feeding vending machines and microwave circuits to eliminate possible overload of circuit. e13. all electrical work to be performed
Page 3: East Coast Electric...over all existing outlets feeding vending machines and microwave circuits to eliminate possible overload of circuit. e13. all electrical work to be performed
Page 4: East Coast Electric...over all existing outlets feeding vending machines and microwave circuits to eliminate possible overload of circuit. e13. all electrical work to be performed

NOTES FOR TRAILER 33 BREAKROOME1. MODIFY EXISTING RECEPTACLE OUTLETS BY PROVIDING NEW GFCI BREAKERS, BOX EXTENSIONS, ½" EMT, AND 3- # 12 AWG CONDUCTORS WITH THHN INSULATION, HANDY BOX, NEMA 5-20R RECEPTACLE AND RECEPTACLECOVER. INSTALL BOX EXTENSION IN LOCATION SHOWN, RUN ½" EMT FROM BOX EXTENSION, AROUND CORNER OFROOM AND LOCATE RECEPTACLE OUTLET CENTERED BEHIND VENDING MACHINE APPROXIMATELY 18" ABOVEFLOOR AND 18" FROM WALL CORNER. REMOVE RECEPTACLES (2) FROM EXISTING LOCATIONS AND WIRENUTCONNECTIONS TOGETHER. PROVIDE NEW RECEPTACLE AT LOCATION BEHIND VENDING MACHINES ONLY. REMOVEEXISTING BREAKER #25 AND INSTALL NEW GFCI BREAKER. RELOCATE EXISTING CIRCUIT WIRES FROM CIRCUIT # 27TO NEW GFCI BREAKER.

E2. MODIFY EXISTING RECEPTACLE OUTLETS BY PROVIDING NEW GFCI BREAKER, BOX EXTENSION, ½" EMT, AND 3 -# 12 AWG CONDUCTORS WITH THHN INSULATION, HANDY BOX, NEMA 5-20R RECEPTACLE AND RECEPTACLECOVER. INSTALL BOX EXTENSION IN LOCATION SHOWN, RUN ½" EMT FROM BOX EXTENSION, APPROXIMATELY 36"TO NEW RECEPTACLE OUTLET CENTERED ON WALL BEHIND VENDING MACHINE APPROXIMATELY 18" ABOVEFLOOR. REMOVE RECEPTACLES FROM EXISTING OUTLET LOCATIONS AND WIRENUT CONNECTIONS TOGETHER.PROVIDE NEW RECEPTACLE AT LOCATION BEHIND VENDING MACHINE ONLY. REPLACE EXISTING BREAKER #26 WITHNEW GFCI BREAKER AND RECONNECT WIRES AT NEW BREAKER.

E3. PROVIDE NEW DEDICATED RECEPTACLE CIRCUIT FOR REFRIGERATOR OUTLETS (4 EACH). PROVIDE NEW GFCIBREAKERS, 3/4" EMT, 3-# 12 AWG CONDUCTORS WITH THHN INSULATION, NEMA 5-20R RECEPTACLE WITH COVER.MOUNT APPROXIMATELY 18" ABOVE FLOOR AT LOCATIONS SHOWN.

E4. PROVIDE THREE NEW DEDICATED CIRCUITS FOR MICROWAVES. PROVIDE NEW GFCI BREAKERS, 3/4" EMT, AND3- # 12 AWG WIRES WITH THHN INSULATION, HANDY BOX, NEMA 5-20R RECEPTACLE AND RECEPTACLE COVER.MOUNT RECEPTACLES APPROXIMATELY 18" ABOVE FLOOR AT LOCATION SHOWN.

E5. MODIFY EXISTING RECEPTACLE OUTLET BY PROVIDING NEW GFCI, BOX EXTENSION, ½' EMT, 3-# 12 AWG WIRESTYPE THHN INSULATION, HANDY BOX, NEMA 5-20R RECEPTACLE AND RECEPTACLE COVER. MOUNT RECEPTACLEAPPROXIMATELY 18" ABOVE FLOOR AT LOCATIONS SHOWN. REMOVE EXISTING BREAKER #22 AND REPLACE WITHNEW GFCI BREAKER. RECONNECT EXISTING WIRES TO NEW GFCI BREAKER.

E6. ALL CIRCUITS FROM PANEL SHALL BE 20 AMP GFCI BREAKERS, 3-#12 AWG, TYPE THHN INSULATION, NEMA5-20R RECEPTACLE IN ¾" EMT UNLESS NOTED OTHERWISE OR APPROVED BY 6.3.1.

E7. PROVIDE NEW 30 AMP WATER HEATER CIRCUIT WITH 3-#10 AWG CONDUCTORS TYPE THHN INSULATION IN ¾"EMT (1)

E8. PROVIDE AND INSTALL NEW GFCI BREAKER FOR WATER COOLER CIRCUIT #31.

E9. PROVIDE NEW DEDICATED 20 AMP ICE MACHINE CIRCUIT WITH NEW GFCI BEAKER, 3-#12 AWG CONDUCTORSTYPE THHN INSULATION, HANDY BOX, RECEPTACLE AND COVER IN ¾" EMT (1)

E10. EXTEND EXISTING RECEPTACLE CIRCUIT UP FOR WALL MOUNTED TV (2). PROVIDE BOX EXTENSION, EMTCONDUIT, 3-#12 AWG TYPE THHN INSULATION, HANDY BOX, NEMA 5-20R RECEPTACLE AND RECEPTACLE COVERAND EXTEND RECEPTACLE OUTLETS UP TO 66".

E11. DISCONNECT AND REMOVE ALL RECEPTACLE CIRCUITS IN WALLS DESIGNATED TO BE DEMOLISHED ANDRECONNECT ANY CONTINUATION OF CIRCUITRY NECESSARY TO MAINTAIN POWER TO REMAINING RECEPTACLES.

E12. REMOVE EXISTING RECEPTACLES, IN ALL E1, E2 AND E5 NOTED AREAS, AND PROVIDE BLANK BOX COVERS (8)OVER ALL EXISTING OUTLETS FEEDING VENDING MACHINES AND MICROWAVE CIRCUITS TO ELIMINATE POSSIBLEOVERLOAD OF CIRCUIT.

E13. ALL ELECTRICAL WORK TO BE PERFORMED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE, NFPA 70, 2014AND STANDARD FOR ELECTRICAL SAFETY, NFPA 70E, 2013.

E14. PANEL IS SQUARE D WITH TYPE HOM BREAKERS.

E15. ALL BREAKERS PROVIDED FOR RECEPTACLES ON REFRIGERATORS, VENDING MACHINES, MICROWAVES ANDWATER FOUNTAIN, SHALL BE 20 AMP GFCI RATED.

E16. LABEL COVER PLATES ON RECEPTACLES WITH P-TOUCH, OR EQUIVALENT, LABELS INDICATING CIRCUITNUMBER AND SOURCE OF POWER.

E17. RE-IDENTIFY ALL CIRCUIT BREAKERS IN PANEL TO MATCH EXISTING CIRCUIT RECEPTACLES AND LIGHT CIRCUITSAND NEW CIRCUIT MODIFICATIONS. PROVIDE NEW PANEL SCHEDULE TO ACCURATELY IDENTIFY CIRCUITS INCORRECT LOCATIONS.

EXISTING - TRAILER 33 PLAN VIEWSCALE: 1

4" = 1'-0