LARSEN & TOUBRO LIMITEDELECTRICAL DIVISION, H.Q., CHENNAI
PROJECT REF. NO. PAGE :
Relocation of Riyam Substation and Transformer
Repair Workshop PREPARED CHECKED APPROVED DATE
TITLE
EARTHING CALCULATIONS SSJ AKR AKS 22-Feb-16
INPUT DATA
1 Soil resistivity = 26 Ohm.m2 Type of conductor used = Copper Flat 3 Length of Grid buried in ground L = 275 m4 Depth of burial of electrode w = 0.5 m5 Length of Rod or Pipe l = 3.5 m6 Dia of Rod or Pipe d = 0.016 m7 No. of Electrodes n = 148 Distance between adjacent rods s = 7 m9 P(Ref: Table 5 BS 7430:1991) = 2
10 Q(Ref: Table 5 BS 7430:1991) = -1.3
CALCULATIONS
8lA Resistance of one vertical Electrode R = ------------ LOGe -------- - 1
2*phi*l d= 7.650 ohms
Net resistance of Electrodes Re = Rr/n
= 0.546443675 ohms
B Resistance of horizontal Buried Rh = ------------ x LOGe ----------
Earth grid P x Phi x L w *d= 0.278 ohms
R x RhC Net Resistance R = -------------
R + Rh= 0.184 ohms
RESULT
Since the total Resistance is less than 1 ohm, earthing for this area is SAFE.
2*L2
-----+ Q2
CONSTRUCTION GROUP
2 OF 2
305260211.xls.xls
LARSEN & TOUBRO LIMITEDELECTRICAL DIVISION, H.Q., CHENNAI
PROJECT REF. NO. PAGE :
Relocation of Riyam Substation and Transformer
Repair Workshop PREPARED CHECKED APPROVED DATE
TITLE
EARTHING CALCULATIONS SSJ AKR AKS 22-Feb-16