Earth Tester

22
PRECIOHM ET – EARTH TESTER Taurus Powertronics – Training

description

earth tester ppt

Transcript of Earth Tester

Page 1: Earth Tester

PRECIOHM ET – EARTH TESTER

Taurus Powertronics – Training

Page 2: Earth Tester

Taurus Earth Tester

1/3/2011Taurus Confidential Document

Page 3: Earth Tester

Earth Tester

04/10/2023Taurus Confidential Document

Current Terminal

Potential Terminal-P1

Potential Terminal-P2

Earth Terminal

Range Selector

RS 232 Port

Mains Switch

Power ON

Memory

Battery Indication

Reset Set Print

Page 4: Earth Tester

Salient Features

Fall-Potential method of Earth Resistance Wenner method for Soil Resistivity measurementHigh dynamic measurement range of 0.01Ω to

20kΩDigital display in Ω with accuracy of ±2%Complete suppression of induction and leakage

power frequencies & its harmonics.Modular with in-built rechargeable batteryAvailable in models of 0–2kΩ & 0-20kΩCompact, portable, AC mains & battery operatedHoused in IP67 pelican casing

1/3/2011Taurus Confidential Document

Page 5: Earth Tester

SOIL RESISTIVITY

1/3/2011Taurus Confidential Document

Page 6: Earth Tester

Factors to be considered

Temperature

Humidity

Type of Soil

Strata of the Soil

Depth of Peg insertion

1/3/2011Taurus Confidential Document

Page 7: Earth Tester

Principle of Operation– Soil Resistivity

1/3/2011Taurus Confidential Document

Wenner 4 Pole Method

a a ab

V

I

ρ = 2πa

ΔvI

ρ = 2πaR

ρ = Resistivity (Ω-m) a = Probe Spacing (m)Δv = Voltage Measured

(volts) I = Injected current (Amps) R = Measured resistance

(Ω)

a = 10*b

Page 8: Earth Tester

Principle of Operation

Soil Resistivity Measurement: Four pole - Wenner Method A constant current with low frequency (128Hz) is

passed to current terminal The voltage across potential terminals P1& P2 is

measured Soil Resistivity is calculated using formula ρ = 2пaR

1/3/2011Taurus Confidential Document

Page 9: Earth Tester

Schematic Diagram

1/3/2011Taurus Confidential Document

Wenner 4 Pole Method for Soil Resistivity Measurement

a a ab

a = 10*b

P2P1E C

Page 10: Earth Tester

Operating Procedure

Soil Resistivity Measurement Install four terminals in the ground equally spaced

in a straight line Using the connecting cables, connect the E, P1,

P2 and C terminals to the corresponding electrodes.

Press the SET button and read the digital display. Record the reading at the appropriate location Using the obtained R-value, calculate the value of

resistivity (ρ), which is represented by the units of Ω-m (Ohm-Meter)

1/3/2011Taurus Confidential Document

Page 11: Earth Tester

Soil Resistivity Measurement Testing Layout

1/3/2011Taurus Confidential Document

a a ab

P2P1E

EP

1P

2

C

C

a

a

a

b

P2

P1

E

C

Building A Soil Resistivity Profile

A minimum of 3 direction of testing

Property line

ρx

ρy ρz

ρx + ρy + ρz 3

ρ =

Page 12: Earth Tester

SUB STATION EARTH MEASUREMENT

1/3/2011Taurus Confidential Document

Page 13: Earth Tester

Principle of Operation—Earth Resistance

1/3/2011Taurus Confidential Document

Distance of potential probe in meters

Ground Electrode Potential

probe (P) Current probe (C)

Current probe resistance

Ground probe resistance 61.8%

CXRes

ista

nce

in

ohm

s

Three pole -Fall Potential Method

Page 14: Earth Tester

Principle of Operation

Earth Resistance Measurement: Three pole -Fall Potential Method A constant current with low frequency (128Hz) is

passed to current terminal The voltage across potential terminal P1& earth

terminal measured The resistance is calculated using formula R =

1/3/2011Taurus Confidential Document

VI

Page 15: Earth Tester

Schematic Diagram

1/3/2011Taurus Confidential Document

d

3 Pole Method for Earth Resistance Measurement

d

h < 5% * d

h

Substation Earth Pit P2 C

Page 16: Earth Tester

Operating Procedure

Earth Resistance Measurement Connect equipment earth terminal to the station

earth pit Potential terminal to centre peg at distance 30m

from the earth pit Current terminal to current peg at distance 60m

from the earth pit The depth of penetration is less than 5% of the

distance between the pegs All the pegs are connected in straight line

1/3/2011Taurus Confidential Document

Page 17: Earth Tester

Case Study

1/3/2011Taurus Confidential Document

Page 18: Earth Tester

Case Study – PGCIL-NR ІІ

Place: Sonepat (PGCIL -NR ІІ)Date: 11/12/2010Substation: 400/220 kV S/s Powergrid,

MohanaContact Person: Mr. Shrivastava, Manager

Mr. Anil Kumar, DT Customer Requirements

Repeatability of the values & Heavy duty battery

Readings

1/3/2011Taurus Confidential Document

Earth Pit Resistance R 0.90 Ohms

Soil Resistivity 5.1 Ohm-meter

Page 19: Earth Tester

Case Study – PGCIL-NR ІІ

Place: Nalagarh (PGCIL -NR ІІ)Date: 13/12/2010Substation: 400/220 kV S/s Power Grid,

ReruContact Person: Mr. Manish Gandotara,

Manager Mr. Vikram Sarochaya,

Engineer Readings

1/3/2011Taurus Confidential Document

Earth Pit Resistance R=(Pit connected to grid)

0.60 Ohms

R= ( Individual earth Pit) 36.5 Ohms

Soil Resistivity 16.48 Ohm-meter

Page 20: Earth Tester

Case Study – PGCIL-NR ІІ

Place: Banala (PGCIL -NR ІІ)Date: 14/12/2010Substation: 400/220 kV S/s PowerGrid,

JhiriContact Person: Mr. Amit Kumar,

Sr.Engineer Mr. Pravesh Kaundal,

EngineerReadings

1/3/2011Taurus Confidential Document

Distance ‘A’meters

Resistance ‘R’ Ohms

ResistivityOhm-meters

Location A 5 6.55 205.67

Location B 4 25.5 640.56

Location C 4 24.5 615.44

Page 21: Earth Tester

Case Study – PGCIL-NR ІІ

Place: Chamba (PGCIL -NR ІІ)Date: 16/12/2010Substation: 400/220 kV S/s Power Grid,

Sultanpur

Contact Person: Mr. Manish Sharma, Chief Manager

Mr. Mahendra Kaloria, Engineer

Readings

1/3/2011Taurus Confidential Document

Earth Pit Resistance R=

2.5 Ohms

Soil Resistivity 138 Ohm-meter

Page 22: Earth Tester

Q & A

1/3/2011Taurus Confidential Document