E1 · 5/31/2016 10:34:57 am project number: 09.011 ... hv high voltage hz hertz ic ... mfs main...

6
architecture studio architecture 327 pricketts fort road fairmont, wv 26554 ph: 304.292.7750 PO Box 360 mchenry, maryland 21541 ph: 301.387.3380 fx: 301.387.3382 PROJECTdata Project Address Client Signature for Phase Completion Schematic Design Design Development Progress Bidding Building Permit Construction Documents 5/31/2016 10:34:57 AM Project Number: 09.011 16.016 WMHS - Chapman-Jackson/Plastics office 12500 Willowbrook Road Cumberland, MD 21502 FILENAME: P:\2016\1617510\BIM\ E1.DWG LAST SAVED BY: ( BAYRES) PLOTTED BY: ( CSCHARDT) ON Jul 11, 2016 - 3:18pm LWA PROJECT NO: 16-175-10 21493 02/08/17 E1 ELECTRICAL LEGEND, CONVENTIONS, AND ABBREVIATIONS NOT ALL SYMBOLS APPLY TO THIS PROJECT AND ABBREVIATIONS NOTE: BATTERY POWERED EMERGENCY LIGHTING UNIT (MULTIPLE HEADS) WALL MOUNTED FLUORESCENT LIGHTING FIXTURE 2'x4' FLUORESCENT LIGHTING FIXTURE SPRINKLER SYSTEM PREACTION VALVE FIRE ALARM SYSTEM SPRINKLER VALVE SUPERVISORY (TAMPER) SWITCH FIRE ALARM SYSTEM FLAME DETECTOR VARIABLE SPEED SWITCH FIRE ALARM SYSTEM MANUAL PULL STATION TELEPHONE TERMINAL BACKBOARD JUNCTION BOX GROUND FAULT INTERRUPTER TYPE RECEPTACLE SPECIAL RECEPTACLE, FLOOR MOUNTED DUPLEX RECEPTACLE MOUNTED 8" ABOVE COUNTER SINGLE RECEPTACLE SINGLE RECEPTACLE, FLOOR MOUNTED LIGHTNING PROTECTION AIR TERMINAL MANUAL MOTOR STARTER (WITH OVERLOAD PROTECTION) LOW VOLTAGE MOMENTARY CONTROL SWITCH SWITCH WITH PILOT LIGHT NURSE CALL DOME LIGHT, WALL MOUNTED NURSE CALL CODE BLUE EMERGENCY STATION INTERCOM STATION, SINGLE CALL SPEAKER (CEILING MOUNTED, WALL MOUNTED) NURSE CALL DUTY STATION NURSE CALL STAFF STATION NURSE CALL MASTER CONTROL STATION NURSE CALL EMERGENCY STATION (PUSH BUTTON ONLY) NURSE CALL EMERGENCY STATION (WITH PULL CORD) NURSE CALL PATIENT STATION FIRE ALARM SYSTEM REMOTE ANNUNCIATOR PANEL FIRE ALARM SYSTEM SPRINKLER FLOW ALARM SWITCH FIRE ALARM SYSTEM HEAT DETECTOR FIRE ALARM SYSTEM SMOKE DETECTOR FIRE ALARM SYSTEM DUCT-TYPE SMOKE DETECTOR FIRE ALARM SYSTEM BELL FIRE ALARM SYSTEM CONTROL PANEL EMERGENCY CIRCUIT DUPLEX RECEPTACLE JUNCTION BOX, WALL MOUNTED SPECIAL RECEPTACLE, REFER TO SCHEDULE DUPLEX RECEPTACLE, SPLIT WIRED DOUBLE DUPLEX RECEPTACLE DUPLEX RECEPTACLE, FLOOR MOUNTED DUPLEX RECEPTACLE TIMER SWITCH (MANUAL) WEATHERPROOF SWITCH KEY OPERATED SWITCH DIMMER SWITCH FOUR WAY SWITCH THREE WAY SWITCH DOUBLE POLE SWITCH SINGLE POLE SWITCH GROUND CONNECTION GROUND ROD POLE MOUNTED SITE LIGHT EXIT SIGN, CEILING MOUNTED, WITH DIRECTIONAL ARROWS AS INDICATED INDUSTRIAL TYPE FLUORESCENT LIGHTING FIXTURE FLUORESCENT LIGHTING FIXTURE ON EMERGENCY AND NORMAL CIRCUIT 2'x2' FLUORESCENT LIGHTING FIXTURE LIGHTING FIXTURE ON EMERGENCY CIRCUIT WALL MOUNTED LIGHTING FIXTURE DOWNLIGHT WALLWASH LIGHTING FIXTURE VOLUME CONTROL SWITCH TELEPHONE OUTLET DATA/COMMUNICATIONS OUTLET DRY TYPE TRANSFORMER (REFER TO SCHEDULE) PANELBOARD 208Y/120 VOLTS (SURFACE MOUNTED, RECESSED) PANELBOARD 240 VOLTS (SURFACE MOUNTED, RECESSED) PANELBOARD 480Y/277 VOLTS (SURFACE MOUNTED, RECESSED) ELECTRIC HEAT TRACED PIPING DOWNLIGHT LIGHTING FIXTURE STRIP FLUORESCENT LIGHTING FIXTURE (BARE LAMP) FLUORESCENT LIGHTING FIXTURE CONNECTED AS NIGHT LIGHT (UNSWITCHED) MULTI-OUTLET ASSEMBLY WITH RECEPTACLES 18" ON CENTER DATA/COMMUNICATIONS OUTLET, FLOOR MOUNTED TELEPHONE OUTLET, FLOOR MOUNTED FEEDER NUMBER (REFER TO SCHEDULE) NURSE CALL DOME LIGHT, CEILING MOUNTED INTERCOM STATION, MASTER FIRE ALARM SYSTEM MAGNETIC DOOR HOLDER FIRE ALARM SYSTEM CHIME UNIT HEATER TELEVISION OUTLET (REFER TO DETAIL) PASSIVE INFRARED MOTION DETECTOR MAGNETIC DOOR CONTACTS PHOTOCELL SECURITY CAMERA DUPLEX RECEPTACLE WITH WEATHERPROOF COVER EMERGENCY VOICE/ALARM SPEAKER, WALL MOUNTED EMERGENCY VOICE/ALARM SPEAKER, CEILING MOUNTED FIRE ALARM SYSTEM SMOKE DETECTOR INITIATES ELEVATOR RECALL FIRE ALARM SYSTEM HEAT DETECTOR INITIATES ELEVATOR SHUTDOWN FIRE ALARM SYSTEM DUCT-TYPE SMOKE DETECTOR INITIATES FAN SHUTDOWN SMOKE DAMPER PROVIDED UNDER MECHANICAL FOR CONNECTION UNDER ELECTRICAL SECURITY MAGNETIC DOOR LOCK WITH FIRE ALARM SYSTEM RELEASE EMERGENCY CIRCUIT RECEPTACLE FOR SERVICE TO MONITOR 1'x4' FLUORESCENT LIGHTING FIXTURE INDUSTRIAL TYPE FLUORESCENT LIGHTING FIXTURE ON EMERGENCY CIRCUIT FLUORESCENT LIGHTING FIXTURE ON EMERGENCY CIRCUIT WALL MOUNTED FLUORESCENT LIGHTING FIXTURE ON EMERGENCY CIRCUIT EXIT SIGN, WALL MOUNTED, WITH DIRECTIONAL ARROWS AS INDICATED REMOTE EMERGENCY LIGHTING UNIT (MULTIPLE HEADS) MONITOR OUTLET FAX OUTLET TELEPHONE OUTLET, WALL MOUNTED DATA/COMMUNICATIONS OUTLET, MOUNTED 8" ABOVE COUNTER ABBREVIATIONS 48" 48" 48" 48" 48" 48" 48" 48" 48" 48" 48" 48" 18" 18" 18" 18" 18" 18" 18" 18" 18" 18" 54" 48" 84" FEEDER TYPE BUSWAY PLUG-IN TYPE BUSWAY M.H. SYNCHRONIZED CLOCK 90" 54" 48" 18" 54" 54" 48" 48" 54" 54" FLUORESCENT LIGHTING FIXTURE WITH (2) BALLASTS FOR DUAL SWITCHING UNLESS INDICATED OTHERWISE LINEWEIGHT INDICATES EXISTING TO REMAIN, ELECTRICAL EQUIPMENT DENOTED BY LIGHT, SOLID ELECTRICAL EQUIPMENT DENOTED BY HEAVY, SOLID LINEWEIGHT SHALL BE NEW WORK PROVIDED BY CONTRACTOR EMERGENCY CIRCUIT DOUBLE DUPLEX (QUAD) RECEPTACLE EMERGENCY CIRCUIT DUPLEX RECEPTACLE MOUNTED 8" ABOVE COUNTER EMERGENCY CIRCUIT DOUBLE DUPLEX (QUAD) RECEPTACLE MOUNTED 8" ABOVE COUNTER FLUORESCENT LIGHTING FIXTURE WITH PARABOLIC LOUVER CARD READER FACP 2 3 4 D K P WP LV T VS M V a b L N 18" GFI S M DOUBLE DUPLEX RECEPTACLE MOUNTED 8" ABOVE COUNTER A C J J WALL-MOUNTED NIGHT LIGHT FIXTURE NL 18" 18" WP SINGLE RECEPTACLE CLOCK HANGER OUTLET TAMPER RESISTANT RECEPTACLE C TR 18" HARDWIRE CONNECTION TO ELECTRIFIED FURNITURE SYSTEMS J F SYMBOLS DESCRIPTION M.H. H T TV M C P PUSHPLATE SWITCH CR PP 48" 48" M F W C P B E S D E I I M S S , COMBINATION TELEPHONE/DATA OUTLET 18" COMBINATION TELEPHONE/DATA OUTLET, MOUNTED 8" ABOVE COUNTER C TELEPHONE OUTLET, MOUNTED 8" ABOVE COUNTER C COMBINATION TELEPHONE/DATA OUTLET, FLOOR MOUNTED NURSE CALL CONTROL PANEL NURSE CALL STAFF REGISTRY/LOCATOR STATION L 54" NURSE CALL ROOM COMMUNICATIONS BOX N NURSE CALL STAFF LOCATOR ANTENNA, CEILING MOUNTED L NURSE CALL ZONE INDICATOR DOME LIGHT, CEILING MOUNTED Z NURSE CALL/BED COMMUNICATIONS INTERFACE OUTLET TRANSFORMER NEUTRAL GROUND CONNECTION M.H. D S H F DH L B F C S S F F S E H E U DL FIRE ALARM SYSTEM ADDRESSABLE CONTROL MODULE FIRE ALARM SYSTEM ADDRESSABLE MONITOR MODULE FIRE ALARM SYSTEM REMOTE ALARM LIGHT RAL 2 A1 1 CONNECT TO EXISTING 90" 90" T J TELEPHONE/DATA CONNECTIONS TO ELECTRIFIED FURNITURE SYSTEMS NCCP NCS (VERSION 02/12) 48" OCCUPANCY SENSOR SWITCH - PASSIVE INFRARED O 48" OCCUPANCY SENSOR SWITCH - DUAL CONTROL O2 48" AUTOMATIC LIGHTING CONTROL SWITCH A 48" CEILING-MOUNTED INFRARED OCCUPANCY SENSOR CEILING-MOUNTED ULTRASONIC OCCUPANCY SENSOR CEILING-MOUNTED LIGHTING CONTROL RELAY O I O U R LC 48" 15 15 15 15 FIRE ALARM SYSTEM COMBINATION BELL AND FLASHING LIGHT UNIT (SUBSCRIPT = CANDELA RATING) FIRE ALARM SYSTEM COMBINATION HORN AND FLASHING LIGHT UNIT (SUBSCRIPT = CANDELA RATING) FIRE ALARM SYSTEM COMBINATION CHIME AND FLASHING LIGHT UNIT (SUBSCRIPT = CANDELA RATING) 15 FIRE ALARM SYSTEM COMBINATION SPEAKER AND FLASHING LIGHT UNIT (SUBSCRIPT = CANDELA RATING) SMOKE BARRIER SMOKE TIGHT PARTITION 3 HOUR RATED FIRE WALL 2 HOUR RATED FIRE WALL 1 HOUR RATED FIRE WALL DUPLEX RECEPTACLE ON UPS CIRCUIT 18" DOUBLE DUPLEX RECEPTACLE ON UPS CIRCUIT DUPLEX RECEPTACLE ON UPS CIRCUIT MOUNTED 8" ABOVE COUNTER DOUBLE DUPLEX RECEPTACLE ON UPS CIRCUIT MOUNTED 8" ABOVE COUNTER 18" 3 HOUR RATED FIRE WALL SMOKE BARRIER 2 HOUR RATED FIRE WALL SMOKE BARRIER 1 HOUR RATED FIRE WALL SMOKE BARRIER OCCUPANCY SENSOR SWITCH - MULTI-TECHNOLOGY OM 48" FIRE ALARM SYSTEM FLASHING LIGHT, SUBSCRIPT CANDELA RATING MOUNTING HEIGHTS SHALL BE SUCH THAT ENTIRE LENS IS BETWEEN 80" & 96" AFF, SUBSCRIPT INDICATES CANDELA RATING. MOUNTING HEIGHTS SHALL BE ** IDENTICAL IN EACH ROOM. ** 88" 88" ** ** ** ** JUNCTION BOX WITH BLANK COVER PLATE J X DUPLEX RECEPTACLE MOUNTED IN SHELVING/MILLWORK (COORDINATE WITH ARCHITECTURAL ELEVATIONS * * * * * * THRU-WALL NIGHT LIGHT FIXTURE NL NL MANUAL MOTOR SWITCH (NO OVERLOAD PROTECTION) MS 48" AREA OF RESCUE ASSISTANCE STATION ARA PATIENT SERVICES HEADWALL UNIT PS HW * * * THERMOSTAT FOR HEAT TRACING T VFC VARIABLE FREQUENCY CONTROLLER FURNISHED UNDER MECHANICAL FOR INSTALLATION BY ELECTRICAL PTS PNEUMATIC TUBE STATION CONNECTION VAV VAV BOX/AIR TERMINAL UNIT CONNECTION FCU FAN COIL UNIT CONNECTION MGAP CONNECTION TO MEDICAL GAS ALARM PANEL IR CONNECTION TO LOW VOLTAGE INFRARED PLUMBING FIXTURE CONTROL CRU COMPUTER ROOM AIR CONDITIONING UNIT CONNECTION ACCU AIR COOLED CONDENSING UNIT CONNECTION WSHP WATER SOURCE HEAT PUMP CONNECTION C2T 24VAC CONTROL POWER TRANSFORMER FOR ATC USE INDICATES CIRCUIT DESIGNATION RAP FIRE ALARM REMOTE (BOOSTER) POWER SUPPLY RPS SWITCH WITH ILLUMINATED HANDLE I SECURE KEY BOX (KNOX BOX) W/ FIRE ALARM TAMPER SWITCH 18" 48" , , , S L C L H L B L ELECTRICAL LEGEND SYMBOLS DESCRIPTION INDICATES SPACE OR POLE NUMBER BRANCH CIRCUIT HOMERUN TO PANELBOARD, SWITCHBOARD, MCC PANELBOARD DESIGNATION INDICATES PHASE, SWITCHED, AND TRAVELER CONDUCTORS (IF NOT SHOWN, PROVIDE 2#12 AWG & 1#12 GROUND) A E-3 C E-5 LIGHTING FIXTURE TYPE (REFER TO SCHEDULE) LIGHTING FIXTURE INDICATES SWITCH DESIGNATION INDICATES NUMBER OF SWITCHES IN GROUP LIGHTING TOGGLE SWITCH DENOTES SWITCH DESIGNATION DUPLEX RECEPTACLE INDICATES CIRCUIT DESIGNATION ELECTRICAL EQUIPMENT DENOTED BY DASHED, HEAVY LINEWEIGHT SHALL BE DISPOSED OF, UNLESS INDICATED TO BE REUSED OR TURNED OVER TO THE OWNER SECTION DESIGNATION - LETTER DENOTES SECTION IDENTIFICATION INDICATES DRAWING NUMBER WHERE SECTION IS DRAWN DETAIL DESIGNATION - LETTER DENOTES DETAIL IDENTIFICATION INDICATES DRAWING NUMBER WHERE DETAIL IS DRAWN DRAWING NOTE GENERAL NOTE - APPLIES TO ALL SHEETS WITHIN THE ELECTRICAL DRAWING SET CONVENTIONS SB S 3H 2H 1H 3HSB 2HSB 1HSB A AMPS OR AMPERE AC ALTERNATING CURRENT ACU AIR CONDITIONING UNIT AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AHU AIR HANDLING UNIT AIC AMPERES INTERRUPTING CAPACITY ATC AUTOMATIC TEMPERATURE CONTROL ATS AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GAUGE BAS BUILDING AUTOMATION SYSTEM C CONDUIT CB CIRCUIT BREAKER CKT CIRCUIT CLG CEILING CPT CONTROL POWER TRANSFORMER CT CURRENT TRANSFORMER CUH CABINET UNIT HEATER DC DIRECT CURRENT DISC DISCONNECT DN DOWN DO DRAW OUT DP DISTRIBUTION PANEL DWG DRAWING EA EACH EC EMPTY CONDUIT ECB ENCLOSED CIRCUIT BREAKER EF EXHAUST FAN EGS EMERGENCY GENERATOR SET EMH ELECTRICAL MANHOLE EMS EMERGENCY MANAGEMENT SYSTEM EMT ELECTRICAL METALLIC TUBING ETR EXISTING TO REMAIN EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER EX. EXISTING EXH EXHAUST F FUSE FACP FIRE ALARM CONTROL PANEL FCU FAN COIL UNIT FDR FEEDER FLEX FLEXIBLE FS FLOAT SWITCH FSS FUSED SAFETY SWITCH FT FOOT OR FEET FVNR FULL VOLTAGE NON-REVERSING FVR FULL VOLTAGE REVERSING GFI GROUND FAULT INTERRUPTER GRD GROUND H-O-A HAND-OFF-AUTOMATIC HID HIGH INTENSITY DISCHARGE HP HORSEPOWER HPS HIGH PRESSURE SODIUM HV HIGH VOLTAGE HZ HERTZ IC INSULATED CASE IMC INTERMEDIATE METAL CONDUIT JB JUNCTION BOX KV KILOVOLT KVA KILOVOLT-AMPERE KW KILOWATT LCP LIGHTING CONTROL PANEL LO LOCKOUT LS LIMIT SWITCH LTG LIGHTING MAFC MAKE ALL FINAL CONNECTIONS MANU MANUFACTURER MC MOLDED CASE MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MCP MOTOR CIRCUIT PROTECTOR MH MOUNTING HEIGHT MFS MAIN FUSED SWITCH MNFS MAIN NON-FUSED SWITCH MLO MAIN LUG ONLY MTD MOUNTED MTG MOUNTING N NEUTRAL NC NORMALLY CLOSED NCAP NURSE CALL ANNUNCIATOR PANEL NCCP NURSE CALL CONTROL PANEL NEC NATIONAL ELECTRICAL CODE NFSS NON-FUSED SAFETY SWITCH NIC NOT IN CONTRACT NL NIGHT LIGHT NO NORMALLY OPEN OL OVERLOAD P POLE OR POLES PB PUSHBUTTON PL PILOT LIGHT PNL PANELBOARD PS PRESSURE SWITCH PT POTENTIAL TRANSFORMER PVC POLYVINYL CHLORIDE RAP REMOTE ANNUNCIATOR PANEL RECEPT RECEPTACLE RGS RIGID GALVANIZED STEEL RMS ROOT MEAN SQUARE RVAT REDUCED VOLTAGE AUTO-TRANSFORMER RVSS REDUCED VOLTAGE SOLID STATE RVYD REDUCED VOLTAGE WYE-DELTA RX REMOVE EXISTING S/N SOLID NEUTRAL S/T SHUNT TRIP SMR SURFACE METAL RACEWAY SW SWITCH SWBD SWITCHBOARD SWGR SWITCHGEAR SYM SYMMETRICAL TDC TIME DELAY CLOSE TDO TIME DELAY OPEN TDR TIME DELAY RELAY TMH TELEPHONE MANHOLE TTB/TTC TELEPHONE TERMINAL BOARD/CABINET TYP TYPICAL UG UNDERGROUND UOI UNLESS OTHERWISE INDICATED UON UNLESS OTHERWISE NOTED UPS UNINTERRUPTIBLE POWER SUPPLY V VOLTS OR VOLTAGE VFC VARIABLE FREQUENCY CONTROLLER W WIRE W/ WITH WP WEATHERPROOF (NEMA 3R) XFMR TRANSFORMER XP EXPLOSION PROOF # NUMBER PHASE ENCLOSED CIRCUIT BREAKER BUSWAY TAP CIRCUIT BREAKER MAGNETIC MOTOR STARTER (SUBSCRIPT = NEMA SIZE) SAFETY SWITCH - UNFUSED, FUSED (SUBSCRIPT = SWITCH AMP/FUSE AMPS) FLEXIBLE CONDUIT BRANCH CIRCUIT - EXPOSED ON CEILING OR WALL BRANCH CIRCUIT - CONCEALED IN SLAB OR BELOW GRADE RACEWAY UP / RACEWAY DOWN KW/KWH METER VOLTMETER, VOLTMETER SELECTOR SWITCH AMMETER, AMMETER SELECTOR SWITCH ENCLOSED CIRCUIT BREAKER WITH SHUNT TRIP BRANCH CIRCUIT - CONCEALED IN CEILING OR WALL V A S DRAW-OUT POWER CIRCUIT BREAKER - MEDIUM VOLTAGE DRAW-OUT POWER CIRCUIT BREAKER - LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER SWITCH AND FUSE UNIT AUTOMATIC TRANSFER SWITCH KEY INTERLOCK N E L K K ELEVATOR FUSED POWER MODULE (SUBSCRIPT = AMPERE RATING) COMBINATION MAGNETIC MOTOR STARTER AND SAFETY SWITCH (SUBSCRIPT = NEMA SIZE) 30 30 30 MOUNTING HEIGHT SHALL BE 42" A.F.F. WHERE NO COUNTER PRESENT ATS 1 , , SYMBOLS DESCRIPTION MOTOR CONNECTION (NUMBER INDICATES HORSEPOWER) GENERATOR PUSHBUTTON STATION TELE-POWER POLE 48" P G M 5 MOUNTING HEIGHT SHALL BE 42" A.F.F. WHERE NO COUNTER PRESENT * A J CONNECTION TO AUTOMATIC DOOR 18" NONE

Transcript of E1 · 5/31/2016 10:34:57 am project number: 09.011 ... hv high voltage hz hertz ic ... mfs main...

Page 1: E1 · 5/31/2016 10:34:57 am project number: 09.011 ... hv high voltage hz hertz ic ... mfs main fused switch mnfs main non-fused switch mlo main lug only mtd mounted mtg mounting

architecture studio

architecture

327 pricketts fort road

fairmont, wv 26554

ph: 304.292.7750

PO Box 360

mchenry, maryland 21541

ph: 301.387.3380

fx: 301.387.3382

PROJECTdata

Pro

ject

Add

ress

Client Signature for Phase Completion

Schematic Design

Design Development

Progress

Bidding

Building Permit

Construction Documents

5/31/2016 10:34:57 AMProject Number: 09.011

16.0

16 W

MH

S -

Ch

apm

an-J

acks

on/

Pla

stic

s o

ffic

e12

500

Will

owbr

ook

Roa

d

Cum

berla

nd, M

D 2

1502

FIL

EN

AM

E: P

:\2

01

6\1

61

75

10

\B

IM

\ E

1.D

WG

L

AS

T S

AV

ED

B

Y: ( B

AY

RE

S) P

LO

TT

ED

B

Y: ( C

SC

HA

RD

T) O

N Ju

l 1

1, 2

01

6 - 3

:1

8p

m

LWA PROJECT NO: 16-175-10

21493 02/08/17

E1

ELECTRICALLEGEND,CONVENTIONS, ANDABBREVIATIONS

NOT ALL SYMBOLS

APPLY TO THIS PROJECT

AND ABBREVIATIONS

NOTE:

BATTERY POWERED EMERGENCY LIGHTING UNIT (MULTIPLE HEADS)

WALL MOUNTED FLUORESCENT LIGHTING FIXTURE

2'x4' FLUORESCENT LIGHTING FIXTURE

SPRINKLER SYSTEM PREACTION VALVE

FIRE ALARM SYSTEM SPRINKLER VALVE SUPERVISORY (TAMPER) SWITCH

FIRE ALARM SYSTEM FLAME DETECTOR

VARIABLE SPEED SWITCH

FIRE ALARM SYSTEM MANUAL PULL STATION

TELEPHONE TERMINAL BACKBOARD

JUNCTION BOX

GROUND FAULT INTERRUPTER TYPE RECEPTACLE

SPECIAL RECEPTACLE, FLOOR MOUNTED

DUPLEX RECEPTACLE MOUNTED 8" ABOVE COUNTER

SINGLE RECEPTACLE

SINGLE RECEPTACLE, FLOOR MOUNTED

LIGHTNING PROTECTION AIR TERMINAL

MANUAL MOTOR STARTER (WITH OVERLOAD PROTECTION)

LOW VOLTAGE MOMENTARY CONTROL SWITCH

SWITCH WITH PILOT LIGHT

NURSE CALL DOME LIGHT, WALL MOUNTED

NURSE CALL CODE BLUE EMERGENCY STATION

INTERCOM STATION, SINGLE CALL

SPEAKER (CEILING MOUNTED, WALL MOUNTED)

NURSE CALL DUTY STATION

NURSE CALL STAFF STATION

NURSE CALL MASTER CONTROL STATION

NURSE CALL EMERGENCY STATION (PUSH BUTTON ONLY)

NURSE CALL EMERGENCY STATION (WITH PULL CORD)

NURSE CALL PATIENT STATION

FIRE ALARM SYSTEM REMOTE ANNUNCIATOR PANEL

FIRE ALARM SYSTEM SPRINKLER FLOW ALARM SWITCH

FIRE ALARM SYSTEM HEAT DETECTOR

FIRE ALARM SYSTEM SMOKE DETECTOR

FIRE ALARM SYSTEM DUCT-TYPE SMOKE DETECTOR

FIRE ALARM SYSTEM BELL

FIRE ALARM SYSTEM CONTROL PANEL

EMERGENCY CIRCUIT DUPLEX RECEPTACLE

JUNCTION BOX, WALL MOUNTED

SPECIAL RECEPTACLE, REFER TO SCHEDULE

DUPLEX RECEPTACLE, SPLIT WIRED

DOUBLE DUPLEX RECEPTACLE

DUPLEX RECEPTACLE, FLOOR MOUNTED

DUPLEX RECEPTACLE

TIMER SWITCH (MANUAL)

WEATHERPROOF SWITCH

KEY OPERATED SWITCH

DIMMER SWITCH

FOUR WAY SWITCH

THREE WAY SWITCH

DOUBLE POLE SWITCH

SINGLE POLE SWITCH

GROUND CONNECTION

GROUND ROD

POLE MOUNTED SITE LIGHT

EXIT SIGN, CEILING MOUNTED, WITH DIRECTIONAL ARROWS AS INDICATED

INDUSTRIAL TYPE FLUORESCENT LIGHTING FIXTURE

FLUORESCENT LIGHTING FIXTURE ON EMERGENCY AND NORMAL CIRCUIT

2'x2' FLUORESCENT LIGHTING FIXTURE

LIGHTING FIXTURE ON EMERGENCY CIRCUIT

WALL MOUNTED LIGHTING FIXTURE

DOWNLIGHT WALLWASH LIGHTING FIXTURE

VOLUME CONTROL SWITCH

TELEPHONE OUTLET

DATA/COMMUNICATIONS OUTLET

DRY TYPE TRANSFORMER (REFER TO SCHEDULE)

PANELBOARD 208Y/120 VOLTS (SURFACE MOUNTED, RECESSED)

PANELBOARD 240 VOLTS (SURFACE MOUNTED, RECESSED)

PANELBOARD 480Y/277 VOLTS (SURFACE MOUNTED, RECESSED)

ELECTRIC HEAT TRACED PIPING

DOWNLIGHT LIGHTING FIXTURE

STRIP FLUORESCENT LIGHTING FIXTURE (BARE LAMP)

FLUORESCENT LIGHTING FIXTURE CONNECTED AS NIGHT LIGHT (UNSWITCHED)

MULTI-OUTLET ASSEMBLY WITH RECEPTACLES 18" ON CENTER

DATA/COMMUNICATIONS OUTLET, FLOOR MOUNTED

TELEPHONE OUTLET, FLOOR MOUNTED

FEEDER NUMBER (REFER TO SCHEDULE)

NURSE CALL DOME LIGHT, CEILING MOUNTED

INTERCOM STATION, MASTER

FIRE ALARM SYSTEM MAGNETIC DOOR HOLDER

FIRE ALARM SYSTEM CHIME

UNIT HEATER

TELEVISION OUTLET (REFER TO DETAIL)

PASSIVE INFRARED MOTION DETECTOR

MAGNETIC DOOR CONTACTS

PHOTOCELL

SECURITY CAMERA

DUPLEX RECEPTACLE WITH WEATHERPROOF COVER

EMERGENCY VOICE/ALARM SPEAKER, WALL MOUNTED

EMERGENCY VOICE/ALARM SPEAKER, CEILING MOUNTED

FIRE ALARM SYSTEM SMOKE DETECTOR INITIATES ELEVATOR RECALL

FIRE ALARM SYSTEM HEAT DETECTOR INITIATES ELEVATOR SHUTDOWN

FIRE ALARM SYSTEM DUCT-TYPE SMOKE DETECTOR INITIATES FAN SHUTDOWN

SMOKE DAMPER PROVIDED UNDER MECHANICAL FOR CONNECTION UNDER

ELECTRICAL

SECURITY MAGNETIC DOOR LOCK WITH FIRE ALARM SYSTEM RELEASE

EMERGENCY CIRCUIT RECEPTACLE FOR SERVICE TO MONITOR

1'x4' FLUORESCENT LIGHTING FIXTURE

INDUSTRIAL TYPE FLUORESCENT LIGHTING FIXTURE ON EMERGENCY CIRCUIT

FLUORESCENT LIGHTING FIXTURE ON EMERGENCY CIRCUIT

WALL MOUNTED FLUORESCENT LIGHTING FIXTURE ON EMERGENCY CIRCUIT

EXIT SIGN, WALL MOUNTED, WITH DIRECTIONAL ARROWS AS INDICATED

REMOTE EMERGENCY LIGHTING UNIT (MULTIPLE HEADS)

MONITOR OUTLET

FAX OUTLET

TELEPHONE OUTLET, WALL MOUNTED

DATA/COMMUNICATIONS OUTLET, MOUNTED 8" ABOVE COUNTER

ABBREVIATIONS

48"

48"

48"

48"

48"

48"

48"

48"

48"

48"

48"

48"

18"

18"

18"

18"

18"

18"

18"

18"

18"

18"

54"

48"

84"

FEEDER TYPE BUSWAY

PLUG-IN TYPE BUSWAY

M.H.

SYNCHRONIZED CLOCK

90"

54"

48"

18"

54"

54"

48"

48"

54"

54"

FLUORESCENT LIGHTING FIXTURE WITH (2) BALLASTS FOR DUAL SWITCHING

UNLESS INDICATED OTHERWISE

LINEWEIGHT INDICATES EXISTING TO REMAIN,

ELECTRICAL EQUIPMENT DENOTED BY LIGHT, SOLID

ELECTRICAL EQUIPMENT DENOTED BY HEAVY,

SOLID LINEWEIGHT SHALL BE NEW WORK

PROVIDED BY CONTRACTOR

EMERGENCY CIRCUIT DOUBLE DUPLEX (QUAD) RECEPTACLE

EMERGENCY CIRCUIT DUPLEX RECEPTACLE MOUNTED 8" ABOVE COUNTER

EMERGENCY CIRCUIT DOUBLE DUPLEX (QUAD) RECEPTACLE MOUNTED 8"

ABOVE COUNTER

FLUORESCENT LIGHTING FIXTURE WITH PARABOLIC LOUVER

CARD READER

FACP

2

3

4

D

K

P

WP

LV

T

VS

M

V

a

b

L

N

18"

GFI

S

M

DOUBLE DUPLEX RECEPTACLE MOUNTED 8" ABOVE COUNTER

A

C

J

J

WALL-MOUNTED NIGHT LIGHT FIXTURENL 18"

18"

WP

SINGLE RECEPTACLE CLOCK HANGER OUTLET

TAMPER RESISTANT RECEPTACLE

C

TR 18"

HARDWIRE CONNECTION TO ELECTRIFIED FURNITURE SYSTEMSJ

F

SYMBOLS DESCRIPTIONM.H.

H

T

TV

M

C

P

PUSHPLATE SWITCH

CR

PP

48"

48"

M

F

W

C

P

B

E

S

D

E

I

I

M

SS ,

COMBINATION TELEPHONE/DATA OUTLET 18"

COMBINATION TELEPHONE/DATA OUTLET, MOUNTED 8" ABOVE COUNTER

C

TELEPHONE OUTLET, MOUNTED 8" ABOVE COUNTER

C

COMBINATION TELEPHONE/DATA OUTLET, FLOOR MOUNTED

NURSE CALL CONTROL PANEL

NURSE CALL STAFF REGISTRY/LOCATOR STATIONL

54"

NURSE CALL ROOM COMMUNICATIONS BOXN

NURSE CALL STAFF LOCATOR ANTENNA, CEILING MOUNTEDL

NURSE CALL ZONE INDICATOR DOME LIGHT, CEILING MOUNTEDZ

NURSE CALL/BED COMMUNICATIONS INTERFACE OUTLET

TRANSFORMER NEUTRAL GROUND CONNECTION

M.H.

D

S

H

F

DH

L

B

F

C

S

S

F

F

S

E

H

E

U

DL

FIRE ALARM SYSTEM ADDRESSABLE CONTROL MODULE

FIRE ALARM SYSTEM ADDRESSABLE MONITOR MODULE

FIRE ALARM SYSTEM REMOTE ALARM LIGHT

RAL

2

A1

1

CONNECT TO EXISTING

90"

90"

T

J TELEPHONE/DATA CONNECTIONS TO ELECTRIFIED FURNITURE SYSTEMS

NCCP

NCS

(VERSION 02/12)

48"

OCCUPANCY SENSOR SWITCH - PASSIVE INFRARED

O

48"

OCCUPANCY SENSOR SWITCH - DUAL CONTROL

O2

48"

AUTOMATIC LIGHTING CONTROL SWITCH

A

48"

CEILING-MOUNTED INFRARED OCCUPANCY SENSOR

CEILING-MOUNTED ULTRASONIC OCCUPANCY SENSOR

CEILING-MOUNTED LIGHTING CONTROL RELAY

O

I

O

U

R

LC

48"

15

15

15

15

FIRE ALARM SYSTEM COMBINATION BELL AND FLASHING LIGHT UNIT

(SUBSCRIPT = CANDELA RATING)

FIRE ALARM SYSTEM COMBINATION HORN AND FLASHING LIGHT UNIT

(SUBSCRIPT = CANDELA RATING)

FIRE ALARM SYSTEM COMBINATION CHIME AND FLASHING LIGHT UNIT

(SUBSCRIPT = CANDELA RATING)

15

FIRE ALARM SYSTEM COMBINATION SPEAKER AND FLASHING LIGHT UNIT (SUBSCRIPT

= CANDELA RATING)

SMOKE BARRIER

SMOKE TIGHT PARTITION

3 HOUR RATED FIRE WALL

2 HOUR RATED FIRE WALL

1 HOUR RATED FIRE WALL

DUPLEX RECEPTACLE ON UPS CIRCUIT 18"

DOUBLE DUPLEX RECEPTACLE ON UPS CIRCUIT

DUPLEX RECEPTACLE ON UPS CIRCUIT MOUNTED 8" ABOVE COUNTER

DOUBLE DUPLEX RECEPTACLE ON UPS CIRCUIT MOUNTED 8"

ABOVE COUNTER

18"

3 HOUR RATED FIRE WALL SMOKE BARRIER

2 HOUR RATED FIRE WALL SMOKE BARRIER

1 HOUR RATED FIRE WALL SMOKE BARRIER

OCCUPANCY SENSOR SWITCH - MULTI-TECHNOLOGY

OM

48"

FIRE ALARM SYSTEM FLASHING LIGHT, SUBSCRIPT CANDELA RATING

MOUNTING HEIGHTS SHALL BE SUCH THAT ENTIRE LENS IS BETWEEN 80" & 96" AFF,

SUBSCRIPT INDICATES CANDELA RATING. MOUNTING HEIGHTS SHALL BE

**

IDENTICAL IN EACH ROOM.

**

88"

88"

**

**

**

**

JUNCTION BOX WITH BLANK COVER PLATEJ

X

DUPLEX RECEPTACLE MOUNTED IN SHELVING/MILLWORK

(COORDINATE WITH ARCHITECTURAL ELEVATIONS

*

*

*

*

*

*

THRU-WALL NIGHT LIGHT FIXTURENLNL

MANUAL MOTOR SWITCH (NO OVERLOAD PROTECTION)

MS

48"

AREA OF RESCUE ASSISTANCE STATIONARA

PATIENT SERVICES HEADWALL UNITPS HW

*

*

*

THERMOSTAT FOR HEAT TRACINGT

VFC VARIABLE FREQUENCY CONTROLLER FURNISHED UNDER MECHANICAL FOR

INSTALLATION BY ELECTRICAL

PTS PNEUMATIC TUBE STATION CONNECTION

VAV VAV BOX/AIR TERMINAL UNIT CONNECTION

FCU FAN COIL UNIT CONNECTION

MGAP CONNECTION TO MEDICAL GAS ALARM PANEL

IR CONNECTION TO LOW VOLTAGE INFRARED PLUMBING FIXTURE CONTROL

CRU COMPUTER ROOM AIR CONDITIONING UNIT CONNECTION

ACCU AIR COOLED CONDENSING UNIT CONNECTION

WSHP WATER SOURCE HEAT PUMP CONNECTION

C2T 24VAC CONTROL POWER TRANSFORMER FOR ATC USE

INDICATES CIRCUIT DESIGNATION

RAP

FIRE ALARM REMOTE (BOOSTER) POWER SUPPLYRPS

SWITCH WITH ILLUMINATED HANDLE

I

SECURE KEY BOX (KNOX BOX) W/ FIRE ALARM TAMPER SWITCH

18"

48"

,

,

,

S

L

C

L

H

L

B

L

ELECTRICAL LEGEND

SYMBOLS DESCRIPTION

INDICATES SPACE OR POLE NUMBER

BRANCH CIRCUIT HOMERUN TO PANELBOARD, SWITCHBOARD, MCC

PANELBOARD DESIGNATION

INDICATES PHASE, SWITCHED, AND TRAVELER CONDUCTORS

(IF NOT SHOWN, PROVIDE 2#12 AWG & 1#12 GROUND)

A

E-3

C

E-5

LIGHTING FIXTURE TYPE (REFER TO SCHEDULE)

LIGHTING FIXTURE

INDICATES SWITCH DESIGNATION

INDICATES NUMBER OF SWITCHES IN GROUP

LIGHTING TOGGLE SWITCH

DENOTES SWITCH DESIGNATION

DUPLEX RECEPTACLE

INDICATES CIRCUIT DESIGNATION

ELECTRICAL EQUIPMENT DENOTED BY DASHED,

HEAVY LINEWEIGHT SHALL BE DISPOSED OF,

UNLESS INDICATED TO BE REUSED OR TURNED

OVER TO THE OWNER

SECTION DESIGNATION - LETTER DENOTES SECTION

IDENTIFICATION

INDICATES DRAWING NUMBER WHERE SECTION IS DRAWN

DETAIL DESIGNATION - LETTER DENOTES DETAIL

IDENTIFICATION

INDICATES DRAWING NUMBER WHERE DETAIL IS DRAWN

DRAWING NOTE

GENERAL NOTE - APPLIES TO ALL SHEETS WITHIN THE

ELECTRICAL DRAWING SET

CONVENTIONS

SB

S

3H

2H

1H

3HSB

2HSB

1HSB

A AMPS OR AMPERE

AC ALTERNATING CURRENT

ACU AIR CONDITIONING UNIT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPERES INTERRUPTING CAPACITY

ATC AUTOMATIC TEMPERATURE CONTROL

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CLG CEILING

CPT CONTROL POWER TRANSFORMER

CT CURRENT TRANSFORMER

CUH CABINET UNIT HEATER

DC DIRECT CURRENT

DISC DISCONNECT

DN DOWN

DO DRAW OUT

DP DISTRIBUTION PANEL

DWG DRAWING

EA EACH

EC EMPTY CONDUIT

ECB ENCLOSED CIRCUIT BREAKER

EF EXHAUST FAN

EGS EMERGENCY GENERATOR SET

EMH ELECTRICAL MANHOLE

EMS EMERGENCY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EX. EXISTING

EXH EXHAUST

F FUSE

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FDR FEEDER FLEX FLEXIBLE

FS FLOAT SWITCH

FSS FUSED SAFETY SWITCH

FT FOOT OR FEET

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

GFI GROUND FAULT INTERRUPTER

GRD GROUND

H-O-A HAND-OFF-AUTOMATIC

HID HIGH INTENSITY DISCHARGE

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HV HIGH VOLTAGE

HZ HERTZ

IC INSULATED CASE

IMC INTERMEDIATE METAL CONDUIT

JB JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KW KILOWATT

LCP LIGHTING CONTROL PANEL

LO LOCKOUT

LS LIMIT SWITCH

LTG LIGHTING

MAFC MAKE ALL FINAL CONNECTIONS

MANU MANUFACTURER

MC MOLDED CASE

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MH MOUNTING HEIGHT

MFS MAIN FUSED SWITCH

MNFS MAIN NON-FUSED SWITCH

MLO MAIN LUG ONLY

MTD MOUNTED

MTG MOUNTING

N NEUTRAL

NC NORMALLY CLOSED

NCAP NURSE CALL ANNUNCIATOR PANEL

NCCP NURSE CALL CONTROL PANEL

NEC NATIONAL ELECTRICAL CODE

NFSS NON-FUSED SAFETY SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

OL OVERLOAD

P POLE OR POLES

PB PUSHBUTTON

PL PILOT LIGHT

PNL PANELBOARD

PS PRESSURE SWITCH

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE

RAP REMOTE ANNUNCIATOR PANEL

RECEPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RMS ROOT MEAN SQUARE

RVAT REDUCED VOLTAGE AUTO-TRANSFORMER

RVSS REDUCED VOLTAGE SOLID STATE

RVYD REDUCED VOLTAGE WYE-DELTA

RX REMOVE EXISTING

S/N SOLID NEUTRAL

S/T SHUNT TRIP

SMR SURFACE METAL RACEWAY

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYM SYMMETRICAL

TDC TIME DELAY CLOSE

TDO TIME DELAY OPEN

TDR TIME DELAY RELAY

TMH TELEPHONE MANHOLE

TTB/TTC TELEPHONE TERMINAL BOARD/CABINET

TYP TYPICAL

UG UNDERGROUND

UOI UNLESS OTHERWISE INDICATED

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTS OR VOLTAGE

VFC VARIABLE FREQUENCY CONTROLLER

W WIRE

W/ WITH

WP WEATHERPROOF (NEMA 3R)

XFMR TRANSFORMER

XP EXPLOSION PROOF

# NUMBER

Ø PHASE

ENCLOSED CIRCUIT BREAKER

BUSWAY TAP CIRCUIT BREAKER

MAGNETIC MOTOR STARTER (SUBSCRIPT = NEMA SIZE)

SAFETY SWITCH - UNFUSED, FUSED (SUBSCRIPT = SWITCH AMP/FUSE AMPS)

FLEXIBLE CONDUIT

BRANCH CIRCUIT - EXPOSED ON CEILING OR WALL

BRANCH CIRCUIT - CONCEALED IN SLAB OR BELOW GRADE

RACEWAY UP / RACEWAY DOWN

KW/KWH METER

VOLTMETER, VOLTMETER SELECTOR SWITCH

AMMETER, AMMETER SELECTOR SWITCH

ENCLOSED CIRCUIT BREAKER WITH SHUNT TRIP

BRANCH CIRCUIT - CONCEALED IN CEILING OR WALL

V

A

S

DRAW-OUT POWER CIRCUIT BREAKER - MEDIUM VOLTAGE

DRAW-OUT POWER CIRCUIT BREAKER - LOW VOLTAGE

MOLDED CASE CIRCUIT BREAKER

SWITCH AND FUSE UNIT

AUTOMATIC TRANSFER SWITCH

KEY INTERLOCK

N

E

L

KK

ELEVATOR FUSED POWER MODULE (SUBSCRIPT = AMPERE RATING)

COMBINATION MAGNETIC MOTOR STARTER AND SAFETY SWITCH

(SUBSCRIPT = NEMA SIZE)

30

30

30

MOUNTING HEIGHT SHALL BE 42" A.F.F. WHERE NO COUNTER PRESENT

ATS

1

,

,

SYMBOLS DESCRIPTION

MOTOR CONNECTION (NUMBER INDICATES HORSEPOWER)

GENERATOR

PUSHBUTTON STATION

TELE-POWER POLE

48"

P

G

M

5

MOUNTING HEIGHT SHALL BE 42" A.F.F. WHERE NO COUNTER PRESENT

*

A

J CONNECTION TO AUTOMATIC DOOR

18"

NONE

Page 2: E1 · 5/31/2016 10:34:57 am project number: 09.011 ... hv high voltage hz hertz ic ... mfs main fused switch mnfs main non-fused switch mlo main lug only mtd mounted mtg mounting

DN

UP

A

A.8

B

B.5

C

C.5

C.7

D

1 2 2.8 3

LE

AHU

architecture studio

architecture

327 pricketts fort road

fairmont, wv 26554

ph: 304.292.7750

PO Box 360

mchenry, maryland 21541

ph: 301.387.3380

fx: 301.387.3382

PROJECTdata

Pro

ject

Add

ress

Client Signature for Phase Completion

Schematic Design

Design Development

Progress

Bidding

Building Permit

Construction Documents

5/31/2016 10:34:57 AMProject Number: 09.011

16.0

16 W

MH

S -

Ch

apm

an-J

acks

on/

Pla

stic

s o

ffic

e12

500

Will

owbr

ook

Roa

d

Cum

berla

nd, M

D 2

1502

FIL

EN

AM

E: P

:\2

01

6\1

61

75

10

\B

IM

\ E

2.D

WG

L

AS

T S

AV

ED

B

Y: ( B

AY

RE

S) P

LO

TT

ED

B

Y: ( C

SC

HA

RD

T) O

N Ju

l 1

1, 2

01

6 - 3

:1

8p

m

LWA PROJECT NO: 16-175-10

AREA OF WORK

N

KEY PLAN

NOT TO SCALE

21493 02/08/17

E2

PART FOURTHFLOOR PLAN -REMOVAL WORK -ELECTRICAL

N

PART FOURTH FLOOR PLAN - REMOVAL WORK - ELECTRICAL

SCALE: 1/4"=1'-0"

14"=1'-0"

Page 3: E1 · 5/31/2016 10:34:57 am project number: 09.011 ... hv high voltage hz hertz ic ... mfs main fused switch mnfs main non-fused switch mlo main lug only mtd mounted mtg mounting

DN

UP

A

A.8

B

B.5

C

C.5

C.7

D

1 2 2.8 3

OO

O

OO

OO

O

O

O

OO

O

O

D

H

L

15

H

L

15

L

15

L

15

L

15

L

15

L

15

L

15

L

30

L

15

L

15

L

15

L

15

L

15

L

15

X1

X1

X1

X1

L

15

A2 A2

A2 A2

A13

A6

A6A6

A6

A6

A11

A11

A11

A11

A6

A6

A6

A11

A11

A11

A11

A11

A11

A11

A11

A11

A11

A11

A1

A1

A1

A1 A1 A1

A1

A1

A1

A6

A1

A1

A1

A1

A1

A1 A1

A1 A1 A1 A1

A1

PANEL 4F

PANEL 4FF

DOC.

OFFICE

430

MED.

ROOM

740

S TOILET

446

BREAK

ROOM

431

TREATMENT

ROOM

434

CORRIDOR

-

SOILED

WORKROOM

442

FUTURE

PA OFFICE

709

IT CLOSET

741

EXAM

ROOM 03

441

EXAM

ROOM 02

440

EXAM

ROOM 01

439

SCHEDULING/

FINANCING

438

RECEPTION

435

WAITING

436

PACS

WORKSTATION/

NURSE

530

architecture studio

architecture

327 pricketts fort road

fairmont, wv 26554

ph: 304.292.7750

PO Box 360

mchenry, maryland 21541

ph: 301.387.3380

fx: 301.387.3382

PROJECTdata

Pro

ject

Add

ress

Client Signature for Phase Completion

Schematic Design

Design Development

Progress

Bidding

Building Permit

Construction Documents

5/31/2016 10:34:57 AMProject Number: 09.011

16.0

16 W

MH

S -

Ch

apm

an-J

acks

on/

Pla

stic

s o

ffic

e12

500

Will

owbr

ook

Roa

d

Cum

berla

nd, M

D 2

1502

FIL

EN

AM

E: P

:\2

01

6\1

61

75

10

\B

IM

\ E

3.D

WG

L

AS

T S

AV

ED

B

Y: ( C

SC

HA

RD

T) P

LO

TT

ED

B

Y: ( C

SC

HA

RD

T) O

N Ju

l 1

1, 2

01

6 - 3

:1

8p

m

LWA PROJECT NO: 16-175-10

AREA OF WORK

N

KEY PLAN

NOT TO SCALE

21493 02/08/17

E3

PART FOURTHFLOOR PLAN - NEWWORK - LIGHTINGAND FIRE ALARM

N

PART FOURTH FLOOR PLAN - NEW WORK - LIGHTING AND FIRE ALARM

SCALE: 1/4"=1'-0"

14"=1'-0"

GENERAL NOTES:

G1. CONNECT ALL EMERGENCY LIGHTING FIXTURES AND EXIT SIGNS TO PANEL

EL5, CIRCUIT #7.

DRAWING NOTES:

1.

Page 4: E1 · 5/31/2016 10:34:57 am project number: 09.011 ... hv high voltage hz hertz ic ... mfs main fused switch mnfs main non-fused switch mlo main lug only mtd mounted mtg mounting

DN

UP

A

A.8

B

B.5

C

C.5

C.7

D

1 2 2.8 3

DOC.

OFFICE

430

MED.

ROOM

740

S TOILET

446

BREAK

ROOM

431

TREATMENT

ROOM

434

CORRIDOR

-

SOILED

WORKROOM

442

FUTURE

PA OFFICE

709

IT CLOSET

741

EXAM

ROOM 03

441

EXAM

ROOM 02

440

EXAM

ROOM 01

439

SCHEDULING/

FINANCING

438

RECEPTION

435

WAITING

436

PACS

WORKSTATION/

NURSE

530

PANEL 4F

PANEL 4FF

GFI

GFI

C

GFI

GFI GFI

GFI

GFI

GFI

GFI

GFI

C

C

C

C

DN UP

C.5

C.7

ELECTRICAL

T

T

T

EX. PANEL RP4-2

EX. PANEL RP4A

EX. PANEL ERP4

EX. PANEL DP-4

EX. PANEL DP4A

EX. PANEL RP4-1

architecture studio

architecture

327 pricketts fort road

fairmont, wv 26554

ph: 304.292.7750

PO Box 360

mchenry, maryland 21541

ph: 301.387.3380

fx: 301.387.3382

PROJECTdata

Pro

ject

Add

ress

Client Signature for Phase Completion

Schematic Design

Design Development

Progress

Bidding

Building Permit

Construction Documents

5/31/2016 10:34:57 AMProject Number: 09.011

16.0

16 W

MH

S -

Ch

apm

an-J

acks

on/

Pla

stic

s o

ffic

e12

500

Will

owbr

ook

Roa

d

Cum

berla

nd, M

D 2

1502

FIL

EN

AM

E: P

:\2

01

6\1

61

75

10

\B

IM

\ E

4.D

WG

L

AS

T S

AV

ED

B

Y: ( C

SC

HA

RD

T) P

LO

TT

ED

B

Y: ( C

SC

HA

RD

T) O

N Ju

l 1

1, 2

01

6 - 3

:1

9p

m

LWA PROJECT NO: 16-175-10

AREA OF WORK

N

KEY PLAN

NOT TO SCALE

21493 02/08/17

E4

PART FOURTHFLOOR PLAN - NEWWORK - POWER ANDCOMMUNICATION

N

PART FOURTH FLOOR PLAN - NEW WORK - POWER AND COMMUNICATION

SCALE: 1/4"=1'-0"

14"=1'-0"

GENERAL NOTES:

G1. CONNECT ALL DEVICES TO PANEL 4FF, CIRCUIT # AS INDICATED UNLESS

OTHERWISE INDICATED.

G2. FOR DEVICES BELOW WINDOWS, ROUTE CONDUIT HORIZONTALLY IN WALL

BELOW WINDOW AND UP TO CEILING SPACE IN NEAREST FULL HEIGHT

WALL.

DRAWING NOTES:

1.

N

PART FOURTH FLOOR PLAN - NEW WORK - POWER AND COMMUNICATION

SCALE: 1/4"=1'-0"

Page 5: E1 · 5/31/2016 10:34:57 am project number: 09.011 ... hv high voltage hz hertz ic ... mfs main fused switch mnfs main non-fused switch mlo main lug only mtd mounted mtg mounting

architecture studio

architecture

327 pricketts fort road

fairmont, wv 26554

ph: 304.292.7750

PO Box 360

mchenry, maryland 21541

ph: 301.387.3380

fx: 301.387.3382

PROJECTdata

Pro

ject

Add

ress

Client Signature for Phase Completion

Schematic Design

Design Development

Progress

Bidding

Building Permit

Construction Documents

5/31/2016 10:34:57 AMProject Number: 09.011

16.0

16 W

MH

S -

Ch

apm

an-J

acks

on/

Pla

stic

s o

ffic

e12

500

Will

owbr

ook

Roa

d

Cum

berla

nd, M

D 2

1502

FIL

EN

AM

E: \\e

lkrid

ge

file

s\P

ro

je

ct\2

01

6\1

61

75

10

\B

IM

\ E

5.D

WG

L

AS

T S

AV

ED

B

Y: ( C

SC

HA

RD

T) P

LO

TT

ED

B

Y: ( C

SC

HA

RD

T) O

N Ju

l 1

1, 2

01

6 - 3

:3

8p

m

LWA PROJECT NO: 16-175-10

21493 02/08/17

E5

ELECTRICALSCHEDULES ANDDETAILS

NONE

4TH FLOOR

EX.

RP4-2

EX.

DP4A

4F4FF

EX. MAIN 4TH FLOOR ELEC. CLOSETCORRIDOR

SCHEMATIC POWER RISER DIAGRAM

NOT TO SCALE

1 1/4"C.W/4#3+1#8GRD.

1 1/4"C.W/4#3+1#8GRD.

DETAIL - LAY-IN RECESSED LUMINAIRE INSTALLATION

NOT TO SCALE

CONNECTION PLATE ON TOP OF FIXTURE

REV. 11/4/11

TYPE MC CABLE TO OUTLET BOX IN LIGHTING

BRANCH CIRCUIT (18" MINIMUM / 6'-0" MAX LENGTH)

(DO NOT USE FLEXIBLE METAL CONDUIT).

SUPPORT LUMINAIRES INDEPENDENT OF

CEILING GRID BY PROVIDING 12 GAUGE

GALVANIZED SUPPORT WIRE FROM LUMINAIRE

TO STRUCTURE ABOVE CEILING (TYPICAL TWO

OPPOSITE CORNERS)

RECESSED FLUORESCENT

LUMINAIRE (TYPICAL)

J

BRANCH CIRCUIT

PROPERLY SECURED

JUNCTION BOX, LOCATED AT

LEAST 12" FROM LUMINAIRE

DETAIL FOR HEALTH CARE FACILITY

NOT TO SCALE

METAL-CLAD CABLE FOR NORMAL POWER LOADS

J

TO MULTIPLE DEVICES.

TYP. NORMAL POWER PANEL.

WHERE CIRCUITS BRANCH

FIRST JUNCTION POINT

(EMT) FROM PANEL TO

PROVIDE 3/4" CONDUIT

TYPICAL NORMAL POWER LOAD.

A1

REV. 1/16/15

PROVIDE HCF MCAP OR APPROVED

EQUAL CABLE TO CONCEALED NORMAL

POWER LOAD UNDER 30A. 20' MAXIMUM

LENGTH.

PROVIDE JUNCTION BOX (SIZED PER NEC) FOR

MULTIPLE BRANCH CIRCUITS SERVING TWO OR

MORE DEVICES. LOCATE AS NEAR TO LOAD AS

POSSIBLE.

WIRING PANELBOARD SCHEDULE

PANEL: 4F MAINS: MLO MTG: SURFACE AMPS: 100

LOCATION: CORRIDOR PHASE: 3 VOLTAGE: 480Y/277

FED FROM: PANEL DP4A WIRES: 4 AIC:14,000

CIR DESCRIPTION P AMP BRANCH CIRCUIT A A B B C C CIR DESCRIPTION P AMP BRANCH CIRCUIT

1 LTS - SUITE 460 1 20 3/4"C.W/2#12+1#12GRD. 0 0 - - - - 2 SPARE 1 20 -

3 SPARE 1 20 - - - 0 0 - - 4 SPARE 1 20 -

5 SPARE 1 20 - - - - - 0 0 6 SPARE 1 20 -

7 SPARE 1 20 - 0 0 - - - - 8 SPARE 1 20 -

9 SPARE 1 20 - - - 0 0 - - 10 SPARE 1 20 -

11 SPARE 1 20 - - - - - 0 0 12 SPARE 1 20 -

13 SPARE 1 20 - 0 0 - - - - 14 SPARE 1 20 -

15 SPARE 1 20 - - - 0 0 - - 16 SPARE 1 20 -

17 SPARE 1 20 - - - - - 0 0 18 SPARE 1 20 -

19 SPARE 1 20 - 0 0 - - - - 20 SPARE 1 20 -

21 SPARE 1 20 - - - 0 0 - - 22 SPARE 1 20 -

23 SPARE 1 20 - - - - - 0 0 24 SPARE 1 20 -

25 SPARE 1 20 - 0 0 - - - - 26 SPARE 1 20 -

27 SPARE 1 20 - - - 0 0 - - 28 SPARE 1 20 -

29 SPARE 1 20 - - - - - 0 0 30 SPARE 1 20 -

31 SPARE 1 20 - 0 0 - - - - 32 SPARE 1 20 -

33 SPARE 1 20 - - - 0 0 - - 34 SPARE 1 20 -

35 SPARE 1 20 - - - - - 0 0 36 SPARE 1 20 -

37 SPARE 1 20 - 0 0 - - - - 38 SPARE 1 20 -

39 SPARE 1 20 - - - 0 0 - - 40 SPARE 1 20 -

41 SPARE 1 20 - - - - - 0 0 42 SPARE 1 20 -

CONNECTED LOAD 0 A TOTAL PHASE A 0 A

DEMAND LOAD 0 A TOTAL PHASE B 0 A

TOTAL PHASE C 0 A

WIRING PANELBOARD SCHEDULE

PANEL: 4FF MAINS: MLO MTG: SURFACE AMPS: 100

LOCATION: CORRIDOR PHASE: 3 VOLTAGE: 208Y/120

FED FROM: PANEL RP4A WIRES: 4 AIC:10,000

CIR DESCRIPTION P AMP BRANCH CIRCUIT A A B B C C CIR DESCRIPTION P AMP BRANCH CIRCUIT

1 SPARE 1 20 - 0 0 - - - - 2 SPARE 1 20 -

3 SPARE 1 20 - - - 0 0 - - 4 SPARE 1 20 -

5 SPARE 1 20 - - - - - 0 0 6 SPARE 1 20 -

7 SPARE 1 20 - 0 0 - - - - 8 SPARE 1 20 -

9 SPARE 1 20 - - - 0 0 - - 10 SPARE 1 20 -

11 SPARE 1 20 - - - - - 0 0 12 SPARE 1 20 -

13 SPARE 1 20 - 0 0 - - - - 14 SPARE 1 20 -

15 SPARE 1 20 - - - 0 0 - - 16 SPARE 1 20 -

17 SPARE 1 20 - - - - - 0 0 18 SPARE 1 20 -

19 SPARE 1 20 - 0 0 - - - - 20 SPARE 1 20 -

21 SPARE 1 20 - - - 0 0 - - 22 SPARE 1 20 -

23 SPARE 1 20 - - - - - 0 0 24 SPARE 1 20 -

25 SPARE 1 20 - 0 0 - - - - 26 SPARE 1 20 -

27 SPARE 1 20 - - - 0 0 - - 28 SPARE 1 20 -

29 SPARE 1 20 - - - - - 0 0 30 SPARE 1 20 -

31 SPARE 1 20 - 0 0 - - - - 32 SPARE 1 20 -

33 SPARE 1 20 - - - 0 0 - - 34 SPARE 1 20 -

35 SPARE 1 20 - - - - - 0 0 36 SPARE 1 20 -

37 SPARE 1 20 - 0 0 - - - - 38 SPARE 1 20 -

39 SPARE 1 20 - - - 0 0 - - 40 SPARE 1 20 -

41 SPARE 1 20 - - - - - 0 0 42 SPARE 1 20 -

CONNECTED LOAD 0 A TOTAL PHASE A 0 A

DEMAND LOAD 0 A TOTAL PHASE B 0 A

TOTAL PHASE C 0 A

EXISTING DISTRIBUTION PANELBOARD SCHEDULE

EX. PANELBOARD: DP4A MAINS: MLO AMPS: 225 MTG: SURFACE AIC:35,000

VOLTAGE: 480Y/277 PHASE: 3 WIRES: 4 LOCATION:

FED FROM: MAIN SWITCHBOARD

CIR ITEM SERVED CIRCUIT BREAKER LOAD FEEDER REMARKS

FRAME TRIP POLE TYPE A B C

1 EX. CIRCUIT 150 100 3 - - - - - -

2 EX. HOT WATER 60 60 3 - - - - - -

3 EX. CIRCUIT 150 100 3 - - - - - -

4 EX. PANEL 4B 150 100 3 - - - - - -

5 EX. TRANSFORMER 150 100 3 - - - - - -

6 PANEL 4F 150 100 3 - 0 0 0 1-1/4"C.W/4#3+1#8GRD. NOTE 1

7 EX. AC4 150 150 3 - - - - - -

8 EX. SPARE 150 100 3 - - - - - -

NOTE 1: CONNECT TO EXISTING SPARE CIRCUIT BREAKER.

EXISTING DISTRIBUTION PANELBOARD SCHEDULE

EX. PANELBOARD: RP4A MAINS: MLO AMPS: 225 MTG: SURFACE AIC:10,000

VOLTAGE: 208Y/120 PHASE: 3 WIRES: 4 LOCATION:

FED FROM: TRANSFORMER T4A

CIR ITEM SERVED CIRCUIT BREAKER LOAD FEEDER REMARKS

FRAME TRIP POLE TYPE A B C

1 EX. CIRCUIT 100 100 3 - - - - - -

2 EX. CIRCUIT 100 100 3 - - - - - -

3 EX. CIRCUIT 100 100 3 - - - - - -

4 PANEL 4FF 100 100 3 - 0 0 0 1-1/4"C.W/4#3+1#8GRD. NOTE 1

5 EX. SPACE - - 3 - - - - - -

6 EX. SPACE - - 3 - - - - - -

7 EX. SPACE - - 3 - - - - - -

8 EX. SPACE - - 3 - - - - - -

9 EX. SPACE - - 3 - - - - - -

10 EX. SPACE - - 3 - - - - - -

NOTE 1: CONNECT TO EXISTING SPARE CIRCUIT BREAKER.

EX. WIRING PANELBOARD SCHEDULE

EX. PANEL: EL5 (LIFE SFTY.)

MAINS: MLO MTG: SURFACE AMPS: 225

LOCATION: 5TH FLR ELEC. PHASE: 3 VOLTAGE: 480Y/277

WIRES: 4 AIC:22,000

CIR DESCRIPTION P AMP BRANCH CIRCUIT CIR DESCRIPTION P AMP BRANCH CIRCUIT

1 EX. LTG: SUITE 570 1 20 ETR 2 EX. SPARE 1 20 -

3 LTG: 6TH FLR OB GYN 1 20 ETR 4 EX. SPARE 1 20 -

5 EX. EM LTG: TRI ST. OBGYN 1 20 ETR 6 EX. SPARE 1 20 -

7 LTG - SUITE 460 1 20* 3/4"C.W/2#12+1#12GRD. 8 EX. SPARE 1 20 -

9 EX. SPARE 1 20 - 10 EX. SPARE 1 20 -

11 EX. SPARE 1 20 - 12 EX. SPARE 1 20 -

13 EX. SPARE 1 20 - 14 EX. SPARE 1 20 -

15 EX. SPARE 1 20 - 16 EX. SPARE 1 20 -

17 EX. SPARE 1 20 - 18 EX. SPARE 1 20 -

19 EX. SPARE 1 20 - 20 EX. SPARE 1 20 -

21 EX. SPARE 1 20 - 22 EX. SPARE 1 20 -

23 EX. SPARE 1 20 - 24 EX. SPARE 1 20 -

25 EX. SPARE 1 20 - 26 EX. SPARE 1 20 -

27 EX. SPARE 1 20 - 28 EX. SPARE 1 20 -

29 EX. SPARE 1 20 - 30 EX. SPARE 1 20 -

* CONNECT TO EXISTING SPARE CIRCUIT BREAKER.

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION MANUFACTURER / CATALOG NO. LAMPS VOLTAGE NOTES

2'x2' LED VOLUMETRIC TROFFER, ROUND PERFORATED- 2000-2300 LUMEN

A1

DIFFUSER, GRID CEILING, WHITELITHONIA 2AVL

LED (INCLUDED)

277/120

ENAMEL FINISH, 0-10V DIMMING DRIVERCORELITE R3 3500K

2'x2' LED VOLUMETRIC TROFFER, ROUND PERFORATED

- 2900-3000 LUMEN

A2

DIFFUSER, GRID CEILING, WHITE

LITHONIA 2AVL

LED (INCLUDED)

277/120

ENAMEL FINISH, 0-10V DIMMING DRIVER

CORELITE R3 3500K

2'x2' LED LENSED TROFFER, A12 ACRYLIC LENS,

- LED 2000 LUMEN

A6

FLUSH WHITE ALUMINUM DOOR,

LITHONIA 2TL 3500K 277/120

0-10V DIMMING DRIVER METALUX 22GRLED

(INCLUDED)

2'x4' LED LENSED TROFFER, A12 ACRYLIC LENS,

- LED 3000 LUMEN

A11

FLUSH WHITE ALUMINUM DOOR,

LITHONIA 2TL 3500K 277/120

0-10V DIMMING DRIVER METALUX 24GR

(INCLUDED)

2'x4' LED LENSED TROFFER, A12 ACRYLIC LENS,

- LED 4800 LUMEN

A13

FLUSH WHITE ALUMINUM DOOR,

LITHONIA 2TL 3500K 277/120

0-10V DIMMING DRIVER METALUX 24GR

(INCLUDED)

SINGLE-SIDED EXIT SIGN,

-

X1

BRUSHED ALUMINUM FACE,

LITHONIA LE

LED (INCLUDED)

277/120

RED STENCIL SURELITES CX-6

NOTES:

Page 6: E1 · 5/31/2016 10:34:57 am project number: 09.011 ... hv high voltage hz hertz ic ... mfs main fused switch mnfs main non-fused switch mlo main lug only mtd mounted mtg mounting

architecture studio

architecture

327 pricketts fort road

fairmont, wv 26554

ph: 304.292.7750

PO Box 360

mchenry, maryland 21541

ph: 301.387.3380

fx: 301.387.3382

PROJECTdata

Pro

ject

Add

ress

Client Signature for Phase Completion

Schematic Design

Design Development

Progress

Bidding

Building Permit

Construction Documents

5/31/2016 10:34:57 AMProject Number: 09.011

16.0

16 W

MH

S -

Ch

apm

an-J

acks

on/

Pla

stic

s o

ffic

e12

500

Will

owbr

ook

Roa

d

Cum

berla

nd, M

D 2

1502

FIL

EN

AM

E: P

:\2

01

6\1

61

75

10

\B

IM

\ E

6.D

WG

L

AS

T S

AV

ED

B

Y: ( C

SC

HA

RD

T) P

LO

TT

ED

B

Y: ( C

SC

HA

RD

T) O

N Ju

l 1

1, 2

01

6 - 3

:1

8p

m

LWA PROJECT NO: 16-175-10

21493 02/08/17

E5

ELECTRICALSPECIFICATION

NONE

ELECTRICAL SPECIFICATION

1. GENERAL:

A. CONTRACTOR SHALL THOROUGHLY EXAMINE THE PREMISES AND OBSERVE ALL CONDITIONS UNDER

WHICH THE WORK WILL BE PERFORMED. NO ALLOWANCES WILL BE MADE FOR ERRORS OR NEGLIGENCE

IN THIS RESPECT.

B. COORDINATE ALL WORK WITH THE PROJECT SCHEDULE. WORK SHALL BE COORDINATED AND

SCHEDULED IN ADVANCE AND APPROVED BY THE OWNER'S REPRESENTATIVE.

C. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, AND SERVICES NECESSARY FOR THE COMPLETION OF ALL

ELECTRICAL WORK SHOWN ON THE DRAWINGS AND HEREIN SPECIFIED.

D. THE CONTRACTOR SHALL COORDINATE WITH OTHER TRADES TO ESTABLISH LIMITS OF RESPONSIBILITY

AND ASSURE THAT ALL WORK AND EQUIPMENT WILL BE PROVIDED WITH THE PROPER SERVICES

CONNECTED AND READY TO USE.

E. ALL ELECTRICAL WORK SHALL MEET THE REQUIREMENTS AS SET FORTH IN THE NATIONAL ELECTRICAL

CODE AND APPLICABLE STATE AND LOCAL CODES. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL

PERMITS AND CERTIFICATES.

F. ALL MATERIALS SHALL BE NEW AND SHALL BE SUITABLE FOR THE CONDITIONS AND DUTIES IMPOSED ON

THEM AFTER INSTALLATION. ALL MATERIALS SPECIFIED HEREIN OR USED SHALL HAVE THE U.L. LABEL.

G. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF

SYSTEMS AND WORK INCLUDED IN THE CONTRACT. DO NOT SCALE THE DRAWINGS. WHERE APPLICABLE,

CONSULT THE ARCHITECTURAL DRAWINGS AND DETAILS FOR EXACT LOCATION OF STRUCTURE,

FURNITURE, AND EQUIPMENT; WHERE SAME ARE NOT DEFINITELY LOCATED BY DIMENSIONS, OBTAIN THIS

INFORMATION FROM THE ENGINEER.

H. ALL AREAS ADJACENT TO THE CONSTRUCTION SITE WILL REMAIN OCCUPIED. CONTRACTOR SHALL

MAINTAIN ALL ELECTRICAL SERVICE TO THESE AREAS AS INDICATED, AS REQUIRED, AND AS DIRECTED BY

THE OWNER'S REPRESENTATIVE IN THE FIELD.

2. CODES, REGULATIONS AND PERMITS:

A. PERFORM ALL WORK AND PROVIDE ALL MATERIALS IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE,

NFPA REGULATIONS AND ALL STATE AND MUNICIPAL ORDINANCES, CODES AND REGULATIONS HAVING

JURISDICTION. PERFORM WORK IN ACCORDANCE WITH WMHS STANDARDS.

B. THE ELECTRICAL INSTALLATION SHALL BE INSPECTED AND APPROVED BY THE GOVERNMENT AGENCY

HAVING JURISDICTION. INSPECTIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

3. SHOP DRAWINGS:

A. WITHIN 5 DAYS AFTER AWARD OF THE CONTRACT, THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER A

LIST OF MANUFACTURERS AND SUBCONTRACTORS, AND A PRELIMINARY DELIVERY SCHEDULE OF ALL

MATERIALS AND EQUIPMENT TO BE USED ON THIS PROJECT.

B. SUBMIT FOR APPROVAL SIX (6) SETS OF SHOP DRAWINGS ON THE FOLLOWING ITEMS OF EQUIPMENT:

WIRING DEVICES, LIGHTING FIXTURES, PANELBOARDS.

C. SUBMIT FOR APPROVAL SIX (6) SETS OF MANUFACTURER'S LISTS WITH CATALOG NUMBERS OR TYPE OF

THE FOLLOWING EQUIPMENT AND MATERIAL BEFORE THE ITEMS IN QUESTION ARE ORDERED OR

INSTALLED: WIRE, CONDUIT, OUTLET BOXES.

4. PROTECTION OF EXISTING WORK:

A. WHEN WORKING IN AND AROUND THE EXISTING BUILDING, EXTREME CARE SHALL BE EXERCISED WITH

REGARD TO PROTECTION OF EXISTING WORK. CORRECT ALL DAMAGE TO EXISTING WORK TO THE

SATISFACTION OF THE OWNER'S REPRESENTATIVE.

5. INTERRUPTION OF EXISTING UTILITIES :

A. THE TIME AND DURATION OF ALL OUTAGES MUST BE SCHEDULED AND APPROVED IN ADVANCE BY THE

OWNER'S REPRESENTATIVE.

B. THE OWNER RESERVES THE RIGHT TO SCHEDULE AN OUTAGE AT ANY PERIOD OF THE DAY OR NIGHT OR

ANY DAY OF THE WEEK, INCLUDING SATURDAYS, SUNDAYS, OR HOLIDAYS.

6. ALTERATIONS AND DEMOLITION:

A. Portions of the existing building WILL be occupied by the Owner during construction, and the electrical systems

associated with these portions of the building shall be kept in operation as much as possible. The duration of outages

shall be kept to a minimum and they shall be scheduled and approved in advance by the Owner. Where necessary,

provide temporary connections as required to maintain service.

B. In areas to be renovated, remove the entire electrical installation except those portions indicated to be reused. All

unused raceways and wiring exposed after demolition shall be removed back to the nearest point of concealment.

Unused wiring shall be removed back to the source of voltage for the unused segment. All electrical equipment

removed under this contract and not reused shall be disposed of as directed by the Owner.

C. Where existing electrical systems pass through renovated areas to serve other portions of the building, they shall be

suitably relocated or modified to avoid conflict with new work. Existing outlet, junction and pull boxes, etc. and

equipment in areas to be renovated and requiring access for service, operation, etc. shall remain "readily accessible" as

required by the NEC.

D. The Contractor shall verify the exact location and rating of all existing system components in the field before starting

any work.

7. EQUIPMENT START-UP AND INITIAL OPERATION :

A. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PLACE EACH ITEM OF EQUIPMENT INSTALLED BY HIM IN

OPERATING CONDITION, INCLUDING ALL INTERFACE WITH DIVISION 15, AND SPECIALTY SYSTEMS SUCH AS

FIRE ALARM, SECURITY, ETC.

8. CUTTING AND PATCHING:

A. CUTTING AND PATCHING ASSOCIATED WITH BOTH NEW AND EXISTING WORK SHALL BE PERFORMED IN A

NEAT AND WORKMANLIKE MANNER. EXISTING SURFACES WHICH ARE DAMAGED BY THE CONTRACTOR

SHALL BE REPAIRED OR PROVIDED WITH NEW MATERIALS. STRUCTURAL MEMBERS SHALL NOT BE CUT

OR PENETRATED UNLESS APPROVED BY THE ENGINEER.

B. ALL PATCHING SHALL BE DONE WITH MATERIALS AND METHODS SIMILAR TO EXISTING ADJACENT WORK,

SUBJECT TO APPROVAL OF THE OWNER AND DECISION SHALL BE FINAL.

9. ACCESSIBILITY:

A. LOCATE ALL EQUIPMENT WHICH MUST BE SERVICED, OPERATED OR MAINTAINED IN FULLY ACCESSIBLE

POSITIONS. PULL BOXES AND ACCESS COVERS SHALL BE LOCATED IN A FASHION TO ENABLE MAXIMUM

ACCESSIBILITY.

10. RECORD DRAWINGS:

A. CONTRACTOR SHALL KEEP ACCURATE RECORDS OF ALL DEVIATIONS IN WORK AS ACTUALLY INSTALLED

FROM WORK INDICATED. WHEN WORK IS COMPLETE, MAKE ONE (1) COMPLETE "AS-BUILT" SET OF

MARK-UP PRINTS AND DELIVER TO THE ARCHITECT/ENGINEER FOR APPROVAL.

11. IDENTIFICATION:

A. ALL EQUIPMENT SHALL BE MARKED TO CLEARLY INDICATE IDENTIFICATION NUMBER, FUNCTIONS AND

SPACE OR DUTY SERVED. EQUIPMENT SHALL BE IDENTIFIED USING ENGRAVED LAMINATED PHENOLIC

PLATES, LETTERS SHALL BE MINIMUM 3/4" HIGH WHITE ON SURROUNDING BLACK. PLATES SHALL BE

MOUNTED BY MEANS OF SHEET METAL SCREWS.

12. GUARANTEE:

A. THE ELECTRICAL CONTRACTOR SHALL LEAVE THE ENTIRE ELECTRICAL SYSTEM INSTALLED UNDER THIS

CONTRACT IN PROPER WORKING ORDER AND SHALL WITHOUT ADDITIONAL CHARGE REPLACE ANY WORK

OR MATERIAL WHICH DEVELOPS DEFECTS RESULTING FROM ORDINARY WEAR AND TEAR WITHIN ONE

YEAR FROM DATE OF FINAL ACCEPTANCE.

13. TESTS:

A. THE CONTRACTOR SHALL FURNISH ALL EQUIPMENT AND APPLIANCES NECESSARY FOR TESTING THE

COMPLETE ELECTRICAL SYSTEM. THE TESTS SHALL DEMONSTRATE TO THE SATISFACTION OF THE

ENGINEER AS FOLLOWS:

1. THAT ALL CIRCUITS ARE FREE FROM UNSPECIFIED GROUNDS AND SHORT CIRCUITS.

2. THAT RESISTANCE TO GROUND OF ALL CIRCUITS IS NOT LESS THAN ONE MEGOHM AT 1000 VOLTS

D.C.

3. THAT ALL CIRCUITS ARE PROPERLY CONNECTED AND ARE OPERABLE.

14. BASIC MATERIALS AND METHODS:

A. JUNCTION, OUTLET, AND PULL BOXES :

1. INSTALL JUNCTION OR PULL BOXES WHEREVER REQUIRED TO FACILITATE WIRE PULLING OR

CONNECTION. FABRICATE BOXES FROM 12-GAUGE MINIMUM GALVANIZED STEEL, AND EQUIP WITH

SCREW COVER. SIZE BOX PER NEC. LABEL ALL CIRCUITS INSIDE EACH BOX AND ON CORNER OF

COVER EXTERIOR WITH ONE-HALF INCH HIGH STENCILED LETTERS.

2. ALL BOXES SHALL BE INSTALLED SO THAT COVERS ARE READILY ACCESSIBLE AFTER COMPLETION

OF THE INSTALLATION. JUNCTION BOXES SHALL NOT BE INSTALLED ABOVE SUSPENDED CEILINGS,

EXCEPT WHERE THE CEILING IS OF THE REMOVABLE TYPE OR IF AN ACCESS PANEL IS PROVIDED

CLOSE TO THE BOX.

3. SHEET METAL BOXES SHALL BE ADEQUATELY SUPPORTED TO MAINTAIN SHAPE. LARGER BOXES

SHALL BE ADEQUATELY FORMED OF STRUCTURAL STEEL BRACING WELDED INTO A RIGID ASSEMBLY

TO MAINTAIN ALIGNMENT IN SHIPMENT AND INSTALLATION.

4. OUTLET BOXES SHALL BE FOUR INCHES SQUARE, MINIMUM 14 GAUGE, AS MANUFACTURED BY STEEL

CITY, RACO, NATIONAL, APPLETON, OR APPROVED EQUIVALENT.

B. GROUNDING:

1. PROVIDE GROUNDING CONDUCTORS FOR ALL FEEDERS AND BRANCH CIRCUITS, IN ACCORDANCE

WITH REQUIREMENTS OF THE NATIONAL ELECTRICAL CODES, AND AS SHOWN AND REQUIRED. ALL

GROUNDING AND BONDING CONNECTIONS SHALL BE SOLDERLESS. WELDING OF CONDUIT AND

FITTING WILL NOT BE ALLOWED FOR BONDING PURPOSES.

2. THE REQUIRED EQUIPMENT GROUNDING CONDUCTORS AND STRAPS SHALL BE SIZED AS INDICATED

ON THE DRAWINGS, IN COMPLIANCE WITH N.E.C. TABLE 250-122, WITH MINIMUM SIZE NO. 12 AWG. ALL

EQUIPMENT GROUNDING CONDUCTORS SHALL BE PROVIDED WITH GREEN INSULATION EQUIVALENT

TO THE INSULATION ON THE ASSOCIATED PHASE CONDUCTORS.

3. PROVIDE PANELBOARD BONDING WITH MINIMUM #10AWG GROUNDING CONDUCTOR, BETWEEN

PANELBOARDS OF DIFFERENT SYSTEMS SERVING THE SAME PATIENT CARE VICINITY, IN

ACCORDANCE WITH NEC 517.14. WHERE BONDING CONDUCTOR IS ROUTED OUTSIDE OF ELECTRICAL

ROOMS, INSTALL IN 3/4” CONDUIT.

C. RACEWAYS:

1. ELECTRICAL METALLIC TUBING (EMT): CONFORMING TO ANSI SPECIFICATION C 80.3, AND U.L. 797.

USE SET SCREW TYPE COUPLINGS.

2. FLEXIBLE METALLIC CONDUIT: STEEL, REDUCED WALL TYPE, CONFORMING TO U.L. 1.

3. LIQUID TIGHT FLEXIBLE METAL CONDUIT (LT/FMC): LT/FMC SHALL BE STEEL, REDUCED WALL TYPE,

CONSTRUCTED OF SINGLE STRIP, FLEXIBLE, CONTINUOUS, INTERLOCKED AND DOUBLE WRAPPED

METAL. LT/FMC SHALL HAVE FLEXIBLE PVC LIQUID TIGHT JACKET.

D. 600 VOLT WIRE AND CABLE:

1. PROVIDE ALL WIRE AND CABLE FOR THE ELECTRICAL SYSTEMS AS INDICATED ON DRAWINGS AND/OR

SPECIFIED HEREIN.

2. WIRE SHALL BE AS FOLLOWS:

a. ALL CONDUCTORS SHALL BE SINGLE CONDUCTOR ANNEALED COPPER WITH DUAL RATED NEC

TYPE THHN-THWN INSULATION, CONFORMING TO U.L. 83. WIRING SHALL BE RATED 600 VOLTS.

BRANCH CIRCUIT WIRING, NO. 10 AND SMALLER, CONNECTED TO RECEPTACLES, LIGHTING

FIXTURES, AND SWITCHES SHALL BE SOLID CONDUCTOR. ALL WIRING NO. 8 AWG AND LARGER

SHALL BE STRANDED. WIRING SHALL BE AS MANUFACTURED BY CERRO WIRE, ENCORE WIRE,

INDUSTRIAL WIRE AND CABLE CORPORATION, GENERAL CABLE, OR SOUTHWIRE.

b. MINIMUM SIZE OF BRANCH CIRCUIT WIRE IS NO. 12 AWG.

c. CONDUCTORS SHALL BE FACTORY COLOR CODED IN ACCORDANCE WITH THE EXISTING BUILDING

COLOR CODES.

d. GREEN COLORED INSULATED EQUIPMENT GROUND CONDUCTORS SHALL BE PROVIDED FOR ALL

FEEDERS, AND FOR ALL BRANCH CIRCUITS.

e. PROVIDE WIRE IDENTIFICATION MARKING ON EACH PHASE, NEUTRAL, AND GROUND WIRE AT

EACH ACCESSIBLE POINT ALONG ITS LENGTH. THE "MARKING" SHALL BE AS DEFINED BY THE

CIRCUIT INFORMATION ON THE DRAWINGS.

3. 600V METAL-CLAD HEALTH CARE FACILITIES (HCF) CABLING SHALL BE AS FOLLOWS:

a. PROVIDE METAL-CLAD CABLE, WITH COPPER CONDUCTORS, INSULATION SHALL NEC TYPE THHN.

METALLIC CABLE ARMOR JACKET SHALL BE ALUMINUM, PAINTED GREEN, WITH #10AWG BARE

ALUMINUM SOLID BONDING CONDUCTOR. CABLE SHALL BE AFC MC-STAT PLUS LITE, SOUTHWIRE

HCF MC-AP OR APPROVED EQUAL.

b. MINIMUM SIZE OF BRANCH CIRCUIT WIRE IS NO. 12 AWG.

c. CONDUCTORS SHALL BE FACTORY COLOR CODED IN ACCORDANCE WITH THE EXISTING BUILDING

COLOR CODES.

d. GREEN COLORED INSULATED EQUIPMENT GROUND CONDUCTORS SHALL BE PROVIDED FOR ALL

BRANCH CIRCUITS.

e. PROVIDE WIRE IDENTIFICATION MARKING ON EACH PHASE, NEUTRAL, AND GROUND WIRE AT

EACH ACCESSIBLE POINT ALONG ITS LENGTH. THE "MARKING" SHALL BE AS DEFINED BY THE

CIRCUIT INFORMATION ON THE DRAWINGS.

f. CABLE SHALL INCORPORATE A SEPARATE NEUTRAL CURRENT FOR EACH BRANCH CIRCUIT

CONDUCTOR. NEUTRALS SHALL BE INDIVIDUALLY MARKED ALONG THEIR ENTIRE LENGTH WITH

CORRESPONDING CIRCUIT IDENTIFICATION.

g. HCF CABLE SHALL BE TERMINATED USING APPROVED FITTINGS THAT CORRECTLY BOND THE

CABLE JACKET TO BOXES AND CABINETS IN ACCORDANCE WITH THE NEC AND MANUFACTURER'S

INSTRUCTIONS.

E. WIRING METHODS:

1. INSTALL ALL WIRING IN EMT RACEWAY, MINIMUM SIZE 3/4 INCH UNLESS OTHERWISE SPECIFIED OR

NOTED.

2. IN PATIENT CARE AREAS, HEALTH CARE FACILITIES (TYPE HCF) METAL-CLAD SHALL BE PERMITTED TO

BE INSTALLED IN LIEU OF EMT CONDUIT FOR NORMAL POWER BRANCH CIRCUITS RATED 30 AMPERES

OR LESS, CONCEALED IN WALLS OR ABOVE CEILINGS ONLY. HCF SHALL NOT BE UTILIZED FOR

BRANCH CIRCUITS FROM ISOLATED POWER PANELS.

3. MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED. WHERE MULTIPLE BRANCH CIRCUITS ARE

INDICATED TO BE ROUTED IN THE SAME RACEWAY OR CABLE ASSEMBLY, PROVIDE A SEPARATE

NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT, CONTINOUS FROM SOURCE TO UTILIZATION

POINT. SHARED NEUTRALS ARE NOT PERMITTED.

4. EACH CONDUIT OR CABLE ASSEMBLY SHALL CONTAIN NOT MORE THAN THREE SINGLE-PHASE

BRANCH CIRCUITS, OR ONE FEEDER OR THREE-PHASE BRANCH CIRCUIT.

5. UNLESS OTHERWISE NOTED, CONCEAL ALL WIRING IN FINISHED SPACES AND ELSEWHERE AS

NECESSARY TO MEET REQUIREMENTS FOR FLUSH OUTLETS. IN UNFINISHED AREAS, ALL WIRING

SHALL BE INSTALLED TIGHT TO STRUCTURE, WITH THE GREATEST POSSIBLE CLEARANCE BELOW

RACEWAYS.

6. MAINTAIN SIX INCH MINIMUM CLEARANCE BETWEEN ALL WIRING AND PARALLELS RUNS OF HOT

WATER PIPES.

7. INSTALL CONDUITS SO AS TO INSURE AGAINST THE COLLECTION OF TRAPPED CONDENSATION,

ARRANGED TO BE FREE FROM TRAPS WHEREVER POSSIBLE. USE SCREW OR PUSH-ON CAPS TO

PREVENT THE LODGEMENT OF FOREIGN PARTICLES IN THE CONDUITS, FITTINGS AND BOXES DURING

CONSTRUCTION.

8. THE GENERAL ARRANGEMENT OF PANELBOARDS AND OTHER EQUIPMENT, AS SHOWN, IS

DIAGRAMMATIC AND APPROXIMATELY CORRECT AS TO LOCATIONS. WHERE MINOR CHANGES ARE

REQUIRED BECAUSE OF STRUCTURAL CONDITIONS OR FOR THE CONVENIENCE OF THE OWNER,

SUCH CHANGES ARE TO BE MADE WITHOUT ADDITIONAL EXPENSE TO THE OWNER. THE

CONTRACTOR IS RESPONSIBLE FOR THE ACCURATE LOCATION OF PANELBOARDS AND SIMILAR

DEVICES, WITH RESPECT TO EQUIPMENT, DOORS, PARTITIONS, CABINETS AND THE FINISHED WORK

OF OTHERS. NO EXTRA WILL BE ALLOWED ON ACCOUNT OF MOVING WORK UNDER THIS SECTION TO

AVOID INTERFERENCE WITH WORK OF OTHER CONTRACTORS OR WORK UNDER OTHER SECTIONS.

9. FOR CONNECTIONS TO MOTORS AND VIBRATING EQUIPMENT, USE FLEXIBLE METALLIC CONDUIT.

10. FOR FINAL CONNECTIONS TO CEILING-MOUNTED LIGHTING FIXTURES, USE METAL CLAD CABLE (HCF

IN PATIENT CARE AREAS), MAXIMUM 6'-0” LENGTH FROM NON-FLEXIBLE RACEWAY BOX TO FIXTURE.

11. FOR CONNECTIONS TO MOTORS AND VIBRATING EQUIPMENT IN EXTERIOR OR WET LOCATIONS, USE

LIQUID TIGHT FLEXIBLE METALLIC CONDUIT.

G. FASTENINGS AND SUPPORTS:

1. PIPE STRAPS AND HANGER RODS SHALL BE FASTENED TO CONCRETE BY MEANS OF INSERTS OR

EXPANSION BOLTS, TO HOLLOW MASONRY BY MEANS OF TOGGLE BOLTS. WOODEN PLUGS AND

SHIELDS SHALL NOT BE USED FOR FASTENING PIPE STRAPS AND HANGERS. IN LIEU OF INSERTS OR

EXPANSION BOLTS, POWER-DRIVEN FASTENERS MAY BE USED TO ATTACH STRAPS AND HANGER

RODS TO CONCRETE. ALL U-BOLTS, CLAMPS, ATTACHMENTS, AND OTHER HARDWARE NECESSARY

FOR HANGER ASSEMBLY, AND FOR SECURING HANGER RODS AND CONDUIT SHALL BE PROVIDED.

2. ALL CONDUITS SHALL BE SECURELY AND INDEPENDENTLY SUPPORTED SO THAT NO STRAIN WILL BE

TRANSMITTED TO OUTLET BOX AND PULL BOX SUPPORTS, ETC. SUPPORT SHALL BE RIGID ENOUGH

TO PREVENT DISTORTION OF CONDUITS DURING WIRE PULLING.

3. INDIVIDUAL HORIZONTAL CONDUITS SHALL BE SUPPORTED BY ONE-HOLD PIPE STRAPS OR SEPARATE

PIPE HANGERS FOR SIZES 1-1/2 INCH AND SMALLER, AND BY SEPARATE PIPE HANGERS FOR LARGER

SIZES. SPRING STEEL FASTENERS SHALL BE SPECIFICALLY DESIGNED FOR SUPPORTING SINGLE

CONDUITS. UNLESS OTHERWISE SPECIFIED, WIRE SHALL NOT BE USED AS A MEANS OF SUPPORT.

4. WHERE TWO OR MORE HORIZONTAL CONDUITS RUN PARALLEL AND AT THE SAME ELEVATION, THEY

SHALL BE SUPPORTED ON MULTIPLE (TRAPEZE) PIPE HANGERS. EACH CONDUIT SHALL BE SECURED

TO THE HORIZONTAL HANGER MEMBER BY A U-BOLT, ONE-HOLE STRAP OR OTHER SPECIALLY

DESIGNED AND APPROVED FASTENER.

5. SUPPORTS FOR HORIZONTAL CONDUITS SHALL BE SPACED NOT MORE THAN 8 FEET APART, WITH

NOT LESS THAN TWO SUPPORTS FOR EACH 10-FOOT STRAIGHT LENGTH AND ONE SUPPORT NEAR

EACH ELBOW OR BEND.

H. LIGHTING FIXTURES:

1. ALL LAMPS SHALL BE AS INDICATED ON THE DRAWINGS. LAMPS SHALL BE AS MANUFACTURED BY

SYLVANIA, GENERAL ELECTRIC OR PHILIPS.

2. FIXTURES SHALL BE AS INDICATED ON THE LIGHTING FIXTURE SCHEDULE.

3. ALL MATERIALS, ACCESSORIES, AND OTHER RELATED FIXTURE PARTS HEREIN MENTIONED SHALL

CONFORM TO THE REQUIREMENTS OF THE DRAWINGS, SPECIFICATIONS, AND THE AGENCIES

HERETOFORE MENTIONED. THEY SHALL BE NEW AND FREE FROM DEFECTS WHICH IN ANY MANNER

MAY IMPAIR THEIR CHARACTER, APPEARANCE, STRENGTH, DURABILITY, AND FUNCTION, AND SHALL

BE OF PRIME QUALITY INTENDED FOR THEIR RESPECTIVE PURPOSE, AND EFFECTIVELY PROTECTED

FROM ANY DAMAGE OR INJURY FROM THE TIME OF FABRICATION TO THE TIME OF DELIVERY AND

UNTIL FINAL ACCEPTANCE OF THE WORK. THE ABOVE ITEMS SHALL MEET WITH THE APPROVAL OF

THE ENGINEER WHO RESERVES THE RIGHT OF REJECTION PRIOR TO OR AFTER INSTALLATION IF

FOUND NOT TO BE IN STRICT ACCORDANCE WITH THE TRUE INTENT OF THE CONTRACT.

4. ALL FIXTURES SHALL BE COMPLETELY WIRED AT THE FACTORY.

5. THE CONTRACTOR SHALL FURNISH AND INSTALL ANY NECESSARY EXTRA CHANNELS, SUPPORT

WIRES OR RODS, ETC., TO PROVIDE A STRUCTURALLY-SOUND SYSTEM. FIXTURES SHALL BE

SUPPORTED INDEPENDENTLY OF CEILING GRID. FIXTURES SHALL NOT BE SUSPENDED FROM

DUCTWORK, PIPING, OR APPURTENANCES THERETO.

6. THE FIXTURES SHALL BE MANUFACTURED IN STRICT ACCORDANCE WITH THE APPROPRIATE AND

CURRENT REQUIREMENTS OF THE UNDERWRITER' LABORATORIES, INC.'S "STANDARD FOR SAFETY"

AND OTHERS AS THEY MAY BE APPLICABLE. A. U.L. LISTING SHALL BE PROVIDED FOR EACH FIXTURE

TYPE, AND THE APPROPRIATE LABEL OR LABELS SHALL BE AFFIXED TO EACH FIXTURE IN A POSITION

CONCEALING IT FROM NORMAL VIEW.

7. BEFORE ANY OF THE FIXTURES ARE FABRICATED, COMPLETE SHOP DRAWINGS SHALL BE SUBMITTED

FOR APPROVAL.

8. PRISMATIC LENSES FOR RECESSED TROFFERS SHALL BE 0.125" THICK, PATTERN 12 MODEL KSH-12 BY

KSH, INC. (ICI ACRYLICS).

9. LIGHT LEAKS BETWEEN FIXTURE DOORS AND FRAMES WILL NOT BE TOLERATED.

10. LAY-IN LIGHTING FIXTURES SHALL BE SUPPORTED INDEPENDENTLY OF THE CEILING GRID. GRID

CLIPS ARE NOT ACCEPTABLE AS A MEANS OF SUPPORT.

I. BALLASTS:

1. ALL FLUORESCENT BALLASTS SHALL BE "CLASS P" TYPE AS DESIGNATED BY U.L., AND SHALL MEET

THE REQUIREMENTS OF SECTION 410-73 (3) OF THE NATIONAL ELECTRICAL CODE. BALLASTS SHALL

HAVE ETL AND CBM CERTIFICATION LABELS AND SHALL BE HIGH POWER FACTOR ELECTRONIC TYPE,

BETTER THAN CLASS A SOUND RATING, AS MANUFACTURED BY UNIVERSAL, ADVANCE,

OSRAM/SYLVANIA, OR VALMONT. BALLASTS FOR COMPACT FLUORESCENT LAMPS SHALL BE

ELECTRONIC, AS MANUFACTURED BY ENERGY SAVINGS INC., UNIVERSAL, OR ROBERTSON. MAXIMUM

TOTAL HARMONIC DISTORTION (THD) FOR ALL BALLASTS SHALL BE 10%.

2. DIMMING FLUORESCENT BALLASTS SHALL BE LUTRON HI-LUME (1% MINIMUM DIMMING LEVEL) FOR

ALL LAMP APPLICATIONS WHERE AVAILABLE. FOR COMPACT FLUORESCENT APPLICATIONS WHERE

HI-LUME IS NOT AVAILABLE, BALLASTS SHALL BE LUTRON COMPACT SE (5% MINIMUM DIMMING LEVEL).

3. ALL BALLASTS SHALL BE COVERED BY A TWO (2) YEAR WARRANTY AGAINST DEFECTS. WARRANTY

SHALL INCLUDE PAYMENT FOR NORMAL LABOR COSTS OF REPLACEMENT OF IN WARRANTY

BALLASTS.

4. LUMINAIRE ASSEMBLIES, INCLUDING BALLASTS, SHALL BE REASONABLY DEVOID OF OBJECTIONABLE

"HUM," IN THE NORMAL AMBIENT NOISE OF THE APPLICATION, AS JUDGED BY THE ENGINEER.

J. WIRING DEVICES:

1. SWITCHES SHALL BE 277V, 20A, QUIET TYPE SPECIFICATION GRADE, HUBBELL 1221/1223/1224.

2. RECEPTACLES SHALL BE HOSPITAL GRADE, 125V, 20A, NEMA 5-20R OR AS INDICATED, HUBBELL

SERIES 8300.

3. GFI RECEPTACLES SHALL BE HOSPITAL GRADE, 125V, 20A, NEMA 5-20R OR AS INDICATED, HUBBELL

SERIES GF8300.

4. WALL PLATES SHALL BE STAINLESS STEEL WITH BEVELED EDGES.

5. WALLBOX DIMMERS SHALL BE LUTRON NOVA-T SERIES.

6. Single level lighting control wall mounted occupancy sensor switch (O): Leviton ODS10-ID.

7. Dual level control lighting wall mounted occupancy sensor switch (O2): Leviton ODSOD-ID.

8. Ceiling mounted ultrasonic occupancy sensor with rectangular field of view (U): Leviton OSC20-UOW.

9. Ceiling mounted ultrasonic occupancy sensor with single sided field of view (U2): Leviton OSC20-UOW.]

10. Ceiling mounted infrared occupancy sensor: Leviton OSC15-IOW.

11. Lighting control relay for use with occupancy sensors shall be rated 20A at 120 or 277 volts, with isolated NO/NC

HVAC interface relay, Leviton “Power Pack” model OSP20-RD0.

12. NORMAL POWER SWITCHES, EMERGENCY POWER SWITCHES, AND NORMAL POWER RECEPTACLES

SHALL BE IVORY COLOR. EMERGENCY POWER RECEPTACLES SHALL BE RED.

13. PROVIDE ENGRAVING ON RECEPTACLE COVER PLATES INDICATING BRANCH CIRCUIT DESIGNATION

AND PANELBOARD OF ORIGIN. COORDINATE ENGRAVING STANDARDS WITH THE OWNER TO MATCH

FACILITY STANDARDS.

K. SAFETY SWITCHES:

1. SAFETY SWITCHES SHALL BE FUSED OR UNFUSED TYPES AS INDICATED, HEAVY DUTY, ENCLOSED IN

NEMA 1 STEEL ENCLOSURES UNLESS OTHERWISE INDICATED.

2. SHORT CIRCUIT WITHSTAND RATINGS FOR FUSED SAFETY SWITCH UNITS SHALL BE MINIMUM 100,000

AMPS RMS WHEN USED WITH CLASS R OR J FUSES. ALL FUSED SAFETY SWITCHES SHALL

ACCOMMODATE CURRENT LIMITING "R" REJECTION FEATURE FUSES.

3. SWITCHES SHALL HAVE PROVISIONS FOR NOT LESS THAN TWO EXTERNAL PADLOCKS. UNITS SHALL

BE AS MANUFACTURED BY SQUARE D, EATON, OR GENERAL ELECTRIC.

L. ENCLOSED CIRCUIT BREAKERS:

1. ENCLOSED CIRCUIT BREAKERS SHALL HAVE THE VOLTAGE, AMPERE RATING, AND INVOICE OF POLES

AS INDICATED. CIRCUIT BREAKERS SHALL BE QUICK MAKE, QUICK BREAK, TRIP-FREE OF THE HANDLE

AND CALIBRATED FOR 40°C AMBIENT TEMPERATURE. CIRCUIT BREAKERS SHALL BE COMMON TRIP

WITH HANDLES CLEARLY INDICATING WHEN THE BREAKER IS "ON" OR "OFF", FRONT OPERABLE,

CAPABLE OF BEING PADLOCKED IN THE "ON" OR "OFF" POSITION.

2. ENCLOSURES SHALL BE GENERAL PURPOSE, NEMA 1, UNLESS OTHERWISE INDICATED. ENCLOSED

CIRCUIT BREAKERS SHALL BE AS MANUFACTURED BY SQUARE D, EATON, OR GENERAL ELECTRIC.

M. PANELBOARDS AND LOAD CENTER:

1. ALL PANELBOARDS SHALL BE SQUARE D, WITH RATINGS AS INDICATED ON THE DRAWINGS. THE

CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS AND CAPACITY AS INDICATED IN THE DRAWINGS.

2. ALL CIRCUIT BREAKERS SHALL BE OF THE BOLT-ON TYPE. ALL PANELBOARD BUS SHALL BE COPPER.

PROVIDE A 100% NEUTRAL AND 50% GROUND BUS IN EACH PANELBOARD.

3. PROVIDE A TYPEWRITTEN SCHEDULE OF CIRCUITS FOR ALL PANELBOARDS, INCLUDING EXISTING

PANELS WHICH ARE MODIFIED. CONTRACTOR SHALL LABEL ALL CIRCUITS IN THE PANELBOARD,

IDENTIFYING ALL REMOVED CIRCUITS AS "SPARE" AND TRACE ALL EXISTING CIRCUITS AS REQUIRED

TO PROVIDE AN "AS-BUILT" PANELBOARD DIRECTORY.

N. TELEPHONE OUTLETS AND DATA RACEWAY SYSTEMS :

1. TELEPHONE AND DATA SYMBOLS ON THE DRAWINGS INDICATE A VARIETY OF POINT-OF-USE OUTLETS

FOR FUTURE WIRING AND "JACKS" PROVIDED BY OTHERS. WHERE EACH SYMBOL IS INDICATED,

PROVIDE A 4-11/16" X 4-11/16" X 2-1/8" DEEP MINIMUM OUTLET BOX WITH SINGLE GANG STAINLESS

STEEL COVER PLATE (BLANK) AND EXTEND A 1" RACEWAY TO CEILING SPACE ABOVE.

2. TELEPHONE OUTLET BOXES SHALL BE PROVIDED WHERE INDICATED ON THE DRAWINGS. STAINLESS

STEEL, BLANK WALL PLATES WITH BEVELED EDGES SHALL BE PROVIDED FOR OUTLETS. BOXES

SHALL BE PROVIDED AS SPECIFIED HEREIN.

3. RACEWAYS SHALL BE PROVIDED AS SPECIFIED HEREIN.

O. FIRE ALARM:

1. FIRE ALARM DEVICES SHALL BE COMPATIBLE WITH EXISTING SIMPLEX SYSTEM. PROVIDE ALL

REQUIRED FIRE ALARM CONTROL PANEL MODIFICATIONS AND ADDITIONAL HARDWARE AS REQUIRED

TO ACCOMMODATE THE DEVICES INSTALLED UNDER THIS PROJECT..

2. FLASHING LIGHT UNITS SHALL BE MODEL SW SPECTRALERT SERIES WHITE, FLUSH MOUNTED,

MEETING OR EXCEEDING THE REQUIREMENTS OF THE AMERICANS WITH DISABILITIES ACT OF 1990.

LAMP SHALL BE XENON STROBE TYPE, MINIMUM 15 CANDELA INTENSITY, FLASH RATE BETWEEN 1 HZ

AND 3 HZ.

3. COMBINATION CHIME / STROBE UNITS SHALL BE WHEELOCK MODEL CH70-MCW, WITH FIELD

SELECTABLE 15/30/75/110 CD FLASHING STROBE LIGHT AND 83DB / 10 FEET CHIME ADJUSTABLE FROM

800 HZ TO 1200 HZ TONE.

4. STROBE OPERATION SHALL BE SYNCHRONIZED WHERE REQUIRED BY ADA AND NFPA 72. IF

NECESSARY, MODIFY EXISTING NOTIFICATION APPLIANCE OPERATION TO PROVIDE REQUIRED

SYNCHRONIZATION.

5. DUCT DETECTORS SHALL BE [MODEL SDX 751] INTELLIGENT PHOTOELECTRIC SMOKE SENSOR, WITH

MATCHING DUCT HOUSING AND SAMPLING TUBE.

6. REMOTE POWER SUPPLIES SHALL BE FCPS-24, 6 AMPERES AT FULL LOAD, 2 CLASS “A” OR FOUR

CLASS “B” NOTIFICATION APPLIANCE CIRCUITS, BATTERY, AND CHARGER. PROVIDE SMOKE

DETACTOR AT EACH REMOTE POWER SUPPLY.

7. PROVIDE SYSTEM WIRING TO DEVICES IN METAL-CLAD FPLP PLENUM RATED FIRE ALARM CABLE, RED

ALERT BY SOUTHWIRE OR APPROVED EQUAL. VERIFY CAPACITY OF EXISTING WARNING DEVICE

CIRCUIT SERVING THIS AREA AND EXTEND TO DEVICES OR PROVIDE NEW WARNING CIRCUITS AS

APPLICABLE.

8. COORDINATE SYSTEM OUTAGES WITH THE OWNER. DEMONSTRATE OPERATION OF SYSTEM IN

PRESENCE OF THE OWNER.

9. THE CONTRACTOR SHALL FURNISH THE SERVICES OF THE OWNER'S EXISTING FIRE ALARM

MAINTENANCE COMPANY TO RE-CERTIFY THE FIRE ALARM SYSTEM.

10. THE CONTRACTOR SHALL FURNISH ALL DRAWINGS, CALCULATIONS, DOCUMENTATION, ETC. AS

REQUIRED BY THE LOCAL CODE AUTHORITY AND OBTAIN ALL PERMITS AND INSPECTIONS. LEACH

WALLACE ASSOCIATES DOES NOT FURNISH SEALED/CERTIFIED DRAWINGS FOR THE PURPOSES OF

OBTAINING A FIRE ALARM PERMIT.

“END OF SECTION”