Modeling Energy
Consumption in Religious
Establishments
Franco Morelli
Hyoungsub Kim
The church is located amongst a community
of residential homes
• College Station, TX
• ASHRAE Climate Zone 2A – Hot
&Humid
• Between 6,000 and 9,000 CDD
The building has a 24,864 ft2 footprint. Community
meeting areas in center. Classrooms and ,offices on
outside.
The buildings have several architectural
features that make modeling challenging, yet
interesting
• Cultural Hall
• Basketball Court
• Stage
• Divider
• Approx. 53’ x 79’ x 20’
• Chapel
• Approx. 53’ x 53’ x 20’
• 2 Tinted glass
doorways lead to
vestibule
A couple more interesting architectural
features
• Transformed Rooms
with Dividers
• Several Self
Contained Rooms
• 2 Vestibules
• 3 Foyers
A couple of energy consuming features of the
building
• Tankless Water
Heating
• Bathrooms
• Baptismal Font
• T8 and T12 Lighting
The buildings use several traditional, vapor
compression split systems for cooling
There are 10 air handles supplying
conditioned air to 10 zones.
Building Layout
Floor Plan Section Plan
Two Parts : 1. Cultural Hall & Chapel
2. Office & Hallway
Zone
EnergyPlus Model
1. HVAC Template_1 Zone
2. HVAC Template_9 Zone
3. Chiller_1 Zone
4. Chiller_9 Zone
1 Zone 9 Zone
HVAC Duct
SketchUp Model
Axonometric Drawing
Schedule
Occupancy
1. Chapel & Cultural hall
(Weekly & Daily)
2. Office
(Weekly & Daily)
Lighting & Equipment
1. Weekly
2. Daily
60% 90%
Results
0.00
5000.00
10000.00
15000.00
20000.00
25000.00
30000.00
35000.00
1 2 3 4 5 6 7 8 9 10 11 12
with attic [kWh]
without attic [kWh]
Measured data(kWh)
Baseline_Template_1 Zone
VS
Attic Without Attic
100% 150%
100% 230%
Total
December
Baseline_Template_9 Zone
(initial result)
Initial result > Measured data : 1.7 times
Internal Gains
People : 0.05 person/m^2 (office)
0.75 person/m^2 (chapel)
Lighting : 10 W/m^2
Equipment : 8.9 W/m^2
0.00
5000.00
10000.00
15000.00
20000.00
25000.00
30000.00
35000.00
40000.00
1 2 3 4 5 6 7 8 9 10 11 12
Initial [kWh]
Measured data [kWh]
Baseline_Template_9 Zone
(Calibration)Schedules
Chapel : weekly, daily
Office : weekly, dailyFinal result < Measured data : 10%
0.00
5000.00
10000.00
15000.00
20000.00
25000.00
1 2 3 4 5 6 7 8 9 10 11 12
calibration [kWh]
Measured data [kWh]
0.00
5000.00
10000.00
15000.00
20000.00
25000.00
1 2 3 4 5 6 7 8 9 10 11 12
1zone [kWh]
9zone [kWh]
Bill(kWh)
Baseline_Template_9 Zone
Final result (9 zone) < Measured data : 10%
Final result (1 zone) < Measured data : 8.4%
; except March, July : 12%
; except March, July : 12%
The energy efficiency improvements
The energy efficiency improvements
0.00
5000.00
10000.00
15000.00
20000.00
25000.00
1 2 3 4 5 6 7 8 9 10 11 12
baseline[kWh]
Insulation [kWh]
Improve Insulation : exterior wall ( 50mm 76mm )
roof insulation ( X 50mm ) 4 % improvement
0.00
5000.00
10000.00
15000.00
20000.00
25000.00
1 2 3 4 5 6 7 8 9 10 11 12
baseline [kWh]
Window [kWh]
Improve window : clear 3mm / Air 13mm / clear 3mm
Triple LoE glass 2% improvement
The energy efficiency improvements
0.00
5000.00
10000.00
15000.00
20000.00
25000.00
1 2 3 4 5 6 7 8 9 10 11 12
baseline [kWh]
Insul+Win [kWh]
6% improvement
The energy efficiency improvements
Improve insulation : 76 mm insulation
Improve window : Triple LoE glass
0.00
5000.00
10000.00
15000.00
20000.00
25000.00
1 2 3 4 5 6 7 8 9 10 11 12
baseline [kWh]
Insul+Win+Orient
The energy efficiency improvements (orientation)
1% improvement
Total : 7 %
Southeast South
Chiller System Simulation Comparison
Comparison of billed energy usage with
chilled water HVAC energy usage for single
zone simulation
Comparison of split HVAC with chilled water
HVAC energy usage for single zone
simulation
Comparison of billed energy usage with chilled water HVAC energy usage for 9 zone simulation
Comparison of split HVAC with chilled water HVAC energy usage for 9 zone simulation