autogen™ el icd, autogen™ mini icd, dynagen™ el icd, dynagen
Dynagen
description
Transcript of Dynagen
www.dynagen.ca | 1-888-396-2436
Genset Control PanelsDiesel & Gas Engine ControllersAutomatic Transfer Switches
PRODUCT CATALOG2
010
Controller Selection ChartUse our engine and genset controller selection chart to choose the best control module for your application. For a complete list of features, functions, and ratings, please refer to the applicable catalog page shown below.
ES52 ES52 GSC100 GSC200 GSC300 GCP300 GSC400 (special)
CatalogPage 7 7 3 5 9 11 12EngineCompatibility: Standard yes yes yes yes yes yes yes Electronic(J1939) - - - - - - yesAnalogACMeters - - - - - yes -SpeedSignalTypes: GensetMainsOutput yes opt yes yes yes yes yes MagneticPickup yes opt - - - - yes AltTach yes opt - - - - yes12Vand24Vcompatibility yes yes - yes yes yes yesBuilt-inAutomotivePlug-inRelays yes yes - - yes yes yesConfigurationMethod: Manual yes yes - - yes yes yes FixedSettings - yes yes - - - - Computer - - - yes yes yes yesBuilt-inAuto/Off/TestSwitch - - - yes yes yes yesTimers Pre-heat yes yes - yes yes yes yes Mid/Post-heat - yes - yes yes yes yes Cool-down - yes yes yes yes yes yes Warm-up yes yes - yes yes yes yes Delay-to-start yes yes yes yes yes yes yes Energize-to-Stop - - - yes yes yes yes EngineExerciser - - - yes - - yesFailuresandWarnings Overspeed,LoOil,HiTemp,Overcrank yes yes yes yes yes yes yes Underspeed - yes yes yes - - yes LowBattery - - yes yes yes yes yes FuelLevel - - - - yes yes yes Over/UnderVolts/Freq/Current - - - - - -yes AuxiliarySwitchedInputs 1 1 - 2 1 1 8AuxiliarySwitchedOutputs 1 1 - 2 1 1 9AnnunciatorOutputs 6 6 8 - 8 8 8AutostartonLowBatteryFunction - - - - - - yesEventLog - - - - - - yesDummyLoadFunction - - - - - - yesPull/HoldCoilOutput - yes - - - - -MomentaryStart/StopInputs - yes - - - - -NFPA110Compliant - - - - - - yesModbusport - - - - - - yesInternet/Wirelessready - - - - - - yesPhotocellinput - yes - - - - - - - - yes Recognized yes yes yes Component
With Basic Indicator Lamps With Instrument Read-Out
BasicAutostart AutoMains Autostart Autostartw/Engine Failure(transfer w/Engine Instruments&ACMetering
1www.dynagen.ca | 1-888-396-2436
GSC100 Autostart Controller Low Cost OEM solution for Small Gensets
Page 3
GSC200 Genset Controller Auto Mains Failure
Single or 3-Phase
Page 5
ES52 Autostart Engine Controller For all Engines and Gensets
Page 7
GSC300 Digital Genset Controller Includes 6 Engine Instruments
Page 9
GSC400Plus Digital Genset ControllerDisplays AC Volts & Amps
Standard or Electronic Engines
Page 12
GSC400Plus Accessories:NFPA110 Remote Annunciator
Remote Genset Monitoring
Page 16
Vigilant Automatic Transfer Switches 100A thru 1250A
Single or 3-Phase
Page 20
Vigilant Load Center 100A Residential ATS 100A Automatic Transfer Switch with Built-in
Breaker Panel
Page 23
Custom OEM Solutions Page 25
Contents
2PRODUCT CATALOG2
010
All catalog products carry a 5-year warranty.Having accumulated research data on the durability of our products over millions of operational hours in the field, we have the highest confidence in providing a full five years of warranty coverage on everything we build.*
Power controls you can trust.Our manufacturing plants manage product assembly in an experienced ISO9001-2000 environment giving you assurance of continued high quality DynaGen products.
Electronics assembly facilities in Nova Scotia, Canada
Transfer switch assembly plant and warehouse in Canton, Ohio
Toll-free technical support. 1-888-DYNAGEN (1-888-396-2436)We offer one toll-free number for all your technical support and applications questions.
When you call DynaGen you get access to the knowledgeable engineers who designed your product and they know how important it is to get you up and running as fast as possible.
*Please consult factory for warranty information on third-party accessories and custom products.
3www.dynagen.ca | 1-888-396-2436
SPECIFICATIONSOperating Voltage
• 5 to 16VDC continuous• Standby Current Draw: 8mA at 12VDC• Reverse battery protected• Surge withstand: 1500V for 250μSOperating Temperature
• Controller Function: -40 to +85˚CPhysical
• Dimensions: 4.0”H x 4.0”W x 0.47”D• Weight: 0.15 lbSpeed Sensing
• Generator Output: Up to 300VAC (no external transformer required)
Failure Inputs
• Low oil pressure switch failure*(closed on failure)
• High engine temp failure*(closed on failure)
*Failureinputscanclosetoeither+batteryorground.Allfailureinputsareignoredforaperiodof15secondsatenginestartup.
Outputs
• Fuel & Crank- 1A relays- Switched to battery positive
Short circuit & overload protection on annunciation outputs (rated 300ma max).Connectors
• Main control mating plug: Dual Row Plug 2x7 Molex 39-01-2140
• Annunciator mating plug: Dual Row Plug 2x5 Molex 39-01-2100
Non-Adjustable Settings• Crank Disconnect (20Hz)
• Overspeed (69Hz)
• Crank Tries (3)
• Crank/Rest (10s)
General Fault Conditions• Low Oil
• High Engine Temperature
• Overcrank
• Overspeed
• Underspeed (53Hz)
• Low Battery Voltage (11V)
Not In AutoNOT-IN-AUTO LED will illuminate when the external AUTO/OFF/TEST switch is not in AUTO.
Failure InputsClose to +BAT or to Ground.
Speed SignalAccepts up to 300VAC, 60Hz from Direct Generator Output.
Time Delay Engine Start (TDES)Provides a delay (10s) before the engine is started.
Optional Cool-Down PeriodWire jumper (2 mins).
GSC100 Autostart ControllerOEM Autostart Solution for Small Gensets:Portables/Residential/Light Commercial
The GSC100 Series is a low cost, full-featured autostart for small generator installations. Factory-fi xed settings prevent unauthorized fi eld tampering. The GSC100 is conformally coated to protect against the elements and carries a 5-year warranty. The unit is supplied as a circuit card to be mounted within a customer supplied panel with appropriate labeling.
4PRODUCT CATALOG2
010
Ordering InformationPart No: GSC102-L-12
Available Accessories: HAS0025 – Main Engine Control Wiring Harness DWG1377– Annunciator Harness 5 ftDWG1410 – Extra Pre-Crimped wires 5ft (package of 5)
To find out more visit www.GSC100.info
GSC100 Autostart Controller
Typical Wiring Example
5www.dynagen.ca | 1-888-396-2436
• Single or 3-Phase utility sensing with adjustable Dropout/Pickup.
• Engine exerciser for 1, 2, 3 or 4 week intervals (adjustable only via front panel buttons).
• Timers for: Pre-heat, Mid/Post-heat, Warm-up (Normal to Emergency), Cool-down, Time Delay Engine Start, and Time Delay Emergency to Normal.
• Built-in Auto/Off /Test switch.
• Overspeed and Underspeed trips.
• 2 auxiliary outputs can be setup for Common Warning/Shutdown, System-in-Auto, Energize-to-Stop, Warmup, or Preheat.
• 2 auxiliary failure/warning inputs.
• Engine Hour Meter display.
• Low battery warning.
• Pluggable Eurostyle terminals.
• Optional Restart on False Attempts.
GSC200 Genset ControllerAuto Mains Failure
Single or 3-Phase
The GSC200 is an Auto Mains (utility) Failure Control module that provides Autostart and a range of engine monitoring and protection features. The GSC200 is designed to automatically start the generator when the mains (utility) power fails. When the mains (utility) power is restored the unit will transfer the load back to the mains (utility) supply and instruct the engine to begin the cool down timer. The GSC200 is an ideal controller to mate with a no-logic transfer switch for cost sensitive applications (ask about our Vigilant ATS without logic). The AMF functions can also be disabled and used as a conventional autostart control with a full-logic ATS.
Easy-to-Use PC Confi guration Software
• Optional Fuel OFF during crank rest.
• 5-Year Warranty.
6PRODUCT CATALOG2
010
SPECIFICATIONSOperating Voltage
• 7 to 32VDC with operation to 0VDC for 100mS
• Standby Current Draw: 22mA• Reverse battery protected• Surge withstand: 1500V for 250μSOperating Temperature
• Controller Function: -40 to +85˚C• Hour Meter Viewing: -16 to +70˚CPhysical
• Dimensions: 4.5”H x 6.75”W x 1.0”D• Weight: 0.67 lbSpeed Sensing
• Generator AC (up to 300VAC direct)
Ordering InformationPart No: GSC200 (no faceplate)GSC200-L-LS (with faceplate)(consult factory for faceplate options)
Available Accessories: GSC300-PGMR – Parallel Port Programming Kit with software
Inputs
• Utility Mains Sensing: - 120/240 3-wire, single-phase - 120/208 4-wire, 3-phase - 120 2-wire, single-phase
• Low oil pressure switch failure* (NO or NC)• High engine temp failure* (NO or NC)• 2 Auxiliary failure inputs* (NO or NC)*Failureinputsmustclosetoground.Allfailureinputsareignoredforanadjustablebypassperiod.
Outputs
• Fuel, Crank & 2 Aux Outputs (1A max): - Switched to Ground - Short circuit & overload protected
GSC200 Genset Controller
To find out more visit www.GSC200.info
Typical Wiring Example
7www.dynagen.ca | 1-888-396-2436
ES52 Autostart Engine ControllerFor Diesel and Gas Engines
The ES52 is designed to provide autostart control and protection for all types of diesel and gas engine-driven equipment. The module is epoxy sealed in an ultra-compact package with mounting compatibility to an industry standard footprint. The module is easily configured using on-board DIP switches and potentiometer adjustments.
Simple Installation and Servicing
• Plug-in Terminals with no wire crimping required.
• 20A Removable Relays and fuses eliminate slave relays and external fusing.
• Works with Mag Pickup, Alternator or Genset Output (300V max).
• Field Settings with potentiometers and DIP switches.
• Setup mode for quick calibration.
ES52 showing on-board 20A relays, fuses, and annunciator strip
• Epoxy sealed for protection against vibration, shock, and moisture.
• Multi-Function Timer Output: Pre-heat, Slow, Airgate, & Choke.
• Warm-up Timer Output.
• Detects lost speed signal.
• Zero speed restart prevents starter pinion wear.
• 5-Year Warranty.
• Preset Calibration with Fixed Settings to prevent tampering
• Under-speed shutdown
• Mid-heat & Post-heat functions (during and after cranking)
• Cool-down timer
• Pull/Hold Coil control for fuel solenoid
• Momentary inputs for multiple start/stop locations
• Inputs for Photocell start/stop control
BY SPECIAL ORDERThe ES52 also offers the following features available by special order. Please contact DynaGen for details.
8PRODUCT CATALOG2
010
SPECIFICATIONSOperating Voltage
• 7 to 32 VDC continuous• Standby Current Draw: 12mA• Surge Withstand: 1500V for 250μS• Reverse Polarity ProtectedOperating Temperature
• -40 to +85°CPhysical
• Dimensions: 3.3”H x 3.3”W x 1.8”D• Weight: 0.67 lbs• Industry standard mounting configuration• Eurostyle removable connectorsSpeed Sensing (user selectable sensing ranges)
• Magnetic pickup: 1V to 300V• Generator Output: Up to 300VAC direct
• Accepts Tach signal from belt driven alternatorsLossofSpeedsignalprotectionduringcrankingandrunning(canbedisabledwhilecranking)
Failure Inputs
• Low oil pressure failure* (closed on failure)• High engine temp failure* (closed on failure)• Auxiliary failure* (closed on failure)*Failureinputscanclosetoeither+batteryorground.Allfailureinputsareignoredforaperiodof15secondsatenginestartup.
Outputs
• Fuel & Crank: 20A high capacity replaceable automotive relays – Switched to battery positive – 12 or 24 VDC battery system (select
appropriate relay for system voltage)• Short circuit & overload protection on annunciation outputs (rated 300max)
ES52 Autostart Engine Controller
To find out more visit www.ES52.info
Ordering InformationPart No: ES52-0000-12-A-08-LS**Comes with 12VDC relays installed. Consult factory for part numbers for special order controllers.
Available Accessories: RLY0017 – 24V relays
Typical Wiring Example
9www.dynagen.ca | 1-888-396-2436
GSC300 Digital Genset ControllerIncludes 6 Engine Instruments
The GSC300 is designed to provide autostart control, protection, and engine instrumentation for all types of diesel and gas generator sets. The module is easily confi gured using either the front panel buttons or our PC confi gurator software. The GSC300 provides direct mounting compatibility with other DynaGen controllers such as the GSC400 to allow for a full range of options to fi t the application.
Displays:• Oil Pressure• Engine Temperature• Fuel Level• Hour Meter• Frequency• Battery Voltage
Compact 4.3” x 5.5” x 2.16” Footprint
GSC300 showing 40A removable relays, replaceable fuses and
annunciator strip
• Conformally coated for protection against moisture and contaminants.
• Customizable Screen Messages.
• Confi gurable via front panel or PC.
• Accepts industry standard senders (VDO, Stewart-Warner, Datcon, Murphy).
• Zero speed restart prevents starter pinion wear.
• Timers for: Pre-heat/Warm-up/Energize-to-stop, Cool-down, Engine Start Delay, Mid-heat and Post-heat.
• Low Battery Indication.
• Restart on false attempts.
• Optional Fuel OFF during crank rest period.
• 5-Year Warranty.
10PRODUCT CATALOG2
010
SPECIFICATIONSOperating Voltage
• 7 to 30VDC continuous, with zero volts cranking dropout protection
• Reverse battery protected• Standby current draw: 40mA• Surge withstand: 1500V for 250μSOperating Temperature
• Controller Function: -40 to +85˚C• Display Screen Viewing: -15 to +70˚CPhysical
• Dimensions: 4.3”H x 5.5”W x 2.16”D• Weight: 0.75 lbSpeed Sensing
• Generator Output: Up to 300VAC (no external transformer required)
Inputs
• Oil Pressure Input – Sender (0-500Ω) or Switch*
• Engine Temp Input – Sender (0-500Ω) or Switch*
• Fuel Level/Aux Input – Sender (0-500Ω) or Switch*
*Failureinputsmustclosetoground.Allfailureinputsareignoredforaadjustablebypassperiod.
Outputs
• Fuel, Crank & Preheat/WarmUp/ETS: 40A high capacity replaceable automotive relays:
– Switched to battery positive – 12 or 24 VDC battery system (select
appropriate relay for system voltage)• Short circuit & overload protection on annunciation outputs (rated 300ma max.)
Incorporates the Functions of 6 External Gauges
The GSC300 displays 6 critical engine readings through a backlit digital display augmented by 8 high-intensity lights for failure and status conditions. A built-in Auto/Manual/Off Switch is also included.
3 On-board Replaceable 40A Relays & Fuses
The GSC300 is socketed to accept 3 industry standard 40A cube relays – each protected by a replaceable automotive fuse. The GSC300 eliminates the need to mount, wire, and fuse external slave relays for Fuel, Crank, and Pre-heat.
Computer or Manually Programmable
The GSC300 can be programmed manually via front panel buttons or with our free, easy-to-use PC software interface that provides customization of screen messages, languages, sender selections, and control settings.
Easy-to-Use PC Configuration Software
GSC300 Digital Genset Controller
11www.dynagen.ca | 1-888-396-2436
To find out more visit www.GSC300.info
GSC300 Digital Genset Controller
Ordering InformationPart No. GSC300-L-12-LS**comes with 12VDC relays installed.
Available Accessories: RLY0043 - 24V relays; RLY0054 - UL Listed 24V relaysACC0108 – S&W Oil Press Sender (279B-F), 100PSI, 240Ω, 1/8”-27 NPTFACC0027 – DATCON Temp Sender 100-280C, 1/8”-27 NPTFGSC300-PGMR – Parallel Port Programming Kit with softwareGSC300-USB-PGMR – USB Programming Kit with softwareENC0057 – NEMA 1 Enclosure with vibration mounts
Control Panels with GSC300 in NEMA 1 enclosure with selector switch, AC Volts & Amps meters, CTs, and vibration mounts: GCP300-L-____A-300V-2-12VDC (1Ph, 300V)GCP300-L-____A-600V-3-12VDC (3Ph, 600V)(100, 200, 300, 500, 600, 1000, or 1500A meters & CTs available)
Typical Wiring Example
Also available in a control panel with AC meters – see left for ordering
information
12PRODUCT CATALOG2
010
GSC400Plus Digital Genset ControllerDisplays AC Volts/Amps
Standard or Electronic Engines
The GSC400Plus is designed to provide complete control, protection, AC metering, and engine instrumentation for both standard and electronic engines and gensets. The module is easily confi gured using either the front panel buttons or our PC confi gurator software. The GSC400Plus provides direct mounting compatibility with other DynaGen controllers such as the GSC300 to allow for a full range of options to fi t any application.
Displays:
• Oil Pressure • Engine Temperature • Fuel Level • Oil Level • Hour Meter • RPM • 3-Phase AC Volts & Amps • Frequency • Battery Voltage• J1939 Diagnostic Codes
Features and Functions:
• SAE J1939 Protocol.
• NFPA Level 1 Compliant.
• 3 On-Board 40A Relays.
• Real-Time Clock.
• 100 Event Failure Log.
• Conformally coated for protection against moisture and contaminants.
• 8 Confi gurable Switched Inputs & 9 Confi gurable Switched Outputs.
• Autostart on Low Battery function.
• Built-in Engine Exerciser.
• Free PC Confi gurator Software.
• Front or Rear Mountable.
• Password protected.
• Modbus Port to connect remote annunciators and other devices.
• Options for remote monitoring over Internet and cellular.
• Accepts common senders (VDO, Datcon, Murphy, and more).
• Custom senders confi gurable with PC software.
• Dummy Load function to prevent wet stacking.
• Options for Fuel OFF during Crank Rest, Restart on False Attempt and Locked Rotor.
• 5-Year Warranty.
GSC400Plus showing 40A removable relays, replaceable
fuses and annunciator strip
Compact 4.3” x 5.5” x 2.75” Footprint
NEW
13www.dynagen.ca | 1-888-396-2436
SPECIFICATIONSOperating Voltage
• 7 to 32VDC with operation to 0VDC for 50mS• Standby Current Draw: 50mA• Reverse battery protected• Surge withstand: 1500V for 250μSOperating Temperature
• Controller Function: -40 to +85˚C• Display Screen Viewing: -20 to +70˚C (consult factory for optional heater for -40˚C operation)
Physical
• Dimensions: 4.3”H x 5.5”W x 2.75”D• Weight: 0.97 lbSpeed Sensing
• Via J1939 bus, Magnetic pick-up, or Generator AC (up to 300VAC direct)
Inputs
• Voltage Sensing: - Single-phase, 3-phase, Delta, Wye - Max 700vac - True RMS, +/- 1% of full scale
• Current Sensing: - Accepts 5A secondary CTs - +/- 2% of full scale
• Sensors: - Inputs 5, 6, 7: Sender (> 500Ω) or Switch*- Inputs 2, 3, 4: Sender (0-500Ω) or Switch*
*Failureinputsmustclosetoground.Allfailure
inputsareignoredforaadjustablebypassperiod.
• Configurable Switched Inputs: - Inputs A,B,C,D (Close to Bat) - Inputs E,F,G,H (Close to Gnd)
Electronic Engine Support:
• Standard J1939 Engines (Tier II, II & IV)• Customized display for Volvo, John Deere, Cummins, Yanmar, Detroit Diesel and more*
*Consultfactoryforupdates
Outputs
• Fuel, Crank & Extra Output – 40A high capacity replaceable automotive relays: - Switched to Battery Positive - 12 or 24 VDC battery system (select appropriate relays for system voltage)
• Switched Outputs (A-H) - 200mA max: - Switched to Ground - Short circuit & overload protected
Communications
• SAE J1939 - Tier II, III, & IV engines - Address settings for both the GSC400 and the engine ECM
• Modbus: - GSC400 operates in RTU Slave mode - RS485 port (9600, 19200, 38400, 57600 baud)
messages, sender selections, control settings, and much more.
Ideal for Mobile Gensets
The GSC400 is a great fit for mobile and trailer genset applications:
• Ultra-Low Standby Draw prevents battery drain (50mA).
• Inputs to automatically re-configure for up to 4 different AC voltage topologies.
• Maintenance Timer.
• Inputs for fuel saving Idle Mode*.*CompatiblewithCumminsTierIVidlemode
3 On-board Replaceable 40A Relays & Fuses
The GSC400 is socketed to accept three industry standard 40A cube relays – each protected by a replaceable automotive fuse. The GSC400 eliminates the need to mount, wire, and fuse external slave relays for Fuel, Crank, and Preheat.
Front Panel or PC Configurable
The GSC400 can be programmed manually via front panel buttons or with our easy-to-use PC software interface that provides customization of screen
GSC400Plus Digital Genset Controller
14PRODUCT CATALOG2
010
Easy-to-Use PC Configuration SoftwareEvery setting of the feature-rich GSC400 is easily configured with its powerful, yet easy-to-use PC-based software interface.
Here are just some of the functions made available to you:
GSC400Plus Digital Genset Controller
Sensor Inputs (Sender/Switch or J1939)
• High Engine Temp• Low Oil Pressure• Fuel Level• Oil Level• Fuel in Basin• Low Engine Temp
Switched Output Functions (Select up to 9)
• Warm-up• Energize-to-Stop • Pre-heat • Cool-down • Overcrank • High Temp Failure/Warning • Low Oil Failure/Warning • Underspeed Failure/Warning • Overspeed Failure/Warning • Low Fuel Failure/Warning • Battery Failure/Warning• Low Coolant Failure/Warning• Not-in-Auto• General Failure• Crank Rest• Engine Running• Engine Cranking• Exerciser Alarm• Battery Recharge Alarm• Under Voltage Warning• Over Voltage Warning• Over Current Warning• Fuel-in-Basin Warning
• Voltage Regulator• Low Temperature• Backlight• Auxiliary Warning• Maintenance Timer• System Ready• Common Fault• Dummy Load• High Fuel Level • Current Latch • User Configurable Warning 1 & 2
• User Configurable Failure 1 & 2
Timers
• Pre-heat, Mid-heat & Post-heat• Delay-to-Start• Warm-up & Cool-down• Energize-to-Stop• Programmable Engine Exerciser
Battery Functions
• Low/High Battery Warning & Failure
• Autostart on Low Battery Function
AC Functions
• Overspeed/Underspeed Warning & Failure
• Over/Under Frequency Warning & Failure
• Over/Under Voltage Warning & Failure
• Over Current Warning & Failure• AC Secondary Crank Disconnect
Switched Input Functions (Select up to 8)
• Emergency Stop• Low Air Pressure• Low Hydraulic Pressure• Low Oil Pressure• EPS Supplying Load• Alarm Silence• Low Coolant• Voltage Topology Select 1 & 2• Idle Mode• Start/Stop• Charger Fault 1 & 2• High Fuel Level• Auxiliary Failure & Warning• User Configurable Warning 1 & 2• User Configurable Failure 1 & 2
15www.dynagen.ca | 1-888-396-2436
GSC400Plus Digital Genset Controller
To find out more visit www.GSC400.info
Ordering InformationPart No. GSC400-0-12-LSB**Comes with 12VDC relays installed.
Available Accessories:
RLY0043 - 24V relays; RLY0054 - UL Listed 24V relaysACC0108 – S&W Oil Press Sender (279B-F) 100PSI, 240 Ohm, 1/8”-27 NPTF ACC0027 – DATCON Temp Sender 100-280C, 1/8”-27 NPTFGSC400-PGMRB – USB/Serial Programming Kit with softwareENC0057 – NEMA 1 Enclosure with vibration mounts
Current Transformers: ACC0045 (100A), ACC0046 (200A), ACC0047 (300A), ACC0048 (500A), ACC0049 (600A), ACC0050 (1000A), ACC0057 (1500A)
Starter Harness Kits: Harness kits are prewired in connector plugs and populated with common connection points for most applications. Extra crimp wires are available for further flexibility.
ACC0086 – 5ft Starter Kit (AC Current Sensing, Switched Inputs, and Sensor Inputs) DWG1373 – 5ft J1939 CableDWG1377 – 5ft Switched Outputs CableDWG1410 – Pre-Crimped individual wires (pkg of 5)DWG1454 - 5ft RS485/Modbus Cable
Typical Wiring Example
Also available with an optional control panel enclosure (ENC0057)
16PRODUCT CATALOG2
010
RA400 Remote AnnunciatorFor NFPA110 Applications
The RA400 remote serial annunciator monitors the condition of the generator set from a remote location when it is equipped with a DynaGen GSC400Plus Genset Controller. If a generator alarm condition occurs, the remote annunciator alerts the operator through lamps and an audible alarm.
Green Amber RedOvercrank X XOverspeed X XEmergency Stop XHigh Engine Temperature X XLow Oil Pressure X XLow Coolant Level XLow Coolant Temperature XLow Fuel Level X XCommunication Status X XNot In Auto X XHigh Battery Volts X XLow Battery Volts X XCommon Fault X XLow Cranking Volts XBattery Charger Failure XUser Configurable 1 X User Configurable 2 X XSystem Ready X XGenerator Running XEPS Supplying Load X
Type LED Indication
• Connects via 3-wire Modbus to the GSC400Plus genset controller up to 2800 ft.
• 20 Lamp Indicator for Warnings, Status, and Failures.
• NFPA-110, NFPA 99 & CSA 282-00 compliant.
• 2 User configurable lamps with writable surfaces.
• Extra switched inputs for System Enable/Disable and Genset Start/Stop.
• Audible Alarm.
• Modbus RTU serial connection.
• Surface or flush-mounted. Also fits in a standard 203 mm x 203 mm (8 in. x 8 in.) Hoffman box.
• Conformal coated circuit board for moisture protection.
• Up to 4 RA400 annunciators can be easily connected to the same wiring.
• Powered by 12 or 24VDC.
• Optional 120 VAC Power Supply.
• 5-Year Warranty.
GSC400Plus Companion Products – RA400 Remote Annunciator
Shown with optional enclosure.
17www.dynagen.ca | 1-888-396-2436
GSC400Plus Companion Products – RA400 Remote Annunciator
SPECIFICATIONS Power Supply
• 6 to 30VDC• Meets SAE J-1113 Load Dump• Reverse Battery Protected• Current Draw: 100mA – 250mA Operating Temperature
• -40˚C to +85˚CPhysical
• Dimensions: 8.0” x 8.0” x 1.5”• Weight: 1.5 lbs Audible Alarm
• 71 to 86db at 2ft
Ordering InformationPart No. RA400-LSAvailable Accessories:
DWG1454 – 5ft pigtail harness for Modbus connection to GSC400ACC0109 – 8”x8”x4” Pull Box (Hoffman ASE8X8X4)ACC0111 – 120VAC to 24VDC power adaptor (Mean Well ELN-60-24)
Communications
• Modbus RTU (RS-485)• Max Distance: 2800ft using Belden 9841 cable or equivalent
• Master or Slave configuration• 9600 or 19200 Baud• Optical Isolation for surge immunity Switched Inputs
• 2 Inputs for System Enable/Disable and Genset Start/Stop
• 2 wire ground/positive input to trigger
18PRODUCT CATALOG2
010
DynaLink Remote Genset MonitoringThe DynaLink genset monitoring system allows you to monitor and control generator sets over LAN, Internet, telephone modem, or wireless cellular connections. The system contains built-in features such as an alarm handler (SMS, Email and SNMP), data logger (with trend graphs) and a built-in web server for monitoring and control.
GSC400Plus Companion Products – DynaLink Remote Monitoring
The DynaLink WS100 module connects to the Internet via its built-in Ethernet port to a GSC400Plus Genset Controller at a facility. The DynaLink system makes the data available in an internal web server that can be accessed by the user using a standard web browser, like Internet Explorer. This makes it possible for the user to instantly read any parameter available from a remote location. Optionally, a PSTN dial-up modem can be connected to the WS100 to provide access via conventional telephone lines.
The WS200 module adds the additional capability of using its built-in quad band GSM/GPRS cellular modem with any standard SIM card for remote or mobile gensets without Internet. It also supports an external GPS receiver which makes it possible to use it for applications where the geographical position is important, such as rental fleets.
19www.dynagen.ca | 1-888-396-2436
GSC400Plus Companion Products – DynaLink Remote Monitoring
Ordering InformationPart No. WS100 – Ethernet onlyPart No. WS200 – Ethernet and built-in GSM/GPRS cellular modemAvailable Accessories:
ACC0112 – Accessory Kit (Power Adapter and Cables) SMA quadband antenna options: ACC0113 – Straight ACC0114 – Right angle ACC0115 – Magnetic footCables for SMA antennae: ACC0116 – 9.8ft ACC0117 – 16.4ft ACC0118 – 32.8ft ACC0118 - Optional GPS receiver (SA-920) for WS200Dial-Up Telephone Modem for WS100 (consult factory)
• Ability to reset faults and restart genset.
• Full start/stop/enable/disable control.
• Monitoring of all warnings, failures, status, sensor readings, AC metering, including J1939 engine information.
• Alarm & Status handler (notifications via SMS, E-mail and SNMP).
• Data logging with trend graph presentation (can be downloaded to a spreadsheet).
• Ability to access GSC400Plus internal event log.
• Password restricted access control.
• DIN rail mounting.
• Optional, fee-based Web Site access to multiple sites
• Easily connects to GSC400Plus via 3-wire Modbus/RS485 port.
• 1-Year Warranty.
20PRODUCT CATALOG2
010PRODUCT
CATALOG
Vigilant Automatic Transfer Switches100A to 1250A
The Vigilant Series ATS is designed to automatically transfer critical loads in the event of a power outage. It consists of a simple, rugged design while maintaining the fl exibility required to meet the needs of residential, agricultural, and light industrial applications.
• Rugged Contactor Design – Double Throw, Mechanically Interlocked.
• Galvanized Steel Enclosure.
• Externally accessible Exerciser Clock and Lamps.
• 5-Year Warranty.
DynaGen’s VTSC100 Controller BoardThe VTSC100 Logic Controller Board is at the heart of every Vigilant Automatic Transfer Switch. It is designed to provide all basic transfer switch control functions with simplicity, fl exibility, and durability.
Features include:
• Powered from genset battery for isolation against line transients.
• Integrated voltage and frequency sensing.
• Adjustable transfer delays using on-board potentiometers.
• Fused remote start contact relays.
• Adjustable drop-out & pick-up values for voltage and frequency.
• Internal test switch included.
Conformally Coated
Every VTSC controller board is thoroughly conformally coated to create an eff ective barrier against moisture, fungus and other contaminants that can cause:
• Short circuits.
• Corrosion of conductors and solder joints.
• Electrical leakage between circuits.
• Mechanical stress of components.
• Loss of insulation protection.
21www.dynagen.ca | 1-888-396-2436
Vigilant Automatic Transfer Switches
Specifi cations (Standard Withstand Models)
Operating Temperature: -20 to +70˚C; Operating Humidity: 0-95% Relative, Non-Condensing
VTSC100 ATS Controller Specifications12 or 24VDC (factory jumpers); Standby Draw: 25mA
Operator Interface with external access
DynaGen’s easy-to-use, 7-day exerciser clock gives you full control over day and time. The exerciser clock and indicator lamps are both accessible from outside the transfer switch. There’s no need to open the door to adjust the clock or view the status of the transfer switch, even with the NEMA 3 enclosure option.
Galvanized Corrosion Protection Standard on all Vigilant Enclosures
The Vigilant enclosure is made from duplex coated, galvanized G90 grade steel and meets American Society for Testing and Materials (ASTM) standard A653. The service life of our galvanized steel enclosures is more than twice that of regular steel.
22PRODUCT CATALOG2
010
To find out more visit www.VigilantATS.info
Vigilant Automatic Transfer Switches
Ordering Information
VTS2 – – – –LS
Example: VTS2-0400-2-240-12-X-N3ATS Rated 400 Amp, Single-Phase 2-Pole, 120/240V, NEMA 3 enclosure
Note: Please consult factory for “LM” version that provides compatibility to Briggs and Stratton generators with Power Management System.
Available Accessories: ACC0107 – Keyed Locks for Enclosure
Ampere Rating
0100 0200 0400 0600 1000 1250
0400 2 240 – 12 – X – N3
Number Poles Voltage Enclosure
TypeDelay-on-
Neutral
2 = 2 Pole 3 = 3 Pole 4 = 4 Pole
240 = 120/240 208 = 120/208 480 = 277/480
X = StandardD = Delay-on-Neutral
(standardon600Aandabove)
N1 = Nema 1 N3 = Nema 3
(N1comeswith
knock-outs.N3isstandard
23www.dynagen.ca | 1-888-396-2436
Vigilant Load Center100A Automatic Transfer Switchwith Breaker Panel
The Vigilant Load Center is ideally suited for residential and light commercial applications. It eliminates the need for a separate sub-panel and fi ts snugly between two studs. The unit also includes the full-featured VTSC100 controller which allows easy adjustment of time delays and voltage/frequency settings.
• Rugged contactor-based double throw switch.
• Eliminates the need for separate sub-panel.
• Robust full-featured controls (see VTSC100 controls on page 20).
• Externally accessible Exerciser Clock and LED’s.
• Square D QO panel accepts 12 Regular or 24 Mini Circuit Breakers (optionally supplied).
• 5-Year Warranty.
Flexible and Easy-to-Use Exerciser
Controller – See Page 21 for VTSC100 controller specifi cations*Please consult factory for specifi c protective device specifi cations and ratings. UL1008 – Optional Standby Systems
Specifi cationsOperating Temperature: -20 to +70˚C; Operating Humidity: 0-95% Relative, Non-Condensing
AC Rating Voltage UL Withstand Ratings* Poles Enclosure
(H x W x D) Lbs. Lug Capacities
100Amp 120/240 10KA 226”x14.25”
x6”45
1/0to14Cuor1/0to
Lightweight and Easy to Install – the Vigilant Load Center fi ts snugly
between two studs and has plenty of conveniently placed knock-outs
24PRODUCT CATALOG2
010
Vigilant Load Center
Ordering InformationVLC2 – – – – 12 – X – –
Example: VLC2-0100-2-240-12-X-N1-LS 100Amp, single-phase 2-pole, 120/240, Nema 1 enclosure, with breakers*.*Breakers supplied: • Five 15A single pole • Three 20A single pole • One 20A double pole
Note: Consult factory for ‘No Logic’ version supplied without VSTC-100 controller.
0100 2 240 N1 LS
Ampere Rating
Number Poles Voltage Enclosure Breakers
240 = 120/2400100 2 = 2 Pole N1 = NEMA 1LS = w/breakers* LX = w/o breakers
To find out more visit www.VigilantATS.info
25www.dynagen.ca | 1-888-396-2436
Custom OEM SolutionsWhen an off-the-shelf controller just won’t do the job, call DynaGen. Our proven control platforms can be adapted to just about any special application. Think of us as your product design team!
DynaGen’s integrated design philosophy centers around the use of flexible, microprocessor control modules that can be integrated to deliver many value-added features in a single, low-cost package. The result is the elimination of many costly external components and increased reliability.
Our capabilities
• Testing to Mil-Spec standards.
• Mobile and special transfer switch applications.
• Battery management.
• Graphic display panels for engines and gensets.
• Air/Fuel & Spark Control for gas engines.
• Electronic Governors.
• CANbus/J1939.
• Remote telemetry by satellite, cellular and internet.
Sample applications from recent projects
• Locomotive Engine Control.
• Marine Engine Management System.
• Truck APU control and remote display.
• Vehicle transfer switch.
• Residential no-logic transfer switch.
POWER CONTROLS YOU CAN TRUST
The US Army conducted a series of tests to establish the ruggedness of
a battlefield communications system on a Humvee genset outfitted with a DynaGen controller. The rough treatment even included jolting chopper transport. The Result: Over 10 years of trouble-free deployment around the globe.
NASA and Carnegie-Mellon University took a Nomad Lunar Rover to the harsh Atacama Desert in Peru for a series of
punishing tests. Their on-board controller? A DynaGen. The Result: The Nomad traveled an unprecedented 215 km in 45 days, under full remote control.
75 Akerley Boulevard, Dartmouth, Nova Scotia, Canada B3B 1R7
1-888-396-2436 (1-888-DYNAGEN) | www.dynagen.ca