dtr optimal gwarancja EJDRUK 09 08 2017 detektor2...

20
rev:12.07.17 MAINTENANCE MANUAL WARRANTY CARD AIR HANDLING UNIT OPTIMAL Below documentation shall be kept by user! In case of not following the conditions of this document, the warranty expires. EN

Transcript of dtr optimal gwarancja EJDRUK 09 08 2017 detektor2...

rev:

12

.07

.17

MAINTENANCE MANUALWARRANTY CARD

AIR HANDLING UNIT

OPTIMAL

Below documentation shall be kept by user!In case of not following the conditions of this document, the warranty expires.

EN

rev:

12

.07

.17

3

3

3

6

6

6

6

7

8

9

9

9

10

10

11

12

13

14

15

15

16

17

20

1. GENERAL INFORMATION................................................................................

1.1. Purpose................................................................................................

1.2. Technical specification..............................................................................

2. ASSEMBLY.................................................................................................

2.1. Required exploitation conditions..................................................................

2.2. Pre-assemblyrequirements.........................................................................

2.3. Unit location..........................................................................................

2.4. Assembly of condensaation dreinage system....................................................

2.5. Connecting to ventilation...........................................................................

2.6. Connecting to power grid...........................................................................

3. STARTING THE UNIT.....................................................................................

3.1. General remarks.....................................................................................

3.2. Connecting contol panel...........................................................................

3.3. Starting the unit.....................................................................................

3.4. Usage and maintenance...........................................................................

3.5. Summer mode (OPTIMAL 400 bypass/600 bypass).............................................

3.6. Working with carbon monoxide sensor (option)...............................................

4. EXPLOITATION RECOMMENDATION..................................................................

5. ELECTRICAL CONNECTION - AUTOMATION MODULE..............................................

5.1. Assembly and disassembly of automation module.............................................

5.2. Connection scheme................................................................................

6. AC2800 DIGITAL CONTROLLER.......................................................................

7. WARRANTY..............................................................................................

CONTENTS

Op

tim

al 4

00

/60

0

EN

rev:

12.0

7.1

7

198mm

3400m /h3600m /h

0-450 Pa0-340 Pa

48,8 kg 49,8 kg

838 mm x 631 mm x 583 mmDimensions

Air flow (100 Pa)

Diameter of ventilating connectors

Disposal compression

Max power consumption

Heat recovery efficiency

Power supply voltage

Motor rational speed

Type of motor bearing

Acoustic pressure

Insulation class

Internationl protection rating

Weight

roller bearing

max. 52dB(A)/1m

I

IP40

max. 53dB(A)/1m

1400 rpm 1650 rpm

up to 95%

OPTIMAL400 BYPASS

OPTIMAL600 BYPASS

OPTIMAL air handling unit is destined for air exchange in residential buildings.

The purpose of the unit is to bring fresh air from the outside and to siphon off used air from the rooms

with simultaneous heat recovery.

1. GENERAL INFORMATION

1.1. Purpose

1.2. Technical specification

Op

tima

l 40

0/6

00

min. 20W / max. 150W min. 20W / max. 250W

230 VAC / 50Hz

EN

rev:

12.0

7.1

7

2. Flow efficiency characteristics OPTIMAL 400 bypass

Optimal 400 BYPASS

3v [m /h]

Op

tim

al 4

00

/60

0

1. Nominal dimensions of OPTIMAL

583570

375175

838725

198178

478 625

EN

rev:

12.0

7.1

7

3. Flow efficiency characteristics OPTIMAL 600 bypass

Optimal 600 BYPASS

3v [m /h]

Op

tima

l 40

0/6

00

EN

rev:

12.0

7.1

7

2. ASSEMBLY

2.1. Required exploitation conditions

The unit and ducts should be assembled in rooms with temperature 5°C - 30C and heat-separated

form surroundings.

Not following above conditions will cause liquefaction of condensate and cumulate it inside and outside

of the unit which may cause dampness in the room or damage to the unit.

2.2. Pre-assembly requirements

While planning the assembly of the unit consider:

- ensuring the expliotation conditions of the unit

- possibility of bringing about ventilation pipes to the device

- possibility of siphonning of steam condensate

- possility of bringing about electric energy

- easy access to maintenance and repairs

2

WARNING!

1. Ventilation installation and other belonging elements must be in accordance with Polish Norms

referring to ventilation in residential and public utility buildings.

2. The unit is not destined for drying the unseasoned houses.

3. In case of damage to elements arising from not following the above instructions,

they will be not repaired under warranty.

4. Due to design reasons there is a possibility of mixing the air inside the unit with amount

not exceeding 2%.

Prior to connecting the unit check elements condition, including casing and wiring. In order to avoid any damage,

the unit should be kept in safe place in original packaging.

2.3. Unit location

The unit is destined for assembly under dry roofed rooms with basements (attics, utility room).

The unit should be assembled in a way to allow free drain condensate from the tub.

WARNING!

Manufacturer does not include assembly elements with the unit. Buyer should purchase elements separately.

After unit is placed, it shoud be leveled. It has an essential meaning for proper work of the condensate

drainage system.

Op

tim

al 4

00

/60

0

EN

rev:

12.0

7.1

7

2.4. Assembly of condensaation dreinage system

Steam condensation can be observed during unit's work. It is completely normal and it is not an abnormality

in working. In order to siphon out condensate the unit is equipped with stub pipe placed on the right side.

It is essental to properly connect the pipe siphoning out the condensate.

Exemplary way of conneting the pipe is shown below. The pipe should have adequate diameter to the stub-

pipe (1/2"). It shoud be bent into letter "U" and suffused with water until stabilizing its level.

Shipon should be palced around 150 mm from the unit and radius should not be less than R=30 mm.

Given measures should be taken as minimal.

Op

tima

l 40

0/6

00

4. Proper positioning of the unit. It is essential to keep level of the base

5. Exemple of pipe assembly to siphon out condensate

water level

EN

rev:

12.0

7.1

7

Inner stub-pipes diameters are 198mm and are fitted to standard Termoflex ducts 200 mm.

Ventilation ducts should be assembled carefully with the use of OZ duct clip (4 pcs).

In case of assembly in temparature below 12°C and above 32°C it is recommended to insulate ventilation

ducts with mineral wool of min. thickenss 30 mm. Such operation will assure efficient work

of the ventilation system.

2.5. Connection to ventilation

Op

tim

al 4

00

/60

0

6. Designation of the unit with stub-pipe description

Automation module

From roomsTo rooms

From intake portTo launcher

Exttract fan Intake fanSupply voltage

EN

rev:

12.0

7.1

7

2.6. Conneting to power grid

Unit should be connected directly to one phase outlet 230V/50Hz in the most accessible place.

All electrical matter should be perfomed by authorized person.

WARNING!

Prior to maintenance work or repairs, unit should be disconnected from the power outlet

by pulling the plug out.

In case of damaging the wire, replacement can only be performed by authorized person.

1. Prior to starting the unit read the manual.

2. Check if there is no objects present in the ducts which may damage the unit or endanger health.

3. It is recommended to test the working mode of the unit prior to connecting it to ventilation.

3. STARTING THE UNIT

3.1. General remarks

Op

tima

l 40

0/6

00

7. Manner of conneting power cord

EN

rev:

12.0

7.1

7

WARNING!

While testing the installation follow the safety rules in order to avoid improper direction of airflow,

i.e. open chimney duct or other devices with open fire towards room.

3.2. Connecting control panel

Air handling unit is equipped with weekly controller.

Control panel is delivered with 20 m connection cord ended with plug type RJ11.

Control panel should be placed on a wall, but you should previosuly plan how to lead cord from unit to panel.

WARNING!!! Cord cannot be less than 5m long.

3.3. Starting the unit

1. Read the manual

2. See if there is no damage

3. Place unit in wanted place

4. Connect control panel

5. Connect connection cord to power grid 230 V

6. Turn on the unit using control panel ot turn on "TURBO" mode for 3 minutes

7. Check if there is air flow at the stub-pipes (WARNING! Do not put hands inside the stub-pipes

- may results in injuries!)

8. Turn off the unit using control panel

9. Unplug power cord from grid

10. Disconnect control panel from unit

11. Mount the unit in ventilation system

12. Lead control panel's cord from unit to destined mounting place

13. Mount control panel

14. Connect unit to control panel

15. Connect power cord to power grid

16. Turn on control panel and set weekly program

17. Control air intake efficiency in accordane with project

Once all above is performed, the unit can be used.

Op

tim

al 4

00

/60

0

EN

rev:

12.0

7.1

7

Properly mounted Optimal does not require any special maintenance during use. Maintenance is the

replacement of air filters. Visual indication informs about filter replacement.

3.4. Usage and maintenance

Filter exchaange in steps:

1. Disconnect connection cord from power grid

2. Disconnect control panel from the unit

3. Dismount the casing by unscrewing butterfly screws

4. Carefully take out used filters and replace with new ones

5. Mount back the casing and screw with butterfly screws

6. Connect power cord and control panel

7. Connect unit to power grid

8. Reset the timer

WARNING!!!

Unit should not work without filters. It is only recommended for testing, but no longer than 10 minutes.

Op

tima

l 40

0/6

00

8. Filter exchange

Casing

Filters

EN

rev:

12.0

7.1

7

3.5. Summer mode

During unit's work heat recovery is only needed to temperature of around 18°C. Cold recovery is neecessary

in ventilated rooms if temperature is above 26°C. When outter temperature is between 15-26°C

it is required to use by-pass, which results in ommision of warming the air. For this purpose Optimal 400 by-

pass/600 b-pass ar equipped with automatic by-pass.

The moment when by-pass is opened hear exchange does not take place. By-pass is used for cooling

ventilated rooms with the use of cool air for example from GWC.

Switch, presented on the picture below in position By-Pass Manual means opening the actuator.

It closes when outter temperature falls below 10℃. Switching to By-Pass Auto means automated work

of actuator.

Op

tim

al 4

00

/60

0

9. By-pass location

10.

1- Bypass Auto

2 - Bypass Manual

3 - Actuator

4 - Carbon monoxide sensor

Bypass

EN

rev:

12.0

7.1

7

3.6. Working with carbon monoxide sensor (option)

OPTIMAL unit is designed to work with carbon monoxide sensor. Basic function of this sensor it detection

of carbon monoxide and generating alarm when excessive amount of it is detected. Sensor decreases

risk of carbon monoxide poisoning and allows to take action in life-threatening situations.

Carnon monoxide sensor should be installed in:- room with fireplace or tiled stove- room with gas burners- bathroom with warm water gas heaters- boiler house- garage or workshops

Unit working with carbon monoxide sensor results in exhaust and intake fans to work on maximum

speed. Decrease of carbon monoxide in air allows unit to return to normal operation mode.

Detailed description of carbon monoxide sensor can be found in manual.

Op

tima

l 40

0/6

00

A2

+12V

+12V

GND

Detektor CO

GND

+12V

A2

+12V

Socket RJ11

Plug RJ11com NO

Plug RJ11 Plug RJ11

External power suply 230VACPower suply 12VDC

A2

+12V +12V

GND

230VAC

+12V GNDL

Nwyjściestykowe

zaciski

zasilania 12V

com NO

wyjście

stykowe

CO Sensor

EN

rev:

12.0

7.1

7

ź Necessity of filter replacement is signaled by countdown timer via visual warning.

The filter cartridge made of polyester fabrics cannot be cleaned and must be replaced with a new one if

necessary. New filters should be ordered from the device supplier.

The time indicator of contamination of the filter counts down the time remaining until the next filter

change.

To start the countdown for the first time, press and hold the RESET button for 3 seconds.

The need to replace the filter is signaled by audible and visual signals - after the countdown is over, the digits

00 00 00 are displayed on the screen.

The signal must be reset by pressing the RESET button.

The device is equipped with a magnet and CR1130 battery.

Fan check-up

Despite of required maintenance work (cleaninf/filer exchange) dust and grase can be slowly embed inside

the fan, which can decrese its effecitivity. Fan can be cleand with cloth or soft brush. Keep caution while

cleaning not to damage fan's impeller. Do not clean with water, do not put in water! Solid dirt can be cleaned

with denaturated alcohol. Prior to placing back - dry well.

Control of condensate's stub-pipe

Stub-pipe can become dirty overtime by fixed particles brought by air. It is recommended to periodically

check (by flushing with water) stub-pipe patency. Clean if needed.

ź

ź

4. Exploitation Recommendation

ź

Unit is a part of a whole system. the system supplies fresh air and launches used air through ducts

and intake/exhaust diffusers. Air diffusers are installed in ceilings, walls, bathrooms and rooms.

They should be periodically cleaned with warm water and soap, if needed. If they were dismounted

for cleaning they should be put in the same places - they cannot be changed.

ź Control of fresh air inlet and launcher

Pollution as leafs, insects, dust, etc.) can clog air inlet which causes air flow throttling.

Check and clean air inlet at least twice a year.

Launcher installed on wall must be checked (cleaned if needed) at least once a year.

ź Duct check-up (every 5 years)

Dust and grease particles will pile up in duct despite of recommended maintenance which can decrease

effectivity of installation. Due to that fact, ducts should be cleaned/exchanged when needed.

Cleaning intake and exhaust

Op

tim

al 4

00

/60

0

EN

rev:

12.0

7.1

7

ź 5. Electrical connection - automation module

Optimal unit has a separated automation module, in which electrical connections are led.

For service purposes the module can be demounted as whole and examined on separate service desk.

1. Disconnect connection cord from power grid

2. Disconnect panel control's connection cord from automation module

3. Dismount the casing by unscrewing butterfly screws

4. Unscew screws holding module inside the unit (6 pcs)

5. Remove module from the casing

6. Disconnect fans, temperature sensor and bypass

Assembly is performed in reversed order. Once performed start unit.

Connections in automation module are carried in accordance with scheme attached to this document.

WARNING!!!

Disassembled module can be connected by authorized person on prepared test stand only.

Module is equipped with elements under 230VAC which can cause damage to health when carried out by

unqualified person.

5.1. Disassembly and assembly of automation module

Op

tima

l 40

0/6

00

11. Location of automation module

EN

rev:

12.0

7.1

7

WARNING:Electric equipment is not a household waste. Once exploitation time is over it should be disassembled

by hand with use of wrench, screwdrivers and pliers). Electric motors, automation, power supply,

steel elements and those made out of plastics should be recycled. Information where to recycle is available

at local administration offices.

Op

tim

al 4

00

/60

0

12. Connection scheme

5.2. Connection scheme

Sock

et

RJ1

1

Male

sock

et

IEC

Male

sock

et

IEC

T3,1

5A*

T3,1

5A*

NTC 1

0K

NTC 1

0K

Male

sock

et

IEC

Male

sock

et

IEC

Fem

ale

plu

g IEC

Fem

ale

plu

g IEC

Fem

ale

plu

g IEC

Fem

ale

plu

g IEC

*) T

2.5

A f

or

Opti

mal 400

Gre

en

4

Gre

en

Gre

en

Gre

en

Gre

en

Gre

en

Blu

e

Blu

e

Blu

e

Blu

e Blu

e

Gre

en

Yellow

-Gre

en

Yellow

-Gre

en

Bro

wn

OPTIM

AL

mkII

OPT

IMA

L 4

00/6

00

Brown

Red

3

Yellow

2

2

22

22 3

33

3

2

2 2

2 2 23

3 3

4

4 4 6

5

5 5 7

D BBA C

C

BBA C

C

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Whit

e

Whit

eBlu

e

Blu

e

Blu

e

Blu

e

Red

Red

Red

Red

SW

ITC

HED

-MO

DE

PO

WER

SU

PPLY

SK

S-3

50-4

8

Red

Red

Bro

wn

Bro

wn

Bla

ck

Bla

ck

Inta

ke f

an

Exhaust

fan

Anti

-fro

st s

enso

r

Byp

ass

senso

rSo

cket

RJ1

1So

cket

RJ1

1

Sock

et

RJ1

2So

cket

RJ1

2

Siło

wnik

BELIM

O

Manualn

y B

ypass

Contr

ol panel

AC2800

Sock

et

RJ1

1

Plu

g R

J11

0,5

m

20m

Plu

g R

J11

Plu

g R

J12

Plu

g R

J12

Plu

g R

J11

Bla

ck1

1

11

11 1

11

1

22

22

1

1 1

1 1 1

Bla

ck

Bla

ck

Bla

ckG

ND

GN

D

A2

+12V

+48V

B1

B2

GN

D

N

TS2

N

GN

D

M2

TS1

M1

GN

D

L

Al

+12V

AU

/M

AU

/M

Bla

ck

LL

PE

PE

NN

LL

PE

PE

NN

LL

PE

PE

NN

LL

PE

PE

NN

T2A/250V

Yellow-Green

Blue

GN

DPW

R

230V

AC

CO

MBIN

ED

SLO

T

GN

D+48V P

EN

L

EN

AC2800 DIGITAL CONTROLLERInstructions

- WEEKLY PROGRAMMABLE TIMER- BLUE BACKLIGHT (OPTIONAL)- ANALOG 0-10VCD OUTPUT FOR FAN CONTROLLER- ON/OFF TIMER- ELECTRONIC THERMOMETER

SPECIFICATION

SET POINT RANGE: 0-99% SETP: 1% NUMBER OF ZONES PER 24 HRS: 4 TEMPERATURE SENSOR: NTC 10K PROTECTION DEGREE: IP30 DISPLAY: LCD

ASSEMBLY

CONNECTION SCHEME

rev:

12.0

7.1

7

Op

tima

l 40

0/6

00

CONTROLLER'S DESCRIPTION

RT - TEMPERATUREwithout RT - AIR FLOW

ROOM TEMPERATURE

DAY OF THE WEEK

CLOCK

INTAKE DEGREE

DECREASING INTAKEINCREASING DEGREE

INTAKE VIEW

CLOCK SET UP

TURN ON BOOST ON/OFF

POWER SUPPLY: DC 12V-15VDIMENSIONS: 86x86x13 mmCASING: ABS FLAME RESITANTOPERATION RATING:TEMPERATURE: 0~40°CHUMIDITY: 5~95% (NON-CONDENSATING)

EN

rev:

12

.07

.17

Op

tim

al 4

00

/60

05.4. Obsługa panelu sterującego

5.4.1.POWER ON/OFF

5.4.2. INTAKE VIEW

5.4.3. BOOST MODE

5.4.4. WORKING IN WEEKLY PROGRAMME

5.4.5. SETTING THE CLOCK

5.4.6. ICONS ON DISPLAY

5.4.7. PROGRAMMING THE CONTROLLER

- Turn on/off AC2800 by pressing

Pressing will indicate percentage of intake.

For boost press "M". In this mode fans will work at their

maximum RPM what will also be shown on display by

In this mode controller works directly after it;s turned on. It

displays current room temperature next to "RT" sign.

Additionaly one of signs is displayed showing

intensity of ventilation in rooms.

Pressing or switches level of intake. Implemented

change is on untill switching to next programmed mode.

Press – to set minutes

Press or zmienić nastawę minut.

Again press – to set hours.

Press or to set hours.

Press to set day of the week.

Using or choose accurate day of the week

"Mo/Tu/We/Th/Fr/Sa/Su".

is shown when intake is is above 60% maximum value.

is shown when inatke is between 30%-60% maximum

value.

is shown when intake is below 30% maximum value.

Press and hold for 3 seconds until number 1 and Mo

(Monday) shows. This means time zone nr 1 is set for

Monday.

Press or to set required zone.

To confirm press Use or to set required intake (%).

55

55

5555

55

55

55

55

55

55

55

55

To confirm press

After programming all 1-4 for Monday, repeat all above after

switching days Tu/We/Th/Fr/Sa/Su.

Use scheme below to avoid mistakes, in which you can

prepare needed data during programming.

Weekly clock

Day

Time zone

1 2 3 4

Time zone

Time zone

Time zone

Monday

Tuesday

Wednesday

Thursday

Saturday

Friday

SundayEN

rev:

12

.07

.17

Op

tima

l 40

0/6

00

400

95

600

recu

pera

tive

AC2800 co

ntro

ller

Varia

ble

speed re

gula

tion

RVU

BVU

FE

A+

A+

B

OPTIM

AL 6

00

OPTIM

AL 6

00

OPTIM

AL 4

00

OPTIM

AL 4

00

-33

-33

-69

-69

-10

-10

DO

SPEL

DO

SPEL

Supplie

r

Device

indentifie

r

Specific e

nerg

y consu

mtio

n (SE

C)

- ave

rage clim

ate

Specific e

nerg

y consu

mtio

n (SE

C)

- cold

climate

Specific e

nerg

y consu

mtio

n (SE

C)

- warm

climate

SEC ra

nge

- ave

rage clim

ate

SEC ra

nge

- cold

climate

SEC ra

nge

- warm

climate

Device

type

Type o

f drive

Heat re

cove

ry system

Therm

al e

fficiency

of h

eat re

cove

ry

Maxim

um

flow

rate

Fan's d

rive p

ow

er

consu

ptio

n

Sound p

ow

er le

vel (L

)w

a [d

B(A

)] 5

2 5

3

[]

3m

/h

[]

W140

200

%

Unit

Inte

rnal le

akage ra

te

Filte

r change w

arn

ing sig

nal

Website

Annual e

lectricity co

nsu

mptio

n

2per 1

00 m

Contro

l facto

r (CTRL)

The a

nnual h

eatin

g sa

ved

(cold

climate

)

The a

nnual h

eatin

g sa

ved

(ave

rage clim

ate

)

Inte

rnal le

akage ra

te

The a

nnual h

eatin

g sa

ved

(warm

climate

)

Flo

w ra

te

Pre

ssure

diffe

rence

rate

Specific p

ow

er in

put (SP

I)

Pro

duct in

form

atio

n a

ccord

ing to

Com

missio

n R

egula

tion n

o 1

253/2014 a

nd C

om

missio

n R

egula

tion n

o 1

254/2014

3[m

/s]

0,0

80,1

2

OPTIM

AL 6

00

OTIM

AL 4

00

Unit

[Pa]

50

50

ww

w.d

osp

el.co

m

85

[kW

h p

rimary

energ

y/ye

ar]

[kW

h p

rimary

energ

y/ye

ar]

44

43

[kW

h p

rimary

energ

y/ye

ar]

20

20

[kW

h/ye

ar]

441

422

%N

ot m

ore

than 2

0,9

5

%N

ot m

ore

than 2

Visu

al filte

r ch

ange w

arn

ing sig

nal

0,3

50,3

3[W

/(

]3

m/h)

EN

DOSPEL Sp. z o.o.ul. Główna 188

42-280 Częstochowatel. +48 34 365 98 43fax +48 34 360 97 00

e-mail: [email protected]

Dospel reserves the right to introduce any changes regarding its products resulting from ongoing technical development. Dospel shall not be liable for printing errors.