    Dry type transformers-ideal for FPSO

    - Transformers for electrical and drivesystems

    Ar ild Furnes,ATPA OGP/Petrobras workshop, 22.09.09

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    2/24

    ABB GroupSeptember 24, 2009 | Slide 2

    Transformers for Ships and Offshore - Standards

    IEC 60092-303 Electrical installations in ships, Part303 equipment -

    Transformers for power and l ighting IEC 61892-3 Mobile and fixed offshore units, Part 3

    equipment -

    Clause 5 -Transformers for power and lighting

    Both refer to general transformer standards IEC 60076 (alltypes) and IEC

    60726 (Dry type transformers) Preferably air cooled dry type

    Liquid-immersed transformers preferably hermeticallysealed type, no spilling of liquid

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    3/24

    ABB GroupSeptember 24, 2009 | Slide 3

    Transformers for Ships and Offshore - Standards

    Differences to be noticed to on shore applications

    Environmental conditions

    Air temperature higher (45 C or higher) = reduced temperature rise

    Cooling water temperatures high = reduced temperature rise

    Humidity and salt = degrees of enclosure

    Inclinations, static and dynamic = mechanic requirements

    Acceleration and vibrations = mechanic requirements, flexibleconnections

    EX-classified zones = specifically designed transformers

    Materials to be used

    Self extinguishing

    High tracking index

    Halogen free

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    4/24

    ABB GroupSeptember 24, 2009 | Slide 4

    Classification often required /ABS, DnV, Rina, Loyds etc)

    Type testing and special tests often required. Routine testsmandatory according to IEC.

    Insulation between HV and LV systems

    Normal practise to have earthed screen between HV and LVwindings

    Reduces capacitively transferred overvoltages fro HV side toLV ITsystems

    Reduces transferred EMC disturbance from drive systems toship distribution system

    Screen is technically clear requirement, increased or

    improved insulation of HV systems is not

    Drive supply transformers should have the screen for EMCreduction, all high power drives make EMC-noise to supplynetwork

    Screen inside transformer is economic way to block EMC

    Transformers for Ships and Offshore - StandardsDifferences to be noticed to on shore applications

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    5/24

    ABB GroupSeptember 24, 2009 | Slide 5

    Transformers for Ships and Offshore - StandardsDry transformers-Technologies

    Dry type transformers IEC 60726

    Fire class F0,F1,F2

    For ships only possibility F1 (self extinguishing), F2 should be able operate

    under fire for limited time is not existing Impulse voltage level according to list 2 (higher alternative)

    Vacuum breakers create switching over voltages, more margin

    3,6 kV = LI 40 kV

    7,2 kV = LI 60 kV

    12 kV = LI 75 kV

    transformers at end of short cables (100-200 m) critical

    If the LI level is not mentioned, you may be getting the lower oneie list 1

    Classification rules have no impulse voltage requirements Area to be improved

    Dry type transformers cannot be installed without extensive measures onExplosion Hazard Zones at all, but must be installed on Safe Areas

    Temperature hot spots on coils, Sparking and charging at switching on

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    6/24

    ABB GroupSeptember 24, 2009 | Slide 6

    Transformers for Ships and Offshore - StandardsDry transformers-Technologies

    Dry type transformers IEC 60726

    Encapsulated type = resin encapsulated (cast resin or filamentwound inside resin)

    Non-encapsulated types =open wound (traditional, with limitation)

    Environmental class E0, E1,E2

    For ships minimum E1 ,can be energised while having moisture onthe transformer coils, but note that in the standard no switching

    overvoltage is considered (known to be a problem with vacumbreakers of certain designs in small offshore networks)

    E2 recommended (can operate while humidity is being sprayed onthe transformer, has more margin compared to E1)

    E1 and E2 can be reached only with encapsulated designs

    Climatic class C1,C2

    For ships minimum C1 (-5 C) is sufficient

    For scandinavian Yards C2 (-25 C) is necessary while buildingships

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    7/24

    ABB GroupSeptember 24, 2009 | Slide 7

    Most common variants of dry type transformersOther important considerations

    Rectifier duty.

    Derating approx. 20 % with

    6 puls diode rectifier. Primary phase shift

    removes possibility fortapping, no-load voltageneeds to be carefullyselected from system study

    Several cooling alternatives

    available for both dry type

    AN, AN/AF, AF/AF, AF/WF

    Ingress protection of enclosure

    The higer number, biggerunit not to exceed thermal

    limits

    Two dry typetransformers incommon enclosurefor 24 pulse rectiferduty.

    Petrobras requiresdedicated enclosureas per today.

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    8/24

    ABB GroupSeptember 24, 2009 | Slide 8

    Most common variants of dry type transformersOther important considerations

    Both size and audible noisecan be reduced by materialselection and design.

    High grade orientend core steel

    High grade copper wire or foil

    High impedance many turns,low impedance fewer turns

    Influences the physical

    dimensions

    Vacum cast coil

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    9/24

    ABB GroupSeptember 24, 2009 | Slide 9

    Most common variants of dry type transformersDry VPI open wound with paper

    Recommendations for offshore applications

    Only for LV distribution

    Below 500 kVA AN

    Indoor in controlled environment

    Salt laden air will degrade

    paper insulation over time

    Up to approx 12 MVA

    15 kV

    Several cooling options available

    Both Cu and Al windings available

    Cost efficient

    Petrobrasspecifications ingeneral calls for resinencapsulated types

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    10/24

    ABB GroupSeptember 24, 2009 | Slide 10

    Most common variants of dry type transformersVacum Cast Coil

    Classes: E2, C2, F1

    Partial discharges:

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    11/24

    ABB GroupSeptember 24, 2009 | Slide 11

    Most common variants of dry type transformersResibloc

    Classes: E2, C2, F1

    Partial discharges close to zero

    Insulation : 155C (F), 180C (H)

    Design Temperature: 40 C

    Design according to class up to 55 C

    amb. or 38 C for cooling water.

    Up to approx 40 MVA

    45 kV

    Several cooling options available

    Both Cu and Al windings available

    Glass-fiber reinforced, crack free

    Wound resin impregnated coil

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    12/24

    ABB GroupSeptember 24, 2009 | Slide 12

    MTBF Resibloc Transformers433 years !

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    13/24

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    14/24

    ABB GroupSeptember 24, 2009 | Slide 14

    Why use dry type transformers on FPSO

    Easy to install, simple foundation and enclosure

    Very clean, no oil, pits etc.

    Less fire load (energy) than oil filled

    Epoxy has higher ignition temp than special synthetic ester

    Can be assembled offshore by skilled service people

    Easy to connect cables and/or bus-ducts

    Easy access for inspection through bolted covers or hingeddoors

    Easy to install fans later to increase power if provisions(Space under coils) are made. Approx. 30 40 % increase

    Practically maintenance free

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    15/24

    ABB GroupSeptember 24, 2009 | Slide 15

    Why use dry type transformers on FPSOAreas to consider liquid filled transformers

    Outdoor location in case of limited HVAC and indoor space

    Highly corrosive offshore location. Tropical condition

    worse than cold in this matter. Exposed parts of Liquidfilled are galvanized and painted.

    Zone requirement

    Dry type not suitable due to difficulties to ensure no

    hotspots on coils and sparking during energizing. Very high power

    Due to weight and size.

    Multi winding transformers for drives (more than 3secondaries due to balance of impedance/flux) Liquid filledare more flexible with respect to phase shift.

    If OLTC (on load tap changer/AVR) is needed

    Very large OLTC for dry types.

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    16/24

    ABB GroupSeptember 24, 2009 | Slide 16

    Why use dry type transformers on FPSOLiquid filled application

    Roof of FPSO E-house

    Compact liquid filled

    Corrugated tank design

    Conservator type design

    Zone 1 or 2 outdoor

    FPSO outside WestAfrica.

    Multi Phase PumpPower ControlModule with

    drives inside

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    17/24

    ABB GroupSeptember 24, 2009 | Slide 17

    Why use dry type transformers on FPSOLiquid filled execution

    OF/WF transformer forpropuplsion

    Seawatercooled

    Syntetic ester,biodegradeable

    300 deg C flamepoint Most compact design

    available,

    Very beneficial on large

    compressor drives etc.

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    18/24

    ABB GroupSeptember 24, 2009 | Slide 18

    Why use dry type transformers on FPSOLiquid filled on module outdoor

    Single lift PowerControl Module forsubsea Multi PhasePump

    Liquid filled

    transformer installedoutdoor on frame toreduce need for largecooling units insidemodule

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    19/24

    ABB GroupSeptember 24, 2009 | Slide 19

    Dry type transformer with water cooling AF/WFIncreasing interest in the offshore and ship market

    Reduces need for HVAC andducts

    Reduces audible noise

    Approx. 5 % of losses toambient, rest to water

    Min. IP 44 design enclosure

    Cooler for seawater available(double titanium tube)

    Redundant blower and coolerarrangement available

    No liquid carryingpipe allowed.

    Clause 1.4 inPetrobras

    I-ET-3000.00-5140-700-PCI-001ELECTRICALBASIC DESIGNGUIDELINES

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    20/24

    ABB GroupSeptember 24, 2009 | Slide 20

    Dry type transformers in a systemWhat can ABB do ?

    Provide the best technologies available conforming withPetrobras specifications and applicable regulations.

    Take responsibility for the integrity of the complete Drive systems

    Electrical system

    Load flow calculations and considerations( impedance,no-load/nominal voltage of the transformer and voltagedrop during DOL motor starts)

    Harmonic calculations (THD)

    Provide transformers which offers the best possiblecancellation configuration with the VFD

    Provide and dimension pre-magnetizing system forreducing inrush current when energizing the transformers

    Up to 1/18 reduction of inrush current !

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    21/24

    ABB GroupSeptember 24, 2009 | Slide 21

    Dry type transformers in a systemConfiguration of converter duty transformers

    Distortion with 6 pulse

    Distortion with 12 pulse

    Distortion with 24 pulse

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    22/24

    ABB GroupSeptember 24, 2009 | Slide 22

    Dry type transformers in a systemSimple pre-magnetizing system

    T1

    C2

    C1

    C3

    T2440 V

    Simple and cost effective ifback up supply available

    Integrated in transformerenclosure

    In Switchgear

    Separate assembly

    Figure of pre-magnetizingsystem in a essential modedrilling transformer to 690 V

    drilling drive system fromweak 440V emergencysupply network

    D t t f i t

  • 8/11/2019 Dry Type Transformers-ideal for FPSO

    23/24

    ABB GroupSeptember 24, 2009 | Slide 23

    Dry type transformers in a systemPeregrino WHPs

    Total 10 units for waterinjection, booster andproduction pumps

    ACS 1000i

    24 pulse integrated dry typetransformer

  • 8/11/2019 Dry Type Transformers-ideal for FPSO