Transcript of Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.
![Page 1: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/1.jpg)
Dr T R Nichols CPhys MIFireE
Mr A Palau Bosch
Fire Protection of Compact Archive
Storage
![Page 2: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/2.jpg)
New Bodleian Library, Oxford University, UK
2
![Page 3: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/3.jpg)
Description of the Site
3
Multi-Level and Multi-Type Risk Areas• 11 Levels
• Basement Archives
• Reading Rooms
![Page 4: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/4.jpg)
Description of the Site
4
Archive Storage in Basement levels• Storage in open racks and
compact racks
• Low ceilings and confined with many obstructions (lighting, ducts)
• <150mm gap from racks to ceiling
• Compact racking gap 25mm to maximize storage and provide safe egress
![Page 5: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/5.jpg)
Risk Analysis
5
Storage of various fire loads including paper, books, micro-film, CD cases
• Fire load very large
Irreplaceable historical works and artefacts
Large areas, below and above ground with difficult access and egress
Ignition sources minimal
Main fire source due to arson
On-site water storage limited
Limited space to run extinguishing system pipe work
![Page 6: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/6.jpg)
Consultant Assessment
6
Objectives:• Quickly control fire within in prescribed area (defined as within a block
of racks)
• Control of temperature
• Attenuation of Radiation (stopping of flame spread)
• Minimize collateral damage through water clean up
Design Parameters• AMAO detailed as 144m2 but later defined on formula based on actual
quantity of nozzles activating
• Specified a high pressure mist system
• 30 minute run time
![Page 7: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/7.jpg)
Tender Process
7
Tender process identified that NO third party protocol exists for risks
NFPA 750 requires that fire testing is undertaken pertinent to the risk8.2.4.1 Fire test protocols shall be designed to replicate the range of the application parameters associated with a particular hazard or occupancy
A performance based test was agreed with the stakeholders• Bodleian Library
Archivists Project Management
• Fire Consultant
• Independent verifier (Warrington Fire Research)
• Main Contractor
• Tyco Certified Distributor/Installer (EA-RS Fire Ltd)
• Tyco (LPG)
![Page 8: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/8.jpg)
Defining the Tests
8
Pass/fail criteria
Protocol written to include:• Test rig and layout, and type of test
Open rack tests Compact rack test Variations of compact rack gaps 25mm upwards
• Fire load (material type and configuration)
• Data acquisition (sensors, imaging)
• Hardware required (pumps, nozzles, pipe, tank, generator)
• Health & Safety procedures (fire brigade, etc)
Location determined (Vinci Test Centre, Leighton Buzzard, UK)
![Page 9: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/9.jpg)
Test Rig
9
![Page 10: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/10.jpg)
Water Mist Components
10
• Test Nozzles
• Pump Set
• Generator
• Water Supply
![Page 11: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/11.jpg)
Sensors
11
• Thermocouples
• Probe & Plate type
• Pressure Transducers
• Cardboard Register (compact rack test only)
![Page 12: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/12.jpg)
Cameras
12
• VGA + Intelligent Video to detect smoke & flame
• 720 HD
• Pan Tilt Zoom Combined Thermal
![Page 13: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/13.jpg)
Data Acquisition
13
• Multi-channel analyser
• Data logging
• Temperature averaging function
• Time stamp
• Fully calibrated
![Page 14: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/14.jpg)
Location of Fire – Open Rack Test
14
Fuel - 120 ml RON95 petrol
![Page 15: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/15.jpg)
Sensor & Camera Location - Open Rack Test
15
![Page 16: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/16.jpg)
Temperature Profile - Open Rack Test
16
![Page 17: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/17.jpg)
Order of Nozzle Operation - Open Rack Test
17
![Page 18: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/18.jpg)
Fire Spread - Open Rack Test
18
![Page 19: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/19.jpg)
Fire Damage - Open Rack Test
19
As found As cleared showing damage to only one section
![Page 20: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/20.jpg)
Location of Fire – Compact Rack Test
20
Fuel - 120 ml RON95 petrol
![Page 21: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/21.jpg)
Sensor & Camera Location - Compact Rack Test
21
![Page 22: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/22.jpg)
Temperature Profile - Compact Rack Test
22
![Page 23: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/23.jpg)
Temperature Profile - Compact Rack Test, Aisle Boundary
23
![Page 24: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/24.jpg)
Order of Nozzle Operation - Compact Rack Test
24
![Page 25: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/25.jpg)
Fire Spread - Compact Rack Test
25
![Page 26: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/26.jpg)
Fire Damage - Compact Rack Test
26
![Page 27: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/27.jpg)
Endorsement – Consultant & Test Authority
27
![Page 28: Dr T R Nichols CPhys MIFireE Mr A Palau Bosch Fire Protection of Compact Archive Storage.](https://reader038.fdocuments.us/reader038/viewer/2022103022/56649cdc5503460f949a7305/html5/thumbnails/28.jpg)
Endorsement – Fire Brigade
28