Dr. Salvador Acha – Imperial College Research Associate

36
Dr. Salvador Acha – Imperial College Research Associate 9th January 2012 Supermarket Tasks and Strategies in Reducing Energy Demand and CO2 Emissions

description

Dr. Salvador Acha – Imperial College Research Associate. Supermarket Tasks and Strategies in Reducing Energy Demand and CO 2 Emissions. 9th January 2012. Contents. Who is Sainsbury’s?. Supermarket chain was founded in 1869. - PowerPoint PPT Presentation

Transcript of Dr. Salvador Acha – Imperial College Research Associate

Page 1: Dr. Salvador Acha – Imperial College Research Associate

Dr. Salvador Acha – Imperial College Research Associate

9th January 2012

Supermarket Tasks and Strategies inReducing Energy Demand and CO2 Emissions

Page 2: Dr. Salvador Acha – Imperial College Research Associate

ContentsSections

1 Sainsbury’s supermarkets

Collaboration agreement / Devising a low carbon roadmap

2 Engineering project: Hythe

• A day in the life of Hythe• Supermarket energy systems• Case Studies• Going Forward

3 Q & A

Page 3: Dr. Salvador Acha – Imperial College Research Associate

Who is Sainsbury’s?• Supermarket chain was founded in 1869.• Currently has16% share of UK market (3rd place), tallying

over 600 supermarkets and 400 convenience stores.• Approximate labour force of 200,000 workers.• Annual sales of £20,000 m and £600 m profits (3%)• Annual energy demand (only supermarkets) – 77% power

and 23% natural gas.

Electricity Use (MWh)

Electricity CO2 (tonnes)1

Electricity Bill (£)3

Natural Gas Use (MWh)

Natural Gas CO2 (tonnes)2

Natural Gas Bill (£)4

1,554,082 860,961 119,664,314 462,132 85,032 9,242,648$2,393,286,280 $184,852,960

Notas:1Electricas Emisiones UK: 0.554 kgCO2/kWh2Natural Gas Emisiones UK: 0.184 kgCO2/kWh3Electricity cost: 0.077 p/kWh = $1.54 pesos/kWh4Natural gas cost: 0.02 p/kWh = $0.40 pesos/kWh

Page 4: Dr. Salvador Acha – Imperial College Research Associate

Strategic Collaboration

SustainabilityWaste

CostEnergy Security

Carbon Footprint

Engineering DesignSmart Systems

Modelling/IntegrationClimate Policy

Optimisation

2020 Storeand beyond

Objectives:- Decarbonisation- Energy efficiency and cost

savings- Wider sustainability- Education and training

BackgroundMarch 2010, Sainsbury’s announced a 5 year business partnership with Imperial College London and Grantham Institute.Covers Climate Change, Supply Chain Management, Energy Efficiency and Intelligent System Operation and Low Carbon Construction.Vision • Develop low carbon pathways to create a store fit for 2020 and beyond ahead of sector• Scenario planning – identify future performance requirements + key policy challenges,

opportunities and constraints.

Page 5: Dr. Salvador Acha – Imperial College Research Associate

Low Carbon Roadmap• Has the purpose to illustrate the factors Sainsbury’s should

consider when defining their long term energy strategy

Page 6: Dr. Salvador Acha – Imperial College Research Associate

Hythe is our Test Bed• The “smart-grid supermarket” concept focuses on

managing the different processes occurring within a store with the objective of enhancing its energy consumption for mutual cost and environmental benefits while not forsaking the appeal and daily operations of supermarkets.

• It will be a learning exercise– Practical implementation or use of existing smart controls to enhance

supermarket energy demand.• Management of in-store processes

– Enhancing energy efficiency strategies and ‘load flexibility’ in order to calculate the capacity available for devising ‘demand response’ programs.

Page 7: Dr. Salvador Acha – Imperial College Research Associate

Hythe Deliverables• Objectives of the project include the following:

– Conduct a thorough monitoring of energy demand– Understand demand characteristics of services– Identify operational constraints of systems– Perform system trials that either save/shift energy use– Define best practices of energy demand per system

and reduce carbon emissions– Trials will serve to validate Imperial College models– Assess potential of adopting flexible tariff schemes and

offering demand response services to the grid– If trials are successful adopt roll back/roll fwd plan

Page 8: Dr. Salvador Acha – Imperial College Research Associate

Hythe Specs – A Carbon Step Store• Store specifications and what's innovative?

– Opened in late February 2011– Sales floor area of 35,759 sq. ft. with reflective ceiling,

light tubes and considerable windows in the shop front and GM areas

– Thorough energy monitoring with over 50 sensors– Rain water harvesting unit reduces water demand– Biomass boiler supplies low carbon heat with a

maximum 700 kW capacity– Generator supplies low carbon electricity with a

maximum 140 kW capacity (installed recently)– 50 kW PV panels in the roof

Page 9: Dr. Salvador Acha – Imperial College Research Associate

A day in the life of Hythe• About 5000 kWh/day = £385/day = 2.7 tCO2

– 272 kW peak, 130 kW base, 205 kW average

00:30

01:00

01:30

02:00

02:30

03:00

03:30

04:00

04:30

05:00

05:30

06:00

06:30

07:00

07:30

08:00

08:30

09:00

09:30

10:00

10:30

11:00

11:30

12:00

12:30

13:00

13:30

14:00

14:30

15:00

15:30

16:00

16:30

17:00

17:30

18:00

18:30

19:00

19:30

20:00

20:30

21:00

21:30

22:00

22:30

23:00

23:30

00:00

0

13

26

39

52

Hythe Energy Profile on 15/03/11 - Overlayed Chart

Lighting

Refrigeration

HVAC

Bakery

Hot Food

Others

Time

kWh

Refrigeration systems begin consuming more energy during trade hours due to higher occupancy levels and ambient temperatures.

Lighting systems go on 15 minutes before store opens and then smart controls manage the sales floor lighting while trading.

HVAC system consume most of its energy through AHU’s during trading hours; weather conditions, occupation and set-points drive this demand.

Bakery activities begin at 4 am and are usually over by lunch time.

Hot food activities begin at 5 am when prepping the fish and meat counters, energy peaks indicate oven use for chickens, pastries, pizzas and staff food.

Page 10: Dr. Salvador Acha – Imperial College Research Associate

A day in the life of Hythe• Load composition

– Lighting 32%, Refrigeration 39%, HVAC 10%, Hot Food 8%, Bakery 6%, Others 4%

00:30

01:00

01:30

02:00

02:30

03:00

03:30

04:00

04:30

05:00

05:30

06:00

06:30

07:00

07:30

08:00

08:30

09:00

09:30

10:00

10:30

11:00

11:30

12:00

12:30

13:00

13:30

14:00

14:30

15:00

15:30

16:00

16:30

17:00

17:30

18:00

18:30

19:00

19:30

20:00

20:30

21:00

21:30

22:00

22:30

23:00

23:30

00:00

0

25

50

75

100

125

150

Hythe Energy Profile on 15/03/11 - Stacked Chart

OthersHot FoodBakeryHVACRefrigerationLighting

Time

kWh

Page 11: Dr. Salvador Acha – Imperial College Research Associate

A day in the life of Hythe• League Table Analysis

– Ability to monitor thoroughly improves the level of analysis

Top usersof energy

Page 12: Dr. Salvador Acha – Imperial College Research Associate

A day in the life of Hythe• Carbon emissions

– Having a biomass boiler shifts almost entirely the carbon emissions to the use of electricity

Hythe Carbon Emissions Profile on 28/07/11 - Stacked Chart

0

20

40

60

80

00:30 02:30 04:30 06:30 08:30 10:30 12:30 14:30 16:30 18:30 20:30 22:30

Time

CO

2 (k

g) Electricity CO2

Heat CO2

Page 13: Dr. Salvador Acha – Imperial College Research Associate

Mains vs Max Daily Temperature - Monday to Saturday

y = 0.5313x2 + 13.766x + 4727.3

4600

4800

5000

5200

5400

5600

5800

0 5 10 15 20 25

Daily Max Temperature

kWh

209,171

122,130

46,185

36,153

27,704

19,224 6,798

2nd Quarter Electricity Load Distribution (kWh)

Refrigeration

Lighting

HVAC

Hot Food

Bakery

Others

Unmetered

Hythe Monitoring• Opened in February 2011, Hythe allows the partnership to

learn the characteristics of each system’s energy demand.– Trials of different systems for energy efficiency and demand

response strategies which will benefit SSL are in progress– Desired outcome will be to better understand how to optimally

integrate the systems• Benchmarking:

– Hythe per week: 1st Q = 0.97 kWh/ft2 and 2nd Q = 1.01 kWh/ft2 – Baselines per week 05/06 = 2 kWh/ft2 and 09/10 = 1.40 kWh/ft2

173,785

138,150

45,836

38,370

29,599

18,277 7,171

1st Quarter Electricity Load Distribution (kWh)

Refrigeration

Lighting

HVAC

Hot Food

Bakery

Others

Unmetered

Page 14: Dr. Salvador Acha – Imperial College Research Associate

Hythe Load Profile Analysis• Thorough monitoring allows us to build virtual store

models and hence assess trade-offs in energy design strategies when the framework is strengthened

• Consequently, impact of low carbon technologies can be estimated (e.g. biomass boiler, bio fuel generator)• At Hythe new technologies can abate emissions 20-45% and

imported electricity from 1-25%

32,000

33,000

34,000

35,000

36,000

37,000

38,000

39,000

0

4

8

12

16

20

24

28

8 10 12 14 16 18 20 22 24 26 28 30 32

Cels

ius

Week

Weekly Energy Demands1st and 2nd Quarters

Max Avg Temp (C)

Min Avg Temp (C)

Total Main (kWh)6,000

8,000

10,000

12,000

14,000

16,000

0

5

10

15

20

25

30

21 23 25 27 29 31 33

Cels

ius

Week

Weekly Heat Demands2nd Quarter

Max Avg Temp (C)

Min Avg Temp (C)

Boiler (kWh)

Page 15: Dr. Salvador Acha – Imperial College Research Associate

Quarterly Report• Refrigeration relationship results (spring 2011)

– Temperature variations have an impact on pack performance however this is not the case for cabinets

Packs vs Max Daily Temperature - Monday to Saturday

y = 0.5699x2 + 21.267x + 933.13

0

500

1,000

1,500

2,000

2,500

0 5 10 15 20 25

Daily Max Temperature

kWh

Cabinets vs Max Daily Temperature - Monday to Saturday

y = -0.026x2 + 1.9922x + 515.13

0

200

400

600

800

0 5 10 15 20 25

Daily Max Temperature

kWh

Page 16: Dr. Salvador Acha – Imperial College Research Associate

Quarterly Report• HVAC relationship results (spring 2011)

– Temperature variations have a slight impact on air handling unit performance but over 15 degrees demand more or less stagnates

AHUs vs Max Daily Temperature - Monday to Saturday

y = -0.3337x2 + 14.289x + 163.1

0

100

200

300

400

500

0 5 10 15 20 25

Daily Max Temperature

kWh

Page 17: Dr. Salvador Acha – Imperial College Research Associate

Quarterly Report• Lighting relationship results (spring 2011)

– As sunlight hours increase the energy demand is reduced indicating that natural light is well used by light tubes, windows and reflective ceiling

Sales Floor Area vs Sunlight Hours - Monday to Saturday

y = 0.1153x2 - 9.2016x + 1166.1

0

300

600

900

1200

1500

0 3 6 9 12 15

Daily Sunlight Hours

kWh

Page 18: Dr. Salvador Acha – Imperial College Research Associate

Quarterly Report• Daily profile results (spring 2011)

– Logging energy data every half hour allows us to visualise daily load profiles with great detail, this will help us build energy models

– This figure displays daily refrigeration demand, clearly showing how the system behaves differently due to weather conditions

Hythe Energy Profile - Refrigeration > max 22 Celsius, < min 6 Celsius, = 13 Celsius

0

20

40

60

80

00:30 02:30 04:30 06:30 08:30 10:30 12:30 14:30 16:30 18:30 20:30 22:30

Time

kWh

Page 19: Dr. Salvador Acha – Imperial College Research Associate

Case study: Lighting System• Research and trials

– Through the Clipsal system lux intensity can be regulated and there is an opportunity to question current settings (900 lux) and re-define best practices when commissioning new projects

– Projected savings at Hythe under current settings are of 50 tCO2

Pre-Clipsal Annual Projections DSI 96 Annual Projections DSI 93 Annual Projections DSI 90 Annual Projections DSI 87 Annual ProjectionskWh 424,320 kWh 410,046 kWh 353,132 kWh 335,855 kWh 320,242Bill 32,673 Bill 31,574 Bill 27,191 Bill 25,861 Bill 24,659kgCO2 229,557 kgCO2 221,835 kgCO2 191,044 kgCO2 181,698 kgCO2 173,251

DSI Control, Lux, and Power Relationship

0

20

40

60

80

100

189 277 415 571 654 756 869 967 1059

Illuminance (Lux)

DSI %

0

20

40

60

80

100

DSI %Power

Page 20: Dr. Salvador Acha – Imperial College Research Associate

Hythe Lighting (September 2011)Granularity is key in analysing performance

Car park load impact

Dimming is being achieved efficiently in GM, shop front,and car park areas when natural day is abundant

Diming in the shop front area is not being achieved

Page 21: Dr. Salvador Acha – Imperial College Research Associate

Case study: Lighting System

• Further work– Revise final commissioning and ideal sensor location– There are 100 Sainsbury’s sites with Clipsal – roll back/fwd

program would be an easy win (10 store pilot approved!!!)– Each store is unique in itself, however new standard settings can

be established based on store characteristics

93% DSI 90% DSI

Peak Reduction

Sensor 1Next to a duct

Page 22: Dr. Salvador Acha – Imperial College Research Associate

Case study: Lighting System• Early learning’s from trials are:

– Customers and staff have not perceived changes and these have not impacted trade

– Trials have been successful due to the robust lighting system control, thorough study of how the system works, and good collaboration between the partners

– Lighting system at Hythe has benefited greatly from light tubes, shop front windows, and reflective ceilings and floor

– Flexible energy demand in the lighting system is non-intrusive with Sainsbury’s business and has potential for further uses that can generate value for the company

– Dial-in system is required to easily modify settings

Page 23: Dr. Salvador Acha – Imperial College Research Associate

Case study: HVAC System

• Research and trials– The BMS Trend system controls the heating and cooling of the

building through AHUs and biomass boiler– Although energy use in this system is efficient it was noted

temperature set-points in the dry goods area are not being met– AHUs are low energy consumers, the boiler constitutes most of the

demand (excessive use of the boiler during summer months)

HVAC + Boiler Energy Consumption Distribution

0% 10% 20% 30% 40% 50% 60% 70% 80%

AHU 1 SF-GM

AHU 2 SA

AHU 3 D

H&V Panel

Biomass Panel

Biomass Boiler

Percentage

00:30

01:00

01:30

02:00

02:30

03:00

03:30

04:00

04:30

05:00

05:30

06:00

06:30

07:00

07:30

08:00

08:30

09:00

09:30

10:00

10:30

11:00

11:30

12:00

12:30

13:00

13:30

14:00

14:30

15:00

15:30

16:00

16:30

17:00

17:30

18:00

18:30

19:00

19:30

20:00

20:30

21:00

21:30

22:00

22:30

23:00

23:30

00:00

0

40

80

120

160

200

Hythe Total Energy Profile Profile on 28/07/11 - Stacked Chart

HVAC + BoilerUnmeteredOthersHot FoodBakeryRefrigerationLighting

Time

Ener

gy (k

Wh)

Page 24: Dr. Salvador Acha – Imperial College Research Associate

Case study: HVAC System• Research and trials

– Called Trend bureau to reduce set-points, changes have achieved less wood pellet use (20%) and ambient temperatures are closer to set point, savings are estimated to be 3 tCO2

– However, boiler efficiency also appears to give poor performance

Set-point

25.5C

Old 19C Set-point

22.7C

6,000

8,000

10,000

12,000

14,000

16,000

0

5

10

15

20

25

30

21 23 25 27 29 31 33

Cels

ius

Week

Weekly Heat Demands2nd Quarter

Max Avg Temp (C)

Min Avg Temp (C)

Boiler (kWh)

Page 25: Dr. Salvador Acha – Imperial College Research Associate

Case study: HVAC System• Early learning’s from trial and further work:

– The HVAC system is quite efficient at Hythe and hence it’s demand is not as flexible as for lighting

– Biggest area of opportunity is to save operating costs by using less wood chips to fuel the boiler and optimising temperature set points, and VSD of AHUs; proper post-comission plan is needed!!!

– Relationship between HVAC and refrigeration needs work (waste heat recovery) and hence data needs to be logged

Page 26: Dr. Salvador Acha – Imperial College Research Associate

Case study: HVAC System• Data logging via Trend Energy Manager is now possible:

– Trend BMS is now able to log its data and display it in its interface for Sainsbury’s and Imperial’s benefit

– Level of detail in comparing metrics will allow us to find easier the relationship between HVAC, refrigeration, and ambient store temperatures.

Page 27: Dr. Salvador Acha – Imperial College Research Associate

Case study: Bakery/Hot Food System

• Research and trials– Dr Acha shadowed bakery and hot food counter activities in order

to learn the reasoning behind energy demand patterns– After studying the equipment and the manner in which staff employ

them tips are advisable to save energy – if followed they could save 22 tCO2 without negatively impacting trade

– Hythe management is aware of the potential benefits and are keen on applying these tips to reduce operating costs; plan is needed!!!

00:29

00:59

01:29

01:59

02:29

02:59

03:29

03:59

04:29

04:59

05:29

05:59

06:29

06:59

07:29

07:59

08:29

08:59

09:29

09:59

10:29

10:59

11:29

11:59

12:29

12:59

13:29

13:59

14:29

14:59

15:29

15:59

16:29

16:59

17:29

17:59

18:29

18:59

19:29

19:59

20:29

20:59

21:29

21:59

22:29

22:59

23:29

23:59

0

10

20

30

40

50Hythe Bakery Profile - 3 Typical Days

Time

kWh

00:29

00:59

01:29

01:59

02:29

02:59

03:29

03:59

04:29

04:59

05:29

05:59

06:29

06:59

07:29

07:59

08:29

08:59

09:29

09:59

10:29

10:59

11:29

11:59

12:29

12:59

13:29

13:59

14:29

14:59

15:29

15:59

16:29

16:59

17:29

17:59

18:29

18:59

19:29

19:59

20:29

20:59

21:29

21:59

22:29

22:59

23:29

23:59

0

5

10

15

20

25

30

Hythe Hot Food Profile - 3 Typical Days

Time

kWh

Page 28: Dr. Salvador Acha – Imperial College Research Associate

Case study: Refrigeration System

• Research and trials– Danfoss and Parasense monitor and control this system– Thorough investigation is in progress, hence only energy saving

trials have taken place by covering frozen and chilled cabinets during ‘non-trading’ with exciting results!

– Management needs to reinforce this practice when possible– After sufficient data is collected and approval is given a pre-cooling

approach of frozen products would like to be trialled

Covering frozen and chilled cabinets during non-trading has very attractive savings

Page 29: Dr. Salvador Acha – Imperial College Research Associate

Case study: Refrigeration System

• Early learning’s from the trial and further work:– Working closely with Danfoss/Sainsbury’s/Arcus FM etc is key to

successfully progress in this area– Covers were done last Sunday and compared to a similar day

<Max> 18C <Min> 13C– Average savings over 29 tCO2

00:30

01:00

01:30

02:00

02:30

03:00

03:30

04:00

04:30

05:00

05:30

06:00

06:30

07:00

07:30

08:00

08:30

09:00

09:30

10:00

10:30

11:00

11:30

12:00

12:30

13:00

13:30

14:00

14:30

15:00

15:30

16:00

16:30

17:00

17:30

18:00

18:30

19:00

19:30

20:00

20:30

21:00

21:30

22:00

22:30

23:00

23:30

00:00

00:30

01:00

01:30

02:00

02:30

03:00

03:30

04:00

04:30

05:00

05:30

06:00

06:30

07:00

07:30

08:00

0

15

30

45

60

75Hythe Energy Profiles on Sundays

Lighting Oc-toberLighting JulyRefrigeration OctoberRefrigeration JulyHVAC Oc-toberHVAC July

Time

Ener

gy (k

Wh)

Page 30: Dr. Salvador Acha – Imperial College Research Associate

Case study: Refrigeration System

• Covering frozen cabinets make much sense since:– Cooling of products is more efficient and packs are not worked that

hard (good opportunity to seriously reduce base load)– Talks with suppliers, retail and refrigeration team to make cover

trials a best practice

Page 31: Dr. Salvador Acha – Imperial College Research Associate

Case study: Refrigeration System

Hythe (S2167) : 200 - CS - Coldstore

-40

-30

-20

-10

0

10

20

0 2 4 6 8 10 12 14 16 18 20 22

Time (hr)

Tem

pera

ture

(C)

Product Temp. 1 (24 hours)

Product Temp. 2 (24 hours)

Max Temp.

Min Temp.

• Imperial College recommends a pre-cooling approach of frozen products to assess energy shifting possibilities:– It would be useful to identify how much energy consumption can

be consumed at night time and avoided during the day.– Furthermore, load shedding alternatives such as fan and defrost

dispatch will also be considered– Close monitoring of product temperature is paramount

Pre-cooling beginsPre-cooling ends

Page 32: Dr. Salvador Acha – Imperial College Research Associate

Generation Trials• Research

– Operating strategies to be tested will first serve to conduct tests that help comprehend the real performance of the bio fuel unit while later trials will focus on optimising particular variables

– The operating strategies being considered are:1. Basic response (efficiency and response times)2. Peak shaving (reduce maximum demand times)3. Partial off-grid scenarios (reduce energy imports)4. Cost reduction scenarios (simulate flexible tariff schemes)

Hythe Energy Profile on 15/03/11

0

40

80

120

160

200

240

280

00:30 02:30 04:30 06:30 08:30 10:30 12:30 14:30 16:30 18:30 20:30 22:30

Time

kW

Status Quo

Off-grid

Hythe Energy Profile on 15/03/11

0

40

80

120

160

200

240

280

00:30 02:30 04:30 06:30 08:30 10:30 12:30 14:30 16:30 18:30 20:30 22:30

Time

kW

Status Quo

Peak Shaving 2

What trade-offs doeson-site generation bring?

Page 33: Dr. Salvador Acha – Imperial College Research Associate

Generation Trials• Research

– Operating strategies to be tested will first serve to conduct basic tests that help comprehend the real performance of the bio fuel unit while later trials will focus on optimising particular variables

– The operating strategies being considered are:1. Basic response (efficiency and response times)2. Peak shaving (reduce local grid max demand)3. Partial off-grid scenarios (reduce energy imports/emissions)4. Cost reduction scenarios (simulate flexible tariff schemes)

Hythe Energy Profile on 15/03/11

0

40

80

120

160

200

240

280

00:30 02:30 04:30 06:30 08:30 10:30 12:30 14:30 16:30 18:30 20:30 22:30

Time

kW

Status Quo

Off-grid

Hythe Energy Profile on 15/03/11

0

40

80

120

160

200

240

280

00:30 02:30 04:30 06:30 08:30 10:30 12:30 14:30 16:30 18:30 20:30 22:30

Time

kW

Status Quo

Peak Shaving 2

Page 34: Dr. Salvador Acha – Imperial College Research Associate

Hythe Savings Summary• Hythe estimated bills are £165k/year with a carbon

footprint of 985 tonnes• Potential savings accumulated thus far are £19k (11%)

and 104 tonnes of carbon (10%) – easy wins that can have immediate impact – winter quarter of 0.90 kWh/ft2?

• If we just extrapolate the electrical power savings to 500 Sainsbury’s stores an attractive benefit of 50,000 tCO2 can be achieved

• Sainsbury’s needs to make the most out of these findings. How can we effectively translate this learning's to other sites?

Page 35: Dr. Salvador Acha – Imperial College Research Associate

Going Forward

• Tasks– Continue thorough monitoring of Hythe to learn seasonal variations

and adopt control strategies accordingly; produce quarterly reports– Address technical issues required to conduct refrigeration trial– Assess trials conducted thus far until capabilities have been fully

explored (e.g. lighting, HVAC, refrigeration, etc.)– Implement regular operating schedule of bio fuel generator– Use data to develop energy models that will serve to evaluate

other Sainsbury supermarkets (e.g. Supervision of Sainsbury’s MSc projects; strategic planning and virtual store projects)

– Contribute in developing a single interface that monitors and analyses the energy consumption of the store (GE partner)

– Key learning's should continue to be explored and when ready transferred to SSL for roll back/forward that enrich the companies position in its business sector

Page 36: Dr. Salvador Acha – Imperial College Research Associate

Thank you for your attention!