Page 2: DP.pdf

Standard Electricals Ltd (SEL), a flagship company of the Rs 5500 Crores (US $ 1.2 Billion) professionally managed group QRG Enterprises is a market leader in the field of low voltage electrical distribution & consumer electrical products. The company has carved a niche in the switchgear market by constantly creating innovative solutions and upgrading the product range to meet the ever-changing needs of the discerning customers.

SEL started its manufacturing operations with conventional Rewirable Switch Fuse units over four decades ago. The product range today includes highly sophisticated domestic & industrial products such as MCBs, RCCBs, RCBOs, Distribution Boards (DBs), MCCBs, Changeover Switches, Switch Disconnector Fuses (SDFs), HRC Fuses, CFLs etc.. All products are designed to comply with major Indian & International Standards and are tested at CPRI/ERDA Laboratories.

The quality control systems of the company have been audited by BVQI and the company is certified for ISO 9001: 2000. STANDARD brand of MCBs are CSA, CE, and KEMA marked & being exported to many European & Middle-East Countries.

SEL emphasises on Research & Development which is the lifeline of the company. The Company uses state-of-the-art CAD/CAM for the entire stage of design and development. It has complete in-house facilities for short circuit testing upto 10kA and all related equipments for conducting electrical / mechanical tests.

The company has its manufacturing plant in Haridwar (Uttarakhand), with a work force of more than 500 people including 100 qualified engineers.

STANDARD brand has a wide customer base through its nationwide marketing network having offices in all major cities in India with over 750 Authorised Dealers for effective sales & services.

SEL products are now available internationally having a strong export base. Its products are being exported to the Middle East, South East Asian countries, Malaysia, Singapore, Germany, U.K., South Africa, Kenya, Ghana, Nigeria.

Page 3: DP.pdf
Page 4: DP.pdf

CONTENTS

Miniature Circuit Breaker (MCB) 6

MCB Changeover Switch 16

Residual Current Circuit Breaker 20

(RCCB/ELCB)

Residual Current Circuit Breaker 28

with Over Current Protection

(RCBO)

Distribution Boards (DB) 32

Page 5: DP.pdf
Page 6: DP.pdf

6

Range

6A-40A (B Type)

0.5A-63A (C Type)

0.5A-63A (D Type)

Execution

SP, SPN, DP, TP, TPN & FP

Specification

IS / IEC : 60898-1

MIN

IATU

RE C

IRCU

IT B

REAKER

Page 7: DP.pdf

7

Electricity is an inseparable part of our daily lifestyle. In residential, commercial and industrial sectors there are myriad systems, equipments and sophisticated appliances that depend on electrical energy. Uncontrolled electrical power can be extremely dangerous. Overloads, crowded wiring, short-circuits and all kinds of interruptions in electric supply can lead to devastating losses, least of them being financial.

We at STANDARD are proud to be known and respected the world over for our range of superior quality electrical control and safety devices. Through these, we speak of our lasting concern for safety, economy and productivity for our customers.

The latest product from STANDARD is 10kA MCB, is an advanced Indian design of high performance, current limiting and switching for control and protection of industrial, commercial & domestic electrical sub circuits. It meets the latest specification IS / IEC : 60898-1 of B & C Characteristics.

The primary function of the MCB is to protect the installation such as cable & other components from damage, resulting due to overload & short-circuit fault. Under overload heating effect can occur on cable. Protection in this respect is assured by matching the cable rating to the current rating of MCB.

Under short-circuit condition, mechanical damage can occur due to strong magnetic field caused by high current peaks and overheating of cables on account of "exclusive let through energy". The current limiting action of "MCB" ensures low value of both peak current "cut off" and minimum let through energy.

Features & Benefits

Design

Latest & one of the best designed MCB.

Higher performance in a smaller package.

• MCBs conforms to the latest Standards IS / IEC : 60898-1 / 2002.

• These MCBs provide reliable protection to circuits against overload & short-circuit ideal for industrial, commercial & residential installations.

Certifications

ISI

Higher breaking capacity

Breaking capacity of 10kA for the complete range from 6A to 63A in single pole and multipole tested at CPRI.

Larger terminals

Dual termination facility for incoming side and can take wire upto 25sq. mm cross section. Wire may be of copper or aluminum.

Shock proof

Offer IP 20 degree of protection. All live parts are out of human reach ensuring safety to user.

Longer life

Reduced electro magnetic stresses resulting in increased contact life.

Flexibility

Can be mounted easily in any of the regular Distribution Boards.

Energy saving

IS / IEC : 60898-1 have recognized the growing importance of limiting power loss in Switchgear devices and stipulated max. permissible power loss values per pole of MCB. MCB having power loss figures of 50% lower watts than IS requirement. Thus, 50% energy & cost saving by application.

Page 8: DP.pdf

8

TIME CURRENT CHARACTERISTIC CURVES

Based on the Tripping Characteristics, Standard MCBs are available in ‘B’, ‘C’ and ‘D’ curve to suit different types of applications.

‘B’ Curve: for protection of electrical circuits with equipment that does not cause surge current (lighting and distribution circuits).

Short circuit release is set to (3 - 5) In

‘C’ Curve: for protection of electrical circuits with equipment that causes surge current (inductive loads and motor circuits).

Short circuit release is set to (5 - 10) In

‘D’ Curve: for protection of electrical circuits which causes high inrush current, typically 12-15 times the thermal rated current (transformers, X-ray machines etc.)

Short circuit release is set to (10 - 20) In

CURRENT LIMITING DESIGN

In a current limiting breaker, the tripping & arc control mechanism is so designed that under short circuit conditions, the contacts are physically separated and the electrodynamic forces set up by fault current assist the extinction in less than half cycle.

The figure shows the current limiting effect of a circuit breakers. Fault Traces for Voltage & Current

0 = Point of fault initiation

tx = Contact opening time (i.e., creation of arc)

t1 = Current / Voltage peak (i.e., current limitation)

t2 = Time to total extinction of arc (i.e., complete shutdown of fault current)

CHARACTERISTIC CURVES

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

Tim

e (s

ec.)

2 3 5 10 20 30 100

1.13 1.45

1

Multiples of Rated Current (x In)

B C D

PROTECTION UNLIMITED

STANDARD MCBs protect against overload and short circuit.

Overload Protection It is achieved by thermal operation of the bimetal strip which deflects when heated by the over current going through it, thereby tripping the operating mechanism and causing the contact to open.

Thermostatic Bi-metal It is a composite material comprising of two metallic layers of different co-efficient of thermal expansion which are permanently bonded together by pressure welding.

Short Circuit Protection In short circuit, the high current in the range of kA energises the solenoid and a magnetic field is created. Due to this magnetic field the anchor is pulled down which pushes the plunger to strike the inner latch, causing instantaneous opening of the contacts.

Voltage across contactsduring opening of MCB

Time

MaximumProspective

FaultCurrent

Cut-offCurrent

A

B

0 tX t1 t2

Cur

rent

Volta

ge

0

As per

Thermal Tripping Magnetic Tripping

No tripping Tripping Time Hold Trip Time

IS / IEC 60898-1

Current Current Limits Current Current Limits

I1 I2 t I4 I5 t

B Curve1.13 x In >1h 3xIn >0.1s

1.45 x In <1h 5 x In <0.1s

C Curve1.13 x In >1h 5xIn >0.1s

1.45 x In <1h 10 x In <0.1s

D Curve1.13 x In >1h 10xIn >0.1s

1.45 x In <1h 20 x In <0.1s

l3 = 2.55 x lN1 s < t < 60s for ln < 32A

1 s < t < 120s for ln > 32A

Page 9: DP.pdf

9

MINIATURE CIRCUIT BREAKER

POWER LOSS DETAILS

60

44

45

70.5

8436

1 POLE 1 POL E + NEUTRAL& 2 P OLE

3 POLE 3 POLE + NEUTRAL& 4 POLE

17.7 35.4 53.1 70.8

DIMENSIONS (in mm)

S. No. MCB Rating (A)

STANDARD MCBs Power

Loss (W)

Max. Permissible Power Loss (W) As per

IS:8828/IEC:60898

1 6 0.9 3.0

2 8 1.1 3.0

3 10 1.6 3.0

4 16 2.5 3.5

5 20 2.8 4.5

6 25 3.2 4.5

7 32 3.4 6.0

8 40 4.9 7.5

9 63 7.3 13

TECHNICAL INFORMATION

*Current Ratings - 0.5A, 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A, 13A, 16A, 20A, 25A, 32A, 40A, 50A, 63A

*** D Type MCB are available on request

** SP Single Pole DP Double Pole TP Three Pole TP + N Three Pole Neutral FP Four Pole

MCB Isolator

Standard Conformity IS / IEC 60898-1 IS / IEC 60947 - 3

Type/Series B C D***

Rated Current (In) A 6 - 40* 0.5 - 63* 0.5 - 63* 40 - 125

Rated Voltage (ac) (Ue) V 240/415 240/415

Rated Frequency (f) Hz 50 50

Nos. of Poles (Execution) SP, SPN, DP, TP, TPN, FP ** SP, DP, TP,FP**

Rated Short Circuit kA 10 10 6 to 32 - 10KA

Breaking Capacity 40 to 63 - 4.5kA

Utilization Category Magnetic Release Setting

(3-5)In (5-10)In (10-20)InAC 22A in 40A & 63

AC 23A in 100A & 125A

Rated Insulation Voltage (Ui) V 690 690

Rated Impulse Voltage (Uimp) kV 4 4

Electrical / Mechanical Endurance Endurance (No. of operations)Less than 32AMore than 32A

20,00010,000 10000

Ambient Temperature (oC) -5 to +45

Terminal Capacity (Max) sq.mm 25 25

Vibration 3 5

Shock 40 mm free fail

Protection Class IP - 20

Installation Position Vertical / Horizontal

Mounting Clip on DIn Rail (35 mm x 7.5 mm)

Case & Cover Moulded, flame retardant thermoplastic material.

Page 10: DP.pdf

10

MINIATURE CIRCUIT BREAKERMINIATURE CIRCUIT BREAKER

Current Cat No. Rating (Amps.) B-Curve C-Curve

0.5 - DSMSCSPF0X5 1 - DSMSCSPF001 2 - DSMSCSPF002 2.5 - DSMSCSPF2X5 3 - DSMSCSPF003 5 - DSMSCSPF005 6 DSMSBSPF006 DSMSCSPF006 10 DSMSBSPF010 DSMSCSPF010 16 DSMSBSPF016 DSMSCSPF016 20 DSMSBSPF020 DSMSCSPF020 25 DSMSBSPF025 DSMSCSPF025 32 DSMSBSPF032 DSMSCSPF032 40 DSMSBSPF040 DSMSCSPF040 50 - DSMSCSPF050 63 - DSMSCSPF063

MCB Single Pole (SP)

MCB SINGLE POLE NEUTRAL (SPN)

MCB DOUBLE POLE (DP)

Current Cat No. Rating (Amps.) B-Curve C-Curve

0.5 - DSMSCSNF0X5 1 - DSMSCSNF001 2 - DSMSCSNF002 2.5 - DSMSCSNF2X5 3 - DSMSCSNF003 5 - DSMSCSNF005 6 - DSMSCSNF006 10 - DSMSCSNF010 16 - DSMSCSNF016 20 - DSMSCSNF020 25 - DSMSCSNF025 32 - DSMSCSNF032 40 - DSMSCSNF040 50 - DSMSCSNF050 63 - DSMSCSNF063

Current Cat No. Rating (Amps.) B-Curve C-Curve

0.5 - DSMSCDPF0X5 1 - DSMSCDPF001 2 - DSMSCDPF002 2.5 - DSMSCDPF2X5 3 - DSMSCDPF003 5 - DSMSCDPF005 6 - DSMSCDPF006 10 - DSMSCDPF010 16 - DSMSCDPF016 20 - DSMSCDPF020 25 - DSMSCDPF025 32 - DSMSCDPF032 40 - DSMSCDPF040 50 - DSMSCDPF050 63 - DSMSCDPF063

Page 11: DP.pdf

11

MCB TRIPLE POLE (TP)

MCB TRIPLE POLE NEUTRAL (TPN)

Current Cat No. Rating (Amps.) B-Curve C-Curve

0.5 - DSMSCTNF0X5 1 - DSMSCTNF001 2 - DSMSCTNF002 2.5 - DSMSCTNF2X5 3 - DSMSCTNF003 5 - DSMSCTNF005 6 - DSMSCTNF006 10 - DSMSCTNF010 16 - DSMSCTNF016 20 - DSMSCTNF020 25 - DSMSCTNF025 32 - DSMSCTNF032 40 - DSMSCTNF040 50 - DSMSCTNF050 63 - DSMSCTNF063

Current Cat N o. Rating (Amps.) B-Curve C-Curve

0.5 - DSMSCTPF0X5 1 - DSMSCTPF001 2 - DSMSCTPF002 2.5 - DSMSCTPF2X5 3 - DSMSCTPF003 5 - DSMSCTPF005 6 - DSMSCTPF006 10 - DSMSCTPF010 16 - DSMSCTPF016 20 - DSMSCTPF020 25 - DSMSCTPF025 32 - DSMSCTPF032 40 - DSMSCTPF040 50 - DSMSCTPF050 63 - DSMSCTPF063

MCB FOUR POLE (FP)

Current Cat No. Rating (Amps.) B-Curve C-Curve

0.5 - DSMSCFPF0X5 1 - DSMSCFPF001 2 - DSMSCFPF002 2.5 - DSMSCFPF2X5 3 - DSMSCFPF003 5 - DSMSCFPF005 6 - DSMSCFPF006 10 - DSMSCFPF010 16 - DSMSCFPF016 20 - DSMSCFPF020 25 - DSMSCFPF025 32 - DSMSCFPF032 40 - DSMSCFPF040 50 - DSMSCFPF050 63 - DSMSCFPF063

MINIATURE CIRCUIT BREAKERMINIATURE CIRCUIT BREAKER

Page 12: DP.pdf

12

ISOLATORISOLATOR

TECHNICAL SPECIFICATION-ISOLATOR

Range 40A, 63A, 100A and 125A

Execution SP, DP, TP, & FP

Specification IS / IEC: 60947-3

Rated Voltage 240V / 415V AC

Rated Frequency 50 Hz

Utilisation Category AC 22A in 40A and 63A AC 23A in 100A and 125A

Electrical Endurance 10000 operations

Mechanical Endurance 20000 operations

Terminal Capacity Flexible Solid 40A, 63A 16 sq.mm 25 sq.mm 100A, 125 A 35 sq.mm 50 sq.mm

ISOLATOR DOUBLE POLE (DP)

Rating(A) Cat No.

40 DSMISODPX040 63 DSMISODPX063 100 DSMIODPX100 125 DSMIODPX125

ISOLATOR SINGLE POLE (SP)

Rating(A) Cat No.

40 DSMISOSPX040 63 DSMISOSPX063 100 DSMIOSPX100 125 DSMIOSPX125

ISOLATOR

Page 13: DP.pdf

13

ISOLATOR TRIPLE POLE (TP)

Rating(A) Cat No.

40 DSMISOTPX040 63 DSMISOTPX063 100 DSMIOTPX100 125 DSMIOTPX125

ISOLATOR FOUR POLE (FP)

Rating(A) Cat No.

40 DSMISOFPX040 63 DSMISOFPX063 100 DSMIOFPX100 125 DSMIOFPX125

ISOLATORISOLATOR

Page 14: DP.pdf

14

SHUNT TRIP ATTACHMENT USED FOR REMOTE TRIPPING Standard ConformityIS / IEC : 60947-3

Coil Consumption6VA

Rated Voltage (ac) (Ue) (dc) (Ue)240V 48V, 24V, 12V

Frequency50Hz

Operating Voltage range70% - 110% of rated voltage

Electrical Endurance (nos. of ops)10000

Terminal Capacity (max)25mm2

Protection ClassIP - 20 as per IS-2147 & IEC-60529

MountingRight side of MCB (Factory assembled)

MINIATURE CIRCUIT BREAKERMINIATURE CIRCUIT BREAKER

AUXILLARY CONTACT Standard ConformityIS / IEC : 60947-1

Rated Current (In)6A

Rated Voltage (Ue)240 V ac

Contact Configuration1 NO + 1 NC2 NO + 2 NC

Utilization CategoryAC 11

Electrical Endurance (nos. of operations)10000

Terminal Capacity (max)4mm2

Protection ClassIP - 20 as per IS : 2147 & IEC : 60529

MountingLeft side of MCB (Factory assembled)

ACCESSORIES

Page 15: DP.pdf

15

• To trip the Circuit Breaker through Shunt Trip Coil, 70% to 110% of the rated voltage is to be applied across D1 & D2

• The Shunt Trip coil is short time rated and it trip the breaker instantaneously. (i.e., continuous duty not required)

MCB SELECTION CHART

SHUNT TRIP COIL

Appliance Capacity / wattage MCB MCB (1φ, 240V~) Current Rating Type Air Conditioner 1.0 tonnes 10A “C” series 1.5 tonnes 16A “C” series 2.0 tonnes 20A “C” seriesRefrigerator 165 litres 3A “C” series 350 litres 4A “C” seriesOven cum Griller 4500W 32A “B” series 1750W 10A “B” seriesOven 750W 6A “B” series Hot plate 2000W 10A “B” series Room Heater 1000W 6A “B” series 2000W 10A “B” seriesWashing Machine 300W 2A “C” series Washing Machine (with heater) 1300W 8A “C” seriesWater Heater(storage/instant) 1000W 6A “B” series 2000W 10A “B” series 3000W 16A “B” series 6000W 32A “B” seriesElectric iron 750W 6A “B” series 1250W 8A “B” seriesToaster (2 slices) 1200W 8A “B” series Electric Kettle 1500W 10A “B” series

MINIATURE CIRCUIT BREAKERMINIATURE CIRCUIT BREAKER

Outgoing D1 CoilTerminal

D2 CoilTerminalIncoming

1 3

2 4

Shunt trip Connection Digram

Incoming Connection

Page 16: DP.pdf

16

MCB C

HAN

GEO

VER S

WIT

CH

Range

25A, 40A

Execution

Double Pole,

Four Pole

Specification

IS / IEC : 60947-3

Page 17: DP.pdf

17

MCB Changeover switch finds wide & varied applications in in-dustries as well as in domestic sphere for use in low voltage distribution circuits, wherever continuity of supply is necessary, for switching to an alternate source of supply from main supply and vice - versa.

They are switch disconnectors with independent manual opera-tion, capable of making, carrying and breaking currents under normal circuit conditions, which may include operating overload condition and also carry currents under specified abnormal circuit conditions such as those of short circuit for a specified time.

Features

• Compact construction

• Double break contacts

• Silver Cadmium Oxide contact tips

• Shrouded terminals

• Front operation with three stable positions I-O-II

• Centre position OFF

• Easy snap on DIN Rail mounting

• Can be mounted with other products viz. MCB, RCCB, Isolator in Distribution Board

CONSTRUCTION

The entire switching mechanism along with the fixed and moving contact assembly are housed in FR thermo plastic moulded case / cover, having high dielectric strength, excellent mechanical & thermal properties.

The switching mechanism is double break type. The contact tips are made of Silver Cadmium oxide for long electrical life, sustained current carrying capacity and they ensure temperature rise is within specified limits.

TECHNICAL INFORMATION

Standard Confirmity IS/IEC-60947-3

No. of Poles (Execution) : DP, FP

Rated Current (In) A : 25, 40

Rated Voltage (Ue) V : 240 AC / 415 AC

Rated Frequency Hz : 50

Rated insulation voltage V : 660

Dielectric Strength kV : 2.5

Rated impulse voltage kV : 4

Utilization Category : AC 21A

Ambient Temp. °C : -5 to +55

Mechanical life Nos. ops. : 10000

Electrical life Nos. ops. : 10000

Mounting : Standard DIN rail

Mounting Position : Vertical / Horizontal

Terminal Capacity sq. mm : 10

Page 18: DP.pdf

18

CONNECTION DIAGRAMS / TERMINAL MARKING

Double Pole

MCB CHANGEOVER SWITCHMCB CHANGEOVER SWITCH

Current Rating (Amps.) Cat. No.

25 DSMCODPX025 40 DSMCODPX040

“I” - Incoming terminals (main supply) - 2 & 6

“II” - Incoming terminals (standby supply) - 4 & 8

Outgoing terminals (to load) - 1 & 5

* Mid position of knob is ‘OFF’ position

1 3

2 4 6 8

5 7

DIMENSIONS (in mm)

Page 19: DP.pdf

19

Four Pole

MCB CHANGEOVER SWITCHMCB CHANGEOVER SWITCH

Current Rating (Amps.) Cat. No.

25 DSMCOFPX025 40 DSMCOFPX040

“I” - Incoming terminals (main supply) - 2, 6, 10 & 14

“II” - Incoming terminals (standby supply) - 4, 8, 12 & 16

Outgoing terminals (to load) - 1, 5, 9 & 13

* Mid position of knob is ‘OFF’ position

1 5

161412

9 13

108642

DIMENSIONS (in mm)

Page 20: DP.pdf

20

RCCB /

ELC

BRange

16A - 63A

Execution

2 Pole, 4 Pole

Specification

IS 12640 - 1: 2008

IEC 61008 - 1

Page 21: DP.pdf

21

The flow of current through electrical facilities always involves risks. Poorly insulated equipment, faulty wires and incorrect use of an electrical device cause currents to flow through the wrong path (i.e. through the insulation) to the earth. This current is called ‘Leakage Current’.

Earth leakage is an electrical hazard and is responsible for electrical shocks and fire risk. Earth leakage and its associated hazard can be prevented by Residual Current Circuit Breaker (RCCB), also popularly known as Earth Leakage Circuit Breaker (ELCB).

Features • Simple and Robust operating mechanism.

• Rotary handle with ON/OFF indication

• Dual termination for Bus Bar as well as cable connection

• Advance neutral

• Test button for regular inspection

• Positive contact indication

Range

16A - 63A

Sensitivity

30mA, 100mA, 300mA

Execution

Double Pole (DP)

Four Pole (FP)

Specification

IEC 61008-1/IS 12640 - 1:2000

Against Electrocution

The use of exposed, substandard, badly wired, wrongly connected or damaged equipment as well as frayed or badly repaired cables reduces the safety of an installation and increases the risk of person receiving an electric shock.

Electrocution is a passage of current through human body, which is dangerous. The flow of current through human body effects vital functions.

1. Breathing

2. Heartbeat

A correctly chosen RCCB can detect small currents flowing to earth and reduces the risk of electrocution. Effect of electric current through human body has been well researched and following chart summarizes the results:

Effect of electric current through human body has been well researched and following chart summarizes the results

Features & Benefits

Page 22: DP.pdf

22

RCCB/ELCBRCCB/ELCB

PROTECTION

Against Electrocution

The use of exposed, substandard, badly wired, wrongly connected or damaged equipment as well as frayed or badly repaired cables reduces the safety of an installation and increases the risk of person receiving an electric shock.

Electrocution is a passage of current through human body, which is dangerous. The flow of current through human body effects vital functions.

1. Breathing

2. Heartbeat

A correctly chosen RCCB can detect small currents flowing to earth and reduces the risk of electrocution. Effect of electric current through human body has been well researched and following chart summarizes the results.

Effect of electric current through human body has been well researched and following chart summarizes the results.

However, electrocution should not be viewed in terms of “current” alone, but in terms of “contact voltage”. A person gets electrocuted by coming in contact with an object that has a different potential from his/her own. The difference in potential causes the current to flow through the body.

The human body has known limits:• Under normal dry conditions, voltage limit = 50V• In damp surroundings, voltage limit = 25V

Rated Tripping Current Maximum permissible of the RCD earth fault loop impedance in

10 mA 5,000 30 mA 1,666 100 mA 500 300 mA 166

EFFECT OF ELECTRIC CURRENT THROUGH HUMAN BODY

500 mA Immediate cardiac arrest resulting in death

70-100 mA Cardiac fibrillation; the heart begins to vibrate and no

20-30 mA Muscle contraction can cause respiratory paralysis

10 mA Muscle contraction : the person remains “stuck” to the conductor

1-10 mA Prickling sensations

AGAINST INDIRECT CONTACT

Over current protection devices like MCB are unable to act promptly on small earth leakage currents. To comply with wiring regula-tions, the earth fault loop impedance in Ohms, multiplied by the rated tripping current of the RCD in amperes must not exceed 50.

Example

For an RCD with a rated tripping current of 30mA, the maximum permissible earth fault loop impedance is calculated as follows: Zs (max) = 50 / In = 50/0.03 = 1,666

AGAINST FIRE

The majority of fires which occur as a result of faulty wiring are started by current flowing to earth. Fire can be started by fault current of less than 1 amp.The normal domestic overload protective device such as a fuse or MCB will not detect such a small current. A correctly chosen RCD will detect this fault current and interrupt the supply, hence, reducing the risk of a fire starting.

Page 23: DP.pdf

23

RCCB/ELCBRCCB/ELCB

Technical Information TWO POLE FOUR POLE

Standard Conformity IS 12640-1: IEC 61008-1 IS 12640-1: IEC 61008-1Rated Current (In) A 16, 25, 32, 40, 63 25, 40, 63Sensitivity * (In) mA 30, 100, 300 30, 100, 300Rated Voltage (Un) Vac 240 415 Rated Insulation Voltage (Ui) V 690 690Rated Frequency Hz 50 50Short circuit Withstand Capacity kA 6 6Residual Making Breaking Capacity A 500 A or 10 In wherever is greater 500 A or 10 In wherever is greaterAmbient Temperature °C -25°C to + 55°C -25°C to + 55°CShock Resistance 40 mm free fall 40 mm free fallVibration Resistance g 3 3Electrical /Mechanical operations 10000 10000Mounting Din Rail (35 x 7.5) mm Din Rail (35 x 7.5) mmDegree of Protection IP 20 IP 20Terminal Capacity (max) mm2 25 25

WORKING PRINCIPLE

The RCCB works on the current balance principle. The supply conductors, i.e. the phases and the neutral, are passed through a torroid and form the primary windings of a current transformer. Its secondary winding is connected to a highly sensitive electromagnetic trip relay, which operates the trip mechanism.

In a healthy circuit, sum of the currents in phases, is equal to the current in the neutral and the vector sum of all currents is equal to zero. If there is any insulation fault in the current and leakage current flows to earth, the currents do not balance and their vector sum is not equal to zero. This imbalance is detected by the core balanced current transformer, the RCCB is tripped and supply to load is interrupted. The trip mechanism is operated at a residual current between 50-100% of its rated tripping current.

Earth

R

Y

B

N

T

*500 mA is available on request

Page 24: DP.pdf

24

WIRING DIAGRAM

The Standard range of four pole RCCBs can be used to provide residual current protection in 3 phase, 3 wire circuits (no neutral), however a link from the neutral to an incoming should be made on the supply side of the RCCB, to enable the operation of the RCCB.

Actuation Time Characteristics

RCCB/ELCBRCCB/ELCB

a

Current in milliamperes

b c1c2c310000

5000

2000

1000

500

200

100

50

20

100.1 0.3 1 3 10 30 100 300 1000 3000 10000

0.2 0.5 2 5 20 50 200 500 2000 5000

30 mA

100 mA

Tim

ein

milli

seco

nds

Typical currentlimits due to body resistanceat 240 V

ms

350

300

350

200

150

100

50

1 2 3 4 5 6

Residual Current multiple of IΔn (mA)

Tim

e (in

ms)

For Three Phase 3 Wire connections

For Single Phase 2 Wire connections

For Three Phase 4 Wire connections

Load

1 N

Load

2 4 6 N

Load

2 4 6 N

2 N 2 4 6 N

1N

T

R

1 3

R

T

5 N 1 3 5 N

2 4 6 N

R

T

SELECTION

30 mA : A 30 mA ELCB will provide a high degree of protection against electrocution in an accidental shock hazard situation. The current flowing through human body could be between 80mA and 240mA depending on the resistance of the human body and the voltage across it.

Zone : Physiological Effects

Zone 1 : Usually no reactions

Zone 2 : Usually no harmful physiological effects

Zone 3 : Usually no organic damage to be expected. Likelihood of muscular contraction and difficulty in breathing, reversible disturbances of formation and conduction of impulse in the heart and transient cardiac arrest without ventricular fibrillation increases with current magnitude and time.

Zone 4 : In addition to the effects of Zone 3, probability if ventricular fabriliation increased upto 5% (curve C2) upto 50% (curve C3) and above 50% beyond curve C3. It increases with magnitude and time, and pathophysiological effects such as cardiac arrest, breathing arrest and heavy burns may occur.

To be within zone of the IEC curve as shown above. It is necessary for the ELCB to operate within 50ms at 240 mA and 150ms at 80mA. Both these conditions are satisfied by 30mA ELCB.

For households, individual outlets, wet areas and temporary installations, ELCB with sensitivity not exceeding 30mA is advisable.

100 mA : A 100mA ELCB will normally give high degree of protection against electrocution but there is a possibility that the shock current could fall below the tripping level of ELCB. This could occur if additional resistances to that of human body are included in the earth path.

The 100mA RCCB protects against leakage currents and indirect contact with earth loop impedance upto 500 Ohms.

300 / 500mA : A 300/500 mA ELCB may be used where only fire protection is required. eg., on lighting circuits, where the risk of electric shock is small. 300/500mA ELCB will not give any protection against electrocution.

Page 25: DP.pdf

25

Dimensions (in mm)

RCCB/ELCBRCCB/ELCB

DOUBLE POLE ‘AC’ TYPE

FOUR POLE ‘AC’ TYPE

Current Sensitivity Cat No. Rating (Amps.) mA

16 30 DSRMCTDF030016 16 100 DSRMCTDF100016 16 300 DSRMCTDF300016 25 30 DSRMCTDF030025 25 100 DSRMCTDF100025 25 300 DSRMCTDF300025 32 30 DSRMCTDF030032 32 100 DSRMCTDF100032 32 300 DSRMCTDF300032 40 30 DSRMCTDF030040 40 100 DSRMCTDF100040 40 300 DSRMCTDF300040 63 30 DSRMCTDF030063 63 100 DSRMCTDF100063 63 300 DSRMCTDF300063

Current Sensitivity Cat No. Rating (Amps.) mA

16 30 DSRMCRFF030016 16 100 DSRMCRFF100016 16 300 DSRMCRFF300016 25 30 DSRMCRFF030025 25 100 DSRMCRFF100025 25 300 DSRMCRFF300025 32 30 DSRMCRFF030032 32 100 DSRMCRFF100032 32 300 DSRMCRFF300032 40 30 DSRMCRFF030040 40 100 DSRMCRFF100040 40 300 DSRMCRFF300040 63 30 DSRMCRFF030063 63 100 DSRMCRFF100063 63 300 DSRMCRFF300063

36.0

36.0

45.0

67.8

60.0

71.0

68.0

60.0

43.5

84.5

36.0

45.0

AC TYPE - STANDARD APPLICATIONS

AC type RCDs detect AC residual currents. In the majority of cses (standard applications), they are used for AC current detection at 50 / 60 Hz

Page 26: DP.pdf

26

Range

IS : 12640-1:2008

IEC : 61008-1:1996

Sensitivity

30, 100 & 300 mA

Execution

2P, 4P

Specification

50Hz

Features

• Short circuit breaking with stand capacity 10kA• Different knob position to indicate whether it is switched by a fault or manually switched OFF (mid trip)• Test button for regular inspection• Contact position indication

Technical Information TWO POLE FOUR POLE

Specification Reference IEC 61008-1 & IS 12640-1: 2008 IEC 61008-1 & IS 12640-1: 2008Rated current (In) A 80, 100 80, 100Sensitivity (IDn) mA 30, 100, 300 30, 100 ,300, 500*Rated Voltage (Ue) V 240 V~ 415V~Rated Insulation voltage (Ui) V 660 660Rated Frequency Hz 50 50Trip Time 1xIDn<300ms 1xIDn<300ms 5IDn<40ms 5IDn<40msShort circuit withstand Capacity kA 10 10Residual Making Breaking capacity A 10 In 10 InAmbient Working Temperature °C -25°C to + 55°C -25°C to + 55°CShock Resistance 40mm free fall 40mm free fall Vibration Resistance g 5 5Electrical Endurance operations >2000 >2000Mechanical Endurance operations >3000 >3000 Mounting Din Rail (35 x7.5 mm) Din Rail (35 x7.5 mm)Degree of protection IP 20 IP 20Terminals Capacity (Max) mm2 50 50

RCCB/ELCBRCCB/ELCB

*500 mA is available on request

HIGHER RATING (80A-100A)

Page 27: DP.pdf

27

DOUBLE POLE ‘AC’ TYPE

FOUR POLE ‘AC’ TYPE

Current Sensitivity Cat No. Rating (Amps.) mA

80 30 DSRMCMDF030080 80 100 DSRMCMDF100080 80 300 DSRMCMDF300080 100 30 DSRMCMDF030100 100 100 DSRMCMDF100100 100 300 DSRMCMDF300100

Current Sensitivity Cat No. Rating (Amps.) mA

80 30 DSRMCMFF030080 80 100 DSRMCMFF100080 80 300 DSRMCMFF300080 100 30 DSRMCMFF030100 100 100 DSRMCMFF100100 100 300 DSRMCMFF300100

Dimensions (in mm)

RCCB/ELCBRCCB/ELCB

36.0

30.5

44.0

60.0

69.5

45.0

36.0

87.5 87.5

72.0

2 Pole 4 Pole

Page 28: DP.pdf

28

Range

6A, 10A, 16A, 20A, 25A, 32A & 40A

Sensitivity

30mA, 100mA, 300mA

Execution

Single Pole with neutral (SPN)

Triple Pole with neutral (TPN)

Specification

IS:12640 Part2: 2008, IEC 61009-1, BSEN:61009-1

RCBO

Page 29: DP.pdf

29

Standard New RCBO is a single composite device which provides protection against over currents and earth leakage faults in the same width and profile as that of a standard MCB. It is designed for use in domestic, commercial and industrial distribution sys-tems at the most downstream circuit for ensuring high degree of protection to the user for a particular circuit. In normal use, it is safe to use and free of to user as well as to environment.

Features

• Pulsating dc protection - Type A• Discrimination using time delay - Type S RCBO• Controlled response VD RCBO (Electronic)• Protection in case of loss of supply neutral in SPN RCBO only• Enhanced immunity to nuisance tripping• Positive contact indication: Red for ON , Green for OFF• Short circuit breaking capacity 10 kA.• Large terminal capacity: RCBOs have 35 mm2 for cool running

while in operation.• Protection in case of loss of supply neutral: Even in event of

loss of supply neutral, Standard RCBO provides protection against earth faults . The Functional Earth (FE) white color wire connected to earth provides this protection.

• Controlled response & immunity to nuisance tripping: The trip level and the response time of the Standard VD (Voltage Dependent) RCBO using electronic circuit is set to very precise values and thereby provide greater immunity to nuisance tripping that can be caused by mains borne noise, surge voltages, lighting surges, reactive loads, mains filters, etc.

• Neutral to earth faults: A connection that occurs between N and E on the load side of any RCBO will impact on its performance and cause the trip level to increase. In the case of a N - E fault, the user may have no way of knowing that this fault exists and that the RCBO has been desensitised. Under this condition, the Standard VD RCBO provides a far greater level of protection than a normal VI (Voltage Independent) RCBO.

Aesthetics & Convenience

• The new module’s unique compact construction enables far more devices to be fitted into a distribution board than previously possible, and 2 Module RCBO can simply replace existing MCB 2 pole when upgrading a board.

• High stacking density = smaller chasis & distribution boards.

Reliability & continuity of service

• Enhanced discrimination with Standard MCBs• Back up to 10 kA with BS & DIN fuses• Retrofits Standard MCBs in distribution boards with no

modifications in general• Robust construction.

Energy limiting

Standard RCBO meets the requirements for energy let through by IEC & British Standard for energy limiting class 3.

Features & Benefits

Page 30: DP.pdf

30

ADDITIONAL RANGE - TYPE A & S

Type A - Pulsating DC Protection: Any electrical appliance with power control has the ability to produce earth fault currents with pulsating DC (rectified AC) components. RCBOs that provide this type of protection are referred to as Type A RCBOs.

VI RCBOs do not provide this protection, and are referred to as Type AC RCBOs. Standard VD RCBOs have been specifically designed to provide protection against pulsating DC fault currents.

• Type S- Selective or Time Delay: RCBOs are also divided into two categories determined by their response time to an earth fault current, as follows

• General Type - having a trip time<300mS for fault currents of IDN and < 40ms for fault currents > 5 IDN.

• S Type- having a trip time of 150 - 500mS for IDN, and 40 - 130mS for >5 IDN.

(IDn is the rated residual operating current of the RCBO)

As the name implies, general types are intended for general purpose use. However, S (selective) types are normally used in conjunction with downstream general type RCBOs.

The S type effectively provides discrimination in terms of the response time to earth fault currents for upstream and downstream RCBOs. For example, when two RCBOs are connected in series the first RCBO will often be an S type.

Technical Information SPN (2M) TPN (4M)

Specification SPN (2M) TPN (4M)Specification Reference IS 12640 (Part 2) & IEC 61009 IS 12640 (Part 2) & IEC 61009Rated Current In 6A, 10A, 16A, 20A,25A, 32A, 40A 6A, 10A, 16A, 20A,25A, 32A, 40ARated Residual Operating Current IDN 30, 100, 300mA. 30, 100, 300mA.Instantaneous Tripping Current ‘C ’curve ‘C ’curveRated Voltage Un (Vac) 240V~ 415V~Rated Insulation Voltage Un (Vac) 660V 660VRated Frequency 50Hz 50HzNo. of Pole 1P+N 3P+NRated Short Circuit Capacity Icn 10kA 10kARated Residual Making Breaking Capacity IDm 500A 500A Operating Characteristics in case of Residual Currents ‘A’ type ‘A’ typeMethod of Mounting Panel Board Type (DIN Rail) Panel Board Type (DIN Rail)Degree of Protection IP 20 IP 20Terminals for External Conductors (mm2) 35 Net Weight (in Kg) 0.420 0.84Ambient Working Temperature -5°C to + 55°C -5°C to + 55°CMechanical Endurance (No. of Operations) 4000 4000Electrical Endurance (No. of Operations) 4000 4000Trip Time (milli Second) <40 <40Shock Resistance 40mm free fall 40mm free fallVibration Resistance 3g 3g

RCBORCBO

Page 31: DP.pdf

31

Current Sensitivity Cat No. Cat No. Rating (Amps.) mA SP&N TP&N

6 30 DSCEACSN2030006 DSCEACTN4030006 6 100 DSCEACSN2100006 DSCEACTN4100006 6 300 DSCEACSN2300006 DSCEACTN4300006 10 30 DSCEACSN2030010 DSCEACTN4030010 10 100 DSCEACSN2100010 DSCEACTN4100010 10 300 DSCEACSN2300010 DSCEACTN4300010 16 30 DSCEACSN2030016 DSCEACTN4030016 16 100 DSCEACSN2100016 DSCEACTN4100016 16 300 DSCEACSN2300016 DSCEACTN4300016 20 30 DSCEACSN2030020 DSCEACTN4030020 20 100 DSCEACSN2100020 DSCEACTN4100020 20 300 DSCEACSN2300020 DSCEACTN4300020 25 30 DSCEACSN2030025 DSCEACTN4030025 25 100 DSCEACSN2100025 DSCEACTN4100025 25 300 DSCEACSN2300025 DSCEACTN4300025 32 30 DSCEACSN2030032 DSCEACTN4030032 32 100 DSCEACSN2100032 DSCEACTN4100032 32 300 DSCEACSN2300032 DSCEACTN4300032 40 30 DSCEACSN2030040 DSCEACTN4030040 40 100 DSCEACSN2100040 DSCEACTN4100040 40 300 DSCEACSN2300040 DSCEACTN4300040

RCBORCBO

Dimensions (in mm)

10000.00

1000.00

100.00

Tim

e(se

c)

10.00

1.00

0.10

0.011 10

Multiples of Reted Current

100

1000.00

100.00

Tim

e (s

ec)

10.00

1.00

0.10

0.010.01 1 10 100 1000 10000

Multiples of Reted Residual Current in I∆n mA

Time Current Characteristics C Curve Residual Current Tripping Characteristics (General Type)

35.4

87.5

36

43.5

68.4

45

70.6

6.8

44

70.8 50.4

4536

6.8

43.568.474.5

125

Page 32: DP.pdf

32

Range

Single Phase & Three Phase

Execution

Horizontal & Vertical

Specification

IS : 13032 / IS : 8623

DIS

TRIB

UTIO

N B

OARD

S

Page 33: DP.pdf

33

• Superior aesthetics that blend well with the decor.

• Made of special grade CRCA sheet steel to provide strength and longer life to enclosures.

• Manufactured with latest technology CNC Punch and Brake presses to attain highest degree of perfection.

• Painted with epoxy polyster and polyster resin based pow-der paints with latest techniques in powder coating ensures strong, scratch resistant coatings.

• Current carrying parts are made of electrolytic grade of cop-per having high conductivity and low resistivity thereby keep-ing temperature rise and distribution losses very low.

• Appropriate sizes of DIN rails to facilitate easy and fast mounting of MCBs, RCCBs, Isolators etc.

• Brass neutral and earth bars of suitable cross-sectional areas are provided to facilitate connections for each outgoing ter-minals.

• Adequate number of knockout holes of various sizes are pro-vided both at the top and the bottom. This facilitate easy installation and connection of conduits of all sizes, both for top and bottom.

• Detachable upper and lower end plates provided for easy and flexibility of cabling.

• Superior single phase bus bars provided which are com-pletely insulated and fitted in PVC channel to avoid accidental touch.

• Suitable for both flush and surface mounting.

• Conforms to IS 13032 & IEC : 439 & 529

Standard make Smart Distribution Boards provides flexibility

and a systematic approach to ever increasing need for effective

methods of the electrical distributions in domestic, commercial

and industrial application. Standard Smart distribution boards

have been specially designed to meet all the technical require-

ments and ensure the distribution boxes blend with the decor of

the place of the installation.

The Smart distribution boards with their features and their range

offer a compact, practical and economic solution to any electri-

cal network in residential / commercial complexes, industries

etc. having single phase or three phase connections. The Smart

distribution board is not merely an enclosure but a complete

system in itself comprising of ETP Copper bus bar, brass neutral

link, earth link, earthing studs, and interconnection wires for ef-

fective distribution of current.

Features & Benefits

Page 34: DP.pdf

34

DISTRIBUTION BOARDS

S.No. Type Configuration Application

(a) SPN SPN Simple, Economical & Safe distribution Consumer Simple, Economical & Safe distribution

(b) TPN TPN (Horizontal) Three phase & Neutral incoming and outgoing can be only single phase Vertical Three phase and neutral incoming, outgoing can be single phase as well as multi phase Per Phase Isolation (PPI) DP RCCB in each phase is provided to avoid the total outage as only the phase where earth leakage fault exist, get isolated. (c) Special Extended loose Wire Most flexible design Three Tier Most flexible design Power Line For fault level higher then 10kA with a provision for MCCB incomer 7 Segment DB Single point distribution where per phase Isolation facility is required Phase Selector(40&63A) Used for selection of a phase in case other phase fails Plug & Socket Used for Air conditioner and motor protection MCB Enclosures To isolate / connect electrical appliances independently

RANGE

SMART DISTRIBUTION BOARDS

Smart board SPN/TPN DBs Single Door

Smart trek SPN/TPN DBs Double Door

Smart line TPN DBs Single Door

NEW ADDITIONAL FEATURES

Masking - (Cement & Water guard)

During the construction stage the DBs can get ingressed with water & cement dust. This can spoil the decor and more importantly alter the performance parameters. Standard Smart Trek DBs come with a masking arrangement that keeps water and cement dust away.

Flexibility during installation

Standard DBs are provided with an intermediate detachable door/plate fixed on the inner door to give flexibility of installa-tion i.e. during installation or maintenance the entire door need not be dismantled thus saving valuable installation time. Ad-ditionally this also ensures that electrically live parts do not get exposed.

Reversible Doors

The outer DB doors are reversible. While the doors come fitted on the left side these can be reversed and fitted on to the right side by the user.

Weather proof design

All DBs are provided with perfect fitted gaskets which ensures ingress protection as per IP-42 category.

Reversible door

Intermediate detachable door

Masking (Cement & waterguard)

Page 35: DP.pdf

35

Ways Dimensions Knock Out Dia

DISTRIBUTION BOARDS

SMART BOARD - SINGLE PHASE SINGLE DOOR DBs IP 40 PROTECTION

A B C D Incoming Outgoing 4 145 135 75 225 2 No. Ø26 2 No. Ø26 6 182 172 111 225 3 No. Ø26 3 No. Ø26 8 217 207 147 225 4 No. Ø26 4 No. Ø26 12 289 279 217 225 6 No. Ø26 6 No. Ø26 16 361 351 291 225 8 No. Ø26 8 No. Ø26

Dimensions (in mm)

Ways Cat No. 4 DSDMSNHOSI04 6 DSDMSNHOSI06 8 DSDMSNHOSI08 12 DSDMSNHOSI12 16 DSDMSNHOSI16

65

D 215

165

C

B

10

A

(fixi

ng c

ente

r)

(fixing center)

Page 36: DP.pdf

36

DISTRIBUTION BOARDS DISTRIBUTION BOARDS

A B C Ø31 4 266 256 175 4 Nos. 6 336 326 245 6 Nos. 8 406 396 315 8 Nos. 12 546 536 455 12 Nos.

Ways Dimensions Knock Out Dia

SMART LINE - THREE PHASE SINGLE DOOR DBs IP 40 PROTECTION

Dimensions (in mm)

Ways Cat No. 4 DSDMTNHCSI04 6 DSDMTNHCSI06 8 DSDMTNHCSI08 12 DSDMTNHCSI12

(fixing center)

(fixi

ng c

ente

r)

B

C

390

305

A

65

Page 37: DP.pdf

37

DISTRIBUTION BOARDS DISTRIBUTION BOARDS

A B C Incoming Outgoing 2+4 217 207 157 4 No. Ø26 4 Nos. Ø26 2+8 289 279 229 1 No. Ø38 1 No. Ø38 4 Nos. Ø26 4 Nos. Ø26 2+12 361 351 301 1 No. Ø38 1 No. Ø38 6 Nos. Ø26 6 Nos. Ø26

Ways Dimensions Knock Out Dia

CONSUMER UNIT - IP 40 PROTECTION

Dimensions (in mm)

Ways Cat No. 2+4 DSDCSNHOSI04 2+8 DSDCSNHOSI08 2+12 DSDCSNHOSI12

171.

521

5.0

225.

0

(fixi

ng c

ente

r)

(fixing center) 22.065.0C

B

A

A B C Ø26 Ø38 4 578 560 484 6 No. 1 Nos. 6 632.5 614.5 538.5 6 No. 1 Nos. 8 687 669 593 6 No. 1 Nos. 12 796 778 702 6 No. 1 Nos.

Ways Dimensions Knock Out Dia

Dimensions (in mm)

Ways Cat No. Single Door Double Door 4 DSDMTNVOSI04 DSDMTNVODI04 8 DSDMTNVOSI08 DSDMTNVODI08 12 DSDMTNVOSI12 DSDMTNVODI12

3.5

A C

270.0 113.0

350.0367.0

B

(fixi

ng c

ente

r)

(fixing center)

ØM

ount

ing

hole

7

.0

VERTICAL TYPE DBs - IP 42 PROTECTION

Page 38: DP.pdf

38

SQVE SERIES - SPN DOUBLE DOOR DISTRIBUTION BOARD

Ways Cat No. 4 DSDESHODRW04 6 DSDESHODRW06 8 DSDESHODRW08 12 DSDESHODRW12 16 DSDESHODRW16

A

B3

8

84.5

C

244

222

D

Knockout holes O/G

(Ø 25) knockout holeson each side

Knockout holes I/C

Dimensions (in mm)

WaysDimensions Knockout holes

A B C DTop Bottom Side (Each

Side)(Ø25) (Ø31) (Ø25) (Ø31)4 125 175 197 172 3 - 3 - 16 151 211 232 166 2 1 2 1 18 187 247 268 166 2 2 2 2 112 269 319 340 176 4 2 4 2 116 341 391 412 172 4 2 4 2 1

Page 39: DP.pdf

39

SQVE SERIES - TPN DOUBLE DOOR DISTRIBUTION BOARD

Ways Cat No. 4 DSDETHODRW04 6 DSDETHODRW06 8 DSDETHODRW08 12 DSDETHODRW12

Knockout holes O/G

Knockout holes I/C

A

B

Knockout holeseach side C

38

97.5

Dimensions (in mm)

WaysDimensions Knockout holes (Ø31)

A B C Top Bottom Side (Each Side)4 196 251 272 3 3 16 268 323 344 2 2 18 340 395 416 2 2 112 479 534 555 4 4 1

Page 40: DP.pdf

40

PREWIRED DISTRIBUTION BOARD - SPN SINGLE DOOR

Dimensions (in mm)

Ways Cat No. 4 DSDMSHMSIW04000 6 DSDMSHMSIW06000 8 DSDMSHMSIW08000 12 DSDMSHMSIW12000

Ways Sheet Thickness

Dimensions Knock out holes

A B C Top Bottom Side (Each Side)

4 1.2 206 129 218 4 4 16 1.2 278 192 290 5 5 18 1.2 278 192 290 5 5 112 1.2 345 274 360 6 6 1

B (fixing center) 65

371

295

(fixi

ng c

ente

r)

372

C

A

Page 41: DP.pdf

41

PREWIRED DISTRIBUTION BOARD - SPN DOUBLE DOOR

Ways Cat No. 4 DSDMSHMDIW04000 6 DSDMSHMDIW06000 8 DSDMSHMDIW08000 12 DSDMSHMDIW12000

Dimensions (in mm)

Ways Sheet Thickness

Dimensions Knock out holes

A B C Top Bottom Side (Each Side)

4 1.2 206 129 223 3 3 16 1.2 278 201 296 5 5 18 1.2 278 201 296 7 7 112 1.2 350 274 366 9 9 1

B (fixing center) 100

394

295

(Fix

ing

cent

er)

372

C

A

Page 42: DP.pdf

42

PREWIRED DISTRIBUTION BOARD - TPN SINGLE DOOR

Ways Cat No. 4 DSDMTHMSIW04000 6 DSDMTHMSIW06000 8 DSDMTHMSIW08000 12 DSDMTHMSIW12000

Dimensions (in mm)

Ways Sheet Thickness

Dimensions Knock out holes

A B C Top Bottom Side (Each Side)

4 1.2 385 318 400 5 5 06 1.2 423 353 437 7 7 08 1.2 460 389 472 9 9 012 1.2 605 534 618 13 13 0

B (fixing center) 65

687

605

(Fix

ing

cent

er)

672

C

A

Page 43: DP.pdf

43

PREWIRED DISTRIBUTION BOARD - TPN DOUBLE DOOR

Ways Cat No. 4 DSDMTHMDIW04000 6 DSDMTHMDIW06000 8 DSDMTHMDIW08000 12 DSDMTHMDIW12000

Dimensions (in mm)

Ways Sheet Thickness

Dimensions Knock out holes

A B C Top Bottom Side (Each Side)

4 1.2 389 315 410 5 5 06 1.2 442 349 445 7 7 08 1.2 460 387 482 9 9 012 1.2 605 534 624 13 13 0

B (fixing center) 81.0

702

605

(Fix

ing

cent

er)

675

C

A

96

Page 44: DP.pdf

44

Ways Capacity of Cat No. 17.8 mm module Incomer + Outgoing 04 4 + (6+12) DSDPTHPDRW04 06 8 + (6+18) DSDPTHPDRW06 08 8 + (6+24) DSDPTHPDRW08

No. of Dimensions Knockout Holes (Ø31) Ways A B C Top Bottom Side(Each Side)

04 323 268 333 6 6 2

06 395 340 405 8 8 2

No. of Dimensions Knockout Holes (Ø31) Ways A B C Top Bottom Side(Each Side)

08 557 482 587 11 11 2

Ways Dimensions Knock Out Dia

A B C Ø26 Ø38 4 578 560 484 6 Nos. 6 Nos. 6 632.5 614.5 538.5 6 Nos. 1 Nos. 8 687 669 593 6 Nos. 1 Nos. 12 796 778 702 6 Nos. 1 Nos.

Dimensions (in mm)

Dimensions (in mm)

Ways Cat No. 4 DSDPVDIBEOTO04 6 DSDPVDIBEOTO06 8 DSDPVDIBEOTO08 12 DSDPVDIBEOTO12

DISTRIBUTION BOARDS DISTRIBUTION BOARDS

POWERLINE VERTICAL TYPE DBs - IP 42 PROTECTION

3.5

A C

270.0 113.0

350.0367.0

B

(fixi

ng c

ente

r)

(fixing center)

ØM

ount

ing

hole

7

.0

E

88

B

A

720

C

375

450

480

CBC

310

310

PER PHASE ISOLATION (PPI) HORIZONTAL DBS - IP 42 PROTECTION

Page 45: DP.pdf

45

Dimensions (in mm)

Ways Capacity of Cat No. 17.8 mm module Incomer + Outgoing 2 + 12 8 + (6 + 36) DSDPTVPDRW12

No. of Dimensions Knockout Holes (Ø31) Ways A B C Top Bottom Side (Each Side)

2 + 12 395 320 405 7 7 6

PER PHASE ISOLATION (PPI) VERTICAL DBs - IP 42 PROTECTION

DISTRIBUTION BOARDS DISTRIBUTION BOARDS

PHASE SELECTOR (HORIZONTAL) DBS - 4 QUADRANT DESIGN (With Rotary Switches & Wires)

PHASE SELECTOR DBS (Without Rotary Switches & Wires)

No. of Rating Cat. No. (DD) Ways Horizontal 4 40A DSDSCHDRZ04040 With eight way incomer slot 4 63A DSDSCHDRZ04063 With eight way incomer slot 6 40A DSDSCHDRZ06040 With eight way incomer slot 6 63A DSDSCHDRZ06063 With eight way incomer slot 8 40A DSDSCHDRZ08040 With eight way incomer slot 8 63A DSDSCHDRZ08063 With eight way incomer slot

No. of Regal Grey Ways Cat. No. (DD)

4 DSDSCHDRZ04000 6 DSDSCHDRZ06000 8 DSDSCHDRZ08000

A

B 310

3

11

460

450

375

C

Page 46: DP.pdf

46

DISTRIBUTION BOARDS DISTRIBUTION BOARDS

4 456 320 494 8 6 562 428 602 8 8 672 536 710 8 12 888 752 926 12

Ways A B C Knock Out Holes (Ø31)

7 SEGMENT DBs - IP 42 PROTECTION

Dimensions (in mm)

Ways Cat No. 4 DSDMTHDDRW04 6 DSDMTHDDRW06 8 DSDMTHDDRW08 12 DSDMTHDDRW12

Dimensions (in mm)

PHASE SELECTOR (VERTICAL) DBs DOUBLE DOOR

4 8+12 40A 333 323 248 9 8 9 8 3 4 8+12 63A 333 323 248 9 8 9 8 3 6 8+18 40A 405 395 320 9 8 9 8 3 6 8+18 63A 405 395 320 9 8 9 8 3 8 8+24 40A 405 395 320 9 8 9 8 3 8 8+24 63A 405 395 320 9 8 9 8 3

Ways Capacity of Rating A B C Knockout Holes 17.8 mm module Top Bottom Each Side Incoming+Outgoing Ø25 Ø20 Ø25 Ø20 Ø20

No. of Rating Cat. No. Ways Double Door 4 40A DSDSNVDRZ04040 4 63 A DSDSNVDRZ04063 6 40 A DSDSNVDRZ06040 6 63 A DSDSNVDRZ06063 8 40 A DSDSNVDRZ08040 8 63 A DSDSNVDRZ08063

11 105

595

670

680

A

BC 3

D- 31 Knockout holes O/G

6W, 8W & 12W

BA

C 2222

102

8

680

650

550

4W

D- 31 Knockout holes O/G

D- 31 Knockout holes O/GD- 31 Knockout holes O/G

680

650

550

B

A

C 2222

102

8

Page 47: DP.pdf

47

DISTRIBUTION BOARDS DISTRIBUTION BOARDS

A B C 1/2 140 45 65 3/4 140 81 65

Ways Dimensions

MCB PLASTIC ENCLOSURES

Dimensions (in mm)

Ways Cat No. ½ DSDEPDP 3/4 DSDEPFP

A B C D E Incoming Outgoing 1 78 64 28 164 150 1Nos. Ø26 1Nos. Ø26 2 118 104 49 189 175 1Nos. Ø26 1Nos. Ø26 3 118 104 49 189 175 1Nos. Ø26 1Nos. Ø26 4 136 122 67 189 175 1Nos. Ø26 1Nos. Ø26

Ways Dimensions Knock Out Dia

Dimensions (in mm)

MCB SHEET STEEL ENCLOSURES

Ways (Amp.) Cat No. 1 DSDESSP 2 DSDESDP 3 DSDESTP 4 DSDESFP

C 63.0

107.

0

125.

0

(fixi

ng c

ente

r)

(fixi

ng c

ente

r)

(fixing center) (fixing center)

E

AAB B (KSS-1+N / 2+N/ 3 /4+N)

(KSS-2+N/ 3+N / 4+N)(KSS-1+N)

53.5

Earth Terminal

C

DD

B C

A

Page 48: DP.pdf

48

PLUG AND SOCKET ENCLOSURES

Rating (Amp.) Cat No. 20A/SPN/DP (AC Box) DSDPUSN020 20A/TP DSDPUTN020 30A/TP DSDPUTN032

Dimensions (in mm)

20 KSPS/SP 133 162 1 No. f 26 1 No. f 26 20 KSPS/TP 123 287 1 No. f 26 1 No. f 26 30 KSPS/TP 123 287 1 No. f 26 1 No. f 26

Rating Item Surface Knockout Amps. Code Mounting Incoming Outgoing W L

ACCESSORIES

• Neutral Bar/Earth Bar • DIN Channel• Bus Bar with PVC Sleeve • Blanking Plate 1/2

CUSTOMIZED DBs• Prewired DB • Dbs with extended loose wire box• Meter Box (1 Phase & 3 Phase)

ROW TYPE DISTRIBUTION BOARDSSTANDARD make row type distribution boards are versatile in design and aesthetics. These are specially designed for domestic as well as multi-storey complexes. Keeping in view the capacity usage requirement, these are available in 1,2,3,4 and 5 rows both in 12 module and 16 module versions. The flush mounting and aesthetic look adds to the grace of interiors. These are supplied duly epoxy powder coated with shade RAL 7035 or as per specific requirement of the customers.

FEATURES• The DB can be supplied with neutral and earth bars if so required• The enclosures are made of special grade CRCA steel sheet manufactured with latest CNC punch and brake presses to attain higher

degree of perfection.• Adequate number of knockouts at the end plates are provided for ease of wiring.• Din rails are provided for snap mounting of MCBs/RCCBs.• The DB is suitable for IP 40 degree of protection.

254.

0

(fixi

ng c

ente

r)

L

L

278.

011

0.0

152.

0

TP

SPN

63.0

63.0

56.0

Earth terminal

W

W

Page 49: DP.pdf

49

IP RATINGSThe IP (International Protection) rating given to an enclosure states the degree of protection it offers by means of two digits. A summary of these is shown below, for a more detaileddefition, see IEC 529 : 1989, BS EN 60529 : 1992.

FIRST DIGIT Protection against solid foreign objects and access to hazardous parts.The first digit covers protection against penetration by solid objects, which includes hands and tools such as screwdrivers. At the lowest of seven levels, 0, no protection is offered, either of the equipment itself from damage by intrusion or of a person contacting live or moving parts. At the highest, there shall be no entry of dust.

SECOND DIGIT Protection against ingress of water. The second digit covers the degree of protection against the entry of water, on a progressive scale. for example, number 1 indicates that dripping water shall have no harmful effect, and number 6, that water projected in powerfuljets against the enclosure from any direction shall have no harmful effects.

The letter X can be used in place of the first or second digit to indicate that tests have either not been made or are not applicable.

Protected against strong jets of water e.g. for use on ship decks -limited ingress permitted

Protected against low pressure jets of water from all directions -limited ingress permitted

Protected against after splashed from all directions -limited ingress permitted

Protected against sprays of water up to 60° from the vertical

Protected against direct sprays of water up to 15° from the vertical

Protected against vertically falling drops of water eg. condensation

No ProtectionNo Protection 0

1

2

3

4

5

6

0

1

2

3

4

5

6

Protected against solid objects up to 50 mm. e.g. accidental touch by hands

Protected against solid objects up to 12 mm e.g. fingers

Protected against solid objects over 2.5 mm e.g. tools and wires

Protected against solid objects over 1 mm e.g. tools, wires and small wires

Protected against dust -limited ingress, no harmful deposits

Totally protected against dust.

Page 50: DP.pdf

50

CATEGORY OF DUTY

The category of duty defines the basic type of circuit and switching capability of the device, and selection should be made accordingly.

Utilisation Category Typical Applications

AC20/DC20 Connecting and disconnecting under no-load.

Assumes all switching operations are carried out by other capable devices before this device is operated.

AC21/DC21 Switching of resistive loads including moderate overloads.

Suitable for purely resistive type loads devices can switch 150% of its rated current under fault conditions

Ue = Rated Operational Voltage

The normal line-to-line voltage of the

system should not exceed (Ue)

Ui = Rated Insulation Voltage

The voltage on which the dielectric properties have conventionally been based using tests at high voltage and mains frequency. It is intended to replace this value with (Uimp)

Uimp = The voltage on which clearance distances are based.

The value of transient peak voltage the circuit breaker can withstand from switching surges or lighting strikes imposed on the supply.

e.g. Uimp = 8kV, Tested @8kV peak with

1.2/50m (ms)S impulse wave

In = Rated Current

The current which the circuit breaker will carry continuously under specified conditions and on which the time / current characteristics are based.

Unless otherwise slated (In) is based on a reference ambient temperature of 30° centigrade.

Icu Rated Ultimate Short Circuit

Breaking Capacity

The calculated prospective fault current at the incoming terminals of the circuit breaker should not exceed (Icu).

Exception: Using back-up protection as specified by the manufacturer.

Ics Rated Short-time Withstand Current

The maximum level of fault current operation after which further service is assured without loss of performance.

Icw Rated Short-time Withstand Current

Circuit breakers of utilisation category ‘B’ have a short-time delay allowing time-graded selectivity between circuit breakers in series.

(Icw) is the current the circuit breaker will withstand for the maximum short-time delay time. Preferred times are 0.05, 0.1, 0.25, 0.5 and 1.0 second.

Ui = 660V

Tested@

2500V ac 50Hz

AC22/DC22 Switching of mixed resistive / inductive loads, including moderate overloads.

Suitable for mixed resistive / inductive loads. Devices can switch 300% of its rated current under fault conditions.

AC23/DC23 Switching of highly inductive loads. Devices complying with AC23/DC23 are

provided mainly as back-up to other means of switching. e.g. contacts. In the event of failure of functional devices, an AC23 / DC23 type device can safety interrupt a stalled motor current. Where devices are the only means of controlling individual motors, they should comply with the requirements of appendix A of the standard. (IEC 60947-3)

Page 51: DP.pdf

REPRESENTATIVE OFFICES

• Goa • Solapur • Gwalior • Jabalpur • Hubli • Davanagere • Gulbarga • Mysore • Trichy • Kathmandu • Sambalpur

• Jalandhar • Bhopal • Calicut • Madurai • Trivandrum

REGIONAL BRANCH OFFICES

NORTH - REGIONAL OFFICE : Delhi : QRG Towers, 2D, Sector-126, Expressway, Noida-201304

Noida : Tel: 0120-4771000, Fax: 0120-4772000

Chandigarh : Tel: 0172-4232400 -401, Fax: 0172-4232403,

Dehradun : Tel: 0135-2521025, 2521552

Haryana : Tel: 91-120 2477848 / 853, Fax: 0120-2583904

Noida : Tel: 0120-3055609 / 3055610, Fax: 0120-3055611

Ludhiana : Tel: 0161-4676001 / 6024, Fax: 0161-46766007

Jammu : Tel:0191-2490424, Fax: 0191-2490405

Jaipur : Tel: 0141-3988210, Fax: 0141-2389024

Lucknow : Tel: 0522-2201032, 2200938

Kanpur : Tel: Airtel: 09935533751/52/53, 0512-2690128/129/130, Fax: 0512-2692800

EAST - REGIONAL OFFICE : Kolkata : ICC Tower, 5th Floor, 4 India Exchange Place, Kolkata-700 001

Kolkata : Tel: 033-40129851/52, Fax: 033-40127339

Bhubaneshwar : Tel: 0674-2598104, 2598105, 2598106, Fax: 0674-2598107

Guwahati : Tel: 0361-2134521, 2458923, Fax: 0361-2460355

Siliguri : Tel: 0353-2525907-3290402 (RIM)

Jamshedpur : Tel: 0657-6542492, 09234369436

Patna : Tel: 0612-3244218, 2655519, Telefax: 0612-2655518

WEST - REGIONAL OFFICE : Mumbai : 302, Boston House, 3rd Floor Suren Road, CTS No. 260/261, Andheri

(E), Mumbai-400 093

Mumbai : Tel: 022-67298600-603

Ahmedabad : Tel: 079-40061111, 40060738-740, Fax: 079-40060741

Indore : Tel: 0731-2572340-41, 4009998 (Airtel), Fax: 0731-2551626

Rajkot : Tel: 0281 3013289 / 3013290

Nagpur : Tel: 0712-2224132, 2222692, 2222029

Pune : Tel: 020-64016413/14

Raipur : Tel: 0771-4243400 / 01, Telefax: 0771-4243402

Surat : Telefax: 0261-2350137

SOUTH - REGIONAL OFFICE : Chennai : Block – 1, A & D Wing, Shakthi Towers, 7th Floor, 766, Annna Salai,

Chennai-600 002

Chennai : Tel: 044-28526941-44, Fax: 044-28524326

Bangalore : Tel: 080-39882100, 30515801 / 2 / 3 /4, Fax: 080-30515804

Coimbatore : Telefax: 0422-2305767, 2306199, 2305199

Hyderabad : Tel: 040-27533372, 27533355, 27533632, 66320407/0408/6401/6402, Fax: 040-27533211

Kochi : Tel: 0484-4099000, 2393165, 2393068, Fax: 0484-2393170

Vishakapatnam : Tel: 0891-6514339, Fax: 0891-2522547

Page 52: DP.pdf

STANDARD ELECTRICAL LIMITEDCorporate Office: QRG Towers, 2D, Sector -126, Expressway, Noida - 201 304 (UP),

Ph. +91-120-4771000, India E-mail: [email protected]

Consumer Care No.: 1800 11 0303 (Toll Free), 011-41 66 0303 (Landline), 1800 103 1313 (All connections)

Registered Office: 1/7, Ram Kishore Road, Civil Lines, Delhi - 110054 Visit us at : www.sel.co.in

For International Trade Enquires, please E-mail to: [email protected]