    DP transmit ter, 7MF4432 air flow

    and

    Output current in mA or % or input pressure in

    unit of pressure

    "Error ", if the transmitter is disturbed. Moving

    text indicating reason for disturbance.

    Current Current Set to

    greater smaller 4 mA

    Current Current Set to

    greater smaller 20 mA

    Dampning Dampning Time constant T63 in seconds

    greater smaller Parameter range 0.0 to 100.0

    Start of scale Pressure Pressure Set to start

    "blind setting" greater smaller of scale 0

    Full scale Pressure Pressure Set to upper  

    "blind setting" greater smaller measuring limit

    Zero adjustment Vent transmitter (start of scale remains

    (position correction) unaffected). Measuring value in unit of pressure

    Current Current Constant output current in mA; 3.6 - 4.0 - 12.0 -

    greater smaller   20.0 - 22.8, switched off by "M" key.

    Output current in the Selected output current

    event of an error Possible: fault current limits set by user  

    "0" = none

    "LA" = all disable

    "LO" = all disable except start of scale

    "LS" = all disable except start and full scale

    "L" = write protection,

    "Lin" = liniar 

    "SrLin" = square rooting

      (linear up to application point)

    "SroFF" = square rooting

      (switched off up to application point)

     Application point of 

    the square rooting Greater Smaller - - Parameter range 5 to 15 % flow

    Characteristic

    Measured value unit of pressure (input value) or output current

    display mA or %

    Unit of pressure 14 Thehnical units of pressure mmh20 mmh20

    3,6

    0

    srlin

    10%

    1,5

    1

    300

    Measured value

    Key functionFunction Mode

    Current transmitter 

    Output current in mA

    Start of scale in selected unit of pressure

    Full scale in selected unit of pressure

    - -

    8 Switch on

    Output current in mA

    NO.2Display, explanation NO.1

    Error display

    Start of scale

    - -

    Full scale

    Electrical dampning

    3

    4

    Changes between the

    two values

    Execute

    2

    5

    6

    7

    9 - -

    Keys and/or function

    disable10

    Changes between the

    five functions- -

    Change

    Characteristic 11Changes between the

    three functions

    13Select from three

    possibilities

    12

    - -

    3,6

    0

    srlin

    10%

    1,5

    1

    300