Data Center Efficiency: More Than Saving Money
Domenic AlcaroAmerican Power ConversionDirector, Enterprise Segment Northeast
Agenda
What is data center efficiency?IT trends
The problemRoot cause
Proposed solutionsSupport material
What is data center efficiency?
Total IT powerTotal IT power
Total input powerTotal input power=
• Input power includes both IT power and NCPI power• Input power is only for data center, not for personnel spaces
Source: APC White Paper #113
What is data center efficiency?Data center
ITEquipment
Power toPower todata centerdata center Cooling
LightsFireSecurityGeneratorSwitchgear
UPSPDUCablingSwitches
Power pathPower pathto ITto IT
Power toPower toSecondarySecondary
SupportSupport Data centerUSEFUL OUTPUTUSEFUL OUTPUT
ComputingComputing
Data centerINPUTINPUT
Power Power to ITto IT
NCPINCPI ITIT
Data center
ITEquipment
Power toPower todata centerdata center Cooling
LightsFireSecurityGeneratorSwitchgear
CoolingLightsFireSecurityGeneratorSwitchgear
UPSPDUCablingSwitches
UPSPDUCablingSwitches
Power pathPower pathto ITto IT
Power toPower toSecondarySecondary
SupportSupport Data centerUSEFUL OUTPUTUSEFUL OUTPUT
ComputingComputing
Data centerINPUTINPUT
Power Power to ITto IT
NCPINCPI ITIT
TOTAL IN
%USEFUL OUT Data CenterData CenterEfficiency = Efficiency =
Power to ITPower to IT
Data centerData centerPower INPower IN
IT Trends
• Compaction• High density computing• Dynamic computer loads• IT / physical infrastructure relationship
The Problem
• More customers reaching power limit• Increased risk of tripping CB• World’s most expensive server• Mostly small data rooms and data centers• Potential impact on Service Providers
The ProblemProgression of moves adds & changes
10 kW Rack 1 kW Rack
UPS Load UPS Load UPS Load
Electric Utility Electric Utility Electric Utility
The Problem
0
5
10
15
20
25
30
35
40
45
50
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Compaction density: kW Per Rack
Are
a in
ft2 /
kW [
m2 /
kW]
Area of IT equipment
Area of power and cooling infrastructure
Total area of IT equipment + infrastructure
[4.65]
[4.18]
[3.72]
[3.25]
[2.79]
[2.32]
[1.86]
[1.39]
[0.93]
[0.46]
Root Cause
• Planning– Capacity - kW– Availability level – N+1– Power density - watts / ft2
• Traditional data center design– Typically built all up front– Built with static power density– Raised floor and perimeter cooling
Proposed Solutions
Close Couple The CoolingClose Couple The Cooling
Which would you rather do?
50 Feet
5 Feet
Much less energy requiredAir distribution much more predictable
Proposed Solutions
0
48
95
143
190
238
285
333
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Average Per-Rack Power Density (kW)
CR
AC
Pow
er C
onsu
mpt
ion
kW
row-oriented cooling
room-oriented cooling
rack-oriented cooling
Source: APC White Paper #130
Proposed Solutions• Change data center specify, design, and build
– Specify the max capacity and availability– Design based on predictable standardized building blocks– Grow in zones – each with its own density and availability
• Rightsize based on your load today• High efficiency components – UPS, VFD Chiller• High voltage distribution• Close coupled cooling• Upgrade utility capacity (source: RSMeans)
– Electrical service > $34,650– Feeder installation > $41,700– Switchgear > $53,280– TOTAL > $129,630
Proposed Solutions
High Efficiency Data Center
Chiller @ 7.0 COP14%
Humidif ier3%
CRAC9%
IT Equipment64%
PDU5%
UPS3%
Lighting1%
Main sw tchgr / Gen1%
Typical Data Center
Main swtchgr / Gen1%
Lighting1%
UPS6%
PDU5%
IT Equipment48%
CRAC13%
Humidifier3%
Chiller @ 2.9 COP23%
IT Load
Support Material
• White Papers about High Efficiency in the Data Center
• #108• #128
• #113• #114
• #120
• Visit DataCenterUniversity.com for learning modules on data center efficiency