SAMSUNG Electronics HVAC SAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: WWW.SamsungHVAC.com Multi-unit heat pump systems with 2 to 5 indoor units Condenser Size Range: 1.5, 2, AND 3 TONS (NOMINAL) STANDARD 1.7, 2, 2.4 TONS (NOMINAL) MAX HEAT Samsung Electronics FJM Condenser Model Numbers: AJ020JCJ2CH/AA AJ024JCJ3CH/AA AJ036JCJ5CH/AA AJ020MCS3CH/AA (MAX HEAT) AJ024MCS4CH/AA (MAX HEAT) AJ030MCS4CH/AA (MAX HEAT) Part 1 – General 1.01 SYSTEM DESCRIPTION The variable capacity, heat pump air conditioning system shall be a Samsung Electronics Free Joint Multi System. The Free Joint Multi systems shall be (cool/heat) split system heat pump. The Free Joint Multi heat pump system shall consist of a single outdoor condensing unit (AJ020JCJ2CH/AA, AJ024JCJ3CH/AA, AJ036JCJ5CH/AA, AJ020MCS3CH/AA, AJ024MCS4CH/AA, or AJ030MCS4CH/AA ) and any combination of 2 – 5 indoor units with model numbers AJ0**JNLDCH/AA, AJ0**JNADCH/AA, AJ0**JNNDCH/AA. The Condensing shall be a horizontal discharge, 208/230V, 1Ph, 60Hz unit. The sum of the nominal capacity of connected indoor units shall not exceed the values noted in the table below. Model Number Maximum Indoor Unit Capacity Connection Ratio Maximum Connected Indoor Unit Capacity (cooling) DRAFT: 01/17/2018 www.SamsungHVAC.com Specifications are subject to change without notice. 1

Transcript of HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide...

Page 1: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

SAMSUNG FREE JOINT MULTI (FJM)HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT:WWW.SamsungHVAC.com

Multi-unit heat pump systems with 2 to 5 indoor units

Condenser Size Range:1.5, 2, AND 3 TONS (NOMINAL) STANDARD 1.7, 2, 2.4 TONS (NOMINAL) MAX HEAT

Samsung Electronics FJM Condenser Model Numbers:AJ020JCJ2CH/AA AJ024JCJ3CH/AA AJ036JCJ5CH/AAAJ020MCS3CH/AA (MAX HEAT)AJ024MCS4CH/AA (MAX HEAT)AJ030MCS4CH/AA (MAX HEAT)

Part 1 – General

1.01 SYSTEM DESCRIPTIONThe variable capacity, heat pump air conditioning system shall be a Samsung Electronics Free Joint Multi System. The Free Joint Multi systems shall be (cool/heat) split system heat pump.

The Free Joint Multi heat pump system shall consist of a single outdoor condensing unit (AJ020JCJ2CH/AA, AJ024JCJ3CH/AA, AJ036JCJ5CH/AA, AJ020MCS3CH/AA, AJ024MCS4CH/AA, or AJ030MCS4CH/AA ) and any combination of 2 – 5 indoor units with model numbers AJ0**JNLDCH/AA, AJ0**JNADCH/AA, AJ0**JNNDCH/AA.

The Condensing shall be a horizontal discharge, 208/230V, 1Ph, 60Hz unit. The sum of the nominal capacity of connected indoor units shall not exceed the values noted in the table below.

Model Number Maximum Indoor Unit Capacity Connection Ratio

Maximum Connected Indoor Unit Capacity (cooling)

AJ020JCJ2CH/AA 140% 24,000 Btu/hAJ024JCJ3CH/AA 135% 30,000 Btu/hAJ036JCJ5CH/AA 125% 45,000 Btu/hAJ020MCS3CH/AA 128% 27,000 Btu/hAJ024MCS4CH/AA 128% 32,000 Btu/hAJ030MCS4CH/AA 140% 40,000 Btu/h

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

1

Page 2: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

The Free Joint Multi outdoor unit model numbers and the associated number of connectable indoor units are indicated in the following table. Each indoor unit or group of indoor units shall be independently controlled.

Model Number Connectable Numberof Indoor Units

AJ020JCJ2CH/AA 2AJ024JCJ3CH/AA 4AJ036JCJ5CH/AA 5

AJ020MCS3CH/AA (MAX HEAT) 3AJ024MCS4CH/AA (MAX HEAT) 4AJ030MCS4CH/AA (MAX HEAT) 4

1.02 QUALITY ASSURANCEA. The units shall be listed by Electrical Laboratories (ETL) and bear the ETL label. B. All wiring shall be in accordance with the National Electrical Code (N.E.C.).C. The units shall be manufactured in a facility registered to ISO 9001 and ISO14001

which is a set of standards applying to environmental protection set by the International Standard Organization (ISO).

D. A full charge of R-410A for the condensing unit only shall be provided in the condensing unit. Additional refrigerant is required based on lengths of system liquid refrigerant lines.

Part 2 – Outdoor Unit Performance

2.01 The FJM outdoor unit shall perform as indicated below (nominal capacity):

Nominal Capacities Maximum Capacities

Outdoor UnitCooling Capacity(Btu/h)*

Heating Capacity (Btu/h)**

Cooling Capacity(Btu/h)

Heating Capacity (Btu/h)

AJ020JCJ2CH/AA 17,000 22,000 17,000 25,300AJ024JCJ3CH/AA 22,000 25,000 22,000 29,200AJ036JCJ5CH/AA 36,000 40,000 36,000 44,000AJ020MCS3CH/AA 21,000 22,000 21,000 22,000AJ024MCS4CH/AA 25,000 25,000 25,000 25,000AJ030MCS4CH/AA 28,400 28,600 28,400 28,600

*Nominal cooling capacities are based on: Indoor temperature: 80⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F, 75⁰F WB.**Nominal heating capacities are based on: Indoor temperature: 70⁰F DB, 60⁰F WB. Outdoor temperature: 43⁰F

Part 3 – Products

3.01 AJ020JCJ2CH/AA FREE JOINT MULTI CONDENSING UNIT

A. General:DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

2

Page 3: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

The AJ020JCJ2CH/AA outdoor units shall be equipped with multiple circuit boards that interface (additional parts necessary) to the Samsung Control Network Solution (Control systems) and shall perform all functions necessary for operation. The outdoor unit shall have a powder coated finish. The outdoor unit shall be completely factory assembled, piped and wired. Each unit shall be run tested at the factory.

1. The sum of connected capacity of all indoor units shall not exceed the nominal capacity of the condensing unit.

2. Outdoor unit shall have a sound rating no higher than 48 dB3. All refrigerant lines from the outdoor unit to indoor units shall be insulated.4. The outdoor unit shall have an accumulator.5. The outdoor unit shall have a compressor overload protection, fuse, and over-

current protection.6. The outdoor unit shall have the ability to operate with a maximum height difference

of 49 feet. Maximum total system line set length shall not exceed 164 feet with a maximum individual line set length of 82 feet.

7. The outdoor unit shall be capable of operating in outside ambient temperatures between 23⁰F to 115⁰F in cooling mode without additional low ambient controls.

8. The outdoor unit shall be capable of operating in outside ambient temperatures between 5⁰F and 75⁰F in heating mode without additional low ambient controls.

9. The control circuit between the indoor units, and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system.

B. Unit Cabinet:1. The chassis shall be fabricated of galvanized steel, bonderized and finished with a

powder coated baked enamel.

C. Fan:1. The outdoor unit shall be furnished with one direct drive, variable speed propeller

type fan.2. All fan motors shall be BLDC type.3. The fan motor shall have inherent protection, have permanently lubricated bearings,

and be completely variable speed.4. The fan motor shall be mounted for quiet operation.5. The fan shall be provided with a raised guard to prevent contact with moving parts.6. The outdoor unit shall have horizontal discharge airflow.

D. Refrigerant:1. The condensing unit shall require R410A refrigerant.2. The condensing unit comes charged for total system line set lengths up to 98 feet.

Additional refrigerant is required if the system line set length is over 98 feet. For every additional foot over 98, 0.11 ounces of refrigerant must also be added.

3. The condensing unit shall contain 2 EEV’s (electronic expansion valves) with 480 positions each to control refrigerant flow to each indoor unit independently.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

3

Page 4: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

E. Coil:1. The outdoor coil shall be of nonferrous construction with lanced or corrugated plate

fins on copper tubing.2. Aluminum coil fins shall be coated with a hydrophilic/protective coating to reduce

corrosion and promote moisture shedding.3. The coil shall be protected with an integral guard.4. Refrigerant flow from the outdoor unit shall be controlled by means of a capacity

modulation capable, inverter driven, twin BLDC rotary compressor.

F. Compressor:1. The compressor shall be an inverter driven, DC voltage, twin BLDC rotary

compressor made by Samsung.2. A crankcase heater shall be factory mounted in/on the compressor.3. The outdoor unit compressor shall have a variable modulation technology to

modulate capacity. The capacity shall be completely variable down to 6,500 Btu/h minimum capacity in cooling mode and 3,500 Btu/h in heating mode.

4. The compressor shall be equipped with an external thermal overload.5. The compressor shall be mounted to avoid the transmission of vibration.

G. Electrical:1. The outdoor unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. 2. The unit shall be capable of satisfactory operation within voltage limitations of 187-

228 volts (208V/60Hz) or 207-253 volts (230V/60Hz) with a maximum 15A overcurrent protection.

3. The outdoor unit shall be controlled by integral microprocessors.4. The control circuit between the indoor units and the outdoor unit shall be 0.5VDC -

7VDC completed using stranded, annealed copper conductor, 16 AWG, shielded, two-core cable to provide total integration of the system. The control wire shall be run from the condensing unit to each indoor unit independently.

5. The outdoor unit shall provide power to the indoor unit with 14 AWG X 3 power wire (2 X high voltage wires, 1 X ground). The power wire shall be run from the condensing unit to each indoor unit independently.

H. Connectable indoor units:1. AJ009JNLDCH/AA, AJ012JNLDCH/AA, AJ007JNADCH/AA, AJ009JNADCH/AA,

AJ012JNADCH/AA, AJ009JNNDCH/AA, AJ012JNNDCH/AA, 2. Connectable combinations:

Indoor Unit

A B

2 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA

AJ007JN*DCH/AA AJ009JN*DCH/AA

AJ007JN*DCH/AA AJ012JN*DCH/AA

AJ009JN*DCH/AA AJ009JN*DCH/AA

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

4

Page 5: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

AJ009JN*DCH/AA AJ012JN*DCH/AA

AJ012JN*DCH/AA AJ012JN*DCH/AA

3.02 AJ024JCJ3CH/AA FREE JOINT MULTI CONDENSING UNIT

A. General:The AJ024JCJ3CH/AA outdoor units shall be equipped with multiple circuit boards that interface (additional parts necessary) to the Samsung Control Network Solution (Control systems) and shall perform all functions necessary for operation. The outdoor unit shall have a powder coated finish. The outdoor unit shall be completely factory assembled, piped and wired. Each unit shall be run tested at the factory.

1. The sum of connected capacity of all indoor units shall not exceed the nominal capacity of the condensing unit.

2. Outdoor unit shall have a sound rating no higher than 49 dB3. All refrigerant lines from the outdoor unit to indoor units shall be insulated.4. The outdoor unit shall have an accumulator.5. The outdoor unit shall have a compressor overload protection, fuse, and over-

current protection.6. The outdoor unit shall have the ability to operate with a maximum height difference

of 49 feet. Maximum total system line set length shall not exceed 230 feet with a maximum individual line set length of 82 feet.

7. The AJ024JCJ3CH/AA outdoor unit shall be capable of operating in outside ambient temperatures between 23⁰F to 115⁰F in cooling mode without additional low ambient controls.

8. The outdoor unit shall be capable of operating in outside ambient temperatures between 5⁰F and 75⁰F in heating mode without additional low ambient controls.

9. The control circuit between the indoor units, and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system.

B. Unit Cabinet:1. The chassis shall be fabricated of galvanized steel, bonderized and finished with a

powder coated baked enamel.

C. Fan:1. The outdoor unit shall be furnished with one direct drive, variable speed propeller

type fan. 2. All fan motors shall be BLDC type.3. The fan motor shall have inherent protection, have permanently lubricated

bearings, and be completely variable speed.4. The fan motor shall be mounted for quiet operation.5. The fan shall be provided with a raised guard to prevent contact with moving parts.6. The outdoor unit shall have horizontal discharge airflow.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

5

Page 6: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

D. Refrigerant1. The condensing unit shall require R410A refrigerant.2. The condensing unit comes charged for total system line set lengths up to 131 feet.

Additional refrigerant is required if the system line set length is over 131 feet. For every additional foot over 131, 0.11 ounces of refrigerant must also be added.

3. The condensing unit shall contain 3 EEV’s (electronic expansion valves) with 480 positions each to control refrigerant flow to each indoor unit independently.

E. Coil:1. The outdoor coil shall be of nonferrous construction with lanced or corrugated plate

fins on copper tubing.2. Aluminum coil fins shall be coated with a hydrophilic/protective coating to reduce

corrosion and promote moisture shedding.3. The coil shall be protected with an integral guard.4. Refrigerant flow from the outdoor unit shall be controlled by means of a capacity

modulation capable, inverter driven, twin BLDC rotary compressor.

F. Compressor:1. The compressor shall be an inverter driven, DC power, twin BLDC rotary

compressor made by Samsung.2. A crankcase heater shall be factory mounted on/in the compressor.3. The outdoor unit compressor shall have a variable modulation technology to

modulate capacity. The capacity shall be completely variable down to 7,500 Btu/h minimum capacity in cooling mode and 4,300 Btu/h in heating mode.

4. The compressor shall be equipped with an external thermal overload.5. The compressor shall be mounted to avoid the transmission of vibration.

G.Electrical:1. The outdoor unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. 2. The unit shall be capable of satisfactory operation within voltage limitations of 187-

228 volts (208V/60Hz) or 207-253 volts (230V/60Hz) with a maximum 30A overcurrent protection.

3. The outdoor unit shall be controlled by integral microprocessors.4. The control circuit bet5. ween the indoor units and the outdoor unit shall be 0.5VDC - 7VDC completed

using stranded, annealed copper conductor, 16 AWG, shielded, two-core cable to provide total integration of the system. The control wire shall be run from the condensing unit to each indoor unit independently.

6. The outdoor unit shall provide power to the indoor unit with 14 AWG X 3 power wire (2 X high voltage wires, 1 X ground). The power wire shall be run from the condensing unit to each indoor unit independently.

H. Connectable indoor units:1. AJ009JNLDCH/AA,AJ012JNLDCH/AA, AJ018JNLDCH/AA, AJ007JNADCH/AA,

AJ009JNADCH/AA, AJ012JNADCH/AA, AJ018JNADCH/AA, AJ009JNNDCH/AA, AJ012JNNDCH/AA, AJ018JNNDCH/AA

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

6

Page 7: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

2. Connectable combinations:

Indoor Unit

A B C

2 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA  

AJ007JN*DCH/AA AJ009JN*DCH/AA  

AJ007JN*DCH/AA AJ012JN*DCH/AA  

AJ007JN*DCH/AA AJ018JN*DCH/AA  

AJ009JN*DCH/AA AJ009JN*DCH/AA  

AJ009JN*DCH/AA AJ012JN*DCH/AA  

AJ009JN*DCH/AA AJ018JN*DCH/AA  

AJ012JN*DCH/AA AJ012JN*DCH/AA  

AJ012JN*DCH/AA AJ018JN*DCH/AA  

Indoor Unit

A B C

3 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA

AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA

AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AA

AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA

AJ007JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA

AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA

AJ009JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA

3.03 AJ036JCJ5CH/AA FREE JOINT MULTI CONDENSING UNIT

A. General:The AJ036JCJ5CH/AA outdoor units shall be equipped with multiple circuit boards that interface (additional parts necessary) to the Samsung Control Network Solution (Control systems) and shall perform all functions necessary for operation. The outdoor unit shall have a powder coated finish. The outdoor unit shall be completely factory assembled, piped and wired. Each unit shall be run tested at the factory.

1. The sum of connected capacity of all indoor units shall not exceed the nominal capacity of the condensing unit.

2. Outdoor unit shall have a sound rating no higher than 54 dB3. All refrigerant lines from the outdoor unit to indoor units shall be insulated.4. The outdoor unit shall have an accumulator.5. The outdoor unit shall have a high pressure safety switch, fuse, over-current

protection and crank case heater.6. The outdoor unit shall have the ability to operate with a maximum height difference

of 49 feet. Maximum total system line set length shall not exceed 262 feet with a maximum individual line set length of 82 feet.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

7

Page 8: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

7. The outdoor unit shall be capable of operating in outside ambient temperatures between 14⁰F to 115⁰F in cooling mode without additional low ambient controls.

8. The outdoor unit shall be capable of operating in outside ambient temperatures between 5⁰F and 75⁰F in heating mode without additional low ambient controls.

9. The control circuit between the indoor units, and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system.

B. Unit Cabinet:1. The chassis shall be fabricated of galvanized steel, bonderized and finished with a

powder coated baked enamel.

C. Fan:1. The outdoor unit shall be furnished with one direct drive, variable speed propeller

type fan. 2. All fan motors shall be BLDC type.3. The fan motor shall have inherent protection, have permanently lubricated

bearings, and be completely variable speed.4. The fan motor shall be mounted for quiet operation.5. The fan shall be provided with a raised guard to prevent contact with moving parts.6. The outdoor unit shall have horizontal discharge airflow.

D. Refrigerant1. The condensing unit shall require R410A refrigerant.2. The condensing unit comes charged for total system line set lengths up to 131 feet.

Additional refrigerant is required if the system line set length is over 131 feet. For every additional foot over 131, 0.22 ounces of refrigerant must also be added.

3. The condensing unit shall contain 5 EEV’s (electronic expansion valves) with 480 positions each to control refrigerant flow to each indoor unit independently.

E. Coil:1. The outdoor coil shall be of nonferrous construction with lanced or corrugated plate

fins on copper tubing.2. Aluminum coil fins shall be coated with a hydrophilic/protective coating to reduce

corrosion and promote moisture shedding.3. The coil shall be protected with an integral guard.4. Refrigerant flow from the outdoor unit shall be controlled by means of a capacity

modulation capable, inverter driven, twin BLDC rotary compressor.

F. Compressor:1. The compressor shall be an inverter driven, DC power, twin BLDC rotary

compressor made by Samsung.2. A crankcase heater shall be factory mounted on/in the compressor.3. The outdoor unit compressor shall have a variable modulation technology to

modulate capacity. The capacity shall be completely variable down to 9,500 Btu/h minimum capacity in cooling mode and 7,600 Btu/h in heating mode.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

8

Page 9: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

4. The compressor shall be equipped with an external thermal overload.5. The compressor shall be mounted to avoid the transmission of vibration.

G.Electrical:1. The outdoor unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. 2. The unit shall be capable of satisfactory operation within voltage limitations of 187-

228 volts (208V/60Hz) or 207-253 volts (230V/60Hz) with a maximum 30A overcurrent protection.

3. The outdoor unit shall be controlled by integral microprocessors.4. The control circuit between the indoor units and the outdoor unit shall be 0.5VDC -

7VDC completed using stranded, annealed copper conductor, 16 AWG, shielded, two-core cable to provide total integration of the system. The control wire shall be run from the condensing unit to each indoor unit independently.

5. The outdoor unit shall provide power to the indoor unit with 14 AWG X 3 power wire (2 X high voltage wires, 1 X ground). The power wire shall be run from the condensing unit to each indoor unit independently.

H. Connectable indoor units:1. AJ009JNLDCH/AA,AJ012JNLDCH/AA, AJ018JNLDCH/AA, AJ007JNADCH/AA,

AJ009JNADCH/AA, AJ012JNADCH/AA, AJ018JNADCH/AA, AJ009JNNDCH/AA, AJ012JNNDCH/AA, AJ018JNNDCH/AA, AJ024JNADCH/AA

2. Connectable combinations:

Indoor Unit

A B C D E

2 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA      AJ007JN*DCH/AA AJ009JN*DCH/AA      AJ007JN*DCH/AA AJ012JN*DCH/AA      AJ007JN*DCH/AA AJ018JN*DCH/AA      AJ007JN*DCH/AA AJ024JN*DCH/AA      AJ009JN*DCH/AA AJ009JN*DCH/AA      AJ009JN*DCH/AA AJ012JN*DCH/AA      AJ009JN*DCH/AA AJ018JN*DCH/AA      AJ009JN*DCH/AA AJ024JN*DCH/AA      AJ012JN*DCH/AA AJ012JN*DCH/AA      AJ012JN*DCH/AA AJ018JN*DCH/AA      AJ012JN*DCH/AA AJ024JN*DCH/AA      AJ018JN*DCH/AA AJ018JN*DCH/AA      AJ018JN*DCH/AA AJ024JN*DCH/AA      

Indoor Unit

A B C D E

3 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ018JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ024JN*DCH/AA    AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA    AJ007JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA    AJ007JN*DCH/AA AJ009JN*DCH/AA AJ018JN*DCH/AA    

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

9

Page 10: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

AJ007JN*DCH/AA AJ009JN*DCH/AA AJ024JN*DCH/AA    AJ007JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA    AJ007JN*DCH/AA AJ012JN*DCH/AA AJ018JN*DCH/AA    AJ007JN*DCH/AA AJ012JN*DCH/AA AJ024JN*DCH/AA    AJ007JN*DCH/AA AJ018JN*DCH/AA AJ018JN*DCH/AA    AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA    AJ009JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA    AJ009JN*DCH/AA AJ009JN*DCH/AA AJ018JN*DCH/AA    AJ009JN*DCH/AA AJ009JN*DCH/AA AJ024JN*DCH/AA    AJ009JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA    AJ009JN*DCH/AA AJ012JN*DCH/AA AJ018JN*DCH/AA    AJ009JN*DCH/AA AJ012JN*DCH/AA AJ024JN*DCH/AA    AJ009JN*DCH/AA AJ018JN*DCH/AA AJ018JN*DCH/AA    AJ012JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA    AJ012JN*DCH/AA AJ012JN*DCH/AA AJ018JN*DCH/AA    

Indoor Unit

A B C D E

4 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ018JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ024JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA AJ018JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AA AJ018JN*DCH/AA  AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA  AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA  AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ018JN*DCH/AA  AJ007JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA  AJ007JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA  AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA  AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA  AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ018JN*DCH/AA  AJ009JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA  AJ009JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA  

Indoor UnitA B C D E

5 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AAAJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AAAJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AAAJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AAAJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AAAJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AAAJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AAAJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AAAJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AAAJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

10

Page 11: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

3.04 AJ020MCS3CH/AA MAX HEAT FREE JOINT MULTI CONDENSING UNIT

A. General:The AJ020MCS3CH/AA outdoor units shall be equipped with multiple circuit boards that interface (additional parts necessary) to the Samsung Control Network Solution (Control systems) and shall perform all functions necessary for operation. The outdoor unit shall have a powder coated finish. The outdoor unit shall be completely factory assembled, piped and wired. Each unit shall be run tested at the factory.

1. The sum of connected capacity of all indoor units shall not exceed the nominal capacity of the condensing unit.

2. Outdoor unit shall have a sound rating no higher than 58 dB3. The outdoor unit shall have a base pan heater to aid in defrost cycle water

drainage.4. All refrigerant lines from the outdoor unit to indoor units shall be insulated.5. The outdoor unit shall have an accumulator.6. The outdoor unit shall have a fuse, over-current protection and crank case heater.7. The outdoor unit shall have the ability to operate with a maximum height difference

of 49 feet. Maximum total system line set length shall not exceed 164 feet with a maximum individual line set length of 82 feet.

8. The outdoor unit shall be capable of operating in outside ambient temperatures between 14⁰F to 115⁰F in cooling mode without additional low ambient controls.

9. The outdoor unit shall be capable of operating in outside ambient temperatures between -13⁰F and 75⁰F in heating mode without additional low ambient controls.

10.The control circuit between the indoor units, and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system.

B. Unit Cabinet:1. The chassis shall be fabricated of galvanized steel, bonderized and finished with a

powder coated baked enamel.

C. Fan:1. The outdoor unit shall be furnished with one direct drive, variable speed propeller

type fan. 2. All fan motors shall be BLDC type.3. The fan motor shall have inherent protection, have permanently lubricated

bearings, and be completely variable speed.4. The fan motor shall be mounted for quiet operation.5. The fan shall be provided with a raised guard to prevent contact with moving parts.6. The outdoor unit shall have horizontal discharge airflow.

D. Refrigerant1. The condensing unit shall require R410A refrigerant.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

11

Page 12: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

2. The condensing unit comes charged for total system line set lengths up to 131 feet. Additional refrigerant is required if the system line set length is over 131 feet. For every additional foot over 131, 0.22 ounces of refrigerant must also be added.

3. The condensing unit shall contain 3 EEV’s (electronic expansion valves) with 480 positions each to control refrigerant flow to each indoor unit independently.

E. Coil:1. The outdoor coil shall be of nonferrous construction with lanced or corrugated plate

fins on copper tubing.2. Aluminum coil fins shall be coated with a hydrophilic/protective coating to reduce

corrosion and promote moisture shedding.3. The coil shall be protected with an integral guard.4. Refrigerant flow from the outdoor unit shall be controlled by means of a capacity

modulation capable, inverter driven, twin BLDC rotary compressor.

F. Compressor:1. The compressor shall be an inverter driven, DC power, twin BLDC rotary

compressor made by Samsung.2. A crankcase heater shall be factory mounted on/in the compressor.3. The outdoor unit compressor shall have a variable modulation technology to

modulate capacity. The capacity shall be completely variable down to 7,500 Btu/h minimum capacity in cooling mode and 7,600 Btu/h in heating mode.

4. The compressor shall be equipped with an external thermal overload.5. The compressor shall be mounted to avoid the transmission of vibration.

G.Electrical:1. The outdoor unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. 2. The unit shall be capable of satisfactory operation within voltage limitations of 187-

228 volts (208V/60Hz) or 207-253 volts (230V/60Hz) with a maximum 30A overcurrent protection.

3. The outdoor unit shall be controlled by integral microprocessors.4. The control circuit between the indoor units and the outdoor unit shall be 0.5VDC -

7VDC completed using stranded, annealed copper conductor, 16 AWG, shielded, two-core cable to provide total integration of the system. The control wire shall be run from the condensing unit to each indoor unit independently.

5. The outdoor unit shall provide power to the indoor unit with 14 AWG X 3 power wire (2 X high voltage wires, 1 X ground). The power wire shall be run from the condensing unit to each indoor unit independently.

H. Connectable indoor units:1. AJ009JNLDCH/AA, AJ012JNLDCH/AA, AJ007JNADCH/AA, AJ009JNADCH/AA,

AJ012JNADCH/AA, AJ009JNNDCH/AA, AJ012JNNDCH/AA2. Connectable combinations:

Indoor Unit

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

12

Page 13: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

A B C D E

2 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA      AJ007JN*DCH/AA AJ009JN*DCH/AA      AJ007JN*DCH/AA AJ012JN*DCH/AA      AJ009JN*DCH/AA AJ009JN*DCH/AA      AJ009JN*DCH/AA AJ012JN*DCH/AA      AJ012JN*DCH/AA AJ012JN*DCH/AA      

Indoor Unit

A B C D E

3 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AA    AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA    AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA    

3.05 AJ024MCS4CH/AA MAX HEAT FREE JOINT MULTI CONDENSING UNIT

A. General:The AJ024MCS4CH/AA outdoor units shall be equipped with multiple circuit boards that interface (additional parts necessary) to the Samsung Control Network Solution (Control systems) and shall perform all functions necessary for operation. The outdoor unit shall have a powder coated finish. The outdoor unit shall be completely factory assembled, piped and wired. Each unit shall be run tested at the factory.

1. The sum of connected capacity of all indoor units shall not exceed the nominal capacity of the condensing unit.

2. Outdoor unit shall have a sound rating no higher than 58 dB3. The outdoor unit shall have a base pan heater to aid in defrost cycle water

drainage.4. All refrigerant lines from the outdoor unit to indoor units shall be insulated.5. The outdoor unit shall have an accumulator.6. The outdoor unit shall have a fuse, over-current protection and crank case heater.7. The outdoor unit shall have the ability to operate with a maximum height difference

of 49 feet. Maximum total system line set length shall not exceed 230 feet with a maximum individual line set length of 82 feet.

8. The outdoor unit shall be capable of operating in outside ambient temperatures between 14⁰F to 115⁰F in cooling mode without additional low ambient controls.

9. The outdoor unit shall be capable of operating in outside ambient temperatures between -13⁰F and 75⁰F in heating mode without additional low ambient controls.

10.The control circuit between the indoor units, and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

13

Page 14: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

B. Unit Cabinet:1. The chassis shall be fabricated of galvanized steel, bonderized and finished with a

powder coated baked enamel.

C. Fan:1. The outdoor unit shall be furnished with one direct drive, variable speed propeller

type fan. 2. All fan motors shall be BLDC type.3. The fan motor shall have inherent protection, have permanently lubricated

bearings, and be completely variable speed.4. The fan motor shall be mounted for quiet operation.5. The fan shall be provided with a raised guard to prevent contact with moving parts.6. The outdoor unit shall have horizontal discharge airflow.

D. Refrigerant1. The condensing unit shall require R410A refrigerant.2. The condensing unit comes charged for total system line set lengths up to 131 feet.

Additional refrigerant is required if the system line set length is over 131 feet. For every additional foot over 131, 0.22 ounces of refrigerant must also be added.

3. The condensing unit shall contain 4 EEV’s (electronic expansion valves) with 480 positions each to control refrigerant flow to each indoor unit independently.

E. Coil:1. The outdoor coil shall be of nonferrous construction with lanced or corrugated plate

fins on copper tubing.2. Aluminum coil fins shall be coated with a hydrophilic/protective coating to reduce

corrosion and promote moisture shedding.3. The coil shall be protected with an integral guard.4. Refrigerant flow from the outdoor unit shall be controlled by means of a capacity

modulation capable, inverter driven, twin BLDC rotary compressor.

F. Compressor:1. The compressor shall be an inverter driven, DC power, twin BLDC rotary

compressor made by Samsung.2. A crankcase heater shall be factory mounted on/in the compressor.3. The outdoor unit compressor shall have a variable modulation technology to

modulate capacity. The capacity shall be completely variable down to 7,500 Btu/h minimum capacity in cooling mode and 7,600 Btu/h in heating mode.

4. The compressor shall be equipped with an external thermal overload.5. The compressor shall be mounted to avoid the transmission of vibration.

G.Electrical:1. The outdoor unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. 2. The unit shall be capable of satisfactory operation within voltage limitations of 187-

228 volts (208V/60Hz) or 207-253 volts (230V/60Hz) with a maximum 30A overcurrent protection.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

14

Page 15: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

3. The outdoor unit shall be controlled by integral microprocessors.4. The control circuit between the indoor units and the outdoor unit shall be 0.5VDC -

7VDC completed using stranded, annealed copper conductor, 16 AWG, shielded, two-core cable to provide total integration of the system. The control wire shall be run from the condensing unit to each indoor unit independently.

5. The outdoor unit shall provide power to the indoor unit with 14 AWG X 3 power wire (2 X high voltage wires, 1 X ground). The power wire shall be run from the condensing unit to each indoor unit independently.

H. Connectable indoor units:1. AJ009JNLDCH/AA, AJ012JNLDCH/AA, AJ018JNLDCH/AA, AJ007JNADCH/AA,

AJ009JNADCH/AA, AJ012JNADCH/AA, AJ018JNADCH/AA, AJ009JNNDCH/AA, AJ012JNNDCH/AA, AJ018JNNDCH/AA

2. Connectable combinations:

Indoor Unit

A B C D E

2 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA      AJ007JN*DCH/AA AJ009JN*DCH/AA      AJ007JN*DCH/AA AJ012JN*DCH/AA      AJ007JN*DCH/AA AJ018JN*DCH/AA      AJ009JN*DCH/AA AJ009JN*DCH/AA      AJ009JN*DCH/AA AJ012JN*DCH/AA      AJ009JN*DCH/AA AJ018JN*DCH/AA      AJ012JN*DCH/AA AJ012JN*DCH/AA      AJ012JN*DCH/AA AJ018JN*DCH/AA      

Indoor Unit

A B C D E

3 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ018JN*DCH/AA    AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA    AJ007JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA    AJ007JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA    AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA    AJ009JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA    

Indoor Unit

A B C D E

4 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA  

3.06 AJ030MCS4CH/AA MAX HEAT FREE JOINT MULTI CONDENSING UNIT

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

15

Page 16: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

A. General:The AJ030MCS4CH/AA outdoor units shall be equipped with multiple circuit boards that interface (additional parts necessary) to the Samsung Control Network Solution (Control systems) and shall perform all functions necessary for operation. The outdoor unit shall have a powder coated finish. The outdoor unit shall be completely factory assembled, piped and wired. Each unit shall be run tested at the factory.

1. The sum of connected capacity of all indoor units shall not exceed the nominal capacity of the condensing unit.

2. Outdoor unit shall have a sound rating no higher than 58 dB.3. The outdoor unit shall have a base pan heater to aid in defrost cycle water

drainage.4. All refrigerant lines from the outdoor unit to indoor units shall be insulated.5. The outdoor unit shall have an accumulator.6. The outdoor unit shall have a fuse, over-current protection and crank case heater.7. The outdoor unit shall have the ability to operate with a maximum height difference

of 49 feet. Maximum total system line set length shall not exceed 230 feet with a maximum individual line set length of 82 feet.

8. The outdoor unit shall be capable of operating in outside ambient temperatures between 14⁰F to 115⁰F in cooling mode without additional low ambient controls.

9. The outdoor unit shall be capable of operating in outside ambient temperatures between -13⁰F and 75⁰F in heating mode without additional low ambient controls.

10.The control circuit between the indoor units, and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system.

B. Unit Cabinet:1. The chassis shall be fabricated of galvanized steel, bonderized and finished with a

powder coated baked enamel.

C. Fan:1. The outdoor unit shall be furnished with one direct drive, variable speed propeller

type fan. 2. All fan motors shall be BLDC type.3. The fan motor shall have inherent protection, have permanently lubricated

bearings, and be completely variable speed.4. The fan motor shall be mounted for quiet operation.5. The fan shall be provided with a raised guard to prevent contact with moving parts.6. The outdoor unit shall have horizontal discharge airflow.

D. Refrigerant1. The condensing unit shall require R410A refrigerant.2. The condensing unit comes charged for total system line set lengths up to 131 feet.

Additional refrigerant is required if the system line set length is over 131 feet. For every additional foot over 131, 0.22 ounces of refrigerant must also be added.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

16

Page 17: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

3. The condensing unit shall contain 4 EEV’s (electronic expansion valves) with 480 positions each to control refrigerant flow to each indoor unit independently.

E. Coil:1. The outdoor coil shall be of nonferrous construction with lanced or corrugated plate

fins on copper tubing.2. Aluminum coil fins shall be coated with a hydrophilic/protective coating to reduce

corrosion and promote moisture shedding.3. The coil shall be protected with an integral guard.4. Refrigerant flow from the outdoor unit shall be controlled by means of a capacity

modulation capable, inverter driven, twin BLDC rotary compressor.

F. Compressor:1. The compressor shall be an inverter driven, DC power, twin BLDC rotary

compressor made by Samsung.2. A crankcase heater shall be factory mounted on/in the compressor.3. The outdoor unit compressor shall have a variable modulation technology to

modulate capacity. The capacity shall be completely variable down to 7,500 Btu/h minimum capacity in cooling mode and 7,600 Btu/h in heating mode.

4. The compressor shall be equipped with an external thermal overload.5. The compressor shall be mounted to avoid the transmission of vibration.

G.Electrical:1. The outdoor unit electrical power shall be 208/230 volts, 1 phase, 60 hertz. 2. The unit shall be capable of satisfactory operation within voltage limitations of 187-

228 volts (208V/60Hz) or 207-253 volts (230V/60Hz) with a maximum 30A overcurrent protection.

3. The outdoor unit shall be controlled by integral microprocessors.4. The control circuit between the indoor units and the outdoor unit shall be 0.5VDC -

7VDC completed using stranded, annealed copper conductor, 16 AWG, shielded, two-core cable to provide total integration of the system. The control wire shall be run from the condensing unit to each indoor unit independently.

5. The outdoor unit shall provide power to the indoor unit with 14 AWG X 3 power wire (2 X high voltage wires, 1 X ground). The power wire shall be run from the condensing unit to each indoor unit independently.

H. Connectable indoor units:1. AJ009JNLDCH/AA, AJ012JNLDCH/AA, AJ018JNLDCH/AA, AJ007JNADCH/AA,

AJ009JNADCH/AA, AJ012JNADCH/AA, AJ018JNADCH/AA, AJ009JNNDCH/AA, AJ012JNNDCH/AA, AJ018JNNDCH/AA, AJ024JNADCH/AA

2. Connectable combinations:

Indoor Unit

A B C D E

2 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA      AJ007JN*DCH/AA AJ009JN*DCH/AA      AJ007JN*DCH/AA AJ012JN*DCH/AA      

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

17

Page 18: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

AJ007JN*DCH/AA AJ018JN*DCH/AA      AJ007JN*DCH/AA AJ024JN*DCH/AA      AJ009JN*DCH/AA AJ009JN*DCH/AA      AJ009JN*DCH/AA AJ012JN*DCH/AA      AJ009JN*DCH/AA AJ018JN*DCH/AA      AJ009JN*DCH/AA AJ024JN*DCH/AA      AJ012JN*DCH/AA AJ012JN*DCH/AA      AJ012JN*DCH/AA AJ018JN*DCH/AA      AJ012JN*DCH/AA AJ024JN*DCH/AA      AJ018JN*DCH/AA AJ018JN*DCH/AA      

Indoor Unit

A B C D E

3 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ018JN*DCH/AA    AJ007JN*DCH/AA AJ007JN*DCH/AA AJ024JN*DCH/AA    AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA    AJ007JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA    AJ007JN*DCH/AA AJ009JN*DCH/AA AJ018JN*DCH/AA    AJ007JN*DCH/AA AJ009JN*DCH/AA AJ024JN*DCH/AA    AJ007JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA    AJ007JN*DCH/AA AJ012JN*DCH/AA AJ018JN*DCH/AA    AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA    AJ009JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA    AJ009JN*DCH/AA AJ009JN*DCH/AA AJ018JN*DCH/AA    AJ009JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA    AJ009JN*DCH/AA AJ012JN*DCH/AA AJ018JN*DCH/AA    AJ012JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA    

Indoor Unit

A B C D E

4 Indoor Units

AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ007JN*DCH/AA AJ018JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA  AJ007JN*DCH/AA AJ007JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA  AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA  AJ007JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA  AJ007JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA AJ012JN*DCH/AA  AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA  AJ009JN*DCH/AA AJ009JN*DCH/AA AJ009JN*DCH/AA AJ012JN*DCH/AA  

3.07 AJ0**JNADCH/AA (WALL-MOUNTED) INDOOR UNITA. General:

The AJ0**JNADCH/AA shall be wall-mounted indoor unit section with a slim silhouette. The AJ0**JNADCH/AA shall support individual control using Samsung Control Network Solution (Control systems). Indoor model numbers shall be DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

18

Page 19: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

AJ007JNADCH/AA / AJ009JNADCH/AA / AJ012JNADCH/AA / AJ018JNADCH/AA / AJ024JNADCH/AA.

Each system shall perform in accordance to the ratings shown in the table below (nominal capacity).

Model Number Btu/hCooling*

BTU/hHeating**

AJ007JNADCH/AA 7,000 7,500AJ009JNADCH/AA 9,000 10,900AJ012JNADCH/AA 12,000 14,000AJ018JNADCH/AA 17,100 20,000AJ024JNADCH/AA 22,000 25,500

*Nominal cooling capacities are based on: Indoor temperature: 80⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F, 75⁰F WB.**Nominal heating capacities are based on: Indoor temperature: 70⁰F DB, 60⁰F WB. Outdoor temperature: 43⁰F.

B. Indoor Unit1. The indoor unit shall be factory assembled, wired and run tested. Contained within

the unit shall be all factory wiring, piping, control circuit board and fan motor. 2. An electronic modulating linear expansion valves is located inside the condensing

unit for refrigerant control. 3. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, and

an auto restart function. 4. Indoor unit and refrigerant pipes shall be charged with dehydrated nitrogen gas

before shipment from the factory. 5. The indoor unit shall have a night time sleep mode to reduce system noise and

provide optimal sleep conditions enabled with the wireless controller. 6. The indoor unit shall have a single event, ON/OFF timer setting enabled at the

wireless controller. 7. The indoor unit high voltage terminals shall have a thermal fuse to prevent

overheating due to loose connections of damaged components.

C. Unit Cabinet:1. The casing shall be UL94 V0 with a white finish.2. Multi directional drain and refrigerant piping offering four (4) directions for

refrigerant piping and four (4) directions for draining shall be standard.3. Drain hose shall be on the right-hand side of the drain pan (when facing the front)

as standard with optional left-hand side connection.4. There shall be a separate galvanized steel mounting plate which secures the unit

firmly to the wall.5. LED’s on front of unit shall provide unit operation and error status.6. The indoor unit shall have easy-access pipe and drain connections via access

panel on front of unit for easier installation and service allowing maintenance without pulling the unit out from the wall thus preventing property damage.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

19

Page 20: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

D. Fan:1. The indoor fan assembly shall be a cross-flow fan direct driven by a single motor.2. The indoor fan shall be statically and dynamically balanced to run on a motor with

permanently lubricated bearings.3. A manual adjustable guide vane shall provide the ability to change the airflow from

side to side (left to right).4. A motorized air sweep louver shall provide an automatic change in airflow by

directing the air up and down to provide uniform air distribution. 5. The motorized supply air louver shall be hinged from the top reducing restriction

and air noise.6. The indoor unit cabinet shall have a triangular shape allowing for a larger fan and

supply air outlet providing superior air throw at lower sound levels.7. The indoor fan shall consist of various speeds, as indicated in the table below.

Model Number Fan Speed SettingAJ007JNADCH/AAAJ009JNADCH/AAAJ012JNADCH/AAAJ018JNADCH/AAAJ024JNADCH/AA

(UL) - Low – Mid– High

E. Filter:1. Return air shall be filtered by means of an easily removable, electro-static,

washable filter.2. The indoor unit air filter shall be on top of the unit and accessible without opening

a panel or door providing simple access for the end-user. 3. Supplemental antibacterial and anti-odor filters are included.

F. Coil:1. The indoor coil shall be of nonferrous construction with Slit fins on copper tubing.2. The tubing shall have inner grooves for high efficiency heat exchange.3. Aluminum coil fins shall be coated with a hydrophilic/protective coating to reduce

corrosion and promote moisture shedding.4. All tube joints shall be brazed with phos-copper or silver alloy.5. The coils shall be pressure tested at the factory.6. A condensate pan and drain shall be provided under the coil.7. Both refrigerant lines to the indoor unit shall be insulated.

G. Electrical:1. The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz supplied from

the condensing unit.2. The system shall be capable of satisfactory operation within voltage limits of 187-

228 volts (208V/60Hz) or 207-253 volts (230V/60Hz)3. The indoor unit PCB contains a time-lag fuse.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

20

Page 21: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

4. The control circuit between the indoor units, and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system.

H. Controls:1. This unit shall use controls provided by Samsung Electronics to perform functions

necessary to operate the system. 2. This unit shall include a wireless controller and holder as standard.

3.08 AJ0**JNNDCH/AA (MINI 4-WAY CEILING CASSETTE WITH GRILLE) INDOOR UNITA. General:

The AJ0**JNNDCH/AA shall be a four-way cassette style indoor unit that recesses into the ceiling with a ceiling grille (part number: PC4SUSMB or PC4SUSMC, included when ordered as a system). The mini four-way cassette shall be compatible with Samsung FJM heat pump condensing units. The mini four-way cassette shall have an optional motion detection sensor (MCR-SMA) to enable/disable the unit based on motion with optional time delay settings. Refer to the controls section of this specification for more MCR-SMA details). The AJ0**JNNDCH/AA shall support individual control using Samsung Control Network Solution (Control systems). Indoor model numbers shall be AJ009JNNDCH/AA / AJ012JNNDCH/AA / AJ018JNNDCH/AA.

Each system shall perform in accordance to the ratings shown in the table below (nominal capacity).

System Model Number BTU/hCooling*

BTU/hHeating**

AJ009JNNDCH/AA 8,900 9,900AJ012JNNDCH/AA 11,900 13,000AJ018JNNDCH/AA 17,700 19,100

*Nominal cooling capacities are based on: Indoor temperature: 80⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F, 75⁰F WB.**Nominal heating capacities are based on: Indoor temperature: 70⁰F DB, 60⁰F WB. Outdoor temperature: 43⁰F.

B. Indoor Unit.The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, control circuit board and fan motor. An electronic modulating linear expansion valves is located inside the condensing unit for refrigerant control. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, an auto restart function. Indoor unit and refrigerant pipes shall be charged with dehydrated nitrogen gas before shipment from the factory.

C. Unit Cabinet:1. The cabinet shall be space-saving ceiling-recessed cassette.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

21

Page 22: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

2. The cabinet panel shall have provisions for a field installed filtered outside air intake. A booster fan is necessary. A 208/230V AC relay terminal is available to control the booster fan (max 1A).

3. Construction shall be insulated HIPS chassis with a galvanized steel frame and fascia panel certified to UL94 V0.

4. The compact cabinet size can be installed on one standard ceiling tile. (24” x 24”)5. The cabinet panel shall have provisions for a field installed, filtered, outside air

intake. A booster fan is necessary. A 12V DC relay terminal is available to control the booster fan (with separate PCB connector).

6. PC4SUSMB and PC4SUSMC panels shall have 4 auto-swing louvers and status LED’s to provide unit operation and error status.

7. PC4SUSMB and PC4SUSMC panels shall have an IR receiver for wireless controller use.

D. Fan:1. The indoor fan shall be an assembly with a turbo fan direct driven by a single

motor.2. The indoor fan shall be statically and dynamically balanced to run on a motor with

permanently lubricated bearings.3. The indoor fan shall consist of three (3) speeds, Low, Mid, and High.4. The auto air swing vanes shall be capable of automatically swinging up and down

for uniform air distribution. 5. The supply air vanes shall have independent control capability (32° – 65° control

range) adjustable with optional wireless or wired controllers.6. The cabinet shall have a fresh air intake opening to accommodate the introduction

of fresh air into the space.

E. Filter:1. Return air shall be filtered by means of a long-life, electro-static, pleated, washable,

permanent filter.

F. Coil:1. The indoor coil shall be of nonferrous construction with Slit fins on copper tubing.2. The tubing shall have inner grooves for high efficiency heat exchange.3. Aluminum coil fins shall be coated with a hydrophilic/protective coating to reduce

corrosion and promote moisture shedding.4. All tube joints shall be brazed with phos-copper or silver alloy.5. The coil fins are coated with hydrophilic paints.6. The coils shall be pressure tested at the factory.7. A condensate pan and drain shall be provided under the coil.8. The condensate lift mechanism shall be able to raise drain water 29 inches above

the condensate pan with float switch.9. Both refrigerant lines to the indoor unit shall be insulated.

G. Electrical:

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

22

Page 23: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

1. The unit electrical power shall be 208/230 volts, 1-phase, 60 hertz supplied from the outdoor.

2. The system shall be capable of satisfactory operation within voltage limits of 187-228 volts (208V/60Hz) or 207-253 volts (230V/60Hz).

3. The indoor unit PCB contains a time-lag fuse.4. The indoor unit shall have a thermal fuse under high-voltage terminal block to

disable unit in the event of overheating due to electrical malfunction/poor connection.

H. Controls:1. This unit shall use controls provided by Samsung Electronics to perform functions

necessary to operate the system. 2. The control circuit between the indoor units, and the outdoor unit shall be 0.5VDC -

7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system.

3. The indoor unit shall have a removable EEPROM on its PCB to store all unit data. All data on the indoor unit EEPROM shall be viewable from the manufacturer provided service software. The indoor unit main EEPROM shall be removable allowing replacement of indoor unit PCB without losing digital, field programmed data. The indoor unit removable EEPROM shall store the following unit data: unit model number, unit serial number, unit PCB firmware and MICOM version, and field programmed unit name/tag viewable on controls and service software.

3.09 AJ0**JNLDCH/AA (CEILING-CONCEALED DUCTED) INDOOR UNIT A. General:

The AJ0**JNLDCH/AA shall be a ceiling-concealed ducted indoor fan coil design that mounts above the ceiling with a 2-position, field adjustable return and a fixed horizontal discharge supply. The AJ0**JNLDCH/AA shall support individual control using Samsung Control Network Solution (Control systems). Indoor model numbers shall be AJ009JNLDCH/AA / AJ012JNLDCH/AA / AJ018JNLDCH/AA.

Each system shall perform in accordance to the ratings shown in the table below (nominal capacity).

System Model Number Btu/hCooling*

Btu/hHeating**

AJ009JNLDCH/AA 9,000 10,000AJ012JNLDCH/AA 12,000 13,000AJ018JNLDCH/AA 18,000 19,000

*Nominal cooling capacities are based on: Indoor temperature: 80⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F, 75⁰F WB.**Nominal heating capacities are based on: Indoor temperature: 70⁰F DB, 60⁰F WB. Outdoor temperature: 43⁰F.

B. Indoor Unit.The indoor unit shall be factory assembled, wired and run tested. Contained within the unit shall be all factory wiring, piping, control circuit board and fan motor. An electronic modulating linear expansion valves is located inside the condensing unit for refrigerant DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

23

Page 24: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

control. The unit shall have a self-diagnostic function, 3-minute time delay mechanism, and an auto restart function. Indoor unit and refrigerant pipes shall be charged with dehydrated nitrogen gas before shipment from the factory.

C. Unit Cabinet:1. The unit shall be space saving, ceiling-concealed, ducted.2. The cabinet shall be constructed of galvanized steel and insulated.

D. Fan:1. The indoor unit fan shall be an assembly with two or three Sirocco fans direct

driven by a single motor.2. The indoor fan shall be statically and dynamically balanced and run on a motor with

permanently lubricated bearings.3. The indoor fan shall consist of various speeds, as indicated in the table below.

Model Number Fan Speed SettingAJ009JNLDCH/AA AJ012JNLDCH/AA AJ018JNLDCH/AA

Low – Mid – High

4. The indoor unit shall have a ducted air outlet system and ducted return air system.5. Standard external static pressure is 0.08” WC (min. 0”, max. 0.16”WC) 6. The fan speed shall be adjustable by optional remote controller according to

external static pressure.

E. Filter:1. Return air shall be filtered by means of a standard factory installed return air filter

on rear of unit.2. Optional return connection through rear or bottom of unit with removal and

replacement of return air conversion plate. Other filtration is field provided.

F. Coil:1. The indoor coil shall be of nonferrous construction with Slit fins on copper tubing.2. The tubing shall have inner grooves for high efficiency heat exchange.3. Aluminum coil fins shall be coated with a hydrophilic/protective coating to reduce

corrosion and promote moisture shedding.4. All tube joints shall be brazed with phos-copper or silver alloy.5. The coils shall be pressure tested at the factory.6. A condensate pan and drain shall be provided under the coil.7. Both refrigerant lines to the indoor unit shall be insulated.

G. Electrical:1. The unit electrical power shall be 208/230 volts, 1 phase, 60 hertz supplied by

outdoor unit.2. The system shall be capable of satisfactory operation within voltage limits of 187-

228 volts (208V/60Hz) or 207-253 volts (230V/60Hz).

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

24

Page 25: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

3. The indoor unit PCB contains a time-lag fuse.H. Controls:

1. The control circuit between the indoor units and the outdoor unit shall be 0.5VDC - 7VDC completed using stranded, annealed copper conductor, two-core, 16 AWG, shielded cable to provide total integration of the system.

2. Wired ControllerA. The AJ0**JNLDCH/AA units include a Standard Wired Controller (MWR-

WH02) as standard.B. This unit shall use controls provided by Samsung Electronics to perform

functions necessary to operate the system.

Part 4 – Samsung Control Network Solutions (Control System)

4.01 PREMIUM WIRED CONTROLLER (MWR-WE10)A. Connection: Can control up to 16 Samsung indoor units (defined and controlled as

one group). Sub-PCB shall install inside the indoor unit.B. Dimensions: 4 5/8” x 4 7/8” in size and white in color C. Easy indoor unit control

1. Indoor unit operation ON/OFF2. Indoor unit operation mode, set temperature, air flow direction, fan speed3. Quiet and sleep modes 4. Error display5. Filter replacement alarm display and reset6. Single indoor unit control or multiple unit control (maximum 16 units)7. Upper/lower temperature setting8. Automatic operation stop function9. Daily/weekly operating schedule setting

Premium Wired ControllerItem Description Operation Display

ON/OFF Run and stop operation for a single group Each Group Each GroupOperation Mode Switches between Auto/Cool/Dry/ Fan/Heat Each Group Each Group

Temperature Setting

Set the temperature for a single group. Range of temperature setting

o Auto/Cool/Dry: 65°F-86°Fo Heat: 61°F-86°F

Each Group Each Group

Fan Speed Setting Models with 3 air flow speed settings: o High /Mid/Low/Auto Each Group Each Group

Air Flow Direction Setting

Air flow 2-step direction (Swing/Stop) Direct setting at a specific angle. Air flow operation varies depending on the model.

Each Group Each Group

Weekly Schedule

ON/OFF, temperature, fan speed, and mode settings can be specified

Maximum 6 schedules may be set for each day. Real-time clock function: current time, day display

function

Each Group Each Group

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

25

Page 26: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

Premium Wired ControllerItem Description Operation Display

Button lock

Button permission level setting (On/Off / Temperature setting / Mode button / Fan speed)

Temperature limit setting After power reset, setting value is restored Various restriction capabilities

Each Group Each Group

Specified Function Automatic stop setting o Setting time range : 0-12 hours Each Group Each Group

Service Mode

Setting/Viewing indoor unit option code Viewing indoor unit RMC address Viewing indoor unit cycle data Setting/Viewing temperature sensor compensation

of the wired remote controller (-9°~ +9°) Viewing the RPM compensation Viewing the filter time (1,000 hours or 2,000 hours) Viewing indoor unit temperature sensor

compensation under Heating (+2 or +5°) Viewing the H/W option setting Viewing the wired remote controller software

version

Each Group Each Group

Error When an error is currently occurring on an air

conditioner unit, the afflicted unit and the error code are displayed

Each Group Each Group

Permit / Prohibit Local Operation

Setting/releasing of simplified locking for remote control buttons can be performed Each Group N/A

Quiet Mode Select the Quiet mode to run the indoor unit to the set mode to lower the fan noise level. Each Group N/A

Room Temperature

Actual room temperature display (or set temperature display) Each Group Each Group

D. Other Premium Controller features1. Different button permission levels2. Partial button lock option (on/off, selection, temperature setting, fan speed, and

schedule setting buttons can be locked individually)3. Backlight4. Daylight savings clock advance option5. Temperature limit setting option6. Real-time clock function; current time/day display function7. Built-in room temperature sensor8. Indoor unit operation state display9. Service mode support (indoor unit cycle data monitoring, option code monitoring

and setting, and dip switch state monitoring)

E. Specifications1. 4 wire connection2. DC 12V (V1/V2) power supplied by indoor unit3. RS485 communication (F3/F4)

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

26

Page 27: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

4. Can sense temperature via internal sensor, temperature sensor inside the air handler, or use the average temperature between controller and air indoor unit sensors

5. The Premium Controller shall require no addressing. 6. The Premium Controller shall connect using four-wire (2 wires for power supply

and the other two for communication), untwisted, shielded. The Premium Controller shall require cross-over wiring for grouping across indoor units.

7. 16AWG shielded cable is necessary for proper operation8. Connection to wall AJ0**JNADCH/AA wall units will require sub-PCB (DB93-

11412A) for wired controller connection.

4.02 STANDARD CONTROLLER (MWR-WH02)A. Connection: The Standard Controller shall be capable of controlling up to 16 indoor

units (defined as 1 group). The sub-PCB shall install inside the indoor unit.B. Dimensions: 4.8” x 4.7” in size and white in color with a light-white LCD display. C. Easy indoor unit control

1. Indoor unit operation ON/OFF2. Indoor unit operation mode, set temperature, air flow direction, fan speed3. Error display4. Filter replacement alarm display and reset5. Single indoor unit control or multiple unit control (maximum 16 units)6. Upper/lower temperature setting7. Automatic operation stop function

Standard Wired ControllerItem Description Operation Display

ON/OFF Run and stop operation for a single group Each Group Each GroupOperation Mode Switches between Auto/Cool/Dry/Fan/Heat Each Group Each Group

Temperature Setting

Sets the temperature for a single group. Range of temperature setting

o Auto/Cool/Dry: 65°F-86°Fo Heat: 61°F-86°F

Each Group Each Group

Fan Speed Setting High /Mid/Low/Auto Each Group Each Group

Air Flow Direction Setting

Air flow 2-step direction (Swing/Stop) Direct setting at a specific angle. Air flow operation varies depending on the

model.

Each Group Each Group

Button lock

Button permission level setting (On/Off / Temperature setting / Mode button / Fan speed)

Temperature limit setting After power reset, the setting value is restored

Each Group Each Group

Specified Function Automatic stop setting Each Group Each Group

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

27

Page 28: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

Standard Wired ControllerItem Description Operation Display

o Setting time range : 0-12 hours

Service Mode

Setting/Viewing indoor unit option code Viewing indoor unit RMC address Viewing indoor unit cycle data Setting/Viewing temperature sensor

compensation of the wired remote controller(-9° ~ +9°)

Viewing the RPM compensation Viewing the filter time (1,000 hours or 2,000

hours) Viewing indoor unit temperature sensor

compensation under Heating (+2 or +5°) Viewing the H/W option setting

Each Group Each Group

Error When an error is currently occurring on an air

conditioner unit, the afflicted unit and the error code are displayed

Each Group Each Group

Permit / Prohibit Local Operation

Setting/releasing of simplified locking for remote control buttons can be performed Each Group N/A

Quiet Mode Select the Quiet mode to run the indoor unit to the set mode to lower the fan noise level. Each Group N/A

Room Temperature Displays set temperature. Room temperature is viewable when room

temperature button is pressedEach Group Each Group

D. Other Standard Controller features1. Different button permission levels2. Temperature limit setting option3. Built-in room temperature sensor4. Indoor unit operation state display5. Service mode support (indoor unit cycle data monitoring, option code monitoring

and setting, and dip switch state monitoring)E. Specifications

1. 4 wire connection2. DC 12V (V1/V2) power supplied by indoor unit3. RS485 communication (F3/F4)4. Can sense temperature via internal sensor, temperature sensor inside the air

handler, or use the average temperature between controller and air indoor unit sensors

5. The Standard Controller shall require no addressing. The Standard Controller shall connect using four-wire (2 wires for power supply and the other two for communication), untwisted, shielded control wire to the connection terminal on the indoor unit. The Standard Controller shall require cross-over wiring for grouping across indoor units.

6. The Standard Controller wired controller shall include interconnect cable as standard (32’).

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

28

Page 29: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

7. Connection to wall AJ0**JNADCH/AA wall units will require sub-PCB (DB93-11412A) for wired controller connection.

4.03 EXTERNAL REMOTE ROOM SENSOR (MRW-TA)A. Connection

The external remote room sensor shall be capable of connection up to 1 indoor unit.

B. Function1. The external remote room sensor shall be used to measure the exact room

temperature. 2. The external remote room sensor shall support wire length of maximum 39 feet.

4.04 WI-FI ADAPTER (MIM-H03U and MIM-H03U-KIT)

A. Function:1. The Wi-Fi adapter shall allow remote control of Samsung FJM indoor units

(AJ0***N***/AA) from a mobile device (Android or iOS) with manufacturer provided mobile app.

2. The Wi-Fi adapter shall control/monitor indoor unit: power status, mode, set temperature, room temperature, fan speed, and supply air louver position.

3. The Wi-Fi adapter shall provide 7 Day scheduling for a single unit or multiple indoor units.

4. The Wi-Fi adapter shall allow group configuration option for simple control of multiple units at the same time

5. Requires a local Wi-Fi router with DHCP enabled and an internet connection.6. The MIM-H03U-KIT shall include DB93-11412A (sub PCB) and DB93-11405A (wire

harness for connection to AJ0**JNADCH/AA wall mount units.

B. Connection:1. The Wi-Fi adapter power supply shall be 12VDC provided by an indoor unit.2. One Wi-Fi adapter shall provide monitoring and control of up to 5 indoor units on a

single system.3. The Wi-Fi adapter must be installed indoors.

4.05 MOTION DETECTOR (MCR-SMA)A. Function:

1. The motion detector shall connect to SAMSUNG FJM Mini 4-Way cassette models AJ0**JNNDCH/AA.

2. The motion detector shall monitor occupancy and turn off indoor unit after motion is not sensed for the specified duration (30, 60, 120, and 180 minutes).

3. The motion detector shall monitor occupancy and adjust target evaporator temperature after motion is not sensed for the specified duration (30, 60, 120, and 180 minutes) thus lowering capacity of unit to reduce energy use.

B. Connection:1. The motion detector shall install in the corner of the mini 4-way cassette fascia

panel.DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

29

Page 30: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

2. The motion detector shall connect to the indoor unit PCB with provided cable.

4.06 EXTERNAL CONTACT CONTROL – INDIVIDUAL UNIT ON/OFF CONTROL AND MONITORING (MIM-B14)

A. Function1. Control options to enable/disable and monitor individual indoor units2. Direct indoor unit control by external contact, 0 volts signal3. Emergency control with simple contact input4. Indoor unit operation (thermo or operation)/error state output through relay contacts

(5VDC)B. Installation location: inside indoor unit

C. Connection to indoor units with included wire harnesses

4.07 MIM-B13D – INTERFACE MODULEA. Communication device that interfaces indoor and outdoor units with DVM Plus central

control systemsB. Used to communicate with DMS (MIM-D00), DMS 2 (MIM-D00A), Centralized

Controller (MCM-A202D), and S-NET Mini (MST-S3W).C. 1 X MIM-B13D for each Free Joint Multi systemD. Specifications

1. Single power source - DC 12V from outdoor unit with supplied connection wire 2. RS485 communication (F1/F2) to outdoor unit with supplied connection wire3. RS485 communication (R1/R2) to Centralized Controller (MCM-A202B), DMS2

(MIM-D00A), S-NET Mini (MST-S3W).4. Mounts in outdoor unit with included wire ties and mounting case

4.08 MIM-N01 – INTERFACE MODULEA. Specifications

1. Allows connection of DVM Plus III and Samsung single zone CAC and multi-zone split systems to DVM S system NASA communication protocol central control options: MIM-D00AN (Data Management Server 2), MIM-D01AUN (Data Management Server 2.5), MIM-B17N (BACnet gateway), MIM-B17BUN (BACnet gateway), MIM-B18BUN (LONWORKS gateway), MIM-B18N (LONWORKS gateway), MCM-A202DN (ON/OFF controller), MCM-A300N (touchscreen controller).

2. 12VDC3. One per system

B. Connection1. Installs at outdoor unit2. Includes connection wires and installation box for simple installation.

Part 5 – Optional Accessories

5.01 WIND BAFFLES

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.

30

Page 31: HVAC Guide Specifications - · Web viewSAMSUNG FREE JOINT MULTI (FJM) HVAC Guide Specifications MOST CURRENT VERSION AVAILABLE AT: Multi-unit heat pump systems with 2 to 5 indoor units

SAMSUNG Electronics HVAC

A. Front wind baffle (WBF)1. WBF-4M wind shield/baffle is compatible with: AJ020JCJ2CH/AA and

AJ024JCJ3CH/AA outdoor units.2. WBF-2M wind shield/baffle is compatible with: AJ020MCS3CH/AA,

AJ024MCS4CH/AA, AJ030MCS4CH/AA, AJ036JCJ5CH/AA outdoor units.3. Designed to be placed on fan discharge side (front).4. Only a front shield is required for applications where the mini split is adjacent to a

structure that would protect the intake side from prevailing wind. Applications without this protection would require a back shield (ex: roof top).

5. The wind baffle material shall be powder coated, galvanized steel.

B. Back wind baffle (WBB)1. WBB-1M wind shield/baffle is compatible with: AJ020JCJ2CH/AA and

AJ024JCJ3CH/AA outdoor units.2. WBB-3M wind shield/baffle is compatible with: AJ020MCS3CH/AA,

AJ024MCS4CH/AA, AJ030MCS4CH/AA, AJ036JCJ5CH/AA outdoor units. 3. Designed to be placed on the coil intake side of the unit (back).4. Note: This back shield is only required for applications where the mini split is not

adjacent to a structure that would protect the intake side from prevailing wind (ex: roof top).

5. The wind baffle material shall be powder coated, galvanized steel.

DRAFT: 01/17/2018 www.SamsungHVAC.comSpecifications are subject to change without notice.