DocAnclaje Esr1056
-
Upload
cesar-ceron -
Category
Documents
-
view
214 -
download
0
description
Transcript of DocAnclaje Esr1056
ICC Evaluation Service, Inc.www.icc-es.org
Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543Regional Office # 900 Montclair Road, Suite A, Birmingham, Alabama 35213 # (205) 599-9800Regional Office # 4051 West Flossmoor Road, Country Club Hills, Illinois 60478 # (708) 799-2305
ESR-1056*Reissued December 1, 2004
This report is subject to re-examination in two years.
*Corrected October 2005
Copyright © 2005 Page 1 of 11
are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an
endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, Inc., express or implied, as to any
finding or other matter in this report, or as to any product covered by the report.
DIVISION: 03—CONCRETESection: 03151—Concrete Anchoring
DIVISION: 04—MASONRYSection: 04081—Masonry Anchorage
REPORT HOLDER:
SIMPSON STRONG-TIE COMPANY, INC.4120 DUBLIN BOULEVARD, SUITE 400DUBLIN, CALIFORNIA 94568(925) 560-9000www.simpsonanchors.com
EVALUATION SUBJECT:
TITEN HD SCREW ANCHORS
1.0 EVALUATION SCOPE
Compliance with the following codes:
# 2000 International Building Code® (IBC).
# 2000 International Residential Code® (IRC).
# 1997 Uniform Building Code™ (UBC).
Properties evaluated:
Structural
2.0 USES
The Titen HD screw anchor is for installation in predrilledholes in normal-weight concrete, structural sand-lightweightconcrete on metal deck, and fully grouted concrete masonrywall construction.
The Titen HD screw anchor is an alternative to cast-in-placeanchors described in IBC Section 1912 and UBC Section1923.1. The anchors are permitted to be used in structuresregulated by the IRC, provided an engineered design issubmitted in accordance with IRC Section R301.1.2.
3.0 DESCRIPTION
3.1 Materials:
3.1.1 Titen HD Screw Anchor: The Titen HD screw anchoris a carbon steel threaded anchor with a hex-washer head.The screw anchor is manufactured from heat-treated steelcomplying with SAE J403 Grade 10B21, and has either anelectrodeposited coating of zinc in accordance with ASTM B633, Service Condition SC1, Type III; or a mechanicallydeposited coating of zinc in accordance with ASTM B 695,Class 65, Type I.
Titen HD screw anchors are available with nominally 3/8-,1/2-,
5/8-, and 3/4-inch (9.5, 12.7, 15.9 and 19.1 mm) shank
diameters, and with various lengths for multiple embedmentsas noted in the tables in this report. Refer to Figure 1 for anillustration of a typical screw anchor.
3.1.2 Normal-weight Concrete: Concrete shall be stone-aggregate normal-weight concrete having a minimumcompressive strength as noted in the tables in this report atthe time of anchor installation. Minimum concrete thicknessis 11/2 times the anchor embedment at the location of anchorinstallation.
3.1.3 Structural Sand-lightweight Concrete-fill Metal-deck Assembly:
3.1.3.1 Metal Deck: The metal deck shall be minimum No.20 gage [0.035 inch (0.889 mm) base-metal thickness]galvanized steel conforming to ASTM A 653/A 653M, with aminimum yield strength of 38 ksi (261.8 MPa) and a minimumultimate strength of 45 ksi (310 MPa). Figure 2 illustratesrequired metal-deck bottom-flute dimensions: a minimum of41/2 inches (114 mm) wide, a maximum of 3 inches (76 mm)deep, and with a minimum spacing of 12 inches (305 mm).Metal decks having greater bottom flute widths and relativespacings shall be permitted.
3.1.3.2 Concrete Fill: The structural sand-lightweightconcrete shall have a minimum 3,000 psi (20.7 MPa)compressive strength at time of anchor installation.Aggregates for structural sand-lightweight concrete shallcomply with Section 3.3 of ACI 318-95. Minimum concretethickness measured from the top flute is 31/4 inches (83 mm).Refer to Figure 2.
3.1.4 Grout-filled Concrete Masonry: When prism testsare required, the compressive strength of masonry, fNm, at 28days shall be a minimum of 1,500 psi (10.3 MPa). Fullygrouted masonry walls shall be constructed from the followingmaterials:
3.1.4.1 Concrete Masonry Units (CMUs): CMUs shall beminimum Grade N, Type II, lightweight, medium-weight, ornormal-weight conforming to ASTM C 90 or UBC Standard21-4. The minimum allowable nominal size of the CMU shallbe 8 inches (203 mm) wide by 8 inches (203 mm) high by 16inches (406 mm) long (i.e., 8×8×16).
3.1.4.2 Grout: Grout shall comply with IBC Section 2103.10,IRC Section R609.1.1, or UBC Section 2103.4, as applicable.Alternatively, the grout shall have a minimum compressivestrength when tested in accordance with ASTM C 1019-98aequal to its specified strength, but not less than 2,000 psi(13.8 MPa).
3.1.4.3 Mortar: Mortar shall comply with IBC Section2103.7, IRC Section R607, or UBC Section 2103.3 and UBCStandard 21-15, as applicable. The mortar shall have aminimum compressive strength of 1,500 psi (10.3 MPa).
3.2 Design:
Page 2 of 11 ESR-1056
3.2.1 General: Anchors described in this report areassigned allowable tension and shear loads for designsbased on allowable stress design (working stress design).Use of the anchors to resist vibratory and moving loads, suchas those produced by reciprocating engines, cranes andvehicles, is beyond the scope of this report.
3.2.2 Design of Anchors in Normal-weight Concrete:Allowable tension and shear loads for installation in normal-weight concrete are noted in Tables 3 through 6. Spacing andedge distance requirements are noted in Tables 1 through 6.Allowable load reduction factors noted in Table 2 areapplicable only to the allowable loads shown in Tables 3 and4.
For installations in normal-weight concrete, anchors arerecognized to resist dead-, live-, wind-, and earthquake-loadapplications. Allowable loads may be increased by 331/3
percent when using the alternate basic load combinations inaccordance with Section 1605.3.2 of the IBC or Section1612.3.2 of the UBC, for wind or earthquake loadingconditions. Alternatively, the load combinations in IBC Section1605.3.2 may be multiplied by a factor of 0.75.
Allowable loads for anchors installed in normal-weightconcrete subjected to combined shear and tension forcesshall be determined by the following equation:
# 1.0PsPt
VsVt
⎛
⎝⎜
⎞
⎠⎟ +
⎛
⎝⎜
⎞
⎠⎟
5/3 5/3
where:
Ps = Applied service tension load.
Pt = Allowable service tension load.
Vs = Applied service shear load.
Vt = Allowable service shear load.
3.2.3 Design of Anchors Installed in the Top or Bottomof Structural Sand-lightweight Concrete Filled Metal-deckAssemblies: Allowable tension and shear loads, and spacingand edge distance requirements, for anchors installed in thetop or bottom of structural sand-lightweight concrete filledmetal-deck assemblies are noted in Table 7. Refer to Figure2 for required assembly details.
Anchors installed in the top of structural sand-lightweightconcrete and metal-deck assemblies may resist wind orearthquake loads. Allowable tension and shear loads may beincreased by 331/3 percent when using the alternate basicload combinations in accordance with Section 1605.3.2 of theIBC or Section 1612.3.2 of the UBC, for wind or earthquakeloading conditions. Alternatively, the load combinations in IBCSection 1605.3.2 may be multiplied by a factor of 0.75.
Anchors installed in the bottom of structural sand-lightweight concrete and metal-deck assemblies may resistwind or earthquake loads:
Allowable tension loads for bottom deck installations maybe increased by 331/3 percent when using the alternate basicload combinations in accordance with Section 1605.3.2 of theIBC or Section 1612.3.2 of the UBC, for wind or earthquakeloading conditions. Alternatively, the load combinations in IBCSection 1605.3.2 may be multiplied by a factor of 0.75.
Allowable shear loads for bottom deck installations shall notbe increased when using the alternate basic loadcombinations in accordance with Section 1605.3.2 of the IBCor Section 1612.3.2 of the UBC, for wind or earthquakeloading conditions.
Allowable loads for anchors installed into the top or bottomof structural sand-lightweight concrete filled metal-deck
assemblies subjected to combined shear and tension forcesshall be determined by the following equation:
# 1.0PsPt
VsVt
⎛
⎝⎜
⎞
⎠⎟ +
⎛
⎝⎜
⎞
⎠⎟
where:
Ps = Applied service tension load.
Pt = Allowable service tension load.
Vs = Applied service shear load.
Vt = Allowable service shear load.
3.2.4 Design of Anchors Installed in Fully Grouted CMUMasonry Walls: Allowable tension and shear loads foranchors installed in the face of fully grouted CMU masonrywalls are noted in Table 8A for structures complying with theIBC or IRC, and Table 8B for structures complying with theUBC. The allowable tension and shear loads are for anchorsinstalled in the grouted cells, the center web of CMU units,and horizontal mortared bed joints of fully grouted CMUmasonry wall construction. Allowable loads for anchorsinstalled in the vertical head joint or the end flanges of theCMU units are outside the scope of this report. Edge and enddistances, and spacing requirements for anchors installed inthe face of fully grouted CMU masonry walls, as shown inFigure 3, are noted in Tables 8A and 8B. Allowable loadreduction factors for anchors installed at reduced edge andend distances, and reduced spacing, are noted in Tables 9and 10.
Allowable tension and shear loads for 1/2-inch and 5/8-inch(12.7 mm and 15.9 mm) anchors installed in the top of fullygrouted concrete masonry walls (CMU grouted cores andCMU webs), are noted in Table 11A for anchors installed instructures complying with the IBC or IRC, and Table 11B foranchors installed in structures complying with the UBC.
When using the alternate basic load combinations in IBCSection 1605.3.2 or UBC Section 1612.3.2 that include windor earthquake loads, the allowable shear and tension loadsfor anchors installed in the face and the top in fully groutedCMU masonry walls may be increased by 331/3 percent.Alternatively, the load combinations in IBC Section 1605.3.2may be multiplied by a factor of 0.75.
Allowable loads for anchors installed in the face of fullygrouted CMU masonry walls subjected to combined shearand tension forces shall be determined by the followingequation:
# 1.0PsPt
VsVt
⎛
⎝⎜
⎞
⎠⎟ +
⎛
⎝⎜
⎞
⎠⎟
where:
Ps = Applied service tension load.
Pt = Allowable service tension load.
Vs = Applied service shear load.
Vt = Allowable service shear load.
4.0 INSTALLATION
4.1 General:
Titen HD screw anchors shall be installed by drilling a pilothole into the substrate using a handheld electro-pneumaticrotary hammer drill with a carbide-tipped drill bit conformingto ANSI B212.15-1994. The pilot hole shall have the samediameter as the nominal diameter of the anchor. The hole isdrilled to the specified embedment depth plus 1/2 inch (12.7mm). Dust and debris in the hole shall be removed by using
Page 3 of 11 ESR-1056
oil-free compressed air. The Titen HD screw anchor shall beinstalled into the hole to the required embedment using asocket wrench or powered impact wrench.
4.1.1 Anchors Installed in Fully Grouted CMU MasonryWalls: Anchors installed in the face of fully grouted CMU wallconstruction shall be limited to the face shell of the CMU unit(center web and grouted cores) and the horizontal mortaredbed joints, as indicated by the shaded areas in Figure 3.Anchors installed in a T-joint, the mortared head joint, or theend webs of a CMU unit, as indicated in the non-shadedareas in Figure 3, are outside the scope of this report.
For anchors installed in the top of fully grouted concretemasonry walls (CMU grouted cores and CMU webs), anchorlocation shall comply with the minimum edge and enddistances noted in Tables 11A and 11B and shown in Figure4. Anchors installed in the mortared head joint are outside thescope of this report
4.2 Installation with Special Inspection (WhenRequired):
Continuous special inspection shall be provided whenrequired by the tables in this evaluation report. Specialinspection under the IBC and IRC shall conform to IBCSection 1704; under the UBC, special inspection shall be inaccordance with UBC Section 1701.
For fasteners installed with special inspection, the followingitems, as applicable, shall be inspected: fastener type anddimensions; concrete type and concrete compressivestrength (for anchors installed in concrete); masonry unit typeand compliance with ASTM C 90; grout and mortarcompressive strengths, and (when required) masonry prismcompressive strength; drill bit size and compliance with ANSIB212.15-1994; and fastener embedment, spacing, and edge(and end) distances. The special inspector shall inspect andverify that anchor installation complies with this evaluationreport and Simpson Strong-Tie Company’s publishedinstallation instructions.
5.0 CONDITIONS OF USE
The Titen HD Screw Anchors described in this report complywith, or are suitable alternatives to what is specified in, thecodes listed in Section 1.0 of this report, subject to thefollowing conditions:
5.1 Anchors are identified and installed in accordance withthis report and the manufacturer’s published installationinstructions.
5.2 Anchors installed in normal-weight concrete to resistdead, live, wind and earthquake load applications shallbe in accordance with Section 3.2.2.
5.3 Anchors installed into the top or bottom of structuralsand-lightweight concrete filled metal-deck assembliesto resist dead, live, wind and earthquake loadapplications shall be in accordance with Section 3.2.3.
5.4 Anchors installed in the face or the top of fully groutedCMU masonry walls to resist dead, live, wind, andearthquake load applications shall be in accordancewith Section 3.2.4.
5.5 Since an ICC-ES acceptance criteria for evaluating datato determine the performance of anchors subjected tofatigue or shock loading is unavailable at this time, theuse of these anchors under these conditions is beyondthe scope of this report.
5.6 Anchors are not permitted for use in conjunction withfire-resistive construction. Exceptions would be:
• Anchors resist wind or seismic loading only.
• For other than wind or seismic loading, specialconsideration is given to fire exposure conditions.
5.7 Since an ICC-ES acceptance criteria for evaluating theperformance of screw anchors in cracked concrete isunavailable at this time, the use of anchors is limited toinstallation in uncracked concrete. Cracking occurswhen ft > fr due to service loads or deformations.
5.8 Anchors are installed in substrates in holes predrilledwith carbide-tipped masonry drill bits complying withANSI B212.15-1994, and having the same diameter asthe nominal diameter of the anchor.
5.9 Calculations demonstrating that the applied loads areless than the allowable loads described in this report,shall be submitted to the building official. Thecalculations shall be prepared by a registered designprofessional where required by the statues of thejurisdiction in which the project is to be constructed.
5.10 Special inspection, when required, shall be provided inaccordance with Section 4.2.
5.11 Anchors shall be limited to dry, interior use.
5.12 The Titen HD screw anchors are manufactured bySimpson Strong-Tie Company at a facility in Brampton,Ontario, Canada, under a quality control program withinspections by CEL Consulting (AA-639).
6.0 EVIDENCE SUBMITTED
6.1 Data in accordance with the ICC-ES AcceptanceCriteria for Predrilled Fasteners (Screw Anchors) inConcrete and Masonry (AC106), dated November 1,2003, including the following optional tests:
6.1.1 Anchors installed in normal-weight concrete: Effects ofedge distance on tension and shear performance(Test Series 4, 5, 6, 7, 13, 14, 15, and 16 of AC106);effects of spacing on tension and shear performance(Test Series 9 and 18 of AC106); oblique load tests(Test Series 19 and 20 of AC106); and seismicperformance tests (Section 4.6 of AC106).
6.1.2 Anchors installed in the top and bottom of structuralsand-lightweight concrete and metal-deck assemblies:Effects of edge distance on tension and shearperformance (Test Series 4 and 13 of AC106), andseismic performance tests (Section 4.6 of AC106).
6.1.3 Anchors installed in the face of fully grouted CMUmasonry wall construction: Effects of edge distance ontension and shear performance (Test Series 4, 5, 13,and 14 of AC106), and seismic performance tests(Section 4.6 of AC106).
6.1.4 Anchors installed in the top of fully grouted CMUmasonry wall construction with a minimum 13/4-inch(44 mm) edge distance: Effects on tension and shearperformance (Test Series 4 and 13 of AC106), andseismic performance tests (Section 4.6 of AC106).
6.2 A quality control manual.
7.0 IDENTIFICATION
Titen HD screw anchor packaging is marked with theSimpson Strong-Tie Company name; product name (TitenHD); anchor diameter and length; the name or logo of theinspection agency (CEL Consulting); and the evaluationreport number (ESR-1056). In addition, the ≠ symbol andanchor length (in inches) is stamped on the head of eachscrew anchor.
Page 4 of 11 ESR-1056
FIGURE 1—TYPICAL TITEN HD SCREW ANCHOR
TABLE 1—SPACING AND EDGE DISTANCE REQUIREMENTS FOR TITEN HD SCREW ANCHORS(Anchors Installed in Normal-weight Concrete)1,2
ANCHORDIAMETER
(inch)
MINIMUMEMBEDMENT
DEPTH, hv
(inches)
EDGE DISTANCE(inches)
SPACING(inches)
Tension Shear Tension or Shear Tension or Shear
Critical EdgeDistance, Ccr
Critical EdgeDistance, Ccr
Minimum EdgeDistance, Cmin
Critical Spacing,Scr
MinimumSpacing, Smin
3/8
23/4 3 41/2 13/4 6 11/233/4
1/2
23/4
4 6 13/4 8 235/8
53/4
5/8
23/4
5 71/2 13/4 10 21/241/8
53/4
3/4
23/4
6 9 13/4 12 345/8
53/4
For SI: 1 inch = 25.4 mm.
1The spacing and edge distance requirements in this table are applicable only to Tables 3 and 4.2The critical edge and spacing distances are for full anchor capacity, and the minimum edge and spacing distances are for reduced anchorcapacity. See Table 2 for applicable load reduction factors for anchors installed at distances less than the critical edge distance or less than criticalspacing.
TABLE 2—LOAD REDUCTION FACTORS FOR TITEN HD SCREW ANCHORS(Anchors Installed in Normal-weight Concrete)1,2,3,4
ANCHORDIAMETER
(inch)
MINIMUMEMBEDMENT
DEPTH, hv
(inches)
EDGE DISTANCE (inches) SPACING (inches)
Tension orShear
Tension Shear Tension orShear
Tension Shear
Critical EdgeDistance, Ccr
Minimum EdgeDistance, Cmin
Minimum EdgeDistance, Cmin
CriticalSpacing, Scr
MinimumSpacing, Smin
MinimumSpacing, Smin
3/8
23/4 1.00.83 0.25
1.00.66 0.77
33/4 0.73 0.24 0.56 0.77
1/2
23/4
1.0
0.67 0.25
1.0
0.72 0.77
35/8 0.57 0.20 0.63 0.77
53/4 0.73 0.17 0.76 0.77
5/8
23/4
1.0
0.67 0.19
1.0
0.79 0.77
41/8 0.57 0.16 0.69 0.77
53/4 0.59 0.19 0.73 0.77
3/4
23/4
1.0
0.67 0.19
1.0
0.80 0.77
45/8 0.48 0.14 0.70 0.77
53/4 0.58 0.13 0.72 0.77For SI: 1 inch = 25.4 mm.
1The load reduction factors in this table are applicable only to the allowable loads shown in Tables 3 and 4.2Reduction factors are cumulative. Multiple reduction factors for more than one spacing or edge distance are calculated separately and multiplied.3Load reduction factors for anchors loaded in tension or shear with spacing between critical and minimum are obtained by linear interpolation.4Load reduction factors for anchors loaded in tension or shear with edge distances between critical and minimum are obtained by linearinterpolation.
Page 5 of 11 ESR-1056
TABLE 3—ALLOWABLE TENSION LOADS FOR TITEN HD SCREW ANCHORSINSTALLED IN NORMAL-WEIGHT CONCRETE1,2,3,4 (pounds)
ANCHORDIAMETER
(inch)
DRILL BITDIAMETER5
(inches)
MINIMUMEMBEDMENT
DEPTH(inches)
CRITICALEDGE
DISTANCE(inches)
CRITICALSPACING(inches)
INSTALLED WITH SPECIALINSPECTION6
INSTALLED WITHOUT SPECIALINSPECTION7
Concrete Strength, fNc (psi) Concrete Strength, fNc (psi)
2,000 3,000 4,000 2,000 3,000 4,000
3/83/8
23/4 3 61,075 1,315 1,550 540 660 775
33/4 1,770 2,115 2,455 885 1,060 1,230
1/21/2
23/4
4 8
1,155 1,400 1,645 580 700 825
35/8 1,855 2,270 2,685 930 1,135 1,345
53/4 2,570 3,240 3,910 1,285 1,620 1,955
5/85/8
23/4
5 10
1,155 1,400 1,645 580 700 825
41/8 2,185 2,630 3,070 1,095 1,315 1,535
53/4 3,240 3,955 4,670 1,620 1,980 2,335
3/43/4
23/4
6 12
1,170 1,410 1,645 585 705 825
45/8 2,585 3,470 4,355 1,295 1,735 2,180
53/4 3,440 4,055 4,670 1,720 2,030 2,335For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kPa.
1Allowable loads are permitted to be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section1605.3.2 of the IBC or Section 1612.3.2 of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section1605.3.2 may be multiplied by a factor of 0.75.2Minimum concrete thickness is 1.5 times the anchor embedment.3Minimum edge distance and spacing shall comply with Table 1.4The tabulated loads are for anchors installed in normal-weight concrete having a minimum compressive strength as shown in the table at thetime of anchor installation.5Anchor installation shall comply with Section 4.0 of this report.6These tension loads are applicable only when the anchors are installed with special inspection as set forth in Section 4.2 of this report.7These tension loads are applicable when the anchors are installed without special inspection.
TABLE 4—ALLOWABLE SHEAR LOADS FOR TITEN HD SCREW ANCHORSINSTALLED IN NORMAL-WEIGHT CONCRETE1,2,3,4 (pounds)
ANCHORDIAMETER
(inch)
DRILL BITDIAMETER5
(inch)
MINIMUMEMBEDMENT
DEPTH(inches)
CRITICALEDGE
DISTANCE(inches)
CRITICALSPACING(inches)
ALLOWABLE SHEAR LOAD6 (lbs)
Concrete Strength, fNc (psi)
2,000 3,000 4,000
3/83/8
23/4 41/2 61,585 1,665 1,740
33/4 1,595 1,670 1,740
1/21/2
23/4
6 8
1,605 2,050 2,495
35/8 2,330 2,795 3,255
53/4 2,830 3,045 3,255
5/85/8
23/4
71/2 10
1,940 2,220 2,495
41/8 2,175 3,415 4,650
53/4 3,125 3,890 4,650
3/83/4
23/4
9 12
1,960 2,415 2,865
45/8 2,805 4,490 6,170
53/4 4,950 5,560 6,170For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kPa.
1Allowable loads are permitted to be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section1605.3.2 of the IBC or Section 1612.3.2 of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section1605.3.2 may be multiplied by a factor of 0.75.2Minimum concrete thickness is 1.5 times the anchor embedment.3Minimum edge distance and spacing shall comply with Table 1.4The tabulated loads are for anchors installed in normal-weight concrete having a minimum compressive strength as shown in the table at thetime of anchor installation.5Anchor installation shall comply with Section 4.0 of this report.6Allowable shear loads are for installations with or without special inspection.
Page 6 of 11 ESR-1056
TABLE 5—ALLOWABLE SHEAR LOADS (PARALLEL TO THE CONCRETE EDGE) FOR TITEN HD SCREW ANCHORSINSTALLED IN fNc = 2,500 psi NORMAL-WEIGHT CONCRETE1,2,3,4 (pounds)
ANCHORDIAMETER
(inch)
DRILL BITDIAMETER5
(inch)
MINIMUMEMBEDMENT
DEPTH(inches)
MINIMUM EDGEDISTANCE
(inches)
MINIMUM ENDDISTANCE
(inches)
CRITICALSPACING(inches)
ALLOWABLESHEAR LOADPARALLEL TO
THE CONCRETEEDGE6
(pounds)
1/21/2
23/4
13/4 8 8
1,165
31/2 1,710
41/2 1,9505/8
5/8 23/4 13/4 10 10 1,205
31/2 1,765For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kPa.
1Allowable loads are permitted to be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section1605.3.2 of the IBC or Section 1612.3.2 of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section1605.3.2 may be multiplied by a factor of 0.75.2Minimum concrete thickness is 1.5 times the anchor embedment.3Minimum screw anchor edge and end distances, and critical spacing limitations, are applicable to the tabulated loads.4The tabulated loads are for anchors installed in normal-weight concrete having a minimum 2,500 psi compressive strength, fNc, at the time ofanchor installation.5The drill bit diameter shall be equal to the nominal diameter of the anchor. Anchor installation shall comply with Section 4.0 of this report.6 Allowable shear loads are for installations with or without special inspection.
TABLE 6—ALLOWABLE TENSION LOADS FOR TITEN HD SCREW ANCHORSINSTALLED IN THE TOP SURFACE OF NORMAL-WEIGHT CONCRETE FOUNDATION STEM WALLS1,2,3,4,5 (pounds)
ANCHORDIAMETER
(inch)
DRILL BITDIAMETER
(inch)
MINIMUMANCHOR
EMBEDMENTDEPTH,
hv
(inches)
MINIMUMCONCRETE
FOUNDATIONSTEM WALLTHICKNESS
(inches)
ANCHOR LOCATION6
(inches)ALLOWABLE TENSION LOADS (pounds)
CriticalEdge
Distance
CriticalEnd
Distance
Concrete Compressive Strength, fNc
fNc = 2,500 psi fNc = 4,500 psi
Installedwith
SpecialInspection7
InstalledwithoutSpecial
Inspection8
Installedwith SpecialInspection7
InstalledwithoutSpecial
Inspection8
1/21/2 10 6 13/4 8 3,855 1,930 5,075 2,540
1/21/2 10 6 13/4 43/8 3,570 1,785 4,760 2,380
For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kPa.
1Allowable loads may be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section 1605.3.2 of theIBC or Section 1612.3.2 of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section 1605.3.2 maybe multiplied by a factor of 0.75.2Minimum concrete thickness is 12 inches.3Minimum screw anchor spacing is 15 inches.4The tabulated loads are for anchors installed in normal-weight concrete having a minimum compressive strength as shown in the table at thetime of anchor installation.5Anchor installation shall comply with Section 4.0 of this report.6Critical screw anchor edge and end distances are applicable to the tabulated loads.7These tension loads are applicable only when the anchors are installed with special inspection as set forth in Section 4.2 of this report.8These tension loads are applicable when the anchors are installed without special inspection.
Page 7 of 11 ESR-1056
TABLE 7—ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORSINSTALLED ON TOP OR BOTTOM OF STRUCTURAL SAND-LIGHTWEIGHT CONCRETE (f ′c = 3,000 psi)
AND METAL-DECK ASSEMBLIES1,2
ANCHORDIAMETER
(inch)
DRILL BITDIAMETER
(inch)
MINIMUMEMBEDMENT
DEPTH(inches)
ANCHOR LOCATION6 (inches) ALLOWABLE LOADS4 (lbs)
Edge Distance CriticalSpacing
Tension Shear7
Minimum Critical Installedwith
SpecialInspection5
InstalledwithoutSpecial
Inspection6
ANCHORS INSTALLED IN THE TOP OF STRUCTURAL SAND-LIGHTWEIGHT CONCRETE AND METAL-DECK ASSEMBLIES3/8
3/8 23/4 6 6 6 640 320 1,0601/2
1/2 23/4 8 8 8 760 380 1,5955/8
5/8 23/4 10 10 10 775 390 1,595
ANCHORS INSTALLED IN BOTTOM FLUTES OF STRUCTURAL SAND-LIGHTWEIGHT CONCRETE AND METAL-DECK ASSEMBLIES8
3/83/8 3 11/2
(9) N/A 6 1,355 675 1,0251/2
1/2 4 11/2 (9) N/A 8 1,755 875 1,710
5/85/8 5 11/2
(9) N/A 10 2,235 1,115 2,675For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kPa.
1The assembly shall consist of a metal deck and structural sand-lightweight concrete fill:• The deck shall be steel conforming to ASTM A 653/A 653M, with a minimum yield strength of 38,000 psi and minimum tensile strength of
45,000 psi, and shall have a minimum thickness of No. 20 gage [0.035 inch base-metal thickness (0.89 mm)]. Figure 2 illustrates requiredmetal-deck bottom-flute dimensions: a minimum of 41/2 inches (114 mm) wide, a maximum of 3 inches (76 mm) deep, and a minimumspacing of 12 inches (305 mm). Metal decks having greater bottom flute widths and relative spacings shall be permitted.
• The structural sand-lightweight concrete shall have a minimum concrete compressive strength, fNc, at the time of anchor installation of 3,000psi, and shall have a minimum thickness of 31/4 inches measured from the top flute. Refer to Figure 2.
2Anchor installation shall comply with Section 4.0 of this report.3Anchor edge distance and spacing shall comply with tabulated loads. N/A = Not applicable.4Use of anchors installed in the top or bottom of structural sand-lightweight concrete and metal-deck assemblies shall be permitted to resist windor earthquake tension and shear loads. Refer to Section 3.2.3 for design requirements for anchors installed in the top of the assembly, and foranchors installed in the bottom of the assembly.5These tension loads are applicable only when the anchors are installed with special inspection as set forth in Section 4.2 of this report.6These reduced tension loads are applicable for anchors installed without special inspection.7Allowable shear loads are for installations with or without special inspection.8Allowable tension and shear loads are for anchors installed in the bottom flute of the steel deck, at a minimum edge distance of 11/2 inches fromthe inclined edge of the bottom flute. Allowable shear loads act parallel or perpendicular to the deck flutes.9Minimum distance from an anchor to the end of a flute for bottom of deck installations shall comply with the following:
• 6 inches for 3/8-inch-diameter anchor.• 8 inches for 1/2-inch-diameter anchor.• 10 inches for 5/8-inch-diameter anchor.
FIGURE 2—TITEN HD SCREW ANCHOR INSTALLED IN THE TOP AND BOTTOM OF ASTRUCTURAL SAND-LIGHTWEIGHT CONCRETE AND METAL-DECK ASSEMBLY
Page 8 of 11 ESR-1056
TABLE 8A—IBC AND IRC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORS INSTALLED IN THEFACE OF FULLY GROUTED CMU MASONRY WALL CONSTRUCTION1
ANCHORDIA.2
(in.)
DRILL BITDIA.(in.)
MIN.EMBED.3
(in.)
ANCHOR LOCATION4 (inches) ANCHORS INSTALLED ATDISTANCES $ CRITICAL EDGEDISTANCE, ccrit, AND SPACING,
scrit5,6,7
(lbf)
Edge Distance Spacing Tension Shear
Critical, ccrit Minimum, cmin Critical, scrit Minimum, smin3/8
3/8 23/4 12 4 6 3 480 8701/2
1/2 31/2 12 4 8 4 690 1,3855/8
5/8 41/2 12 4 10 5 1,060 2,0853/4
3/4 51/2 12 4 12 6 1,600 3,000For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.48 N
1Anchors shall be installed a minimum of 11/4 inches from vertical head joints and T-joints. Refer to Figure 3 for permitted and prohibited anchorinstallation locations.2The drill bit diameter shall be equal to the nominal diameter of the anchor. Anchor installation shall comply with Section 4.0 of this report.3Embedment depth is measured from the outside face of the masonry.4Critical and minimum edge distances, ccr and cmin, respectively, shall comply with this table. Refer to Figure 3. Critical and minimum spacing, scrit
and smin, respectively, shall comply with this table. Critical and minimum edge and spacing distances are valid for anchors resisting tension or shearloads. Refer to Table 9 for allowable tension and shear load reduction factors for anchors installed between critical and minimum edge distances,and to Table 10 for anchors installed between critical and minimum spacing.5Tabulated loads are for anchors installed in fully grouted masonry wall construction, consisting of Grade N, Type II, lightweight, medium-weight,or normal-weight, closed-end, concrete masonry units (CMUs) conforming to ASTM C 90. Masonry shall be fully grouted with coarse grout havinga minimum compressive strength of 2,000 psi, and complying with IBC Section 2103.10 or IRC Section R609.1.1 as applicable. Mortar shallcomply with IBC Section 2103.7 or IRC Section R607, as applicable, and shall have a minimum specified compressive strength of 1,500 psi. Thespecified compressive strength of masonry, fNm, at 28 days shall be a minimum of 1,500 psi.6Tabulated allowable loads are based on a safety factor of 5.0 and are based on special inspection being provided during anchor installation.Special inspection requirements shall comply with Section 4.2 of this report.7Allowable loads may be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section 1605.3.2 of theIBC for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section 1605.3.2 may be multiplied by a factor of 0.75.
FIGURE 3—TITEN HD SCREW ANCHOR INSTALLED IN THE FACE OF GROUT-FILLED CMU(CONCRETE MASONRY UNIT) WALL CONSTRUCTION (Refer to Tables 8, 9, and 10)
Page 9 of 11 ESR-1056
TABLE 8B—ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORS INSTALLED IN THEFACE OF FULLY GROUTED CMU MASONRY WALL CONSTRUCTION1
ANCHORDIA.2
(in.)
DRILLBIT DIA.
(in.)
MIN.EMBED.3
(in.)
ANCHOR LOCATION4 (inches) ALLOWABLE LOADS BASED ONANCHORS INSTALLED AT DISTANCES> CRITICAL EDGE DISTANCE, ccrit, AND
SPACING, scrit5,6,7
(lbf)
Edge Distance Spacing Tension Shear9
Critical, ccrit Minimum, cmin Critical, scrit Minimum, smin Installed withSpecial
Inspection7
InstalledwithoutSpecial
Inspection8
3/83/8 23/4 12 4 6 3 600 300 1,085
1/21/2 31/2 12 4 8 4 860 430 1,730
5/85/8 41/2 12 4 10 5 1,325 665 2,605
3/43/4 51/2 12 4 12 6 2,000 1,000 3,750
For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.48 N.
1Anchors shall be installed a minimum of 11/4 inches from vertical head joints and T-joints. Refer to Figure 3 for permitted and prohibited anchorinstallation locations.2The drill bit diameter shall be equal to the nominal diameter of the anchor. Anchor installation shall comply with Section 4.0 of this report.3Embedment depth is measured from the outside face of the masonry.4Critical and minimum edge distances, ccr and cmin, respectively, shall comply with this table. Refer to Figure 3. Critical and minimum spacing, scrit
and smin, respectively, shall comply with this table. Critical and minimum edge and spacing distances are valid for anchors resisting tension or shearloads. Refer to Table 9 for allowable tension and shear load reduction factors for anchors installed between critical and minimum edge distances,and to Table 10 for anchors installed between critical and minimum spacing.5Tabulated loads are for anchors installed in fully grouted masonry wall construction, consisting of Grade N, Type II, lightweight, medium-weight,or normal-weight, closed-end, concrete masonry units (CMUs) conforming to UBC Standard 21-4. Masonry shall be fully grouted with coarse grouthaving a minimum compressive strength of 2,000 psi, and complying with UBC Section 2103.4. Mortar shall comply with UBC Section 2103.3and UBC Standard 21-15, and shall have a minimum specified compressive strength of 1,500 psi. The specified compressive strength of masonry,fNm, at 28 days shall be a minimum of 1,500 psi.6Allowable loads may be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section 1612.3.2 of theUBC for wind or earthquake loading conditions.7These allowable tension loads are based on a factor of safety of 4.0 and special inspection being provided during anchor installation. Specialinspection requirements shall comply with Section 4.2 of this report.8These reduced allowable tension loads are applicable for anchors installed without special inspection and are based on a factor of safety of 8.0.9These allowable shear loads are based on a factor of safety of 4.0 and anchor installation with or without special inspection.
Page 10 of 11 ESR-1056
TABLE 9—LOAD REDUCTION FACTORS FOR TITEN HD SCREW ANCHORS INSTALLED BETWEEN CRITICALAND MINIMUM EDGE DISTANCES (Anchors Installed in the Face of Grout-filled CMU Masonry Walls)1,2,3
ANCHORDIAMETER
(inch)
MINIMUMEMBEDMENT
DEPTH, hv
(inches)
LOAD REDUCTION FACTORS FOR ANCHORS INSTALLED AT:
Critical EdgeDistance, Ccrit
Minimum Edge Distance, Cmin
Tension or ShearLoad
Tension Load Shear Load Acting:
Towardsan Edge
Away froman Edge
Parallel toan Edge
3/8 23/4 1.0 1.0 0.58 0.89 0.771/2 31/2 1.0 1.0 0.38 0.79 0.485/8 41/2 1.0 0.83 0.30 0.58 0.463/4 51/2 1.0 0.66 0.21 0.38 0.44
For SI: 1 inch = 25.4 mm.
1The load reduction factors in this table are applicable to the allowable loads shown in Tables 8A and 8B.2Reduction factors are cumulative. Multiple reduction factors for more than one spacing or edge distance are calculated separately and multiplied.3Load reduction factors for anchors loaded in tension or shear with edge distances between critical and minimum are obtained by linearinterpolation.
TABLE 10—LOAD REDUCTION FACTORS FOR TITEN HD SCREW ANCHORS INSTALLED BETWEEN CRITICAL AND MINIMUMSPACING
(Anchors Installed in the Face of Grout-filled CMU Masonry Walls)1,2,3
ANCHORDIAMETER
(inch)
MINIMUMEMBEDMENT
DEPTH, hv
(inches)
LOAD REDUCTION FACTORS FOR ANCHORS INSTALLED AT:
Critical Spacing, Scrit Minimum Spacing, Smin
Tension or Shear Load Tension Load Shear Load3/8 23/4 1.0 0.87 0.621/2 31/2 1.0 0.69 0.625/8 41/2 1.0 0.59 0.623/4 51/2 1.0 0.50 0.62
For SI: 1 inch = 25.4 mm.
1The load reduction factors in this table are applicable to the allowable loads shown in Tables 8A and 8B.2Reduction factors are cumulative. Multiple reduction factors for more than one spacing or edge distance are calculated separately and multiplied.3Load reduction factors for anchors loaded in tension or shear with spacing between critical and minimum are obtained by linear interpolation.
TABLE 11A—IBC AND IRC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORSINSTALLED IN TOP OF GROUT-FILLED CMU MASONRY WALLS1
ANCHORDIA.
(inch)
DRILLBITDIA.
(inch)
MIN.EMBED.(inches)
ANCHOR LOCATION2 (inches) IBC AND IRC ALLOWABLE LOADS3,4,5 (pounds)
MinimumEdge
Distance
MinimumEnd
Distance
MinimumSpacing
Tension Shear
Parallelto Edge of
Masonry Wall
Perpendicularto Edge of
Masonry Wall1/2
1/2 41/2 13/4 8 8 570 585 1605/8
5/8 41/2 13/4 10 10 570 675 160For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N, 1 psi = 6.89 kPa.
1The allowable tension and shear loads in Table 11A are applicable when anchors are installed in structures regulated by the IRC or IBC.2Minimum edge and end distances are measured from the anchor centerline to the edge and end of the CMU masonry wall, respectively. Referto Figure 4. Minimum spacing is measured from center-to-center of two anchors. Anchors installed in the mortared head joint are outside the scopeof this report.3The allowable loads in Table 11A are for anchors resisting dead, live, wind, and earthquake load applications. For short-term loading due to windand earthquake forces, the allowable loads may be increased as indicated in Section 3.2.4 of this report.4Loads for Grade N, Type II, lightweight, medium-weight, or normal-weight concrete masonry units (CMUs) conforming to ASTM C 90. Allowableminimum nominal dimensions of the CMU shall be 8 inches wide by 8 inches high by 16 inches long (8"×8"×16"). Masonry wall construction shallbe fully grouted with coarse grout having a minimum compressive strength of 2,000 psi, and complying with IBC Section 2103.10 or IRC SectionR609.1.1, as applicable. Mortar shall comply with IBC Section 2103.7 or IRC Section R607.1, as applicable, and have a minimum compressivestrength of 1,500 psi. The specified compressive strength of masonry, fNm, at 28 days shall be a minimum of 1,500 psi.5Allowable tension and shear loads are based on a safety factor of 5.0, and are based on anchor installations with special inspection. Specialinspection shall be provided during anchor installation in accordance with Section 2107.2.1 of the IBC or Section R104.4 of the IRC, as applicable.Refer to Section 4.2 of this report for special inspection requirements.
Page 11 of 11 ESR-1056
TABLE 11B—UBC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORSINSTALLED IN TOP OF GROUT-FILLED CMU MASONRY WALLS1
ANCHORDIA.
(inch)
DRILLBITDIA.
(inch)
MIN.EMBED.(inches)
ANCHOR LOCATION2 (inches) UBC ALLOWABLE LOADS3,4 (pounds)
MinimumEdge
Distance
MinimumEnd
Distance
MinimumSpacing
Tension Shear5
Installedwith
SpecialInspection6
InstalledwithoutSpecial
Inspection7
Parallelto Edge ofMasonry
Perpendicularto Edge ofMasonry
1/21/2 41/2 13/4 8 8 715 355 730 200
5/85/8 41/2 13/4 10 10 715 355 845 200
For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N, 1 psi = 6.89 kPa.
1The allowable tension and shear loads in Table 11B are applicable for anchors installed in structures regulated by the UBC.2Minimum edge and end distances are measured from the anchor centerline to the edge and end of the CMU masonry wall, respectively. Referto Figure 4. Minimum spacing is measured from center-to-center of two anchors. Anchors installed in the mortared head joint are outside the scopeof this report.3The allowable loads in Table 11B are for anchors resisting dead, live, wind, and earthquake load applications. For short-term loading due to windand earthquake forces, the allowable loads may be increased as indicated in Section 3.2.4 of this report.4Loads for Grade N, Type II, lightweight, medium-weight, or normal-weight concrete masonry units (CMUs) conforming to UBC Standard 21-4.Allowable minimum nominal dimensions of the CMU shall be 8 inches wide by 8 inches high by 16 inches long (8"×8"×16"). Masonry wallconstruction shall be fully grouted with coarse grout having a minimum compressive strength of 2,000 psi, and complying with UBC Section 2103.4.Mortar shall comply with UBC Section 2103.3 and UBC Standard 21-15, and have a minimum compressive strength of 1,500 psi. The specifiedcompressive strength of masonry, fNm, at 28 days shall be a minimum of 1,500 psi.5Allowable shear loads are based on a safety factor of 4.0. Special inspection for anchor installation is not required.6Allowable tension loads in the column entitled “Installed with Special Inspection” are based on a safety factor of 4.0. Special inspection shall beprovided during anchor installation, and shall comply with the requirements described in Section 4.2 of this report.7Allowable tension loads in the column entitled “Installed without Special Inspection” are based on a safety factor of 8.0. Special inspection foranchor installation is not required for anchors assigned these reduced allowable tension loads.
FIGURE 4—EDGE AND END DISTANCES FOR THE TITEN HD ANCHORINSTALLED IN THE TOP OF CMU MASONRY WALL CONSTRUCTION